MOVIMOT® Installation Guidelines 8...8 138 System Manual - Drive System for Decentralized...
Transcript of MOVIMOT® Installation Guidelines 8...8 138 System Manual - Drive System for Decentralized...
System Manual - Drive System for Decentralized Installation 137
8MOVIMOT® Installation Guidelines
8 Electrical Installation
8.1 MOVIMOT®
Installation Guidelines
Connect Power
Supply Lines
• The nominal voltage and frequency of MOVIMOT® must correspond to the data for
the supply system.
• Line cross-section: according to input current Iin for rated power (see Technical
Data).
• Permitted line cross-section of MOVIMOT® terminals (does not apply to field
distributor)
• Use conductor end sleeves without insulation collar
(DIN 46228 Part 1, material E-CU)
• Install line safety at the beginning of the supply system cable behind supply bus
junction (see the section "Connection of MOVIMOT® Basic Unit," F11/F12/F13). Use
D, D0, NH or circuit breakers. The fusible rating should be selected in accordance
with the cross-section of the cable.
• It is not permissible to use a conventional residual-current-operated circuit breaker
as a protection device. Universal current-sensitive residual-current-operated circuit
breakers (tripping current 300 mA) are permitted as a protective device. During
normal operation of MOVIMOT®, earth-leakage currents of > 3.5 mA can occur.
• Use contactor switch contacts to switch MOVIMOT® from utilization category AC-3
according to IEC 158.
• SEW recommends using earth-leakage monitors with pulse-code measurement for
power supply systems with non-grounded star point (IT systems). This step will
prevent accidental triggering of the earth-leakage monitor by means of the grounding
capacities of the inverter.
Altitude above
1000 m MSL
MOVIMOT® drives with supply voltages of 380 to 500 V can be used at altitudes above
2000 m MSL up to 4000 m MSL1 under the following peripheral conditions.
• The rated continuous power is reduced based on the reduced cooling above 1000 m
(see the section Technical Data and Dimension Drawings).
• Above 200 m MSL, the air and creeping distances are only sufficient for overvoltage
class 2. If the installation requires overvoltage class 3, an additional external
overvoltage protection must be used to ensure that overvoltage surges are limited to
2.5 kV phase-to-phase and phase-to-ground. If safe electrical separation is required,
it must be implemented outside the units at altitudes above 2000 m MSL (presently,
safe electrical separation is not specified by a standard outside the EU)
• The permitted rated supply voltage of 3 x 500 V up to 2000 m MSL is reduced by 6 V
for every 100 m to a maximum of 3 x 380 V at 4000 m MSL.
Power terminals Control terminals
1.0 mm2 – 4.0 mm2 (2 x 4.0 mm2) 0.25 mm2 – 1.0 mm2 (2 x 0.75 mm2)
AWG17 – AWG10 (2 x AWG10) AWG22 – AWG17 (2 x AWG18)
1. The maximum altitude is limited by creeping distances and flameproof components such as electrolytic
capacitors.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
138 System Manual - Drive System for Decentralized Installation
MOVIMOT® Installation Guidelines
Connecting 24
VDC supply
• Supply MOVIMOT® either via external 24 VDC or via the MLU..A or MLG..A options.
Conventional
Control (via
Binary
Commands)
• Connect the required control leads (e.g. CW/Stop, CCW/Stop, f1/f2 setpoint change)
• Use cables shielded as control cables and run separate from power cables.
Control via RS-
485 Interface
with bus master PLC, MLG..A, MBG11A, MWA21A option or MF... fieldbus interfaces
• Caution: Connect only one bus master.
• Use twisted pair shielded cables as control leads and route them separate from
power current cables.
Protection
Devices
• MOVIMOT® drives have integrated protection elements against overloads, external
elements will not be necessary.
UL-Compliant
Installation
• Only use copper cables with the following temperature ranges as connection leads:
Temperature range: 60 / 75 °C
• The permissible tightening torques of the MOVIMOT® power terminals are:
– 1.5 Nm (13.3 lb.in)
• MOVIMOT® are suited for operation on voltage supply systems with grounded star
(TN and TT systems) supplying a maximum supply current of 5,000 AAC and having
a maximum rated voltage of 240 VAC (MM03B-233 to MM22B-233) or 500 VAC
(MM03-503 to MM30B-503). The rating for the fuses is not to exceed the following
values:
– MM03B-503 to MM07B-503: 25 A/600 V
– MM11B-503 to MM30B-503: 35 A/600 V
– MM03B-233 to MM22B-233: 35 A/250 V
• As external 24 VDC voltage source use only tested units with a limited output voltage
(Vmax = 30 VDC) and limited output current (I ≤ 8 A).
• UL certification does not apply to operation in voltage power systems with a non-
grounded star point (IT systems).
System Manual - Drive System for Decentralized Installation 139
8Additional Installation Instructions for Fieldbus Interfaces, FieldDistributors
8.2 Additional Installation Instructions for Fieldbus Interfaces, Field Distributors
Current Carrying
Capacity of
Terminals
• Cage clamp terminals X20 (gray): 12 A maximum continuous current
• Screw terminals X1, X21 (green): 32 A maximum continuous current
Daisychaining 24
VDC Supply
Voltage for MFZ.1
Module Carrier:
• Two M4 x 12 studs are located on the connection part of the 24 VDC supply. These
studs can be used for daisychaining the 24 VDC supply voltage.
• The studs have a current carrying capacity of 16 A.
Additional
Connection
Options with
MFZ.6 and MFZ.8
Field Distributor
• The connection part of the 24 VDC supply comprises a X29 terminal block with two
M4 x 12 studs and a pluggable X40 terminal.
• The X29 terminal block can be used alternatively to X20 terminal for daisychaining
the 24 VDC supply voltage. The two studs are connected internally with the 24 V
connection on terminal X20.
Terminal assignment:
• The pluggable X40 terminal ("Safety Power") is intended for the external 24 VDC
supply of the MOVIMOT® inverter via a safety reset device.
Terminal assignment:
This allows a MOVIMOT® drive to be used in safety applications. Corresponding
information can be found in the documentation "Safe Disconnection for MOVIMOT®."
• X29/1 and X40/1 are factory-jumpered, so that the MOVIMOT® inverter is supplied
by the same 24 VDC voltage as the fieldbus module.
• The current carrying capacity of the two studs is 16 A.
• The current carrying capacity of screw terminal X40 is: 10 A.
05236AXX
05237AXX
No. Name Function
X29 1 24 V 24 V power supply for module electronics and sensors(stud, jumpered with terminal X20/11)
2 GND 0V24 reference potential for module electronics and sensors(stud, jumpered with terminal X20/13)
No. Name Function
X40 1 24 V 24 V voltage supply for MOVIMOT® for disconnection with safety reset device
2 GND 0V24 reference potential for MOVIMOT® for disconnection with safety reset device
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
140 System Manual - Drive System for Decentralized Installation
Additional Installation Instructions for Fieldbus Interfaces, Field Distributors
Transfer Rates >
1.5 Mbps (in
connection with
MFP..D)
With transfer rates > 1.5 Mbps it must be observed that the PROFIBUS connecting leads
in the inside of the field distributor are kept as short as possible and have the same
length for incoming and outgoing bus.
Wiring Check Before connecting power to the system for the first time, it is necessary to perform a
wiring check to prevent damage to persons, systems and equipment caused by
wiring faults.
• Remove all bus modules from the connecting module.
• Disconnect all MOVIMOT® inverters from the connecting module (only with MFZ.8).
• Disconnect all plug connectors of the motor circuits (hybrid cable) from the field
distributor.
• Perform an insulation test of the wiring in accordance with valid national standards.
• Check the grounding.
• Check whether supply system cable and 24 VDC cable are insulated.
• Check whether supply system cable and communications cable are insulated.
• Check the polarity of the 24 VDC cable.
• Check the polarity of the communications cable.
• Check the supply phase sequence.
• Ensure equipotential bonding between the fieldbus interfaces.
After the Wiring
Check
• Plug on and fasten all motor circuits (hybrid cable).
• Insert the bus modules and fasten screws.
• Plug on all MOVIMOT® inverters and fasten screws (only with MFZ.8).
• Install all terminal box covers.
• Seal plug connections not in use.
System Manual - Drive System for Decentralized Installation 141
8Additional Installation Instructions for Fieldbus Interfaces, FieldDistributors
EMC Metal Cable
Glands
EMC metal cable glands supplied by SEW must be installed as follows:
(1) Caution: Cut off insulation foil, but do not fold it back
03432BXX
(1)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
142 System Manual - Drive System for Decentralized Installation
Connection of MOVIMOT® Basic Unit
8.3 Connection of MOVIMOT® Basic Unit
05293AEN
M3~
L1L2L3PE
K11
F11/F12/F13
K1
RS
-485
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
24V
24V
24V
24V
R L24V
R L
R L
R L
R L
R L
24V
f1/f
2
R L24V
f1/f
2
=+
-
R L24V
BMG
MOVIMOT®
red
wh
ite
BMGBoth directionsare enabled
Only direction enabled.Setpoint selection for CCW rotationcauses the drive to stop.
CW
Only direction enabled.Setpoint selection for CW rotationcauses the drive to stop.
CCW
Drive is inhibited orbrought to a stop
Functions of the CW and CCW
Functions of f1/f2 terminals
Functions of CW and CCW Terminals
terminals under binary control
controlled via RS-485 interface / field distributor
CW direction ofrotation activated
CCW direction ofrotation activated
Setpointactivated
f1 Setpointactivated
f2
MOVIMOT®
BW braking resistor(only for MOVIMOTwithout brake)
®
24V
supp
lyD
C
CW
/sto
p
CC
W/s
top
Set
poin
t sw
itcho
ver
f1/f2
Rea
dy s
igna
lC
onta
ct c
lose
d =
rea
dy f o
r op
erat
ion
24 V supplyDCexternal orMLU../MLG..option.
blu
e
System Manual - Drive System for Decentralized Installation 143
8Connection of MLU11A / MLU21A Option
8.4 Connection of MLU11A / MLU21A Option
8.5 Connection of MLG11A / MLG21A Option
03272BXX
13 14 15
L1
L2
L3
R L f1/f2
K1a
K1b
RS
-R
S+
L1
L2
24V
MLU..A
MOVIMOT®
24V
YE (MLU11A) / BN (MLU21A)
YE (MLU11A) / BN (MLU21A)
RD
BU
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
L1
L2
24V
MLU..A
MOVIMOT®
03182BXX
(1) Observe Enable of direction of rotation (see the section "Connection of MOVIMOT® Basic Unit" Functions of terminals CW/Stop, CCW/Stop with controller via RS-485 interface)
RD
BU
OG
GN
YE (MLG11A) / BN (MLG21A)
YE (MLG11A) / BN (MLG21A)
13 14 15
L1
L2
L3
MOVIMOT®
L1
L2
24V
RS
+
RS
-
MLG..A
24V
R L f1/f2
K1a
K1b
RS
-R
S+
(1)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
144 System Manual - Drive System for Decentralized Installation
Connection of MBG11A Option
8.6 Connection of MBG11A Option
8.7 Connection of MWA21A Option
03183BXX
03184BXX
(1) Observe Enable of direction of rotation (see the section "Connection of MOVIMOT® Basic Unit" Functions of terminals CW/Stop, CCW/Stop with controller via RS-485 interface)
(2) EMC metal cable gland(3)
MBG11A
24V
RS
+
RS
-
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®
24 VDC
(2)
(1)
MWA21A1 24V2 24V34 R5 L6 10V7 +8 -9
1011 RS+12 RS-
24VDC
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®
(1)
(2)(2)
(3)
6 10V7 +8 -9
10
6 10V7 +8 -9
10
MW
A21
A
MW
A21
A6 10V7 +8 -9
10
6 10V7 +8 -9
10
MW
A21
A
MW
A21
APotential-freeanalog signal
Potentiometerwith use of 10Vreference voltage
2 kΩ∗can be 5 kΩ∗
System Manual - Drive System for Decentralized Installation 145
8Connection of AS-i Binary Slave MLK11A
8.8 Connection of AS-i Binary Slave MLK11A
8.9 Connection RS-485 Bus Master
05118AXX
(1) AS-i connection(2) Connection for 2 external sensors
4
21
3
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MLK11A
WHBK/BU
BK/RD
BK/WHRD
BU
2 1
3 45
(2)
AS-i +
AS-i -
24V
DI20V
N.C.
N.C.
N.C.DI3
MOVIMOT®
(1)
03177AXX
(1) Observe Enable of direction of rotation (see the section "Connection of MOVIMOT® Basic Unit" Functions of terminals CW/Stop, CCW/Stop with controller via RS-485 interface)
(2) EMC metal cable gland(3) Potential compensation MOVIMOT®/ RS-485 master
RS-485
RS-485Busmaster(SPS / PLC)
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®
24 VDC
(1)
(3)
(2)(2)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
146 System Manual - Drive System for Decentralized Installation
Connection of MDG11A Option
8.10 Connection of MDG11A Option
• The diagnostic unit must be connected prior to the possible occurrence of a fault
since the MOVIMOT® fault messages are not saved and the information is lost when
the 24 V supply is disconnected.
• Connecting the MDG11A to an RS-485 bus with several MOVIMOT® is not
permitted.
• The diagnostic unit can be used if the MOVIMOT® is controlled via terminals (=
address 0 [S1/1-S1/4 = OFF]).
• Using the diagnostic unit with setpoint setting via RS-485 interface is not permitted.
03404BXX
(1) EMC metal cable gland
MDG11A
24V
RS
+
RS
-
13 14 15
L1
L2
L3
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®
(1)
System Manual - Drive System for Decentralized Installation 147
8Connection with PROFIBUS
8.11 Connection with PROFIBUS
Connecting MFZ21 with MOVIMOT®
Terminal assignment
04914AXX
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
24V
RS
+
RS
-
GN
D 24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®MFZ21 (PROFIBUS)
24 VDC
+ -
A B
DG
ND A B
DG
ND
res.
VP
DG
ND
res.
A
B
A
BPROFIBUS DP
(3)
(2)
(1) (1)
0 1+MFZ21
MFP...
X20
0 = Potential level 0
1 = Potential level 1
(1) For separate assembly of MFZ21 / MOVIMOT®:Connect the shield of the RS-485 cable via an EMC metal cable gland on MFZ and MOVIMOT® housing.
(2) Ensure equipotential bonding between all bus stations.(3) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 A Output PROFIBUS-DP data line A (outgoing)
5 B Output PROFIBUS-DP data line B (outgoing)
6 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
7 - - Reserved
8 VP Output +5 V output (max. 10 mA) (only for test purposes)
9 DGND - Reference potential for VP (terminal 8) (only for test purposes)
10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 24 V Output 24 V power supply for MOVIMOT®
16 RS+ Output Communications link to MOVIMOT® terminal RS+
17 RS- Output Communications link to MOVIMOT® terminal RS-
18 GND - 0V24 reference potential for MOVIMOT®
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
148 System Manual - Drive System for Decentralized Installation
Connection with PROFIBUS
Connecting MFZ23 Field Distributor with MFP...
MFZ23 connection module with MFP21, MFP22 fieldbus module and two separate 24 VDC voltage circuits
Terminal assignment
04916AXX
1 2 3 4 5 6 7 8
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2X1
+MFZ23
MFP21
MFP22
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
A B
DG
ND A B
DG
ND
DG
ND
res.
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
PE
L1
L1
L2
L2
L3
L3
PE
≤ 4 mm (AWG10)
A
B
A
B
24V1
GND1
24V1
GND1
24V2
GND2
24V2
GND2
≤ 2.5 mm (AWG12)
0 1 2
2 2
X20 X21
res.
VP
PROFIBUS DP(1) (1)
2 x 24 VDC
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) EMC metal cable gland
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 - - Reserved
5 VP Output +5 V output (max. 10 mA) (only for test purposes)
6 A Output PROFIBUS-DP data line A (outgoing)
7 B Output PROFIBUS-DP data line B (outgoing)
8 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
9 - - Reserved
10 DGND - Reference potential for VP (terminal 5) (only for test purposes)
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
System Manual - Drive System for Decentralized Installation 149
8Connection with PROFIBUS
MFZ23 connection module with MFP21, MFP22 fieldbus module and one common 24 VDC voltage circuit
Terminal assignment
04917AXX
+MFZ23
MFP21
MFP22
(1) (1)
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
A B
DG
ND A B
DG
ND
DG
ND
res .
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
A
B
A
B
24V
GND
24V
GND
0 1 2
2X1
X20 X21re
s.
VP
PROFIBUS DP
≤ 4 mm (AWG10)≤ 2.5 mm (AWG12)2 2
1 x 24 VDC
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) EMC metal cable gland
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 - - Reserved
5 VP Output +5 V output (max. 10 mA) (only for test purposes)
6 A Output PROFIBUS-DP data line A (outgoing)
7 B Output PROFIBUS-DP data line B (outgoing)
8 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
9 - - Reserved
10 DGND - Reference potential for VP (terminal 5) (only for test purposes)
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
150 System Manual - Drive System for Decentralized Installation
Connection with PROFIBUS
MFZ23 connection module with MFP32 fieldbus module
Terminal assignment
04918AXX
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2X1
+MFZ23 MFP32
(1) (1)
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
A B
DG
ND A B
DG
ND
DG
ND
res.
24V
24V
GN
D
GN
D
res.
A
B
A
B
24V
GND
24V
GND
0X20 X21
res.
VP
PROFIBUS DP
res.
res.
res.
1
≤ 4 mm (AWG10)≤ 2.5 mm (AWG12)2 2
1 x 24 VDC
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) EMC metal cable gland
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 - - Reserved
5 VP Output +5 V output (max. 10 mA) (only for test purposes)
6 A Output PROFIBUS-DP data line A (outgoing)
7 B Output PROFIBUS-DP data line B (outgoing)
8 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
9 - - Reserved
10 DGND - Reference potential for VP (terminal 5) (only for test purposes)
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 - - Reserved
6 - - Reserved
7 - - Reserved
8 - - Reserved
System Manual - Drive System for Decentralized Installation 151
8Connection with PROFIBUS
Connecting MFZ26, MFZ28 Field Distributor with MFP...
MFZ26, MFZ28 connection modules connected with MFP21, MFP22 fieldbus module and two separate 24
VDC voltage circuits
Terminal assignment
04919AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) EMC metal cable gland(2) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
A B
DG
ND A B
DG
ND
res. VP
DG
ND
res.
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
A
B
A
B
24V1
GND1
24V1
GND1
24V2
GND2
24V2
GND2
2
(2)
X1
+
MFZ28
MFP21MFP22
MFZ26
(1)
0 1 2
1 2
PROFIBUSDP
≤ 2.5 mm (AWG12)2
(1)
2 x 24 VDC
X20
No. Name Direction Function
X20
1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 A Output PROFIBUS-DP data line A (outgoing)
5 B Output PROFIBUS-DP data line B (outgoing)
6 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
7 - - Reserved
8 VP Output +5 V output (max. 10 mA) (only for test purposes)
9 DGND - Reference potential for VP (terminal 8) (only for test purposes)
10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for voltage potential
18 GND2 - 0V24V reference potential for voltage potential
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
152 System Manual - Drive System for Decentralized Installation
Connection with PROFIBUS
MFZ26, MFZ28 connection module with MFP22 fieldbus module and one common 24 VDC voltage circuit
Terminal assignment
04922AXX
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
A B
DG
ND A B
DG
ND
res. VP
DG
ND
res.
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8 ≥ 10 mm(AWG8)
≤ 4 mm (AWG10)
A
B
A
B
24V
GND
24V
GND
0 1 2
1 2
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
22
PROFIBUSDP
≤ 2.5 mm (AWG12)2
(2)
+
MFZ28
MFP21MFP22
MFZ26
(1) (1)
1 x 24 VDC
X1
X20
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) EMC metal cable gland(2) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 A Output PROFIBUS-DP data line A (outgoing)
5 B Output PROFIBUS-DP data line B (outgoing)
6 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
7 - - Reserved
8 VP Output +5 V output (max. 10 mA) (only for test purposes)
9 DGND - Reference potential for VP (terminal 8) (only for test purposes)
10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for voltage potential
18 GND2 - 0V24V reference potential for voltage potential
System Manual - Drive System for Decentralized Installation 153
8Connection with PROFIBUS
MFZ26, MFZ28 connection module with MFP32 fieldbus module
Terminal assignment
04925AXX
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
A B
DG
ND A B
DG
ND
res. VP
DG
ND
res.
24V
24V
GN
D
GN
D
res.
res.
res.
res.
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≥ 10 mm(AWG8)
≤ 4 mm (AWG10)
A
B
A
B
24V
GND
24V
GND
0 1
1
22
PROFIBUSDP
≤ 2.5 mm (AWG12)2
(2)
+
MFZ28
MFP32
MFZ26
(1) (1)
1 x 24 VDC
X1
X20
0 = Potential level 0
1 = Potential level 1
(1) EMC metal cable gland(2) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 A Input PROFIBUS-DP data line A (incoming)
2 B Input PROFIBUS-DP data line B (incoming)
3 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
4 A Output PROFIBUS-DP data line A (outgoing)
5 B Output PROFIBUS-DP data line B (outgoing)
6 DGND - Data reference potential for PROFIBUS-DP (only for test purposes)
7 - - Reserved
8 VP Output +5 V output (max. 10 mA) (only for test purposes)
9 DGND - Reference potential for VP (terminal 8) (only for test purposes)
10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 - Reserved
16 V2I24 - Reserved
17 GND2- - Reserved
18 GND2 - Reserved
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
154 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Copper Line)
8.12 Connection with InterBus (Copper Line)
Types of the
InterBus Interface
The MFI can be connected to the remote bus as well as the installation remote bus. The
principal distinguishing feature between these types of interfaces can be found in the
structure of the bus cable. Normal remote bus cables consist of 2-core cables twisted
together in 3 pairs for data transmission. In the installation remote bus, the wires for data
transmission may be supplemented by the power supply for the MFI and active sensors.
Remote Bus
Connection
The typical remote bus connection for IP20 units involves a 9-pin sub D plug. The
following wiring examples show how MFIs are connected to units on the input or output
end using 9-pin sub D plugs.
05027AEN
MFI
MFI
MFI
MM
MM
MM
max. 400 m (max. 1,200 ft.)
INTERBUSMaster
max. 400 m (max. 1,200 ft.)
max. 12.8 km(max. 8 miles)
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
System Manual - Drive System for Decentralized Installation 155
8Connection with InterBus (Copper Line)
Line Type
D9-MFI (9-pin Sub
D to MFI)
The incoming remote bus is picked off from the preceding module using a 9-pin Sub D
plug.
Line Type
MFI-D9 (MFI to 9-
pin Sub D)
The subsequent InterBus module is connected using a 9-pin Sub D socket.
05120AXX
1122334455
66778899
DO/DODI
/DICOM
1627359
DO/DODI/DI
COM
16273
-
+24 VDCB
N
PK
GY
GN
YE
BN
PK
GY
GN
YE
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
MFZ11 (I B )NTER US
(1) (2) (2)
0 1
(5)(6)
(7)
(7)
(4)
X20
(3)
(1) Incoming remote bus cable(2) Connect shield of incoming/outgoing remote bus cable with EMC metal cable gland at MFZ housing(3) Outgoing remote bus cable(4) Assignment of terminals 19-36 starting on page 188(5) 9-pole Sub-D connector(6) 9-pole Sub-D socket(7) Strain relief
0 = Potential level 0
1 = Potential level 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
156 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Copper Line)
Installation
Remote Bus
Connection
An 8-core cable is used for the installation remote bus. In addition to the strands for
transmitting data, the cable also carries the 24 VDC supply voltage for the MFI bus
electronics and the active sensors.
The maximum number of modules which can be connected to an installation remote bus
terminal depends on the current consumption of the individual modules.
Line Type
CCO-I → MFI
(IP 65 Round
Connector → MFI
Terminals)
A special InterBus installation remote bus terminal is required in order to open an
installation remote bus segment. The installation remote bus can be connected to this
bus terminal (e.g. type IBS IP CBK 1/24F) using an IP 65 round plug connector (type
CCO-I).
05029AEN
MFIIBS IP CBK
MM
MFI
MM
MFI
MM
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
Installationremote bus
terminal
Incomingremote bus
Outgoing/continuingremote bus
24V supplyvoltage
Installation remote busmax. 50m
05122AXX
(1) IP 65 round connector(2) incoming installation remote bus cable(3) Connect shield of installation remote bus cable with an EMC cable gland on the
MFZ housing.(4) Assignment of terminals 19-36 starting on page 188
0 = Potential level 0
1 = Potential level 1
DO/DODI/DI
COM
RBST
1234
5
9
9
PE 6+24 V 7
0V 8
21 8
34 5
76
RDBU
YE/GN
BN
PK
GY
GN
YE
(2) (3)
(4)
(1)
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
0 1
MFZ11 (InterBus)
X20
System Manual - Drive System for Decentralized Installation 157
8Connection with InterBus (Copper Line)
MFZ11A Connection with MOVIMOT® (in combination with MFI21, MFI22, MFI23)
Terminal assignment
04927AXX
/DO
DO /DI
DI
CO
M
/DO
DO /DI
DI
CO
M
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
24V
RS
+
RS
-
GN
D 24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®MFZ11 (INTERBUS)
24 VDC
+ -
(2)
(1) (1)
(3)
0 1+MFZ11
MFI...
X20
0 = Potential level 0
1 = Potential level 1
(1) For separate assembly of MFZ11 / MOVIMOT®:Connect the shield of the RS-485 cable via an EMC metal cable gland on MFZ and MOVIMOT® housing.
(2) Ensure equipotential bonding between all bus stations.(3) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 /DO Input Incoming remote bus, negated data send direction (green)
2 DO Input Incoming remote bus, data send direction (yellow)
3 /DI Input Incoming remote bus, negated data receive direction (pink)
4 DI Input Incoming remote bus, data receive direction (gray)
5 COM - Reference potential (brown)
6 /DO Output Outgoing remote bus, negated data send direction (green)
7 DO Output Outgoing remote bus, data send direction (yellow)
8 /DI Output Outgoing remote bus, negated data receive direction (pink)
9 DI Output Outgoing remote bus, data receive direction (gray)
10 COM - Reference potential (brown)
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 24 V Output 24 V power supply for MOVIMOT®
16 RS+ Output Communications link to MOVIMOT® terminal RS+
17 RS- Output Communications link to MOVIMOT® terminal RS-
18 GND - 0V24 reference potential for MOVIMOT®
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
158 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Copper Line)
Connecting Field Distributor MFZ13 with MFI... (Installation Remote Bus Connection)
Line Type
CCO-I → MFI
IP 65 round connector → MFI terminals
A special InterBus installation remote bus terminal is required in order to open an
installation remote bus segment. The installation remote bus can be connected to this
bus terminal (e.g. type IBS IP CBK 1/24F) using an IP 65 round plug connector (type
CCO-I).
MFZ13 connection module with MFI21/MFI22 fieldbus module
04928AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) EMC metal cable gland(2) Incoming installation remote bus cable(3) Outgoing installation remote bus cable(4) IP 65 round connector
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8P
E
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
/DI
/DI
DI
DI
CO
M
CO
M
/DO
/DO
DO
DO
≤ 2.5 mm (AWG12) ≤ 4 mm (AWG10)
X1
X210 1 2
DO/DODI/DI
COM
RBST
1234
5
9
9
PE 6+24V 7
0V 8
21 8
34 5
76
RD
BU
YEGNGYPKBN
BU
RD
YE
/GN
YE/GN
Kl.3/X21Kl.1/X21Kl.2/X20Kl.1/XKl.4Kl.3Kl.5PE
20202020
/X/X/X
BN
PK
GY
GN
YE
24V2
GND2
24V2GND2
2
2 2+MFZ13
MFI21
MFI22
(1) (1)
(4)
(3)
(2)
X20
System Manual - Drive System for Decentralized Installation 159
8Connection with InterBus (Copper Line)
Terminal assignment
No. Name Direction Function
X20 1 /DO Input Incoming remote bus, negated data send direction (green)
2 DO Input Incoming remote bus, data send direction (yellow)
3 /DI Input Incoming remote bus, negated data receive direction (pink)
4 DI Input Incoming remote bus, data receive direction (gray)
5 COM - Reference potential (brown)
6 /DO Output Outgoing remote bus, negated data send direction (green)
7 DO Output Outgoing remote bus, data send direction (yellow)
8 /DI Output Outgoing remote bus, negated data receive direction (pink)
9 DI Output Outgoing remote bus, data receive direction (gray)
10 COM - Reference potential (brown)
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
160 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Copper Line)
MFZ13 connection module with fieldbus module MFI32
04929AXX
0 = Potential level 0
1 = Potential level 1
(1) EMC metal cable gland(2) Incoming installation remote bus cable(3) Outgoing installation remote bus cable(4) IP 65 round connector
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PE L1 L1 L2 L2 L3 L3 PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V
24V
GN
D
GN
D
res.
res.
res.
res./DI
/DI
DI
DI
CO
M
CO
M
/DO
/DO
DO
DO
X1
X20 X211
≤ 2.5 mm (AWG12)2 ≤ 4 mm (AWG10)2
0
DO/DODI/DI
COM
RBST
1234
5
9
9
PE 6+24V 7
0V 8
21 8
34 5
76
RD
BU
YEGNGYPKBN
BU
RD
YE
/GN
YE/GN
BN
PK
GY
GN
YE
2
Kl.3/X21Kl.1/X21Kl.2/X20Kl.1/XKl.4Kl.3Kl.5PE
20/X20/X20/X20
+MFZ13 MFI32
(1)
(4)
(3)
(2)
(1)
System Manual - Drive System for Decentralized Installation 161
8Connection with InterBus (Copper Line)
Terminal assignment
No. Name Direction Function
X20 1 /DO Input Incoming remote bus, negated data send direction (green)
2 DO Input Incoming remote bus, data send direction (yellow)
3 /DI Input Incoming remote bus, negated data receive direction (pink)
4 DI Input Incoming remote bus, data receive direction (gray)
5 COM - Reference potential (brown)
6 /DO Output Outgoing remote bus, negated data send direction (green)
7 DO Output Outgoing remote bus, data send direction (yellow)
8 /DI Output Outgoing remote bus, negated data receive direction (pink)
9 DI Output Outgoing remote bus, data receive direction (gray)
10 COM - Reference potential (brown)
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 - - Reserved
6 - - Reserved
7 - - Reserved
8 - - Reserved
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
162 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Copper Line)
Connecting MFZ16, MFZ18 Field Distributor with MFI... (Installation Remote Bus Connection)
Line type CCO-I
→ MFI
IP 65 round connector → MFI terminals
A special InterBus installation remote bus terminal is required in order to open an
installation remote bus segment. The installation remote bus can be connected to this
bus terminal (e.g. type IBS IP CBK 1/24F) using an IP 65 round plug connector (type
CCO-I).
MFZ16, MFZ18 connection modules with MFI21/MFI22 fieldbus module
04930AXX
0 = Potential level 0 (1) EMC metal cable gland(2) incoming installation remote bus cable(3) outgoing installation remote bus cable(4) IP 65 round connector(5) Assignment of terminals 19-36 starting on page 188
1 = Potential level 1
2 = Potential level 2
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
/DI
/DI
DI
DI
CO
M
CO
M
/DO
/DO
DO
DO
≤ 2.5 mm (AWG12)
0 1 2
1 2
DO/DODI/DI
COM
RBST
1234
5
9
9
PE 6+24V 7
0V 8
21 8
34 5
76
RD
BU
YEGNGYPKBN
BU
RD
YE
/GN
YE/GN
Kl.13Kl.11Kl.2Kl.1Kl.4Kl.3Kl.5PE
BNPK
GY
GN
YE
24V2
GND2
24V2GND2
2
2
+MFZ16
MFI21MFI22
MFZ18
(4)
(3)
(2)
(1)(1)
(5)
X1
X20
System Manual - Drive System for Decentralized Installation 163
8Connection with InterBus (Copper Line)
Terminal assignment
No. Name Direction Function
X20 1 /DO Input Incoming remote bus, negated data send direction (green)
2 DO Input Incoming remote bus, data send direction (yellow)
3 /DI Input Incoming remote bus, negated data receive direction (pink)
4 DI Input Incoming remote bus, data receive direction (gray)
5 COM - Reference potential (brown)
6 /DO Output Outgoing remote bus, negated data send direction (green)
7 DO Output Outgoing remote bus, data send direction (yellow)
8 /DI Output Outgoing remote bus, negated data receive direction (pink)
9 DI Output Outgoing remote bus, data receive direction (gray)
10 COM - Reference potential (brown)
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for actuators
18 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
164 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Copper Line)
MFZ16, MFZ18 connection modules with MFI32 fieldbus module
04931AXX
0 = Potential level 0
1 = Potential level 1
(1) EMC metal cable gland(2) Incoming installation remote bus cable(3) Outgoing installation remote bus cable(4) IP 65 round connector(5) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
1 2 3 4 5 6 7 8
PE L1 L1 L2 L2 L3 L3 PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V
24V
GN
D
GN
D
res.
res.
res.
res./DI
/DI
DI
DI
CO
M
CO
M
/DO
/DO
DO
DO
≤ 2.5 mm (AWG12)
0 1
1
DO/DODI/DI
COM
RBST
1234
5
9
9
PE 6+24V 7
0V 8
21 8
34 5
76
RD
BU
YEGNGYPKBN
BU
RD
YE
/GN
YE/GN
Kl.13Kl.11Kl.2Kl.1Kl.4Kl.3Kl.5PE
BN
PK
GY
GN YE
2
2
+MFZ16 MFI32
MFZ18
(4)
(3)
(2)
(1)(1)
(5)
X1
X20
System Manual - Drive System for Decentralized Installation 165
8Connection with InterBus (Copper Line)
Terminal assignment
No. Name Direction Function
X20 1 /DO Input Incoming remote bus, negated data send direction (green)
2 DO Input Incoming remote bus, data send direction (yellow)
3 /DI Input Incoming remote bus, negated data receive direction (pink)
4 DI Input Incoming remote bus, data receive direction (gray)
5 COM - Reference potential (brown)
6 /DO Output Outgoing remote bus, negated data send direction (green)
7 DO Output Outgoing remote bus, data send direction (yellow)
8 /DI Output Outgoing remote bus, negated data receive direction (pink)
9 DI Output Outgoing remote bus, data receive direction (gray)
10 COM - Reference potential (brown)
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 - - Reserved
16 - - Reserved
17 - - Reserved
18 - - Reserved
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
166 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Fiber Optic)
8.13 Connection with InterBus (Fiber Optic)
Connection of
Communication
and 24 VDC
Supply
• InterBus and 24 VDC supply are installed via rugged-line plug connector.
• The cable connectors are not part of the SEW scope of delivery (manufactured by
Phoenix-Contact).
• It is absolutely necessary to observe the project planning and installation
guidelines for the rugged-line connection technology of Phoenix-Contact.
Fitting the Bus
Cable Connector
The cable connectors can be connected to the bus module in four different ways (see
the following figure).
50326AXX
1) Fiber optic (InterBus remote bus)2) US1/US2 voltage supply
1
2
50323AXX
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
(1) (2)
(3) (4)
Remote OUT(X12)
Remote IN(X11)
Remote OUT(X12)
Remote IN(X11)
Remote OUT(X12)
Remote IN(X11)
Remote OUT(X12)
Remote IN(X11)
• Cable connectors may only be connected with de-energized equipment.
• Do not use the clip of the cable connector to pull the connector into the correct
position.
• Caution: Cable connectors not in use must be fitted with a dummy plug to
ensure the enclosure!
System Manual - Drive System for Decentralized Installation 167
8Connection with InterBus (Fiber Optic)
Assembly • Switch off the voltage.
• Open the clip (1.) and sufficiently insert the connector into the module electronics (2.)
• Close the clip (3.)
Disassembly • Switch off the voltage.
• Open the clip and pull the connector away from the module in the direction of the
cables.
Supply Voltage • The two available supply voltages are used as follows:
– US1: 24 VDC supply of bus logic, sensors and MOVIMOT®
– US2: Supply of actuators (for current consumption see Technical Data)
Contact
Assignment
50325AXX.eps
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
1.
2.
3.
50327AXX
IB DIAG
IB DIAG
RCRC
US1US1
DI0DI0
DI2DI2
DI4
DI1DI1
DI3DI3
DI5DI5
TRTR
US2US2
RDRD
MFI INTERBUS RL
MFI INTERBUS RL FO1
FO1
FO2FO2
SYS-FSYS-F
+US1 +US1
+US2US1
+US2US1
US2 US2
+US1 +US1
+US2US1
+US2US1
US2 US2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
168 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Fiber Optic)
Cable Installation Cabling for the plug connectors requires maintaining a distance that is dependent upon
the bending radius of the cable type being used (observe the project planning and
installation guidelines for rugged-line connection technology from Phoenix-Contact).
Line Lengths < 1 m Line lengths < of 1 m are only permitted using the special pre-fabricated IBS RL
CONNECTION-LK cable link (observe the project planning and installation guidelines
for rugged-line connection technology from Phoenix-Contact).
50329AXX
Rmin
Rmin
System Manual - Drive System for Decentralized Installation 169
8Connection with InterBus (Fiber Optic)
Sample Topology
of an InterBus
Design with
Rugged-Line
04800AEN
INTERBUS-
Interface module
Remote bus spur line
Re
mo
teb
us
Re
mo
teb
us
(ma
x.
12
.8km
inco
pp
er
an
dp
oly
me
rfib
er)
Re
mo
teb
us
Bus
segm
ent
(max.400
min
copper
Max.35m
/50m
inpoly
mer
fiber)
Rem
ote
bus
Rem
ote
bus
Rugged-Line bus terminal
Dummyconnector
MFI. 3BMFI. 3B
Dummyconnector
MFI. 3BMFI. 3B
MFI. 3B
If fiber optic cables are installed as permanent polymer fibers, a maximum distance of
50 m can be linked between two remote bus stations. If flexible polymer fibers are used,
the maximum distance is 35 m.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
170 System Manual - Drive System for Decentralized Installation
Connection with InterBus (Fiber Optic)
MFZ11A Connection with MOVIMOT® (in combination with MFI23 and MFI33)
Terminal assignment
04782AXX
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
res.
RS
+
RS
-
GN
D
0 1
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®MFZ11 (I B )NTER US
(2)
(3)
(1) (1)
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
X20
+MFZ11
MFI23MFI33
0 = Potential level 0
1 = Potential level 1
(1) For separate assembly of MFZ11 / MOVIMOT®:Connect the shield of the RS-485 cable via an EMC metal cable gland on MFZ and MOVIMOT® housing.
(2) Ensure equipotential bonding between all bus stations.(3) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 - 14 – – Reserved
15 24 V Output 24 V power supply for MOVIMOT®
16 RS+ Output Communications link to MOVIMOT® terminal RS+
17 RS- Output Communications link to MOVIMOT® terminal RS-
18 GND – 0V24 reference potential for MOVIMOT®
System Manual - Drive System for Decentralized Installation 171
8Connection with InterBus (Fiber Optic)
Connecting MFZ13 Field Distributor with MFI23 + MFI33
Connecting MFZ16, MFZ18 Field Distributor with MFI23 + MFI33
04784AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
1 2 3 4 5 6 7 8 9 10 1 2 3 3 4 5 6 7
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
res.
res.
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
≤ 2.5 mm (AWG12) ≤ 4 mm (AWG10)
X1
X210 1 2
2
2 2
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
+MFZ13 MFI23
MFI33
X20
04786AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
res.
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
≤ 2.5 mm (AWG12)
0 1 2
1 2
2
2
(1)
X1
X20+MFZ16
MFZ18
MFI23MFI33
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
172 System Manual - Drive System for Decentralized Installation
Connection with DeviceNet
8.14 Connection with DeviceNet
DeviceNet
Connection
Capabilities
The MFD can be connected either via a multi-port or via a T-connector. If the connection
with MFD is removed, the remaining stations will not be influenced, and the bus can
remain active.
05028AEN
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
T-connector T-connector T-connector
Multi-Port
Bus terminatingresistor
MFD
MFD
MFD
MFD
MFD
MFD
Bus terminatingresistor
120
System Manual - Drive System for Decentralized Installation 173
8Connection with DeviceNet
MFZ31 Connection with MOVIMOT® (in combination with DeviceNet)
Terminal
assignment
04932AXX
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
24V
RS
+
RS
-
GN
D
0 1
MFZ31 (DeviceNet)
24 VDC
+ -
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®(3)
+MFZ31
MFD...
(2)
(1) (1)
X11
X20
0 = Potential level 0
1 = Potential level 1
(1) For separate assembly of MFZ31 / MOVIMOT®:Connect the shield of the RS-485 cable via an EMC metal cable gland on MFZ and MOVIMOT® housing.
(2) Ensure equipotential bonding between all bus stations.(3) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6 - - Reserved
7 - - Reserved
8 - - Reserved
9 - - Reserved
10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 24 V Output 24 V power supply for MOVIMOT®
16 RS+ Output Communications link to MOVIMOT® terminal RS+
17 RS- Output Communications link to MOVIMOT® terminal RS-
18 GND - 0V24 reference potential for MOVIMOT®
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
174 System Manual - Drive System for Decentralized Installation
Connection with DeviceNet
Connecting MFZ33 Field Distributor with MFD...
MFZ33 connection module with MFD21, MFD22 fieldbus module and two separate 24 VDC voltage circuits
Terminal assignment
05008AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
1 2 3 4 5 6 7 8
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2X1
+MFZ33
MFD21
MFD22
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
PE
L1
L1
L2
L2
L3
L3
PE
≤ 4 mm (AWG10)
24V1
GND1
24V1
GND1
24V2
GND2
24V2
GND2
≤ 2.5 mm (AWG12)
0 1 2
2 2
X20
X11
X21
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
2 x 24 VDC
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6-10 - - Reserved
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
System Manual - Drive System for Decentralized Installation 175
8Connection with DeviceNet
MFZ33 connection module with MFD21, MFD22 fieldbus module and one common 24 VDC voltage circuit
Terminal
assignment
05009AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
+MFZ33
MFD21
MFD22
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V
GND
24V
GND
0 1 2
2X1
X20
X11
X2≤ 4 mm (AWG10)≤ 2.5 mm (AWG12)2 2
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
1 x 24 VDC
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6-10 - - Reserved
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
176 System Manual - Drive System for Decentralized Installation
Connection with DeviceNet
MFZ33 connection module with MFD32 fieldbus module
Terminal
assignment
05010AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2X1
+MFZ33 MFD32
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
24V
24V
GN
D
GN
D
res.
24V
GND
24V
GND
0X20 X21
res.
res.
res.
1
≤ 4 mm (AWG10)≤ 2.5 mm (AWG12)2 2
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
1 x 24 VDC
X11
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6-10 - - Reserved
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5-8 - - Reserved
System Manual - Drive System for Decentralized Installation 177
8Connection with DeviceNet
Connecting MFZ36, MFZ38 Field Distributor with MFD
MFZ36, MFZ38 connection modules with MFD21, MFD22 fieldbus module and two separate 24 VDC voltage
circuits
Terminal
assignment
04996AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2
(1)
X1
0 1 2
1 2
≤ 2.5 mm (AWG12)2
+
MFZ38
MFD21MFD22
MFZ36
2 x 24 VDC
X20
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
24V1
GND1
24V1
GND1
24V2
GND2
24V2
GND2
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
X11
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6-10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuator (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for actuators
18 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
178 System Manual - Drive System for Decentralized Installation
Connection with DeviceNet
MFZ36, MFZ38 connection modules with MFD21, MFD22 fieldbus module and one common 24 VDC voltage
circuit:
Terminal
assignment
04997AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) Assignment of terminals 19-36 starting on page 188
(1)
X1
+
MFZ38
MFD21MFD22
MFZ36
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8 ≥ 10 mm(AWG8)
≤ 4 mm (AWG10)
24V
GND
24V
GND
0 1 2
1 2
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
22
≤ 2.5 mm (AWG12)2
1 x 24 VDC
X20
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
X11
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6- 10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for actuators
18 GND2 - 0V24V reference potential for actuators
System Manual - Drive System for Decentralized Installation 179
8Connection with DeviceNet
MFZ36, MFZ38 connection modules with MFD32 fieldbus module
Terminal
assignment
04998AXX
0 = Potential level 0
1 = Potential level 1
(1) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
res.
res.
res.
res.
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≥ 10 mm(AWG8)
≤ 4 mm (AWG10)
24V
GND
24V
GND
4
21
35
1:2:3:4:5:
DRAINV+V-CAN_HCAN_L
0 1
1
22
≤ 2.5 mm (AWG12)2
+MFZ36 MFD32
MFZ38
(1)
X1
1 x 24 VDC
X11
X20
No. Name Direction Function
X20 1 V- Input DeviceNet reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 DRAIN Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 V+ Input DeviceNet power supply 24 V
6-10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15-18 - - Reserved
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
180 System Manual - Drive System for Decentralized Installation
Connection with CANopen
8.15 Connection with CANopen
CANopen
Connection
Capabilities
MFO is connected via T connector. If the connection with MFO is removed, the
remaining stations will not be influenced, and the bus can remain active.
open
05086AXX
(1) Bus terminating resistor 120 Ω(2) T connector
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
MF
IIN
TE
RB
US
SYS-F
RD
TR
BA
RC
UL
(2)
(1)
(1)
MFO
MFO
MFO
MFO
MFO
MFO
(1)
(2)
(2)
(2)
(2)
(2)
(2)
System Manual - Drive System for Decentralized Installation 181
8Connection with CANopen
MFZ31 Connection with MOVIMOT® (in combination with CANopen)
Terminal
assignment
05011AXX
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
24V
RS
+
RS
-
GN
D
0 1
MFZ31 (CANopen)
24 VDC
+ -
4
21
35
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
24V
R L f1/f2
K1a
K1b
RS
-R
S+
MOVIMOT®(3)
+MFZ31
MFO...
(2)
(1) (1)
X20
X11
0 = Potential level 0
1 = Potential level 1
(1) For separate assembly of MFZ31 / MOVIMOT®:Connect the shield of the RS-485 cable via an EMC metal cable gland on MFZ and MOVIMOT® housing.
(2) Ensure equipotential bonding between all bus stations.(3) Assignment of terminals 19-36 starting on page 188
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24V
6 - - Reserved
7 - - Reserved
8 - - Reserved
9 - - Reserved
10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 24 V Output 24 V power supply for MOVIMOT®
16 RS+ Output Communications link to MOVIMOT® terminal RS+
17 RS- Output Communications link to MOVIMOT® terminal RS-
18 GND 0V24 reference potential for MOVIMOT®
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
182 System Manual - Drive System for Decentralized Installation
Connection with CANopen
Connecting MFZ33 Field Distributor with MFO...
MFZ33 connection module with MFO21, MFO22 fieldbus module and two separate 24 VDC voltage circuits
Terminal
assignment
05052AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
1 2 3 4 5 6 7 8
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2X1
+MFZ33
MFO21
MFO22
2 x 24 VDC
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
PE
L1
L1
L2
L2
L3
L3
PE
≤ 4 mm (AWG10)
24V1
GND1
24V1
GND1
24V2
GND2
24V2
GND2
≤ 2.5 mm (AWG12)
0 1 2
2 2
X20
X11
X21
4
21
35
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24V
6-10 - - Reserved
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
System Manual - Drive System for Decentralized Installation 183
8Connection with CANopen
MFZ33 connection module with MFO21, MFO22 fieldbus module and one common 24 VDC voltage circuit
Terminal
assignment
05053AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
+MFZ33
MFO21
MFO22
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V
GND
24V
GND
0 1 2
2X1
X20
X11
X21≤ 4 mm (AWG10)≤ 2.5 mm (AWG12)2 2
4
21
35
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
1 x 24 VDC
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24V
6-10 - - Reserved
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5 V2I24 Input 24 V power supply for actuators (digital outputs)
6 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X21/5
7 GND2 - 0V24V reference potential for actuators
8 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
184 System Manual - Drive System for Decentralized Installation
Connection with CANopen
MFZ33 connection module with MFO32 fieldbus module
Terminal
assignment
05054AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)2X1
+MFZ33 MFO32
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8
24V
24V
GN
D
GN
D
res.
24V
GND
24V
GND
0X20
X11
X21
res.
res.
res.
1
≤ 4 mm (AWG10)≤ 2.5 mm (AWG12)2 2
4
21
35
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
1 x 24 VDC
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24 V
6-10 - - Reserved
X21 1 24 V Input 24 V power supply for module electronics and sensors
2 24 V Output 24 V power supply (jumpered with terminal X21/1)
3 GND - 0V24 reference potential for module electronics and sensors
4 GND - 0V24 reference potential for module electronics and sensors
5-8 - - Reserved
System Manual - Drive System for Decentralized Installation 185
8Connection with CANopen
Connecting MFZ36, MFZ38 Field Distributor with MFO
MFZ36, MFZ38 connection modules with MFO21, MFO22 fieldbus module and two separate 24 VDC voltage
circuits
Terminal
assignment
05012AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≤ 4 mm (AWG10)
24V1
GND1
24V1
GND1
24V2
GND2
24V2
GND2
2
(1)
0 1 2
1 2
≤ 2.5 mm (AWG12)2
4
21
35
+
MFZ38
MFO21MFO22
MFZ36
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
2 x 24 VDC
X20
X11
X1
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24 V
6-10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for actuators
18 GND2 - 0V24V reference potential for actuators
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
186 System Manual - Drive System for Decentralized Installation
Connection with CANopen
MFZ36, MFZ38 connection modules with MFO21, MFO22 fieldbus module and one common 24 VDC voltage
circuit:
Terminal
assignment
05013AXX
0 = Potential level 0
1 = Potential level 1
2 = Potential level 2
(1) Assignment of terminals 19-36 starting on page 188
(1)
+
MFZ38
MFO21MFO22
MFZ36
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
V2I
24
V2I
24
GN
D2
GN
D2
1 2 3 4 5 6 7 8 ≥ 10 mm(AWG8)
≤ 4 mm (AWG10)
24V
GND
24V
GND
4
21
35
0 1 2
1
X1
X20
2
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
22
≤ 2.5 mm (AWG12)2
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
1 x 24 VDC
X11
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24 V
6-10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15 V2I24 Input 24 V power supply for actuators (digital outputs)
16 V2I24 Output 24 V power supply for actuators (digital outputs) jumpered with terminal X20/15
17 GND2 - 0V24V reference potential for actuators
18 GND2 - 0V24V reference potential for actuators
System Manual - Drive System for Decentralized Installation 187
8Connection with CANopen
MFZ36, MFZ38 connection modules with MFO32 fieldbus module
Terminal
assignment
05014AXX
0 = Potential level 0
1 = Potential level 1
(1) Assignment of terminals 19-36 starting on page 188
1
19
2
20
3
21
4
22
5
23
6
24
7
25
8
26
9
27
10
28
11
29
12
30
13
31
14
32
15
33
16
34
17
35
18
36
24V
24V
GN
D
GN
D
res.
res.
res.
res.
1 2 3 4 5 6 7 8
PE
L1
L1
L2
L2
L3
L3
PE
L3
L2
L1
PE
L3
L2
L1
PE
≥ 10 mm(AWG8)
≤ 4 mm (AWG10)
24V
GND
24V
GND
4
21
35
0 1
1
22
≤ 2.5 mm (AWG12)2
+MFZ36 MFO32
MFZ38
(1)
1:2:3:4:5:
CAN_SHLDCAN_V+CAN_GNDCAN_HCAN_L
1 x 24 VDC
X1
X20
X11
No. Name Direction Function
X20 1 CAN_GND Input CANopen reference potential 0V24
2 CAN_L Input/output CAN_L data line
3 CAN_SHLD Input Equipotential bonding
4 CAN_H Input/output CAN_H data line
5 CAN_V+ Input CANopen voltage supply 24 V
6-10 - - Reserved
11 24 V Input 24 V power supply for module electronics and sensors
12 24 V Output 24 V power supply (jumpered with terminal X20/11)
13 GND - 0V24 reference potential for module electronics and sensors
14 GND - 0V24 reference potential for module electronics and sensors
15-18 - - Reserved
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
188 System Manual - Drive System for Decentralized Installation
Connecting Inputs/Outputs (I/O) of MF.. Fieldbus Interfaces
8.16 Connecting Inputs/Outputs (I/O) of MF.. Fieldbus Interfaces
Connection via
Terminals with..MFZ21
MFZ26
MFZ28
in combination withMFP21
MFP22
MFZ11
MFZ16
MFZ18
in combination withMFI21
MFI22
MFI23
MFZ31
MFZ36
MFZ38
in combination withMFD21
MFD22
MFO21
MFO22
04933AEN
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
DI 0
GN
D
VO
24
DI 1
GN
D
VO
24
DI 2
GN
D
VO
24
DI 3
GN
D
VO
24
DO
0
GN
D2
DO
1
GN
D2
GN
D2
1 2X20
MFI23B only: reservedall other MF.. modules: V2I24
1 = Potential level 1
2 = Potential level 2
No. Name Direction Function
X20 19 DI0 Input Switching signal from sensor 1
20 GND - 0V24 reference potential for sensor 1
21 V024 Output 24 V power supply for sensor 1
22 DI1 Input Switching signal from sensor 2
23 GND - 0V24 reference potential for sensor 2
24 V024 Output 24 V power supply for sensor 2
25 DI2 Input Switching signal from sensor 3
26 GND - 0V24 reference potential for sensor 3
27 V024 Output 24 V power supply for sensor 3
28 DI3 Input Switching signal from sensor 4
29 GND - 0V24 reference potential for sensor 4
30 V024 Output 24 V power supply for sensor 4
31 DO0 Output Switching signal from actuator 1
32 GND2 - 0V24 reference potential for actuator 1
33 DO1 Output Switching signal from actuator 2
34 GND2 - 0V24 reference potential for actuator 2
35 V2I24 Input24 V power supply for actuatorsonly with MFI23B: Reservedonly with MFZ.6 and MFZ.8: jumpered with terminal 15 or 16
36 GND2 - 0V24 reference potential for actuatorsonly with MFZ.6 and MFZ.8: jumpered with terminal 17 or 18
System Manual - Drive System for Decentralized Installation 189
8Connecting Inputs/Outputs (I/O) of MF.. Fieldbus Interfaces
Connection via
Terminals with…MFZ21
MFZ26
MFZ28
in combination with MFP32
MFZ11
MFZ16
MFZ18
in combination with MFI32 MFI33
MFZ31
MFZ36
MFZ38
in combination with MFD32 MFO32
04934AXX
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
DI 0
GN
D
VO
24
DI 1
GN
D
VO
24
DI 2
GN
D
VO
24
DI 3
GN
D
VO
24
DI 4
GN
D
DI 5
GN
D
res.
GN
D
1X20
1 = Potential level 1
No. Name Direction Function
X20 19 DI0 Input Switching signal from sensor 1
20 GND - 0V24 reference potential for sensor 1
21 V024 Output 24 V power supply for sensor 1
22 DI1 Input Switching signal from sensor 2
23 GND - 0V24 reference potential for sensor 2
24 V024 Output 24 V power supply for sensor 2
25 DI2 Input Switching signal from sensor 3
26 GND - 0V24 reference potential for sensor 3
27 V024 Output 24 V power supply for sensor 3
28 DI3 Input Switching signal from sensor 4
29 GND - 0V24 reference potential for sensor 4
30 V024 Output 24 V power supply for sensor 4
31 DI4 Input Switching signal from sensor 5
32 GND - 0V24 reference potential for sensor 5
33 DI5 Input Switching signal from sensor 6
34 GND - 0V24 reference potential for sensor 6
35 res. - Reserved
36 GND - 0V24 reference potential for sensors
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
190 System Manual - Drive System for Decentralized Installation
Connecting Inputs/Outputs (I/O) of MF.. Fieldbus Interfaces
Connection via M12 Connector with MF.22 / MFI23
Notes • Connect sensors / actuators using either M12 sockets or terminals
• When using the outputs: Connect 24 V to V2I24 / GND2.
• Connect dual channel sensors/actuators to DI0, DI2, and DO0. DI1, DI3, and DO1
can then no longer be used.
01799BXX
1
5
43
2
01800BEN
Caution: Connections which are not used must be fitted with M12 closing caps in
order to guarantee degree of protection IP 65!
System Manual - Drive System for Decentralized Installation 191
8Connecting Inputs/Outputs (I/O) of MF.. Fieldbus Interfaces
Connection via M12 Connector with MF.32 / MFI33
Notes • Connect sensors using either M12 sockets or terminals
• Connect dual channel sensors to DI0, DI2, and DI4. DI1, DI3, and DI5 can then no
longer be used.
01799BXX
1
5
43
2
01801BEN
DIO DI2 DI4
DI3 DI5DI1
24 V (V024) 24 V (V024)
24 V (V024)24 V (V024)
GND GND GND
GND GND GND
DI1 DI3 DI5
24 V (V024)
24 V (V024)
Input DI2 Input DI4
Input DI3 Input DI5
Input DI0
Input DI1
Caution: Connections which are not used must be fitted with M12 closing caps in
order to Enclosure IP 65 protection!
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
8
192 System Manual - Drive System for Decentralized Installation
Connection of Pre-Fabricated Cables
8.17 Connection of Pre-Fabricated Cables
Connection between MF.../Z.3. or MF.../Z.6. Field Distributor and MOVIMOT® (Part No. 0186 725 3)
Assignment
Observe Release
of Direction of
Rotation
03046AXX
MOVIMOT® terminal Core color / designation
L1 black / L1
L2 black / L2
L3 black / L3
24 V red / 24 V
⊥ white / 0 V, white / 0 V
RS+ orange / RS+
RS- green / RS-
PE terminal green-yellow + shield end
Both directions of rotation are enabled.
Only counterclockwise direction of rotation is enabled.Setpoint entries for clockwise rotation. result in standstill of drive.
Only clockwise direction of rotation is enabled.Setpoint entries for counterclockwise. rotation result in standstill of drive.
Drive is inhibited or brought to a stop.
24V
LR LR24V
LR24V
LR24V
System Manual - Drive System for Decentralized Installation 193
8Connection of Pre-Fabricated Cables
Connection between MF.../Z.8. Field Distributor and AC Motors (Part No. 0186 742 3)
Assignment
03047AXX
Motor terminal Core color / designation
U1 black / U1
V1 black / V1
W1 black / W1
13 red / 13
14 white / 14
15 blue / 15
TH black / 1
TH black / 2
PE terminal green-yellow + shield end (inside shield)
Connect overall shield via an EMC metal cable gland to the housing of the motor
terminal box.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22