MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4...

6
MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT GARY MESSENGER (626) 674-3478 EMAIL| [email protected] FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM Protected by US PATENT NO 9,163,450 626|674|3478 Waterproofing Systems STEP 1: FUTURE FLASH SEALANT APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT AS SHOWN ON ISOMETRIC DRAWING PRIOR TO INSTALLING STEP #2, FUTURE FLASH SILL DIVERTER SHEETS. FLASHING SYSTEM: METHOD #2.1 @ SILL STEP: 1 FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL STEP 1 DATE: APR 2018 PAGE: 1 OF 6 SECURE BUTTERFLY TAPE WITH JT-21 STAPLES ADD BEAD OF FUTURE FLASH SEALANT 6”x 6” BUTTERFLY TAPE

Transcript of MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4...

Page 1: MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4 window is installed. apply a 1/2” bead of future flash sealant to inside flange of

MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL

FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT

GARY MESSENGER (626) 674-3478 EMAIL| [email protected]

FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM

Protected by US PATENT NO 9,163,450

626|674|3478

Waterproofing Systems

STEP 1: FUTURE FLASH SEALANT

APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT AS SHOWN ON ISOMETRIC DRAWING PRIOR TO INSTALLING STEP #2, FUTURE FLASH SILL DIVERTER SHEETS.

FLASHING SYSTEM: METHOD #2.1 @ SILL STEP: 1FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL

STE

P 1

DATE: APR 2018 PAGE: 1 OF 6

SECURE BUTTERFLY TAPE WITH JT-21 STAPLES ADD BEAD OF FUTURE FLASH SEALANT

6”x 6” BUTTERFLY TAPE

Page 2: MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4 window is installed. apply a 1/2” bead of future flash sealant to inside flange of

MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL

FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT

GARY MESSENGER (626) 674-3478 EMAIL| [email protected]

FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM

Protected by US PATENT NO 9,163,450

626|674|3478

Waterproofing Systems

STEP 2: FUTURE FLASH - 40

RUN 12” 40mil. FUTURE FLASH DIVERTER SHEET ALONG ENTIRE LENGTH OF SILL. LENGTH OF SHEET SHOULD BE THE WIDTH OF RECESS PLUS 12” TO ALLOW FOR 6” OVERLAP ON BOTH SIDES.

NOTES: - SEE NOTE IN UPPER LEFTCORNER TO ENSURE UTILIZINGAPPROPRIATE MATERIAL WIDTH.

FLASHING SYSTEM: METHOD #2.1 @ SILL STEP: 2FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL

ATTACH WITH JT-21 STAPLES

STE

P 2

DATE: APR 2018 PAGE: 2 OF 6

FUTURE FLASH COMES IN 12", 18", 24" OR 36" WIDE ROLLS. USE WIDTH APPROPRIATE TO COVER H (HEIGHT) + S (SLOPE) + 6" min.

Page 3: MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4 window is installed. apply a 1/2” bead of future flash sealant to inside flange of

MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL

FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT

GARY MESSENGER (626) 674-3478 EMAIL| [email protected]

FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM

Protected by US PATENT NO 9,163,450

626|674|3478

Waterproofing Systems

STEP 3: FUTURE FLASH - 25

RUN 12” 25mil FUTURE FLASH DIVERTER SHEET ALONG RIGHT AND LEFT JAMB. MEASURE HEIGHT OF RECESS AND ADD 12” TO ALLOW FOR 6” OVERLAP ON EACH SIDE.

NOTE:

- MAKE SURE TO PRE-MEASURE

RECESS AND RISE TO ENSUREAPPROPRIATE MATERIALWIDTH.

FLASHING SYSTEM: METHOD #2.1 @ JAMBSTEP: 3 FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL

STE

P 3

DATE: APR 2018 PAGE: 3 OF 6

JT-21 STAPLES

PLACE STAPLES IN RETURN ON SILLTO HOLD UNTIL FUTURE FLASH SEALANT HAS CURED

Page 4: MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4 window is installed. apply a 1/2” bead of future flash sealant to inside flange of

MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL

FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT

GARY MESSENGER (626) 674-3478 EMAIL| [email protected]

FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM

Protected by US PATENT NO 9,163,450

626|674|3478

Waterproofing Systems

INS

TALL

WIN

DO

W

INSTALL WINDOW

AFTER STEP#3 AND BEFORE STEP #4 WINDOW IS INSTALLED. APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT TO INSIDE FLANGE OF WINDOW. SET WINDOW IN OPENING, LEVEL WINDOW, AND FASTEN. APPLY ANOTHER 1/2” BEAD OF FUTURE FLASH SEALANT TO THE OUTSIDE FLANGE, TOOL SEALANT OVER OUTSIDE OF THE WINDOW FLANGE TO COVER ANY VOIDS BETWEEN WINDOW FLANGE AND FLASHING.

INSTALL WINDOW PER MANUFACTURER’S INSTRUCTIONS.

FLASHING SYSTEM: METHOD #2.1 STEP: BETWEEN STEP 3 AND 4FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL

DATE: APR 2018 PAGE: 4 OF 6

Page 5: MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4 window is installed. apply a 1/2” bead of future flash sealant to inside flange of

MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL

FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT

GARY MESSENGER (626) 674-3478 EMAIL| [email protected]

FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM

Protected by US PATENT NO 9,163,450

626|674|3478

Waterproofing Systems

STEP 4: FUTURE FLASH SEALANT

APPLY A 1/2” BEAD OF FUTURE FLASH SEALANT AS SHOWN IN THE ISOMETRIC PRIOR TO THE INSTALLATION OF STEP 5, FUTURE FLASH HEADER DIVERTER SHEET.

FLASHING SYSTEM: METHOD #2.1 @ HEADERSTEP: 4FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL

USE JT-21 STAPLE TO HOLD FLASHING IN PLACE WHILE SEALANT CURES

3”x3” BEAD OF FUTURE FLASH SEALANT

STE

P 4

DATE: APR 2018 PAGE: 5 OF 6

BEAD OF FUTURE FLASH SEALANT

Page 6: MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW … · after step#3 and before step #4 window is installed. apply a 1/2” bead of future flash sealant to inside flange of

MOISTURE DIVERSION METHOD #2.1 STANDARD RECESSED WINDOW w/ SLOPED SILL

FOR TECHNICAL SUPPORT and WHERE TO ORDER, PLEASE CONTACT

GARY MESSENGER (626) 674-3478 EMAIL| [email protected]

FOR PRODUCT LITERATURE, TECHNICAL DATA SHEETS, ICC REPORTS VISIT WWW.MOISTUREDIVERSIONMETHOD.COM

Protected by US PATENT NO 9,163,450

626|674|3478

Waterproofing Systems

STEP 5: FUTURE FLASH - 25

RUN 12” 25mil FUTURE FLASH DIVERTER SHEET ALONG HEADER, OVERLAPING TOP OF NAIL FIN ON WINDOW. MEASURE 12” BEYOND OPENING TO ALLOW FOR 6” OVERLAY ON EACH SIDE.

PLACE STAPLE TO HOLD FLASHING IN PLACE UNTIL FUTURE FLASH SEALANT HAS CURED.

FLASHING SYSTEM: METHOD #2.1 @ HEADERSTEP: 5FOR MOISTURE DIVERSION METHOD: #2.1 / RECESSED WINDOW w/ SLOPED SILL

JT-21 STAPLES

STE

P 5

DATE: APR 2018 PAGE: 6 OF 6