Monolithic acoustic ceiling Installation guidelines OWAplan

28
Monolithic acoustic ceiling Installation guidelines OWAplan OWAplan OWAconsult collection

Transcript of Monolithic acoustic ceiling Installation guidelines OWAplan

Page 1: Monolithic acoustic ceiling Installation guidelines OWAplan

Monolithic acoustic ceiling Installation guidelines OWAplan

OWAplan

OWAconsult collection

Page 2: Monolithic acoustic ceiling Installation guidelines OWAplan
Page 3: Monolithic acoustic ceiling Installation guidelines OWAplan

3Table of contents

1. General information on installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �4

2. Requirements for installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �52�1 Requirements prior to installation of the OWAplan ceiling:� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �52�2 Requirements during installation of the OWAplan ceiling: � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �62�3 Final inspection of the OWAplan ceiling � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �6

3. Grid, OWAplan70/OWAplan90 boards and plaster systems � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �73�1 Grid � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �73�2 OWAplan70/OWAplan90 boards� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �7

3�2�1 Absorption properties � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �73�3 Plaster systems � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �8

3�3�1 OWAplan S plaster system, white� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �83�3�2 OWAplan XS plaster system, white � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �83�3�3 OWAplan color plaster system � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �8

3�4 System-compatible components and accessories � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �83�5 Bevelled installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �9

4. Installation instructions � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �104�1 Installation of the first layer (supporting grid)� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �104�2 Installation of the second layer (tile grid) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �114�3 Installation of angle profile (no� 51/22 resp� no� 51/27) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �114�4 Installation of the OWAplan70/90 boards � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �124�5 Comfort access flaps no� 8031/9, no� 8031/10, no� 8031/11 and no� 8031/12 � � � � � � � � � � � � � � � � � � � � �134�6 Mounting frame no� 8069/6� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �164�7 Connection to wall, gypsum frieze, bulkhead and folded gypsum� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �16

5. Installing fire protection ceiling REI 60 under steel beam floors acc. to EN 13501-2� � � � � �185�1 Grid and grid spacings for installing fire protection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �185�2 Installation instructions for fire protection version� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �19

5�2�1 Suspension depth � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �195�2�2 Tile screw spacing � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �195�2�3 Wall connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �195�2�4 Components � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �19

6. Required materials � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20

7. Instructions for plaster coating � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 227�1 OWAplan S, white plaster system � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22

7�1�1 OWAplan S, white plaster system materials � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 227�1�2 Description for coating � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 227�1�3 Application quantity / basis weight (wet application) OWAplan S, white on plaster base plate � � 227�1�4 OWAplan S, white plaster applicator � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 22

7�2 OWAplan XS, white plaster system � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 237�2�1 OWAplan XS, white plaster system materials � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 237�2�2 Description for coating� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 237�2�3 Application quantity / basis weight (wet application) OWAplan XS, white on plaster base plate � 247�2�4 Plaster applicator for OWAplan XS, white � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 24

7�3 OWAplan color plaster system � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 247�3�1 OWAplan color plaster system materials � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 247�3�2 Description of the coating � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 257�3�3 Application quantity/weight (wet application) OWAplan color on ceiling board � � � � � � � � � � � � � 257�3�4 Plaster applicator for OWAplan color � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 25

Page 4: Monolithic acoustic ceiling Installation guidelines OWAplan

4 OWAplan

1� General information on installation

OWAplan is a special high-quality ceiling system whose appearance is largely determined by the installation of the grid and plaster system� Installing and covering this ceiling system requires appropriate experience and knowledge in seamless plaster-covered ceilings� OWA therefore offers a training course on how to install an OWAplan ceiling� The training course covers the entireprocess, from assembling the grid, fitting the mineral boards, taping and jointing, to the various plaster coatings� If the installation of the grid and the mineral boards is not to be carried out by a certified coating company, detailed and extensive step by step instructions must be provided in advance by the responsible technical advisor or OWAplan technician, Kevin Fischer� Training dates need to be arranged in good time with OWA� Contact by telephoning: +49 9373 201-450 or -304� Since this is a certified building product training can only be provided if all system components being used are OWA products�

Classification of fire behaviour as a building product OWAplan seamless acoustic plaster ceiling S 7 has been classified as A2-s1,d0 - non-combustible in compliance with EN 13501-1 and is CE marked as a ceiling-KIT� The quantities to be applied as specified in the relevant test report and the system components listed there must be adhered to and applied� If other non-tested system components are used, the system characteristics of the OWAplan70/90 building product cannot be guaranteed�

Labelling in accordance with the Construction Products Regulation (EU-BauPV) S 7 OWAplan has been tested and labelled in accordance with the Construction Products Regulation no� 305/2011� The requirement for a Declaration of Performance (DoP) is therefore satisfied for the grid, the mineral board and the plaster system� You can find the DoP number on the respective packaging� Plaster system OWAplan S, whiteOWAplan XS, whiteOWAplan color, RAL/NCS colour on request Further information on the plaster systems and their applications is available on request or can be obtained from our video “Installation - system S 7 / OWAplan“ on the website www�owa-ceilings�com

Handling, transport and storage of the mineral boards Board boxes should only be transported horizontally by 2 people� Do not place on a corner or edge when setting down� Store in a dry place on a level surface, do not place on damp ground� The boards always lie in the packaging with the visible side facing upwards� There is a cardboard interleaf between each board for protection� The cardboard packaging should be carefully cut open and removed without damaging the board� It is advisable to also cut open the cardboard packaging at the front sides so that the cardboard packaging opens completely� It is always advisable for 2 people to remove each board from the packaging, one at each end, to prevent damage to the board edges, corners or the visible face�

Page 5: Monolithic acoustic ceiling Installation guidelines OWAplan

5OWAplan

2� Requirements for installation

1

3

4

72

5

6

8

912

1110

1 Nonius hanger lower part no� 2001, spacing ≤ 1000 mm2 Supporting grid CD profile 60/27 no� 2003, spacing ≤ 1000 mm3 Profile connector no� 20054 Cross connector no� 20045 Tile grid CD profile 60/27 no� 2003, spacing ≤ 400 mm6 Wall angle no� 51/22 resp� no� 51/277 Tile screw no� 2019, spacing ≤ 300 mm resp� 400 mm8 Self-tapping screw no� 20249 Plaster coating

10 Board width11 Board length12 OWAplan ceiling board

2�1 Requirements prior to installation of the OWAplan ceiling:

– The area for installation must be dry�– EN 13964 stipulates site conditions should be > +7 °C� The coating could be applied at a temperature of up to +5 °C� – Relative humidity must not exceed 70 %�– System-compatible original construction parts must be used�– All layout plans including the required fittings must be available prior to commencing work�– All wall connections are to be executed in a flexible joint design�– Existing building expansion joints are to be incorporated into the OWAplan ceiling�– All fittings that may be required must be provided prior to installing the OWAplan boards� This requires coordination with

drywall workers, electricians and other participating tradespersons�– Taping and jointing and plaster coating must to be completed by a certified contractor only� The certificate needs to be verified

during the tender phase (refer to section 1)�– Higher quality standards regarding surface properties, e�g� using a suspended ceiling in poor daylight or artificial light

conditions, must be agreed in advance�– Artificial lighting directed at the ceiling surface from below or from the side (e�g� spotlights, indirect lighting) is to be avoided�

If this is not possible, the ceiling is to be sanded, filled and coated under the lighting conditions prevailing in subsequent use� Such extra quality standards for the surface are to be agreed in advance�

If fire safety is a requirement, the maximum spacing for the main tees, nonius hangers and tile screws specified in the test report, and the minimum suspension depth, must be adhered to. Furthermore, installation with a shadow gap is not permissible.

Page 6: Monolithic acoustic ceiling Installation guidelines OWAplan

6 OWAplan

2�2 Requirements during installation of the OWAplan ceiling:

– The installed ceiling system (grid and OWAplan70/90 boards) is to be approved by the coating company prior to coating� Any re-working requested by the coating company must be carried out�

– All drying times for the plaster system must be observed�– All fittings are to be additionally suspended from the raw ceiling�– The room temperature, humidity and the outdoor temperature should be recorded daily during installation�– If installation work is hindered by external influences for which the contractor is not responsible, or if installation conditions,

drying times etc� specified in these installation instructions are deviated from, concerns must be made in writing to the client� (German Construction Contract Procedures (VOB) /B §6)

2�3 Final inspection of the OWAplan ceiling

Final inspection for evenness and surface quality may only be carried out under diffuse light conditions and not under artificial light conditions, e�g� from construction site lighting� It is not always possible to make joints invisible� Minor deviations (within the tolerance limits) may become visible in light coming from the side�

Unusual lighting conditions within the building must be discussed beforehand with an OWAplan specialist�

Page 7: Monolithic acoustic ceiling Installation guidelines OWAplan

7OWAplan

3� Grid, OWAplan70/OWAplan90 boards and plaster systems

3�1 Grid

Only the OWAconstruct profile parts listed below are to be used� The specified grid spacings are to be observed� Any deviations can adversely affect and alter the end look of the OWAplan ceiling�

– Nonius hanger no� 2001 – max� grid spacing = 1000 mm + 2 safety pins no� 76– CD profile no� 2003 (supporting grid), 60 x 27 x 0�6 mm – max� grid spacing = 1000 mm– CD profile no� 2003 (tile grid), 60 x 27 x 0�6 mm – max� grid spacing = 400 mm– cross connector no� 2004– profile connector no� 2005– tile screws no� 2019 – max� grid spacing = 300 resp� 400 mm– angle profile no� 51/22 resp� no� 51/27 wall connection in flexible joint design (attached to the grid)– self-tapping screws no� 2024 for angle profile no� 51/52 resp� no� 51/27 – max� grid spacing = 400 mm– U-shaped hanger for inclined installation/direct mounting no� 2012, to be shortened on site, max� centre spacing = 1000 mm– Nonius base for inclined installation no� 2013 must be non-positively connected to no� 2012 on site

3�2 OWAplan70/OWAplan90 boards

The OWAplan70/90 mineral boards are laminated with glass fibre fleece on the visible side by the manufacturer� Before installation, the fleece must be removed from around the perimeter of the board� The fleece-free edge, approx� 30 mm, must be created on site using a single-handed plane� This will later determine the width that is filled with OWAplan Filler� The boards are fixed to the CD profile construction with special screws and butt-jointed tightly� Apply OWAplan Tape over the joint within the fleece-free edge before filling� Filling the board joint gaps creates a flat, homogeneous, airtight ceiling surface (for further information see section 4�4, page 12)�

Board edges: K3Building material class: A2-s1,d0 in accordance with EN 13501-1Board sizes: OWAplan70: 2400 x 1200 x 20 mm

OWAplan90: 2400 x 1200 x 25 mmVisible board side: fleece-laminated, white

3�2�1 Absorption properties

OWAplan90 boards, fleece-laminated, size 2400 x 1200 mm, thickness 25 mm

OWAplan70* OWAplan90*

Freq.[Hz] p

125 0�40250 0�55500 0�551000 0�702000 0�904000 1�00NRC 0.70

w 0.65SRA 0.80

Freq.[Hz] p

125 0�50250 0�75500 0�851000 0�902000 1�004000 1�00NRC 0.90

w 0.90SRA 0.95

Pra

ctic

al s

ound

abs

orpt

ion

leve

l

Frequency f [Hz]

1,0

0,8

0,6

0,4

0,2

0,0125 250 500 1000 2000 4000

* The absorption properties refer to OWAplan S, white and OWAplan XS, white� OWAplan color can lead to a minimal reduction in the absorption properties depending on the colour tone� For further information, please contact our customer service�

Page 8: Monolithic acoustic ceiling Installation guidelines OWAplan

8 OWAplan

3�3 Plaster systems 3�3�1 OWAplan S plaster system, white

OWAplan Tape, textile tapeOWAplan Filler, spatulaOWAplan S, Acoustic Coating 60/2, white, wet material

3�3�2 OWAplan XS plaster system, white

OWAplan Tape, textile tapeOWAplan Filler, spatulaOWAplan XS, Finest Acoustic Coating 27/990H, white, dry material

3�3�3 OWAplan color plaster system OWAplan Tape, textile tapeOWAplan Filler, spatulaOWAplan color, Colored Acoustic Coating 162, RAL/NCS colour on request, wet material

3�4 System-compatible components and accessories

– Comfort access flap no� 8031/9, 340 x 340 mm (external dimension) for 20 mm OWAplan70 boards, excl� OWAplan board– Comfort access flap no� 8031/10, 540 x 540 mm (external dimension) for 20 mm OWAplan70 boards, excl� OWAplan board– Comfort access flap no� 8031/11, 340 x 340 mm (external dimension) for 25 mm OWAplan90 boards, excl� OWAplan board– Comfort access flap no� 8031/12, 540 x 540 mm (external dimension) for 25 mm OWAplan90 boards, excl� OWAplan board– Nonius hanger no� 17/81 + extension no� 16/��� for comfort access flap, 2 pcs /4 pcs per access flap (refer to section 4�6)�– Mounting frame no� 8069/6 (two-part), for the installation of downlights� The frame is placed on the CD profile of the tile grid

and can be moved or positioned during installation (refer to section 4�7)�– The OWAplan70/90 mineral board must be cut to the size of the inspection hatch on site� Using the one-handed plane, a

circumferential fleece-free edge of approx� 30 mm is to be made before the tile is glued with adhesive no� 99/24 into the lid of the inspection flap�

– A fleece-free edge of approx� 30 mm must also be created on the ceiling cut-out adjoining the inspection flap using the one-handed plane on site�

– Before filling, a fabric tape (OWAplan Tape) is to be applied to the fleece-free edge on site (both for the ceiling cut-out adjoining the inspection hatch and for the ceiling tile located in the lid of the inspection hatch)�

Page 9: Monolithic acoustic ceiling Installation guidelines OWAplan

9OWAplan

3�5 Bevelled installation

Bevelled installation longitudinal section:

Nonius hanger no. 16/...Safety pin no. 76 Max. 1000 mm

Max. 250 mm

Grid spacing board profile max. 350 mm

Max. 400 mm

Cross connectorno. 2004

CD profile no. 2003

Self-tapping screw no. 2024secure profiles against slipping

Tile screw no. 2019grid spacing max. 300 mm

OWAplan70/90 ceiling board

Plaster system

Self-tapping screwno. 2024

L-angle no. 51/22 resp. no. 51/27 screwed to CD profile

Nonius base for inclined installation no. 2013

U-shaped hanger no. 2012 for inclined installation/direct mounting to be shortened on site and attached to CD profile with self-tapping screw no. 2024

20/25 mm

Page 10: Monolithic acoustic ceiling Installation guidelines OWAplan

10 OWAplan

4� Installation instructions

4�1 Installation of the first layer (supporting grid)

Installation with CD profiles (no� 2003) and Nonius hangers (no� 2001, no� 16/���, no� 76) with a max� grid spacing of 1000 mm for the CD profiles� The first and last CD profiles are to be installed with a max� grid spacing of 150 mm from the wall� The entire construction must be made level� The max� grid spacing of Nonius hangers from the wall is 250 mm� The max� grid spacing of the Nonius hangers to each other is 1000 mm� The CD profiles are connected using profile connectors (no� 2005)�

(To meet fire protection requirements, the max� grid spacing between CD profiles and hangers, as well as the minimum suspension depths must comply with the valid test certificate – refer to section 5 of these installation guidelines�)

85 6

2

1

7 4

3 3

250

60

>10

100020

/25

Grid spacing < 400

1 Nonius lower part2 CD supporting grid3 Cross connector4 CD tile grid5 Angle no� 51/22 resp� no� 51/276 Tile screw7 Self-tapping screw8 Plaster system

5 6

2

1

7 4 3

8>10

20/2

5

1000150

Page 11: Monolithic acoustic ceiling Installation guidelines OWAplan

11OWAplan

4�2 Installation of the second layer (tile grid)

Installation with CD profiles (no� 2003) at max� grid spacing of 400 mm� The first and last CD profiles are to be installed with a max� grid spacing of 60 mm from the wall� Attachment to supporting grid using cross connector (no� 2004)� The cross connector is first hooked under one side of the CD profile so that both lugs engage in the curved edge of the CD profile� The connector is only then clicked into the opposite bent edge of the CD profile� The CD profiles are connected using profile connectors (no� 2005)�

250

250

150 150>10

350

6060

>10

400

400

< 4

00

Max. 1000 Max. 1000 Max. 1000

Max

. 100

0M

ax. 1

000

Supp

ortin

g gr

id

Supp

ortin

g gr

id

Supp

ortin

g gr

id

Supp

ortin

g gr

id

Tile grid

Tile grid

Tile grid

Hanger

Hanger

No. 51/22 resp. no. 51/27No. 51/22 resp. no. 51/27

4�3 Installation of angle profile (no� 51/22 resp� no� 51/27)

Angle profile no� 51/22 for 20 mm OWAplan70 boards and angle profile no� 51/27 for 25 mm OWAplan90 boards can be screwed to the grid CD profiles to create a shadow gap wall junction� The angle profile no� 51/22 is fixed with self-tapping screws no� 2024 at a centre distance of max� 400 mm to the CD profiles� Angle profile spacing ≥ 10 mm from the wall�

85 6

2

1

7 4

3 3

250

60

>10

1000

20/2

5

Grid spacing < 400

5 6

2

1

7 4 3

8>10

20/2

5

1000150

1 Nonius lower part2 CD supporting grid3 Cross connector4 CD tile grid5 Angle no� 51/22

resp� no� 51/276 Tile screw7 Self-tapping screw8 Plaster system

For fire protection, shadow gaps are not permitted� See section 5 of this installation guide�

Page 12: Monolithic acoustic ceiling Installation guidelines OWAplan

12 OWAplan

4�4 Installation of the OWAplan70/90 boards

Prior to installing the OWAplan70/90 boards, the fleece must be removed from around the perimeter of each board, on site, using a one-handed plane, approx� 30mm wide� The boards are installed using screws (no� 2019) at max� centres of 300 mm or 400 mm, depending on grid orientation� Penetrations or openings that need subsequent sealing are to be sealed using the relevant OWAplan board parts� Attachment to the CD

profiles is always from the centre of the board outwards� The screw heads must be recessed 5 - 8 mm below the visible face of the OWAplan boards (see detail on “Fitting the screws”)�

Note: always install the longitudinal edges of the boards in the direction of the incidence of daylight (main light direction).

During installation, the flatness tables 1 - 3 according to DIN 18202 (tolerances in building construction) must be observed�

Install the boards as running bond (offset joint gaps), with at least 800 mm offset� Approx� 30 mm of fleece on the cut edge of shims installed at a subsequent board must be removed� This can be performed using a single-handed plane (e�g� the “David combischaaf 647104” brand)� Shims of less than 800 mm are not to be used�

Any lines used for guidance during board installation must be made using a laser device� Drawing lines on the fleece of the OWAplan board with a pencil or similar is not permitted� Such lines cannot be removed on finishing and may be visible through the plaster coating�

800

400

1000

300

Board screw no� 2019, centres ≤ 300 and 400 mm

Wall angle no� 51/22 or no� 51/27

Direction of light

Nonius hanger

Board offset

Direction of light

OWAplan board2400 x 1200 mm

Supporting grid, centres ≤ 1000 mmBoard grid, centres ≤ 400 mm

Page 13: Monolithic acoustic ceiling Installation guidelines OWAplan

13OWAplan

Installing the screwsUse no� 2019 plate screws with a grid spacing of 300 mm and/or 400 mm� They must be screwed approx� 5 - 8 mm deep from the lower edge of the board� Ensure the tile screws either side of the board joint have 15 – 20 mm clearance from the board edge� Around the wall perimeter, the tile screws must have a 55 mm clearance from the board edge�

20/2

5

15 - 20 mm

15 - 20 mm

5 - 8

mm

55 mm

> 10 mm

Spacing < 400 mm

Note

When using a board lifter, ensure that no pressure points are created in the base board otherwise the OWAplan board will exert excessive pressure against the CD profile construction�

Using a helmet to support boards during installation may produce indentations which will be visible later� This is therefore to be avoided� The boards need to be treated with great care�

4�5 Comfort access flaps no� 8031/9, no� 8031/10, no� 8031/11 and no� 8031/12

When installing a seamless OWAplan ceiling, access flaps are usually required�

No. 8031/9 (340 x 340 mm) for 20 mm OWAplan70 boards, excl. OWAplan boardNo. 8031/10 (540 x 540 mm) for 20 mm OWAplan70 boards, excl. OWAplan boardNo. 8031/11 (340 x 340 mm) for 25 mm OWAplan90 boards, excl. OWAplan boardNo. 8031/12 (540 x 540 mm) for 25 mm OWAplan90 boards, excl. OWAplan boardHangers required, see section 3�4

The following points need to be considered: – The exact location of the access board needs to be aligned to the grid of the suspended ceiling�– The Nonius hangers must be installed according to the size and weight of the planned access flaps (see ceiling plan)�– The size of the ceiling opening must match the exterior dimension of the access flap to be installed�– The access flaps need to be installed prior to board installation�– When using access flap no� 8031/10 resp� no� 8031/12, the CD profile around the hatch needs to be removed� Two CD profiles

(length = 1000 mm) also need to be installed and suspended from the raw ceiling (see ceiling plan 540 x 540 mm)�– The OWAplan70/90 mineral board must be cut to the size of the inspection hatch on site� Using the one-handed plane, create

a circumferential fleece-free edge of approx� 30 mm around the tile before gluing with adhesive no� 99/24 into the lid of the inspection flap�

– Using the one-handed plane, create a fleece-free edge of approx� 30 mm around the perimeter of the cut-out before installing the inspection hatch�

– Before filling, OWAplan Tape must be applied within the fleece-free edge (both for the ceiling cut-out adjoining the inspection hatch and for the ceiling tile located in the lid of the inspection hatch)�

Page 14: Monolithic acoustic ceiling Installation guidelines OWAplan

14 OWAplan

Ceiling plan, access flap 340 x 340 mm:

= 2 additional hangers no� 17/81 + extension no� 16/��� + safety pin no� 76 (x 2)

= Nonius hanger no� 2001

1000

400 400 400

1000

340

340

Cross-section of access flap no. 8031/9 resp. no. 8031/11:

400

340 mm

20/2

5

Nonius hanger no� 17/81

Comfort access flap with an OWAplan70/90 board (site)

Tile grid no� 2003, spacing < 400 mmOWAplan70/90 board

Nonius hanger no� 2001

FleeceAcoustic plaster

Tile screw no� 2019attachment spacing ≤ 300 mm resp� 400 mm

Ceiling plan, access flap 540 x 540 mm:

400 400

540

540

1000

1000

400

Additional supporting grid no� 2003, length = 1000 mm, attached to tile grid no� 2003 using cross connectors no� 2004

= 4 additional hangers no� 17/81 + extension no� 16/��� + safety pin no� 76 (x 2)

= Nonius hanger no� 2001

Page 15: Monolithic acoustic ceiling Installation guidelines OWAplan

15OWAplan

Cross-section of access flap no. 8031/10 resp. no. 8031/12:

540 mm

20/2

5

Nonius hanger no� 17/81Nonius hanger no� 2001

Cross connector no� 2004

Supporting grid no� 2003

Tile grid no� 2003spacing < 400 mm

Tile screw no� 2019spacing ≤ 300 mm resp� 400 mm

Plaster system

Extra tile grid no� 2003, length = 1000 mm, attached to supporting grid no� 2003 using cross connectors no� 2004

Comfort access flapwith an OWAplan70/90 board (site)

The access flap is inserted sideways into the opening and then aligned and fixed in place onto the CD profiles using six screws� Fine adjustment can be made at the hinge fasteners and the locking mechanism by unscrewing the Phillips screws and vertically sliding along the slot hole� The inspection flap must be assembled by the customer and incorporate the OWAplan board sprayed with the plaster system coating according to manufacturer‘s instructions� After coating, the flap needs to be opened, cleaned, and made accessible�

The flap is opened by pressing upwards on the side of the access part and immediately lowering it� The flap is closed by lightly pressing it� An audible click triggers the closing mechanism� We strongly recommend opening and closing the hatch only with clean installation gloves�

Page 16: Monolithic acoustic ceiling Installation guidelines OWAplan

16 OWAplan

4�6 Mounting frame no� 8069/6

When installing downlights, mounting frame no� 8069/6 (two-part) is to be used� One mounting frame is required for each downlight� The frames must be placed with their edges on the CD profiles� Spacing between the frames depends on the diameter of the chosen downlight�

Ensure that the clamping device of the downlight later rests on the frame and that the mounting frame does not project beyond the edge of the hole� The opening for the downlight can be created with radius cutter no� 99/16� The size is to be adapted to the diameter of the downlight� Install before mounting the board!

Downlights each weighing 250 g - 2�5 kg require installation with a frame� Downlights weighing more than 2�5 kg each require additional suspension from the raw ceiling�

Electrical wiring is to be carried out before sealing the ceiling� Cables are to be kept to the length required� Light functioning is to be checked prior to installation because later modifications will not be possible�

If there are fire protection requirements, all components must be equipped with fire boxes - please refer to section 5 of these installation guidelines�

4�7 Connection to wall, gypsum frieze, bulkhead and folded gypsum

Connecting S 7 OWAplan to gypsum frieze:

Max. 250 mm Max. 250 mmMax. 1000 mm

60 60350 400 400

20/2

5

>10

Cross connector no. 2004

Nonius hanger base no. 2001

CD profile no. 2003

CD profile no. 2003

All wall or frieze junctions must have an expansion gap between both.Joints between OWAplan70/90 boards must be levelled and sanded.

Tile screw no. 2019, grid spacing max. 300 mm and/or 400 mm

Self-tapping screw no. 2024L angle no. 51/22 resp. no. 51/27 attached to CD profile

OWAplan70/90 ceiling board

Fleece

Plaster system

Weight supported by the CD profile hangerInstall gypsum frieze according to manufacturer's instructions.

Page 17: Monolithic acoustic ceiling Installation guidelines OWAplan

17OWAplan

Connecting S 7 OWAplan to gypsum bulkhead:

Max. 250 mm Max. 1000 mm Max. 250 mm

60 60350 400 400

20/2

5

>10

Cross connector no. 2004

Nonius hanger base no. 2001

CD profile no. 2003

CD profile no. 2003

Tile screw no. 2019, grid spacing max. 300 mm and/or 400 mmSelf-tapping screw no. 2024L angle no. 51/22 resp. no. 51/27 attached to CD profile

OWAplan70/90 ceiling board

Fleece

Plaster system

All wall or bulkhead junctions must have an expansion gap between both.Joints between OWAplan70/90 boards must be levelled and sanded.

Vertical gypsum board ceiling Protrusion as per manufacturer's specificationsSuspension rigid with horizontal reinforcementGypsum tile painted white

Top connection of gypsum partition board as per manufacturer's specifications.

Connecting S 7 OWAplan to folded gypsum:

Max. 250 mm Max. 250 mmMax. 1000 mm

60 60350 400 400

20/2

5

>10

Cross connector no. 2004

Nonius hanger base no. 2001

CD profile no. 2003

CD profile no. 2003

All wall or frieze junctions must have an expansion gap between both.Joints between OWAplan70/90 boards must be levelled and sanded.

Tile screw no. 2019, grid spacing max. 300 mm and/or 400 mm

Self-tapping screw no. 2024L angle no. 51/22 resp. no. 51/27 attached to CD profile

OWAplan70/90 ceiling board

Fleece

Plaster system

Weight supported by the CD profile hangerInstall gypsum frieze according to manufacturer's instructions.

Page 18: Monolithic acoustic ceiling Installation guidelines OWAplan

18 OWAplan

5� Installing fire protection ceiling REI 60 under steel beam floors acc� to EN 13501-2

Only OWAconstruct profile parts listed below are to be used� Specifications and grid spacings in the test certificate are to be observed�

5�1 Grid and grid spacings for installing fire protection

– minimum suspension depth ≥ 250 mm– Nonius hanger no� 2001 – max� grid spacing = 1000 mm, maximum grid spacing from the outer boundary = 250 mm– CD profile no� 2003 (supporting grid), 60 x 27 x 0�6 mm – max� grid spacing = 1000 mm, maximum grid spacing from the outer

boundary = 150 mm– CD profile no� 2003 (tile grid), 60 x 27 x 0�6 mm – max� grid spacing = 400 mm, maximum grid spacing from the outer boundary

= 50 mm– cross connector no� 2004– profile connector no� 2005– tile screws no� 2019 – max� grid spacing = 150 mm and/or 400 mm– For a butt joint junction at a wall, without angle profile no� 51/22 resp� no� 51/27, the maximum permissable expansion gap is

≤ 3mm�

350

5050

400

400

400

<40

040

0

150 150Max. 1000 Max. 1000 Max. 1000

250

250

Max

. 100

0M

ax. 1

000

Supp

ortin

g gr

id

Supp

ortin

g gr

id

Supp

ortin

g gr

id

Supp

ortin

g gr

id

Tile grid

Tile grid

Tile grid

Hanger

Hanger

Page 19: Monolithic acoustic ceiling Installation guidelines OWAplan

19OWAplan

5�2 Installation instructions for fire protection version

Installation of the fire protection version needs to be carried out in the same way as the general installation described in sections 4�1 to 4�5 of these installation guidelines� However, the required grid spacing details for installation as a fire protection ceiling as specified in section 5�1 are to be observed (see also fire protection layout sample) and the following additional specification must also be noted:

5�2�1 Suspension depth

Minimum suspension depth ≥ 250 mm

5�2�2 Tile screw spacing

For the fire safety, the spacing between the tile screws no� 2019 is reduced to max� 150 mm or 400 mm�

5�2�3 Wall connection

To meet fire protection requirements, open shadow gaps are not permitted� The boards must be butt-jointed to the outer boundary without angle profile�

5�2�4 Components

All components – e�g� integrated light fixtures, downlights, inspection hatches, etc� – must be equipped on the rear with OWA fire boxes� Installation in accordance with test certificate�

OWA fire boxes are made from 15 mm MINOWA® fire protection boards, kit no� 00082673, and must be assembled on site�

Page 20: Monolithic acoustic ceiling Installation guidelines OWAplan

20 OWAplan

6� Required materials

Material requirements per m2 (recommended values):tile dimensions in mm, grid weight approx� 2�5 kg/m2, approx� 5 kg/m2 for OWAplan70 boards and approx� 4�5 kg/m2 for OWAplan90 boards

No. Description2400 x 1200 x 20 mm2400 x 1200 x 25 mm

2001 Nonius hanger lower part 1 pce16/… Nonius hanger upper part 1 pce76 Safety pin 2 pcs2012 U-shaped hanger for inclined installation/direct mounting 1 pce2013 Nonius base for inclined installation 1 pce2003 CD profile 3�5 m2004 Cross connector 2�5 pcs2005 Profile connector 0�9 pcs2019*1 Tile screw 15 pcs | 26 pieces for the fire safety version2024 Self-tapping screw 2�5 pcs/m, not applicable for fire protection 51/22 Angle profile for 20 mm OWAplan70 boards Dependent on project, not applicable for fire protection 51/27 Angle profile for 25 mm OWAplan90 boards Dependent on project, not applicable for fire protection 51/22-O Curved angle profile in m for 20 mm OWAplan70 boards Dependent on project, not applicable for fire protection

51/22-OAngle profile column semi-circles up to Ø = 1500 mm, as a piece, for 20 mm OWAplan70 boards

Dependent on project, not applicable for fire protection

51/27-O Curved angle profile in m for 25 mm OWAplan90 boards Dependent on project, not applicable for fire protection

51/27-OAngle profile column semi-circles up to Ø = 1500 mm, as a piece, for 25 mm OWAplan90 boards

Dependent on project, not applicable for fire protection

8069/6 Mounting frame Dependent on project8031/9*2 Access flap 340 x 340 mm + no� 17/81 for 20 mm OWAplan70 boards Dependent on project8031/10*2 Access flap 540 x 540 mm + no� 17/81 for 20 mm OWAplan70 boards Dependent on project8031/11*2 Access flap 340 x 340 mm + no� 17/81 for 25 mm OWAplan90 boards Dependent on project8031/12*2 Access flap 540 x 540 mm + no� 17/81 for 25 mm OWAplan90 boards Dependent on project99/24 Glue for inspection hatch Dependent on project

*1 The number of tile screws is an average value� The number of screws varies depending on the section of the ceiling concerned� For example, more screws are required for areas with board joints compared to areas without joints�

*2 All inspection hatches excluding OWAplan board� The OWAplan70/90 mineral board must be trimmed to the size of the inspection flap on site and glued in with adhesive no� 99/24�

Page 21: Monolithic acoustic ceiling Installation guidelines OWAplan

21OWAplan

Material needed per plaster system

OWAplan S plaster system, whiteCoating with screw pump for a fine texture

No. Description Container sizes Range per VPE Material required*3 per m2

2015 OWAplan Filler*1, spatula, dry goods7�5 kg bucket of powder

corresponds to 12,5 kg mixed on site Approx� 55 - 65 m²

(mixed)Approx� 0�20 kg

2016 OWAplan Tape, textile tape, wide 48 mm 90 m roll Approx� 70 m² Approx� 1�3 m

2017OWAplan S, Acoustic Coating 60/2, white, similar to RAL 9016, wet material

15 kg bucket Approx� 7 - 10 m² *3 Approx� 2�0 kg *3

OWAplan XS plaster system, whiteCoating with Airless pump for a very fine texture

No. Description Container sizes Range per VPE Material required*3 per m2

2015 OWAplan Filler*1, spatula, dry goods7�5 kg bucket of powder

corresponds to 12,5 kg mixed on site Approx� 55 - 65 m²

(mixed)Approx� 0�20 kg

2016 OWAplan Tape, textile tape, wide 48 mm 90 m roll Approx� 70 m² Approx� 1�3 m2018 OWAplan XS*2, Finest Acoustic Coating 27/990H,

white, similar to RAL 9016, dry material7�5 kg bucket of powder

corresponds to 12,2 kg mixed on site Approx� 10 - 13 m² *3

(mixed)Approx� 1�1 kg *3

OWAplan color plaster systemCoating with screw pump for a fine texture

No. Description Container sizes Range per VPE Material required*3 per m2

2015 OWAplan Filler*1, spatula, dry goods7�5 kg bucket of powder

corresponds to 12,5 kg mixed on site Approx� 55 - 65 m²

(mixed)Approx� 0�20 kg

2016 OWAplan Tape, textile tape, wide 48 mm 90 m roll Approx� 70 m² Approx� 1�3 m

2025OWAplan color, Colored Acoustic Coating 162, RAL/NCS colour on request, wet material

15 kg bucket Approx� 7 m² *3 Approx� 2�1 kg *3

OWAplan color plaster systemCoating with Airless pump for a very fine texture

No. Description Container sizes Range per VPE Material required*3 per m2

2015 OWAplan Filler*1, spatula, dry goods7�5 kg bucket of powder

corresponds to 12,5 kg mixed on site Approx� 55 - 65 m²

(mixed)Approx� 0�20 kg

2016 OWAplan Tape, textile tape, wide 48 mm 90 m roll Approx� 70 m² Approx� 1�3 m2025 OWAplan color, Colored Acoustic Coating 162, RAL/

NCS colour on request, wet material15 kg bucket Approx� 10 m² *3 Approx� 1�5 kg *3

*1 Mixing ratio for OWAplan Filler: 5 l water to 7�5 kg powder*2 Mixing ratio for OWAplan XS: 4�7 l water to 7�5 kg powder*3 Incl� Overspray

Page 22: Monolithic acoustic ceiling Installation guidelines OWAplan

22 OWAplan

7� Instructions for plaster coating

7�1 OWAplan S, white plaster system

OWAplan S, Acoustic Coating 60/2, white, for spraying with screw pump onto OWAplan ceiling board�

7�1�1 OWAplan S, white plaster system materials

OWAplan Tape, textile tape for OWAplan S, whiteOWAplan Filler, spatula for OWAplan S, white; dry shelf life min� 6 monthsOWAplan S, Acoustic Coating 60/2, white, grain size approx� 0�5 mm, wet material; cool, but frost-free storage up to 12 months

7�1�2 Description for coating

Before applying, note the following:– According to EN 13964, the site conditions must not be < +7 °C and > 70 % humidity�– During the application and drying phase, the ambient or substrate temperature must not fall below +5 °C and or rise above

+30 °C�– Excessive filled surfaces can reduce the absorption properties of the ceiling boards�– Any existing, coarse unevenness in the ceiling surface must be re-sanded with a long-neck sander, fine unevenness with a

hand sander�

On day one, apply OWAplan Tape over the board joints within the fleece-free edges� Fill the board joint gaps with two layers of OWAplan Filler and allow to dry� Drying time between the two layers at least 4 hours (may vary depending on the room temperature)� The width of the abutting fleece-free panel edges may be a maximum of 90 mm, the edge area a maximum of 45 mm� The screw heads are also to be filled� The next day, or after 18 hours at the earliest (may vary depending on the room temperature), sand the ceiling surface, vacuum and then apply the first layer of OWAplan S plaster� Drying time is at least 12 hours�

On the final day, spray on two layers of OWAplan S plaster with a drying time of approx� 4 hours between the two plaster layers�

Recommended spraying distance to the ceiling approx� 70 cm� Smaller distances lead to a cloudy and coarse spray pattern� Larger distances lead to a finer spray pattern, but also result in a high level of material spillage�

7�1�3 Application quantity / basis weight (wet application) OWAplan S, white on plaster base plateApprox� 1,2 kg/m², depending on structure and design�

7�1�4 OWAplan S, white plaster applicatorThe equipment required to apply our OWAplan S plaster is a screw pump system� The delivery rate must be between 4 and 8 litres per minute� The STROBOT 305 RSD is recommended�

In addition, a compressor is required which has a flow rate of at least 455 litres per minute and achieves a pressure of 10 bar� Since the pressure is not constant during the coating process, the flow rate is decisive� The STROCOMP 865 is recommended�

The diameter of the spray gun nozzle should be 4 - 5 mm� The smaller the diameter, the finer the plaster finish, but there is greater risk of nozzle blockage with a smaller nozzle�

Page 23: Monolithic acoustic ceiling Installation guidelines OWAplan

23OWAplan

PlasterPressure

(compressor)Flow rate

(compressor)Flow rate

(screw pump)Nozzle

(diameter)

OWAplan S ≈10 bar min� 455 l/min 4 - 8 l/min 5 mm

7�2 OWAplan XS, white plaster system

OWAplan XS, Finest Acoustic Coating 27/990H, white, for spraying onto OWAplan ceiling boards using the airless method

7�2�1 OWAplan XS, white plaster system materials

OWAplan Tape, textile tape for OWAplan XS, whiteOWAplan Filler, spatula for OWAplan XS, white; dry shelf life min� 6 monthsOWAplan XS, Finest Acoustic Coating 27/990H, white, grain size approx� 0�2 mm, dry material; cool, but frost-free storage up to 6 months

7�2�2 Description for coating

Before applying, note the following:– According to EN 13964, the site conditions must not be < +7 °C and > 70 % humidity�– During the application and drying phase, the ambient or substrate temperature must not fall below +5 °C and or rise above

+30 °C�– Excessive filled surfaces can reduce the absorption properties of the ceiling boards�– Any existing, coarse unevenness in the ceiling surface must be re-sanded with a long-neck sander, fine unevenness with a

hand sander�

On day one, apply OWAplan Tape over the board joints within the fleece-free edges� Fill the board joint gaps with two layers of OWAplan Filler and allow to dry� Drying time between the two layers at least 4 hours (may vary depending on the room temperature)� The width of the abutting fleece-free panel edges may be a maximum of 90 mm, the edge area a maximum of 45 mm� The screw heads are also to be filled� The next day, or after 18 hours at the earliest (may vary depending on the room temperature), sand the ceiling surface, vacuum and then apply the first layer of OWAplan XS plaster� Drying time is at least 12 hours�

On the final day, spray on two layers of OWAplan XS plaster� Allow a drying time of approx� 4 hours between the two plaster layers�

Recommended spraying distance from the ceiling approx� 70 cm� Smaller distances lead to a cloudy and coarse spray pattern� Larger distances lead to a finer spray pattern, but also result in a higher material loss�

Page 24: Monolithic acoustic ceiling Installation guidelines OWAplan

24 OWAplan

7�2�3 Application quantity / basis weight (wet application) OWAplan XS, white on plaster base plate

Approx� 1,0 kg/m², depending on structure and design�

7�2�4 Plaster applicator for OWAplan XS, whiteThe equipment required to apply our OWAplan XS plaster is an airless pump system� It must be able to build up a pressure of at least 200 bar. For a homogeneous surface the pressure should be reduced accordingly in small rooms�

The Graco Mark V, VII, X and the corresponding spray gun Graco TexSpray HeavyDuty are recommended� The nozzle no. 635 matches the required criteria�

For an even finer plaster texture, nozzle no. 633 is an optional alternative�

PlasterPressure

(Airless pump)Nozzle Recommended Airless pump Recommended pistol

OWAplan XS ≈200 bar 635 Graco MARK V, VII, X Graco TexSpray HeavyDuty

7�3 OWAplan color plaster system

OWAplan color, Colored Acoustic Coating 162, for airless spraying or with screw pump depending on the desired texture on OWAplan ceiling board�

7�3�1 OWAplan color plaster system materials OWAplan Tape, fabric tape for OWAplan colorOWAplan Filler, reinforcing filler for OWAplan color; dry shelf life min� 6 monthsOWAplan color, Colored Acoustic Coating 162, RAL/NCS colour on request, grain size approx� 0�2 mm, wet material; cool, but frost-free storage up to 12 months

Page 25: Monolithic acoustic ceiling Installation guidelines OWAplan

25OWAplan

7�3�2 Description of the coating Before execution, please note that:– According to EN 13964, the site conditions must not be < +7 °C and > 70 % humidity� – During the application and drying phase, the ambient or substrate temperature must not fall below +5 °C and or rise above

+30 °C�– Large surface areas filled with filler will reduce the absorption properties of the ceiling board�– Any existing, coarse unevenness in the ceiling surface must be re-sanded with a long-neck sander, fine unevenness with a hand

sander�

On day one, apply OWAplan Tape over the board joints within the fleece-free edges� Fill the board joint gaps with two layers of OWAplan Filler and allow to dry� Drying time between the two layers at least 4 hours (may vary depending on the room temperature)� The width of the abutting fleece-free panel edges may be a maximum of 90 mm, the edge area a maximum of 45 mm� The screw heads are also to be filled� The next day, or after 18 hours at the earliest (may vary depending on the room temperature), sand the ceiling surface, vacuum and then apply the first layer of OWAplan color plaster� Drying time is at least 12 hours�

During the following days, spray on two to three further layers of OWAplan color, with a drying time between spray layers of approx� 4 hours�The number of layers depends on the colour� Darker colours are sprayed in a total of 4 layers, while a total of 3 layers is sufficient for lighter colours�

Recommended spraying distance from the ceiling approx� 70 cm� Smaller distances lead to a cloudy and coarse spray pattern� Larger distances lead to a finer spray pattern, but also result in a higher material loss�

7�3�3 Application quantity/weight (wet application) OWAplan color on ceiling board Coating with screw pump: approx� 1�2 kg/m² should be used, depending on the structure and type of construction�Coating with Airless pump: approx� 1�4 kg/m² should be used, depending on the structure and type of construction�

7�3�4 Plaster applicator for OWAplan color Depending on the desired surface finish, different applicators can be used�For a fine surface texture, use a screw pump as with OWAplan S, white� Please refer to chapter 7�1�4, Plaster applicator for OWAplan S, white�

If you want to create a very fine surface finish, as with OWAplan XS, white, use an Airless pump� Please refer to chapter7�2�4, Plaster applicator for OWAplan XS, white�

Page 26: Monolithic acoustic ceiling Installation guidelines OWAplan
Page 27: Monolithic acoustic ceiling Installation guidelines OWAplan
Page 28: Monolithic acoustic ceiling Installation guidelines OWAplan

Broc

hure

103

1 e

0122

00

The information provided in this leaflet is based on the standards and data available at the time of publication� Any performance, warranties or guarantees provided, expressed or implied, are subject to the exclusive use of OWA components and the installation of those components in accordance with our recommendations� Failure to adhere to these conditions will result in the invalidation of any performance claims, warranties or guarantees and rejection of any liability� OWA reserves the right to make any technical improvements to the products, systems or services without prior notice� All goods and services are supplied in accordance with our current Terms and Conditions of Sale. Errors excepted!

Product warranties

The information in this brochure is up-to-date at the time of publication� Errors and mistakes excepted� Please contact our competence team OWAconsult for specific advice� Our experts will be happy to answer your questions under the following contact details: tel: +49 9373 201-444 or e-mail: info@owaconsult�de

Odenwald Faserplattenwerk GmbH Dr�-F�-A�-Freundt-Straße 3 | 63916 Amorbach | Germanytel +49 9373 201-0 | info@owa�dewww�owa-ceilings�com