PRODUCT LEAFLET
MODULOBLOC TRANSFORMERS
60 10592 - 13/06/2014
Network Modulobloc Transformer (3200 V - 5500 V - 6600 V from 1 to 160 kVA)
-
2
PRODUCTS PRESENTATION
SINGLE-PHASE SETS FOR SINGLE-PHASE NETWORKS
A concentric two-pole cable or two single-pole cables
SINGLE-PHASE TRANSFORMERS FOR THREE-PHASE NETWORKS
A three-pole cable or three single-pole cables
THREE-PHASE TRANSFORMERS FOR THREE-PHASE NETWORKS
A three-pole cable or three single-pole cables
Connection interface
IDR BI Transformer TEE
(1 to 6 kVA)
Transformer TED-E
(8 to 10 kVA) Transformer TED-E
(16 to 50 kVA)
Connection interface
IDR TRI Transformer TEE
(1 to 6 kVA)
Transformer TED-E
(8 to 10 kVA)
Transformer TED-E
(16 to 50 kVA)
Connection interface
IDR TRI Transformer TED-E
(5 to 32 kVA) Transformer TEH-E
-
3
NETWORK TRANSFORMERS
Modulobloc Type 1 to 160 kVA With independent connection interface
CONTENTS
GENERAL PRESENTATION .....................................................................………………….
SINGLE PHASE NETWORKS :Modulo Bi............................................................................ ...
Single phase transformers for single phase networks
TEE transformer (1 to 6 kVA)......................................................................
TED-E transformer (8 to 50 kVA)...................................................................
Connection interface IDR Bi......................................................................................
Single phase network accessories...............................................................................
THREE PHASE NETWORKS : Modulo Tri................................................................................ ..
Single phase transformers for three phase networks
TEE transformer (1 to 6 kVA)..........................................................................
TED-E transformer (8 to 50 kVA)....................................................................
Three phase transformers for a three phase network
TED-E transformer (5 to 32 kVA)....................................................................
TEH-E transformer (50 to 160 kVA)................................................................
Interface connection IDR Tri................................................................................…...
Three phase network equipment.................................................................................
INTERLOCKING - MODULOBLOC PITS..............................................................................
Pages
4 - 5
6
7
8
9
10 - 11
12
13
14
15
16
17
18
19
-
4
ALL THE ADVANTAGES OF EPOXY RESIN
For sets, transformers and connection interfaces :
single-phase from 1 kVA to 50 kVA or
three-phase from 5 kVA to 160 kVA
The use of epoxy resin guarantees that the transformers have the following characteristics :
Corrosion resistant, remain unaltered over time.
Watertight and immersible.
Insulated.
Can be buried into purposedely-deisgned pits.
MODULOBLOC MAIN CHARACTERISTICS
Watertight and immersible sets
Conform to NFC 52 410 standards and CEI 76
Dielectric : Dry, epoxy, up to 6 kVA
Oil from 8 to 160 kVA
Primary insulation voltage : 7.2 kV
Secondary insulation voltage : 1.1 kV
Reduced losses
Protection degree : IP 68 - IK 10
Working temperature : -15 °C +40°C
Impulse withstand : 45 kV wave shape 1 / 50
Withstand industrial frequency : 5.5 kV : 22 kV - 50 Hz - 1 minute
: 3.2 kV : 16 kV - 50Hz - 1 minute
Especially designed to support the no load lamp stress.
Studied to allow network continuity in case of a transformer default.
MV PLUG-INS ON THE SEPARATED CONNECTION INTERFACE :
The MV plug-in terminal systems of the connection interface guarantees total operational flexibility :
Easy to plug in and unplug.
Optimum reliability : the watertight connections rarely come in contact with water.
Regardless of type of cable used, a specially designed plug-in terminal answers all your requirements.
Absence of voltage test, earthing and short circuiting checking compartments, in conformity with
recommended NFC 17-200 standards, accessible directly on the top of the interface.
IDR Tri with a network input and
output on the twisted three-pole cable
and a transformer supply derivation.
IDR Bi with a network input and output on the two
pole cable, an output network on the twisted single
pole cables and a transformer supply derivation.
The transformers low voltage output is carried out with a 1.5 meter H 07 RNF cable. A LV plug-in terminal for the
transformers with a power rating superior to 8 kVA can be provided.
-
5
DOUBLE « AUTO » PROTECTED TRANSFORMERS :
Protection devices directly incorporated in the transformer guarantee :
MV protection with easily-accessible HRC fuses
Thermal protection using a thermal probe on a 1.5 meter long cable
Optional : Low voltage protection using thermal-magnetic circuit breaker or fuses installed in a separate cabinet
allowing protection against short circuiting with the possibility of several feeders. Starting from 8 kVA this
protection can be integrated directly on the transformer.
ADVANTAGES OF MODULOBLOCS SERIES
A complete range of equipment to carry out absence of voltage tests available
on request, conforming to recommended NFC 17-200 standards.
Connection accessories routinely delivered with each transformer.
Voltage adjustment tap changers of +-5% provided to transformers from
16kVA and to the three-phase transformers of all power ratings.
Selection of phases carried out directly on IDR connection interface enables,
using the single-phase transformer installed on three-phase networks, the
charge on the three-phases of the network to be balanced.
On request, AUGIER technicians carry out on site
technical assistance, in France start up of MV installation
and guarantees technical training leading to full
understanding of the technical features of the product and
how it works.
The IDR connection interfaces are also used as deviation boxes. MV networks epoxy resin accessories are also
available. They enable cable isolation to be carried out, among other things.
Stick fuse on the
TEE 1 kVA
Stick fuse on the
Three-phase
TED-E 5 kVA
Two-pole circuit breaker in a low
Voltage cabinet (CBT)
Modulo tri
10 kVA
-
6
MODULO BI RANGE
Electrical modular equipment comprising the single-phase 3200 V network
The range of MODULOBLOC products consists of TEE or TED-E transformers, IDR connection interfaces and
annex equipment.
EXAMPLES :
All above sets have a checking compartment allowing absence of voltage text to be carried out as well as earthing
and short circuiting (MALT / CC), conforming to NF-C 17 200 and UTE 18510 standards and requirements.
DESIGN CHARACTERISTICS
-Functional separation in three parts guarantees optimal reliability and easy access to maintenance points:
*The transformation and MV fuse protection part, installed at bottom of the pit, are immersible. There is no
connection point and therefore it needs no maintenance.
*The connection part installed in the upper part provides easy access to all circuit points, the phases or neu
tral position is clearly visible.
*Low voltage protection is optional.
- Application of regulations in force guarantee safety of maintenance workers:
*A specially-provided compartment is directly accessible for this, situated on top
*The absence of voltage test is carried out directly on the network, without interface.
*Earthing and short circuiting is carried out before any handling of the terminals.
- Easy installation:
*Easy- to- assemble and operate connections : only network ends need to be built.
*Connection to the network is carried out by one- pole plugs.
*Equipment standardisation: connection box has only one model, fewer transformers and low voltage cubicles.
IDR BI junction
Two way junction allowing existing
networks to conform to safety
regulations and recommended
NFC 17 200 standards.
IDR BI deviation
Three way junction bow allowing
a two-phase concentric or twisted
single-phase cable connection
6 to 25 mm² in cross section. MODULO BI system with TEE 5 kVA single-phase transformer and
IDR BI connection interface
-
7
SINGLE PHASE TEE TRANSFORMER (1 to 8 kVA)
SINGLE PHASE TEE TRANSFORMER FOR A SINGLE
PHASE NETWORK
The transformer is immersible IP68 modulobloc, in epoxy resin, dry
type with the following characteristics :
Coupling : Single-phase
Primary voltage : 3200 V
Secondary no load voltage : 237 V
Insulation voltage : 7,2 kV
Power rating : 1; 2; 3; 4; 5; 6 kVA
Power output rating* : 0,8 1,6; 2,4; 3,2; 4; 4,8 kVA
The transformer also comprises :
Medium voltage input by two 1.5 meter-long flexible ca-
bles equipped with a single pole plug made in the
factory, connectable to the IDR BI terminal.
Primary protection fuse.
Low voltage output by a two-pole 1.5 meter cable.
Thermal probe output on a 1.5 meter cable to allow overload protection activated by current tripping circuit breaker
with current indication alarm.
Two earth terminals connected to metal part inside as well as to a low voltage winding end. **
Conditions of use : Environment class AD7 : can be totally or
partially immersed in water temporarily.
* Conforms to public lighting NFC 52 - 410 standards
** Others available on request
LOW VOLTAGE PROTECTION CUBICLE
Waterproof polyester cubicle, containing protection equipment, remova-
ble plexiglass cover, with compression glands for incoming cables.
Suivant le cas, ces équipements peuvent être :
One HRC fuse.
A single pole + neutral circuit breaker up to 6 kVA and a two pole
one for the 8 kVA, linked to a thermal probe located at the center of
thansformers windings.
Two half-power circuit breakers, single pole + neutral.
Conforms to NFC 52-410 standards
Protection degree IP 68
Technical characteristics :
Power rating (kVA) 1 2 3 4 5 6
Power output rating (kVA) 0,8 1,6 2,4 3,2 4 4,8
Iron losses (W) 20 30 45 55 60 65
Copper losses (W) 26 38 45 60 75 90
Short circuit impedance (%) 2,9 2,5 2,5 2,5 2,5 3
Voltage drop (%) cos 2,6 1,91 1,52 1,51 1,52 1,86
Voltage drop (%) cos 2,84 2,49 2,4 2,08 2,4 2,89
Magnetising current (%) 9 8,5 8 9 8 7
Height H (mm) 240 240 280 280 280 330
Length L (mm) 260 260 310 310 310 390
Width l (mm) 220 260 276 276 276 290
Total weight (kg) 29 39 58 65 66 95
Low voltage cubicle CBT IP67
Equipped with a LV circuit breaker
Size : L 140 x W 170 x H 95 mm
LV cable L = 1.5 m
HO 7 RNF 2 x 6 mm² < 6
kVA
MV cords L = 1.5 ml with plug /
IDR
MV fuse terminal Borne de terre
M 10x20
Thermal probe cable
HO 7 RNF 2 x 1.5 mm²
H
L
l
TEE 5kVA 3200 V / 230 V
-
8
SINGLE PHASE TED-E TRANSFORMER from 8 to 50 kVA
SINGLE PHASE TRANSFORMER TED-E FOR
A SINGLE PHASE NETWORK
The transformer is immersible, in epoxy resin, oil type with the
following characteristics :
Coupling : Single phase
Primary voltage : 3200 V
Secondary no load voltage : 237 V
Insulation voltage : 7,2 kV
Power rating : 8, 10, 16, 25, 32, 50 kVA
Power output rating* : 6,4; 8; 12,8; 20; 25,6; 40 kVA
The transformer also comprises :
Medium voltage input by two 1.5 meter long flexible cables
equipped with a single pole plug, made in the factory, connectable to the IDR BI terminal.
Primary protection fuse.
LV output by a two-pole 1.5 meter long cable.
Optional : two-pole unpluggable terminal for H 07 RNF cable up to 2 x 25 mm².
Thermal probe output on 1.5 meter-long cable allowing overload protection activated by current tripping circuit
breaker with current indication alarm.
Two earth terminals connected to metal part inside as well as to a low voltage winding end. **
Technical characteristics :
Power rating (kVA) 8 10 16 25 32 50
Power output rating (kVA) 6,4 8 12,8 20 25,6 40
Iron losses (W) 100 110 100 130 155 160
Copper losses (W) 115 130 360 580 600 900
Short circuit impedance (%) 3 3 5,5 5 5 6,5
Voltage drop (%) cos 1,47 1,34 2,3 2,42 1,98 2
Voltage drop (%) cos 2,73 2,66 4,81 4,51 4,28 5,11
Magnetising current (%) 6 5 6 5 3,1 2,3
Height H (mm) 565 565 620 720 830 830
Length L (mm) 658 784 925 925
Width l (mm) 540 574 652 652
Total weight (kg) 130 145 250 375 530 650
Tap changer for voltage adjustment : Adjustments by strips of voltage, from 16 kVA,
taps +-5%.
Conditions of use : Environment class AD7 : can be totally or
partially immersed in water temporarily.
* Conforms to public lighting NFC 52-410 standards
** Others available on request
Conforms to NFC 52-410 standards
Protection degree IP 68
LOW VOLTAGE PROTECTION CUBICLE CBT
Waterproof polyester cubicle, containing protection equipment, removable
plexiglass cover, equipped with compression glands for incoming cables
Depending on requirements, this equipment can have:
Two HRC fuses
A two pole circuit breaker up to 25 kVA, activated by a thermal probe
placed at centre of transformer’s windings.
Two half*-power two -pole circuit breakers.
On request, it can include circuit breaker (up to 25kVA) or low voltage
fuse directly on transformer lid. In this case, the low voltage cables are
6 metres long.
l
H
L
LV cable L = 1.5 ml
HO 7 RNF 2 x 10mm² 10 kVA
HO 7 RNF 2 x 25mm² 16 kVA
HO 7 RNF 2 x 35mm² 25 kVA
HO 7 RNF 2 x 50 mm² 32 kVA
HO 7 RNF 2 x 95mm² 50 kVA
MV cords L = 1.5 ml with plug / IDR
preapared 1 x 6 mm² + shield
MV fuse terminal Earth terminal
M 10 x 20
TED-E 16 kVA 3200 V / 230 V with integrated LV protection
Low voltage cubicle CBT
Dimension : see with us
Equipped with a LV circuit breaker
-
9
CONNECTION INTERFACE IDR BI INTERFACE IDR BI :
Epoxy resin monobloc terminal, pluggable, waterproof, single pole, lockable, to be fixed on the pit’s walls, with
following characteristics:
Insulation voltage: 7.2 kV
Crossing current in operation 3200 V single phase: 100 A
This terminal consists of eight, single pole plug-in inputs allowing equally the functions of the input line, output or
deviation line, deviation towards TEE or TED-E transformers, absence of voltage test (VAT) as well as earthing
and short circuiting.
On request : : this VAT cabinet can be equipped with a devices used only to test absence of voltage and to carry
out earthing and short-circuiting.
INTERFACE IDR BI EQUIPMENT :
Single- pole plug assembly kit
Allowing all types of two pole concentric or twisted
cables to be used from 6 to 25 mm². The single pole
plugs resin support is asymmetrical to guarantee
positioning of the phase in relation to neutral position
Male two -pole plug
Manipulated with a safety rod equipped with CMB
key, for absence of voltage test and carrying out ear-
thing and short-circuiting. There are two models avai-
lable:
For earthing of neutral (diagram TNRC)
For isolating neutral (diagram TNRS)
Male two pole plug
BBM-C
for TNRC network
Male two pole plug
BBM-I
for TNRS networks
Single pole plug
1. Earth terminal
2. Single pole plugs
3. Disconnectable BBM plug to check for
absence of voltage and to carry out earthing
190
3
2
1
2
275
230
Junction layout (1I / 1O) TEE layout (1I / 1O / 1TEE) 3 Ways layout (1I / 2O)
-
10
ANNEX EQUIPEMENTS
SPECIFIC MAINTENANCE TOOLS:
The operation key CMB for a two- pole plug
allow extraction of male plugs and placing of ear-
thing plate, with the help of a safety manipulating
rod.
The earthing and short circuiting plate PMCB,
manipulated with a safety rod, must be used only
after extraction of the male two pole plug.
BBM male two pole plug can be used to insulate any
one of the four IDR inputs.
EQUIPMENT TO INSULATE THE UNPLUGGABLE
BBF female two pole plug can be used to insulate
two
single pole plugs, thus leaving an isolated network.
EQUIPMENT TO EARTHING, IF NEEDED, PLUGGABLE PARTS:
Earthing and short circuiting plate, PMCB, can
earth any one of the four two -pole IDR inputs.
Earthing and short circuiting plug allows the
earthing of two single- pole plugs.
Operation key CMB Earthing and short circuiting plate PMCB
Three pole plug
BBM-I
(For TNRS network)
Earthing and short circuiting plate PMCB Earthing and short circuiting plug EMCB (*)
(*) These parts have a square base enabling IDR wall fixation support.
Female two plug BBF (*)
-
11
MAINTENANCE ACCESSORIES
Maintenance operations for all MODULOBLOC systems must conform to NF C 17-200 standards using the follo-
wing accessories. Maintenance procedure is fully described in AUGIER’S brochure «Maintenance of Modulobloc
5500 V networks».
The safety manipulating rod is used for all
operations and is telescopic.
The electric voltage detector with sound signal is
delivered in a special protection box supplied with
extensions and batteries.
The earthing clamp is attached to one part to the
earthing strap, and another to the nearby earth
circuit.
The 1.5 metre-long earthing strap allows attach-
ment of eathing and short-circuiting plate to the
earth circuit.
-
12
MODULOBLOC TRI RANGE
Electrical modular equipment comprising the 5500 V three-phase networks
The range of MODULOBLOC products consist of TEE ou TED-E transformers, IDR tri connection interfaces
and annex equipment.
All above sets have a checking compartment for absence of voltage test (VAT) and carrying out earthing and short
circuiting for safety protection (MALT/CC), conforming to NF-C 17200 and UTE 18510 standards and
requirements.
DESIGN CHARACTERISTICS
-Functional separation in three parts guarantees optimal reliability and easy access to maintenance points:
*Transformation and MV fuse protection part, installed at bottom of pit, are immersible. There is no
connection point and therefore it needs no maintenance.
*The connection part installed in the upper part provides easy access to all circuit points, the selection of
phases or neutral is clearly visible.
*Low voltage protection is optional.
- Application of safety regulations in force guarantee maintenance work security:
*A specially-provided compartment for this is easily accessible, situated on top
*Checking for absence of voltage is carried out directly on the MV conductors.
*Earthing and short circuiting is carried out before any handling of the terminals.
- Easy installation:
*Easy-to-assemble and easy to operate connections: only network ends need to be built.
*Connection to the network is carried out by three- pole plugs.
- Standardisation of equipment: connection box has only one model, fewer transformers and low voltage cubicles.
EXAMPLES :
MODULO tri system with
5 kVA single phase
transformer.
Three-way three-phase deviation
Two -way three -phase junction
allowing existing networks to conform to
safety regulations.
Three -way derivation with two
5 kVA transformers.
-
13
SINGLE-PHASE TEE TRANSFORMER (1 to 6 kVA)
SINGLE - PHASE TRANSFORMER TEE FOR A
THREE -PHASE NETWORK
The transformer is immersible epoxy resin monobloc,
dry type with the following characteristics:
Coupling : Single phase
Primary voltage : 5500 V
Secondary no load voltage : 237 V
Insulation voltage : 7.2 kV
Power rating : 1, 2, 3, 4, 5, 6 kVA
Power output rating* : 1.6; 2.4; 3.2; 4; 4.8 kVA
This transformer also comprises:
Medium voltage input by two 1.5 metre-long flexible
cables equipped with a single -pole plug,made in the
factory, connectable to the IDR BI terminal.
Two primary protection fuses.
LV output by a two- pole 1.5 metre-long cable.
Thermal probe output on a 1.5 metre-long cable for overload protection activated by a current tripping circuit
breaker with current indicator alarm.
Two earth terminals connected to metal part inside as well as to a low voltage winding end. **
Conditions of use:
Environment class AD8: can be totally or
partially immersed in water temporarily
*Conforms to public lighting NFC 52-410 standards
** Others available on request
LOW VOLTAGE PROTECTION CUBICLE CBT
Waterproof polyester cubicle, containing protection equipment, removable
plexigas cover, with compression glands for incoming cables.
Depending on requirements, this equipment can have:
Two HRC fuses
A single pole + neutral circuit breaker, up to 6kVA activated by a thermal
p r o b e p l a c e d a t c e n t r e o f t h e
transformer’s windings.
Two half-power circuit breakers, single- pole plus neutral.
Conforms to the NFC 52-410 standards
Protection degree IP 68
Technical characteristics :
Power rating (kVA) 1 2 3 4 5 6
Power output rating (kVA) 0,8 1,6 2,4 3,2 4 4,8
Iron losses (W) 20 30 45 55 60 65
Copper losses (W) 26 38 45 60 75 90
Short circuit impedance (%) 2,9 2,5 2,5 2,5 2,5 3
Voltage drop (%) cos 2,6 1,91 1,52 1,51 1,52 1,86
Voltage drop (%) cos 2,84 2,49 2,4 2,08 2,4 2,89
Magnetising current (%) 9 8,5 8 9 8 7
Height H (mm) 240 240 280 280 280 330
Length L (mm) 260 260 310 310 310 390
Width l (mm) 220 260 276 276 276 290
Total weight (kg) 29 39 58 65 66 95
LV cable L=1,5 ml
HO 7 RNF 2 x 6 mm² < 6kVA
HO 7 RNF 2 x 10 mm² < 8 kVA
MV cords L = 1.5 ml with plug / IDR
prepared 1x 6 mm² + shield
MV fuse terminal
Earth terminal M 10 x 20
Thermal probe cable
HO 7 RNF 2 x 1.5 mm²
L = 1.5 ml
H
L
l
TEE 5kVA 5500 V / 230 V
Low voltage cubicle CBT IP 67
Dimensions : L 140 x H 170 x P 95 mm
Equipped with one LV circuit breaker
-
14
SINGLE-PHASE TRANSFORMER TED-E FOR A
THREE PHASE NETWORK
The transformer is immersible epoxy resin, oil type with the
following characteristics: Coupling : Single phase
Primary voltage : 5500 V
Secondary no load voltage : 237 V
Insulation voltage : 7.2 kV
Power rating : 8, 10, 16, 25, 32, 50 kVA
Power output rating* : 6.4; 8; 12.8; 20; 25.6; 40 kVA
This transformer also comprises:
Medium voltage input by two 1.5 metre-long flexible cables
equipped with a single- pole plug,made in the factory, connectable to the IDR TRI terminal.
Two primary protection fuses.
LV output by a two- pole 1.5 metre cable. Optional: a two- pole unpluggable terminal for H.07.RN.F cable up
to 2 x 25 mm².
A thermal probe output on a 1.5 metre -long cable for overload protection activated by a current tripping circuit
breaker with current indicator alarm.
Two earth terminals connected to metal part inside as well as to a low voltage winding end. **
Technical characteristics :
Power rating (kVA) 8 10 16 25 32 50
Power output rating (kVA) 6,4 8 12,8 20 25,6 40
Iron losses (W) 100 110 100 130 155 160
Copper losses (W) 115 130 360 580 600 900
Short circuit impedance (%) 3 3 5,5 5 5 6,5
Voltage drop (%) cos 1,47 1,34 2,38 2,42 1,98 2
Voltage drop (%) cos 2,73 2,66 4,81 4,51 4,28 5,19
Magnetising current (%) 6 5 6 5 3,1 2,3
Height H (mm) 585 585 720 720 830 830
Length L (mm) 784 784 925 925
Width l (mm) 574 574 652 652
Total weight (kg) 160 170 370 375 530 650
Tap changer for voltage adjustment:
Adjustment by moving straps of voltage, from
16 kVA, taps +-5%.
Conditions of use:
Environment class AD7: can be totally or
partially immersed in water temporarily.
*Conforms to public lighting NFC 52-410 standards
** Others available on request
Conforms to NFC 52-410 standards
Protection degree IP 68
LOW VOLTAGE PROTECTION CUBICLE CBT Waterproof polyester cubicle, containing protection equipment, with removable
plexiglas cover, equipped with compression glands for incoming cables.
Depending on requirements, this equipment can be with:
Two HRC fuses
A two -pole circuit breaker up to 25kVA, activated by a thermal probe
placed at centre of transformer’s windings.
Two half-power two -pole circuit breakers.
On request, it can include circuit breaker (up to 25kVA) or low voltage
fuse directly on transformer lid. In this case, the low voltage cables are
6 meters long.
l
H
L
LV cable L=1.5 ml
HO 7 RNF 2 x 10mm² 10 kVA
HO 7 RNF 2 x 25mm² 16 kVA
HO 7 RNF 2 x 35mm² 25 kVA
HO 7 RNF 2 x 95mm² 50 kVA
MV cords L = 1.5 ml with plug / IDR
prepared 1 x 6 mm² + shield
MV fuse terminal
Earth terminal
M 10 x 20
TED-E 16 kVA 5500 V / 230 V with integrated LV
SINGLE-PHASE TED-E TRANSFORMER (10 to 50 kVA)
Low voltage cubicle CBT IP 67
Dimensions : see with us
Equipped with one LV circuit breaker
-
15
THREE-PHASE TED-E TRANSFORMER (5 to 32 kVA)
THREE-PHASE TRANSFORMER TED-E FOR A
THREE-PHASE NETWORK
The transformer is immersible epoxy resin oil type with the
following characteristics : Coupling : Three- phase
Primary voltage : 5500 V
Secondary no load voltage : 410V
Insulation voltage : 7.2 kV
Power rating : 5, 10, 16, 25, 32 kVA
Power output rating* : 4; 8; 12.8; 20; 25.6 kVA
This transformer also comprises:
A medium voltage input using three 1.5 meter-long
flexible cables equipped with a single- pole plug, made
in the factory, connectable to the IDR TRI terminal.
Three primary protection fuses.
LV output by a five -pole 1.5 metre-long cable.
Optional :
A four- pole pluggable terminal for H.07.RN.F cables maximum diameter 44.5 mm.
Thermal probe output on a 1.5 metre-long cable for overload protection activated by current tripping circuit brea-
ker
Two earth terminals connected to internal metal part as well as to a low voltage winding end. **
Technical characteristics :
Power rating (kVA) 5 10 16 25 32
Power output rating (kVA) 4 8 12,8 20 25,6
Iron losses (W) 85 90 120 130 180
Copper losses (W) 100 290 390 700 750
Short circuit impedance (%) 2,3 3,5 3,5 4 3,5
Voltage drop (%) cos 2,1 2,92 2,3 2,84 2,4
Voltage drop (%) cos 2,4 3,5 3,4 3,96 3,4
Magnetising current (%) 9 5,5 4 3 3,5
Height H (mm) 770 770 870 980 980
Length L (mm) 784 925 925
Width l (mm) 540 540 574 652 652
Total weight (kg) 240 250 430 550 580
Tap changer for voltage adjustment:
Adjustment by moving straps of voltage, from
16 kVA, taps +-5%.
Conditions of use:
Environment class AD7: can be totally or partially
submerged in water on a temporary basis.
*Conforms to public lighting standard NFC 52-410
** Others available on demande
Conforms to the standard NFC 52-410
Protection degree IP 68
LOW VOLTAGE PROTECTION CUBICLE CBT
Waterproof polyester cubicle, containing the protection equipment, removable
plexiglass cover, equipped with compression glands for incoming cables
Depending on requirements, this equipment can have:
Three HRC fuses
A four -pole circuit breaker up to 25 kVA, activated by a thermal probe
placed at centre of the transformer’s windings.
Two half-power four -pole circuit breakers.
On request, it can include circuit breaker or low voltage fuse situated directly
on transformer lid. In this case, the low voltage cables are 6 metres long.
H
L
LV cable L=1,5 ml
HO 7 RNF 5 x 6mm² 5/10 kVA
HO 7 RNF 5 x 16mm² 16 kVA
HO 7 RNF 5 x 25mm² 25/32 kVA MV Cords L=1.5 ml with plug/IDR
prepared 1 x 6 mm² + shield
MV fuse terminal
Earth plug
M 10 x 20
TED-E 10 kVA 5500 V / 400 V three phase transformer
l
Low voltage cubicle CBT IP 67
Dimensions : see with us
Equipped with one LV circuit breaker
-
16
THREE-PHASE TEH-E TRANSFORMER (50 à 160 kVA)
THREE PHASE TEH-E TRANSFORMER FOR A
THREE PHASE NETWORK
Transformer is immersible epoxy resin, oil type, with the following
characteristics:
Coupling : Three phase
Primary voltage : 5500 V
Secondary no load voltage : 410V
Insulation voltage : 7.2 kV
Power rating : 50 ; 63 ; 80 ; 100 ; 125 ; 160 kVA
Power output rating* : 40 ; 50.4 ; 64 ; 80 ; 100 ; 128 kVA
This transformer also comprises:
Medium voltage input by three 1.5 metre long flexible cables, equipped with a single- pole plug, made in the
factory, pluggable on the IDR TRI terminal.
Three primary protection fuses.
LV output in four single -pole 6 metre-long cables
Thermal probe output on a 6 metre-long cable for overload protection activated by a current tripping circuit brea-
ker with current indicator alarm
Two earth terminals connected to internal metal part as well as to a low voltage winding end. **
Technical characteristics :
Power rating (kVA) 50 80 100 125 160 63
Power output rating (kVA) 40 64 80 100 128 50,4
Iron losses (W) 200 295 320 375 395 280
Copper losses (W) 780 1080 1330 1700 2350 850
Short circuit impedance (%) 3,5 3,5 4 4 4 3,5
Coupling (%) cos Yzn11 Dyn11 Dyn11 Dyn11 Dyn11 Dyn11
Magnetising current (%) 2,8 2,6 2,4 2,2 2,1 2,6
Height H (mm) 837 937 937 937 1037 937
Length L (mm) 1042 1090 1090 1122 1122 1090
Width l (mm) 545 595 595 627 627 595
Total weight (kg) 650 805 845 970 1010 770
Oil weight (kg) 110 160 160 210 210 150
Tap changer for voltage adjustment:
Adjustment by moving straps of voltage, from
16 kVA, taps +-5%
Conditions of use:
Environment class AD7: can be totally or
partially immersed in water temporarily.
*Conforms to public lighting NFC 52-410 standards
** Others available on request
Conforms to NFC 52-410 standards
Protection degree IP 68
H
L
Câble BT L=6 ml
HO 7 RNF 4 x 1 x 35mm² 50 à 80 kVA
HO 7 RNF 4 x 1 x 50mm² 100 kVA
HO 7 RNF 4 x 1 x 70mm² 125/160 kVA
Cordons 1 x 6 mm² + écran
L=1,5 mètre avec fiche
unipolaire confectionnée
Bornes fusibles HTI
Anneau de levage
TEH-E 50 kVA 5500 V / 400 V
Fiches unipolaires HTI
Commutateur de réglage
-
17
CONNECTION INTERFACE IDR TRI
INTERFACE IDR TRI
Epoxy resin monobloc terminal, pluggable, waterproof IP68, three -pole, lockable, to be fixed to the pits walls, with
the following characteristics:
Insulation voltage: 7.2 kV
Closing power rating in operation 5.5 kV three phase: 1000 kVA
This terminal consists of four, three -pole pluggable inputs allowing the following functions:
Input line.
Output or derivation line.
Derivation towards a TEE or TED-E transformer
Absence of voltage test as well as carrying out earthing and short circuiting.
Conditions of use: For easy maintenance and even with the IDR having protection degree IP68, we recommend its
use in an environment compatible with the AD7 class «can be totally or partially immersed in water temporarily».
INTERFACE IDR EQUIPMENT:
Stainless steel wall fixation support Three -pole plug
FTR assembly kit for use with all types of
three- pole belt or twisted cable from 6 to 35 mm².
Male three-pole plug
Manipulated with a safety rod equipped with a CMB
key for absence of voltage test, and carrying out
earthing.
Male three-pole plug BTM Three-pole plug
FTR
1 - Earth terminal 3 - Single-pole deviation towards TEE
2 - Three-pole FTR plug 4 - Detachable BTM plug to test absence of voltage and carry out earthing
1
2
3
1
4
2
4 456
367
307
TEE layout Junction layout 3 Ways layout
-
18
ANNEX EQUIPEMENTS
SPECIFIC MAINTENANCE TOOLS:
The CMB operation key for three- pole plugs allows
extraction of male three- pole plugs and placing of
earthing plate, with the help of a safety manipulating
rod.
The earthing and short circuiting plate, PMC,
manipulated with a safety rod, must be used only
after extraction of the male three- pole plug.
The BTM male three- pole plug can be used
to insulate any one of the four three- pole IDR
inputs.
The BTF female three -pole plug can be used to
insulate either a three- pole plug or no more than
three single- pole plugs.
EQUIPMENT FOR EARTHING, IF NEEDED, PLUGGABLE PARTS:
The earthing and short circuiting plate, PMC, can
earth any one of the four three- pole IDR inputs. The earthing and short circuiting plug allows the
earthing of either three -pole plugs or no more than
three single -pole plugs.
Operation key CMB Earthing and short circuiting plate PMC
Three- pole plug BTM Female three- pole plug BTF (*)
Earthing and short circuiting plate PMC Earthing and short circuiting plug EMC (*)
(*) These parts have a square base enabling IDR wall fixation support.
EQUIPMENT TO INSULATE THE UNPLUGGABLE PARTS:
-
19
MAINTENANCE ACCESSORIES
Accessories described on page 11.
LOCKING SYSTEM
PRINCIPLE
Using an interlocking system access to the transformers and connection interface are dependant on the earthing and
short circuiting of the cabling supplied at origin. This is carried out using an interlocking key together with a Ronis
or Profalux key.
MANHOLE LOCK
The TED key can activate a safety lock
to release the grid located inside the
inspection manhole between access
cover and transformer.
Only specific pieces, corresponding to
figures 5, 7 and 8, are listed in Augier
rates.
LOCKING TRANSFORMER TERMINALS AND CONNECTION INTERFACES If the manhole locking system cannot be used, a terminal locking system of fuse terminals can be installed directly
on the transformer and MV terminals on the connection interface. The operating principle is the same as for the
manhole lock, using a locknut.
CONCRETE PIT DIMENSIONS For MODULOBLOC BI and TRI
MODULOBLOC
Power rating
Dimensions of concrete pit
(mm)
Approximative
Weight (kg)
Models exam-
ple: Pre-
fatlantique L l H
Modulobloc bi or tri De 1 to 6 kVA 800 800 900 900 EP80
Modulobloc bi or tri 8 and 10 kVA 1000 800 900 1100 EP100
Modulobloc bi or tri 16 to 32 kVA 1790 880 1200 3000 LT5
IDR locking by nut TEE locking by nut TEE locking detail
Nylon cap,
Cap,
Special nut.
1 - Fixation device 5 - Nylon cap
2 - Washer 6 - HM 10 screw
3 - Stainless steel nut 7 - Special nut
4 - Wire mesh 8 - Cap
-
20
AUGIER ® SA BP 131 – 06513 CARROS Cedex
France
Tel. +33 (0)4 92 08 62 00 – Fax +33 (0)4 93 29 01
40
www.augier.com
AUGIER IS CERTIFIED ISO 9001 SINCE 1995
Wit
h c
onst
ant
imp
rovem
ents
, th
e m
an
ufa
ctu
rer
may a
lter
in
form
ati
on w
ith
out
pri
or
warn
ing