Mr. Slim Air Conditioner Error Codes
Transcript of Mr. Slim Air Conditioner Error Codes
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
1/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
AC Error CodeError Codes of All Air Conditioning Brands.
MR. SLIM AIR CONDITIONER ERROR CODES
December 10, 2014 Mitsubishi, Mitsubishi Electric, Mr. Slim
After
completing
installation and
the wiring and
piping of the indoor and outdoor units, check for
refrigerant leakage, looseness in the power supply or
control wiring, wrong polarity, and no disconnection
of one phase in the supply.
P1 Intake sensor error
P2 P9 Pipe (Liquid or 2-phase pipe) sensor error
E6 E7 Indoor/outdoor unit communication error
P4 Drain sensor error
P5 Drain pump error
PA Forced compressor error
P6 Freezing/Overheating safeguard operation
EE Communication error between indoor and outdoor units
P8 Pipe temperature error
E4 Remote controller signal receiving error
Fb Indoor unit control system error (memory error, etc.)
E0 E3 Remote controller transmission error
E1 E2 Remote controller control board error
For details, check the LED display of the outdoor controller board.
E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
UP Compressor overcurrent interruption
U3, U4 Open/short of outdoor unit thermistors
UF Compressor overcurrent interruption (When compressor locked)
U2 Abnormal high discharging temperature/49C worked/insufficient refrigerant
U1 Ud Abnormal high pressure (63H worked)/Overheating safeguard operation
U5 Abnormal temperature of heat sink
HOME CONTACT
Search
http://acerrorcode.com/http://acerrorcode.com/brands/mitsubishihttp://acerrorcode.com/brands/mitsubishi-electrichttp://acerrorcode.com/brands/mitsubishi-electrichttp://acerrorcode.com/brands/mr-slimhttp://acerrorcode.com/http://acerrorcode.com/contacthttp://acerrorcode.com/contacthttp://acerrorcode.com/http://acerrorcode.com/brands/mr-slimhttp://acerrorcode.com/brands/mitsubishi-electrichttp://acerrorcode.com/brands/mitsubishihttp://acerrorcode.com/mailto:[email protected]://plus.google.com/
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
2/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
U8 Outdoor unit fan safeguard stop
U6 Compressor overcurrent interruption/Abnormal of power module
U7 Abnormality of super heat due to low discharge temperature
U9 UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/
Current sensor error.
Others Other errors (Refer to the technical manual for the outdoor unit.)
List of error codes and stop codes (for all models)
Pdf -1
Pdf -2
Pdf -3
Mr.Slim A-control error code list
Display of remote controller
Code EA
Error detail Mis-wiring of indoor/outdoor unit. exceed the number of indoor unit connection.
Inspected unit Outdoor.
Code Eb
Error detail Mis-wiring of indoor/outdoor unit. (mis-wiring disconnection) Inspected unit Outdoor.
Code EC
Error detail Start-up time over
Inspected unit Outdoor.
Code E6
Error detail Indoor/outdoor unit transmission error (signal receiving error). Inspected unit Indoor.
Code E7
Error detail Indoor/outdoor unit transmission error (transmitting error).
Inspected unit Indoor.
Code E8
Error detail Indoor/outdoor unit transmission error (signal receiving error).
Inspected unit Outdoor.
Code E9
Error detail Indoor/outdoor unit transmission error (transmitting error).
Inspected unit Outdoor.
https://docs.google.com/file/d/0BwpXRGTFIK57anNjd0E2SzJvTUEhttps://docs.google.com/file/d/0BwpXRGTFIK57OEdaSGgxMWlsZzghttps://drive.google.com/file/d/0BwpXRGTFIK57RVkwbTNqX2RDc0Ehttps://drive.google.com/file/d/0BwpXRGTFIK57RVkwbTNqX2RDc0Ehttps://docs.google.com/file/d/0BwpXRGTFIK57OEdaSGgxMWlsZzghttps://docs.google.com/file/d/0BwpXRGTFIK57anNjd0E2SzJvTUE
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
3/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Code E0 Error detail Remote control transmission error (signal receiving error)
Inspected unit Remote control
Code E3
Error detail Remote control transmission error (transmitting error)
Inspected unit Remote control.
Code E4
Error detail Remote control transmission error (signal receiving error)
Inspected unit Indoor.
Code E5
Error detail Remote control transmission error (transmitting error)
Inspected unit Indoor.
Code EF Error detail M-NET transmission error
Inspected unit Indoor and outdoor.
Code Ed
Error detail Serial transmission error
Inspected unit Outdoor.
Code P1
Error detail Abnolmality of room temperature thermistor (TH1). Inspected unit Indoor.
Code P2
Error detail Abnormality of pipe temperature themistor/liquid (TH2).
Inspected unit Indoor.
Code P4
Error detail Abnomarlity of drain sensor (DS)
Inspected unit Indoor.
Code P5
Error detail Malfunction of drain-up machine.
Inspected unit Indoor.
Code P6
Error detail Freezing/overheating protection detect.
Inspected unit Indoor.
Code P8
Error detail Abnormality of pipe temperature.
Inspected unit Indoor.
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
4/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Code P9
Error detail Anormality of pipe temperature thermistor/condenser/evaporator (TH5)
Inspected unit Indoor.
Code F1
Error detail Reverse phase detection.
Code F2
Error detail L3 open phase detection.
Code F3
Error detail 63L connector open.
Code F4
Error detail 49C connector open.
Code F9
Error detail Connector 2 or more open.
Code FA
Error detail L2-phased open phase or 51CM connector open.
Code F7
Error detail Reverse phase detection circuit (p.c.board) fault.
Code F8 Error detail Input circuit fault.
Code U2
Error detail Abnormal high discharging temperature.
Code U2
Error detail Inner thermostat (49C) operation.
Code U1 Error detail Abnormal high pressure (high pressure swicth 63H worked)
Code U1
Error detail Direct cut operation.
Code UE
Error detail High pressure error (ball valve closed)
Code UL Error detail Abnormal low pressure.
Code Ud
Error detail Over heat protection
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
5/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Code U6
Error detail Compressor over current (overload) cut off.
Code UA
Error detail Compressor over current (terminal relay operation).
Code UF Error detail Compressor over current (start-up locked) cut off.
Code UF
Error detail Compressor over current (operating locked) cut off.
Code UH
Error detail Current sensor error.
Code U3 Error detail Discharge thermistor short/open.
Code U4
Error detail Outdoor thermistor short/open.
Mr.Slim K-control
Display of remote controller
LED E0 Diagnosis of malfunction Transmitting/receiving signal error.
Inspected unit Indoor.
LED P1
Diagnosis of malfunction Intake air sensor abnormal.
Inspected unit Indoor.
LED P2
Diagnosis of malfunction Pipe sensor abnormal.
Inspected unit Indoor.
LED P4
Diagnosis of malfunction Drain sensor abnormal.
Inspected unit Indoor.
LED P5
Diagnosis of malfunction Malfunctioning of the drain overflow protecting mechanism.
Inspected unit Indoor.
LED P6
Diagnosis of malfunction Abnomality of the coil frost/overheating protection mode.
Inspected unit Indoor.
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
6/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED P3
Diagnosis of malfunction System error (transmitting/receiving signal).
Inspected unit Indoor.
LED P7
Diagnosis of malfunction System error (address)
Inspected unit Indoor.
LED P8
Diagnosis of malfunction Outdoor unit malfunction
Inspected unit Outdoor.
Mr.Slim K-control PUH-EK
Outdoor unit
LED ON = Operation status
LED Flash = Check code diplay
LED LD1
LED ON Compressor directive
LED Flash Reverse phase detect
LED LD2
LED ON Heating directive
LED Flash Open phase detect
LED LD3
LED ON During 63H1 operation
LED Flash Pipe sensor short/open
LED LD4
LED ON Compressor ON
LED Flash High pressure swicth (63H2) operation.
LED LD5
LED ON Outdoor fan ON
LED Flash Over current relay (51CM) operation.
LED LD6
LED ON 4-way valve ON
LED Flash Thermal swicth (26C) operation.
LED LD7
LED ON Bypass valve ON
LED Flash Thermistor (TH3) overheat protection.
LED LD8
LED ON Crankcase heater ON
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
7/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED Flash Devective input.
Mitsubishi Electric ‘Mr. Slim’ P-Series Commercial Models
Mitsubishi Electric ‘Mr. Slim’ P-Series Commercial Models
TROUBLESHOOTING TIPS / P8 ERROR CODE
List of error codes and stop codes (for all models)
Pdf -1
Pdf -2
Pdf -3
Mitsubishi Mr.Slim Error Code Pdf
Mr Slim MULTI-S CHECK CODE
https://docs.google.com/file/d/0BwpXRGTFIK57VjYtN1hsQm9KMjA/previewhttps://docs.google.com/file/d/0BwpXRGTFIK57anNjd0E2SzJvTUEhttps://docs.google.com/file/d/0BwpXRGTFIK57OEdaSGgxMWlsZzghttps://drive.google.com/file/d/0BwpXRGTFIK57RVkwbTNqX2RDc0Ehttps://docs.google.com/file/d/0BwpXRGTFIK57X1BMVk91ZmFWMFk/previewhttps://docs.google.com/file/d/0BwpXRGTFIK57X1BMVk91ZmFWMFk/previewhttps://drive.google.com/file/d/0BwpXRGTFIK57RVkwbTNqX2RDc0Ehttps://docs.google.com/file/d/0BwpXRGTFIK57OEdaSGgxMWlsZzghttps://docs.google.com/file/d/0BwpXRGTFIK57anNjd0E2SzJvTUEhttps://docs.google.com/file/d/0BwpXRGTFIK57VjYtN1hsQm9KMjA/preview
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
8/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
ERROR CODE = 1102
POSTPONED ERROR CODE = 1202
FAULT = Discharge temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?
ERROR CODE = 1108
POSTPONED ERROR CODE = 1208
FAULT = Inner thermostat of compressor is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the S phase on outdoor board open?
ERROR CODE = 1302
POSTPONED ERROR CODE = 1402
FAULT = High-pressure is unusual
DETECTED UNIT
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
9/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is the ball valve opened?
2) Confirm whether indoor filter is blocked or whether outdoor short cycle occurred
ERROR CODE = 1500
POSTPONED ERROR CODE = 1600
FAULT = Refrigerant is overcharged
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?
ERROR CODE = 1501
POSTPONED ERROR CODE = 1601
FAULT = Refrigerant is insufficient
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
10/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?
ERROR CODE = 1505
POSTPONED ERROR CODE = 1605
FAULT = Vacuum operation is protected
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether gas leak or gas shortage occurred
2) Is the ball valve open?
ERROR CODE = 2502
POSTPONED ERROR CODE =
FAULT = Drain pump is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED
1) Confirm whether drain pipe is inclined or blocked
2) Connector of drain pipe seperated
ERROR CODE = 2503
POSTPONED ERROR CODE =
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
11/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
FAULT = Drain sensor (THd) is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED
1) Drain sensor is dirty
2) CN50 connector on indoor board seperated
ERROR CODE = 4115
POSTPONED ERROR CODE = 4165
FAULT = Synchronizing signal of power is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is R phase or T phase open?
2) Has fuse of R phase or T phase blown?
ERROR CODE = 4116
POSTPONED ERROR CODE =
FAULT = Rotation amount of fan is wrong (PKFY-AM)
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
12/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Remote Control =
THE PART TO BE CHECKED
1) Is air filter blocked
ERROR CODE = 4220
POSTPONED ERROR CODE = 4320
FAULT = Voltage of inverter bus is insufficient
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is S phase open?
ERROR CODE = 4230
POSTPONED ERROR CODE = 4330
FAULT = Temperature of heat dissipation board is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is ventilation of heat dissipation board for cooling blocked
ERROR CODE = 4250
POSTPONED ERROR CODE = 4350
FAULT = IPM error (Heat current is intercepted) IPM error
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
13/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Is any power phase open?
2) Has voltage of power supply failed?
ERROR CODE = 5101
POSTPONED ERROR CODE = 1202
FAULT = Thermistor (TH21) for suction temperature is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) CN20 connector on indoor board seperated
ERROR CODE = 5101
POSTPONED ERROR CODE = 1202
FAULT = Thermistor (TH1) for Discharge temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH1 connector on outdoor board seperated
ERROR CODE = 5102
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
14/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
POSTPONED ERROR CODE = 1211
FAULT = Thermistor (TH22) for refrigerant pipe temperature is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) CN21 connector on indoor board seperated
ERROR CODE = 5102
POSTPONED ERROR CODE = 1211
FAULT = Thermistor (TH2) for suction pressure saturation temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH2 connector on outdoor board seperated
ERROR CODE = 5103
POSTPONED ERROR CODE = 1213
FAULT = Thermistor (TH23) for gas pipe temperature is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
THE PART TO BE CHECKED = 1) TH29 connector on indoor board seperated
ERROR CODE = 5105
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
15/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
POSTPONED ERROR CODE = 1205
FAULT = Thermistor (TH5) for condensor outlet temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH5 connector on indoor board seperated
ERROR CODE = 5106
POSTPONED ERROR CODE = 1221
FAULT = Thermistor (TH6) for outdoor temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) TH6 connector on indoor board seperated
ERROR CODE = 5110
POSTPONED ERROR CODE = 1214
FAULT = Thermistor (THHS) for IPM heat dissipation board temperature is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) THHS connector on indoor board seperated
ERROR CODE = 5201
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
16/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
POSTPONED ERROR CODE = 1402
FAULT = Pressure sensor (63HS) is unusual
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Affirm whether gas leak or gas shortage occurred
ERROR CODE = 6600
POSTPONED ERROR CODE =
FAULT = Address double definition error
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Is the same address as the error generating origin specified?
ERROR CODE = 6602
POSTPONED ERROR CODE =
FAULT = Transmission processor H/W error
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Turn power OFF simultaneously for 2 minutes or more, Then turn them back on
again.
ERROR CODE = 6603
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
17/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
POSTPONED ERROR CODE =
FAULT = Transmission circuit (bus) Busy error
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Wiring mistake of TB3 or TB7 on outdoor unit
ERROR CODE = 6606
POSTPONED ERROR CODE =
FAULT = Communication error with the transmission processor
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control = *
THE PART TO BE CHECKED = 1) Turn power OFF simultaneously for 2 minutes or more, Then turn them back on
again.
ERROR CODE = 6607
POSTPONED ERROR CODE =
FAULT = No ACK
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control = *
THE PART TO BE CHECKED = 1) Address setting is improper, or transmission cable seperated
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
18/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
ERROR CODE =6608
POSTPONED ERROR CODE =
FAULT = No response
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control = *
THE PART TO BE CHECKED = 1) Check the used electric wire
ERROR CODE = 6810
POSTPONED ERROR CODE =
FAULT = UR communicaton
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control = *
THE PART TO BE CHECKED = 1) Wire connection for the unit remote control transmission is poor
ERROR CODE = 7100
POSTPONED ERROR CODE =
FAULT = Over index
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Has index been exceeded
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
19/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
ERROR CODE = 7101
POSTPONED ERROR CODE =
FAULT = Over index
DETECTED UNIT
Indoor Unit = *
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED = 1) Has an indoor unit beyond the permitted index connected
ERROR CODE = 7102
POSTPONED ERROR CODE =
FAULT = The number of connected units
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
Remote Control =
THE PART TO BE CHECKED
1) Are connected units over the number of restriction?
2) Transmission cord of indoor unit seperated
ERROR CODE = 7105
POSTPONED ERROR CODE =
FAULT = Address setting error
DETECTED UNIT
Indoor Unit =
Outdoor Unit = *
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
20/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Remote Control =
THE PART TO BE CHECKED = 1) Is outdoor unit address set to 000 or to a range of 51-100?
ERROR CODE = 7111
POSTPONED ERROR CODE =
FAULT = Remote control sensor is unusual
DETECTED UNIT
Indoor Unit = *
Outdoor Unit =
Remote Control =
Mr Slim A-CONTROL CHECK CODE (U INDICATIONS)
INDICATIONS ON REMOTE CONTROL = U1
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) =
LED2 (RED) =
FAULTS = Unusual high pressure (63H) operated
STANDARD =
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Is ball valve open?
2) Check the indoor/outdoor short cycle
INDICATIONS ON REMOTE CONTROL = U2
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
21/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash Once
FAULTS = Discharge temperature is unusual/49C (inner thermostat operated) Refrigerant is insufficient
STANDARD =
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Check whether air filter is dirty to Clean it
2) Confirm whether gas leak or gas shortage occurred
3) Check the indoor/outdoor short cycle
INDICATIONS ON REMOTE CONTROL = U7
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash Once
FAULTS = Superheat occurred by low discharge
STANDARD =
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Has the discharge thermistor seperated?
2) Confirm whether electronic expansion valve has failed
3) Check CN LEV connector on the outdoor board
INDICATIONS ON REMOTE CONTROL = UE
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
22/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash Twice
FAULTS = Unusual high-pressure (63H) operated
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Is the ball valve open?
2) Check the indoor/outdoor short cycle
3) Is gas overcharged
INDICATIONS ON REMOTE CONTROL = UL
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash Twice
FAULTS = Unusual low-pressure (63L) operated
STANDARD = *
INVERTER =
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Is the ball valve open?
2) Confirm whether gas leak or gas shortage has occurred
INDICATIONS ON REMOTE CONTROL = Ud
INDICATIONS ON OUTDOOR UNIT
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
23/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 3 Times
FAULTS = Over raise is protected (overload operation is protected/Fan fault)
STANDARD = *
INVERTER =
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Check whether outdoor heat exchanger is dirty try to Clean it
2) Check the outdoor short cycle
INDICATIONS ON REMOTE CONTROL = U6
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 4 Times
FAULTS = Compressor is intercepted by over-current (overload)
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) After turning crank case heater on, have 12 hours or more passed?
INDICATIONS ON REMOTE CONTROL = U6
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 4 Times
FAULTS = Powered module fault occurred
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
24/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
STANDARD =
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = (Replace the outdoor board)
INDICATIONS ON REMOTE CONTROL = UC
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 4 Times
FAULTS = Compressor self protection activated
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Is ball valve open?
INDICATIONS ON REMOTE CONTROL = UF
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 4 Times
FAULTS = Compressor is over-current (locked)
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Is ball valve open?
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
25/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
2) Is power capacity insufficient?
INDICATIONS ON REMOTE CONTROL = UH
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 4 Times
FAULTS = Current sensor is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) If outdoor board has been replaced: Check wiring and board setting
INDICATIONS ON REMOTE CONTROL = U3
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 5 Times
FAULTS = Discharge thermistor (TH14) is open/short
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = TH4 connector on outdoor board seperated
INDICATIONS ON REMOTE CONTROL = U4
INDICATIONS ON OUTDOOR UNIT
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
26/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 5 Times
FAULTS = Pipe thermistor (TH3) is open/short
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = TH3 connector on outdoor board seperated
INDICATIONS ON REMOTE CONTROL = U4
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 5 Times
FAULTS = 2-phase pipe thermistor (TH6) is open/short
STANDARD =
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = TH6 connector on outdoor board seperated
INDICATIONS ON REMOTE CONTROL = U4
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 3 Times
LED2 (RED) = Flash 5 Times
FAULTS = Outdoor temperature thermistor (TH7) is open/short
STANDARD =
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
27/45
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
28/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON REMOTE CONTROL = UP
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) =
LED2 (RED) =
FAULTS = Compressor is intercepted by over-current
STANDARD =
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Is ball valve open?
Mr Slim A-CONTROL CHECK CODE (F.P INDICATIONS)
INDICATIONS ON REMOTE CONTROL = F1
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
LED2 (RED) = Flash Once
FAULTS = Negative phase is detected, or power or connection between indoor unit and outdoor unit is incorrec
STANDARD = *
INVERTER =
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Power or connection cable between indoor unit and outdoor unit is misplaced
2) Negative Phase –> Exchange R.T phase on outdoor power terminal
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
29/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
3) Are all the 3 phases of power voltage the same voltage
INDICATIONS ON REMOTE CONTROL = F2
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
LED2 (RED) = Flash Once
FAULTS = Open phase is detected (T phase is open)
STANDARD = *
INVERTER =
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) T phase of outdoor power terminal is loose
2) Are all the 3 phases of power voltage the same voltage
INDICATIONS ON REMOTE CONTROL = F3
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
LED2 (RED) = Flash Twice
FAULTS = Connector (63H) is open
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Connector (63L) on outdoor board seperated
2) Terminal of low-pressure switch (63L) seperated
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
30/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON REMOTE CONTROL = F5
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
LED2 (RED) = Flash Twice
FAULTS = Connector (63H) is open
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Connector (63H) on outdoor board seperated
2) Terminal of high-pressure switch (63H) seperated
INDICATIONS ON REMOTE CONTROL = F9
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
LED2 (RED) = Flash Twice
FAULTS = Two or more connectors are open
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) Confirm whether the connector on board seperated, or is loose
INDICATIONS ON REMOTE CONTROL = F7
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
31/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED2 (RED) = Flash 3 times
FAULTS = Circuit (board) of negative phase detection is poor
STANDARD = *
INVERTER =
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = (Replace the outdoor board)
INDICATIONS ON REMOTE CONTROL = F8
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Once
LED2 (RED) = Flash 3 times
FAULTS = Input circuit (board) is poor
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = (Replace the outdoor board)
INDICATIONS ON REMOTE CONTROL = P1
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 4 Times
LED2 (RED) = Flash Once
FAULTS = Suction sensor is unusual
STANDARD = *
INVERTER = *
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
32/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) CN20 connector on indoor board seperated
INDICATIONS ON REMOTE CONTROL = P2
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 4 Times
LED2 (RED) = Flash Once
FAULTS = pipe (refrigerant pipe) sensor is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) CN21 connector on indoor board seperated
INDICATIONS ON REMOTE CONTROL = P4
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 4 Times
LED2 (RED) = Flash Twice
FAULTS = Drain sensor is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) CN31 connector on indoor board seperated
INDICATIONS ON REMOTE CONTROL = P5
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
33/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 4 Times
LED2 (RED) = Flash Twice
FAULTS = Drain overflow is protected or water leakage ocurred
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) Confirm whether draining pipe is inclined or blocked
2) Confirm whether drain-pan or drain sensor becomes dirty
3) CNP connector on indoor board seperated
INDICATIONS ON REMOTE CONTROL = P6
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 4 Times
LED2 (RED) = Flash 3 Times
FAULTS = Freeze protecting (in cooling mode) / Over rise protecting (in heating mode)
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) Air filter is dirty
2) Gas leak or gas shortage occurred
3) Does fan work on indoor unit?
– Check the fan connector
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
34/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON REMOTE CONTROL = P8
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash 4 Times
LED2 (RED) = Flash 4 Times
FAULTS = Pipe temperature is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) Confirm whether wiring between indoor unit and outdoor unit or piping is faulty
when using 2 indoor units
2) Gas leak or gas shortage occurred
INDICATIONS ON REMOTE CONTROL = P9
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) =
LED2 (RED) =
FAULTS = Pipe (two-phase pipe) sensor is unusual
STANDARD =
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) CN29 connector on indoor board seperated
Mr Slim A-Control Check Code (E Indication)
INDICATIONS ON REMOTE CONTROL = E0
INDICATIONS ON OUTDOOR UNIT
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
35/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Remote Control
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave
been performed?
2) Is a specified 2 core wire used for the electric wire? (03 – 1.25mm2 ) A wire with 3 or more cores is NG
INDICATIONS ON REMOTE CONTROL = E3
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Remote Control
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave
been performed?
2) Is a specified 2 core wire used for the electric wire? (03 – 1.25mm2 ) A wire with 3 or more cores is NG
INDICATIONS ON REMOTE CONTROL = E4
INDICATIONS ON OUTDOOR UNIT
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
36/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave
been performed?
2) Is a specified 2 core wire used for the electric wire? (03 – 1.25mm2 ) A wire with 3 or more cores is NG
INDICATIONS ON REMOTE CONTROL = E5
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 3 times
FAULTS = Communication or reception of remote control is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) When using two or more remote controls, has a setup for master and slave
been performed?
2) Is a specified 2 core wire used for the electric wire? (03 – 1.25mm2 ) A wire with 3 or more cores is NG
INDICATIONS ON REMOTE CONTROL = E6
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
37/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated
INDICATIONS ON REMOTE CONTROL = E7
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
38/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated
INDICATIONS ON REMOTE CONTROL = E8
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated
INDICATIONS ON REMOTE CONTROL = E9
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
39/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
LED2 (RED) = Flash Twice
FAULTS = Communication or reception between indoor unit and outdoor unit is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated
INDICATIONS ON REMOTE CONTROL = EA
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Once
FAULTS = Wiring for connection between indoor unit and outdoor unit is wrong
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
40/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated
INDICATIONS ON REMOTE CONTROL = Eb
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash Once
FAULTS = Wiring for connection between indoor unit and outdoor unit is wrong (improper or seperated)
STANDARD = *
INVERTER = *
DETECTED UNIT = Outdoor Unit
THE PART TO BE CHECKED = 1) The line between indoor unit and outdoor unit is slack or unsuitable
2) Is VVF with 3 cores used for the electric wire
3) Is there a branch connection in middle of the line between indoor unit and outdoor unit
4) Is the connection line between unit and outdoor unit wet
5) Has fuse of outdoor board blown?
6) Connector (CN01, 02 or 03) is slack or seperated
INDICATIONS ON REMOTE CONTROL = EE
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 4 times
FAULTS = The combination is unusual
STANDARD = *
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
41/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
INVERTER = *
DETECTED UNIT = Indoor unit and Outdoor unit
THE PART TO BE CHECKED = 1) Check the combination of indoor unit and outdoor unit
INDICATIONS ON REMOTE CONTROL = EF
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 4 times
FAULTS = Non-definition error (M-NET system error / No target code)
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor unit and Outdoor unit
THE PART TO BE CHECKED = 1) Check the unusual indications of M-NET system’ remote control or centralized
management system
INDICATIONS ON REMOTE CONTROL = Ed
INDICATIONS ON OUTDOOR UNIT
LED1 (GREEN) = Flash Twice
LED2 (RED) = Flash 5 times
FAULTS = Communication between M-NET adapters is unusual
STANDARD = *
INVERTER = *
DETECTED UNIT = Indoor unit and Outdoor unit
THE PART TO BE CHECKED = 1) The connector between indoor control board and M-NET board seperated.
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
42/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Related Posts:
1. Mr. Slim Ai r Conditioner Error Codes
2. Mitsubishi Mr Slim Air Conditioning Fault Codes
CATEGORIES
Acson
Airwell
Amana
AmeriCool
Aux
Baxi
Bryant
Carrier
Chigo
Chunlan
Leave a ReplyYour email address will not be published. Required fields are marked *
Comment
Name *
Email *
Website
Search
Post Comment
http://acerrorcode.com/mr-slim-air-conditioner-error-codes-2.htmlhttp://acerrorcode.com/mitsubishi-mr-slim-air-conditioning-fault-codes.htmlhttp://acerrorcode.com/brands/acsonhttp://acerrorcode.com/brands/airwellhttp://acerrorcode.com/brands/amanahttp://acerrorcode.com/brands/americoolhttp://acerrorcode.com/brands/auxhttp://acerrorcode.com/brands/baxihttp://acerrorcode.com/brands/bryanthttp://acerrorcode.com/brands/carrierhttp://acerrorcode.com/brands/chigohttp://acerrorcode.com/brands/chunlanhttp://acerrorcode.com/brands/chunlanhttp://acerrorcode.com/brands/chigohttp://acerrorcode.com/brands/carrierhttp://acerrorcode.com/brands/bryanthttp://acerrorcode.com/brands/baxihttp://acerrorcode.com/brands/auxhttp://acerrorcode.com/brands/americoolhttp://acerrorcode.com/brands/amanahttp://acerrorcode.com/brands/airwellhttp://acerrorcode.com/brands/acsonhttp://acerrorcode.com/mitsubishi-mr-slim-air-conditioning-fault-codes.htmlhttp://acerrorcode.com/mr-slim-air-conditioner-error-codes-2.html
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
43/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Climatemaster
Comfortaire
Comfortmaker
Daikin
Danby
Delonghi
Derby
Dometic
Edgestar
Fedders
Friedrich
Frigidaire
Fujitsu
Fujitsu General
Galanz
GE
Gree
Haier
Hitachi
Home
Keeprite
Kelvinator
Klimaire
Koppel
Lennox
LG
Lloyd
McQuay
Midea
Mitsubishi
Mitsubishi Electric
http://acerrorcode.com/brands/climatemasterhttp://acerrorcode.com/brands/comfortairehttp://acerrorcode.com/brands/comfortmakerhttp://acerrorcode.com/brands/daikinhttp://acerrorcode.com/brands/danbyhttp://acerrorcode.com/brands/delonghihttp://acerrorcode.com/brands/derbyhttp://acerrorcode.com/brands/dometichttp://acerrorcode.com/brands/edgestarhttp://acerrorcode.com/brands/feddershttp://acerrorcode.com/brands/friedrichhttp://acerrorcode.com/brands/frigidairehttp://acerrorcode.com/brands/fujitsuhttp://acerrorcode.com/brands/fujitsu-generalhttp://acerrorcode.com/brands/galanzhttp://acerrorcode.com/brands/gehttp://acerrorcode.com/brands/greehttp://acerrorcode.com/brands/haierhttp://acerrorcode.com/brands/hitachihttp://acerrorcode.com/brands/homehttp://acerrorcode.com/brands/keepritehttp://acerrorcode.com/brands/kelvinatorhttp://acerrorcode.com/brands/klimairehttp://acerrorcode.com/brands/koppelhttp://acerrorcode.com/brands/lennoxhttp://acerrorcode.com/brands/lghttp://acerrorcode.com/brands/lloydhttp://acerrorcode.com/brands/mcquayhttp://acerrorcode.com/brands/mideahttp://acerrorcode.com/brands/mitsubishihttp://acerrorcode.com/brands/mitsubishi-electrichttp://acerrorcode.com/brands/mitsubishi-electrichttp://acerrorcode.com/brands/mitsubishihttp://acerrorcode.com/brands/mideahttp://acerrorcode.com/brands/mcquayhttp://acerrorcode.com/brands/lloydhttp://acerrorcode.com/brands/lghttp://acerrorcode.com/brands/lennoxhttp://acerrorcode.com/brands/koppelhttp://acerrorcode.com/brands/klimairehttp://acerrorcode.com/brands/kelvinatorhttp://acerrorcode.com/brands/keepritehttp://acerrorcode.com/brands/homehttp://acerrorcode.com/brands/hitachihttp://acerrorcode.com/brands/haierhttp://acerrorcode.com/brands/greehttp://acerrorcode.com/brands/gehttp://acerrorcode.com/brands/galanzhttp://acerrorcode.com/brands/fujitsu-generalhttp://acerrorcode.com/brands/fujitsuhttp://acerrorcode.com/brands/frigidairehttp://acerrorcode.com/brands/friedrichhttp://acerrorcode.com/brands/feddershttp://acerrorcode.com/brands/edgestarhttp://acerrorcode.com/brands/dometichttp://acerrorcode.com/brands/derbyhttp://acerrorcode.com/brands/delonghihttp://acerrorcode.com/brands/danbyhttp://acerrorcode.com/brands/daikinhttp://acerrorcode.com/brands/comfortmakerhttp://acerrorcode.com/brands/comfortairehttp://acerrorcode.com/brands/climatemaster
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
44/45
Mr. Slim Air Conditioner Error Codes
ttp://acerrorcode.com/mr-slim-air-conditioner-error-codes.html[03/03/2016 10:23:01 PM]
Recent Posts Comments
Mitsubishi Heavy
Mr. Slim
Onida
Panasonic
Ramsond
Rheem
Rittal
Ruud
Samsung
Sanyo
Sharp
Shinco
TCL
Teco
Thermal Zone
Thermo King
Toshiba
Trane
Unionaire
Westinghouse
Whirlpool
York
Daikin AC Heat Pump Error Codes
6:53 pm By admin
Fault diagnosis by remote controller Read More »
Samsung DVM S Error Codes
10:20 am By admin
E-101 Indoor unit communication error. No response from outdoor unit. (Indoor unit display) Read More »
Daikin VRV 4 Fault Codes
7:48 pm By admin
In case a malfunction code appears on the indoor unit user interface display, contact your installer and inform the
http://acerrorcode.com/brands/mitsubishi-heavyhttp://acerrorcode.com/brands/mr-slimhttp://acerrorcode.com/brands/onidahttp://acerrorcode.com/brands/panasonichttp://acerrorcode.com/brands/ramsondhttp://acerrorcode.com/brands/rheemhttp://acerrorcode.com/brands/rittalhttp://acerrorcode.com/brands/ruudhttp://acerrorcode.com/brands/samsunghttp://acerrorcode.com/brands/sanyohttp://acerrorcode.com/brands/sharphttp://acerrorcode.com/brands/shincohttp://acerrorcode.com/brands/tclhttp://acerrorcode.com/brands/tecohttp://acerrorcode.com/brands/thermal-zonehttp://acerrorcode.com/brands/thermo-kinghttp://acerrorcode.com/brands/toshibahttp://acerrorcode.com/brands/tranehttp://acerrorcode.com/brands/unionairehttp://acerrorcode.com/brands/westinghousehttp://acerrorcode.com/brands/whirlpoolhttp://acerrorcode.com/brands/yorkhttp://acerrorcode.com/daikin-ac-heat-pump-error-codes.htmlhttp://acerrorcode.com/daikin-ac-heat-pump-error-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-error-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-error-codes.htmlhttp://acerrorcode.com/daikin-vrv-4-fault-codes.htmlhttp://acerrorcode.com/daikin-vrv-4-fault-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-error-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-error-codes.htmlhttp://acerrorcode.com/daikin-ac-heat-pump-error-codes.htmlhttp://acerrorcode.com/daikin-ac-heat-pump-error-codes.htmlhttp://acerrorcode.com/brands/yorkhttp://acerrorcode.com/brands/whirlpoolhttp://acerrorcode.com/brands/westinghousehttp://acerrorcode.com/brands/unionairehttp://acerrorcode.com/brands/tranehttp://acerrorcode.com/brands/toshibahttp://acerrorcode.com/brands/thermo-kinghttp://acerrorcode.com/brands/thermal-zonehttp://acerrorcode.com/brands/tecohttp://acerrorcode.com/brands/tclhttp://acerrorcode.com/brands/shincohttp://acerrorcode.com/brands/sharphttp://acerrorcode.com/brands/sanyohttp://acerrorcode.com/brands/samsunghttp://acerrorcode.com/brands/ruudhttp://acerrorcode.com/brands/rittalhttp://acerrorcode.com/brands/rheemhttp://acerrorcode.com/brands/ramsondhttp://acerrorcode.com/brands/panasonichttp://acerrorcode.com/brands/onidahttp://acerrorcode.com/brands/mr-slimhttp://acerrorcode.com/brands/mitsubishi-heavy
-
8/20/2019 Mr. Slim Air Conditioner Error Codes
45/45
Mr. Slim Air Conditioner Error Codes
malfunction code, the unit type, and serial Read More »
Samsung DVM S Hydro Unit Error Codes
5:48 pm By admin
Samsung DVM S Hydro Unit Error Codes Read More »
Comfortmaker Air Conditioner Troubleshooting11:26 pm By admin
Some models are factory equipped with the Comfort Alert Diagnostics device in the control box (refer to Figure
Read More »
© 2016 AC Error Code
http://acerrorcode.com/daikin-vrv-4-fault-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-hydro-unit-error-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-hydro-unit-error-codes.htmlhttp://acerrorcode.com/comfortmaker-air-conditioner-troubleshooting.htmlhttp://acerrorcode.com/comfortmaker-air-conditioner-troubleshooting.htmlhttp://acerrorcode.com/http://acerrorcode.com/http://acerrorcode.com/comfortmaker-air-conditioner-troubleshooting.htmlhttp://acerrorcode.com/comfortmaker-air-conditioner-troubleshooting.htmlhttp://acerrorcode.com/samsung-dvm-s-hydro-unit-error-codes.htmlhttp://acerrorcode.com/samsung-dvm-s-hydro-unit-error-codes.htmlhttp://acerrorcode.com/daikin-vrv-4-fault-codes.html