Monicon 4 channel datasheet

2
Monicon 4 Channel 4 Channel Gas Detector The 4 Channel Gas Monitor is an innovative, cost effective, wall mounted unit. It is designed to operate in conjunction with the T100 toxic gas detector and the highly successful CGS500 combustible gas sensor to monitor a range of toxic gases, combustible gases and oxygen in a wide range of applications Digital Signal Processing The 4 Channel Gas is also compatible with a wide range of third party 4-20mA transmitters including temperature probes. Monicon have pioneered a novel approach to significantly reduce false alarms by processing the sensor signal through an advanced analysis program in the microprocessor. User Customisation for Alarm Settings Simple to use and microprocessor controlled, the 4 Channel Gas Monitor is menu assisted and fully user programmable for alarm setpoints, relay options, range, sensor type, gas type and many other parameters in a user friendly manner offering unique flexibility and control over the system Project Driven, Bespoke Solutions Using our expert engineering knowledge, the a1-cbiss project team produce the design, specify equipment and integrate the system before it’s delivered to site by our service and maintenance team KEYBENEFITS Individual voltage free relay contacts Advanced digital readout User programmable Low power consumption Built-in battery backup circuit Alarm inhibit during calibration Individual 4-20mA analogue outputs Sealed to IP65 rating RS485 communications interface Remote reset and accept terminals It offers a robust, easy to use, cost effective approach to providing an effective gas detection system where safety matters

Transcript of Monicon 4 channel datasheet

Page 1: Monicon 4 channel datasheet

Monicon 4 Channel4 Channel Gas DetectorThe 4 Channel Gas Monitor is an innovative, cost effective, wall mounted unit.

It is designed to operate in conjunction with the T100 toxic gas detector and the highly successful CGS500 combustible gas sensor to monitor a range of toxic gases, combustible gases and oxygen in a wide range of applications

Digital Signal Processing The 4 Channel Gas is also compatible with a wide range of third party 4-20mA transmitters including temperature probes. Monicon have pioneered a novel approach to significantly reduce false alarms by processing the sensor signal through an advanced analysis program in the microprocessor.

User Customisation for Alarm SettingsSimple to use and microprocessor controlled, the 4 Channel Gas Monitor is menu assisted and fully user programmable for alarm setpoints, relay options, range, sensor type, gas type and many other parameters in a user friendly manner offering unique flexibility and control over the system

Project Driven, Bespoke Solutions Using our expert engineering knowledge, the a1-cbiss project team produce the design, specify equipment and integrate the system before it’s delivered to site by our service and maintenance team

KEYBENEFITS

• Individual voltage free relay contacts

• Advanced digital readout

• User programmable

• Low power consumption

• Built-in battery backup circuit

• Alarm inhibit during calibration

• Individual 4-20mA analogue outputs

• Sealed to IP65 rating

• RS485 communications interface

• Remote reset and accept terminals

“ It offers a robust, easy to use, cost effective approach to providing an effective gas detection system where safety matters

Page 2: Monicon 4 channel datasheet

TECHNICALSPECIFICATION

GENERAL• 4 channel gas detector

• Works with T100 & CGS500 to detect toxic, combustible

and oxygen gases

• Automatic self-test capabilities

PERFORMANCE• Ec-cell operating life in air at S.T.P: Typically 2 years

• Preconditioning Requirements: 1 Hour (24 hours for HCl,

C2H4O, & NO)

• Storage life at 0 to 20°C: 6 months

• Drift, S.T.P. continuous duty in air: <2% Full Scale per

month

• Max. units on RS485 loop: 25 controllers (100 channels)

• RS485 communications parameters: 1200-N-8-1

• Unit interrogation time: 40mS

OPERATING RANGES • Operating temperature range: -18˚C to +66˚C

• Storage temperature: -40˚C to +66˚C

• Humidity range: 10%RH to 90%RH (Non-condensing)

PHYSICAL• Dimensions: 230 (H) x 300 (W) x 110 (D) mm

• Weight: 3.5kg

• Housing: Two-piece, hinged, ABS or polycarbonate with

neoprene gasket

• Mounting holes: 4 holes, Ø4.2mm, spaced at

200mm (vert) 288mm (horz)POWER• Supply voltage: 230Vac (115Vac optional)

• Power consumption: 6W

• Battery fuse: 1.5A PCB mounted, auto reset, PTC fuse

• Relay contacts: SPDT, 250V, 3A each for A1, A2, Common

A3 & FAULT (10 relays)

• Analogue outputs: 4-20mA into maximum 250 Ω for each

channel

• RS485 operating mode: Slave mode, half duplex, polled

SENSOR TYPE• Combustible gas sensor type: Monicon CGS500 or

compatible third-party sensor

• Toxic gas sensor type: Monicon T100, or compatible

4-20mA transmitter

ALARMS• Alarm setting: Digital setting (fully adjustable between

10% and 90% of full scale)

• Alarm types: Energised/de-energised. Enrichment /

deficiency. User selectable

• Resolution: 1%

• Accuracy: 5%

• Full scale range: 1.00 to 5000 (user selectable)

CERTIFICATIONS• Electromagnetic Conformance (EMC): Complies with

EN50081 and EN50082

• IP65 Rating

Cert No. 996ISO 9001

11 Ark Royal Way, Lairdside Technology Park, Tranmere, Wirral, CH41 9HTT: +44(0)151 666 8300 F: +44(0)151 666 8329 E: [email protected] W: www.a1-cbiss.com Buy Online: shop.a1-cbiss.com