MODEL PWFY-P200VM-E1-AU - For high temperature flow · piping contains a large amount of chlorine...
Transcript of MODEL PWFY-P200VM-E1-AU - For high temperature flow · piping contains a large amount of chlorine...
DATA BOOK
PWFY-P200VM-E1-AU- For high temperature flow
MODEL
- i -
• Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or � re during use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.- MITSUBISHI ELECTRIC CORPORATION cannot
be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
• Do not use steel pipes as water pipes. - Copper pipes are recommended. • The water circuit should be a closed circuit. • Ask the dealer or an authorized technician to
install the air conditioner.- Improper installation by the user may result in water
leakage, electric shock, or � re.• Install the unit in a place that can withstand its
weight.- Inadequate strength may cause the unit to fall down,
resulting in injuries.• Do not touch the unit. The unit surface can be hot.• Do not install the unit where corrosive gas is
generated.• Use the speci� ed cables for wiring. Make the
connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a � re.
• Prepare for rain and other moisture and earthquakes and install the unit at the speci� ed place.
- Improper installation may cause the unit to topple and result in injury.
• Always use an strainer and other accessories speci� ed by Mitsubishi Electric.
- Ask an authorized technician to install the accesso-ries. Improper installation by the user may result in water leakage, electric shock, or � re.
• Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or � re may result.
• Do not touch the refrigerant pipes and Water pipes.
- Improper handling may result in injury.• When handling this product, always wear protec-
tive equipment. EG: Gloves, full arm protection namely boiler suit,
and safety glasses.- Improper handling may result in injury.• If refrigerant gas leaks during installation work,
ventilate the room.- If the refrigerant gas comes into contact with a � ame,
poisonous gases will be released.• Install the unit according to this manual.- If the unit is installed improperly, water leakage,
electric shock, or � re may result.• Have all electric work done by a licensed electri-
cian according to “Electric Facility Engineering Standard” and “Interior Wire Regulations” and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed improperly, electric shock and � re may result.
• Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching � re or smoke.
• Securely install the heat source unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter the heat source unit and � re or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge it with a refrigerant different from the refrigerant (R410A) speci� ed on the unit.
- If a different refrigerant or air is mixed with the origi-nal refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.
Safety Precautions
- ii -
• Do not use the existing refrigerant piping.- The old refrigerant and refrigerant oil in the existing
piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to dete-riorate.
- R410A is a high-pressure refrigerant and can cause the existing piping to burst.
• Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized copper as speci� ed in the JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the in-ner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-ing particles, oils, moisture, or any other contami-nant.
- Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
• Apply a small amount of ester oil, ether oil, or alkyl benzene to � ares. (for indoor unit)
- In� ltration of a large amount of mineral oil may cause the refrigerant oil to deteriorate.
• Use liquid refrigerant to � ll the system.- If gas refrigerant is used to seal the system, the
composition of the refrigerant in the cylinder will change and performance may drop.
• Do not use a refrigerant other than R410A.- If another refrigerant (R22, etc.) is mixed with
R410A, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
• Use a vacuum pump with a reverse � ow check valve.
- The vacuum pump oil may � ow back into the refrig-erant cycle and cause the refrigerant oil to deterio-rate.
• Do not use the following tools that are used with conventional refrigerants.
(Gauge manifold, charge hose, gas leak detector, reverse � ow check valve, refrigerant charge base, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerant oil are mixed in the R410A, the refrigerant may deterio-rated.
- If water is mixed in the R410A, the refrigerant oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
• Do not use a charging cylinder.- Using a charging cylinder may cause the refrigerant
to deteriorate.• Do not use antioxidant or leak-detection additive.• Be especially careful when managing the tools.- If dust, dirt, or water gets in the refrigerant cycle, the
refrigerant may deteriorate.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refriger-ant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate meas-ures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or � re may result.
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may gen-erate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those speci� ed by Mitsubishi Electric are used, � re or explosion may result.
• To dispose of this product, consult your dealer.• The installer and system specialist shall secure
safety against leakage according to local regula-tion or standards.
- Following standards may be applicable if local regu-lation are not available.
• Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigeration is heavier than the air.
- iii -
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.• Do not use the air conditioner in special environ-
ments.- Oil, steam, sulfuric smoke, etc. can signi� cantly reduce
the performance of the air conditioner or damage its parts.
• When installing the unit in a hospital, communica-tion station, or similar place, provide suf� cient protection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio commu-nication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor unit. Perform collective drainage work together with the unit, as required.
- iv -
• Ground the unit.- Do not connect the ground wire to gas or water
pipes, lightning rods, or telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a � re.
• Install a leak circuit breaker, as required.- If a leak circuit breaker is not installed, electric shock
may result.• Use power line cables of suf� cient current
carrying capacity and rating.- Cables that are too small may leak, generate heat,
and cause a � re.• Use only a circuit breaker and fuse of the
speci� ed capacity.- A fuse or circuit breaker of a larger capacity or a
steel or copper wire may result in a general unit failure or � re.
• Do not wash the air conditioner units.- Washing them may cause an electric shock.• Be careful that the installation base is not
damaged by long use.- If the damage is left uncorrected, the unit may fall
and cause personal injury or damage property.• Install the drain piping according to this manual to
ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture and other possessions.
• Be very careful about product transportation.- If the unit weighs more than 20kg, carry the unit with
more than one person.- Some products use PP bands for packaging. Do not
use any PP bands for a means of transportation. It is dangerous.
- When transporting the unit, support it at the speci� ed positions on the unit base. Also support the unit at four points so that it cannot slip side ways.
• Safely dispose of the packing materials.- Packing materials, such as nails and other metal or
wooden parts, may cause stabs or other injuries.- Tear apart and throw away plastic packaging bags
so that it is out of reach of children. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
- v -
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch the switches with wet � ngers.- Touching a switch with wet � ngers can cause elec-
tric shock.• Do not touch the refrigerant pipes during and im-
mediately after operation.- During and immediately after operation, the
refrigerant pipes are may be hot and may be cold, depending on the condition of the refrigerant � owing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least � ve minutes before turning off the power. Otherwise, water leakage and trouble may occur.
• Do not touch the surface of the compressor during servicing.
- If unit is connected to the supply and not running, crank case heater at compressor is operating.
• Do not touch the panels near the fan outlet with bare hands: they can get hot while the unit is in operation (even if it is stopped) or immediately after operation to prevent burns. Wear gloves to protect your hands when it is necessary to touch the panels.
• While the unit is in operation or immediately after operation, high-temperature exhaust air may blow out of the fan exhaust outlet. Do not hold your hands over the outlet or touch the panels near the outlet.
• Be sure to provide a pathway for the exhaust air from the fan.
• Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials to prevent burns.
ContentsSafety Precautions
I General Equipment Descriptions
1. Unit configuration table ················································· 12. Operable temperature range ······································· 13. Setting of Dip switch······················································ 1
II Product Specifications1. Specifications ································································· 2
(1) PWFY-P200VM-E1-AU (for high temperature flow)2. External Dimensions ····················································· 3
(1) PWFY-P200VM-E1-AU(2) PUHY-P300YJM-A(-BS)(3) PQHY-P300YHM-A
3. Electrical Wiring Diagrams ··········································· 6(1) PWFY-P200VM-E1-AU(2) PUHY-P300YJM-A(-BS)(3) PQHY-P300YHM-A
4. Accessories ····································································· 9(1) PWFY
III Product Data1. Capacity tables·····························································10
(1) Correction by temperature (Estimated performance without defrost)
(2) Correction by water flow rate(3) Correction at frosting and defrosting(4) Water pressure drop(5) Operation temperature range
2. Sound pressure levels ················································ 15(1) PWFY-P200VM-E1-AU
3. Refrigerant circuit diagrams and thermal sensors ··· 15(1) PWFY-P200VM-E1-AU
IV Installation1. How to calculate the necessary heating capacity ·· 16
(1) Heating capacity calculation(2) Calculation example
2. Installation ·····································································17(1) Selecting an installation site (for PWFY unit)(2) Installing the unit(3) Refrigerant pipe and drain pipe specifications(4) Connecting refrigerant pipes and drain pipes
3. Water pipe installation················································· 24(1) Water circuit sample(2) Selecting a water pump(3) Installing the strainer(4) Precautions during installation(5) Example of unit installation(6) Insulation installation(7) Flow switch installation(8) Water processing and water quality control(9) Pump interlock(10) Anti freeze mode (Dip SW4-4 ON)
V System Design1. Electrical work ······························································30
(1) General cautions(2) Power supply for PWFY unit(3) Connecting remote controller, indoor and outdoor
transmission cables(4) Transmission cable specifications(5) Connecting electrical connections(6) Indoor unit address setting(7) External input/output function
VI Controller1. PAR-W21MAA specifications····································· 362. Dip switch functions ···················································· 37
VII Maintenance Cycle1. Routine maintenance checks ···································· 382. Parts Replacement Cycle··········································· 38
- 1 -
1. Unit configuration table
Model NameATW unit PWFY-P200VM-E1-AUOutdoor unit(Heat source unit)
PUHY-P300YJM-A PQHY-P300YHM-A
2. Operable temperature rangePWFY
Cooling HeatingInlet water temperature 10 to 35ºC 10 to 55ºCOutdoor temperature Y series -5 to 46ºCDB -5 to 15.5ºCWBCirculating water temperature WY series 10 to 45ºC 10 to 45ºC
3. Setting of Dip switch<Outdoor unit (Heat source unit)>Dip SW 3-7 OFF, Dip SW 4-7 ON
<ATW unit>Dip SW 1-6 ON, Dip SW 3-8 ON
General Equipment Descriptions I
- 2 -
1. Specifications(1) PWFY-P200VM-E1-AU (for high temperature flow)
Product Specifications II
Model
Power sourcekW*1Heating capacitykcal / hBTU / hkWkcal / hBTU / h
*1*1
kW
-
Inlet Water temp.-
*2
Cooling capacity-kWkcal / hBTU / hkW
*2
(Nominal)
*2
*3*3*3
Power inputCurrent input A
--
dB<A>mm(in.)mm(in.)mm(in.)mm(in.)mm(in.)mm(in.)
mmExternal finishExternal dimension H × W × D
in. kg(lbs)Net weight
Circulating waterRange
Design pressureWaterR410A
Drawing
Standard attachment
Optional partsRemark
Note:
InletOutlet
Operation Volume
LiquidGas
m3/h
MPaMPa
Accessory
ExternalWiringDocument
Unit converter
*2 Hi-temp flow Heating conditions
*1 Nominal heating conditions
Outdoor Temp. : 7°CDB/6°CWB (45°FDB / 43°FWB)
Outdoor Temp. : -3°CWB (27°F)Pipe length : 7.5m (24-9/16ft)
Pipe length : 7.5m (24-9/16ft)
Level difference : 0m (0ft)
Level difference : 0m (0ft)Inlet water Temp 30°C Water flow rate 4.30m3/h Inlet water Temp 30°C Water flow rate 4.30m3/h
Inlet water Temp 45°C Water flow rate 2.50m3/h
Water flow rate 3.86m3/h
Inlet water Temp 45°C Water flow rate 2.50m3/h
* Due to continuing improvement, the above specifications may be subject to change without notice.* The unit is not designed for outside installations.* Please don't use the steel material for the water piping material.* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 0°C or less.* Please always make water circulate or pull out the circulation water completely when not using it.* Please do not use groundwater and well water.* Install the unit in an environment where the wet bulb Temp. will not exceed 32°C. * The water circuit must use the closed circuit.* Please do not use it as a drinking water.
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual.
10~45°C (50~113°F)
25.0 / 22.521,500 / 19,40085,300 / 76,800
21,50085,300
0.015
E94C228X01
NONE
Ø32 (1-1/4'')
PWFY-P200VM-E1-AU (for high temperature flow)1-phase 220-230-240V 50/60Hz
10~55°C (50~131°F)-5~45°C (23~113°F)
29
25.0
1.2~4.30
1.00
Strainer, Connecter, Heat insulation material, 2 × Connector sets, Expansion joint, wire, Flow switch × 1set
PT 1 Screw
Installation Manual, Instruction Book
NO
WKB94L763
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”38 (84)
800 (785 without legs) × 450 × 300
4.15
19,300
Ø19.05 (Ø3/4") Brazed
Ø19.05 (Rc3/4") Brazed
Ø9.52 (Ø3/8") Brazed
PT 1 Screw
76,400
22.4
-5~45°C (23~113°F)10~35°C (50~95°F)
PUHY-P300YJM-A(-BS) / PQHY-P300YHM-A
0.0150.068 - 0.065 - 0.063
kcal = kW × 860BTU/h= kW × 3,412cfm = m3/min × 35.31lbs = kg / 0.4536* The specification data is subject to rounding variation.
AW.B
0.068 - 0.065 - 0.063-5~15.5°C (23~60°F)
D.B-
-5~43°C (23~110°F) 10~45°C (50~113°F)
<PUHY-series>
<PUHY-series>
*3 Nominal cooling conditions
Outdoor Temp. : 35°CDB (95°FDB)Pipe length : 7.5m (24-9/16ft)Level difference : 0m (0ft)Inlet water Temp 23°C
<PUHY-series>
Circulating water Temp. : 20°C (68°F) Pipe length : 7.5m (24-9/16ft)Level difference : 0m (0ft)
brain connection 0%
brain connection 0%
<PQHY-series>
<PQHY-series>Circulating water Temp. : 2°C (36°F)Pipe length : 7.5m (24-9/16ft)Level difference : 0m (0ft)
Inlet water Temp 23°C Water flow rate 3.86m3/hbrain connection 0%
<PQHY-series>Circulating water Temp. : 30°C (86°F)Pipe length : 7.5m (24-9/16ft)Level difference : 0m (0ft)
Temp.range ofheating
Heatsourcerange
Nominal
High temp. flow Heating(PUHY/PQHY)
Power inputCurrent input
PUHY - seriesPQHY - seriesPQHY - series (for ground source)
PWFY range
Temp.range ofheating
Heatsourcerange
PUHY - seriesPQHY - seriesPQHY - series (for ground source)
PWFY range
Outdoor temp.Circulating water temp.Circulating brine temp.
Inlet Water temp.
Outdoor temp.Circulating water temp.Circulating brine temp.
Diameter of refrigerant pipe
Diameter of water pipe
Sound pressure level (measured in anechoic room)
Strainer sizeField drain pipe size
Connectable outdoor unit/heat source unit
- 3 -
2. External Dimensions(1) PWFY-P200VM-E1-AU
300 600
Fig.
A
Ser
vice
spa
ce(fr
ont s
ide)
Top
view
400
Pip
ing
spac
e(r
ight
sid
e)P
200:
Use
the
Exp
ansi
on jo
int
o
f acc
esso
ries
Dra
in (R
1 sc
rew
)
ø9.5
2 <B
raze
d>
ø27
Kno
ckou
t hol
e<H
ole
for c
ontro
l wiri
ng>
ø27
Kno
ckou
t hol
e<H
ole
for p
ower
sup
ply>
Wat
er o
utle
t(R
C3/
4 sc
rew
)
Wat
er in
let
(R3/
4 sc
rew
)
P20
0:ø1
9.05
<B
raze
d>
ø27
Kno
ckou
t hol
e<H
ole
for e
xter
nal w
iring
inpu
t>ø2
7 K
nock
out h
ole
<Hol
e fo
r ext
erna
l wiri
ng o
utpu
t>
Con
nect
ion
pipe
of o
utdo
or u
nit
(Gas
)
Con
nect
ion
pipe
of o
utdo
or u
nit
(Liq
uid)
Fron
t vie
wR
ight
sid
e vi
ew
Con
trol b
ox
Ser
vice
pan
el
Top
view
2X2-
ø14
Hol
e
525
(Mou
ntin
g pi
tch)
450
(Mounting pitch)300 800
205
500
<Acc
esso
ries>
●Y-ty
pe s
train
er (R
C3/
4) ··
······
······
······
······
··· 1
pc.
●Wire
·····
······
······
······
······
······
······
······
······
·····
1pc.
●Flo
w s
witc
h ···
······
······
······
······
······
······
······
·· 1s
et
●Hea
t Ins
ulat
ion
mat
eria
l ····
······
······
······
······
1pc
.●C
onne
ctor
set
·····
······
······
······
······
······
······
··· 2
set
●Exp
ansi
on jo
int (
P20
0) ··
······
······
······
······
···· 2
pcs.
[F
rom
RC
3/4
to R
C1]
Not
e 1.
Ens
ure
no ra
in w
ater
or d
ebris
can
ent
er th
e un
it th
roug
h an
y ga
ps a
roun
d
w
iring
or p
ipin
g.
2.E
nsur
e ad
equa
te s
ervi
ce s
pace
is ri
ght a
roun
d th
e un
it, a
ccor
ding
to F
ig A
.
3.P
leas
e al
way
s m
ake
wat
er c
ircul
ate
or a
dd th
e br
ine
to th
e ci
rcul
atio
n w
ater
w
hen
the
ambi
ent t
empe
ratu
re b
ecom
es 0
°C o
r les
s.
4.T
he u
nit i
s no
t des
igne
d fo
r out
side
inst
alla
tions
.
5.In
stal
l the
uni
t in
an e
nviro
nmen
t whe
re th
e w
et b
ulb
Tem
p.
will
not
exc
eed
32de
gC.
6
.Ple
ase
alw
ays
mak
e w
ater
circ
ulat
e or
pul
l out
the
circ
ulat
ion
wat
er c
ompl
etel
y w
hen
not u
sing
it.
7
.The
wat
er c
ircui
t mus
t use
the
clos
ed c
ircui
t.
8.P
leas
e do
n't u
se th
e st
eel m
ater
ial f
or th
e w
ater
pip
ing
mat
eria
l.
9.C
onne
ct th
e st
rain
er w
hich
is p
ut a
s ac
cess
ory
to w
ater
inle
t pip
e.
9191
35 5535
480 102
206
134
114
100 1914660 140 80 165
54
<Uni
t:mm
>
- 4 -
(2) PUHY-P300YJM-A(-BS)
For t
rans
miss
ion ca
bles
For w
ires
For p
ipes
Spe
cific
atio
nsU
sage
NO.
<Acc
esso
ries>
Conn
ectin
g pip
e
<Gas
>•E
lbow(
IDø2
5.4X
ODø2
5.4)
······
·P30
0•P
ipe (I
Dø25
.4XO
Dø22
.2)··
······
P300
Note
1.Pl
ease
refe
r to
the
next
page
for i
nfor
mat
ionre
gard
ing n
eces
sary
spac
ing a
roun
d th
eun
it and
foun
datio
n wo
rk.
2.Th
e de
tach
able
leg ca
n be
rem
oved
at s
ite.
At b
razin
g of
pipe
s,wra
p th
e re
frige
rant
serv
ice va
lvewi
th w
et cl
oth
and
keep
the
tem
pera
ture
of
refri
gera
nt se
rvice
valve
und
er 1
20°C
3.
1pc.
1pc.
<Liqu
id>•P
ipe (I
Dø12
.7XO
Dø12
.7)··
······
P300
•Pipe
(IDø
12.7
XODø
9.52
)·····
···P3
001p
c.1p
c.
1 2 3 4 5 6
Fron
t thro
ugh h
oleBo
ttom
throu
gh ho
leFr
ont th
roug
h hole
Fron
t thro
ugh h
oleBo
ttom
throu
gh ho
leFr
ont th
roug
h hole
102X
72 K
nock
out h
ole15
0X92
Kno
ckou
t hole
ø65
or ø
40 K
nock
out h
oleø5
2 or
ø27
Kno
ckou
t hole
ø52
Knoc
kout
hole
ø34
Knoc
kout
hole
2X5-
ø4.6
Hol
e(M
ake
hole
at t
he p
last
ic fa
n gu
ard
for s
now
hoo
d at
tach
men
t)
150 150 150 150 80
1888
418
760
920
<Sno
w h
ood
atta
chm
ent h
ole>
Top
view
1710
14101650
240
Inta
keai
r
Ser
vice
pane
l
Con
trol b
ox
Inta
keai
r
(60)
72 90
102
9820
425
1
13288
2X2-
14X
20 O
val h
ole
(fron
t and
bac
k,2
poin
ts)
Not
e 2*
Det
acha
ble
leg
64 3
1
Fron
t vie
w22
115
083
251
186
145
760
1818
86
8080
92
Ref
riger
ant s
ervi
ce
valv
e <g
as>
52
131C
Refri
gera
nt s
ervic
eva
lve <
liqui
d>
(Mou
ntin
g pi
tch)
Bot
tom
vie
w
(Mounting pitch)(760)
724(721~727)
Dis
char
ge a
ir
Inta
keai
r
Ref
riger
ant s
ervi
ceva
lve
<gas
>
Ref
riger
ant s
ervi
ce
valv
e <l
iqui
d>
A
B (60)
556025
760
255560
54
Left
side
vie
wC
onne
ctin
g pi
pe s
peci
ficat
ions
150C
172
143
BA
Gas
Liqu
id
PUHY
-P30
0YJM
Mod
el
Pos
ition
dim
ensi
ons
for t
he re
frige
rant
serv
ice
valv
eC
onne
ctio
n sp
ecifi
catio
ns fo
rth
e re
frige
rant
ser
vice
val
ve*1
Gas
Liqu
id
ø22.
2 Br
azed
ø9.5
2 Br
azed
(ø12
.7 Br
azed
)*2 *3
*1 C
onne
ct by
usin
g th
e co
nnec
ting
pipes
(for
bot
tom
pipi
ng a
nd fr
ont p
iping
)
that
are
supp
lied.
*2 In
dicat
es d
imen
sions
and
conn
ectio
n sp
ecific
ation
s in
the
case
the
unit i
s
use
d in
com
binat
ion w
ith o
ther
out
door
unit
s.*3
Tota
l leng
th>=
40m
Unit : mm
- 5 -
(3) PQHY-P300YHM-A
Ser
vice
spa
ce(fr
ont s
ide)
Servi
ce sp
ace
(fron
t sid
e)
Top
view
550
6060
20
74
1160(60)
The
spac
e fo
rco
ntro
l box
repl
acem
ent
450
600
170
350 72
5
600450
170
1100550 (530)
(102
)(5
3)
506 (503~509)
470 (467~473)
834
720
1100
141213240
2 x
2-14
x 2
0 O
val h
ole
14075
608
563
584
83 58
121226234
18
78 168
433 54
8
(550)2222
4040
550
880
2 x
2-14
x 2
0 O
val h
ole
(Inst
alla
tion
supp
ort h
ole)
(880
)
8080 23
23
Con
trol b
ox
Ser
vice
pane
l
(Inst
alla
tion
supp
ort h
ole
pitc
h) (M
ount
ing
pitc
h)
(Installation support hole pitch)
(Mounting pitch)
88
7654
3 2
Refri
gera
nt s
ervic
e va
lve
<Gas
>
Refri
gera
nt s
ervic
e va
lve
<Liq
uid>
1
(fron
t and
bac
k, 2
poi
nts)
Not
e 8*
Det
acha
ble
leg
880
ø22.
2 Br
azed
ø9.5
2 B
raze
d
Gas
Liqu
id
PQ
HY-
P30
0YH
M-A
*1*1
Fig.
BFi
g. A
Not
e 1.
Clo
se a
hol
e of
the
wat
er p
ipin
g, th
e re
frige
rant
pip
ing,
th
e po
wer
sup
ply,
and
the
cont
rol w
iring
and
unu
sed
knoc
kout
h
oles
with
the
putty
etc
. so
as n
ot to
infil
trate
rain
wat
er
etc
. (fie
ld e
rect
ion
wor
k)N
ote
2. A
t the
tim
e of
pro
duct
shi
pmen
t, th
e fro
nt s
ide
pipi
ng
spe
cific
atio
n se
rves
as
the
loca
l dra
inag
e co
nnec
tion.
W
hen
conn
ectin
g on
the
rear
sid
e, p
leas
e re
mov
e th
e
rear
sid
e pl
ug s
ealin
g co
rks,
and
atta
ch a
fron
t sid
e.
Ens
ure
ther
e is
no
leak
afte
r the
atta
chm
ent h
as b
een
fitte
d.N
ote
3. T
ake
notic
e of
ser
vice
spa
ce a
s Fi
g. A
. (In
cas
e of
sin
gle
in
stal
latio
n, 6
00m
m o
r mor
e of
bac
k sp
ace
as fr
ont s
pace
m
akes
eas
ier a
cces
s w
hen
serv
icin
g th
e un
it fro
m re
ar s
ide)
Not
e 4.
If w
ater
pip
es o
r ref
riger
ant p
ipes
stre
tch
upw
ard,
re
quire
d sp
ace
for s
ervi
ce a
nd m
aint
enan
ce d
ue to
repl
acem
ent o
f con
trol b
ox is
sho
wn
in F
ig. B
.N
ote
5. E
nviro
nmen
tal c
ondi
tion
for i
nsta
llatio
n; -2
0~40
°C (D
B)
a
s in
door
inst
alla
tion.
Not
e 6.
In c
ase
the
tem
pera
ture
aro
und
the
heat
sou
rce
unit
has
p
ossi
bilit
y to
dro
p un
der 0
°C, b
e ca
refu
l for
the
follo
win
g
poi
nt to
pre
vent
the
pipe
bur
st b
y th
e w
ater
pip
e fre
eze-
up.
·
Circ
ulat
e th
e w
ater
all
the
time
even
if th
e he
at s
ourc
e
un
it is
not
in o
pera
tion.
·
Dra
in th
e w
ater
from
insi
de o
f the
hea
t sou
rce
unit
whe
n
th
e he
at s
ourc
e un
it w
ill n
ot o
pera
te fo
r a lo
ng te
rm.
Not
e 7.
Ens
ure
that
the
drai
n pi
ping
is d
ownw
ard
with
a p
itch
of
m
ore
than
1/1
00.
Not
e 8.
The
det
acha
ble
leg
can
be re
mov
ed a
t site
.N
ote
9. A
t bra
zing
of p
ipes
, wra
p th
e re
frige
rant
ser
vice
val
ve
w
ith w
et c
loth
and
kee
p th
e te
mpe
ratu
re o
f
refri
gera
nt s
ervi
ce v
alve
und
er 1
20°C
.
ø45
Kno
ckou
t hol
e
ø34
Kno
ckou
t hol
eø5
2 or ø
27 K
nock
out h
ole
For p
ipes
For w
ires
For t
rans
miss
ion ca
bles
Fron
t thr
ough
hol
e
Fron
t thr
ough
hol
eFr
ont t
hrou
gh h
ole
Fron
t thr
ough
hol
e
140
x 77
Knoc
kout
hole
ø65 o
r ø40
Kno
ckou
t hole
Fron
t thr
ough
hol
e
Wat
er p
ipe
Dra
in p
ipe
inle
tou
tlet
Rc1
-1/2
Scr
ewR
c1-1
/2 S
crew
Rc3
/4 S
crewSpe
cific
atio
nsU
sage
NO
.C
onne
ctio
n sp
ecifi
catio
ns fo
rth
e re
frige
rant
ser
vice
val
veM
odel
Con
nect
ing
pipe
spe
cific
atio
ns
*1. C
onne
ct b
y us
ing
the
conn
ectin
g pi
pes
that
are
sup
plie
d.
<Acc
esso
ries>
· Ref
riger
ant (
Liqu
id) c
onn.
pip
e ···
··1 p
c.(P
300
; Pac
kage
d in
the
acce
ssor
y ki
t)· R
efrig
eran
t (G
as) c
onn.
pip
e ···
··1 p
c.(P
300
; Pac
kage
d in
the
acce
ssor
y ki
t)
Unit : mm
- 6 -
3. Electrical Wiring Diagrams(1) PWFY-P200VM-E1-AU
gray
red
M
For o
peni
ng/c
losi
ng th
e by
pass
circ
uit
Sol
enoi
d va
lve
SV
1
TB5
M1M2
S(SH
IELD)
To o
utdo
or u
nit/
B
C c
ontro
ller/
W
CB
4-20
mA
4-20
mA
13
2C
N42
1bl
ack
13
2C
N42
2bl
ue1
32
CN
422
blue
2bl
ack
CN
421
13
IN1
2345
yello
w/g
reen
LEV1
Wa
LEV1
Wb
Line
arex
pans
ion
valv
eB
C c
ontro
ller/W
CB
/out
door
uni
tB
C c
ontro
ller/W
CB
/out
door
uni
t
Func
tion
Func
tion
Func
tion
blac
kye
llow
purp
lebl
uere
d
NL
IN7IN
8IN
6IN
5CO
M+IN
4IN
3
oran
ge
*3.D
iffer
ence
of a
pplia
nce
*4 T
B14
1A(o
utpu
t)
*5 T
B14
2A(in
put)
*6 T
B14
2B(in
put)
*7 T
B14
2C(in
put)
Mod
el n
ame
App
lianc
eP
200
*3 e
xist
*7*6
*5
*4
Coo
ling
TH23
gas
pipe
tem
p
CN50
2bla
ck
COM+
TH8
TH6
TH23
t°t°t°
blue
CN
2M2121
CN
402
gree
n
21C
N40
3re
d
1 2C
N40
4bl
ack
yello
wC
N40
5t°
TH22
1 2
21 To
MA
rem
ote
cont
rolle
rP
ower
Sup
ply
~220
/230
/240
V50
Hz/
60H
z
Unit a
ddre
ss se
tting(
SWU1
,SW
U2)
Conn
ectio
n No
.(SW
U3)
LED
1
TB15
ZNR
1
UD
SA
1
CN
11 3
SWU2
SWU1
SWP3
SWP2
SWP1
OFF
ON
110
SW
4OF
FON
110
SW
3
OFF
ON
110
SW
1
OFF
ON
110
SW
2LE
D4:
Rem
ote
cont
rolle
r
whe
n po
wer
ed5
CN
LVC
6 1
LEV1
Wb
1234
X50
2
CN50
7
31
M56
ON OFF 1S
W5
SWU3
LED
3:Li
t whe
n po
wer
ed
Con
trol B
oard
CN
LVB
LEV1
Wa
TB2
SV1
*3
DS
A B
oard
CN
3Tre
d13
T01
ZNR
01
31
12
CNAC
red
U
F01
AC25
0V6.
3A
LED1
Disp
lay se
tting(
SW2)
Func
tion
settin
g(SW
1,SW
3,SW
4)
OUT4
OUT3
OUT2
X514
X513
X512
TB14
1A
OUT1
X511
31
CN
3Abl
ue
TB14
2CTB
142B
X516
X517
X515
OUT6
OUT7
OUT5
TB14
1B
TB14
2A
IN2
IN8
IN7
Ant
i-fre
eze
IN6
Hea
ting
EC
O
Sym
bol
CO
M+
Com
mon
IN5
Hea
ting
IN4
Ope
ratio
n O
N/O
FFC
onne
ctio
n de
man
dS
ymbo
lIN
3
Sym
bol
Flow
sw
itch
IN1
Func
tion
Sym
bol
OU
T1O
pera
tion
ON
/OFF
OU
T2D
efro
stO
UT4
Err
or s
igna
l
<CA
UTI
ON
FO
R IN
STA
LLAT
ION
> ·P
rior t
o in
stal
latio
n,re
ad th
e In
stal
latio
n M
anua
l car
eful
ly.*1
.Sin
gle-
dotte
d lin
es in
dica
te w
iring
not
sup
plie
d wi
th th
e un
it.*2
.Dot
-das
h lin
es in
dica
te th
e co
ntro
l box
bou
ndar
ies.
TH8
wat
er o
utle
t tem
pTH
6w
ater
inle
t tem
p
TH22
liqui
d pi
pe te
mp
Ther
mis
tor
TB15
MA
rem
ote
cont
rolle
rTB
5O
utdo
or u
nit/W
CB
/BC
con
trolle
rTB
2
Exp
lana
tion
Term
inal
bloc
kP
ower
sup
ply
Sym
bol
<Sym
bol e
xpla
natio
n>
- 7 -
(2) PUHY-P300YJM-A(-BS)
+-
++
+
+
2 1
++
++
+
3 3
2 2
Heat
exc
hang
er c
apac
ity c
ontro
lCo
olin
g/He
atin
g sw
itchi
ng21
S4b,
c
*7
63HS
1
SV9
SV5b
,c
For o
peni
ng/c
losin
g th
e by
pass
circu
it un
der t
he O
/S
21S4
a4-
way
valve
Expl
anat
ion
Sym
bol
63H1
63LS
Pres
sure
sens
or
Pres
sure
switc
hHi
gh p
ress
ure
prot
ectio
n fo
r the
outd
oor u
nit
Disc
harg
e pr
essu
reLo
w pr
essu
re72
CM
agne
tic re
lay(
inve
rter m
ain
circu
it)Cu
rrent
sen
sor(A
C)Cr
ankc
ase
heat
er(fo
r hea
ting
the
com
pres
sor)
CH11
CT12
,22,
3
HIC
bypa
ss,C
ontro
ls re
frige
rant
flow
in H
IC c
ircui
t
Sole
noid
valve
Line
arex
pans
ion
valve
LEV1
LEV2
SV1a
DCL
DC re
acto
r
Pres
sure
con
trol,R
efrig
eran
t flo
wra
te c
ontro
l
TB1
TB3
TB7
Term
inal
bloc
k
Cent
ral c
ontro
l tra
nsm
issio
nca
ble
Indo
or/O
utdo
or tr
ansm
issio
nca
ble
Powe
r sup
ply
TH2
TH3
TH4
TH5
TH6
TH7
THHS
Func
tion
setti
ng c
onne
ctor
IPM
tem
pera
ture
OA
tem
pera
ture
Subc
oole
d liq
uid
refri
gera
ntte
mpe
ratu
re
ACC
inle
t pip
e te
mpe
ratu
reDi
scha
rge
pipe
tem
pera
ture
Subc
ool b
ypas
s ou
tlet
tem
pera
ture
Ther
mist
or
Z24,
25
Pipe
tem
pera
ture
Out
door
uni
t hea
t exc
hang
erca
pacit
y co
ntro
lFo
r ope
ning
/clo
sing
the
bypa
sscir
cuit
21S4
c
X08
15
X07
SV5c
3CN
507
red
6
P200
/P25
0/P3
00EP
200
Appl
ianc
e*7
.Diff
eren
ce o
f app
lianc
eM
odel
nam
e*7
do
not e
xist
*7 e
xist
P350
/P40
0EP
250
3 C
N3gr
een
1
N
N
L
N
TB24
*1.S
ingl
e-do
tted
lines
indi
cate
wiri
ng n
ot s
uppl
ied
with
the
unit.
*2.D
ot-d
ash
lines
indi
cate
the
cont
rol b
ox b
ound
arie
s.*3
.Ref
er to
the
Data
boo
k fo
r con
nect
ing
inpu
t/out
put s
igna
l con
nect
ors.
*4.D
aisy
-cha
in te
rmin
als
(TB3
) on
the
outd
oor u
nits
in th
e
sam
e re
frige
rant
sys
tem
toge
ther
.*5
.Fas
ton
term
inal
s ha
ve a
lock
ing
func
tion.
M
ake
sure
the
term
inal
s ar
e se
cure
ly lo
cked
in
pla
ce a
fter i
nser
tion.
Pre
ss th
e ta
b
on th
e te
rmin
als
to re
mov
e th
em.
*6.C
ontro
l box
hou
ses
high
-vol
tage
par
ts.
Be
fore
insp
ectin
g th
e in
side
of th
e
cont
rol b
ox,tu
rn o
ff th
e po
wer,k
eep
th
e un
it of
f for
at l
east
10
min
utes
,
and
conf
irm th
at th
e vo
ltage
bet
ween
FT
-P a
nd F
T-N
on IN
V Bo
ard
has
drop
ped
to
DC2
0V o
r les
s.
L3L1
L2Po
wer S
ourc
e 3
N~ 5
0/60
Hz 3
80/4
00/4
15V
21S4
bCN
501
X01
13
X09
36
CN50
8bl
ack
Unit
addr
ess
setti
ng
CN50
4gr
een
CT12
C31
C33
CN5
red
D1R4
Z5
1
SV9
R631
white
TH2
t °
C8
red
CNIT
yello
w C
NS2
t °
1
1
LED1
Disp
lay
setti
ngCN
5112
V
Func
tion
setti
ng
SW1
101
CN21
2
CNTY
P4gr
een
F4 AC25
0V6.
3A T
R5
F3 F1Z4 R2
F2
*3
32
Com
pres
sor O
N/O
FF o
utpu
tEr
ror d
etec
tion
outp
ut
CN20
1
Z25
1 4 1
1
1
TH3
Z3
3
Z2U
ON
OFF
SW2
101SW
U2
LED1
C4
C35
C37
R31
R33
R30
ON
SW3
10
Cont
rol B
oard
TH7
CN40
63HS
1
CN41
TH6
t °tTH
4
32 2
2
1
SW5
LED3
:Lit
when
pow
ered
13
4
R32
2
Z1
1
DSA
C10
R34
R35
LEV1
LEV2
C36
3
C34
SC-V
CT22
SC-U
V1
CN4
blue
red
1M
1
1
t
LED3
:CPU
in
ope
ratio
n
blac
k
4
1CN
TYP2
blac
k
3
6
yello
w C
N3K
*3
3
M
C3
TB21
C1
R3
3
CN1A
5
U
CN2
blue
CN3N
5
6
C7
U
44
R1
CN21
blue
TB1
1
CN1B
3TB
7 Po
wer
sele
ctin
gco
nnec
tor
CN10
2
CNVD
C
3
2
1
IPM
2
1
U
4
TP1
W
L3
DCL
V
blac
k
72C
white
red
32
1
ON
OFF
1
M-N
ET p
ower
supp
ly cir
cuit
12
3
C6
M-N
ET B
oard
12
1
Powe
r fai
lure
dete
ctio
n cir
cuit
1
CNAC
2bl
ack
CN50
2
5
Indo
or/O
utdo
ortra
nsm
issio
nca
ble
INV
Boar
dre
d
3
CNT0
1
TB23
L2L1
U
4
1
ON
1
2
1's
digi
t
THHS
1
CNIT
red
S
2
1
1
CN99
0
1
3 W
TB3
10's
digi
t
OFF
LED2
:CPU
in o
pera
tion
5
2
CNS
2ye
llow
TB7
1
CNDC
pink
M1
2
2
red
6
MS 3~
1
1
t
C100
*5
3
3
U1
4
LED1
:Pow
er s
uppl
y to
I
ndoo
r/Out
door
t
rans
miss
ion
line
ZNR0
1
M2
32
M1
blac
k
Cent
ral c
ontro
ltra
nsm
issio
nca
ble
*6
SC-L
1
1
4
C2C9
ON
C5
OFF
FT-N
R5
M 3~
M
otor
(Com
pres
sor)
°
CN5
Vye
llow
5
2
3
3
3red
CN3S
11
CN04
red
1
CN2
2
3
CN4
X05
2
2
Fan
mot
or(H
eat e
xcha
nger
)
SC-P
2 P
1
CN21
1
CN20
2 re
d
TH5
°
N
CN1
M2
2
TP2
LED1
:Nor
mal
ope
ratio
n(Li
t)
/ Er
ror(B
link)
2
CN50
3bl
ue
5
X04
4
*4
SC-W
U
C32
SC-L
3
CH11
CN50
6
12
CN72
red
3
P63H1
CN80
1ye
llow
1
2
CN33
2bl
ue
F1,F
2,F3
AC25
0V6.
3A T
21
OFF
SW4
10
1
CNT0
2
11
CN3D
43
2
1
21
CPU
powe
rsu
pply
circu
it
CNAC
red
2
1
F01
AC25
0V3.
15A
T
1
t
ON
OFF
10
SWU1
white
CN21
3 re
d
SC-L
2
3
Z24
7
4
°
32
11
22
7
12
CN5
1 CN4
red
CNIN
V
3
4
R630
1
1
C630
3
CN22
red
C631
5
F01
DC70
0V4A
T
1
CNTY
P5gr
een
4
LED2
:Erro
r
21S4
a
1
LED1
:Nor
mal
o
pera
tion
2
3 2
U
X02
X03
CN18
Vbl
ue
5
1
7
CN4
3CN
6
2
°IP
M4
SC-P
1
FT-P
blac
k
C30re
d
DB1
CT3
72C
C1CN
2 CNTY
Pbl
ack
R1bl
ack
TB22
6
3
RSH1
CN10
2
3
R6C1
1
1
1
1
FAN
Boar
d
63LS
ZNR1
U3
Noise
Filte
r
SV5b
red
CNLV
A
CNLV
B re
d
12345 6
white
blac
k
SV1a
6 4 3 2 1 21
L1L2
L3
CN21
5bl
ack
<Sym
bol e
xpla
natio
n>
- 8 -
(3) PQHY-P300YHM-A
~
CNAC
4
31
CN83
CNOU
T2 43
21
65
CNPW
42
1
75
3
tTH
312
CN21
2
tTH
6
12t
THIN
VCN
TYP1
black
LEVI
NVCN
LVE
123456
LEV2
b
CNLV
C re
d
123456
CN51
0ye
llow
CN50
9blu
e3
CNOU
T1ye
llow
blue
yellow
red
orange
41
1 2 3 4 5 6
6 5 4 3 2 1
CNLV
B re
dLE
V2a
tTH
812
CN99
2ye
llow
12
4
blue
CN63
PW
MF1
SV4d
156X1
2156
SV4b
SV7b
SV7a
3
DCL
t
M1M2
SV1a
Z3
21
-+
C5
SC-L
1
SC-L
2SC
-W
1Z5
R1R2R3
C3 C2F3 F2 F1Z1
Z2
R5D1
R4 R6C1
7
Diod
eBr
idge
C7C8C9C10
C4
C1
C6
TB1
L
F4 AC25
0V6.3
A T black
white
red 31 CN
3gr
een
TB24
TB23
TB22
TB21
CN1B
41
31
CN1A
UU
U
F1,F
2,F3
AC25
0V6.3
A TUZ4
DSA
CN2
6 5 3 1
UZNR0
1
U
+
31
CN5
red
3CN
4blu
e1
C100
R1R5
black
red
2 431
72C bla
ckre
d
SC-P
1SC
-P2
4CN
1 1
CN6
21CN
412
CN2
157 1CN
TYP
black
C1 RSH1
t THHS
FT-P
FT-N
++++
++++
R34
C30
C32
C34
C36
R30
R32
C31
C33
C35
C37
R31
R33
black
white
red
R35
CT3
SC-L
3
IGBT
SC-U
SC-V
CT12
CT22
red
white
black
black
white
red U
VW
TP2
TP1
TB7
SM2
M1TB3
13
CN04
red
CN10
243
21CN
S2ye
llow
2154
32CN
ITre
d
1
63H1
P
LEV1
123456
CNLV
A
3 1CN
TYP2
black
Z24
3 2 1
Z25
CNTY
P5gr
een
CNTY
P4gr
een
4 2 1CN
213
red
CN99
02 1
TH7
TH5
t t
21 363
LS
63HS
121 3
TH2
tTH
4
3 2 1CN
202
red
CN20
123 1
CN21
5bla
ck2 1
CN21
121
red
CNIT
yello
wCN
S25
12
34
14
14
CN41
CN40
CN10
2 43
21
CN3D 1
23
blue
CN3N 1
23
yello
w C
N3K 1
2CN
ACre
d2
13
F01
AC25
0V3.1
5A T
6 3 1
SV9
X09
CN50
8bla
ck
SV4a
X08
X07
1356
CN50
7re
d
6 5 3 1
CN50
6
X13
X05
3 121
S4a
CN50
4gr
een
X04
X03
CH11
3 1CN
503
blue
2 1CN
502
X02
12
CNAC
2bla
ck
65 72C
12CN
72re
d
31
CNDC
pink
12CN
T01
13
1221
CN80
1ye
llow
CNT0
2CN
4
CN2
7 5 1
SW1ON
OFF 1 10
SW2ON
OFF 1 10
SW3ON
OFF 1 10
SW4ON
OFF 1 10
ONOF
F 1 10SW
5
543
12V
1CN
51SWU2
SWU1
10's
digit
1's digit
*1.
Sin
gle-
dotte
d lin
es in
dica
te w
iring
no
t sup
plie
d w
ith th
e un
it.*2
. D
ot-d
ash
lines
indi
cate
the
cont
rol
bo
x bo
unda
ries.
*3.
Ref
er to
the
Dat
a bo
ok fo
r con
nect
ing
in
put/o
utpu
t sig
nal c
onne
ctor
s.*4
. D
aisy
-cha
in te
rmin
als
(TB
3) o
n th
e
heat
sou
rce
units
in th
e sa
me
re
frige
rant
sys
tem
toge
ther
.*5
. Fa
ston
term
inal
s ha
ve a
lock
ing
fu
nctio
n. M
ake
sure
the
term
inal
s
are
secu
rely
lock
ed in
pla
ce a
fter
in
serti
on. P
ress
the
tab
on th
e
term
inal
s to
rem
oved
them
.*6
. C
ontro
l box
hou
ses
high
-vol
tage
par
ts.
B
efor
e in
spec
ting
the
insi
de o
f the
co
ntro
l box
, tur
n of
f the
pow
er, k
eep
th
e un
it of
f for
at l
east
10
min
utes
,
and
conf
irm th
at th
e vo
ltage
bet
wee
n
FT-P
and
FT-
N o
n IN
V B
oard
has
dro
pped
to
20V
DC
or l
ess.
*7.
Ref
er to
the
Dat
a bo
ok fo
r wiri
ng
te
rmin
al b
lock
for P
ump
Inte
rlock
(TB
8).
<Sym
bol e
xpla
natio
n>
Sub
cool
ed li
quid
refri
gera
ntte
mpe
ratu
reTH
6
Pip
e te
mpe
ratu
reTH
3S
ubco
ol b
ypas
s ou
tlet t
empe
ratu
reTH
2
Pre
ssur
e co
ntro
l, R
efrig
eran
t flo
wra
te c
ontro
lLE
V2a
, b
Out
let t
emp.
det
ect o
f hea
t ex
chan
ger f
or in
verte
rTH
INV
Wat
er o
utle
t tem
pera
ture
TH8
Hea
t exc
hang
er c
apac
ity c
ontro
lS
V7a
, bH
eat e
xcha
nger
cap
acity
con
trol
SV
4a, b
, d
Hea
t exc
hang
er fo
r inv
erte
rLE
VIN
V
For o
peni
ng/c
losi
ng th
e by
pass
circ
uit u
nder
the
O/S
HIC
byp
ass,
Con
trols
refri
gera
ntflo
w in
HIC
circ
uit
Fan
mot
or (R
adia
tor p
anel
)M
F1S
V1a
For o
peni
ng/c
losi
ng th
e by
pass
circ
uit
Z24,
25
Ther
mis
tor
Ope
ratio
n O
N s
igna
l, P
ump
Inte
rlock
Dis
char
ge p
ipe
tem
pera
ture
AC
C in
let p
ipe
tem
pera
ture
Wat
er in
let t
empe
ratu
re
IGB
T te
mpe
ratu
reFu
nctio
n se
tting
con
nect
orTH
HS
TH7
TH5
TH4
TB8
Pow
er s
uppl
yE
xpla
natio
n
Indo
or/H
eat s
ourc
e tra
nsm
issi
onca
ble
Cen
tral c
ontro
l tra
nsm
issi
onca
ble
Term
inal
bloc
k
TB7
TB3
TB1S
ymbo
l
DC
reac
tor
DC
LLE
V1
Line
arex
pans
ion
valv
e
Sol
enoi
dva
lve
CT1
2, 2
2, 3
CH
11C
rank
case
hea
ter (
for h
eatin
g th
e co
mpr
esso
r)C
urre
nt s
enso
r (A
C)
Mag
netic
rela
y (in
verte
r mai
n ci
rcui
t)72
CLo
w p
ress
ure
Hig
h pr
essu
re
Hig
h pr
essu
re p
rote
ctio
n fo
r the
heat
sou
rce
unit
Pre
ssur
esw
itch
Pre
ssur
ese
nsor
63LS
63H
1Sym
bol
Exp
lana
tion
4-w
ay v
alve
21S
4a
SV
9
63H
S1
RELA
Y Bo
ard
Noise
Filte
r
INV
Boar
d
M-N
ET B
oard
Cont
rol B
oard
Powe
r Sou
rce
3N~
50/6
0Hz
380/
400/
415V
NL3
L2L1
NL3
L2L1
P N
Pum
p In
terlo
ckO
pera
tion
ON
sig
nal
M
otor
(Com
pres
sor)
MS 3~
1TB
82
34
*7
*5
*6
*4OFF
ON
*3
LED1
*3
Unit a
ddre
ssse
tting
LED1
Disp
layse
tting
Func
tion
settin
g
Com
pres
sor O
N/OF
F ou
tput
Erro
r det
ectio
n ou
tput
TB7
Powe
rse
lectin
g
LED3
:Lit w
hen
powe
red
LED2
:CPU
in o
pera
tion
LED
1 : N
orm
al o
pera
tion
(lit)
/
Err
or (b
link)
CP
U p
ower
supp
ly c
ircui
t
Pow
er fa
ilure
dete
ctio
n ci
rcui
t
M-N
ET
pow
ersu
pply
circ
uit
Cen
tral c
ontro
ltra
nsm
issi
onca
ble
Indo
or/
Hea
t sou
rce
trans
mis
sion
cabl
e
LED
1:P
ower
sup
ply
to In
door
/Hea
t sou
rce
trans
mis
sion
line
MMMM
°°° ° °° ° °
conn
ecto
rM
°
NL3
L2L1
- 9 -
4. Accessories(1) PWFY
(A) Strainer (B) Heat insulation material (C) Connecter sets 2 (D) Expansion joint 2 (E) Wire (F)
(A) Install the strainer at the water pipe inlet.(B) This insulation is for exclusive use with the strainer. Wrap the strainer with the insulation after water pipes are
installed.(C) These are analog input connectors. Cut the wire before using.(D) Install them at the strainer inlet. Refer to P26 for details.(E) To perform test run before the pump interlock circuit is completed, short circuit the terminal block TB142A (IN1),
and then perform test run.(F) When installing the unit, be sure to install the supplied flow switch on the water outlet side of the unit and connect the
wire to IN1 of TB142A on the unit.
- 10 -
1. Capacity tables(1) Correction by temperature (Estimated performance without defrost)PUHY-P300YJM-A(-BS) + PWFY-P200VM-E1-AU (for high temperature flow)
Product Data III
PUHY-P300YJM-A + PWFY-P200VM-E1-AU (for high temperature flow)
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0
Outdoor temp. [°CWB]
Rat
io o
f hea
ting
capa
city
HEX
uni
t out
let-w
ater
tem
p.[°
C]
Rat
io o
f out
door
uni
t inp
ut
46°C
48°C
50°C
54°C
52°C
40°C
42°C
44°C
54°C52°C50°C48°C46°C44°C42°C40°C
40°C
42°C
46°C
50°C
44°C
48°C
52°C
54°C
HEX unit inlet-water temp. [°C]
HEX unit inlet-water temp. [°C]
HEX unit inlet-water temp. [°C]
-5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
585756555453525150494847464544
-5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1.4
1.2
1.0
0.8
0.6
0.4
0.2 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Outdoor temp. [°CWB]
Outdoor temp. [°CWB]
*Ratio of heating capacity ··· PWFY-P200VM-E1-AU heating capacity (25kW) base.
- 11 -
(2) Correction by water flow ratePWFY-P200VM-E1-AU
Heating Cooling
1.5 2.0 2.5 3.0 3.5 4.0 4.5
1.5 2.0 2.5 3.0 3.5 4.0 4.5
1.5 2.0 2.5 3.0 3.5 4.0 4.5
1.5 2.0 2.5 3.0 3.5 4.0 4.5
HEX unit water-volume [m3/h] HEX unit water-volume [m3/h]
HEX unit water-volume [m3/h] HEX unit water-volume [m3/h]
Ratio
of H
EX u
nit h
eatin
g ca
pacit
y
Ratio
of H
EX u
nit c
oolin
g ca
pacit
y
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Rat
io o
f out
door
uni
t in
put
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
Rat
io o
f out
door
uni
t in
put
- 12 -
(3) Correction at frosting and defrostingDue to frost at the outdoor heat exchanger and the automatic defrost operation, the heating capacity of the outdoor unit can be calculated by multiplying the correction factor shown in the table below.
Table of correction factor at frost and defrostOutdoor inlet air temp. °C 6 4 2 1 0 -2 -4 -6 -8 -10 -20Outdoor inlet air temp. °F 43 39 36 34 32 28 25 21 18 14 -4PUHY-P300YJM-A (-BS) 1.00 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95
(4) Water pressure drop
(4)-1 PWFY-P200VM-E1-AU (with strainer)
HEX unit inlet-water volume [m3/h]
HEX
unit
wate
r-pre
ssur
e dro
p [k
Pa]
0
10203040
50607080
90100
PWFY-P200VM-E1-AU (with strainer)
1.5 2 2.5 3 3.5 4 4.5
Water pressure drop of strainer
(4)-2 Water pressure drop of Strainer only (accessory for PWFY-P200VM-E1-AU)
0
10
20
30
40
ATW unit inlet-water volume [m3/h]
Wat
er-p
ress
ure
drop
[kPa
]
0.5 1 1.5 2 2.5 3 3.5 4 4.5
- 13 -
(5) Operation temperature rangePWFY-P200VM-E1-AU
Heating
0
10
20
30
40
50
Outdoor temp. [°CWB]
HEX
unit
inlet
wat
er te
mp.
[°C]
PUHY-P300YJM-A(-BS)
-5-10-15-20 0 5 10 15 20 25 30 35 40 45 50
Heating
0
10
20
30
40
50
Heat source unit circulating water temp. [°C]
HEX
unit
inlet
wat
er te
mp.
[°C]
PQHY-P300YHM-A
-5-10-15-20 0 5 10 15 20 25 30 35 40 45 50
- 14 -
Cooling
0
10
20
30
40
50
Outdoor temp. [°CDB]
HEX
unit
inlet
wat
er te
mp.
[°C]
PUHY-P300YJM-A(-BS)
-5-10-15-20 0 5 10 15 20 25 30 35 40 45 50
Cooling
0
10
20
30
40
50
Heat source unit circulating water temp. [°C]
HEX
unit
inlet
wat
er te
mp.
[°C]
PQHY-P300YHM-A
-5-10-15-20 0 5 10 15 20 25 30 35 40 45 50
- 15 -
2. Sound pressure levels(1) PWFY-P200VM-E1-AU
50/60HzWhen Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63 125 250 500 1k 2k 4k 8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Oct
ave
band
sou
nd le
vel (
dB)
Sound level of PWFY-P200VM-E1-AU
Approximate minimumaudible limit oncontinuous noise
dB(A)29.0
8k12.0
4k15.0
2k14.5
1k22.5
500k25.0
25033.0
12532.0
6342.0
Measurement conditionPWFY-P200VM-E1-AU
Measurementlocation
1m
1m
3. Refrigerant circuit diagrams and thermal sensors(1) PWFY-P200VM-E1-AU
Hex
TH6
TH23
LEV1Wa
TH8
TH22
LEV1Wb
SV1
ST2
ST4
CV1
Water inlet
Water outlet
screw
screw
Brazed
Brazed
- 16 -
++
A. For Air conditioning using such as Panel Heaters, Floor Heating and Fan coil unitsRequired total heating capacity kWSafety factor; %
B. For Sanitary use such as Shower and BathroomsConditions
Tank inlet water Temp.; °CTank outlet water Temp.; °C(Set Temp -5 °C)Safety factor for Heat Loss; %Operating time; HoursFor Shower; /person x Person = (Water Temp. Condition °C)
°C)For Bathrooms; /Person x Person = (Water Temp. ConditionThe conversion of water volume to °C
x ( - ) / ( - )+ x ( - ) / ( - )= ℓ /dayHeating Capacity Calculation for sanitary usage
/ 1,000 x ( - ) = M cal / dayThe conversion of M cal to kW
/ 860 x 1,000 / = kWC. Total (A+B)
Total Heating Capacityx (100%
+x (100%
%) + x (100% %) = kWD. No. of units required
Safety factor; %%) / 12.5 kW = units
units are required
TankPWFY unit 4
3 3
33
7
1. How to calculate the necessary heating capacity(1) Heating capacity calculation
(2) Calculation example
++
A. For Air conditioning using such as Panel Heaters, Floor Heating and Fan coil unitsRequired total heating capacity 20
10
1060
60
158
2030
1,200240
4045
1,200240
4045
1010
6060
1010
888
888
44.4
20
29.42 20
3
2.82
10
20
6.45 15 29.42
8 6.45
60 10 44.4
kWSafety factor; %
B. For Sanitary use such as Shower and BathroomsConditions
Tank inlet water Temp.; °CTank outlet water Temp.; °C(Set Temp -5 °C)Safety factor for Heat Loss; %Operating time; HoursFor Shower; 60 /person x Person = (Water Temp. Condition °C)
°C)For Bathrooms; 8 /Person x Person = (Water Temp. ConditionThe conversion of water volume to °C
x ( - ) / ( - )+ x ( - ) / ( - )= ℓ /dayHeating Capacity Calculation for sanitary usage
/1,000 x ( - ) = M cal / dayThe conversion of M cal to kW
/ 860 x 1,000 / = kWC. Total (A+B)
Total Heating Capacityx (100%
+x (100%
%) + x (100% %) = kWD. No. of units required
Safety factor; %%) / 12.5 kW = units
units are required
TankPWFY unit 4
3 3
33
7
Installation IV
- 17 -
2. Installation(1) Selecting an installation site (for PWFY unit)• Do not install outdoors. The unit is not waterproof.• Back up system is recommended in case of PWFY unit breakdown.• The unit will get hot. Do not install in a location where heat gets trapped inside. • Be sure to install unit in a place strong enough to withstand its weight. Any lack of strength may cause unit to fall down, resulting in a personal injury.• Do not install the unit where corrosive gas is generated.• Have installation work in order to protect against earthquake. Any installation de� ciency may cause unit to fall down, resulting in a personal injury.• Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigera-
tion is heavier than the air.• Do not install the unit where combustible gas may leak.- If the gas leaks and accumulates around the unit, an explosion may result.• When installing the unit in a hospital, communication station, or similar place, provide suf� cient protection
against noise.- The inverter equipment, private power generator, high-frequency medical equipment, or radio communication
equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.- When the room humidity exceeds 80 % or when the drain pipe is clogged, condensation may drip from the indoor
unit. Perform collective drainage work together with the unit, as required.• It is recommended that a water pump is connected to each PWFY unit.
(1)-1 Securing installation and service space• Please secure the following service spaces after installation. (All servicing can be performed from the front of the unit) [Fig. IV. 2. (1). 1]
Warning:• Be sure to install the unit in a location which can adequately support its weight.- If there is insuf� cient strength to support the unit’s weight, it could fall and cause injuries.
(A) Piping space (right side)(B) Top view(C) Service space (front side)
(A) Piping space (right side)(B) Top view(C) Service space (front side)
(B)
400mm
300mm
600mm(C)
(A)
- 18 -
(2) Installing the unit(2)-1 Lifting method
(2)-2 Product net weight
Model
Net weightPWFY-P200VM-E1-AU
38 kg
PUHY-P300YJM-A(-BS)
215 kg
(2)-3 Center of gravity
(2)-3-1 PWFY-P200VM-E1-AU
X277
ModelPWFY-P200VM-E1-AU
Z99
Y347
20513
X
Y
800
500
525
300450
Z
47
Unit : mm
· Products weighing more than 20 kg [45 LBS] should not be carried alone.· Do not carry the product by the PP bands.· To avoid the risk of injury, do not touch the heat exchanger fins. · Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.· When lifting and transporting outdoor units (heat source unit) with ropes, run the ropes through lifting hole at the unit base. Securely fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.
Exercise caution when transporting products.CAUTION
- 19 -
(2)-3-2 PUHY-P300YJM-A(-BS)
760 80
Y
724
1470
Z
60
920
X
760
Model
Unit:mm
X Y Z320 319 632PUHY-P300YJM-A (-BS)
(2)-3-3 PQHY-P300YHM-A
Model X Y Z418[16-8/16] 250[9-14/16] 532[21]PQHY-P300YHM-A
Unit : mm[in.]
1100
[43-
5/16
]60
[2-6
/16]
550[21-11/16]880[34-11/16]
506[19-15/16]
YX
Z
1160
[45-
11/1
6]
80[3-3/16]
720[28-6/16]
- 20 -
(2)-4 Installation method
• Using the anchoring holes shown below, � rmly bolt the unit to the base. [Fig. IV. 2. (2). 1]
Bases• Be sure to install unit in a place strong enough to withstand its weight. If the base is unstable, reinforce with a con-
crete base.• The unit must be anchored on a level surface. Use a level to check after installation.• If the unit is installed near a room where noise is a problem, using an anti-vibration stand on the base of the unit is
recommended.
(A) 4-ø14 (Anchoring hole)(B) (Top view)
(A)
(B)
205
300
450
500
525
Unit : mm
- 21 -
(3) Refrigerant pipe and drain pipe specifications
(3)-1 Refrigerant pipe and drain pipe speci� cations
(3)-2 Refrigerant pipe, drain pipe and � lling port
ModelGas
LiquidDrain
Insulating material's thickness
PWFY-P200VM-E1-AUø19.05ø9.52ø32
More than 10 mm
To avoid dew drops, provide suf� cient antisweating and insulating work to the refrigerant and drain pipes.When using commercially available refrigerant pipes, be sure to wind commercially available insulating material (with a heat-resisting temperature of more than 100 °C and thickness given below) onto both liquid and gas pipes.Be also sure to wind commercially available insulating material (with a form polyethylene’s speci� c gravity of 0.03 and thickness given below) onto all pipes which pass through rooms.1) Select the thickness of insulating material by pipe size.
2) If the unit is used on the highest story of a building and under conditions of high temperature and humidity, it is necessary to use pipe size and insulating material’s thickness more than those given in the table above.
3) If there are customer’s speci� cations, simply follow them.
(A) Refrigerant piping (gas)(B) Refrigerant piping (liquid)(C) Water inlet(D) Water outlet(E) Drain outlet
(D)
(A)
(B)
(C)
(E)
480
100
191
54102
114
134
206
Unit : mm
Unit : mm
- 22 -
(4) Connecting refrigerant pipes and drain pipes
(4)-1 Refrigerant piping workThis piping work must be done in accordance with the installation manuals for outdoor unit (heat source unit).• For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit installation manual.• The method of pipe connection is brazing connection.
Caution:• Install the refrigerant piping for the indoor unit in accordance with the following.1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed cap. [Fig. IV. 2. (4). 1]
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping, and replace the insulation in its original position.
Wrap the piping with insulating tape.Note:• Pay strict attention when wrapping the copper piping since wrapping the piping may cause condensation
instead of preventing it.* Before brazing the refrigerant piping, always wrap the piping on the main body, and the thermal insulation
piping, with damp cloths to prevent heat shrinkage and burning the thermal insulation tubing. Take care to ensure that the � ame does not come into contact with the main body itself.
[Fig. IV. 2. (4). 2]
(A)
(A)
(E)
(C)
(F)
(B)
(D)
(A) Thermal insulation(B) Pull out insulation(C) Wrap with damp cloth(D) Return to original position(E) Ensure that there is no gap here(F) Wrap with insulating tape
(A) Cut here(B) Remove brazed cap
- 23 -
Cautions On Refrigerant Piping
• Be sure to use non-oxidative brazing for brazing to ensure that no foreign matter or moisture enter into the pipe.
• e sure to apply refrigerating machine oil over the � are connection seating surface and tighten the connection using a double spanner.
• Provide a metal brace to support the refrigerant pipe so that no load is imparted to the indoor unit end pipe. This metal brace should be provided 500 mm away from the indoor unit’s � are connection.
Warning:When installing and moving the unit, do not charge it with refrigerant other than the refrigerant (R407C or R22) speci� ed on the unit.- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to malfunction and result in severe damage.
Caution:• Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized copper as speci� ed in the JIS H3300
“Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
• Never use existing refrigerant piping.- The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new
refrigerant to deteriorate.• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just
before brazing.- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and the compressor may fail.
(4)-2 Drain piping work
1. Ensure that the drain piping is downward (pitch of more than 1/100) to the outdoor (discharge) side. Do not provide any trap or irregularity on the way. (a)
2. Ensure that any cross-wise drain piping is less than 20 m (excluding the difference of elevation). If the drain piping is long, provide metal braces to prevent it from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
3. Use a hard vinyl chloride pipe VP-25 (with an external diameter of 32 mm) for drain piping.4. Ensure that collected pipes are 100 mm lower than the unit body’s drain port as shown in (b). 5. Do not provide any odor trap at the drain discharge port.6. Put the end of the drain piping in a position where no odor is generated.7. Do not put the end of the drain piping in any drain where ionic gases are generated. [Fig. IV. 2. (4).3]
(A) Downward slope 1/100 or more(B) Drain hose(C) Unit (D) Collective piping(E) Maximize this length to approx. 100 mm(A)
(B) (a)
(C) (C) (C)
(D) (b)
(E)
- 24 -
3. Water pipe installation(1) Water circuit sample
Water-side heat exchanger
Solid arrows in the figure indicate the direction of water flow.
PWFY Field supply
Tank Outlet
Inlet
City waterOverflowed water
Roof
To drain outlet
Uphill gradient ≥ 1/200
P
P
T
T
P
1)
1)
1)
1)
2)13)
2)
3)
3) 3)
4)
4) 4)4)
5)
5) 5)
6)
7)
8) 8)
9)
11) 11)12)
Sample of water circuit for PWFY
Consider the following when designing and installing a water piping system. (Items (1)-(12) in the � gure are explained below.) 1) Union joints/� ange joints etc. Install a � ange etc. to allow for easy replacement of connected equipment.2) Thermometer For checking unit performance and operation monitoring3) Water pressure gauge For operation status monitoring4) Valve Install a valve for easy replacement and cleaning of the refrigerant � ow control device. Install a refrigerant � ow control valve on the fan coil outlet side.5) Flexible joint Recommended to prevent the noise and vibration from the pump from being transmitted. 6) Drain pipe Install the drain pipe with an inclination of between 1/100 and 1/200 to provide a downward � ow of drain water. For cold climate installation, take an appropriate measure (e.g., drain heater) to prevent the drain water from
freezing.7) Pump Use a pump that is large enough to compensate for the total water pressure loss and to supply suf� cient water to the
unit.8) Air vent valve Provide air vent valves on the pipes.9) Expansion tank Install an expansion tank to accommodate expanded water and to supply water.10) Cold/Hot water pipe Use pipes that allow for easy air purging, and provide suf� cient insulation.11) Drain valve Install drain valves so that water can be drained for servicing.12) Strainer Install a strainer near the PWFY unit to keep foreign materials from entering the water-side heat exchanger. 13) Flow switch Install the supplied � ow switch on the outlet pipe.
- 25 -
(1)-1 Caution for water pipe installationConsider the following when designing and installing a water piping system.• Do not use steel pipes as water pipes.- Copper pipes or stainless steel pipes are recommended.If iron pipes are used in the existing system, do not connect
a new circuit to the old one. Keep the existing and new circuits separate. • Light pipes are similar to other air-conditioning pipes, however, please observe the following precautions during installation.• Before a long period of non use, purge the water out of the pipes and thoroughly let them dry. • Use a closed water circuit. • When operating the unit, add brine to the circulating water to prevent it from freezing. To use brine in the system,
DipSW 1-10 must be set to ON.• When installed in a low-ambient temperature environment, keep the water circulating at all times. If that is not
possible, purge the water out of the pipes completely. • Do not use the water used for this unit for drinking or food manufacturing.• When the ambient temperature is 0 �C or lower during stop operation, keep the water circulating at all times, or
purge the water out of the pipes completely.
Model Water inlet Water outletPWFY-P200VM-E1-AU*1 When the attached expansion
joints are installed.PT 1 Screw*1 PT 1 Screw*1
(2) Selecting a water pumpUse a pump that is large enough to compensate for the total water pressure loss and to supply sufficient water to the unit.
(3) Installing the strainer• Install the strainer at the angle of 45� or less as shown in [Fig. IV 3.(3).1].• Install the supplied strainer at the water inlet.
(4) Precautions during installation• Use the reverse-return method to insure proper pipe resistance to each unit.• To insure easy maintenance, inspection, and replacement of the unit, use a proper joint, valve, etc. on the water
intake and outlet port. In addition, be sure to install a strainer on the water intake pipe. (In order to maintain the heat source unit, a strainer on the circulating water inlet is necessary.)
* An example of the heat source unit installation is shown in [Fig. IV 3.(5).1].• Install a suitable air vent on the water pipe. After sending water through the pipe, be sure to vent the excess air.• Compressed water may form in the low-temperature sections of heat source unit. Use a drainage pipe connected to
the drain valve at the base of the unit to drain the water.• Install a back � ow-prevention valve on the pump and a � exible joint to prevent excess vibration.• Use a sleeve to protect the pipes where they go through a wall.• Use metal � ttings to secure the pipes, and install them so that they have maximum protection against breakage and
bending.• Do not confuse the water intake and outlet valves.• This unit doesn’t have any heater to prevent freezing within tubes. When the water � ow is stopped on low ambient,
take out the water from tubes.• The unused knockout holes should be closed and the opening of refrigerant pipes, water pipes, power source and
transmission wires should be � lled with putty and so on to prevent from rain. (� eld construction)• Wrap some sealing tape around the screw part to prevent water leakage. • Wrap the sealing tape as follows. 1. Wrap the joint with sealing tape in the direction of the threads (clockwise), and do not let the tape run over the edge. 2. Overlap the sealing tape by two-thirds to three-fourths of its width on each turn. Press the tape with your � ngers so that it is pressed � rmly against each thread. 3. Leave the 1.5th through 2nd farthest threads away from the pipe and unwrapped.• Hold the pipe on the unit side in place with a spanner when installing the pipes or strainer. Tighten screws to a torque
of 50 N.m. • Water pipes can get very hot, depending on the preset temperature. Wrap the water pipes with insulating materials
to prevent burns. • Install the expansion joint (accessory) at the inlet after installing the strainer, and outlet.
(A) Y-type strainer(A)
45°
[Fig. IV 3.(3).1]
- 26 -
(5) Example of unit installation[Fig. IV. 3.(5).1]
(A)
(A)(D)
(C)
(B)(E)(F)
(E)(B)
(C) (G)
(G)
PWFY- P200VM-E1-AU(A) Close valve(B) Water inlet(C) Water outlet(D) Refrigerant piping
(E) Y-type strainer(F) Drain pipe(G) Expansion joint
(6) Insulation installationThe surface temperature of the water pipe would be very high, depending on the set temperature. Insulate the pipe to prevent burns. When operating PWFY-P200VM-E1-AU with cold water, insulate the water pipe to prevent condensation. Wrap insulation material around water pipes as shown in [Fig. IV. 3.(6).1].• Any heat source piping.• Indoor piping in cold-weather regions where frozen pipes are a problem.• When air coming from the outside causes condensation to form on piping.• Any drainage piping. [Fig. IV. 3.(6).1]
(A) Heat insulation material (accessory)(B) Inject with caulking material
(A)
(B)
(7) Flow switch installation<Caution>When installing the unit, be sure to install the supplied flow switch on the water outlet side of the unit and connect the wire to IN1 of TB142A on the unit.If the flow switch is not installed, the unit will emit the error signal (2100: Interlock error) and not operate.* A short-circuit wire is supplied, but it is only for test run.
- 27 -
<Installation procedures>1) Remove the pipes attached to the flow switch.
Note: The unit is shipped with the pipes loosely tightened. 2) Wrap seal tape around the threads at the end of the pipes, starting at the 1.5th or 2nd thread, and not over the
openings. Apply two to three wraps in the direction of the pipe threads (clockwise). Each course of the tape should overlap the one before it by 2/3 to 3/4 the width of the tape. Run your fingers around the threads and tape to press the tape into the threads.Then, attach the pipes to the flow switch, holding parts A and B with a spanner. The maximum tightening torque is 60 N•m (611 kgf•cm).
3) Attach the flow switch and pipes to the water outlet in the horizontal position.The angle of the axis of the pipe should be less than 45 degrees.Check the direction of the flow switch as shown in Fig. C.
4) Connect the flow switch wire to IN1 of TB142A.From the External Wiring Input, route the wire as shown in Fig. D and connect it to the terminal as shown in Fig. E. Use a wire protector such as a rubber bushing in the access hole on the unit.
AA BB
Water OutletWater Outlet
OKOK OKOK
OKOK
45°45°45°
Not AcceptableNot AcceptableNot Acceptable
Not AcceptableNot AcceptableNot Acceptable
1) 2)
3)
Check the direction.Check the direction.
4)
Fig. C
Secure thewiring in place.Secure thewiring in place.Secure thewiring in place.
Enlarged viewEnlarged viewEnlarged view
Fig. D Fig. E
Flow SwitchFlow Switch
WireWire
Rubber bushingRubber bushing
- 28 -
(8) Water processing and water quality controlTo preserve water quality, use the closed type of cooling tower for unit. When the circulating water quality is poor, the water heat exchanger can develop scales, leading to a reduction in heat-exchange power and possible corrosion of the heat exchanger. Please pay careful attention to water processing and water quality control when installing the water circulation system.• Removal of foreign objects or impurities within the pipes. During installation, be careful that foreign objects, such as welding fragments, sealant particles, or rust, do not enter
the pipes.• Water Quality Processing
a) Depending on the quality of the cold-temperature water used in the air-conditioner, the copper piping of the heat exchanger may become corroded. We recommend regular water quality processing.Cold water circulation systems using open heat storage tanks are particularly prone to corrosion.When using an open-type heat storage tank, install a water-to-water heat exchanger, and use a closed-loop circuit on the air conditioner side. If a water supply tank is installed, keep contact with air to a minimum, and keep the level of dissolved oxygen in the water no higher than 1mg/liter.
b) Water quality standard
Reference : Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994)c) Please consult with a water quality control specialist about water quality control methods and water quality
calculations before using anti-corrosive solutions for water quality management.
d) When replacing a previously installed air conditioning device (even when only the heat exchanger is being replaced), � rst conduct a water quality analysis and check for possible corrosion.
Corrosion can occur in cold-water systems even if there has been no prior signs of corrosion.
If the water quality level has dropped, please adjust water quality suf� ciently before replacing the unit.Refer to the below graph for the maximum amount of circulating water in the water pipe. Make sure that this amount does not exceed.
[Fig. IV. 3. (8).1] Maximum circulating water
pH (25 �C)Electric conductivity (mS/m) (25 �C) (� s/cm) (25 �C)Chloride ion (mg Cl-/liter)Sulfate ion (mg SO42-/liter)Acid consumption (pH4.8) (mg CaCO3/liter)Total hardness (mg CaCO3/liter)Calcium hardness (mg CaCO3/liter)Ionic silica (mg SiO2/liter)Iron (mg Fe/liter)Copper (mg Cu/liter)
Sul� de ion (mg S2-/liter)
Ammonium ion (mg NH4+/liter)
Residual chlorine (mg Cl/liter)Free carbon dioxide (mg CO2/liter)Ryzner stability index
Standard items
Refer-ence items
ItemsLower mid-range temperature water system
Water Temp. =< 60 �C
7.0 ~ 8.030 or less
[300 or less]50 or less50 or less
50 or less
70 or less50 or less30 or less1.0 or less1.0 or lessnot to be detected
0.3 or less0.25 or less0.4 or less
–
7.0 ~ 8.030 or less
[300 or less]50 or less50 or less
50 or less
70 or less50 or less30 or less0.3 or less1.0 or lessnot to be detected
0.1 or less0.3 or less4.0 or less
–
Tendency
Recirculating water Make-up water Corrosive Scale-forming
Higher mid-range temperature water systemWater Temp. > 60 �C
Recirculating water Make-up water7.0 ~ 8.030 or less
[300 or less]30 or less30 or less
50 or less
70 or less50 or less30 or less1.0 or less1.0 or lessnot to be detected
0.1 or less0.1 or less0.4 or less
–
7.0 ~ 8.030 or less
[300 or less]30 or less30 or less
50 or less
70 or less50 or less30 or less0.3 or less1.0 or lessnot to be detected
0.1 or less0.3 or less4.0 or less
–
0
500
1000
1500
2000
2500
3000
0 10 20 30 40 50 60 70Total hardness [mg/L]
Wat
er v
olum
e lim
itatio
n [L
]
Condition: Water outlet temp. 45°C
PWFY-P200VM-E1-AU
Available water volume area
- 29 -
(9) Pump interlockThe unit may become damaged if it is operated with no water circulating through the pipes.Be sure to interlock unit operation and the water-circuit pump. [Fig. IV. 3. (9).1]
IN1
TB142A
Water Pump
Strainer
Control Box
Broken lines are fieldsupply products.
Operation signalPump interlock
Example drawing for pump interlock
In the system including PWFY-P200VM-E1-AU, the circulating water may freeze, and result in a unit malfunction. Perform the electrical work as shown in [Fig. IV. 3. (9).2] to prevent water from freezing.Set the DipSW as shown in the table below.
DipSW3-6 External output contactON Effective when Thermo-ONOFF Effective when Operation-ON
(Remote controller-ON)
Be sure to turn on the power supply of the pump, since the control does not work if the power supply of the pump is turnd off. *Refer to (7) Flow switch installation for details.
F: Fuze52P: Magnetic contactor for heat source water pumpMCB: Circuit breakerMP: Water pump
(10) Anti freeze mode (Dip SW4-4 ON)Anti freeze mode is to prevent water pipe from freezing.The Anti freeze mode can set the heating temperature range between 10ºC~45ºC enabling the unit to maintain low water temperature to prevent water pipes from freezing.
[Fig. IV. 3. (9).2]
52P
Board
F
NL
52P52P
MCB
MP
TB141A OUT1AC220V ~ 240V
DC30V or lessor
[Fig. IV. 3. (9).2]
52P
Board
F
NL
52P52P
MCB
MP
TB141A OUT1AC220V ~ 240V
DC30V or lessor
- 30 -
1. Electrical work(1) General cautions
Warning:Electrical work should be done by quali� ed electrical engineers in accordance with “Engineering Standards For Electrical Installation” and supplied installation manuals. Special circuits should also be used. If the power circuit lacks capacity or has an installation failure, it may cause a risk of electric shock or � re.
1. Be sure to take power from the special branch circuit.2. Be sure to install an earth leakage breaker to the power.3. Install the unit to prevent that any of the control circuit cables (remote controller, transmission cables, or external
input/output line) is brought in direct contact with the power cable outside the unit.4. Ensure that there is no slack on all wire connections.5. Some cables (power, remote controller, transmission cables external input/output line) above the ceiling may be
bitten by mouses. Use as many metal pipes as possible to insert the cables into them for protection.6. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken.7. Be sure to connect control cables to the indoor unit, remote controller, and the outdoor unit.8. Be sure to ground the unit.9. Select control cables from the conditions given in page 32.
Caution:Be sure to put the unit to the ground on the outdoor unit side. Do not connect the earth cable to any gas pipe, water pipe, lightening rod, or telephone earth cable. Incomplete grounding may cause a risk of electric shock.
(2) Power supply for PWFY unit(2)-1 Electrical characteristics of PWFY unit• Power supply cords of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.• A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
(2)-2 Power cable specifications
PWFY-P200VM-E1-AU
Hz
50/60
Volts
220-230-240 V
Voltage rangeMax. 264 VMin. 198 V
MCA (A)
0.085
Cooling HeatingModel
0.068-0.065-0.063
RLA (A)Power supply
branch1.52.54.0
ModelMinimum wire thickness (mm2) Local swich (A)Breaker for current
leakage capacityBreaker for wiring (NFB) (A)
Main cable1.52.54.0
Ground1.52.54.0
fuse
PWFY-P200VM-E1-AUTotal operating current
16 A or less25 A or less32 A or less
20 A 30 mA 0.1 sec. or less30 A 30 mA 0.1 sec. or less40 A 30 mA 0.1 sec. or less
203040
16
25
32
162532
[Fig. V. 1.(2).1]
(A) (B)
(D) (D)
PEPE(C) PE(C) (C)
PWFY-P200VM-E1-AU(A) Breaker for current leakage(B) Local switch or breakers for wiring(C) PWFY-P200VM-E1-AU(D) Pull box
Caution:Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of malfunction or � re.
System Design V
- 31 -
(3) Connecting remote controller, indoor and outdoor transmission cables• Connect unit TB5 and outdoor unit TB3. (Non-polarized 2-wire (shield)) The “S” on unit TB5 is a shielding wire connection. For speci� cations about the connecting cables, refer to the
outdoor unit installation manual.• Install a remote controller following the manual supplied with the remote controller.
(3)-1 Power supply examples(3)-1-1 Using MA Remote controller (Remote controller is optionally available)• Connect the “1” and “2” on unit TB15 to a MA remote controller. (Non-polarized 2-wire) [Fig. V. 1. (3). 1] MA Remote controller
TB3
M1M2
(A) (B)
(C)TB15TB5
SM1M2 1 2
(A) Outdoor unit(B) PWFY-P200VM-E1-AU(C) MA remote controller
• DC 10 to 13 V between 1 and 2 (MA remote controller) [Fig. V. 1. (3). 2] MA Remote controller
• The MA remote controller cannot be used at the same time or interchangeably.
Note:Ensure that the wiring is not pinched when � tting the terminal box cover. Pinching the wiring may cut it.
Caution:• Use wire with supplemental insulation. • Input to TB142A, TB142B, and TB142C should not carry voltage.• Cables from equipment connected to external input/output should have supplemental insulation. • Use a single multiple-core cable for external input/output to allow for connection to the PG screw.
Caution:Wire the power supply so that no tension is imparted. Otherwise disconnection, heating or � re result.
2
S
M2
M1
(A)
(B)
(D)
(E)
1
LN
DC10~13V
A B1 2
(C)
(A) Non-polarized (B) TB15 (MA remote controller cables)(C) MA remote Controller(D) TB5 (Transmission cables)(E) TB2 (Power supply wiring)
PWFY- P200VM-E1-AU
- 32 -
(4) Transmission cable specifications(4)-1 Transmission cables
(5) Connecting electrical connections
*1 Connected with simple remote controller. CVVS, MVVS: PVC insulated PVC jacketed shielded control cable CVV, MVV : PVC insulated PVC sheathed control cable CPEVS : PE insulated PVC jacketed shielded communication cable
Type of cable
Cable diameter
Remarks
Transmission cables
Shielding wire (2-core)CVVS, CPEVS or MVVS
More than 1.25 mm2
-
MA Remote controller cables
Sheathed 2-core cableCVV (unshielded)
0.3 � 1.25 mm2 (0.75 � 1.25 mm2)*1
Max.length: 200 m
External input
Sheathed multi-core cableCVV or MVV (unshielded)
0.3 � 0.5 mm2
Max.length: 100 m
External output
Sheathed multi-core cable (unshielded)CVV or MVV
0.3 � 1.25 mm2
Rated voltage: L1-N: 220 � 240 VRated load: 0.6 A
PWFY-P200VM-E1-AU
Note:Ensure that the wiring is not pinched when � tting the terminal box cover. Pinching the wiring may cut it.
Caution:Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.• Fix power source external input/output line wiring to control box by using buffer bushing for tensile force to prevent
electric shock. (PG connection or the like.) Connect transmission wiring to transmission terminal block through the knockout hole of control box using ordinary bushing.
• After wiring is complete, make sure again that there is no slack on the connections, and attach the cover onto the control box in the reverse order removal.
[Fig. IV. 1.(5).2]
(A) Screws(B) Front panel(C) Control box
(A) To prevent external tensile force from applying to the wiring connection section of power source terminal block use buffer bushing like PG connection or the like.(B) External signal input cable(C) External signal output cable(D) Power source wiring(E) Tensile force(F) Use ordinary bushing(G) Transmission cable and MA remote controller cable
(A) (C)
(B)
(C)
(A)(A)
(A)
(B)
(D)
(E)
(G)
(F)
Verify that the model name on the operating instructions on the cover of the control box is the same as the model name on the nameplate.Step 1Remove the screws holding the terminal box cover in place. [Fig. V.1.(5).1]
Caution:Wire the power supply so that no tension is imparted. Otherwise disconnection, heating or � re result.
- 33 -
(6) Indoor unit address setting(Be sure to operate with the main power turned OFF.) [Fig. V. 1.(6).1] <Address board>
SWU2 SWU3SWU1
(6)-1 Rule of setting address
AG-150AGB-50ADA 000, 201 ~ 250
10 1100
0,2 0~5 0~9
PAC-YG50ECA 000, 201 ~ 250
10 1100
0,2 0~5 0~9
BAC-HD150 000, 201 ~ 250
10 1100
0,2 0~5 0~9
Settings are made on the initial screen of AG-150A.
Settings are made with setting tool of BM ADAPTER.
Unit
PWFY unit
ME, LOSSNAYRemote controller(Main)
ME, LOSSNAYRemote controller(Sub)
Address setting
01 ~ 50
101 ~ 150
151 ~ 199, 200
NoteExample
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
ON/OFF remote controller 000, 201 ~ 250
Loca
l rem
ote
cont
rolle
rS
yste
m c
ontro
ller
The address of main remote controller + 50
The address automatically becomes "200" if it is set as "00"
LMAP02-E 201 ~ 250
1
1
Fixed
Fixed
2Fixed
Outdoor unit(Heat source unit)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant system + 50 Please reset one of them to an address between 51
and 99 when two addresses overlap. The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of indoor units.
(Note1)
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
0 1 2 3 4 5 6 7
8
90 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1100
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
Note1: To set the address to "100", set it to "50"
- 34 -
(6)-2 System examples
PWFY-P200VM-E1-AU with PUHY-P300YJM-A or PQHY-P300YHM-A outdoor unit (heat source unit)
(6)-2-1 MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long M-NET wiring
1. Address should be set to Indoor units, LOSSNAY and central controller.
2. M-NET power is supplied by the Outdoor unit (heat source unit) at TB3, while Indoor unit and MA consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to Data book SYSTEM DESIGN, SYSTEM DESIGN Y SERIES, 2-3 "System configuration restrictions".
NOTE:
PWFY-P200VM-E1-AU
WMA
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
10TB5 TB15
TB15
PWFY-P200VM-E1-AU
WMA MA
4341 42 45TB15 5BT5BT
LOSSNAY
5BT5BT
SRU
Wireless R/C
*1
*1
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
Group 32 33 puorG
13 puorG
7BT7BT
TB3
201
PSU
*2
51
OC
PUHY-P300YJM-APQHY-P300YHM-A
[SW4-7 ON] [SW4-7 OFF]
SC
TB3
91
OC
PUHY-P-YSJMPQHY-P-YHM
CN41CN40 CN4104NC
ONDipSW2-1
ONDipSW2-1
- 35 -
• External analog inputUse the supplied connector. If no temperature settings are made via the MA remote controller, the temperature changes with the current of generator.
External output terminalExternal output terminal (refer to Fig. V. 1.(7).2) is ineffective when the circuit is open. Refer to Table V. 1.(7).1 for information about each contact. The current and voltage in the circuit to be connected to external output terminal (TB141A OUT1) must meet the following conditions.
Contact rating currentContact rating voltage
AC250V 1A or lessAC125V 3A or lessDC30V 3A or less
External input terminalThe piping length must be within 100 m.External input terminal (refer to Fig. V. 1.(7).3) is ineffective when the circuit is open. Refer to Table V. 1.(7).2 through Table V. 1.(7).4 for information about each contact.Only the “pump interlock” function is ineffective when the circuit is short-circuited.Connect a relay circuit to the external output terminal as shown in Fig. IV. 3.(9).2.The speci� cations of the relay circuit to be connected must meet the following conditions. Contact rating voltage >= DC15VContact rating current >= 0.1AMinimum applicable load =< 1mA at DC[Table V. 1.(7).2] TB142A [Table V. 1.(7).4] TB142C
[Table V. 1.(7).3] TB142B
*1 PWFY-P200VM-E1-AU Heating*2 Effective when SW 4-3 is set to ON.*3 Effective when SW 4-4 is set to ON.*4 PWFY-P200VM-E1-AU only*5 When Heating ECO mode is effective, the outlet water temp. will be changed based on ambient temp. automatically. (Except for PQHY-series)*6 When Anti-freeze mode is effective, the unit will set the heating temperature range between 10ºC~45ºC enabling the unit to maintain low water temperature to prevent water pipes from freezing.
Note: When setting Heating ECO or Anti-freeze mode, reset all power supply of all units (outdoor/indoor units).Note: Dip S/W 1-1 OFF: Water Inlet Temp. Dip S/W 1-1 ON : Water Outlet Temp. The factory setting for Dip SW 1-1 is OFF.Signal priority = External input > centralized controller > remote controller
(7) External input/output functionPreset temperature input (external analog input: 4mA-20mA)• External inputInput through CN421, CN422 on the circuit board. (Fig. V. 1.(7).1)
OUT1OUT2OUT4
Operation ON/OFFDefrost
Error signal
IN1 Pump interlock
IN3IN4
Connection demandOperation ON/OFF
[Fig. V. 1.(7).1]
[Fig. V. 1.(7).3]
[Fig. V. 1.(7).2]
OUT4OUT3OUT2
TB141A
OUT1
IN1 IN2 IN3 IN4 IN5IN6 IN7 IN8
TB142CTB142BTB142A
COM+
CN
421
(BK
)(B
U)
CN
422
3
2
2
1
1
3
CN
421
(BK
)
(BU
)C
N42
2
32
+
21 13
currentdirection
Current generator
Externalanalog input
+
currentdirection
COM+IN5 *1IN6 *2IN7 *3IN8 *4
CommonHot Water/Heating
Heating ECO *5Anti-freeze *6
Cooling operation
Method Input T(A), T(B)4mA :T(A)20mA:T(B)
S/W default T(A)=10°C T(B)=70°C.
*All setting with a controller.
T(B)°C
T(A)°C
4mA 20mAla
Conversion equation:To=[{T(B) - T(A)}/16] × Ia + [ T(A) - {T(B) - T(A)}/4] To: set temperature, Ia: analogue input value (mA)
Calculation example: T(A)=30°C, T(B)=70°C, Ia=10mAConversion equation: To=2.5 × Ia+20 To=45°C
Changeable with PAR-W21MAA
[Table. V. 1.(7).1]
- 36 -
1. PAR-W21MAA specifications
ON/OFF
Operation mode switching
Water temperature setting
Preset temperature range
Water temperature display
Permit / Prohibitlocal operation
Weekly scheduler
Error
Self check (Error history)
Test run
Circulating waterreplacement warning
LANGUAGE setting
Operation locking function
Runs and stops the operation of a group of unitsSwitches between Hot Water / Heating / Heating ECO / Anti-freeze / Cooling* Available operation modes vary depending on the unit to be connected.* Switching limit setting can be made via a remote controller.Temperature can be set within the ranges below. (in increments of 1°C or 1°F)Hot Water 30°C ~ 70°C Heating 30°C ~ 55°C Heating ECO 30°C ~ 55°CAnti-freeze 10°C ~ 45°C Cooling 10°C ~ 30°C * The settable range varies depending on the unit to be connected.Preset temperature range setting can be limited via a remote controller.10°C ~ 90°C(in increments of 1°C or 1°F)* The settable range varies depending on the unit to be connected.Individually prohibits operations of each local remote control function :ON/OFF, Operation modes,water temperature setting, Circulating water replacement warning reset.* Upper level controller may not be connected depending on the unit to be connected.ON / OFF / Water temperature setting can be done up to 6 times one day in the week.(in increments of a minute)When an error is currently occurring on a unit, the afflicted unit and the error code are displayed.Searches the latest error history by pressing the CHECK button twice.Enables the Test run mode by pressing the TEST button twice.* Test run mode is not available depending on the unit to be connected.Displays the circulating water replacement warning via the unit message.Clears the display by pressing the CIR.WATER button twice.* Circulating water replacement warning is not available depending on the unit to be connected.The language on the dot matrix LCD can be changed. (Seven languages)English/German/Spanish/Russian/Italian/French/SwedishRemote controller operation can be locked or unlocked.·All-switch locking·Locking except ON/OFF switch
Item Description Operations Display
Controller VI
- 37 -
2. Dip switch functions
Switch FunctionFunction according to switch setting
Switch setting timingOFF ON
SW1
1 T
Operation after power recovery *1
Operation after power recovery
H0 thermistor selection Water inlet thermistor TH6 Water outlet thermistor TH8 Before power on
Before power on
Before power on
2 - - - -
3 Remains stopped
Depends on the SW1-3 setting
Auto recovery (to the status before power failure)
Forced to operate
*1 Valid only when SW1-4 is set to OFF*2 The following changes can be made by changing the setting of the switch from OFF to ON.
0.5
4
5 - - - -
6 - - - -
6 - - - -
7 Test-run mode OFF ON Any time
8 Error history deleted Normal Deleted Any time
Interlocked operation with the pump Effective Ineffective Any time
9Effective only when SW1-7 is set to ON and only on the HEX models.
Heating Cooling Any time
10
SW2 1-10 For self-diagnosis/operation monitoring - - Any time
SW3
1 - 8HP
2 Service LED display selection Display in Centigrade Display in Fahrenheit Any time
3 - -
-
- -
-
4 - - - -
5 Cumulative compressor opera-tion time is deleted. Normal Deleted Any time
6
7 - - - -
8 - - - -
9
10 - - - -
SW4
1
2
3Use to change pr
Do not change from factory setting.
Do not change from factory setting.
eset tempera-ture range for the Heating ECO mode.
Ineffective 30°C to 55°C Before power on
4Use to change pr
Interlocked pump switching Excludes stoppage Thermo-ON only Any time
Any timeHeating Thermo OFF differential change *2
eset tempera-ture range for the Anti-freeze mode.
Ineffective 10°C to 45°C Before power on
5 - - - -
7 - - - -
8 - - - -
9 - - - -
10 - - - -
SW5
1 Error detection enabledEnabling/disabling ACCT sensor error detection
Error detection disable(No load operation is possible)
Any time
2 - - - -
3 - - - -
4 - - - -
1 0.5 2 0.5 3 0.5 4 0.5 5 0.5 6 0.5 7 0.5 8
- 38 -
1. Routine maintenance checks• Periodically and thoroughly check the circulating water circuit. (See table below.)• Consult a maintenance technician.
2. Parts Replacement Cycle
Components
Refrigerant circuit
components
Electric circuitparts
What to look for Maintenance cycle(times/year) Replacement cycle
Compressor
Water-refrigerant heat exchangerSolenoid valve(PWFY-P200VM-E1-AU)Check valve(PWFY-P200VM-E1-AU)Linear expansion valveStrainerCapillary tubePipes
Electromagnetic contactor
Overcurrent relay
Relay
Solenoid valveFuseElectronic boardSwitchPressure switchTerminal blockCable/connectorFanMotor
High/low pressure, vibration, noiseInsulation resistance, loose terminalsHigh/low pressure, water pressure loss
Operation, leakage, clogging
Operation, leakage, clogging
OperationInlet/outlet temperature differenceContact wear, VibrationContact wear, VibrationCorroded contact, loose terminalsInsulation resistanceloose terminalsOperation, Contact resistance.Insulation resistanceInsulation resistanceExternal appearanceExternal appearanceOperation, Contact resistance.Contact resistance.loose terminalsLooseness, corrosion, and wearingBalanceInsulation resistance, noise, vibration
20,000 hours
10 Years
7 Years
10 Years 7 Years
While in heavy use10 Years10 Years
8 Years
7 to 10Years
6 Years
7 Years8 Years8 Years8 Years
7 to 10Years8 Years10 Years10 Years
6 to 10Years
2
2
2
1
2111
2
2
2
222222222
Regular preventive maintenance and parts replacement help keep the unit running smoothly and minimize problems. The table below shows the maintenance schedule. Use the replacement timing in the table only as a guide. Some parts may need to be replaced sooner, depending on the usage.
Maintenance Cycle VII
DATA BOOK PWFY-P200VM-E1-AU- For high temperature flow
MEE11K028
New publication effective Feb. 2012Specifications subject to change without notice
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Eco Changes is the Mitsubishi Electric Group’s environmental statement, and expresses the Group’s stance on environmental management. Through a wide range of businesses, we are helping contribute to the realization of a sustainable society.
WarningDo not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, during repair, or at the time of disposal of the
unit.- It may also be in violation of applicable laws.- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong
type of refrigerant.
■
http://Global.MitsubishiElectric.com