Fort Hood LONWORKS®
UMCS / MeteringImplementation
PRESENTED BY
Bobby Lynn & Dick Strohl Fort Hood,Texas DPW
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 2 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
FORT HOOD UMCS
PURPOSE
• Provide a general overview of the Fort Hood’s Utility Monitoring and Control System (UMCS) and Metering System
TOPICS
• Fort Hood UMCS History• System Configuration• Facility Performance Indexing (Continuous Commissioning)• Use of Meter Data
• Mock Billing• Reimbursable customers
• Next Step• Summary
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 3 12 July 201112 July 2011
Fort Hood UMCS / DDC
Army’s First Base-Wide Facility Control SystemUsing Flat LonWorks Open Controls
Technology
In Cooperation with:
• Headquarters U.S. Army Corps of Engineers (HQUSACE)
• COE Engineer Research Development Center CERL
• COE Huntsville Mandatory Center of Expertise for UMCS
• COE Fort Worth District Mechanical Design Branch
• Johnson Controls Inc, Circon, Echelon, Loytec, Honeywell, TAC, Trane, Voyant, Invensys, Gesytec, Distech, Continental Control Systems, Capelon, ABB, others
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 4 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
Fort Hood Open Systems History:
• 2001: Begin collaboration with CERL, HNC, SWF, and vendors on open system technologies
• Led to whiter paper decision to develop LonWorks specification• UFGS 25 10 10 (UMCS), and UFGS 23 09 23 (DDC)
• 2003: ESPC Delivery Order #1 • DDC in 36 Buildings• Non-flat, less than fully open LONWORKS ®
• Accessible via PC over LAN• Eliminated the need for laptops and software
• 2006: ESPC Delivery Order #2• DDC in 55 Buildings• JCI provided a PC solution to replace Network Application Engines (NAEs),
Flat/Open LONWORKS• Workstations and printers delivered to Maintenance Shops• Local Display Panels (LDPs) were included for local access to DDC
• 2009 ESPC Delivery Order #3• Commission and integrate an additional 54 facilities• Includes Facility Performance Indexing (Continuous Commissioning) for a chilled
water thermal storage plant and 17 satellite facilities
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 5 12 July 201112 July 2011
Fort Hood BAS
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 6 12 July 201112 July 2011
JCI Facility Performance Indexing (JCFPI)
• Continuous Commissioning is becoming the standard for optimizing and sustaining performance of mechanical/electrical systems
• Definition of a Performance Index: A number derived from a formula, used to characterize a set of data
“You can’t manage if you don’t measure”
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 7 12 July 201112 July 2011
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 8 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
Why is the VAV zone temp Red? Setpoint is not being achieved.
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 9 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
FORT HOOD METERING SYSTEM
Utilities Monitoring and Control System (UMCS)• Metasys (software) by Johnson Controls, Inc.• Based on LonWorks (open communication system)• Using Run-Time Management• Flat Architect (communication peer-peer)• Point mapping: Current 29,161 points are mapped.
Metering System• Meters Online
• Electric: 125• Gas: 15
• Meter: Wattnode (by CCS)• Variables (42 available) - RMS Power - Watts (ph) - Voltage (ph) - Reactive Power - VARs (ph) - Current (ph) - Power Factor (ph) - Reactive Energy (sum) - RMS Energy – WH, kWh (ph) - Net Energy (ph) - RMS Voltage (Phase A, B, C) - Demand (int, pk) - Reactive Energy - VAR-hours (ph) - AC Frequency
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 10 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
SYSTEM CONFIGURATION
Authorized Users
UMCS SERVER
Lon Router / Lon Devices
FORT HOOD LAN/ /
Wireless xtr / Lon Devices
RF Wireless //
1. Two methods of transmission2. NEC recently approved RF (Wireless)3. Data stored on Servers4. Assessable by authorized users
NEW TRANSMISSION METHOD
Lon Router / Wireless xtr
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 11 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
BILLING
Used at Ft Hood to modify behavior and collect reimbursement from non-ASIP organizations.
Reimbursable Customers• Billed with UBS for actual usage• Reimbursements made thru DFAS
Mock Billing• Increases awareness• Fosters competition• Provided to O-6 level commanders by
Garrison Cdr monthly
Family Housing• Residents billed by RCI partner• Refund/charge based on individual unit
baseline
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 12 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
NEXT STEP
• Install electric meters down to 10,000 SF facilities • Continue with installation of gas and water meters • Continue to add buildings to the UMCS
• Expand “Mock” billing
No Measuring – No Management
Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716 13 12 July 201112 July 2011Mr. Bobby, IMWE-HOD, [email protected], (254) 287-8716
SUMMARY
• Open systems planning is necessary to get the desired results. The system must be properly specified, designed, and managed.
• Securing NEC approval is lengthy – need Army policy • Investment funding • Recruiting qualified energy employees, including techs to maintain advanced meters and UMCS
• Identify how systems are turned over to the installation• Fully tested and commissioned• To a highly trained staff