NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Inspection Type Last EditedTime InInspectionId
MORRIS HEIGHTS EDUCATIONAL COMPLEX - BRONX, 1780 DR MARTIN LUTHER KING JR BLVD, BRONX, NY, 10453School:
2844 2019-03-07 07:11AM 2019-06-27 10:15AMARCHITECTURAL - ASSOCIATE
2923 2019-03-07 07:33AM 2019-03-26 03:26PMARCHITECTURAL - SENIOR
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Amanda Blatter
Principal Organization P.S. 204 - Bronx
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments:
1- All spaces are either too hot or too cold and the climate
controls need adjusting or replacement.
2- The BMS system is not reliable and this needs to be addressed.
Principal Name Shante Chunn
Principal Organization X723 SPED - Bronx
Meeting with Principal? No
Principal Feedback The Unit Coordinator provided the information on the
Questionnaire on behalf of the Principal, and provided the
following comment; The Walls throughout the school are
tarnished and needs to be repainted.
Custodian Was not present
Fireman Christian Perez
Building Square Footage 98,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 4+B+ PH
Comments on the Year Built 2010
Comments on the Student Population 628
Comments on the Staff Population 112
Comments on the Number of Classrooms 33
Weather Fair
Facade Photo
Corner of University Avenue and Macombs Road - West View
Page 1 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural InspectionMain Entrance Photo
Facade A - University Ave
Roof Photo
Roof - Northeast View
No System UpgradedHave any Systems/Major Building Components been upgraded?
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoYesExterior Ramps and Railings
Interior Routes
Page 2 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
NoArt Rooms
Auditorium
Yes Yes1st Floor
Cafeteria
Yes YesBasement
Classrooms
Yes Yes1st to 4th Floors
NoComputer Rooms
Gymnasium
Yes Yes3rd Floor
Library
Yes YesRoom 426
Main Office
Yes YesRooms 101 ( P723X @ P338X) and 124
( P.S. 204)
NoMulti-purpose Room
Nurse's Office
Yes YesRoom 227
NoPool
Science Lab
Yes YesRoom 401 and 405,
Toilet Rooms (boys)
Yes YesBasement to 4th Floors
Toilet Rooms (girls)
Yes YesBasement to 4th Floors
Toilet Rooms (staff)
Yes YesBasement to 4th Floors
Page 3 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on AW1 Inspected
2- Between Good and FairInstance Condition
Instance Quantity 1
Instance Quantity Uom EACH
No deficiencies recordedDeficiency
Does not existAWNINGS AND CANOPIES
Does not existCHIMNEY
InspectedCOPING
Condition 3- Fair
CAST STONE:OPEN TRANSVERSE JOINTS WITH
DAMAGED CAULKING
Deficiency
Deficiency Location/Instance
90Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 4 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
EXTERIOR
COPING
Deficiency Photo 1
Facade B
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL CLAD:DETERIORATED DOOR AND FRAME -
MINOR DETERIORATION
Deficiency
Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Door B01 shown, similar condition at Exit 6
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR WALLS
Masonry, OtherMaterial Type(s)
27,000Replacement Quantity
Page 5 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Replacement Uom S.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 27,000
Instance Quantity Uom S.F.
BRICK:MINOR CRACKS AND SPALLINGDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A, B, C
40Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
250Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
Page 6 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
Masonry, OtherMaterial Type(s)
2,900Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 2,900
Instance Quantity Uom CF
No deficiencies recordedDeficiency
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 20,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF BARRIER
Does not existROOF CAGE
Does not existROOF FENCE
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on IRMA:All Roofs Inspected
2- Between Good and FairInstance Condition
Instance Quantity 20,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2010
Source of Installation Year Documented
IRMA:ROOFING:MAJOR ACTIVE ROOF LEAKS IN
INSTRUCTIONAL SPACE
Deficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT
REMOVAL
PRIORITY 5Urgency of Action
Page 7 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 426
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
DETERIORATEDDeficiency
Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 - Facade I
Violations No violations recorded
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 3- Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Page 8 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade G
Violations No violations recorded
InspectedRAILINGS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTAIRS/RAMPS
Condition 2- Between Good and Fair
CONCRETE:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Ramp
Violations No violations recorded
InspectedWINDOWS
13,000Replacement Quantity
Replacement Uom S.F.
Page 9 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
EXTERIOR
WINDOWS
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum, Other
Instance on Aluminum - Other:All Facades Inspected
2- Between Good and FairInstance Condition
Instance Quantity 13,000
Instance Quantity Uom S.F.
Installation Year 2010
Source of Installation Year Documented
No deficiencies recordedDeficiency
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (378 Seats) Inspected
Ceiling
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (378 Seats) Does not exist
Fixed Seating
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor (378 Seats) Does not exist
Stage
Instance on 1st Floor (378 Seats) Inspected
Stage
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
Page 10 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Curtains
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor (378 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (378 Seats) Does not exist
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Does not exist
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Corridor near Room 426Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 11 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo 1
Corridor near Room 426
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
GYMNASIUM
Instance on 3rd Floor Inspected
Ceiling
Instance on 3rd Floor Does not exist
Door(s)
Instance on 3rd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 3rd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 3rd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on 3rd Floor Inspected
4- Between Fair and PoorInstance Condition
INOPERABLE BLEACHERSDeficiency
West, East Sides of RoomDeficiency Location/Instance
360Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 12 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Seating
Deficiency Photo 1
West Side of Room
Violations No violations recorded
Sliding-folding Partition
Instance on 3rd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage
Instance on 3rd Floor Does not exist
Walls
Instance on 3rd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 3rd Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 426 Inspected
Built-in Furnishing
Instance on Room 426 Does not exist
Ceiling
Page 13 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
INTERIOR
LIBRARY
Ceiling
Instance on Room 426 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 426 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 426 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 426 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LOCKER ROOM
Instance on Room 305 - Girls Inspected
YesAlternative Use
Instance on Room 327 - Boys Inspected
YesAlternative Use
Ceiling
Instance on Room 305 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 327 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 305 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 327 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 305 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 327 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Locker Room Lockers
Instance on Room 305 - Girls Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 327 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 305 - Girls Inspected
Page 14 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Walls
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 327 - Boys Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
SCIENCE LAB
Instance on Room 401 Inspected
YesAlternative Use
Instance on Room 405 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 401 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 405 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE PREP ROOM
Instance on Room 403 Inspected
YesAlternative Use
Instance on Room 407 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 403 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Room 407 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
Page 15 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
No deficiencies recordedDeficiency
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existStalls
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
Page 16 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
SITE
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
Does not existDRAINAGE SYSTEM FOR CONCRETE
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedSite Sidewalks & Walkways
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existConcrete
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
4- Between Fair and PoorCondition
CRACKS - MAJORDeficiency
SchoolyardDeficiency Location/Instance
550Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 17 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
SITE
PAVING
Student Use
Asphalt
Schoolyard
Violations No violations recorded
Does not existConcrete
Does not existPavers
InspectedPLAYGROUNDS
Adjacent to Harrison AvenueInstance
Benches
Instance on Adjacent to Harrison Avenue Does not exist
Fence
Instance on Adjacent to Harrison Avenue Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Pavement
Instance on Adjacent to Harrison Avenue Does not exist
Play Equipment
Instance on Adjacent to Harrison Avenue Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on Adjacent to Harrison Avenue Inspected
3- FairInstance Condition
DETERIORATED/MISSINGDeficiency
PlaygroundDeficiency Location/Instance
225Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Playground
Violations No violations recorded
Unpaved Area
Instance on Adjacent to Harrison Avenue Does not exist
Does not existPLAYING SURFACE
InspectedRETAINING WALLS
Condition 2- Between Good and Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
No deficiencies recordedDeficiency
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 2- Between Good and Fair
Page 18 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X338Architectural Inspection
Question Response
SITE
STAIRS/RAMPS: EXTERIOR
Railings
No deficiencies recordedDeficiency
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Near Exit 5Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Exit 5
Violations No violations recorded
InspectedStairs/ramps
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 19 of 19 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)