EHNA Electric Heaters 5-20kWFor 60 Hz Small Packaged Products
MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3
Installation Instructions
NOTE: Read the entire instruction manual before starting theinstallation.
NOTE: Installation Instructions include Single and Dual pointconnection instructions separately.
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardousdue to mechanical and electrical components. Only trained andqualified personnel should install, repair, or service thisequipment.
Untrained personnel can perform basic maintenance functionssuch as cleaning and replacing air filters. All other operationsmust be performed by trained service personnel. When workingon this equipment, observe precautions in the literature, on tags,and on labels attached to or shipped with the unit and othersafety precautions that may apply.
Follow all safety codes. Installation must be in compliance withlocal and national building codes. Wear safety glasses,protective clothing, and work gloves. Have fire extinguisheravailable. Read these instructions thoroughly and follow allwarnings or cautions included in literature and attached to theunit. Consult local building codes, the current editions of theNational Electrical Code (NEC) NFPA 70.In Canada refer to the current editions of the Canadian ElectricalCode CSA C22.1.
Recognize safety information. This is the safety-alert symbol/_.
When you see this symbol on the unit and in instructions ormanuals, be alert to the potential for personal injury. Understandthese signal words; DANGER, WARNING, and CAUTION.These words are used with the safety-alert symbol. DANGERidentifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards whichcould result in personal injury or death. CAUTION is used toidentify unsafe practices which may result in minor personalinjury or product and property damage. NOTE is used tohighlight suggestions which will result in enhanced installation,reliability, or operation.
Follow all safety codes. Wear safety glasses and work gloves.Have a fire extinguisher available.
Before proceeding with heater installation, inspect thoroughly forshipping damage. Notify shipper immediately if any damage isfound. Clean all dirt, dust and moisture from heater package.Check for proper clearances of live parts, between phases andto ground. Make sure that all required barriers are in place.Check conductors run in multiple to insure that they are properlywired. Refer to unit installation instructions for complete unitinstallation details. The maximum duct static for safe electric
heater operation is shown in Table 1.
ELECTRICALSHOCKHAZARD
Failure to follow this warning could result in personal injury ordeath.
Before performing installation, service or maintenanceoperations on this system, turn off all main power to system.There may be more than one disconnect switch. Turn offaccessory heater power switch if applicable. Lockout and tagswitch with a suitable warning label.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use careand wear appropriate protective clothing and gloves whenhandling parts.
DESCRIPTION AND USAGE
This electric heater series is engineered, designed and listed tobe installed only in the models shown in Table 2. Beforeproceeding, verify the heater label for correct voltage and kWrequirements.
PACKAGE CONTENTS
Electric Heater Packaqe Contents
1. Heater assembly2. UPC heater label
3. Installation instructions
4. Identification label
5. Schematic on lid door for all fused units
6. Schematic on sticker to be placed inside unit panel fornon-fused units
7. Wire connectors (3)
8. Wire ties-6-in. (5)
9. Screws #10A (5)
10. Dual Point Warning Label
11. Dual Point Electrical Rating Label
518 06 160200 8/11/10
INSTALLATION
SINGLE POINT HEATER INSTALLATION
NOTE: Thermostat used must be capable of energizing "G"(indoor fan) on a call for "W" (heating). If "G" is not energizedsystem malfunction wilt occur.
1. Open all electrical disconnects and install lockout tagbefore beginning any installation or service work.
2. Check for proper equipment model number from list.
3. Verify that unit ductwork is installed per base unitinstructions.
4. Remove unit electrical access panel (See Fig. 1).
5. Locate and remove the heater access cover plate insideunit access panel (See Fig. 3). Save screws.
6. Remove electric heater from the packaging.
7. Install heater, sliding assembly carefully through accesshole. Ensure that mounting holes of heater align withmounting holes on the unit. Secure heater assembly withscrews provided.
8. Attach provided heater wiring labels at appropriate loca-tions (see Fig. 11 or Fig. 12).
9. Dress wires with wire ties provided.
Fig. 1 - Unit Access Panel and Label Location
ELECTRICAL ELECTRICALACCESS ELECTRIC RATING
WARNING LABELPANEL HEATLABEL ACCESS LOCATION
PANEL
Fig. 2 - Second Power Line Access Hole Location
,,_ _ 6=--==-=a L==_==J _ L=_ 0
0
)_Qf 7/8" (22.2 mm)ELECTRIC
J HEATACCESS
PANEL
8-3/4" (222.25 mm)
--4
@
OF
O2-1/2" (63.5 mm)
@@
L _._1:
SINGLE POINT ELECTRICAL CONNECTION
NOTE: All electrical connections, wire sizes and type of conduitshall meet the National Electric Code (NEC) and state and local
codes (or International Electric Code) as applicable.
NOTE: Use minimum 75°C copper wire only.
1. Make sure all disconnects are still open and tagged out asrequired previously.
2. Mark the main unit nameplate with an "X" for the electricheater size being installed. Refer to the electrical datamarked with an "X" on the nameplate for wire andmaximum over current protection sizing.
3. Connect low voltage wires as shown in unit schematicdiagrams found on the base unit installation instructions.These connections must be made in the 24v barrier
section inside the unit panel (See Fig. 3).
4. Insert field power line through the electrical heater accesspanel hole (see Fig. NO TAG or NO TAG) and connect toelectric heater as shown in their respective wiring diagram.Fused electrical heaters field lines wilt be connected to the
fuse block tugs (see Fig. NO TAG) and non fused electricheater field lines wilt be connected to heater leads usingwire nuts. Ground electrical equipment in the appropriatelocations.
IMPORTANT: Heaters with factory installed fuses may beinstalled on a branch circuit protected by either a fuse or circuitbreaker. For all other heaters, the branch circuit must beprotected by a fuse or circuit breaker supplied by others.
5. Connect stripped wires from heater to compressorcontactor leads using supplied wire nuts according to theirheater wiring diagram.
NOTE: Dress wires with wire ties provided. For fused heaters,use pre-mounted wire tires inside of fuse box cover to secureand strain relieve wires.
6. Separate all wires from incoming power leads.
7. Close electrical access panel.
DUAL POINT HEATER INSTALLATION
NOTE: Complete single point heater installation proceduresbefore completing the follow steps.
1. Open all electrical disconnects and install lockout tagbefore beginning any installation or service work.
2. Remove electric access panel (see Fig. 1), check to makesure there is clearance on the inside of control box above
the existing high voltage knockout. Using a knockoutpunch and die combination, make a 7/8-in. hole on theElectrical Heat access panel for second power circuit (seeFig. 2). A knockout punch and die combination or equi-valent toot is required to make this hole. Other types of drillbits or standard hole saws are not acceptable.
3. Attach warning and rating labels in the selected location(see Fig. 1).
4. Mark the main unit nameplate with an "X" next to theaccessory heater "none". Mark the dual point rating labelinstalled at step 3 with an "X" for the electrical heater sizebeing installed. Refer to the electrical data marked with an"X" on each nameplate for wire and maximum over currentprotection sizing.
5. Remove power line connection from heater to unitcontactor and compressor (see Fig. NO TAG and Fig.NO TAG). These are the stripped end wires black andyellow, with opened ends.
518 06 1602 00 2
DUAL POINT ELECTRICAL CONNECTION
NOTE: AIt electrical connections, wire sizes and type of conduitshall meet the national Electric Code (NEC) and state and local
codes (or International Electric Code) as applicable.
NOTE: Use a minimum 75°C copper wire only.
1. Make sure att disconnects are still open and tagged out asrequired previously.
2. Connect low voltage wires as shown in unit schematicdiagrams found on base unit installation instructions.These connections must be made in the 24v barrier
section inside the unit panel (see Fig. 3).
3. Insert first field power line through the electrical heateraccess panel bottom hole (see Fig. NO TAG or Fig.NO TAG) and connect to electric heater as shown in theirrespective wiring diagram found on the heater accessorykit. Fused electrical heaters field lines wilt be connected to
the fuse block tugs (see Fig. NO TAG.) and non fusedelectric heater field lines will be connected to heater leads
using wire nuts. Ground electrical equipment in theappropriate locations.
Fig. 3 - Heater Blank Plate Location
IMPORTANT: Heaters with factory installed fuses may beinstalled on a a branch circuit protected by either a fuse or circuitbreaker. For att other heaters, the branch circuit must beprotected by a fuse or circuit breaker supplied by others.
NOTE: Dress wires with wire ties provided. For fused heaters,
use pre-mounted wire ties inside of fuse box cover to secureand strain relieve wires.
4. Insert second field power line through the electrical heateraccess panel top hole (see Fig. NO TAG or Fig. NO TAG)and connect to unit contactor black and yellow leads usingwire nuts. Ground electrical equipment in the appropriatelocations.
5. Separate att wires from incoming power leads.
6. Close electrical access panel.
HEATERBLANKPLATE
24V BARRIER
3 518 06 1602 00
Fig. 4 - Wiring Diagram Example for Fused Heater
WIRES TO BE
REMOVED
I
@ Control WMng I
Power Wiring
Field WJdng
Fig. 5 - Wiring Diagram Example for Non-Fused HeaterTO UNITCONTROLWIRING 24V _ --_ -- -- -- _"_ .......
WIRES TO BE '_ ITO COMPRESSOR YtUW
REMOVEDI CO"TACTOR_OAWG______ III I
L1
1III
I I I
Control Wiring
Power Wiring
Field Wirin
518 06 1602 O0 4
Fig. 6 - Single Point Connections for Fused Heater
©
iPOWERLINETOHEATER
/©
24 VOLT FIELDWIRING BOX
5 518 06 1602 O0
Fig. 7 - Single Point Connections for Non-Fused Heater
©
©
POWERLINETO HEATER
24 VOLT FIELDWIRING BOX
518 06 1602 O0 6
Fig. 8 - Dual Point Connections for Fused Heater
SECOND FIELD
POWER LINE TO
UNIT CONTACTOR
FIRST FIELD POWERLINE TO HEATER
/"
24 VOLT FIELDWIRING BOX
Fig. 9 - Dual Point Connection for Non-Fused Heater
SECOND FIELD POWER
LINE TO UNIT CONTACTOR
FIRST FIELD POWERLINE TO HEATER
24 VOLT FIELDWIRING BOX
? 518 06 1602 00
START-UP
ELECTRICALSHOCKHAZARD
Failure to follow this warning could result in personal injuryor death.
Before proceeding, verify that all wiring is correct per factoryapproved schematic. Notify factory immediately of anydiscrepancies.
NOTE: Refer to base unit installation instructions as required.1. Check for loose terminal connections.
2. Check that all fuse and circuit breaker short circuit
interrupting ratings are adequate.
3. Turn on unit and heater power.
4. Set thermostat to call for heat.
5. Check operation of heater.6. Check that airflow across the heater is at or above the
minimum recommended CFM requirement (See unitinstallation instructions). Adjust indoor blower heat speedas required. Check that duct system conforms to staticpressure limits in Table 1.
NOTE: See Table 1 for Non-Export units (with -3, -5 or -6 aselectrical option-see product data).
7. Any modifications or repairs to this equipment withoutwritten permission from the factory will be done at theinstaller's own risk and expense.
TROUBLESHOOTING
1. Fuses - Malfunction wilt interrupt power to the unit. Checkfor cause of failure, replace fuses.
2. Limit Switch - Malfunction prevents heating element(s)from being energized. Replace switch if malfunctionoccurs,
3. Contactor - Malfunction wilt not allow heater to energize.Replace faulty contactor. Do not attempt to replace coil ordress contacts.
UNIT
(60 HZ UNITS) 05LO024 030 036 042 048 N
Table 1 -Maximum Duct Static Pressure for Non-ExportUnits (IN. W.C.) (pa)
MAXIMUMSTATICPRESSUREUNIT SIZE
.30 .30" .30 .50 .50 .50Heat Pump (75) (75) (75) (125) (125) (125)
Electric .30 .30 .30 .50 .50 .50
Cooling (75) (75) (75) (125) (125) (125)
*15kW size 030 heat pump must be used with medium speed only. Allothers can be run at low speed.
Fig. 10 - Fused Heater Control Box
HeaterFuse Block -- --
Field WireConnection
\\
i
Heater Door(Fused Models Only)Shown Open --
I
C°n_Parc_SS°vvire In 1 _
Yellow & Black _ _-
1Strain Relief for .J_Field Power Wires /
L
i
Attach Heaterwith 5 Screws
Door Latch
Low Voltage Wiring
Ground LugLocation
518 06 1602 O0 8
Fig. 11 - Schematic Location for Fused Heaters
L_
iT.,ss,o oplc
to de-energize this equipment, Open all remote 1
disconneots befor_ servicing.
DO not block or otherwise cover control cabinet
with in_uletion or other meterial8.
HeaterSchematic
m
_i I
)
Heater DoorShown Closed
Fig. 12 - Schematic Location for Non-Fused Heater
ELECTRIC HEATERWIRING LABEL
9 518 06 1602 O0
Table 2 - Electric Heater Usage Chart--Non-Export Units
PAD& WPA3 ( C Series) PAD4 (C Series)
EHNA Code kW V PH Fuse 24 30 36 42 48 60 24 30 36 42
05KON UL 5 230 1 0 x x x x x x x x x x x
05K4F UL 5 230 1 4 x x x x x x x x x x x
07KON UL 7.2 230 1 0 x x x x x x x x x x x
07K4F UL 7.2 230 1 4 x x x x x x x x x x x
IOKON UL 10 230 1 0 x x x x x x x x
IOK4F UL 10 230 1 4 x x x x x x x x x x x
15K4F UL 15 230 1 4 x x x x x x
15K6F UL 15 230 1 d x x x x x x x x x
20K4F UL 20 230 1 4 x x
20K6F UL 20 230 1 d x x x x x
05HON UL 5 230 3 0 x x x x x !!_!_!J_ii_i!!_!i!!!!!i!!i!!i!!i!!i!!i!!i!_ii_i!!i!!i!!i!!i!!i!!i!!i!!i!iii_!_!_ix x x x
IOHON UL 10 230 3 0 x x x x x x x x x
IOH6F UL 10 230 3 d x x x x x x x x x
15HON UL 15 230 3 0 x x x x x x x x x
15H6F UL 15 230 3 d x x x x x x x x x
20H6F UL 20 230 3 d x x x x x
05LON UL 5 460 3 0 x x x x x x x
IOLON UL 10 460 3 0 x x x x x x x
15LON UL 15 460 3 0 x x x x x x x
20 460 3 0 x x x x x20LON UL
48 60
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
= base unit not offeredx = Approved combination
Table 2 -- Electric Heater Usage--Non-Export Units Chart Continued
PHD3, WPH3 (C Series) PHD4 (D Series)
EHNA Code kW V PH Fuse 24 30 36 42 48 60 24 30 36 42 48 60
05KON UL 5 230 1 0 x x x x x x
05K4F UL 5 230 1 4 x x x x x x x x x x x x
07KON UL 7.2 230 1 0
07K4F UL 7.2 230 1 4 x x x x x x x x x x x x
IOKON UL 10 230 1 0
IOK4F UL 10 230 1 4 x x x x x x x x x x x x
15K4F UL 15 230 1 4
15K6F UL 15 230 1 d x x x x x x x x x x
20K4F UL 20 230 1 4
20K6F UL 20 230 1 d x x x x x x
05HON UL 5 230 3 0 x x x x x x x x x x
IOHON UL 10 230 3 0 x x x x x x x
IOH6F UL 10 230 3 d x x x x x x x x x x
15HON UL 15 230 3 0
15H6F UL 15 230 3 d x x x x x x x x x x
20H6F UL 20 230 3 d x x x x x x
05LON UL 5 460 3 0 x x x x x x x x
IOLON UL 10 460 3 0 x x x x x x x x
15LON UL 15 460 3 0 x x x x x x x x
20LON UL 20 460 3 0 iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ili!iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ix x × iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii;iiliiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii!ilx x x
= base unit not offeredx = Approved combination
518 06 1602 O0 10
Table 2 -- Electric Heater Usage--Non-Export Units Chart Continued
PAD5(C Series) PHD5 (C Series)
36 42
x
EHNA Code kW V PH Fuse 24 30 36 42 48 60 24 30 48 60
05KON UL 5 230 1 0 x x x x x x x
05K4F UL 5 230 1 4 x x x x x x x x
07KON UL 7.2 230 1 0 x x x x x x
07K4F UL 7.2 230 1 4 x x x x x x x x x x x x
10KON UL 10 230 1 0 x x x
10K4F UL 10 230 1 4 x x x x x x x x x x x x
15K4F UL 15 230 1 4
15K6F UL 15 230 1 6 x x x x x x
20K4F UL 20 230 1 4
20K6F UL 20 230 1 6 x x x x
111001866
tom BROWNTO UNIT CONTROL
WIRING 24V wl ¢@HITE
YELLO_"k_]_]_ TO COMPRESSOR
CONTACTOR 10 AWG ,u BI ¢C,K
L1
L2
FUSE BLOCK
T_
YELLOW
YELLOW
i ii i ii i ii i i
iii ELI AUTO-LIMIT
I
KILOWATTSVOLTS-PH-HZCONTROL VOLTSSTEPSHEATER AMPS
HEATER FUSES T1, T2M1, M2
7.5/10.0208/240-1-6024236.1/41.760A50A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 60TX11-F165Replace with 250VAC type SIo-Blow fuses
*** Wires for single point connection only. Removewires for dual point connection.
I
Control WiringPower Wiring
Field Wiring
Fig. 13 - EHNA10K4F Wiring Diagram
A10348
11 518 06 1602 00
111001867
COM BROW[,ITO UNIT CONTROL
WIRING 24V Wl WHITE
W2 .... vJ#J_.T .....W3 PINK
YELLOW_'_ TO COMPRESSOR
CONTACTOR 10 AWG = BL_CI(
L1,
_t
FUSE BLOCK
BLACK
_ 8_CK
11 1 _L, AOTO-L,_,T
1 --
11
HR3
YELLOW
YELLOW
KILOWATTS 11.3/15.0
VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24
STEPS 3HEATER AMPS 54.2/62.5
HEATER FUSES T1, T4 30A
T2, T3 60A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I
**Replace Auto Reset with Therm-O-Disctype 60TX11 -F165 & 64TX11-F165
Replace with 250VAC type Slow-Blow fuses
*** Wires for single point connection only. Removewires for dual point connection.
I
Control WiringPower WiringField Wiring
A10349
Fig. 14 - EHNA15K4F Wiring Diagram
518 06 1602 00 12
111001868
TO UM_ CONTROL
WIRING 24V
_ TO COMPRESSOR
CONTACTOR10AWG
L1
y_
mv_ m m m _HtTF ....... ,_
YELLO_
• nl_6K
BLACKJ
/I II II II I
_BLACK _
HR1
EL1
AUTO_IMIT
i
YELLOW
KILOWATTSVOLTS-PH-HZ
CONTROL VOLTSSTEPSHEATER AMPS
3.8/5.0
208/240-1-60241
18.1/20.8
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I
**Replace Auto Reset with Therm-O-Disctype 60TX11-F165
*** Wires for single point connection only. Removewires for dual point connection.
Control WiringPower WiringField Wiring
IFig. 15 - EHNA05KON Wiring Diagram
A10350
13 518 06 1602 00
112005832
TO UNIT CONTROL
WIRING 24V
_',_ TO COMPRESSORCONTACTOR 10 AWG
L1,
iw4 GR_y
YELLOW
11111t1111L__
'1
11t1
L_EL3 AUTO LIIvlIT
_cK YEL "k'_
HR3
EL4 AUTO LIIvlITBLACK YEL
EL1 AUTO-LIMIT
EL2 AUTO LIIvIIT
LA _, YEL "#'#
KILOWATTSVOLTS-PH-HZ
CONTROL VOLTSSTEPSHEATER AMPS
HEATER FUSES T1, T4T2, T3
15.0/20.0
208/240-1-60244
72.2/83.360A
60A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I
**Replace Auto Reset with Therm-O-Disctype 64TXl 1-F165
Replace with 250VAC type Slo-Blow fuses*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
A10351
Fig. 16 - EHNA2OK4F Wiring Diagram
518 06 1602 00 14
111001870
TO UNIT CONTROL
WIRING 24V
COM BROWN
_ .... WriTE--,V_ VIOLET
,V4 CRA_
YELLOW_ _J__J_ TO COMPRESSOR
COMTACTOR 10 AWG _ BIAOK
L2
FUSE BLOCK
T4
B_CK
t
I BLACK EL1 YEt AUTO-LIMIT
EL2 AUTO LIMIT
1 1 BR2
t EL3 AUTO LIMIT
tHR3
EL4 AUTO LIMITBLACK YEL
YELLOW
YELLOW
YELLOW
KILOWATTS 15.0/20.0VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24STEPS 4HEATER AMPS 72.2/83.3
HEATER FUSES M1, M2 50AT1, T4 60AT2, T3 60A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I
**Replace Auto Reset with Therm-O-Disctype 64TX11-F165
Replace with 250VAC type SIo-Blow fuses
*** Wires for single point connection only. Removewires for dual point connection.
Control Wiring
Power Wiring
Field Wiring
IFig. 17 - EHNA20K6F Wiring Diagram
A10352
15 518 06 1602 O0
111001871
TO UNIT CONTROL
WIRING 24V
_€ "k _1_ TO COMPRESSOR
CONTACTOR 10 AWG
L2
IM
L3
CON BROV_N
Wl WHITE
aWE
YELLOW
,M nlA_K 1"
f
IM
SLACK
YELLOW
II II I
EL1 AUTO-LIMIT
_cK YEL _Y_
. EL2 _ AUTO LIMIT
EL3 AUTO LIMIT
HR3
BLUE
BLACK •
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
3.8/5.0208/240-3-60
243
10.4/12.0
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TXl 1-F165 & 64TX11-F165
*** Wires for single point connection only. Removewires for dual point connection.
Control WiringPower WiringField Wiring
IFig. 18 - EHNAO5HON Wiring Diagram
A10353
518 06 1602 00 16
111001872
TO UNIT CONTROLWIRING 24V
_ TO COMPRESSOR
CONTACTOR10AWG
L1
,i,I
L2
,.M
L3
CON
Wl
BROWN
WHITE
..... V OLET,_*_
YELLOW
BLACK
• I BLAcK
YELLOW
JBLUE
/
BLUE
II
I II I
I --II
EL1 AUTO-LIMIT
BLACK YEt _
EL2 AUTO LIMIT
____ H
EL3 AUTO LIMIT
HR3
YELLOW
®BLACK
,)
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
7.5/10.0208/240-3-60
243
20.8/24.1
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TX11-F165 & 64TX11-F165
*** Wires for single point connection only. Removewires for dual point connection.
Control Wiring
Power Wiring
Field Wiring
IFig. 19 - EHNAIOHON Wiring Diagram
A10354
17 518 06 1602 00
111001873
COM
TO UNIT CONTROLWIRING 24V wl
_ w,__2
"k _k _1_ TO COMPRESSOR
CONTACTOR 10 AWG
L2
L3
BLUE
YELLOW
,, nlA_K l"
,M
BROWN
WHITE
BLACK
YELLOW
_ BLUE
_ /
BLUE
11 1I 1
EL1 AUTO-LIMIT
_cK YE[
. EL2 W'/,r AUTO LIMIT
EL3 AUTO LIMIT
HR3
BLACK
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
11.3/15.0208/240-3-60
243
31.3/36.1
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TX11-F165 & 64TX11-F165
*** Wires for single point connection only. Removewires for dual point connection.
Control WiringPower WiringField Wiring
IFig. 20 - EHNA15HON Wiring Diagram
A10355
518 06 1602 00 18
......... . 112005837q
TO UNIT CONTROL WHITE
WIRING 24V
_... _-2 v__LECT "_ j
___ _ ...... _ iI"il
_I_I_ TO COMPRESSOR _ _UE , ICONTACTOR O AWG _ELLQW -- I ' I V I ' --.
B .... _'_ .... I 1,,_1 I_,,_L B[K_ A A AE,_ A A A A A A A A YEL ,_UTO L NIT
" x/ r ' I _ - vvvvvvvvvvvvv - _.=___ - -FUSE BLOCK I HR1
_TI_ JJ-- --_[ J I L_ EL2 AUTO LIMIT
......
" qll L--_ EL3 AUTO LIMIT
I I / BLU BLK
L ....... ._ /"- _LUE
TT "_ _ BLUE J
L3 -- _
KILOWATTS 11.3/15.0VOLTS-PH-HZ 208/240-3-60CONTROL VOLTS 24STEPS 3HEATE R AM PS 31.3/36.1
HTR FUSES T1, T3, T5 50AM1, M2, M3 40A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° CUse copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 60TX11-F165 & 64TXl 1-F165Replace with 250VAC type Slow-Blow fuses*** Wires for single point connection only. Removewires for dual point connection.
I
Control WiringPower WiringField Wiring
Fig. 21 - EHNA15H6F Wiring DiagramA10356
19 518 06 1602 00
112005838
COM BROWNTO UNIT CONTROLWIRING 24V _','1 _fHITE
PINK
_1_1_1_ TO COMPRESSOR BLUE YELLOW
CONTACTOR 10 AWG EL1 AUTO-LIMIT
FUSE BLOCK
YELLOW EL2 _ AUTO LIM T
L__ L__
BLUE BLU EL3 BLK AUTO LIMIT
YELLOW
L2 BLACK
L3 _ BLUE
I_l *Power supply wiring per NEC & local codes.L_J Suitable for at least 75° C
Use copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
KILOWATTS 14.9/19.9 type 64TX11-F165 & 60TXl 1-F165VOLTS-PH-HZ 208/240-3-60 Replace with 250VAC type Slow-Blow fusesCONTROL VOLTS 24 *** Wires for single point connection only. RemoveSTEPS 3 wires for dual point connection.HEATER AMPS 41.4/47.9HTR FUSES T1, T3, T5 60A Control Wiring
Ul, M2, M3 40A Power Wiring
Field Wiring
IFig. 22 - EHNA2OH6F Wiring Diagram
A10357
518 06 1602 00 20
112005839
COM BROWNTO UNIT CONTROL
WIRING 24V wl WHITE
_ TO COMPRESSOR
CONTACTOR10AWG
L2
_r
L3
,i,,ll
,i
BLUE
YELLOW
BLACK i 8_cK+i +LUEl
AUTO-LIMIT
LS1 EL1BLACK BLACK RED
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
5.0480-3-602416.0
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 64TXX11-F165
*** Wires for single point connection only. Remove
wires for dual point connection.
Control WiringPower WiringField Wiring
IFig. 23 - EHNAO5LON Wiring Diagram
A10358
21 518 06 1602 00
112005840
COM BROWNTO UNIT CONTROL
WIRING 24V wl WHITE
_ TO COMPRESSOR
CONTACTOR10AWG
L2
L3
BLUE
YELLOW
,, BIA_K l"
I
1
AUTO-LIMIT
LS1 EL1
BLACK RED
AUTO LIMIT
LS1 EL2
YELLOW
EL3
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
10.0480-3-6024112.0
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 64TXX11-F165
*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
A10359
Fig. 24 - EHNAIOLON Wiring Diagram
518 06 1602 00 22
COM BROWNTO UNIT CONTROL
WIRING 24V Wl WHITE
'_ '_ '_ TO COMPRESSOR
CONTACTOR 10 AWG
L1
L2
L3
BLUE
YELLOW
BLACK "_BLACK
IBLACK
LE__BLACK BLACK EL1 YELLOWAUTO-LIMITLS1 r _
CONTACTOR E
AUTO-LIMIT
'/t_ BLUE
KILOWATTSVOLTS-PH-HZ
CONTROL VOLTSSTEPS
HEATER AMPS
15.0480-3-6024118.0
*Power supply wiring per NEC & local codes.Suitable for at least 75° CUse copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 64TXX11 -F165*** Wires for single point connection only. Removewires for dual point connection.
IFig. 25 - EHNA15LONWiring Diagram
Control Wiring
Power Wiring
Field Wiring
A10360
23 518 06 1602 00
TO UNIT CONTROL
WIRING 24V
_1__1__1_ TO COMPRESSOR
OONTACTOR 10AWG
L2
CON BROWN
Wl WHITE
IM BLUE
YELLOW
BLACKBLACK
1 j I# .... OW BLUE
] h1BLACK
AUTO-LIMIT i/"
1 " 1 BLACK LS1 BLACK | EL1 :YELLOW
CONTACTOR E
t LSI I EL3
_'# BLUE
KILOWATTSVOLTS-PH-HZ
CONTROL VOLTSSTEPS
HEATER AMPS
20.0480-3-6024124.1
*Power supply wiring per NEC & local codes.Suitable for at least 75° CUse copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disctype 64TXX11 -F165
*** Wires for single point connection only. Removewires for dual point connection.
IFig. 26 - EHNA2OLONWiring Diagram
Control Wiring
Power Wiring
Field Wiring
A10361
518 06 1602 00 24
111001880
COM BROWN"k_'_ TO UNIT CONTROL
WIRING 24V wl WHITE
TO COMPRESSOR
CONTACTOR10AWG
YELLOWlU
L1
L2
IIII
EL1 AUTO-LIMIT
KILOWATTS 3.8/5.0
VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24
STEPS 1HEATER AMPS 18.1/20.8
HEATER FUSES T1, T2 30A
M1, M2 50A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TX11-F165
Replace with 250VAC type Slo-Blow fuses
*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
Fig. 27 - EHNA05K4F Wiring DiagramA10362
25 518 06 1602 00
111001881
TO UNIT CONTROL
WIRING 24V
_ _ -_1_ TO COMPRESSOR
CONTACTOR 10 AWG
L1
t_
tom BROWN
Wl WHITE
C_,,-__-LLC=...... -qBLACK
,,,I
,M
BLACK
1 1I I 1I I 1I I 1
1EL1 AUTO-LIMIT
1
BLACK EL2 YEL AUTO'LIMIT
YELLOW
YELLOW/
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
7.5/10.0208/240-1-60
242
36.1/41.7
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TXl 1-F165
*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
A10363
Fig. 28 - EHNAIOKON Wiring Diagram
518 06 1602 00 26
111001882
TO UNIT CONTROL
WIRING 24V
CON BROWNX
Wl WHITE -4W2 VIOLET
YELLOW
_ TO COMPRESSOR _1
CONTACTOR 1O AWG BLACK
FUSE BLOCK
EL2 AUTO LIMIT
_j
Lfl ................._ i EL3 AUTOLIMIT"" ............_ i i : v vvv vvv vvv vv v ** .........,\_..
T3 ..... ..............................i ....................................................................._£_£E .............................................................................................................................................................................................................................................................................................................................................................../
YELLOW " i
\/
L2
....................._ z
KILOWATTS ! !,.31!5,0 ..........................................
VO LTS- PH- HZ ..... .........................
CONTROL VOLTS .....24 ..........................................................................STEPS 3HEATE R AM PS 54.2/62.5
HEATER FUSES T1, T4 ....60AT2, T3 .....30A ................................................................................M 1, M2 .....50A ...............................................................................
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I
**Replace Auto Reset with Therm-O-Disctype 60TX11-F165 & 64TXl 1-F165
Replace with 250VAC type SIo-Blow fuses
*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
Fig. 29 - EHNA15K6F Wiring DiagramA10364
27 518 06 1602 00
112OO5847
COM BROWN
TO UNIT CONTROLWIRING 24V wl WHITE
W2 _LE_
BLUE"k_k_l_ TO COMPRESSOR
YELLOW
CONTACTOR10AWG: _IAnK
FUSEBLOCK
T1
L2 T_
L3 T_
F
fBLK
_ YEL
BLUE
I11 HR1
I_ AUTO-UM'T
illI _ _ AUTOLIMIT
_ _ EL2 _t,k LS1
J •
BLUE ,_
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPS
HEATER AMPS
HTR FUSES T1, T3, T5M1, M2, M3
7.5/10.0
208/240-3-6024
320.8/24.135A
40A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TX 11-F 165 & 64TX 11 -F 165
Replace with 250VAC type SIo-Blow fuses*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
Fig. 30 - EHNAIOH6F Wiring DiagramA10366
518 06 1602 00 28
111001885
COM BROWNTO UNIT CONTROLWIRING 24V wl WHITE
4
_ TO COMPRESSOR ,ICONTACTOR10AWG
L1
,,11
,i
,i
YELLOW
BLACK
BLACK
YELLOW
YELLO_V
1 11 11 11 1
EL1 AUTO-LIMITBLACF YEL "_t "]1
HR1
BLACK EL2 YEL AUTO-LIMIT
KILOWATTS
VOLTS-PH-HZCONTROL VOLTS
STEPSHEATER AMPS
5.4/7.2
208/240-1-60242
25.9/30.0
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.
Field wire, NEC Class I**Replace Auto Reset with Therm-O-Disc
type 60TX11-F165
*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
A10367
Fig. 31 - EHNA07KON Wiring Diagram
29 518 06 1602 00
111001886
CO_4 BRO_NTO UNIT CONTROLWIRING 24V wl WHITE
*** TOOTO2_'RESS%G,: ...._.......",
___FUSE BLOCK
1_2
BLACK
1 11 I 1I 1 1I 1 1
1l EL1 AUTO-LIMIT
1
HR2
YELLOW
KILOWATTS 5.4/7.2
VOLTS-PH-HZ 208/240-1-60CONTROL VOLTS 24
STEPS 2HEATER AMPS 25.9/30.0
HEATER FUSES T1, T3 60A
M1, M2 50A
*Power supply wiring per NEC & local codes.Suitable for at least 75 ° C
Use copper conductor wiring only.Field wire, NEC Class I
**Replace Auto Reset with Therm-O-Disctype 60TX11-F165
Replace with 250VAC type Slow-Blow fuses
*** Wires for single point connection only. Remove
wires for dual point connection.
I
Control WiringPower WiringField Wiring
A10368
Fig. 32 - EHNA07K4F Wiring Diagram
518 06 1602 00 30