Modular Contactor Panel 50-225 Amps Circuits spec sheet · Modular Contactor Panel 50-225 Amps...

2
PSP Products, Inc. | 8535 Phoenix Drive | Manassas, VA 20110 | www.pspproducts.com | 1-800-648-6802 | [email protected] Revised: 7/27/2020 Modular Contactor Panel 50-225 Amps Circuits Allows 200 Amp service rated switch on smaller Generators to meet National Electric Code Features UL listed & IEC-60947 50, 65, 100, 125, 180 and 225 Amp contactor modules Any combination of 1- 8 contactor modules Surface and Flush Mount enclosures Heavy duty industrial grade contactors Modular Load Shedding Contactor Assembly Features Universal load shedding contactors work with all Generac transfer switches with load controllers (even new low voltage board) Provides load shedding capabilities for double pole circuits with 15-225 Amps breakers/loads Reduces installation time and space requirements and assists in meeting the new NEC codes Din-rail mounting allows for fast and easy customization for any configuration required Available in a variety of enclosure configurations including NEMA 1 and NEMA 3R Compact Flush Mount version fits inside of studs and the optional flush cover extends 3/4” past edge of can on all 4 sides for finished walls 8X8X4 NEMA01 20X14X4 NEMA01 12x12x04 NEMA01

Transcript of Modular Contactor Panel 50-225 Amps Circuits spec sheet · Modular Contactor Panel 50-225 Amps...

Page 1: Modular Contactor Panel 50-225 Amps Circuits spec sheet · Modular Contactor Panel 50-225 Amps Circuits Allows 200 Amp service rated switch on smaller Generators to meet National

PSP Products, Inc. | 8535 Phoenix Drive | Manassas, VA 20110 | www.pspproducts.com | 1-800-648-6802 | [email protected]

Revised: 7/27/2020

Modular Contactor Panel 50-225 Amps CircuitsAllows 200 Amp service rated switch on

smaller Generators to meet National Electric Code

Features• UL listed & IEC-60947• 50, 65, 100, 125, 180 and 225 Amp contactor modules• Any combination of 1- 8 contactor modules• Surface and Flush Mount enclosures• Heavy duty industrial grade contactors

Modular Load Shedding Contactor Assembly Features• Universal load shedding contactors work with all Generac transfer switches with load controllers (even new low voltage board)• Provides load shedding capabilities for double pole circuits with 15-225 Amps breakers/loads• Reduces installation time and space requirements and assists in meeting the new NEC codes• Din-rail mounting allows for fast and easy customization for any configuration required• Available in a variety of enclosure configurations including NEMA 1 and NEMA 3R• Compact Flush Mount version fits inside of studs and the optional flush cover extends 3/4” past edge of can on all 4 sides

for finished walls

8X8X4 NEMA01

20X14X4 NEMA01

12x12x04 NEMA01

Page 2: Modular Contactor Panel 50-225 Amps Circuits spec sheet · Modular Contactor Panel 50-225 Amps Circuits Allows 200 Amp service rated switch on smaller Generators to meet National

PSP Products, Inc. | 8535 Phoenix Drive | Manassas, VA 20110 | www.pspproducts.com | 1-800-648-6802 | [email protected]

Revised: 7/27/2020

Specifications

Electrical 50 Amp Relay 65 Amp Relay 100 Amp RelayUL 508 A:Ith 60 Amps 100 Amps 135 AmpsMaximum Horse Power At 240 VAC Single Phase 7.5 Horse Power 10 Horse Power 15 Horse PowerIEC-60947:AC1 Load 60 Amps 100 Amps 135 AmpsAC3 Load 200-240 Volts 14KW / 50 Amps 18.5KW / 65 Amps 30KW / 100 AmpsWire CU Wire Only CU Wire Only CU Wire OnlyConnection Terminal Mechanical Lugs Mechanical Lugs Crimp LugsContactor Coil Voltage 120 Volts AC 120 Volts AC 120 Volts ACShort Circuit 5Ka RMS Sym 600 V Max 5Ka RMS Sym 600 V Max 10Ka RMS Sym 600 V MaxOperation Temperature (°C): -40°C to +85°C -40°C to +85°C -40°C to +85°CContactor Mounting: Din-Rail Din-Rail Din-RailWarranty 12 Months 12 Months 12 Months

Part Number Three Pole Contactors with Din-Rail Mounting Receiver

LSC-50 50 Amp Normally Open Contactor with Din-Rail Receiver (24 or 120 Volt Coil)

LSC-65 65 Amp Normally Open Contactor with Din-Rail Receiver (24, 120, 240 Volt Coil)

LSC-100 100 Amp Normally Open Contactor with Din-Rail Receiver (24, 120, 240 Volt Coil)

LSC-125 125 Amp Normally Open Contactor (120 Volt Coil)

LSC-180 180 Amp Normally Open Contactor (120 Volt Coil)

LSC-225 225 Amp Normally Open Contactor (120 Volt Coil)

Enclosures and Contactor(s)Select can size and add contactors as needed

Dimensions NEMA 01 NEMA 3R F.M Option 50 Amp Cont 65 Amp Cont 100 Amp Cont

8X8X04 Yes No Yes 2 X X

12X08X06 No Yes No 2 1 1

12X12X04 Yes No Yes 4 X X

12X12X06 Yes Yes Yes 4 3 3

15X15X04 Yes No No 6 X X

15X15X06 No Yes No 6 4 4

20X14X04 Yes No Yes 6 2 2

20X14X06 No Yes No 6 4 4

20X20X07 No Yes No 8 5 5

UL Listed Enclosures with Grounding Bars and Din-Rail