A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE CNRS, Laboratoire des Signaux et Systèmes CNRS, Laboratoire des Signaux et Systèmes Thursday 25 th March 2010

Transcript of Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR...

Page 1: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

A&T sector SEMINAR

Modeling, Simulation and Control of CERN cryogenic systems

Benjamin BRADU

CERN, EN-ICECNRS, Laboratoire des Signaux et SystèmesCNRS, Laboratoire des Signaux et Systèmes

Thursday 25 th March 2010

Page 2: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Contents

Introduction Motivations and state of art

Dynamic simulator for cryogenic systems Simulation and control architecture

C i M d li Cryogenic Modeling

Simulations of cryogenic systems operating at 4.5 K CMS cryoplant CMS cryoplant Central Helium Liquefier LHC refrigerator

Simulation of LHC 1.8 K refrigeration units Cold compressors Cryogenic Distribution Line

Conclusion & Perspectives

2

Page 3: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Contents

Introduction Motivations and state of art Motivations and state of art

Dynamic simulator for cryogenic systems Simulation and control architecture Cryogenic Modeling

Simulations of cryogenic systems operating at 4.5 K CMS l t CMS cryoplant Central Helium Liquefier LHC refrigerator

Simulation of LHC 1.8 K refrigeration units Cold compressors Cryogenic Distribution Line

Conclusion & Perspectives3

Page 4: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Motivations

Develop a dynamic simulator for CERN cryogenic systems Model Large-Scale helium refrigerators

CERN cryogenic systems: large scale complex systems Similar to large industrial systems (Petroleum refineries, food industry , etc.) LHC cryogenics : 42 000 I/O & 5 000 control loops

Non-linearity of helium properties (wide operation ranges) Temperature : 1.9 K to 300 K Pressure : 14 mbar to 20 bar Pressure : 14 mbar to 20 bar

Unique systems Built to be operated at nominal conditions Few information about transients and out of predefined operation points

Dynamic simulation is a good tool for : Train operators safely and in degraded conditions Train operators safely and in degraded conditions Test new control strategies without disturbing real operation Validate control and supervision systems in simulation : « Virtual Commissioning »

4

Page 5: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Multidisciplinary Approach

Compute physical valuesIn Space and Time

Fluid Mechanics

Thermodynamic Choose a set of PDEs Parametric Identification

Computer Science

N

Numerical implementation Control Theory

New Control command developments / optimizationsC t l Th

Validation withExperimental data

Mathematics No

New Control command developments / optimizationsControl Theory

Successfulsimulations

No

5

Engineering Test on real plant

Page 6: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

State of art

Dynamic simulators of large-scale cryogenic systemsTeam Simulated Process Process

ModelingControl

ModelingOptimization

Modeling Modeling

R. MaekawaNIFSJapan

Commercial liquefier+

LHD Refrigerator

PhysicsDAE*

(cryo lib)

Partial High Pressure control with

feed forwardJapan LHD Refrigerator10kW @ 4.5 K

(cryo lib) feed-forward action

I.ButkevitchKapitza insti.

Commercial liquefierfor university

MathematicalHeuristic

No NoKapitza insti.

Russiafor university

educationHeuristic

H. QuackUT Dresden

Commercial liquefier PhysicsDAE*

No No

Germany (cryo lib)

C. Deschildre CEA/AL/Gipsa

800 W refrigerator+

PhysicsDAE*

No Pulse management

6

France Commercial liquefier (standard lib) for future tokamaks

*Differential Algebraic Equations

Page 7: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

PROCOS : Process & Control Simulator

CERN processes : Commercial liquefierCommercial liquefier Medium and very large helium refrigerators @ 4.5 K Refrigeration units @ 1.8 K with cold-compressors

Modeling tasks Use of equations from physics

Differential Algebraic Equation (DAE) with EcosimProg q ( ) Identification techniques

Matlab

C t i t Si l ti f t l t Constraint : Simulation of control systems Use of existing control programs

PLC Schneider & Siemens (Programmable Logic Controller ) Use of existing CERN supervision system Use of existing CERN supervision system

PVSS

7

Page 8: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Contents

Introduction Motivations and state of art

Dynamic simulator for cryogenic systems Simulation and control architecture Cryogenic Modeling

Simulations of cryogenic systems operating at 4.5 K CMS cryoplant Central Helium Liquefier LHC refrigerator

Simulation of LHC 1.8 K refrigeration units Cold compressors Cryogenic Distribution Line

Conclusion & Perspectives8

Page 9: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

CERN control architecture for cryogenics

SupervisionLayerData Server

SCADA(PVSS)

Supervision controles(PVSS)

Control

(PVSS)

Réseau technique Ethernet / MOD ou S7

ControlLayer

PLCSchneider

PLCSiemens

FieldLayer

I/O (Field bus)I/O (Field bus)

Real process

9

Page 10: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

CERN control architecture for simulation

SupervisionLayerData Server

SCADA(PVSS)

Supervision controles(PVSS)

C t l

(PVSS)

Réseau technique Ethernet / MOD ou S7

ControlLayer

Unity(PLC simulator)

Simatic WinLC(PLC simulator)

FieldLayer

OPC clientProcess model (EcosimPro)

I/O (OPC) I/O (OPC)

C++ application

C++ class

EcosimPro

model

10Cryogenic Process Simulator (CPS)

EcosimPro algorithm

model

Page 11: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Refrigerator operationog

(T)

C1 1 bar15 bar

Electrical power

Water cooler

Heat

mpe

ratu

re -

Lo

300 K300 K

Extraction

HX1

Tem

HX2

HX3

T1Mechanical Work

HX3

HX4T2Mechanical

k

Expansionvalve

Joule-ThomsonJT valve

HX5Work

5 K

Entropy - S

Joule-Thomson

Thermal load

Thermal load

1 bar / 4.5 K

11

Q = m * Lv

Lv ~ 19 g/J for helium

Page 12: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

A component library for cryogenics

Interface components

Inputs/OutputsAnalog/Digital

PLC components

Logical blocksControllers (PID)

Helium port

P, h, m

EcosimProHelium MaterialProperties

Analog/Digital Controllers (PID)

EcosimProLibrary

Helium cryogenics

Thermodynamicproperties

(HEPAK tables)

PropertiesStainless steel 304L Aluminum 6061 T6

Copper

Storage components

- pipes

Hydraulic components

- Valves- Turbines

Thermal components

-Thermal loads- Phase separators

Calcul : P, hout

-Screw compressors-Hydrodynamic compressors

Calcul : m, hout

-Heat Exchangers

Calcul : hout, Pout, min

12

Page 13: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Interconnections between components

Rule 1Hydraulic component

Between 2 storage componentsg

Rule 2Rule 2Thermal component in series or

between a storage component and an hydraulic component

13

Page 14: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Variational approach

Some parameters are difficult to find in large cryogenic systems Geometrical parameters (length, pipe shape, HX parameters, etc.) Thermal parameters (insulation) “Secret” parameters (turbines)

Generally, manufacturers guarantee a nominal operation point : Static calculations performed by manufacturers

If X depends on an unknown constant K1 :

Known design point : Known design point :

Ratio between both:

Non-linearity of ‘f(P,T)’ are kept and unknown constants are removed

Page 15: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Example in EcosimPro

Example of a model in EcosimProLinde18kW cold-box for the LHC

15

Page 16: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Example in EcosimPro (Zoom)

16

Page 17: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Example in EcosimPro (HX parameters)

17

Page 18: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Example in EcosimPro (first turbines)

18

Page 19: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Example in EcosimPro (adsorbers)

19

Page 20: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Contents

Introduction Motivations and state of art

Dynamic simulator for cryogenic systems Simulation and control architecture

C i M d li Cryogenic Modeling

Simulations of cryogenic systems operating at 4.5 K CMS cryoplant CMS cryoplant Central Helium Liquefier LHC refrigerator

Simulation of LHC 1.8 K refrigeration units Cold compressors Cryogenic Distribution Line

Conclusion & Perspectives20

Page 21: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Component model validation

Individual validation Constant boundary conditions Transient checkingg Operation point checking

Validation of a reduced set of components Ex : Valve + pipe + turbine

21

Page 22: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Multi-component model validation

CMS cryoplant Cooldown CMS magnet (225 tons) Air Liquide – 1.5 kW @ 4.5 K 3310 Algebraic equations 244 Differential equations Simulation speed during cool-down : x15

Validation of a complete system Validation of a complete system Simulation architecture validation Operator training tool

22

Page 23: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Virtual Commissioning

CERN central helium liquefier (B165) Provide liquid helium for small CERN experiments Commercial Linde TCF 50 – 70 Lhe / hour 2060 Algebraic equations 170 Differential equations Simulation speed during cool-down : x20

Test and improve PLC code and supervision Test and improve PLC code and supervision (collaboration with TE-CRG-CE) Bad calibration of sensors PLC-coding errors Sequence errors (timers, threshold, etc.) New turbine starting sequence PI tuning

23

Page 24: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Large-Scale system simulation: LHC refrigerator

4.5 K LHC refrigerator Linde 18 kW @ 4.5 K 4600 Algebraic equationsg q 400 Differential Equations Simulation speed: x3

Operator training tool High Pressure control High Pressure control

optimization (IMC) New control strategies to

reduce operation costs (fl ti )(floating pressure)

24

Page 25: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

LHC refrigerator simulations

Cool-down cold-box alone

After model validation :Optimization in simulation

(real refrigerator in operation non available)

Cool-down cold-box alonecold box alone

Cool-down cold-box alone Stable state reached

with LHC(16 kW @ 4.5 K)

25

Page 26: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

High Pressure control optimization (IMC)

-IMC : « Internal Model Control »-Model Synthesis-Model uncertainties evaluations

-Synthesis of the controller Q using a robust tunning

Guarantee stability for the worst caseAdapt model in real-time (according to compression station state)Take into account saturation of valves (« anti-windup »)

Simulation results:

B tt b tBetter disturbance

Better set-point tracking

Better robustnessrejection

26

Page 27: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Floating pressure System

High Pressure (HP) influences refrigeration power Load adjusted with an electrical heater in the phase separator

Floating Pressure system: Adaptation of HP and MP to loads applied to the refrigerator Floating Pressure system: Adaptation of HP and MP to loads applied to the refrigerator Compressor flow rate decreases : Electrical consumption decreases First tests in1994 on12kW @ 4.5 K refrigerators (LEP) Manual or semi-automated management

Automatic control system to fluctuate HP and MP Objective : Stabilize the electrical heater at a desired value (ex : 1kW)

27

Page 28: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Floating Pressure approach

Contrôle direct du niveau en pilotant la Haute Pression : Régulation Cascade

Heaterniveau

Level set point +10

Heater 1 = 1kW

Level set-point80%

Level set-point +1090%

L l t i t 2060%

Heater 1 + 2

Level set-point -20

t t

Refrigerator PhaseSeparator

Liquid levelHP set-point liquefactionFloating Pressure Controller

Levelset-point

+-

Level controller 1

Heater 1Level set-point-20%

Sat=1kW+

-

28

Level controller 2

Heater 2 (secu)Level set-point + 10% + -

Page 29: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Non-Fragile PI tuning

Floating Pressure controller (FPC)

Non-fragile

Level controllers (LC240/LC241)

Non-fragile

29

Page 30: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Simulation results

FPC start High Set-Point

FPC set-point

Load decrease

LoadLow Set-Point

Increase

Activation of 2nd heater

No Saturation on1st heater

Heater Set-point = 1kW

30

Page 31: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Variable-Frequency drive for compressors

31

Page 32: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Variable-Frequency drive for compressors

With ideal VFD

32

Page 33: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Variable-Frequency drive for compressors

With ideal VFD

33

Page 34: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

VFD Vs slide valve during floating pressure

With ideal VFD

34

Page 35: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Contents

Introduction Motivations and state of art

Dynamic simulator for cryogenic systems Simulation and control architecture

C i M d li Cryogenic Modeling

Simulations of cryogenic systems operating at 4.5 K CMS cryoplant CMS cryoplant Central Helium Liquefier LHC refrigerator

Simulation of LHC 1.8 K refrigeration units Cold compressors Cryogenic Distribution Line

Conclusion & Perspectives35

Page 36: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Large cryogenic systems at 1.8 K

Cool-down dysphasic helium from 4.5 K to 1.8 K Pumping on helium baths from 1 bar to 16 mbar

Large cryogenic systems (pumping flow rate > 60 g/s for LHC) Cold Compressors (helium at 4 K, compression ratio ~ 60) Pumping on long cryogenic lines (3.3 km for the LHC)

1.8 K refrigeration unit for the LHC 2800 Algebraic equations 2800 Algebraic equations 210 Differential equations Simulation speed during pumping : x80

36

Page 37: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Cold-Compressor : characteristic identification

Cold compressor= hydraulic component Strict pressure field to respect: m = f(ratio pressure, speed) “Move” theoretical pressure field from measurements to fit real data Move theoretical pressure field from measurements to fit real data

37

Page 38: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

LHC cryogenic distribution line

QRL : Transport cold helium along LHC Return Pumping Line (Line B)

Low pressure cold helium : 3 K /16 mbarp

Development of a dynamic model Low pressure and temperature helium flow Convection heat transfers Convection heat transfers Interconnections every 107 m

Euler equations:

Simplification for QRL (PDE 1D) : Simplification for QRL (PDE 1D) :

with:38

Page 39: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Jacobian calculation

Equation of state:

Perfect GAZ Gaseous low pressure helium

Equation of state:

Pressure: Pressure:

Sound speed: Sound Speed:

Jacobian: Jacobian:

Eigen values: Eigen values :Eigen values: Eigen values :

39

Page 40: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Discretization

Finite element method with an upwind scheme Discretization according to the propagation direction Mass and energy along the flow direction (transport) Mass and energy along the flow direction (transport) Momentum on the inverse direction of the flow (pumping)

Dirichlet boundary conditions: Dirichlet boundary conditions: Input density ρ(0,t) Input energy E(0,t) Output momentum M(L t) Output momentum M(L,t)

Implicit temporal discretization (backward Euler) :p p ( )

40

Page 41: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Interconnections and heat transfers

Interconnections every 107 m Source term is augmented (mass, momentum and energy)

Heat transfers: Constant term (conduction, radiation) : 1,92 W/m3 on line B

Variable term(convection) :

41

Page 42: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Simulation of the final pumping

Pumping between 100 mbar and16 mbar

42

Page 43: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Simulation after a « quench »

« Quench » : Resistive transition between the superconductor state and the resistive state: Release a large amount of energy (heat)

Simulation of the “heat wave” induced by a quench in the return pumping line Comparison with a quench in the LHC sector 5-6 during hardware commissioning (May 2008)

Simulation with Δx=107m Simulation with Δx=10,7m

43

Page 44: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Contents

Introduction Motivations and state of art

Dynamic simulator for cryogenic systems Simulation and control architecture

C i M d li Cryogenic Modeling

Simulations of cryogenic systems operating at 4.5 K CMS cryoplant CMS cryoplant Central Helium Liquefier LHC refrigerator

Simulation of LHC 1.8 K refrigeration units Cold compressors Cryogenic Distribution Line

Conclusion & Perspectives44

Page 45: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Main Contributions

A dynamic simulator for CERN cryogenic plants « Cryo Simulation Lab » available at CERN for TE-CRG (building 36) « Virtual commissioning » in collaboration with TE CRG CE (B163 & B165) « Virtual commissioning » in collaboration with TE-CRG-CE (B163 & B165)

45

Page 46: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Main Contributions

Control Improvements Optimization of the High Pressure control on LHC refrigerators (IMC) Development of a floating pressure control to reduce operational costs on Development of a floating pressure control to reduce operational costs on

LHC cryoplants

QRL model Dynamic model of low pressure helium flow in long pumping lines

46

Page 47: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Perspectives

Export simulator to other large cryogenic plants Helium refrigerator @ 2 K for the XFEL project at DESY (in discussion) Helium refrigerator @ 2 K for the XFEL project at DESY (in discussion) Dynamic behavior during pulsed heat loads for tokamaks (ITER ?)

IMC and floating pressure control test on real LHC refrigerators Possible windows in may/june 2010 ? Speed variator study (in discussion)

Extension of the « cryo » library to other industrial processes Water cooling (already done for STP18) Electronic cooling for detectors (C0 C F ) Electronic cooling for detectors (C02, C6F14 …) LHC ventilation systems

47

Page 48: Modeling, Simulation and Control of CERN cryogenic systems · 2010-03-26 · A&T sector SEMINAR Modeling, Simulation and Control of CERN cryogenic systems Benjamin BRADU CERN, EN-ICE

Thank you for your attention

Questions ?Questions ?