MPI-II user manual

86
24.7.2019 Handbuch https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 1/86 MPI-II user manual (english) Art.Nr. 9352 Art.Nr. 9352.05M Art.Nr. 9352.10M Art.Nr. 9352.15M 21.02.2014 © PI 2014

Transcript of MPI-II user manual

Page 1: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 1/86

MPI-IIusermanual(english)

Art.Nr.9352Art.Nr.9352.05MArt.Nr.9352.10MArt.Nr.9352.15M

21.02.2014

©PI2014

Page 2: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 2/86

indexofcontents

MPI-II

1Description

2Systemrequirements2.1Operatingsystem(s)

2.2Software

2.3Hardware

2.4ProvidedPLCs

3Installation3.1Hardware

3.2Software

3.3USB-driver-installationfor32-bit-systems

3.4USB-driver-installationforWin764-bit

4Controlelements4.1Keys

4.2Display

5Implementing5.1FirstConfiguration

5.2UsingthePLC-VCOM

5.3Programmingsoftwaretousewithdirectaccess

5.3.1PG2000fürS7(V5.10)

5.3.2PSetPG/PCinterface

5.3.2.1PC-Adapter(Auto,MPI,PROFIBUS)

5.3.2.2TCP/IPRFC1006Communication

Page 3: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 3/86

5.3.2.3MPIsetting

5.3.2.4Profibussetting

5.3.2.5TCP/IPRFC1006setting

5.3.2.6ProTool/ProRunTime(RT)Configuration

5.3.3SIMATICStep©7Manager(v5.2+SP1)

5.3.4WindowsControlCenter(WinCC)(v6.0)

5.3.4.1MPIConfiguration

5.3.4.2TCP/IPConfiguration

5.3.4.3Communicationandfaultdiagnosis

5.3.5WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)

5.3.6ProTool/Prov6.0SP2

5.3.7Microwinv3.2(onlyforS7200)

5.3.8Microwinv4.0inPPI-Multimaster-Mode

5.3.9S7forWindowsv5.02

5.4ConfigureoperatingterminalviaMPI-II/MPI-USB

5.4.1DirectsettingofaslaveaddresstoapassiveProfibus-Slave

6Configuration6.1KeysandDisplay

6.1.1GraphicalDescription

6.1.2Config

6.1.3Bus

6.1.4Info

7S7-InterfaceConfiguratorHelp7.1Languageselection:

7.2Userinterface:

7.3Busconfiguration

7.4Networksettings

7.5ParameterizeTELEService

7.5.1Index"Network":

7.5.2Index"Modem":

Page 4: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 4/86

7.5.3Index"Serialparameter":

7.5.4Index"AccessProtection":

7.5.5Index"GSM/ISDN/SMS":

7.5.6Index"Internet/Mail":

7.6Tuning

7.7Factorydefaults

7.8PPIBootoff

7.9Emergency-Loader

8MPIcablemanager8.1Description

8.2Installation

8.3Overview

8.3.1Language

8.3.2Interface

8.3.3Update

8.3.4Teleservice

8.3.4.1Telephonebook

8.3.4.2Connect

8.3.4.3Extra

8.3.4.3.1„Setup“

8.3.4.3.2„TS-function“

8.3.4.3.3„configureadapter“

8.3.4.3.4„Importparameter“

8.3.4.3.5„Exportparameter“

8.3.5Tuning

9PLC-VCOM9.1Description

9.2Installation

9.2.1USBdriverinstallationusingWindowsNT/2000/XP

9.2.2FinalconfigurationofthePLC-VCOM

Page 5: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 5/86

9.2.3USBdriverinstallationusingWindows98SE/ME)

9.3Overview

9.3.1Statusdescription:

9.3.2MainWindow

9.3.3Configurationwindow

9.4Configuration

9.4.1MPI-II

9.4.1.1Automatic

9.4.1.2Manual

9.4.1.3AbschließendeEinstellungen

10Technicaldata10.1Pinassignment

10.2PinassignmentRS232

10.3Pinning(USB)PC

Page 6: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 6/86

MPI-II

1DescriptionTheMPI-II-CableconnectstheprogrammingdeviceorPCovertheserialInterface(COM-Port)orthePCovertheUSB-BuswiththeMPI-orDP/FMS-ConnectoroftheS7-300/400PLC.TheCableselectsautomaticallyonthefirstaccesswhichPortandwhichBaudrateisused.WithourPLC-Programming-ApplicationPG-95/PG-2000orS7-for-WindowsworkstheMPI-II-Cablewithupto115.2kBaudonthePC-Side.DedicatedforSiemens-ApplicationstheMPI-Speed-driverisdelivered,whichcoulduseBaudratesupto115.2kBaud.TogetherwiththeVCOM-driveryoucouldprogramyourPLCovertheUSB-PortofthePC.

OntheMPI-SideyoucoulduseBaudratesfrom19k2upto12Mbaud.TheBaudrates3M,6Mand12MbaudcouldonlyusedwhenconfiguredontheMPI-II-Cablebykeyboard.AnautomaticselectionoftheMPI-Baudrateispossible.

TheMPI-II-Cableispower-suppliedfromthePLCandneedsthennoexternalsupply.Overanexternalconnector it ispossible tosupply24V to theCable (if theConnectionhasonly the2Data-Lines). All Voltages are decoupled together (24V Input toMPI-Bus and internal Power-Supply).

2Systemrequirements2.1Operatingsystem(s)

Windows98+SEWindowsME/NT/2000WindowsXPWindowsVistaWindows7

2.2Software

PLC-Programmingsoftware(fore.g.PG2000,Step©7,S7fürWindows,Microwin)DirectdriverforSimatic-ManagerforUSBPLC-VCOMSoftware

Avideodescriptionoftheinstallationofdirect-driverandhowtoconfigureitcanbefoundonthepagesupport!

2.3Hardware

9pinor25pinCOM-Portinterface24Vpowersupply(MPI-PPI-interfaceorexternalwithPhoenix-plug)USB1.1-connectortypeA

2.4ProvidedPLCs

S7-200S7-300(providesbaudratenupto12M(whenthePLCisabletosupportthis)S7-400(providesbaudratesupto12M)FM-devicesSinamix(Step7-direct-driverupV1.20orPLCVComupV2.71)MicroMasterandotherelectricaldrivesandinverter-feds(Step7-direct-driverupV1.20orPLCVComupV2.71)Sinumerik(onlyPLC-side)SEW-EURODRIVEpowerinverterandatlastroutingofS7-PLCs

Page 7: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 7/86

3Installation3.1Hardware

MPI/PPInormalmode:

ThiscablewillbeconnectedwithhisshortsidetotheMPI-ortheDP/FMS-InterfaceofthePLC.TheMPI-II -Cable works with the current output voltages of the PLC and doesn’t need anyexternal voltages. The cable requires a PLC to get the 24V out of it. You can also use anoptionalpowersupplytoworkwithanexternal24Vvoltage.Sothecablecanbelengthen.Thelongersideofthecablemustbeconnectwiththeprogramming-deviceorwithanPCtotheCOM-Port.USBisconnectedwithaTypeAtoAcable.

WhentheMPI-II-Cablegetsthepoweritshowsthesoftware-versioninthedisplayandbeginswiththetestofitsinternalcomponents.Onthedisplayallrelevantdataisdisplayed.ThecablewillfindataMPI-Connectiontheactivebaudratetotheprogramming-deviceortothePCinthefirsttimeofcommunicationandsethisbaudratehimself.

Ifyouwanttoconnectthecabletothe25-pinconnectorofthePC,youcanuseanadapter(9pinto25pinsubminiatureD-connector)toworkwiththisport.

ThePLC-ProgrammingapplicationPG95/PG-2000orS7-for-WindowswotkstheMPI-II-Cablewithupto115,2kBaudonthePC-Side.

MPI-IIasTS-Adapter(TS=TeleService):

TheTS-functionallowstheconnectionofamodem,tomakeadial-up-networkconnectionwitha2ndModemandaPCtoaS7-300/400.TheCablemustbeconnectedtoTS-Adapter(withaspecialpinning,noGender-Changer)whichisbetweenthemodemandthePLC.

ToworkwiththeMPI-II-CableinhisTS-function,youmustmakethefollowingactions:

1)ThecablemustbeconfiguredasaTS-Adapter(insteadof“PG”or“Pg”theLCDdisplayshows“TS”or“Ts”).Youcanturnon/offthesefunctionwiththefreeprogram“MPI-CableManager”.

2)DasBetriebssystemdesAdaptersmusseineVersionhöherals1.45haben.DieseVersionwirdkurznachdemAufsteckenaufdieSPSangezeigt.MitdemkostenlosenProgramm„MPI-cableManager“kanndasBetriebssystemaufdenaktuellenStandgebrachtwerden.

3) You need the TeleService-software fromSiemens in your PC toworkwith the cable. TheconfigurationofthecablecanbemadewiththeTeleService-softwarefromSiemensorwiththe„MPI-cableManager“

4)TheconnectionofthemodemtotheMPI-II-cablemustmadewithaspecialadapterplug(nogender-changerorso)

Interfacecable9pintoModemOrder.No.9350-TS

The adapter for the TS-functiononlyworkswith theMPI-II Cablewith the order-number9352!

MPI-IIasHMI-Adapter(HMI=HumanMachineInterface):

TheHMI-possibilityallowstheconnectionofaoperatorpanel(whohasnotaninternalMPI-port,but theHMI-protocol and aRS232-interface orUSB)with aS7-300/400. The cablemust beconnectedbetween theoperatorpaneland thePLC.TheHMI-protocolmustbeapartof theoperatorpanel.

Behind the version V1.45 of the software inside the cable, you can use the cable as aHPIadapter. Some operating panels are made to work with a serial Siemens-HMI-Adapter. Thepiningtoourcableisdifferent.Youmayturnthewires2and3inalittleadapter.Pleaselookintothehandbookoftheoperatorpanelwhatyouneedforthecorrectpinning.

ThisapplysNOTtoHMI-TerminalswhichareconnectedoverUSB.

Page 8: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 8/86

3.2Software

To communicatewith the PLC, please install following products forMPI-USB, S7-USB,MPI-II[onlyUSB],MPI-LANandS7-LAN:

Product Driver

TIA-PortalTIC "TICETH/USB"forMPI,PPIorPROFIBUSconfigurationofdriverwithcontroll-panel settingPD/PC-interface

Simatic-Manager TIC "TICETH/USB"forMPI,PPIorPROFIBUSStarter-Software TIC "TICETH/USB"forMPIorPROFIBUSMicroWin TIC "TICETH/USB"forPPIandS7-22x-PLCMicroWin PLCVComforS7-21x-PLC(noMultiMaster-protocol)PG-2000 PLCVComorforS7-LAN/MPI-LANdirectininterface-settingsS7fürWindows TIC "TICETH/USB"forMPIorPROFIBUSoverPD/PC-interfaceS7fürWindows PLCVCom

To communicate with the PLC, please install following products for MPI/PPI and MPI-II[onlyserial]:

Product Driver

TIA-Portal nosupportbecauseSiemenshastakenouttheserialsupportinthedriver"PC-Adapter"

Simatic-Manager includeddriver"PC-Adapter"forMPIandPROFIBUSStarter-Software includeddriver"PC-Adapter"forMPIandPROFIBUSMicroWin includeddriver"PC/PPI-cable"PG-2000 Standard-function,configurationintheinterface-settingsS7fürWindows Standard-function,configurationintheinterface-settings

3.3USB-driver-installationfor32-bit-systems

The S7-Interface S7-USB, MPI-USB or MPI-II-Kabel over USB as well as the devices ofTeleService-familiywillbeconnectedtoUSB1.1-compatibleportofthePC.ThisopenstheHardware-Installation-Wizard:

Wedon´tneedaconnectiontoWindowsupdate.Selectnow"Installfromalistorspecificlocation":

Page 9: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 9/86

Enter as source the folder "..\USB-Treiber-x86". Either in the folder where the downloadeddriverswereextractedorthedirectoryontheproductCD:

Themessageofwindowslogotestskipwith"ContinueAnyway":

Page 10: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 10/86

Aftercopyingthedataappearsalittlemomentlaterthesuccessmessage:

Uponasuccessfulinstallationthe"PI_Usb.Sysdriver"willbedisplayedwithoutanywarningsinthedevicemanager:

Page 11: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 11/86

Will this entry in the device manager shown with a "yellow exclamation mark", then pleaseinstallthedriveragainorlookinthedriverpropertiesaboutthereason.

Ifthedriverhastobeupdated,pleaseusethefunction"Update..."inthedriverproperties:

Ifthedriverhastobedeleted,pleaseusethefunction"Uninstall"inthedriverproperties:

Ifyou installolderversionsofPLCVCom,Step7-direct-driverorS7IFC, theactualusb-driverwillbepossibleoverwrittenbypreviousversionsbecauseitwasincludeduntil01/11/2012intheirinstall-shields!

Page 12: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 12/86

3.4USB-driver-installationforWin764-bit

The S7-Interface S7-USB, MPI-USB or MPI-II-Kabel over USB as well as the devices ofTeleService-familiywillbeconnectedtoUSB1.1-compatibleportofthePC.AfterthefirstplugofthedeviceWin7displaysthemessageNachdemerstenAnsteckenamPCmeldet Win7 zuerst „Installing device driver software“ and after some time „Device driversoftwarewasnotinstalled“.Thismessagescouldbeclosed.Pleasestartthewindowsdevicemanagerinthecontrolpanel.

Inthedevicemanagerwouldbethenewdeviceshownwithaexclamationmark:

Page 13: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 13/86

Witharightmouse-button-clickyouwillopenthepropertiesofthenewdevice:

Nowselect"UpdateDriver...":

Page 14: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 14/86

Pleaseselect"Browsemycomputerfordriversoftware"anddefineassourcethefolder"..\USB-Treiber-x64".EitherinthefolderwherethedownloadeddriverswereextractedorthedirectoryontheproductCD:

Afterpressing"Next"themessageappearsofwindowsUAC

Page 15: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 15/86

Pleasepressinstallandalittlemomentlaterappearsthesuccessmessage

Toverifythesuccessfulinstallation,youcanlookagaininthedevicemanager:

Page 16: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 16/86

Heremayappearnoexclamationmark!

If the driver has to be updated, please use the function "Update driver ..." in the driverproperties:

Page 17: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 17/86

If the driver has to be deleted, please use the function "Uninstall" and set the check-box in"Deletethedriversoftwareforthisdevice":

Ifyou installolderversionsofPLCVCom,Step7-direct-driverorS7IFC, theactualusb-driverwillbepossibleoverwrittenbypreviousversionsbecauseitwasincludeduntil01/11/2012intheirinstall-shields!

4Controlelements4.1Keys

Page 18: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 18/86

Key Name Description

ENTER Changemenuandconfirminput.

LEFT Goonemenulevelback.Cancelinput(Inputwillnotbesaved).

RIGHT Selectsubmenu.

UP Navigateupwards.Enhancementavalue.

DOWN Navigatedownwards.Depreciationavalue.

4.2Display

Firstline => #02PD00¯

Secondline => !02AG04°

Displaydescriptionfromlefttoright.

Firstline

#02=>InthisexampletherearetwoactivestationsontheMPI–BUS

PD=>letterdefinitionofthePC-baudrate.

Display DescriptionsPD 115,2korbaudrateidentificationisactive.PU USBconnectionP? Baudraterecognitionandaccesswayactive.TD 115,2korbaudraterecognitionisactive.(cableisconfiguredasTS–adapter)PG 19,2kTS 19,2k(cableisconfiguredasTS–adapter)Pg 38,4kTs 38,4k(cableisconfiguredasTS–adapter)pG 57,6ktS 57,6k(cableisconfiguredasTS–adapter)PM PPIMulti(187,5k)

Page 19: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 19/86

00=>thestationnumberoftheMPI–cable.(Defaultis„0“)

(In the system configuration click on „Set PG/PC interface“. In the following dialog click“properties”. Now you can change in the registry card “MPI” part “station-related” the“adress”ofthecable.)

(InthePG2000softwareyoucanfinditbyclickingon„Options“„Interfaces“.Closetothebottomofthedialogyoucanchangethe„localaddress“ofthecable.)

¯=>ifthissignappearsinthetopoftheline,yourcableiscommunicatingwiththePLC.

Ifthissignappearsinthebottomoftheline,yourcableiscommunicatingwiththecomputer.

SecondLine

!=>(Exclamationmark)specifiestheconnectiontypetothePLC.

Display Description! DirectlyconnectedtothePLC.? NotdirectlyconnectedtothePLC.!(inverse) DirectlyconnectedtothePLCwithpassiveunitofthePLC.?(inverse) NotdirectconnectedtothePLCwithpassiveunitofthePLC.

02=>isthestationnumberofaconnectedandactivePLCintheMPI-BUS.Every750milliseconds(a¾second)anotheruserwillbedisplayedifmore thenoneuserhasbeenfound.

AG=>Thetypeoftheprotocolwhichisusedforthecabletorunuptothecomputer.

Display Description

AG Unknownbecausethereisnoconnectionoranolderprotocolversion(before5.0)isused.

Ag v5.1ProtocolAg v5.0Protocol

04=>Showsthestationnumberofthedevice,whichisconnectedinthatmomentwiththecomputersoftware(inthisexamplestationnumber04).

Configurationspecificmessages:

Withthefollowingbaudratesettings,themenumessagechangesaccordingly:

Baudrate–configuration 1.line 2.linePPI9,6k–(PPISER96) PPISER96 ACTIVEPPI19,2k–(PPISER19) PPISER19 ACTIVEPPI187,5k–(PPIMulti) ???PM? ????PPILAN–(PPILAN) PPILAN ACTIVEPPIUSB–(PPIUSB) PPIUSB ACTIVESONDSER SONDSER 19,2kBaud8N1SONDUSB SONDUSB 38,2kBaud7E2

Description8N1:8=DatabitsN=Parity1=Stopbit

5Implementing

Page 20: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 20/86

Connectyourmoduleasdescribedinthechapter"Hardwareinstallation"tothePLCandtotheprogrammingdeviceortoyourcomputer.

If you want to respond to a PLC via the module you have to comply therequirementsasdescriptinthechapter"systemrequirements". Inaddition,pleasemakesurethatthemoduleisproperlyconnected

5.1FirstConfiguration

Key Display Description

#01P?!02AG

Take the cable and press the ? key. (Control elements see chapterControlelements)).

MENUConfig PresstheUp/Down-keytogettothe“Config”menuandpressenter.

ConfigMPI-BUS

Searchforthesubmenu“MPI-BUS”andgetinwithenter.

MPI/PPIBaudrate Tosetthebaudrateconfigurationpressenter.

MPI-BaudAuto

Navigatetotheentry“Auto”andconfirmyourselectionwithenter.

ConfigPG/PC

Go back to the “Config” menu and navigate down to the “PG/PC”menu.Pressenter.

PG/PCBaudrate PressEntertoconfigurethe"Baudrate".

PG-Baud

fromPCSearchfortheentry“fromPC”andconfirmwithenter

Thecableisnowreadytowork..Gobacktothemenu"message"toseethestatus.

5.2UsingthePLC-VCOM

(ThePLC-VCOMisonlyneededifyourmoduleisnotconnectedviathe9pinCOMporttothecomputer.ForproductswithUSB,Ethernetconnection,etc.,thePLC-VCOMisrequired)

Page 21: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 21/86

1.StartthePLC-VCOMapplication(Ifithasnotalreadystartedyet).

2.ClickinthemainwindowofthePLC-VCOM,inthestatusarea“configure”.Theconfigurationwizardwillstart.

3.Itlistsallthefoundmodules/cablesandtheadditionalinformation’ssuchasIPaddressandMACaddressofthemodule.

4.ChoosethedesiredMPIcableandclick„OK“togoon.

5.Iftheconnectionisestablishedthechosencableisshowninthesectionstateandontheleftsideyoucanseethestatusconnected.

6. It also displays, thePLC-VCOM the IP address for themodule and the IP addressof thecomputerwhichisconnectedtothemodule.

If you have any promlems with the use of PLC-VCOM software, go to thechapterPLC–VCOMandlookthereforoperatinginstructions.

5.3Programmingsoftwaretousewithdirectaccess

After you have adjusted and connected the PLC-VCOM or the programming adapter to theCOM-portonyourcomputer,youwillbeabletoconnectwithyourprogrammingsoftwaretothePLCandworkwithit.

Howyouhavetoadjustyourprogrammingsoftwareisdescribedinthefollowingpoints:

5.3.1PG2000fürS7(V5.10)

1.StartthePG2000softwarebyusingthedesktoplinkorbyusingtheapplicationentryinthestartmenu.

2.Choosefrom"View"=>"S7-300/400"

Inthemenu“Options“click“Interfaces“..

3.Adialogappears,inwhichyouareabletoset the “AG-Interface” (COM-port) in thesection“Interfaces”.

Page 22: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 22/86

4.Configurethebaudrateinthesection“Busaccess“ to “19,2k“. Below change the valueforPC-MPIto“187,5kBaud“.

5.Saveyourconfigurationbypressing“OK“.

6.Now the software is ready to establish aconnectiontothePLC

Click the symbol “Open“ and afterwardspress“PLC”.

Alternativeyoucanclick:„File“=>„Open“=>„PLC“

The connection between PG 2000 and thePLCisnowestablished.

A new window appears. Now you can edittheblocksinthePLC.

5.3.2PSetPG/PCinterface

Thisstepisrequiredforthefollowingsoftware:=>SIMATICStep©7Manager(v5.2+SP1)=>WindowsControlCenter(WinCC)(v6.0)=>WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)=>ProTool/Pro(v6.0+SP2)=>Microwin3.2

1.Open thesystemconfigurationbyusing thestartmenu.

2.Clickon„SetPG/PCinterface“.

3. A Dialog with a list box named

Page 23: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 23/86

“Interface Parameter Assignment Used:”appears.Thisboxshouldoffersome“PC-Adapter”entries

Ifthisisthecase,pleasecontinuewiththestepMPIsettingsorProfibussettings.

If you can't find these entries go aheadwith step PC-Adapter or TCP/IPinstallation.

5.3.2.1PC-Adapter(Auto,MPI,PROFIBUS)

4.Clickon„Choose“toaddtheseentriestothePG/PCinterfaceconfiguration

5.Inthisdialogyoucandeinstalleveryinstalledconstructionset

Furthermoreyoucanaddvariousmodules(see"Selection")

Choose„PC-Adapter“fromthe„Selection“boxontheleftsideandclickon„Install“.

6.Thechosenconstructionsetwillbe installedandaquestionappearswhichasksyoutousethe“MPI“accessforthePLCused.

Click“Yes“ifyouwanttousethe„MPI“communicationtype.

Otherwiseclick“No“(e.g.ifyouwanttousethe“PROFIBUS“communicationtype).

5.3.2.2TCP/IPRFC1006Communication

7.Press"Select"toaddtheRFC1006requiredelements to the PG / PC - interfaceconfiguration.

8.Inthedialog"Select",choose"TCP/IP"andclickon"Install".

9.Aftersuccessfulinstallation,click"Close".

Page 24: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 24/86

10.Backtothe“SetPG/PCinterface“dialogyouwillnowfindthedesiredentriescalled“PC-Adapter(Auto)“(notsupported),“PC-Adapter(MPI)“and“PC-Adapter(PROFIBUS)“.Nowyouareabletoconfigurethebus.

Ifyouwanttousethe“MPI“communicationtypegoaheadwithstepMPIsetting.

Thesettingsfor"PROFIBUS"isexplainedinProfibussetting.

5.3.2.3MPIsetting

11. Select "PC Adapter (MPI)" and click"Properties".

12.Openthepropertiesdialog

Choosetheregister"LocalConnection"

13.SetheretheCOMport.

14.Youalsochangethe"transferrate" to"19200".

15. In the register card “MPI“choose the“TransmissionRate”to“187,5kbit/s".

Changethe"HighestStationAddress"(HSA)to"126".

16.Acept your settingswith "OK" and exit the"PG/PCinterfacesetting"dialogwith"OK".

Page 25: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 25/86

5.3.2.4Profibussetting

17.Mark theentry „PC-Adapter(PROFIBUS)“andclickon„Properties“.

18. In the registry card “Localeconnection” you have to set the COMPort.

19. Set the "Transmission Rate" to"19200"

20.Choose the registrycard “PROFIBUS”and

Page 26: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 26/86

setthe“TransmissionRate”to“187,5kbit/s”.

21. Set the “Profile“ to “DP“ (“decentralizedPeripherals“).

22. Save your settings by clicking the“OK“buttonandclosetheopened“SetPG/PC-interface“dialog

5.3.2.5TCP/IPRFC1006setting

23.Forthiskindofcommunicationyouonlyhavetoinstallthecorrespondingsoftware.

5.3.2.6ProTool/ProRunTime(RT)Configuration

24.IfyouwanttouseProTool/ProRunTimeyoucanset the "PG/PC Interface"by selecting theentry "DPSONLINE". Therefore you have toselect "Access Point of Application" andconfigure it as described above. The easiestway is to use the S7-LAN/MPI-LAN/MPI-USB-driverwhichsupportsUSBandLANproducts.

Theinterfaceconfigurationfortheseprogramsisfinished.Continuewiththesoftwarewhichyouwanttouse:

=>SIMATICStep©7Manager(v5.2+SP1)=>WindowsControlCenter(WinCC)(v6.0)=>WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)=>ProTool/Pro(v6.0+SP2)=>Microwin3.2

5.3.3SIMATICStep©7Manager(v5.2+SP1)

ConfiguratetheinterfaceasdescribedinSetPD/PC-Interface.

1. Klick in the drop - down menu "target

Page 27: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 27/86

system"on"DisplayAccessibleNodes".

2. If youcansee the listwithpossibleBus-devices,acommunicationoverthecablehastaken place. "Direct" connected deviceswillbe shown, also the conditions if it is an"active"or"passive"assembly.

3.Inthiswindowyoucanediteachassemblywithhisblocks.

5.3.4WindowsControlCenter(WinCC)(v6.0)

ConfiguratetheinterfaceasdescribedinSetPD/PC-Interface.

1.StartWinCCbyusingthedesktoplinkortheprogramentryinthestartmenu.

2.Choose „New” in themenu „File” or click on the white („letter”) symbol to start a newproject.

3. The next dialog offers youseveral project types “Single-UserProject”, “Multi-User Project” and“ClientProject”.

The next steps are the describingforthe“Single-UserProject”.

4.“OK”leadsyoutoanewdialog.Typeinthe“ProjectName”andthe“Subfolder”oftheprojectpath.

Thechosenconfigurationisconfirmedwith“Create”.

To use one of the other options please go ahead and read in themanual ofWinCCsoftware.

5.Pleasewaituntiltheprojectiscreated.Theprojectcontentwillbeshownintheleftpartofthemainwindow.

6. For a proper workingcommunicationwiththePLCthere

Page 28: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 28/86

mustbedefinedhow the softwarehastocommunicatewiththePLC

Therefore you have to right-clickon“TagManagement”itopensthecontextmenu.Choose“NewDriverConnection…“.

7. In the „Add new driver“ dialogselect thedriverwhich fits to yourPLC

For a S7 PLC choose „SIMATICS7ProtocolSuite.chn“.

If you want to use an other PLCplease inform yourself first, whichdriverfitswithyourPLC.

It is very important that the selected driver fits with the PLC otherwise theconnectioncannotbeestablished..

8. You should see now in the Explorer under the branch “Tag Management” the branch“SIMATIC S7 PROTOCOL SUITE”. Expand the branch and many protocols for variouscompoundswillappear.

TheGeneralwayofproceedinganewconnectionisto:

Right-clickonthedesiredconnection(MPI->Picture:“MPI“,TCP/IP->Picture:“TCP/IP“).Acontextmenuopens.Clickon„NewDriverConnection…”.

ThismanualdescribestheconnectionconfigurationsforMPIandTCP/IP

MPI TCP/IP

Page 29: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 29/86

5.3.4.1MPIConfiguration

9.Nowyouareabletotypeinthename of the connection. With aclick on “Configuration“ a newdialog will appear. Now you areable to set the properties of theconnection.

Set up the station address of thePLC(inthisexample"2“).

Confirm with "OK" until you arebacktothemainwindow.

Read further "Communicationandfaultdiagnosis“.

5.3.4.2TCP/IPConfiguration

10. A dialog appears where youcan configure the connectionparameters.

Set up the IP - Address of themodule and configure the racknumberaswellastheslotnumber.

Confirm this configuration byclicking“OK”.

Exampleconfiguration:IP-address192.168.1.55Rack-Number:0Slot-Nr.:2

Page 30: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 30/86

11.Witharight-clickonthenewconnectionyoucanstartthepropertiesdialog.Inthisdialogpleaseclickonproperties.

12.Inthis“Channelunitproperties”you are able to see all “availableconnections”.

Choose the latest createdconnection and click again on„Properties”.

Nowyoucanseeall thevariableswhich has been created for thisconnection.

In fact this connection is a newconnectionso thereshouldnotbeanyvariableinthelist.

To add a new variable click on„New”.

13.Nowyouareabletosetupthenameofthevariableanddifferentmoreproperties.

Inourexample,weassignthefollowingvalues:

Name:„S7LAN_MW0“Datatype:„unsigned16-Bitvalue“Length:„2“Address:„MW0“Formatadaptation:„WordToUnsignedWord“

Clickon„Choose”besidetheAddresstodefinetheaddressfromthevariable.Exampleconfiguration:Thedataareafromthevariableissetto„Mark“andtheaddressissetto„Word”.Theeditbox„MW“issetto„0”.

14.Confirmallopendialogswith„OK“untilyoureachthemainwindow.

15.Theconnectionneedstoknowwhichnetworkinterfacecarditshouldbeusedtosenddata via theEthernet.Open the “Systemparameters“dialog from the contextmenu (right-

Page 31: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 31/86

clickonTCP/IP).

16.Choosefromtheregistrycard„Unit“andsetthe“logicaldevicename“toyournetworkinterfacecard(usuallythenameoftheNICbeginswitha„TCP/IP->„).

17.Confirmwith„OK“.

18.Nowyouareabletostart thecommunication.Stopitbyclickingon .

5.3.4.3Communicationandfaultdiagnosis

TocleanuperrorsfastertheWinCCSoftwareoffersatoolnamed"ChannelDiagnosis”.Thistool analyses all connections from your WinCC software. For demonstration purposespleasestopthelaststartedconnectionfromyourWinCCexplorer.

19.Startthesoftware"ChannelDiagnosis“byusingyourlinkinthestartmenu.

20. The tool could not detect arunning connection so it markedthe connection/s with a red ‘X’(registry card"Channels/Connections“).

Clickonthelastcreated,notactiveconnection (with the red ‘X’) andsome informations from theconnectionwill appear in the rightpartofthedialog.

One of these counters is called"LastErrorCode“.

21. If you takea right-clickon theerror value a window opens with“Help”.

Click on the “Help”window and ayellow window appears (tooltip)withdetailederrordescriptions.

22. Lets see what happens if theconnectionrunsproperly.Start theconnection from your WinCCExplorer.

The "Channel Diagnosis“dialogmarkstheconnectionwithagreenhookifeverythingworkedout.

Page 32: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 32/86

5.3.5WindowsControlCenterflexible2004(WinCCflexible)(v5.2.0.0)

PleasemakesurethattheinterfaceconfigurationiscorrectasdescribedinPD/PC-Setinterface

1.StarttheWinCCflexible2004softwarebyusingthedesktoplinkortheprogramentryinthestartmenu.

2.Firstyouneedtoselect“Createanemptyproject”onyourfirstpage.

3. In the "Device selection“mark the usedoperatorpanel(example:"TP170A“)

confirmwith"OK“.

4.After theprojecthasbeencreated right-clickintheprojectwindowon“Connections“ofthesubmenu“Communication“.

Inthecontextmenuclickon“AddConnection“.

5.Anewconfigurationwindow“Connections”opens in therightpartof themainwindow.Thisoffersyoudifferentsettingoptions.

Importantfortheconnectionis:

=> the communication driver (set up which PLC you are using (example: "SIMATIC S7300/400“))=>theBaudrate(Setthison"187500")=>theaddressoftheterminal(HMI)(inthisexample"1“)=>theProfile("MPI“forexample)=>theHighestStationAddress(HSA)(e.g."126“)=>theaddressofthePLC(e.g."2“)

Page 33: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 33/86

6.Nowyoucanstartwithyourwork.

If you have finished work you can transferthisproject to thepanelby reading thenextsteps.

7. Choose „Transfer Settings“ from the submenu„Transfer”.

8. In the new dialog change the „Mode“ to „MPI/DP“ and set the „Station address“ of theoperatorpanel(e.g.„1“).Ifdesiredyoucanswitchthe„Deltatransfer“to„On”(inthisexamplewesetit„Off”).

9.Pressthebutton„Transfer“tostartcommunicationwiththeterminal.Yourprojectisabouttobetransferred.

TheWinCCflexiblesoftwareisnowabletocommunicatewithyouroperatorpanel.

5.3.6ProTool/Prov6.0SP2

PleasebesurethattheinterfaceconfigurationiscorrectasdescribedinPD/PC-setinterface

Page 34: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 34/86

1.StartProTool/Probyusingthedesktoplinkorprogramentryinthestartmenu.

2.Choosefromthemenu„File“thesubmenu„New“orclickontherightsymbol.

3. The next dialog askes you which operatorpanelyouareusing.

Marktheusedpanel(e.g.„TP170A“)

4.„Next“leadsyoutoanewdialog.Typeinthespecfic fields thenameof thePLCdeviceandchoose the used PLC in the driver selection(e.g.„SIMATICS7–300/400V6.0“).

5. Via „Parameter...“ you are calling anconfigurationdialogfromthechosenPLCdriver

Setupthestationaddressofthepanel(example„1“)andofthePLC(example„2“).

Leave the point "Interface" in the standardconfiguration. In the sector „Net parameter“choose the interfacewhichusesyourmoduleonthePLC (e.g. „MPI“).Configure thebaud rate to„187.5“.

6. The button „More ...“ leads you to a smalldialogwherethe„HighestStationAddress“shouldbe configured to „126“. Set up the „Number ofmasters“(e.g.„1“)

7.confirmwith„OK“untilyougotbacktothe„ControlSelection“.Goonwith„Next“.

8.InthemainwindowstarttheTransferSettingsdialogbyclickingon„File“„Transfer“„Settings...“.Choose„MPI/PROFIBUSDP“fromthelistboxandtypeinthestationaddressoftheoperatorpanel(e.g.„1“).

Confirmwith„OK“.

andstartwithyourwork

Ifyouhavefinishedworkingonthisprojectyoucangoonwiththenextsteps.

9.Ifyouwanttotransferyouprojecttothepanelyouhavetogeneratetheprojectfirst.Thiscanbedonewithaclickon„File“-„Compile“.

Page 35: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 35/86

10. To transfer the project just click on „File“„Download“„StartProjectDownload“orclickon

therightsymbol .

Pleasewaitwhiletheprojectistransferred.

Thecommunicationbetweentheoperatorpanelisnowestablished.

5.3.7Microwinv3.2(onlyforS7200)

PleasebesurethattheinterfaceconfigurationiscorrectasdescribedinPD/PC-setinterface

1.StartMicrowinusingthedesktoplinkorprogramentryintheStartmenu.

2.Clickon„Type“inthemenu„PLC

Configurethe„PLCType“(e.g.„CPU224“)aswellasthe„CPUVersion“(e.g.„01.22”)tothedialog.

Page 36: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 36/86

3.Clickon„Communications...”tostartthenextdialog.

Inthesector„Address”setupthe„Remote”listboxwiththestationaddressofthePLC(e.g.„2”).

If you skipped the point b („ PD/PC-set interface“) you can configure the PG/PCinterfacewithaclickon„SetPG/PCinterface“.

4.Intherightpartofthedialogdoubleclickonthebluearrow symboltotestthecommunicationwiththePLC.

5.Thesector„Address“shouldbeupdatedanddisplaysthe„PLCType”.AlsotheCPUofthePLCisdisplayedintherightpartofthedialog.

Page 37: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 37/86

6.Confirmwith„OK“untilyougetbacktothemainwindow.

ThecommunicationwiththePLCistnowestablished.

5.3.8Microwinv4.0inPPI-Multimaster-Mode

1.ThePPI-Multimaster-Modewasdevelopedthatmoredevices can communicate parallel with one PLC. Thefollowingstepsdescribehowtoconfigure thismode inhardwareandsoftware.

2.ThemoduleorcablehastoswitchedinthePPIMulti-Mode. This mode can be switched in the menu-treeunder„Generally“and„Bootconfiguration“

3. There you have to select „PPIMMaster“ andconfirmedwith„Saving“.For LAN-devices you can do this in the integratedWebServer,also.

4. Now, you have to configure the PG/PC - Interface.ThiscouldyoualsodowithintheMicrowin-Software.

5.StartyourMicrowin-Software.

6. Click on the button „Set PG/PC-Interface“ under„View“intheleftdownpartofthewindow.

7.Selecttheentry„PC/PPIcable(PPI)“andclickonthebutton„Properties“.

8. In the menu „PPI“ you are able to configurediversesettingslikefore.g.“HSA“.

9.Inthemenu“LocalConnection“youselectthecom-port“Interface to“ to theportwhich is served from thetoolPLCVCom.

10.Clickon thebutton “OK“andclick in the leftdownareainyourwindowson„Communikations“.

Page 38: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 38/86

11.Clickdoubleon“Double-Clicktorefresh“.ThePLCswouldbesearched.

12.WhenthePLCwasfound,thepicturechangesitlikethis:

Page 39: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 39/86

13.Provethedialogwith„OK“untilyouwouldbeinthemainwindow.

ThecommunicationtothePLCisnowready.

5.3.9S7forWindowsv5.02

1. Start the „S7 for Windows” software byusingthelinkonyourdesktoporusethelinkinyourstartmenu(standardis„Programs\S7forWindows\S7forWindows“)

2.ChooseFile->Preferences... toconfigurethecommunicationconfigurationbetweenthecomputerandthePLC.

Anewdialog appearswhich provides to setup a lot of configuration data about thecommunicationwithyourPLC.

Page 40: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 40/86

3.Choose the first registry card „Interface“ (standard) and set up the configurationdataasdescripedbelow:

=>Area:„Preferencesfrom:“=>PC=>Area:„PLCType:“=>S7=>Area:„Protocol:“=>MPI-Umsetzer=>Area: „SerialPort:“=>Choose thevirtualCOMportwhichhasbeencreatedbyPLC-VCom(e.g.„COM4”).=> Area: „Baud Rate“ => Choose the speed you want to use at the bus (e.g.„115200“)=>Area:„MPIConverter:“

-Activate the checkbox „OnlyMaster at theBus“ if youhaveonlyonePLCinthebus.-Leavethefields„S7WMPIAddress“and„MPIAddressPLC“asitis.-Thenumberinthelistbox„MaxMPIAddress“mustbehigherthanthePLCwith thehigheststationaddress inyourMPIbus.OtherwiseeveryPLCwhichishigherthanthisnumberwillnotbeenseen(e.g.ifthereisonlyonePLCinyourbus„15“ismorethanenough).

4. After the software is configured , please click „Select PLC” in the area „MPIConverter“.AnewdialogappearswhereyoucanselectthedesiredPLC

5. The dialog displays all the PLCsthatcanbefoundinyourMPIbus.

Select the desired one and confirmwith„OK”.

6. Close the preferences dialog bypressingthe„OK“button.

Page 41: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 41/86

7. Back in the main window press the „PCBlock List“ button for testing the newestablishedcommunicationconfiguration.

8.Pleasewaitamoment for thesoftware toread the desired blocks from the PLC. Theblockswill be displayed in the listbox belowthemenubar(seepicturetotheright).

ThecommunicationbetweenthesoftwareandyourPLCisestablished.

5.4ConfigureoperatingterminalviaMPI-II/MPI-USB

Note:TheTP070andOP73canbeconfiguredviatheRS485withtheMPI-II/MPI-USB.

Key Display Name

#01P?!02AG

Take the cable and press the Enter – Key . (Control elements seechapter).

MENUConfig

NavigatewiththeUp/Down–KeysuntilyoureachtheMenu“Config”.PressEnter.

ConfigMode Searchforthesubmenu„Mode“.PressEnter

ModeSONDUSB

PresstheEnterkeytoconfigurethenewmode.

ConfigPD/PC

NavigateintheConfigmenuto"PG/PC".PresstheEnterkey.

Page 42: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 42/86

PD/PCBaudrate PressEntertoconfigurethe"baudrate"to38.4k.

PG/PCparity PressdownonceandpressEntertosetthethe"parity"toNone.

PG/PCStopbit Pressdownonceandpressentertoconfigurethe"StopBits"to1.

PG/PCDatabit Pressdownonceandpressentertoconfigurethe"bits"to8.

Justgetbacktothe“Message”menutoseethestatus.

ThisshouldnowdisplaySNDUSBinthefirstlineand38k4N81inthesecondline.

The MPI-II / MPI-USB cable has been adjusted for the configuration of the operatingterminal. The configuration of the operating terminal, please refer to the manufacturer'sinstructions.

5.4.1DirectsettingofaslaveaddresstoapassiveProfibus-Slave

With the S7-LAN-module or MPI-LAN-cable and Step7-direct-driver V1.21 (or later) and theMPI-II-cable(onlywithUSB)orS7-USBandStep7-direct-driverV1.22(orlater)isitpossibletogiveadirectlyconnectedProfibus-Slaveabus-address.Importanthere isthatthesubscriber isconnecteddirectlytotheS7-interfaceandtheexternalsupplyof24VDCisalsoconnected. IntheStep7-direct-drivermustthen in thepropertiessetthat"PD/PCisonlymaster".Thereisnoanothernoteinthiscase,youwillusethisfunctionasifyouareconnectedwithyourPDtothemodule.

6Configuration6.1KeysandDisplay

Themenumessage is explained in the chapter "Control elements" Further isassumed,thatyouareclosetothehandlingwiththeMPI-LANcable.Ifthisnotthecase,pleasegobacktothechapter"Controlelements".

6.1.1GraphicalDescription

Withenteryouwillgetinthemenuofthecable.Thismenuhasthefollowingstructure:

Page 43: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 43/86

MENUMessage

MENUConfig

MENUBus

MENUInfo

Standarddisplay(Status)

Configuration BUSdisplay Cable

information

ConfigMode

BusAddress

InfoVersion

CableMode BusAddress

OperatingSystemVersion

ConfigPassword

Configurationspassword

ConfigReset

Cablereset

ConfigSetDef.

Settheconfigurationtodefault

ConfigLanguage

Language

ConfigProtocol

Protocolwhichisusedonthebus

ConfigPD/PC

PDinterfacesettings

ConfigMPI-BUS

MPIinterfacesettings

ConfigUSBCurrent

Changethecurrentofthecable

ConfigData

Un-/locksconfigurationsendby

Page 44: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 44/86

thecomputer

6.1.2Config

oModeoPasswordoResetoDefaultsettingsoLanguageoProtocoloPD/PCoMPI-BUSoUSBCurrentoData

•Mode:

Choosethismenutoconfigurethecablemode.

mode meaningMPISER MPI-communicationoverRS232-interfaceMPIUSB MPI-communicationwithPLCVCom/Step7-driveroverUSB-interfacePPI9K6 PPI-communicationwith9600baudoverRS232-interfacePPI19K2 PPI-communicationwith19200baudoverRS232-interface

PPIUSB96 PPI-communication only with PLCVCom and 9600 baud over USB-interface

SPECSER Specialmode RS232 (complies RS232-RS485-converter, interface-parametermustbeseparatelyparameterized)

SPECUSB Specialmode USB (complies RS232-RS485-converter with PLCVCom,interface-parametermustbeseparatelyparameterized)

PPIUSB19 PPI-communication only with PLCVCom and 19200 baud over USB-interface

PPIMulti PPI-communication (MultiMaster 9K6 - 187,5K) over RS232- or USB-interface(withPLCVCom)

HINT: „MPI SER“, „SONDSER“, „PPI 19K2“ and „PPI 9K6“ doesn't fit with theMPI-USBcable(Ord.No.9352USB).

•Password:

Choosethismenutochangetheconfigurationpassword.(Standard:„0“)

•Reset:

Thecablereset.

•Defaultsettings:

Presstheenter-keytochangethecableconfigurationtodefault.

•Language:

Inthismenuyoucanchoosethelanguageofyourchoice.Choosebetween„German“and„English“.

•Protocol:

Changetheprotocolversion.

Choose„Auto“ifyouwantthatthecabletakestheconfigurationfromthePG.

If you experience any trouble on the bus with the protocol version „V 5.1“ set theconfiguration to „V5.0 Old“. The 5.0 version is more stable but slower than the „V 5.1“protocolversion.

•PD/PC:

Page 45: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 45/86

In thismenuyoucanchange theconnectionspeedbetween theprogrammingdeviceandthecomputer.

ThisworksonlybyusingaMPI–II(Ord.No.9352)cablewiththeserialdeviceconnectedtothecomputer.

Availablebaudrates:„2400“,„4800“,„9.6k“,„19.2k“,„38.4k“,„57.6k“,„115.2k“.

IfyouareusingthecabletakesthePDconfiguration.

•MPI-BUS:

Youhavetochoosebetweenthesesubmenus.

-Baudrate-Master-lokalNo-HSA

-Baudrate

ChangethespeedoftheMPI-Bus.

Availablebaudrates:„Auto“,„19,2k“,„45,45k“,„93,75k“,„187,5k“,„500k“,„1,5M“,„3M“,„6M“,„12M“

HINT: Thebaud rates„3M“, „6M“ and „12M“ can only be configured by cable.Thesehigherbaudrates(from“3M“)willbeoverwrittenbythePC.Togetsurethatthiswillnothappenconfigure(inthecablesmenu)„Lock“inthesubmenu„Data“.(Thissubmenuisalsodescribedatthebottomofthenextpage)

-Master

Inthecasethatthecableisconnectedwithonlyonepassivestation,configure„Master“tothecabletodeterminethatthecableisconfiguringitself.Inallothercasespleaseconfigure„Multimaster“tothecable

-lokalno.

Tochangethestationnumberofthecable.Hexadecimalvaluesof„00“to„7E“arepossible.

-HSA

HSAstandsfor“HighestStationAddress”.ConfigurethehigheststationnumbertothecablewhichisconnectedtotheMPIbus.Possiblevalues:„15“,„31“,„63“,„126“.

Thesetting„fromPC“means,thatthecabletakesthesettingsfromthePC.(IftheHSAhigh,theperformanceislow!)

•USBCurrent:

WhenconnectingthecablewiththeUSBinterfacefromthePCthecabletellsthePChowmuchpowerittakes.Withthismenuyoucanchangethisconfiguration(inspecialcases).

000mA=>OnlyforMPI-II.BecausethiscabletakeitspoweroutofthePLC.

360mA=>Defaultvalue.ThecabletakespoweroutoftheUSBinterface.

Some computers are blocking the drivers for the communication if the USBHUB cannotprovideenoughpower.

HINT:InanycasetheMPI-USBcabletakes360mA.ChangetheUSBcurrentonyourownrisk.(TheUSBdeviceofyourPCcanbeoverloaded!)

•Data

Changeto„Lock“ifyouwantthatconfigurationdatacomingofthecomputerwillbeignored

Page 46: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 46/86

(onlyimportantifyouareusing„3M“orhigherbaudrates

ThemaximumbaudrateofthePCdriverisusedifyou„Unlock“thisoption.

6.1.3Bus

Select themenu „Bus“ to choose, by pressing theEnter –Key, the submenu „Address“.WiththeUp/Down–Keysyoucandisplaytheconnectedstations.

Themenu„Address“:AddressDA020

Thelettersinthesecondlinearedescribingthestation:

Letter Description

D TheMPIcableisdirectlyconnectedtothePLC.

A Thisstationisactiveinthebus.

P This station is passive in the bus, for e.g. some OP’s, FM –blocksalsoMPIBus–Slaves.

6.1.4Info

Select themenu„Info“ tochoose,bypressing theEnter-Key, thesubmenu„Version“Thismenushowsyoutheoperatingsystemversionofthecable.

7S7-InterfaceConfiguratorHelpLanguageselectionUserinterfaceBusconfigurationNetworksettingsParameterizeTELEServiceIndex"Network"Index"Modem"Index"SerialParameter"Index"AccessProtection"Index"GSM/ISDN/SMS"Index"Internet/Mail"TuningFactorydefaultsPPIBootoffEmergency-Loader7.1Languageselection:

SelectthemenuConfigurationtochangethelanguagepermanently:

7.2Userinterface:

Page 47: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 47/86

SelectnearSearchwhichinterfacesaresearchedpermanentlyfordevices.Youcouldchoose:

•Serial AllexistingCOM-Portsarescannedfordevices•USB SearchdeviceswhichareconnectedbyUSB•LAN Searchdevicesonallnetwork-cards

ThebuttonSearchstartsaparallelsearchonallselectedinterfaces.AfterselectingaupdateabledevicethebuttonUpdategetsavailable.

Belowthebuttonsisalistofthefounddevices.Ineachlineanimage,thetypeofthedevice,name (if existing), interface, serial number (if possible) and the OS-version of the device isdisplayed.OntherightmostpositiontheactualOS-versionontheharddiskisdisplayed.

Thebackgroundofthelinescouldusethefollowingcolours:

•White TheOSofthedeviceisup-to-date•Lightblue TheOSofthedeviceisnotup-to-date,thedevicecouldbeupdated•Red Anerroroccuredbyaccessingthedevice•Yellow Updateisinprogressforthisdevice•Darkblue Selecteddevice

Double click onto a devicewhich could be updated shows the version-documentation of thedevice(onlyavailableinGerman):

Page 48: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 48/86

ThebuttonUpdatewithFDupdatestheOSofthedeviceandsetsthefactorydefault.

ThebuttonBootstrapsetsthefirmware/configurationtofactorydefault.

ThebuttonFactorydefaultssetstheconfigurationtofactorydefault.

ThebuttonParameterizeactivatesadialogregardingtothedevice:

Overview:

Device DialogTELEServiceMPI/PPI-Profibusmodem ParameterizeTELEService

MPI/PPI ParameterizeTELEService

MPI-IIMPI-USB

Choices:BusconfigurationParameterizeTELEService

S7-USB Busconfiguration

S7-LANMPI-LAN

Choices:BusconfigurationNetworksettings

ThebuttonPPIBootoffdisablesthePPIbootoptionofaserialconnecteddevice.

The buttonEmergency-Loader tries to repair LAN products which are in emergency-loadermode.

ThebuttonTuningactivatesadialogforspecialparameters.

ThebuttonExitleavestheapplication.

7.3Busconfiguration

Toparameterizetheconnectiontothedevice,selectadeviceandclick"Parameterize".

Page 49: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 49/86

Regarding to the device you maybe have to click on the button Bus configuration (seeparameterizetable).

Hereyoucanparameterizethefollowing:

UsebusconfigforPC TooksthebusconfigurationfromthePC

Baudrate choosestheBautrateforthecabletobuscommunication

Higheststationaddress

Thehigheststation-addressinthebus(thelessyouuse,themoreperformanceontheMPI-bus,mustbecorrespondingwiththeconfigurationintheCPU’s)

PD/PCistheonlymasteronthebus

TheTS-AdapteristheoneandonlymasterintheMPI-bus(adapterhasttospeaktoallpassiveclients)

Profile BustypeoftheconnectionLocalclientaddress Whichlocalstation-addressisusedfortheTS-Adapter.

Page 50: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 50/86

Pleaseconsiderthataprogrammingdevicehasnormallythenumber0,operatorpanelhave1,CPU’suse2,FM/CP’s3etc.Please:Neverusethesamestation-numberfor2differentstations!

Protocoltype ProtocoltypeoftheconnectionBootsettings Bootsettingoftheconnection

7.4Networksettings

Hereyoucansetthenetworkconfigurationoftheselecteddevice:

•Factorydefault This button sets all over the network reachable devices to factorydefault.

•DHCP-clientactive WhensetthedeviceactsasDHCP-client.

•IPaddress HereyoucouldentertheIPAddressoverwhichthedeviceisaccessedinthenetwork.

•Subnetmask HereyoucouldentertheSubnetmaskofyournetwork.

•Gatewayaddress Hereyoucouldenter the IPaddressofyourGateway.Usualarouteraddress.

•Devicename Hereyoucouldchangethedevicename.

Factorydefault:•DHCP-clientactive notset•IPAddress 192.168.1.56•Subnetmask 255.255.255.0•Gatewayaddress 0.0.0.0•Devicename empty

7.5ParameterizeTELEService

Toparameterizethedevice,firstclickonthedevice,afterthaton"Parameterize".

Page 51: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 51/86

Regardingtothedevice,youmaybehavetoclickontheTELEServicebutton.

Afterclickingon"TELEService"amessagewillshowup:

DependingontheversionofyourTELEServicesoftwarechooseYesorNo.

Theregularparameterscanbechangedmanuallyinthefollowingcategories:

7.5.1Index"Network":

Hereyoucanconfiguratefollowing:

Page 52: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 52/86

Stationrelated:

PD/PCistheonlymasteronthebus

TheTS-AdapteristheonlymasterontheMPI-bus(adaptermustspeaktoallpassiveclients)

Address

Whichlocalstation-addressisusedfortheTS-Adapter.Pleaseconsiderthataprogrammingdevicehasnormallythenumber0,operatorpanelhave1,CPU’suse2,FM/CP’s3etc.Remind:Neverusethesamestation-numberfor2differentstations!

Networkrelated:

Networktype ThenetworktypeMPIorPROFIBUSTransmissionrate ThetransmissionspeedontheMPIbusCurrenttransferrate Showsthecurrenttransferrateofthedevice

HigheststationaddressThehigheststationaddressinthebus(thelessyouuse,themoreperformanceontheMPIbus,mustbecorrespondingwiththeconfigurationinthePLC’s)

7.5.2Index"Modem":

Inthisdialogyoucouldconfigurethemodemrelatedsetup.

Page 53: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 53/86

ModemSettings:

Initialization

AT startcommand&F usefactorysettingsE0 echooffL1 volumeofspeakerislowM1 speakerisonatconnectionQ0 outputofthereturnvaluesV1 returnvaluesplaintext&C1 DCDshowsstatusofthecarriersoundS0=1 automaticconnectionafter1ring

Hangup+++ SwitchtocommandmodeAT startcommandH Hangupconnection

Location:

Thephonesystemuses

Therearetwopossiblecalltechniques:MFVtone,thetelephonenumberistransferedbyseveralfrequenciesIWVpulse,thetelephonenumberistransferedwiththeamountofseveralpulsesontheline

Toaccessanoutsideline,firstdial

Ifyouneedaprefixbeforeyournumbertoestablishacalloutside,youmustentertheprefixheree.g.0.

CallPreferences:

Waitfordialtonebeforedialing

Incasethemodemshouldwaitforafreeline,youshouldsetthecorrespondingcheckbox.

Numberofredialattempts

Atnumberofretriesyoucouldconfigurethenumberofretriesforaconnectionbeforethecallisstopped.

Redialafter Usingaretryyoucouldenterthesecondstheapplicationshouldwaitbetweencalls.

7.5.3Index"Serialparameter":

Page 54: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 54/86

InthisdialogthetransferratebetweenmodemandTS-Adapterisselected.

ConnectionPreferences:

Transferrate Thetransfer-ratecouldchoosenbetweenthefollwingvalues:2400,4800,9600,19.2k,38.4k,57.6kand115.2kBaud

Parity

Theparitycouldbechoosen,butthisismodemdependendbecausesomemodemscouldnothandletheparitybit:None:(Thereisnoparitytesting)Odd:(Theamountofbitssetto1isodd)Even:(Theamountofbitssetto1iseven)

7.5.4Index"AccessProtection":

Theaccessoveratelephonelinecouldbeconfiguredinthisdialog.

AccessProtection:

Theadministratorcanchangetheconfigurationoveratelephoneline.Thetwouseraccountscannotchangetheconfiguration.Theusernameismaximal8characterslong.Everyuserandtheadministratorshoulduseapasswordwhichisusedtologininthe

TELEServiceoveratelephone-line.Afterthreefailedretriestheconnectionishangedup,soyoumustcallagain(notlikethe

originalTS-adapter).Afterchangingthepasswordforauser/administratoryoumustre-typeitagaincorrectly.YoucanenteracallbacknumberwhichisusedforacallbackfromtheTS-adapter.After

youdialedthenumberoftheTS-adapter,youareaskedforusernameandpassword.Incasetheusernameandpasswordisvalid,theconnectionishangupandtheTS-adaptercallsbacktheconfiguredcallbacknumber.7.5.5Index"GSM/ISDN/SMS":

Informationaboutthethreedifferentdevices:

AnalogModem::

Page 55: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 55/86

Type Youcouldchoosethelocationofthemodem.

ISDNModem:

Type

ChoosethetypeoftheISDNnetwork:AT&T5ESSNothernTelecomDMS-100EuroISDNNET3(Standard)INS64USNI-1VN4

Protocol

Choosethetransferprotocoltype:ModemlikeV.120X.75(Standard)ML-PPPSoftBondingHDLCCLEAR

MSN MultipleSubscriberNumberisusedforallISDNchannels.IfemptynoMSNisused.

GSMModem:

Page 56: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 56/86

PIN PINnumberoftheSIMcard,uptoeightnumericcharacters(onlyforTELE-SERVICEGSM).

Provider

Withthebutton„Provider“theprovidercouldbechoosen.Readthelistofproviderscouldbeelapsemorethanaminute.Intheendthepossibleproviderarelistedforselection.With„Automatic“the

GSM-Modemtriestoconnectautomaticallytoaprovider.Ontherightsideofthebutton,theactualusedselectionisdisplayed.DisplayDescription:

Automatic:TheproviderisautomaticallysearchedandselectedfromtheGSM-modem.

Manual:TheProviderisselectedmanuallyfromtheGSM-Modemnonetworkregistered:NoconnectiontotheGSM-network,thereceive-

qualityistoobadsetformat:TheformatoftheproviderissetManual/automatic:Themodemtriestoselectmanuallytheprovider,ifthis

failsanautomaticsearchisdoneunknown:UnknownresponsefromGSM-Modem

Refresh

Thebutton„Refresh“readsthesignalstrengthfromthemodem,thequalityisdisplayed.DisplayDescription:

Unknown:UnknownstateoftheGSM-networknoregistration:ThemodemisnotregisteredintheGSMnetwork,no

providerfoundregistrationdenied:RegistrationintheGSM-networkisdeniedSearchnetwork:InSearchforaGSM-ProviderGSM:AttachedtoGSMGSM(ROAMING):AttachedtoGSM,butwithaRoaming-Partner.Thiscould

leadtohighcosts!Theradioqualityisdisplayed,togetherwiththebit-error-rate.ValueDescription:

99Nonetwork,noreceive00Very,verybadreceive-quality01Verybadreceive-quality02to09Badreceive-quality10to17Mediumreceive-quality18to25Normalreceive-quality26to30Goodreceive-quality31Bestreceive-quality

InformationabouttherestoftheIndexGSM/ISDN/SMS:

Page 57: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 57/86

SMS:

SMS

Switches:NOSENDSMSRECEIVESMSSEND+RECEIVESMSDMTFCONFIRMATIONSENDSMS+DTMFCONFIRMATIONRECEIVESMS+DTMFCONFIRMATIONSEND+RECEIVE+DTMFCONFIRMATIONSENDMAILSENDMAIL+SENDSMSSENDMAIL+RECEIVESMSSENDMAIL+SEND+RECEIVESMSSENDMAIL+DTMFCONFIRMATIONSENDMAIL+SENDSMS+DTMFCONFIRMATIONSENDMAIL+RECEIVESMS+DTMFQUITTUNGSENDMAIL+SEND+RECEIVE+DTMFCONFIRMATION

Attention:beforesettingONcheckconfiguration,afteractivatingthedevicewillgoontheMPIbusandtriestoconnecttothedefinedPLC.ReceiveofSMSonlywithTELEService-GSMReceiveofDTMFonlywithTELEServiceGSM

BusaddressTS localstationaddress(shouldnotbeusedtwiceintheMPI/Profibus!)

BusaddressCPU fromthisstationaddresstheflagwordanddatablockisaccessedforcommunication

Communicationflagword

communication-flagword(thefirstbyteisthecommand,thesecondisthestate).Useevenoperand-addresses.

Page 58: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 58/86

Communicationdatablock

AddressoftheCPUintheBus

Provider0/1/2/3

ConfiguretheSMS-Providertouse,includingtype,phone-numberandchar-code.

1.FirstInput:Chooseatypeofthetransmission.2.SecondInput:Telephonenumberoremailaddress.3.ThirdInput:Chooseacharacterencoding.

NTP-Server InputforanNetworkTimeProtocoll-Server

Erroranalysis::

Thepossibleerrorconditionsforthemodem,mpibusproblemsorotherproblemsaredisplayedinthistext-field.Firstthemodem-relatedinformationisshown:

MessageModemreadyModemerrorNoanswerfrommodemModemdetectsringEndofconnectionconnectedviamodemlineNodialtonedetectedPhone-lineortelephonebusyPhone-numberisblacklistedinmodemPhone-numberdelayed.Accessdeniedfor1minute.Fax-calldetectedData-calldetectedunknownerrorTheselecteddirect-access-numbernotconfiguredTheconfiguredPIN-NumberiswrongfortheinsertedSIM-CardTheSIM-CardisnotorwronginsertedortheSIM-Cardisa5VType

PossibleMPI-Buserror-messagesMPI/Profibus-ConfigurationerroneousTimeoutatMPI/Profibusdetachfromdevice.Thelocalstation-addressisusedtwiceintheMPI/Profibus.A20/M20/TC35ModemoperationTheMPI/ProfibusisnotcorrectlyconfiguredTheHSAisnotconfiguredoptimalTheMPI/Profibus-BaudrateisnotdetectableOverflowintheinternalMPI-ReadbufferOverflowintheinternalLAN-ReadbufferOverflowintheserialBufferTheselectedMPI/Profibus-BaudrateiswrongOverflowininternalLAN-WritebufferLAN-Recieve-ErrorLAN-Send-ErrorThePD-NumberriswrongThetransferredSAPiswrong/unknownErrCode01:TheDestinationaddress(XXX)ofaStateprotocol>127detected.Inthe

MPI/Profibus-Bustherearenostationspossiblewhichstationnumberisgreaterthan127.(FC=YYh)

ErrCode02:Atstate-protocoltheSource-Addressisdetectedas127.ThisistheBroadcast-addresswhichisnotpossible.

ErrCode03:ThereceivedStateprotocolsdestinationaddress(XXXrespectivelyYYY)doesnotexistintheMPI-Bus.(FC=ZZh)

ErrCode04:Thefunction-code(YYh)ofthereceivedStateprotocolfromXXXisincorrect.The7thBitisHigh,butaccordingtothespecificationtheBithastobelow.

ErrCode05:AStateprotocolhasbeenreceived.Butthefunction-code(YYh)meansthattheparticipantisnotreadytoenterthebus.

ErrCode06:Thefunction-codeintheState-protocolreceivedfromXXXisunknown(FC=YYh)

ErrCode11:Thesender(XXX)ofthereceiveddata-protocolisunknown.TosenddatatheparticipantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)

ErrCode12:Data-protocolwithSource-address255(Broadcast)isuseless.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

Page 59: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 59/86

ErrCode13:Thesender(XXX)ofthereceiveddata-protocolisunknown.TosenddatatheparticipantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)

ErrCode14:The7thBitofthefunction-codeisHigh,butaccordingtothespecificationtheBithastobelow.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode15:Theupper4BitoftheFunction-codearewrong/unknown)(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode16:Unknownfunction-codehasbeentransmittedtothecable.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode17:Destination-SAParedefinedtill3Fhindata-protocols.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode18:Source-SAParedefinedtill3Fhindata-protocols.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode19:Receivedadata-protocolwithdestination-SAP=0,Connectionrequestfromanotherbus-participantwithourcable.(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)

ErrCode1A:Participantsaresendingdatatoourcablewithsource-SAP=0,whichmeansthattheparticipanthasnotmadeaconnectionestablishmentorhaslostthenegotiatedSAP.(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)

ErrCode1B:Data-protocolwithunknowndata-function-codereceived.(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)

ErrCode1CData-protocolwithunknowndata-function-codereceived.(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)

ErrCode1D:Receivedastate-protocolwitherror-code.(CPU=XXX,FPGA=YYh,RAM=ZZh)ErrCode1E:FPGAhascausedaninterruptalthoughnodatapresent.

(SD1=XXh,SD1=YYh,CPU=ZZZ,FC=UUh)ErrCode20:UnknownprotocolatPPIMultimaster-Mode.(FC=XXh,Länge=YYY)ErrCode21:Unknownbaud-rateatPPIMultimaster-Mode.(Baudrate=XXh)

Afterthatadditionalhintsaredisplayed.

7.5.6Index"Internet/Mail":

The internet connection is configured by PPP, often a username and password is needed.Definethemin"InternetaccessoverPPP".Attention:ThisisNOTtheusernameandpasswordofyourE-Mail-account!

Inthenextsection"Mail"theE-Mail-accountisdefined:

InternetaccessoverPPP:

Username UsernamefortheInternetaccessPassword UserpasswordfortheInternetaccess

Mail:

Server NameoftheSMTP-Email-Servers,whichisusedtosendtheE-Mail.Mailfrom Source-E-Mail-Address

(shouldbefromthesameFree-mailer,insteadadeliveryisoftennot

Page 60: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 60/86

possible)

Username NameoftheUser-account(oftentheE-Mail-addressorCustomer-number)

Password PasswordfortheE-Mail-Account

7.6Tuning

Thismenuisonlyusedinsomespecialcases.Selectthedeviceandclickthebutton"Tuning"andafterthatthefollowingdialogisdisplayed:

Thefollowingconfigurationispossible,itwillbetransferredtotheCablebypressingthebutton„OK“.TheconfigurationissavedpermanentlyintheFlash-ROM:

DelaybeforesendAtProToolRTthecommunicationcouldbreakdown,becausetheMPI-Cableistransferringtheanswer-protocoltofast.Inthiscaseyoucouldinsertatimein0.1msticks.Insertatfirst300,togreatvaluesarepreventingthecommunication.

HMI-CableversionSomeTouch-panelshastheproblem,thatwhentheygetawrongversion-informationtheyneverretrytoconnect(andthenthecorrectversionistransferred).InthiscasetheHMI-version-informationcouldbetransferredimmediately.

A20-Terminal

WhenusingtheA20orM20-Terminal,thecontrol-linesontheserialportarenotused.InthatcasetheTELEService-functionisnotworking.Withthispropertythecontrol-linesarenolongerusedandthereforetheA20/M20cancommunicateoverTELEservice.

ShowErrCodemessagesindisplay Showserrormessagesonthedisplayoftheconnecteddevice

Bootsettings:

NormallytheMPI-Cableautomaticallyselectsthecorrectbustype,nochangesareneeded.Inspecial-casestheMPI-BuscouldbeselectedasPPI.

Forexample:ThisapplicationandthePLCarepoweredonatthesametime.Theapplicationiscommunicatingimmediatelywiththecable,thePLCisbooting,inthiscasetheMPI-Busisnotrunning.TheMPI-Bus iserroneous,sonocommunication isstarting. If thisoccursyoucouldchoose,thatthecableisworkingasMPI-Adapteronly.

Language:

Youcouldselectthelanguagewhichisusedonthecable(GermanorEnglish).

S5onMPImodeoff:

Page 61: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 61/86

Deactivatestemporarythe"S5onMPI"function,thecabledoesn'tpollthebusanymore.

sendresettocable:

Sendresettocable.

Console:

Showssomeinformationaboutthestatusoftheconnection.

7.7Factorydefaults

Thisbuttonsetstheconfigurationoftheselecteddevicetofactorydefaults.

7.8PPIBootoff

InPPIbootmodeS7IFCcannotcommunicatewith thecable.Todisable thePPIbootmode,clickonthebuttonPPIBootoff.Inthefollowingdialogyoumustselecttheserialportwherethecableisconnected:

7.9Emergency-Loader

LANproductsrunninginemergency-loaderareautomaticallyfoundbyS7IFC:

AfteraclickonEmergency-Loaderthefollowingdialogappears:

Page 62: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 62/86

OnaclickonYestheemergency-loadertriestorunthemainprogramofthefirmware.OnaclickonNotheemergency-loadertriestorewritethecompletefirmware.

8MPIcablemanager8.1Description

The MPI cable manager allows you to install an update in your cables and modules andconfigurethem.

TheMPIcablemanagercanbeusedforthefollowingproducts:

•MPI-LANcable–Art.ID.9352-LAN•S7-LANmodule–Art.ID.9352-LANCon•MPI-USBcable–Art.ID.9352-USB•S7-USBmodule–Art.ID.9352-S7-USB•MPI-IIcable(USB–operation)–Art.ID.9352+9352.1•MPI/PPIcable–Art.ID.9350•Tele-Service–Art.ID.9377-(ANALOG/ISDN/GSM)-OP•MPI/PPI-profibusmodem–Art.ID.9379-(G)-OP

8.2Installation

1.Download theMPI-Kabelmanager from theproduct-pageofyourMPI-productandstart theinstallation.

2.Following the Language selection theinstallation starts and a welcome-screen isdisplayed.

Nextclickontothebutton„Next“.

To change the installation path, click on"Browse".

Thenclick"Continue".

3. Select in this dialog the program folder fortheMPIcablemanagerstartupitems.

Thenclick"Continue".

Page 63: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 63/86

4.Waitfortheinstallationofthefiles.

5.End the installationafterasuccessfulcopyofdatawith"Finish".

8.3Overview

8.3.1Language

AfterstartingtheapplicationthetabLanguageisdisplayedatfirst:

InthisDialogyoucouldchoosetheusedlanguageintheapplication.

You could choose between German and English and confirm by clicking on the desiredlanguage.

8.3.2Interface

Page 64: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 64/86

In„setinterface“youcanchoosetheCOM-portyoudeviceisconnectedat.OnlytheCOM-portwhichwasaktiveatstartingtheMPI-Kabel-Managerareshown.

„Search“ update the COM-port listed in „set interface“ and put the Kabelmanager to therespectiveCOM-port.

For access query choose „Direct“ if yourproduct connects via USB-cable orNullmodem-cable. „Modem“ if your productconnectsviatelephonelineor„TELE-Network“ifyourproductconnectswithaTELE-Networkdeviceviatelephoneline.

ThebarsbelowshowsatwhichCOM-portsomethingwasfoundornot.

8.3.3Update

Page 65: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 65/86

ThedisketteshowthecurrentoperatingsysteminstalledonyourPCforcorrespondingproduct.

Thecabel-symbolontherightshowtheoperatingsystemwhichisinstalledonyourproductatthemoment.

With the button „default settings“ you can set your products on default settings. Should thedevicebeoutoforderafterconfigurated.Thisbuttonisselectableaftertheversioncheck.

With„Update“youcaninstallthecurrentoperatingsystem.Thisbuttonalsoisselectableafterversioncheck.

With„versioncheck“yourcablewhichisconnectedtotheCOM-Portreviewed.

Thesymbolnexttoversioncheckshowstherunningupdate.

WhileupdatedonotplugoutthecablefromthePLCorturnoffthepowersupply(Thecablewilllostalldata)!

Iftheupdateisbreakingbeforefinished,itcouldbethattheMPI-CabledisplaysinthefirstlineoftheLCD„Load1.50“andinthesecondline„CheckUpd“.ClosetheMPI-Cable-Mangerandrestartit.After“checkversion”(whichcouldtimeabout30seconds)andfollowing„Update“thebrokenupdateisrestartedandfinished.

8.3.4Teleservice

InthisdialogthespezificconfigurationoftheTele-Serviceistaken.Thereare3Tabs,wherethelastoneisactivated:

Page 66: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 66/86

8.3.4.1Telephonebook

Atthemomentnotimplemented!

Inthisdialogyoucoulddefinenewelementsoredit/eraseexistingelementsinyourtelephone-book.

Youcouldeditthefollowingdata:

=>Namefortheconnection(thesearedisplayedatconnection)=>street=>ZIP-codeandcountry=>TelephonenumberyoucanreachtheTS-adapter

8.3.4.2Connect

Atthemomentnotimplemented!

InthisdialogtheconnectiontoanothermodemwithaMPI-cableconnectedisstarted.Chooseontherightsidethenamedconnection,thenpress„connect“toestablishit.

With„Hang-Up“youcouldstopanexistingconnection.

Withthebutton„State“thestateoftheconnectionisdisplayedatthelowersideofthedialog.

8.3.4.3Extra

Page 67: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 67/86

Inthisdialog,allconfigurationtotheTS-adapterisdone.

The actual state of the MPI-cable is displayed right of the button “TS-function”, where thefollwing4possibleMessagescouldapear:

„TS-AdapterfunctionisNOTactiv.ToactivatepressTS-function“

The MPI-cable acts like an PC-Adapter. There will no answer for TS-spezific protocols, theattachedmodemwillnotinitializedandthebaud-ratetothePG/Modemisnotfixed.Thebaud-rateisdetectedautomatically.

„TS-AdapterfunktionisACTIVE.TodisablepressTS-function“

The MPI-cable acts like an TS-Adapter. There will an answer to TS-spezific protocols, theadaptercouldnowconfigured.AnattachedModemwillbe initiliazedand thebaud-rate to themodemisfixed.

„SNDERR“or„RCVERR“

Thereisacommunicationerroratsendingorrecievingdatafromthempi-cable.DisconnecttheMPI-cable from the power supply (PLC). Change to the tab Connect and after that back toExtra.Iftheproblemremains,checktheconnectiontotheMPI-cable,especiallytheCOM-portinthedialoginterface.

Withthebuttonsyoucoulddefinewhichmodemisused,activateordisabletheTS-functionorconfiguretheTS-adapter:

8.3.4.3.1„Setup“

Inthefollwingdialogyoucouldchoosetheusedmodem.

Page 68: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 68/86

8.3.4.3.2„TS-function“

With this button you select the functionof theMPI-cable asTS- orPC-adapter.Right of thisbuttontheactualstateoftheMPI-cableisdisplayed.

8.3.4.3.3„configureadapter“

Inthefollowingdialogyoucould,afteractivatingtheMPI-cableasTS-adapter,configuretheTS-spezificsetup.

Network

stationrelated:

Hereyoucanconfiguratefollowing:

TheTS-AdapteristheoneandonlymasterintheMPI-bus

Page 69: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 69/86

Which local station-address is used for theTS-Adapter. Please consider that aprogrammingdevicehasnormallythenumber0,operatorpanelhave1,PLC’suse2,FM/CP’s3etc.

Please:Neverusethesamestation-numberfor2differentstations!

networkrelated:

Hereyoucanconfiguratefollowing:

TheNettypeMPIorPROFIBUS

Thetransfer-speedontheMPI-bus

Thehigheststation-adressinthebus(thelessyouuse,themoreperformanceontheMPI-bus,mustbecorrespondingwiththeconfigurationinthePLC’s)

Modem

Inthisdialogyoucouldconfigurethemodem-relatedsetup.

TheInit-Stringiscomposedoutofseveralcommandstothemodem:AT=>startcommand&F=>usefactorysettingsE0=>EchooffL1=>loudnessofspeakerislowM1=>speakerisonatconnectionQ0=>outputofthereturnvaluesV1=>returnvaluesplaintext&C1=>DCDshowsstatusofthecarriersoundS0=1=>automaticconnectionafter1ring

TheHang-Up-Stringiscomposedof2elements:+++=>Changetocommand-modeAT=>startcommandH=>Hand-Upconnection

Therare2possiblecallingtechnics:MFVtone,thetelphone-numberistransferbyseveralfrequenciesIWVpulse,thetelephone-numberistransferedwiththecountofseveralpulsesontheline

When you must a pre-call to establish a call outside your company, you could define it atAmtskennzahl.

Whenthemodemshouldwaitforafreeline,soyoushouldsetthecorrespondingcheckbox.

Atnumberofretriesyoucouldconfigurethenumberofretriesforaconnectionbeforethecallisstopped.

Page 70: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 70/86

Whenusinga retryyoucouldchoose thesecondswhich theapplicationshouldwaitbetweencalls.

Serialparameter

Inthisdialogthetransfer-ratebetweenmodemandTS-Adapterisselected.Thetransfer-ratecouldchoosenbetweenthefollwingvalues:2400,4800,9600,19.2k,38.4k,57.6kand115.2kBaud

TheParitycouldbechoosen,butthis ismodem-dependantbecausesomemodemscouldnottransfertheparity-bit:

None:(Thereisnoparitytesting)Odd:(Thenumberofone-bitsareodd)Even:(Thenumberofone-bitsareeven)

Password

TheAccessoveratelephone-lineonthePLCcouldbeconfiguredinthisdialog.

Page 71: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 71/86

TheAdministratorcouldchangetheconfigurationoveratelephoneline,wherean2Usercouldnotchangetheconfiguration.

The User-Name is maximal 8 Chars long.Every user and the administrator could use apasswordwhichisusedtologintothePLCoveratelephone-line.Thesehavetoenterforeachnewcall.

After 3 wrong retries the connection is hanged up, so you must call again (Not so with anoriginalTS-adapter).

After changing the password for one user/administrator you must re-type it again correctlybeforeitisused.

Incall-back-numberyoucoulddefineatelephone-numberwhichisusedforcall-backfromtheTS-adapter. After you connect with the TS-adapter, you are asked for your user-name andpassword.Whenthecorrectpasswordanduser-nameistransfered,theconnectionishanged-upandtheTS-adapteriscallingbackthisconfiguredcall-back-number.

GSM/ISDN/SMS

Analogmodem:

YoucouldchoosetheLocationoftheModem.

ISDNmodem:

Page 72: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 72/86

Type:ChoosethetypeoftheISDN-networkswitch:

AT&T5ESSNothernTelecomDMS-100EuroISDNNET3(Standard)INS64USNI-1VN4

Protocol:Choosethetransfer-protocol-type:

ModemlikeV.120X.75(Standard)ML-PPPSoftBondingHDLCCLEAR

DN/MSN:DirectoryNumberresp.MultipleSubscriberNumberIsusedforbothISDN-channels.Whenusingthenumber255noDN/MSNisused.

GSMmodem:

Page 73: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 73/86

PIN:PIN-NumberoftheSIM-Card,upto8numericchars,(onlyforTELE-SERVICEGSM).

Provider: With the button „Provider“ the provider could be choosen. Reading of the list ofproviders could be elapse more than a minute. At end the possible provider are listed forselection.With„Automatic“theGSM-Modemtriestoconnectautomaticallytoaprovider.Ontherightsideofthebutton,theactualusedselectionisdisplayed.

DisplayDescription:

Automatic:TheproviderisautomaticallysearchedandselectedfromtheGSM-modem.Manual:TheProviderisselectedmanuallyfromtheGSM-Modemnonetworkregistered:NoconnectiontotheGSM-network,thereceive-qualityistoobadsetformat:TheformatoftheproviderissetManual/automatic: Themodem tries to selectmanually the provider, if this fails anautomaticsearchisdoneunknown:UnknownresponsefromGSM-Modem

Refresh: The button „Refresh“ reads from the Modem the receive quality, the quality isdisplayed.

DisplayDescription:

Unknown:UnknownstateoftheGSM-networknoregistration:ThemodemisnotregisteredintheGSMnetwork,noproviderfoundregistrationdenied:RegistrationintheGSM-networkisdeniedSearchnetwork:InSearchforaGSM-ProviderGSM:AttachedtoGSMGSM(ROAMING):AttachedtoGSM,butwithaRoaming-Partner.Thiscouldleadtohighcosts!

TheReceiveQualityisdisplayed,alsoasvaluetogetherwiththebit-error-rate.

ValueDescription:

99Nonetwork,noreceive00Very,verybadreceive-quality01Verybadreceive-quality02to09Badreceive-quality10to17Mediumreceive-quality18to25Normalreceive-quality26to30Goodreceive-quality31Bestreceive-quality

Messages:

Thepossibleerrorconditionsforthemodem,mpi-bus-problemsorotherproblemsaredisplayedinthistext-field.Firstly,themodem-relatedinformationisshown:

Page 74: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 74/86

Message

Modemready

Modemerror

Noanswerfrommodem

Modemdetectsring

Endofconnection

connectedviamodemline

Nodialtonedetected

Phone-lineortelephonebusy

Phone-numberisblacklistedinmodem

Phone-numberdelayed.Accessdeniedfor1minute.

Fax-calldetected

Data-calldetected

unknownerror

Theselecteddirect-access-numbernotconfigured

TheconfiguredPIN-NumberiswrongfortheinsertedSIM-Card

TheSIM-CardisnotorwronginsertedortheSIM-Cardisa5VType

FollowingthepossibleMPI-Buserror-messages

Message

MPI/Profibus-Configurationerroneous

TimeoutatMPI/Profibusdetachfromdevice.

Thelocalstation-addressisusedtwiceintheMPI/Profibus.

A20/M20/TC35Modemoperation

TheMPI/Profibusisnotcorrectlyconfigured

TheHSAisnotconfiguredoptimal

TheMPI/Profibus-Baudrateisnotdetectable

OverflowintheinternalMPI-Readbuffer

OverflowintheinternalLAN-Readbuffer

OverflowintheserialBuffer

TheselectedMPI/Profibus-Baudrateiswrong

OverflowininternalLAN-Writebuffer

LAN-Recieve-Error

LAN-Send-Error

ThePD-Numberriswrong

ThetransferredSAPiswrong/unknown

ErrCode 01: The Destination address (XXX) of a State protocol > 127 detected. In theMPI/Profibus-Bustherearenostationspossiblewhichstationnumberisgreaterthan127.(FC=YYh)

ErrCode 02: At state-protocol the Source-Address is detected as 127. This is theBroadcast-addresswhichisnotpossible.

Page 75: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 75/86

ErrCode03:ThereceivedStateprotocolsdestinationaddress(XXXrespectivelyYYY)doesnotexistintheMPI-Bus.(FC=ZZh)

ErrCode04:Thefunction-code(YYh)ofthereceivedStateprotocolfromXXXisincorrect.The7thBitisHigh,butaccordingtothespecificationtheBithastobelow.

ErrCode05:AStateprotocolhasbeenreceived.But thefunction-code(YYh)meansthattheparticipantisnotreadytoenterthebus.

ErrCode 06: The function-code in the State-protocol received from XXX is unknown(FC=YYh)

ErrCode11:Thesender(XXX)ofthereceiveddata-protocolisunknown.TosenddatatheparticipantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)

ErrCode 12: Data-protocol with Source-address 255 (Broadcast) is useless. (CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode13:Thesender(XXX)ofthereceiveddata-protocolisunknown.TosenddatatheparticipantmustgettheToken.(SSAP=YYh,FC=ZZh,length=UUU)

ErrCode14:The7thBitofthefunction-codeisHigh,butaccordingtothespecificationtheBithastobelow.(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode15:Theupper4BitoftheFunction-codearewrong/unknown)(CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode 16: Unknown function-code has been transmitted to the cable. (CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode 17: Destination-SAP are defined till 3Fh in data-protocols. (CPU=XXX,SSAP=YYh,FC=ZZh,length=UUU)

ErrCode 18: Source-SAP are defined till 3Fh in data-protocols. (CPU=XXX, SSAP=YYh,FC=ZZh,length=UUU)

ErrCode 19: Received a data-protocol with destination-SAP=0, Connection request fromanotherbus-participantwithourcable.(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)

ErrCode1A:Participantsaresendingdatatoourcablewithsource-SAP=0,whichmeansthat the participant has notmade a connection establishment or has lost the negotiatedSAP.(CPU=XXX,SSAP=YYh,FC=ZZh,DSAP=UUh)

ErrCode1B:Data-protocolwithunknowndata-function-codereceived.(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)

ErrCode1CData-protocolwithunknowndata-function-codereceived.(CPU=XXX,SSAP=YYh,FC=ZZh,DFC=UUh)

ErrCode1D:Receivedastate-protocolwitherror-code.(CPU=XXX,FPGA=YYh,RAM=ZZh)

ErrCode1E:FPGAhascausedaninterruptalthoughnodatapresent.(SD1=XXh,SD1=YYh,CPU=ZZZ,FC=UUh)

ErrCode20:UnknownprotocolatPPIMultimaster-Mode.(FC=XXh,Länge=YYY)

ErrCode21:Unknownbaud-rateatPPIMultimaster-Mode.(Baudrate=XXh)

Afterthatadditionalhintsaredisplayed.

SMS:

SMS:SwitchesProcessingOFF/OnlyReceive/OnlySend/ReceiveandSend.Attention:beforesettingONcheckconfiguration,afteractivatingthedevicewillgointotheMPI-BUSandtriestoconnecttothedefinedPLC.ReceiveofSMSonlywithTELESERVICE-GSMReceiveofDTMFonlywithwithTELESERVICEGSM

TS:localstation-address(shouldnotbeusedtwiceintheMPI/Profibus!)

PLC:fromthisstation-addresstheFlagwordandData-blockisaccessedforcommunication

MW:communication-flagword(thefirstbyteisthecommand,thesecondisthestate).Useevenoperand-addresses.

Page 76: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 76/86

DB:communication-data-block.

Provider1/2/3/4:Configure theSMS-Provider touse, including type,phone-numberandchar-code.

Internet/Mail

8.3.4.3.4„Importparameter“

WiththisbuttonyoucouldimporttheparameterfromanASCII-file.Thisfileiscompatibletotheoriginalfile-format.

8.3.4.3.5„Exportparameter“

WiththisbuttonyoucouldexporttheparametertoanASCII-filewhichhasthesamefile-formatastheoriginal.

8.3.5Tuning

Page 77: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 77/86

Thistabisonlyusedinsomespecialcases.Ifyoupressthebutton„CheckAdapter“thecableisconnectedundafterthatthefollowingdialogisdisplayed:

There are the following configuration possible, they will be transferred to the MPI-Cable bypressingthebutton„Transfer“.TheconfigurationissavedpermanentlyintheFlash-ROM:

Timetosend:

AtProToolRTthecommunicationcouldbreakdown,becausetheMPI-Cableistransferringtheanswer-protocoltofast.Inthispropertyyoucouldinsertatimein0.1msticks.Insertatfirst300,togreatvaluesarepreventingthecommunication.

HMI-Cable-Version:

Page 78: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 78/86

Some Touch-panels have the problem, that when they get a wrong version-information theyneverretrytoconnect(andthenthecorrectversionistransferred).InthiscasetheHMI-version-informationcouldbetransferredimmediately.

A20-Terminal:

WhenusingtheA20orM20-Terminal, thecontrol-linesontheserialportarenotused. In thatcasethetele-service-function isnotworking.Withthisproperty thecontrol-linesareno longerusedandthereforetheA20/M20cancommunicateovertele-service.

Bootconfiguration:

NormallytheMPI-Cableautomaticallyselectsthecorrectbus-type,nochangesareneeded.Inspecial-casestheMPI-BuscouldbeselectedasPPI.

Forexample:ThisapplicationandthePLCarepoweredonatthesametime.Theapplicationiscommunicatingimmediatelywiththecable,thePLCisbooting,inthiscasetheMPI-Busisnotdriven.TheMPI-Busiserroneous,sonocommunicationisstarting.Ifthisoccursyoucouldchoose,thatthecableisworkingasMPI-Adapteronly..

Language:

Youcouldselectthelanguagewhichisusedfromthecable(GermanorEnglish).

9PLC-VCOM9.1Description

Itcreatesanew,virtualcom-portinyoursystem,withwhichtheprogrammingsoftwareofyourPC(sucha.PG2000,Step©5/7,S5/S7forWindows,WinCC,Microwin)cancommunicatewiththedevice

ThePLC-VComapplicationisneededforusewiththefollowingdevices:

•MPI-LANCable–Art.No..9352-LAN•S7-LANModul–Art.No..9352-LANCon•MPI-USBCable–Art.No..9352-USB•S7-USBModul–Art.No..9352-S7-USB•MPI-IICable(USB–mode)–Art.No..9352+9352.1•S5-LANModul–Art.No..9359-LAN•Tele-Service(asprogrammingadapter)–Art.No..9377-(ANALOG/ISDN/GSM)-OP

ByinstallingthePLC-VCOMadiconalmentewereinstalledtheS5-LANandtheMPI-LAN.Bothofferthepossibilitytomanagethenetworkconfigurationofyourproducts

9.2Installation

1.DownloadthePLCVComfromtheproduct-pageofyourMPI-productandstarttheinstallation.

2.Afterchoosinglanguagethewelcomedialogappearsinthechosenlanguage.

Click“Next“todefinetheinstallationpath(seerightpicture).

Thiscanbedonewithaclick“Browse…”

Ifyouarereadypress“Next“togoon.

3. In the next dialog you can choose theprogramfolderforyourstartmenu.

Goonwith“Next”.

Page 79: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 79/86

9.2.1USBdriverinstallationusingWindowsNT/2000/XP

ThispartofthedescriptionisfortheoperatingsystemsWindowsNT/2000/XP.IfyouareusingWindows98SEorMEpleasereadthedescription„FinalconfigurationofthePLC-VCOM“.

ThisdriverisonlyrequiredforUSBdevicessuchasMPI-USB/MPI-II/S7-USB.ConnectthisyourMPI-USBcabletoyourcomputer.

5."Yes"tostartthedriverinstallation.

"No" to skip the driver installation and godirectly to the"Final configuration of the PLC-VCOM".

6. OnWindows XP this dialog appears whileinstallation(seeleftpicture).

Itisthe“WindowsDriverQualifyingQuestion”.

Press“continueinstallation“togoon.

7. After the driver has been installed, pleasedisconnect your MPI-USB Cable and thanconnectitagain.

Thisloadsthenewinstalleddriver.“OK”togoon.

9.2.2FinalconfigurationofthePLC-VCOM

8.ChoosingtheCOM–Port

Already occupied COM port can be viewed in WindowsDeviceManager ifyouarenotsurewhichCOMportsarestillavailable.

Ifyouarenotsurewhichportisunused,press“OK“.

Page 80: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 80/86

Lateryoucanstartthisdialogagainbyclickingintheapplicationfolderofyourstartmenuon“SelectCOM”.

9.Theinstallationendswithaclickon“OK”.

9.2.3USBdriverinstallationusingWindows98SE/ME)

AfteryouhavefinishedtheinstallationofthePLC–VComsoftware(Step9and10)younowhavetoinstallanUSBdriver.ThereforethesoftwarePLC–VCommustbeinstalled.Otherwisetheneededdriverfileisnotavailable.

ThisdriverisonlyrequiredforUSBdevicessuchasMPI-USB/MPI-II/S7-USB.

10.PlugthecableintotheUSBportofyour computer and wait until theautomaticalhardwarerecognitionstarts

. Alternative: „Control panel -Hardware“.

11.The“hardwareassistent“wantsyouto install the “USB< ->Serial“driver.Click on “Next” to configure the driversearch.

12.Choose in thenextdialog “Searchfor the best device driver(recommended)“andclickon„Next“..

13. Activate the checkbox “Set thedriver position:“ and deactivate all theothers.

Click on “Choose…“ and choose thepathwhere thePLC–VComsoftwareisinstalled.

Confirm your configuration with “OK“andclickon”Next“.

14. Now the “Hardware - Assistent“shouldshowadialogwhichisequaltothepicturebelow.

Clickon“Next“tostarttheinstallation.

Page 81: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 81/86

15. After the installation finishedsuccessfulclickon“Ready“toendthisinstallation.

16.Theinstallationisfinishedsuccessfullyafteryouhaverestartedyousystem.

ThevirtualCOM-Portisonlyview-,select-andaccessiblewhenthePLCVCOMisinthe„connected“state,thatmeansacableispresentandusable.

9.3Overview

Besideyourwatch,inyourWindows–Taskbar,appearsanewSymbol.ThisoneisforthePLC–VComsoftware.

Itshows theactualconnectionstatuswithyourcable/moduleMPI-II,MPI-USB,MPI-LAN,S7-USB,S7-LANorS5-LAN.

9.3.1Statusdescription:

PLC–VComisconnectedwithyourcable/moduleandoperational.

PLC–VComisnotconnected.

Theredsymbolindicatesthatsending/receivingdatahasbeenfailed.

Sendstatus:(leftfield):Dataissendtothecable/module

ifthisoneisgreen.

Receivestatus:(rightfield):Dataisreceivedfromthe

cable/moduleifthisoneisgreen.

9.3.2MainWindow

Page 82: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 82/86

1.Configuration:Selectandopentheconfigurationprogramforyourproducts.=>PLC-VCOM:Management,connectionandcommunicationwiththecables=>S5-LAN:configurationofyourS5-LANmodules=>MPI/S7-LAN:ConfigurationofyourMPI-LANorS7LAN

2.Info:informationaboutthePLC-VCOMandyourcomputer.

3.Status:Displaytheconnectionparametersofthecableconnected.=>Topleft:showsthenameofthecurrentlyconnectedproduct=>semi-left:showstheconnectionstatus=>halfright:showstheIPaddressoftheconnectingcable=>Topright:Clickheretosearchorselectadevice=>rightmiddle:nameoftheconnectedcable=>bottomright:displaysinformationaboutcurrentcomputerconnections

4.VirtualPort:DisplayofselectedvirtualCOMportsandtheprogramthatthelasthasaccessedonthisCOMport.

5.Program:ButtonstoadjustthePLC-VCOM=>Exit.ThisbuttonclosestheprogramandtheCOM–Port=>Lenguage:SwitchtheLanguagetoenglish/german.=> Help: opens the Help menu of the PLC-VCOM, when they should have problems orquestions=>“Minimize”thedialog.Thisbuttondoesnotclosetheprogram.Itjustminimizestheprogram.YouwillfindthePLC–VComsymbolintheWindows–taskbarbesidethewatch.

9.3.3Configurationwindow

Page 83: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 83/86

1.Listofavailablecable/modules:=>Linewisedisplayoftheproductsfoundwithyourproperties

2.IP-Adress:=>IPaddressandMACaddressoftheselectedcable/module

3.Vianetworkcard:=>Selectionoftheusednetworkinterfacecard

4.LAN-Type:=>Selectionofthebeconnectedcable/ModuleTypes

5.Severalcheckboxes:=>Manualentry:allowsyoutoentertheparametersmanually=>nonetwork:forproductswhicharenotinanynetwork=>InstallinginthedeviceManager:InstallsthePLC-VCOMCOMportinDeviceManager(requiredonlyforS7forWindowsandS7Doctorsoftware)=>RFC1006:activationofRFC1006communicationmethod=>nonetworkcardselection:Passestheroutingofpacketstotheoperatingsystem=>serialintervaltimes:slowdowntheserialtransmissionegpaneltransfers

6.Search=> With a click on Search you are sending an broadcast to every cable/module that isconnectedwithyournetworkoryoursystem.Everyrespondingcable/modulewillbeinsertedtothelist.

7.Help:=>openstheHelpmenuoftheconfiguration,iftheyhaveproblemsorquestions

8.OK:=>EndsthePLC-VCOMconfigurationandacceptstheentered/selectedsettings

9.Cancel:=>EndsthePLC-VCOMconfigurationanddiscardstheentered/selectedsettings

9.4Configuration

1.StartthePLC–VComapplication,ifthisisnotalreadyrunning.

2.OpenthePLC-VCOMbyclickingontheicon PLC-VCOMinthesystemtray.

3.After thePLC-VCOMisopen,click in thestatusareaon the"Configure"and thewizard toconfigureislaunched.

9.4.1MPI-II

Page 84: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 84/86

9.4.1.1Automatic

1.WithaclickonSearchyouaresendinganbroadcasttoeverycable/modulethatisconnectedwithyournetworkoryoursystem.Everyrespondingcable/modulewillbeinsertedtothelist.

2.WählenSiedasgewünschteKabel/Modulaus,sodassesblaumarkiertist.HierbeiwerdenalleParameterautomatischindenKonfigurations-Assistentenübernommen.

9.4.1.2Manual

DiemanuelleEingabebetrifftdieNetzwerkteilnehmerdiesichhinterRoutern,inanderenNetzen befinden, da der Broadcast zur automatischen Erkennung nicht von RouternweitergegebenwirdunddieseNetzwerkteilnehmersomitnichtgefundenwerdenkönnen.

DieserPunkt ist beiUSB-Geräten nicht zu beachten, da diese alle direktmit demComputerverbundensind.

9.4.1.3AbschließendeEinstellungen

3. Wählen Sie die Optionen an, die Sie eventuell benötigen, wie z.B. keineNetzwerkkartenauswahl, kein Netzwerk, Installation im Gerätemanager oder seriellePausenzeiten.

Informationen zu denOptionen, diemit Hilfe der Checkboxen an und abgewähltwerdenkönnen,erhaltenSieimKapitel„Übersicht“desPLC-VCOMs.

4.BestätigenSieIhreEingaben/Auswahlmit„OK“.

5. ImHauptfenster desPLC-VCOMserscheint nach einemerfolgreichenVerbindungsaufbau,derKabeltypemitdemsichderComputerverbindetundderVerbindungsstatus„verbunden“.

6. Abschließend Klicken Sie auf „Minimieren“ um den PLC-VCOM in den Infobereich zuverkleinern,damitdieserweiterhindenvirtuellenCOM-Portverwaltenkann.

10Technicaldata

Page 85: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 85/86

TechnicalSpecifications:Supplyvoltage: 24V/DC+/-20%Powerconsumption: 2,5wattDisplay: doublelinedLCD-display

Handling/Configuration: Kabelmanager-Softwarekeypadontheback

Interfaces:

tothePLC:PPI/MPI/Profibusinterface:9,6KBd-12MBdtothePD/PC:RS232:9,6KBd-115,2KBdUSB1.1forcabletypeA<->A

Galvanicseparation: 1000VPPI/MPI/ProfibustothePCOperatingtemperature: 5-55°CCase: ABS-plasticcaseDimensions: 146x41x29mm10.1Pinassignment

PinNo. Notation Signalname Direction (ofcable)

1 NC NotConnected 2 M24V Groundofthe24V In3 Ltg_B DatalineB BiDir.4 RTS-AS RequesttoSendfromthePLC In5 M5V Groundofthe5V IN6 P5V 5Voutput Out7 P24V 24VSupplyinput IN8 Ltg_A DatalineA BiDi9 RTS-PG RequesttoSendtothePLC Out

Note

TheshieldisattachedwiththeMPI/PPIconnectorviatheshieldoftheadaptercasing.To finddirectly attended PLC´s , RTS-AS andM5Vmust be connected in the cable. P5Vmeans aoutputof thecableandworksonlyasanoutput forabus-terminationwith resistors.This5Voutputdoesn’tdriveanyloadandhavea100Rresistorinsidehisdirection.

observe:

Don’tlengthentheconnectionbya1:1cabletothePLC,becausethereare24Vand5Vinsideofthecable.Thequalityofthebus-signalwillberisendown!

To lengthen the connection, please use a MPI-NETZ-Adapter and connect only the signalsLtg_AandLtg_B1:1andtheshieldatbothsidesofthemetal-casingattheSUB-Dconnector

Foranextensionofthecablepleasesupplythecablewithexternalpowerandonlyprolong the signals Ltg_A and Ltg_B 1:1. Connect the shield on the SUB-Dconnector,possiblyincludeaterminationresistors(onthebus-END).

10.2PinassignmentRS232

Pinnumber Shortform Designation Direction

1 DCD receivelinesignaldetected input2 TXD transmitdata output3 RXD receivedata input4 DSR transmissionmeansisready output5 GND signalmass 6 DTR datadeviceready input7 CTS cleartosend output

Page 86: MPI-II user manual

24.7.2019 Handbuch

https://www.traeger.de/tpa/ftp/pub/handbook/en_Handbuch MPI-II.html 86/86

8 RTS requesttosend input9 RI ringtone input

ThecableisdesignedsothatitcanbedirectlyconnectedtothePC.Optionallytheendofthecablecanbeextendedwitha1:1extensioncableupto15m.Agoodqualityof theextensioncordmustberespected.

10.3Pinning(USB)PC

PinNo. Shortform Description Direction (cable–view)

1 Vcc Powersupply(DC) In2 D– Dataline– BiDi3 D+ Dataline+ BiDi4 GND Ground In

Important:

Pleasedonot lengthenthisside, thissidealsosupportsthe5V/DCpowersupply(max.cablelengthare5meters)

Alongercablewoulddecreasethequalityofthesignalonthebusandmaycauseseveralerrorsinthetransmission!