Modelling Workshop

download Modelling Workshop

of 38

Transcript of Modelling Workshop

  • 8/12/2019 Modelling Workshop

    1/38

    1

    WECC Modeling Workshop

    Load ModelMotor Protection, Drives and Lighting

    John Kueck

  • 8/12/2019 Modelling Workshop

    2/38

    2

    A Range of Applicable Standards

    Most Small Motors Only Have Over-current

    and Overload Protection

    Newer Standards Are Requiring Under-voltage

    The Ice Cube Relay Is the real culprit

    Point of Wave Has More Effect than Voltage

    Dip Magnitude

    Motor Protection and Control

  • 8/12/2019 Modelling Workshop

    3/38

    3

    Many Well Known Standards: Buff Book IEEE Std 242-2001 Protection and Coordination of Industrial and

    Commercial Power Systems

    Gray Book IEEE Std 241-1990 Electric Power Systems in CommercialBuildings

    Red Book IEEE Std 141-1993 Electric Power Distribution for Industrial Plants

    Gold Book IEEE Std 493-2007 Design of Reliable Industrial and CommercialPower Systems

    Blue Book IEEE Std 1015-2006 Applying Low Voltage Circuit Breakers Usedin Industrial and Commercial Power Systems

    The National Electrical Code (NEC, 2011)

    The above standards provide little guidance on the suggested

    setpoint for undervoltage trip for various types of equipment,especially for equipment under 600 volts. There is significantlatitude allowed to the designer, and really no requirement that thedesigner rigorously follow the standard.

    Biggest problem may be the common ice cube relay.

    A Range of Standards for Equipment

    Protection and Voltage Tolerance

  • 8/12/2019 Modelling Workshop

    4/38

    4

    Thermal capability(overload)

    Locked Rotor

    Short Circuit

    (Instantaneous) Single Phasing

    Undervoltage

    Unbalance

    Protection settingwith new motorstarters is mucheasier than it usedto be.

    Basic Motor Protection

  • 8/12/2019 Modelling Workshop

    5/38

    5

    Voltage Unbalance

    Has a Major Impact on Motor Efficiency

  • 8/12/2019 Modelling Workshop

    6/38

    6

    Motor Torque

    Induction motor electrical torque is a functionof the terminal voltage squared.

    During a rapid dip, the motor goes into

    regeneration and will be slowed.A stiff system or dc offset slows the motor faster

    Low inertia in the driven equipment means evenfaster deceleration

  • 8/12/2019 Modelling Workshop

    7/38

    7

    NEMA Torque Designs

    B Most common by far. Normal starting torque forfans, pumps, miscellaneous machinery. Mediumstarting torque, high breakdown torque.

    C High starting torque, medium breakdown torquefor high inertia loads such as conveyors, positivedisplacement pumps.

    D Extra high starting torque, low breakdown torquefor very high inertia loads, may have high slip. Used for

    motor operated valves.

    E No longer included, but was for high efficiencymotors, similar to shape of B, but lower.

  • 8/12/2019 Modelling Workshop

    8/38

    8

    NEMA Design Motor

    Speed Torque Curves

  • 8/12/2019 Modelling Workshop

    9/38

    9

    For this Hypothetical Motor, the Torque Available

    at 75% Voltage May Fail to Accelerate the Load

    Percent

    Full

    Load

    Torque

    Percent Full Load Speed

    600

    40

    80

    120

    160

    200

    20 40 80 100

    Motor Torque Rated V

    Motor Torque 75% V

    Load Torque

    Motor May Fail to

    Accelerate Load

  • 8/12/2019 Modelling Workshop

    10/38

    Synchronous motors run without slip and do not have torque curves like

    induction motors; if the "pull out" torque is exceeded,

    the motor will pull out of step

    Armature

    Amps

    % Power

    Factor

    Field Amps

    15

    0

    20

    40

    60

    80

    10

    0

    5 10 20

    Full Load Power Factor

    Full Load Current

    Lagging

    PF Leading PF

  • 8/12/2019 Modelling Workshop

    11/38

    11

    Representative Speed Torque Curves

    for Various Types of Loads

    Percent

    Full

    Load

    Torque

    Percent Full Load Speed

    600

    40

    80

    120

    160

    200

    20 40 80 100

    Centrifugal Pump

    or Fan (Open

    Discharge)

    Axial Pump or Fan

    Centrifugal Pump or

    Fan (Closed Discharge)

  • 8/12/2019 Modelling Workshop

    12/38

    12

    The IEEE Buff Book (242, 2001) Section

    10.3.2.1 Purposes of Under-voltage Protection

    To prevent a motor from automatically restarting whenvoltage returns.

    To avoid excessive inrush to the total motor load on thepower system.

    To avoid reaccelerating motors before their fieldscollapse.

    Time delay undervoltage protection will often not besatisfactory because magnetically held contactors maydrop out before the undervoltage protection.

  • 8/12/2019 Modelling Workshop

    13/38

    13

    Very Few Other Standards Mention

    Undervoltage Protection for Motors

    For large motors, the IEEE Red Book (IEEE_Standard_141,1993) states in Section 5.6.3.1 motor protection may include:

    Internal fault protection - either overcurrent relays or percentage

    differential relays; sometimes ground fault protection is provided

    using a zero sequence approach.

    Sustained overloads and locked rotor- Conventional over current

    relays may provide too much margin between the motor thermal

    capability curve and the relay operating time characteristic.

    Overcurrent relays do, however, provide excellent locked rotor and

    short circuit protection. Thermal relays will give adequate protection

    for light and medium overloads.

    Under voltage - Large motors and medium voltage motors should have

    separate undervoltage protection.

    For small motors, the Red Book and the NEC do not require

    undervoltage protection.

  • 8/12/2019 Modelling Workshop

    14/38

    14

    Emerson Secure Start and ComfortAlert

    for Air Conditioning Compressors

    ComfortAlert will flash an alert if the voltage is below71%

    Secure Start

    Monitors supply voltage in air conditioning compressorsand protects against low voltage or locked rotor.

    Also provides a reduced voltage soft start.

    Can be used in areas with problems in voltage variation.

  • 8/12/2019 Modelling Workshop

    15/38

    15

    Programmable Logic Controllers

    Adjustable Speed Drives

    Personal Computers

    Fluorescent Lighting

    Power Electronic Loads

  • 8/12/2019 Modelling Workshop

    16/38

    16

    0 200 400 600 800

    Duration of Sag

    (milliseconds)

    Upper Range Average Lower Range

    %V

    8060

    40

    PLC Power Supply Voltage Sag Tolerance (CIGRE 412)

    20

    10

    0

    Voltage Tolerance of Programmable

    Logic Controllers, A Wide Range

  • 8/12/2019 Modelling Workshop

    17/38

    480 VCircuit Breaker

    VFD

    ControlsVoltage and

    Frequency

    Motor

    VFD to Control Fan Speed Instead of Dampers

  • 8/12/2019 Modelling Workshop

    18/38

    18

    Useful

    Work

    Controller losses

    10%

    Coupling device losses10% for large speed

    reduction

    Driven load losses

    30 to 50%

    for pumps and fans

    Load modulation

    devices

    0 to >50%

    Typical Motor System Losses

  • 8/12/2019 Modelling Workshop

    19/38

    19

    Controlling Speed and Torque with a VFD

    Is More Efficient than Valves or Dampers

    Power Required to

    Achieve Needed Flow

    Percent of Full Flow

    Vane Adjustment

    VSD

    Control

  • 8/12/2019 Modelling Workshop

    20/38

    20

    Variable Frequency Drive (VFD)

    Tolerance and Protection

    0 200 400 600 800

    Duration of Sag

    (milliseconds)

    Upper Range Average Lower Range

    %

    V

    80

    60

    40

    ASD Voltage Sag Tolerance (Djokic, 2005)

    20

    10

    0

    Overcurrent Protection

    Undervoltage

    Protection

  • 8/12/2019 Modelling Workshop

    21/38

    21

    VFD Voltage Sag Test

    Our data comes from a test at which the vfd frequency

    reference was set to 30 Hz.

    vp

    vdc 20% voltage drop, held for

    10 seconds, and then

    ramped back over 10seconds.

  • 8/12/2019 Modelling Workshop

    22/38

    Voltage Sag Test Contd.

    Power is roughly constant,except at the point of voltage

    drop.

    Speed is almost

    constant

    Power is not strongly dependenton voltage in this data.

  • 8/12/2019 Modelling Workshop

    23/38

    23

    Lighting

    Incandescent filament lamps are quite tolerant to voltagesags, but the light output and lifetime are dramaticallyimpacted by sustained voltage deviations.

    Fluorescent lamps:

    Electronic ballast ( vast majority today)o tend to drop out at lower voltages 10 to 20%,

    o have nearly constant current characteristic at the fundamentalfrequency, dim at lower voltages

    o Current contains significant harmonics

    o New dimmable fluorescent lamps with electronic ballasts are

    controlled with either a 0 to 10 volt dc signal or a digital signal, not byvarying voltage

    Magnetic ballasto Usually drop out between 70 and 80% in as little as 10 milliseconds

    o Highly non-linear reactive power characteristic

  • 8/12/2019 Modelling Workshop

    24/38

    24

    Electronic Ballast Fluorescent Lights

    4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1

    -200

    -100

    0

    100

    200

    Time

    Voltage

    Fluorescent Voltage and Current

    4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1

    -4

    -2

    0

    2

    4

    Current

  • 8/12/2019 Modelling Workshop

    25/38

    25

    Electronic Ballast Fluorescent Lights

    0 20 40 60 80 100 120 140-10

    0

    10

    20

    30

    40

    50

    60

    Voltage [V]

    RealPower[W]

    0 20 40 60 80 100 120 140-30

    -25

    -20

    -15

    -10

    -5

    0

    5

    ReactivePower[VAR

    ]

    Fluorescent Power

    Reactive Power

    Active Power

  • 8/12/2019 Modelling Workshop

    26/38

    26

    Compact Fluorescent Lights

    0 20 40 60 80 100 120

    -10

    0

    10

    20

    30

    Voltage [V]

    RealPower[W]

    0 20 40 60 80 100 120

    -15

    -10

    -5

    0

    5

    Compact Fluorescent Power

    ReactivePower

    Reactive Power

    Active Power

  • 8/12/2019 Modelling Workshop

    27/38

    27

    Magnetic Ballast Fluorescent Lights

    4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1

    -200

    -100

    0

    100

    200

    Time [sec]

    Voltage

    Fluorescent Old-Ballast Voltage and Current

    4 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.1

    -2

    -1

    0

    1

    2

    Time [sec]

    Current

  • 8/12/2019 Modelling Workshop

    28/38

    28

    Magnetic Ballast Fluorescent Lights

    0 20 40 60 80 100 120 140-50

    0

    50

    100

    Voltage [V]

    RealPower[W]

    Fluorescent Old-Ballast Power

    0 20 40 60 80 100 120 140-20

    0

    20

    40

    Voltage [V]

    ReactivePower[VA

    R]

    Active Power

    Reactive Power

  • 8/12/2019 Modelling Workshop

    29/38

    29

    Ice Cube Relay, the Achilles Heel

    These relays are commonly used in 120 volt controlcircuits, for example:

    Emergency stop circuits for pumps and fans

    Door interlock circuitsAir compressor starter controls

    Chiller controls

    Conveyor controls

    Oven controlsPLC - Motor interface circuit

    ASD start circuit

    Vending machines

  • 8/12/2019 Modelling Workshop

    30/38

  • 8/12/2019 Modelling Workshop

    31/38

    31

  • 8/12/2019 Modelling Workshop

    32/38

    32

    0 200 400 600 800

    Duration of Sag (milliseconds)

    Upper Range Lower Range

    %V8060

    40

    20

    10

    0

    Ice Cube Relay Voltage Sag Tolerance

    (EPRI)

  • 8/12/2019 Modelling Workshop

    33/38

    33

    Contactors

    Large Motor Starter ContactorsMotor starter contactors may open at 65 to 75% voltage

    in the case of 2300 or 4600 Volt motors and 55 to 65% inthe case of 460 Volts and below.

    The contactor dropping out or control relays droppingout is often the only fast undervoltage protection thatmotors under 600 volts typically have.

    Large Air Conditioners

    Large three phase air conditioning in industrial orcommercial applications typically have undervoltagerelays which trip in perhaps six cycles after the voltagedrops below 0.6 pu.

  • 8/12/2019 Modelling Workshop

    34/38

    34

    0 200 400 600 800

    Duration of Sag (milliseconds)

    Upper RangeDC

    Lower Range

    %

    V

    80

    60

    40

    20

    10

    0 AC Upper

    Range

    AC Lower

    Range

    DC

    Contactors Voltage Sag Tolerance

    (CIGRE 412)

  • 8/12/2019 Modelling Workshop

    35/38

    35

    Other Parameters Are Probably More

    Important than the Dip Magnitude

    More recent studies have shown that there are anumber of parameters which have a major impact thecapability of a device to ride through an interruptionthan just the dip magnitude and duration.

    (CIGRE_Voltage_Dip_Immunity_of_Equipment_and_Installations 2010Voltage Dip Immunity of Equipment and Installations C4.110)

    These parameters include:Pre dip voltage magnitude and distortion of sine wave.

    Unbalance during dip for three phase devices, dip shape,and point on the sine wave where the dip starts.

    Speed of recovery of dip.

    Source impedance (distribution transformer).

    Other equipment connected close by.

  • 8/12/2019 Modelling Workshop

    36/38

    36

    Point on Wave

    The point on the sine wave is important because of theenergy stored in the magnetic circuit.

    The stronger the field when the dip begins, the morelikely the contactor or relay will ride through the dip.

    Because of the lagging current drawn by the contactorcoil, contactors are most sensitive to dips that begin at90 degrees and least sensitive to dips that begin at zerocrossing.

    Dips initiated at 90 degrees may drop out a contactor

    in less than 10 msec. Dips initiated at 0 degrees maynot drop out the same contactor for 80 msec even atzero volts.

  • 8/12/2019 Modelling Workshop

    37/38

    37

    0 20 40 60 80

    Duration of Sag (milliseconds)

    90 Degree Point on

    Wave of Sag Initiation0 Degree Point on

    Wave of Sag Initiation

    %

    V

    40

    20

    60

    Pass

    Fail

    Contactor Point on Wave Influence,

    CIGRE Data

  • 8/12/2019 Modelling Workshop

    38/38