4
Standby: kW 130-200 kVA 163-250 Ratings Range — 60 Hertz Operation RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. STANDBY RATINGS: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. PRIME POWER RATINGS: Prime power ratings apply to installations where utility power in unavailable or unreliable. At varying load the number of generator set oper- ating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO -3046/1, BS5514, AS2789, and DIN 6271. For limited running time and base load ratings consult the factory. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 0.5% per 100m (328 ft.) elevation above 1000m (3279 ft.)Temperature: Derate 1.0% per 10°C (18°F) tem- perature above 40°C (104°F). Genset Model Number Alternator Voltage L-N / L-L Phase Hertz Natural Gas 130º Rise Standby Rating LP Gas 130º Rise Standby Rating kW / kVA Amps kW / kVA Amps TG200 431CSL6206 277/480 3 60 200/250 301 130/163 195 139/240 3 60 200/250 602 130/163 391 127/220 3 60 200/250 657 130/163 426 240/416 3 60 200/250 347 130/163 226 120/208 3 60 200/250 695 130/163 451 120/240 3 60 200/250 602 130/163 391 220/380 3 60 170/212 322 130/163 247 120/240 1 60 161/161 691 130/130 542 432PSL6228 120/240 1 60 200/200 833 130/130 542 Single source responsibility for the generator set and accessories. Prototype and production tested to insure one step load acceptance per NFPA 110. Two year limited warranty on generator sets and accessories. Extended warranties also available. Unit conforms to CSA, NEMA, EGSA, ANSI and other standards. Heavy duty 4 cycle industrial engine for reliability and fuel efficiency. Brushless rotating field generator with class H insulation. Heavy duty steel base with integral vibration isolators. EPA Certified for Stationary Emergency Standby use only. FEATURES GEN SET RATINGS Shown with optional features. Model: TG200

Transcript of Model: TG200 - Penncat Corporation · Heavy duty 4 cycle industrial engine for reliability...

Standby: kW 130-200 kVA 163-250

Ratings Range — 60 Hertz Operation

RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. STANDBY RATINGS: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. PRIME POWER RATINGS: Prime power ratings apply to installations where utility power in unavailable or unreliable. At varying load the number of generator set oper-ating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS5514, AS2789, and DIN 6271. For limited running time and base load ratings consult the factory. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 0.5% per 100m (328 ft.) elevation above 1000m (3279 ft.)Temperature: Derate 1.0% per 10°C (18°F) tem-perature above 40°C (104°F).

Genset Model Number

Alternator Voltage L-N / L-L

Phase Hertz

Natural Gas 130º Rise

Standby Rating

LP Gas 130º Rise

Standby Rating

kW / kVA Amps kW / kVA Amps

TG200 431CSL6206 277/480 3 60 200/250 301 130/163 195

139/240 3 60 200/250 602 130/163 391

127/220 3 60 200/250 657 130/163 426

240/416 3 60 200/250 347 130/163 226

120/208 3 60 200/250 695 130/163 451

120/240 3 60 200/250 602 130/163 391

220/380 3 60 170/212 322 130/163 247

120/240 1 60 161/161 691 130/130 542

432PSL6228 120/240 1 60 200/200 833 130/130 542

Single source responsibility for the generator set and accessories.

Prototype and production tested to insure one step load acceptance per NFPA 110.

Two year limited warranty on generator sets and accessories. Extended warranties also available.

Unit conforms to CSA, NEMA, EGSA, ANSI and other standards.

Heavy duty 4 cycle industrial engine for reliability and fuel efficiency.

Brushless rotating field generator with class H insulation.

Heavy duty steel base with integral vibration isolators.

EPA Certified for Stationary Emergency Standby use only.

FEATURES

GEN SET RATINGS

Shown with optional features.

Model: TG200

Application and Engineering Data

Basic Technical Data Manufacturer Doosan Model D111TIC Number of cylinders 6

Cylinder arrangement Vertical in-line

Cycle 4 Induction system Turbocharged, Aftercooled

Compression ratio 10.5.:1

Bore 4.84 in (123 mm) Stroke 6.10 in (155 mm) Cubic capacity 674 cu in (11.05 L)

Piston speed 1831 ft/min (558 m/min)

Main bearings: qty and type 7, Precision Half-Shell Governor type Electronic Rated rpm 1800 Max power at rated rpm 302 hp (225 kW)

Engine power at Standby rating

302 (225)

Frequency regulation, no-load to full-load

Isochronous

Frequency regulation, steady state

± 0.5%

Frequency Fixed

Air cleaner type Dry

Exhaust System

Exhaust manifold type Wet

Exhaust flow at rated kW 1121 cfm

Exhaust temperature at rat-ed kW

1112 ºF (600 ºC)

Maximum allowable back pressure

3.0 in (10.2 kPa)

Exhaust outlet size at engine hookup

N/A

Cooling System

Ambient temperature 122 ºF (50 ºC) Engine jacket water capacity 5.5 gal (21 L) Radiator system capacity, including engine

30.6 gal (116 L)

Engine jacket water flow 75 gpm (284 Lpm) Heat rejected to cooling water at rated

8100 Btu/min (142.3 kW)

Max restriction of cooling air, intake and discharge side of radiator

0.5 H2O (0.125 kPa)

Lubrication System

Type Full Pressure

Oil pan capacity 26.4 qt (25 L)

Oil pan capacity with filter 28.8 qt (27 L)

Oil filter: qty and type 1, Cartridge

Electrical System

Ignition system

Battery charging alternator:

Ground negative

Volts 24

Ampere rating 45

Starter motor rated voltage 24

Battery, recommended cold cranking amps (CCA):

Qty rating for –18 ºC (0 ºF) Two, 1000

Battery voltage 12

Operation Requirements

Radiator-cooled cooling air 18,000 scfm (510 m³/min)

Combustion air 390 cfm (12.6 m³/min)

Heat rejected to ambient air:

Engine 3430 Btu/min (60.3 kW)

Alternator 910 Btu/min (16.0 kW)

Fuel System

Fuel Type LP Gas, Natural Gas or Dual Fuel

Fuel Consumption

Natural Gas

100% Load 2115 cfh (59.9 m³/hr)

75% Load 1649 cfh (46.7 m³/hr)

50% Load 1158 cfh (32.8 m³/hr)

25% Load 706 cfh (20.0 m³/hr)

LP Gas 100% Load 703 cfh (19.9 m³/hr)

75% Load 600 cfh (17.0 m³/hr)

50% Load 406 cfh (11.5 m³/hr)

25% Load 254 cfh (7.2 m³/hr)

Generator Controller Options

Manufacturer Marathon NEMA MG1, IEEE, AND ANSI standards compliance for temperature and motor starting. Type Ext. Voltage Regulated, Brushless

Gen Frame MAGNAPLUS Sustained short-circuit current of the rated current for up to 10 seconds. Insulation NEMA

Material Class H Sustained short-circuit current enabling downstream

circuit breakers to trip without collapsing the alternator Temperature Rise 130 ºC, Standby

Hertz 60 Self-ventilated and dripproof construction.

Phase 3 Superior voltage waveform from a two-thirds pitch stator and skewed rotor. RPM 1800

Exciter Rotating Linkboards

# Leads 12 Reconnectable or 4 Single Phase Optimized Electrical Design

PF 0.8 Enhanced Ventilation

Ambient 40ºC Fully Guarded

Coupling Single Bearing Flexible Heavy Duty Bearings

Amortisseur Windings Full

Cooling Air Volume 1280 CFM

Peak Motor Starting 30% Voltage Dip, 664 skVA @ 480V

Voltage Regulation no-load and full-load

1 Phase Sensing 1% Optional 3 Phase Sensing 1/2%

Alternator Specifications

- Dashboard Style LCD Panel- NFPA 110

- Load Share Synch Features- Metering, Data Trending, Alarms

- CanBus, ModBus- Ethernet Communications- Remote Contacts Form C, RS 232/485

- Remote Access & Control- InteliMonitor Network Management- SNMP, PC SCADA- Site Overview & Statistic Settling- Automatic Downloads, Report Writer- Receive Emails or IM Text- CAT 5e, RS232/485, RJ 45

- Fleet Scalability

- Internet Bridge Module

- Fuel Consumption

- Internet Connection & Web Browser

- SAE J1939 ECU Communications

- Engine Status Indicators

- Ethernet or Dial Up Connection

OVERALL SIZE, L x W x H, in.: 120 in x 66 in x 80 in WEIGHT: 5395 lbs. Note: Dim and weights reflect standard open unit with no options

Note: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.

Heavy Duty Steel Base

Vibration Isolators

Oil Drain Valve with Extension

Battery Rack

Battery Cables

High Ambient Unit Mounted Radiator

Battery Charging Alternator

Factory Paint

Factory Test Prior to Shipment

2 Year Warranty

Owners Manual

STANDARD FEATURES

AVAILABLE ACCESSORIES

WEIGHTS AND DIMENSIONS

DISTRIBUTED BY:

OPEN UNIT

⃞ Narrow Skid Base

⃞ Radiator Duct Flange

⃞ Ship Loose Flex Exhaust

⃞ Ship Loose Critical Silencer

ENCLOSED UNIT

⃞ Wide Skid Base

⃞ Standard Enclosure With Internal Silencer

⃞ Sound Attenuated Enclosure With Silencer

⃞ Load Center With Lights and GFI Receptacle

CONTROLLER

MISCELLANEOUS

⃞ Flexible Fuel Lines

⃞ Coolant Drain Kit

⃞ Water Jacket Heater

⃞ Oil Pan Heater

⃞ Generator Strip Heater

⃞ Battery

⃞ Battery Charger

⃞ Pad Type Battery Heater

⃞ Battery Heater Blanket with Thermostat

⃞ Line Circuit Breaker

⃞ Dual Fuel

WARRANTY

⃞ 3 Year Warranty

⃞ 5 Year Warranty

InteliLite Model IL-NT-MRS19

Ethernet Bridge

Remote Annunciator

PENNCAT CORPORATION404 ELM AVENORTH WALES, PA 19454TEL: (610) 272-0505www.PENNCAT.com