Product Specification 03248E
MFR 2 Multi Function Relay
Mains & Generator Protection & Control
· Generator and mains protection
· Synchronization for two breakers
· Frequency and voltage matching
· Real power control
· Power factor control
· Load/var sharing
· Counters for kWh, operating hours, maintenance call
· Programmable relay outputs
· PC and front panel configurable
· CAN bus based communication
· Microprocessor technology for flexible and reliable operation
· CE marked
· UL/cUL Listed
APPLICATIONS
Based on micro-controller technology, Woodward's MFR 2 Multi Function Relay incorporates functions and features for multiple applications (e.g. gensets, hydropower, etc.) in isolated or parallel utility operation. The MFR 2 is designed for generators and switchgear equipment that require independent protection. The ability for the MFR 2 to quickly decouple from the mains when working in parallel with the mains gives complete generator protection for frequency, voltage, and real and re-active power control allowing load/var sharing between as many as eight units.
DESCRIPTION
The Series of MFR 2 Multi Function Relays consists of the model MFR 2S/PSVA.
Features · Battery voltage monitoring · kWh/oper.hours/start/maintenance
counter · 4 configurable discrete alarm inputs · 4 configurable relays · Two-line LC display · Synchroscope · Multi level password protection · Configuration directly or via PC · CAN bus communication
DESCRIPTION (continued)
Protection ANSI # Mains · Over-/undervoltage (59/27) · Over-/underfrequency (81O/U) · Voltage asymmetry (47) · Phase/vector shift (MFR 2S only) (78) Generator · Over-/undervoltage (59/27) · Over-/underfrequency (81O/U) · Overload (32) · Reverse/reduced power (32R/F) · Unbalanced load (46) · Re-active power monitoring · Loss of excitation (40Q) · Time-overcurrent (50)
Controller · Synchronizer for 2 CB · Discrete raise/lower for n/f/V/P/Q · Speed/frequency/real power · Voltage/power factor · Isolated operation · Mains parallel operation · Load/var sharing (up to 8 units) (MFR 2S only) · Dead bus operation
MFR 2S/PSVA The PSVA package additionally includes: · df/dt (ROCOF) (81RL) · 2 conf. analog outputs (20 mA) · 2 conf. pulse outp. for kWh/kvarh · Real power set-point input (20 mA)
SPECIFICATIONS
Accuracy .......................................................................................... Class 1 Power supply ..................................................................... 24 Vdc (+/-30 %) Intrinsic consumption .................................................................. max. 15 W Ambient temperature ................................................................ -20 to 70 °C Ambient humidity ...................................................... 95 %, non-condensing Voltage ........... Rated value /D: [1] 66/115 Vac or [4] 230/400 Vac Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV Measuring frequency ................................................ 50/60 Hz (40 to 70 Hz) Linear measuring range up to ....................................................... 1.3×Vrated Input resistance ..................................................... [1] 0.21 MW, [4] 0.7 MW Max. power consumption per path ................................................... 0.15 W Current (Irated) .............................................................. [1] ../1 A or [5] ../5 A Linear measuring range up to ............................................... Igen = 3.0×Irated Imains = 1.5×Irated Load ............................................................................................. < 0.15 VA Rated short-time current (1 s) ................................. [1] 50×Irated, [5] 10×Irated Discrete inputs .............................................................................. isolated Input range .................................................................... 18 to 250 Vac or dc Input resistance ..................................................................... approx. 68 kW
Pulse outputs ................................................................... transistor output Rated gate voltage ............................................................................ 24 Vdc Maximum gate voltage ...................................................................... 32 Vdc Minimum gate current .................................................................... 10 mAdc Maximum gate current ................................................... 30 mAdc (0.5 Vdc) Relay outputs ................................................................................ isolated Contact material ............................................................................... AgCdO Load (GP) ................................................. 24 Vdc@2 Adc, 250 Vac@2 Aac Pilot duty (PD) ...................................................................... 24 Vdc@1 Adc Analog output ................................................................................ isolated Type ............................................................. 0/4 to 20 mA, freely scaleable Resolution .................................................... 8/12 Bit (depending on model) Max. load 0/4 to 20 mA ..................................................................... 500 W Insulating voltage ......................................................................... 3,000 Vdc Housing ...................................................... Type APRANORM DIN 43 700 Dimensions ....................................................................... 144×72×122 mm Front cutout ............................................................................... 138×67 mm Connection ................................................ screw/plug terminals depending on connector 1.5 mm² or 2.5 mm² Front ................................................................................. insulating surface Protection system ................................................................................ IP 21 Weight ............................................ depending on version, approx. 1,000 g Disturbance test (CE) .................................................. tested according to applicable EN guidelines Listings ............................................... UL/cUL listed for ordinary locations
DIMENSIONS
Bottom view
72
DIN rail mountoption (please order
brackets P/N 8923-1023)
8
116 50
139
179
65
2735
Back view withconnecting terminals
Front view
X1 X5
6570 6075 5450
0 24
48 25
2004-11-11 | MFR 2 Dimensions r2ww-4604-ab.skf
144
80 87
Configuration portConfiguration port
WIRING DIAGRAM (MFR 2S/PSVA; refer to manual for other units)
Drive raise
lower109
80 V
I A
Analog output0/4 to 20 mA
7071
72
Subject to technical modifications.
G
s2 (l)25
s1 (k)
s2 (l)
s1 (k)2629
3020
s1 (k)
s2 (l)3132
2122
Alarm input 2 62
N
0 Vdc
24 Vdc
Switching set point 1 <---> 2
Enable GCB
0
2005-09-13 | MFR 2 Wiring Diagram r2ww-0537-ap.skf
21
35
Isolated operation ON
Common
Common (terminal 3/4/5/6/53/54)
Release monitoring
Not used
External acknowledgment352
336
734
Alarm input 1
Blocking of mains protection 4
3 3660
61
Relay 3
Ready for operation
Relay 4
Common
Alarm input 4
Alarm input 3
1863
6465
1937
3843
Relay 1
Relay 2
4644
4547
48
8081
8283 0 V
I A
Analog output0/4 to 20 mA
8485 Impulse output kvarh
Open Collector
8687 Impulse output kWh
Open Collector
1
Analog input0/4 to 20 mA- Setpoint value: Real power kW
X1X2
X3X4
X5
InterfaceCAN bus
PSVA
Generator current L1
Generator current L2
Generator current L3
SPEED / POWERThree-position controller
PSVA
Battery#2
#2Battery
#1NO/NC
#1NO/NC
#2Battery
#1NO/NC
#1NO/NC
#1NO/NC
#1NO/NC
#1NO/NC
conf
igura
ble d
uring
setu
p (N
O/NC
)#1
Batte
ry o
r ano
ther
pow
er su
pply;
term
inal 7
/33/
65 is
pos
. or n
eg. s
ignal
#2
The
sock
et fo
r the
PC
conf
igura
tion
is sit
uate
d on
the
side
of th
e un
it. Th
is is
wher
e th
e DP
C ha
s to
be p
lugge
d in.
up to
7 a
dditio
nal g
ener
ator
s(e
ach
via o
ne M
FR2)
GATE
WAY
GW 4
Cont
rol r
oom
SPS
PC
GND
CAN-H
CAN-L
Termination
5
6
7
8
MFR
2S/P
SVA
(Mult
i Fun
ction
Rela
y)
41
MCB
33
5052
51
s2 (l)
s1 (k)
2728
Mains voltage L1
Mains voltage L2
Mains voltage L3
5339
1640
1754
Enable MCB
Command: open MCB
Command: close MCB
Busbar voltage
Reply: MCB is open
GCB
3
4214
154 Reply: GCB is open
Command: close GCB
Command: open GCB
raise
lower
1112
13
Generator voltage L1
Generator voltage L2
Generator voltage L3
Mains current L1
VOLTAGE / POW.FACTThree-position controller
2324 L2
L1
International Woodward PO Box 1519 Fort Collins CO, USA 80522-1519 1000 East Drake Road Fort Collins CO 80525 Ph: +1 (970) 498-3634 Fax: +1 (970) 498-3058 email: [email protected] Europe Woodward GmbH Handwerkstrasse 29 70565 Stuttgart, Germany Ph: +49 (0) 711 789 54-510 Fax: +49 (0) 711 789 54-101 email: [email protected] Distributors & Service Woodward has an international network of distributors and service facilities. For your nearest representative, call the Fort Collins plant or see the Worldwide Directory on our website. Corporate Headquarters Rockford IL, USA Ph: +1 (815) 877-7441 www.woodward.com Subject to technical modifications. This document is distributed for informational purposes only. It is not to be construed as creating or becoming part of any Woodward Governor Company contractual or warranty obligation unless expressly stated in a written sales contract. We appreciate your comments about the content of our publications. Please send comments including the document number below to [email protected] © Woodward Governor
Company All Rights Reserved
03248E - 12/6/S
TYPICAL APPLICATIONS
52
52
MFR 2
CAN
RS232
0/4..20mA
I / O
G
81RL
78
90
79
47
81U
81O
59
27
25
25
27
59
81O50
79
32 81U
32R
32F
40Q
4639
38
12
49 55
90
74
MFR 2S
ANSI
PSVA
Control Breaker 2 Synchronization 25 ü Isolated single-unit operation ü Mains parallel operation ü Accessories kWh counter ü kvarh counter ü Operat. hours/start/mainten. counter ü Configuration via PC #1 ü Protection Gen.: Over-/undervoltage 59/27 ü Mains: over-/undervoltage 59/27 ü Gen.: Over-/underfrequency 81O/U ü Mains: over-/underfrequency 81O/U ü Mains: Voltage asymmetry 47 ü Mains: phase/vector shift 78 ü Mains: df/dt (ROCOF) 81RL ü Gen.: Overload 32 ü Gen.: Reverse power 32R ü Gen.: Reduced power 32F/37 ü Gen.: Unbalanced load 46 ü Gen.: Re-active power ü Gen.: Loss of excitation 40Q ü Gen.: Time-overcurrent 50/51* ü Controller Discrete raise/lower: n/f & P ü Discrete raise/lower: V & Q ü Active power setp.: 0/4 to 20 mA ü Load/var sharing ü I/O's Discrete alarm inputs (config.) 4 Relay outputs (config.) 74 4 Analog inputs 0/4 to 20 mA (conf.) 2 Analog outp. 0/4 to 20 mA (conf.) 2 Impulse output for kWh/kvarh ü CAN bus communication #2 ü Listings/Approvals UL/cUL listed ü Product Number P/N Language
Measuring inputs 100 Vac, ../5 A English 8440-1287 German 8440-1733
Measuring inputs 400 Vac, ../5 A English 8440-1735 German 8440-1323
* not according to ANSI guidelines (two-step protection instead of inverse time characteristic) #1 Cable incl. software necessary (DPC, Product Number P/N 5417-557) #2 Remote monitoring, control, configuration (GW 4 could be used for several interfaces)