MSMODEL
Safety Precautions
Please read the instruction manualbefore using the device.
G-199-3-C9173-A HQ1303 Printed in Japan (MDOC)New Publication, effective Mar. 2013.
Specifications are subject to change without notice.
MEDIUM VOLTAGESWITCHGEAR AND CONTROLGEAR
MP Series multi-relay● Combining the MP23 and wide-range
CT makes it easy to cope with the changes in load capacity by using only the CT ratio setting changes of the multi-relay (CT setting ranges are 60~600A and 200~2,000A).
● Display lights protrude from the panels to enhance visibility when viewing panels from side-on.
VPR-C Series VCBs● Comply with Restriction of Hazardous
Substances (RoHS).
● Long-life grease and non-lubricated bearing realize reduced maintenance.
Consideration for easy maintenance
● Through vertical location of the main busbar, maintenance from the back of panels is simplified, reducing maintenance work.
● The number of bolts for busbar connection has been reduced. This contributes to easier maintenance to check the bolt condition.
1 2
Page
STANDARD & RATINGS 3
VACUUM CIRCUIT BREAKER
SECTION VIEW OF “MS”
VACUUM MAGNETIC CONTACTOR
5
6
7
OUTLINE DIMENSION
1. MS2. LSH
11
SECTION VIEW OF “LSH” 8
CONSTRUCTION 9
1. Operation for Vacuum Circuit Breaker2. Grounding busbar3. Control circuit4. Single line diagram5. Arrangement6. System compatibility
HIGH RELIABILITYMS is designed with the benefit of Mitsubishi’s vast medium voltage panels production experience of hundreds of thousands of panels over the last almost 60 years. 3D-Thermo Fluid Analysis of the switchgear structure has led to a heat-resistant design in which circuit breakers up to 3150 A are self-cooled (i.e. cooling fans not required).The reduced number of parts decreases the chance of failure.
EASY INSTALLATIONInstallation and testing duration are considerably reduced as the panel is tested and adjusted in the factory and then delivered as a complete unit.
SAFETYPartitions between compartments and an automatic shutter system (for withdrawable equipment primary junctions) completely isolate live parts.
FEATURES
Easymainte-nance
Eco-conscious
Intelligent
Innovation
Since the 1950s, Mitsubishi Electric has been providing power distribution equipment and systems matched to the needs of the era. Now, inheriting the technologies and reliability forged from this manufacturing record of over half a century, the MS Series switchgear realizes the next evolutionary step forward.
MP Relay 13
ACCESSORIES 149
3 4
1 STANDARD & RATINGS
Ratings
Type designation
Applied standard
Rated voltage
Rated frequency
Location
Degree of protection
Ambient temperature
Altitude a.s.l.
Rated normal main busbar current
Rated short-time withstand current , symmetrical
Rated peak withstand current
Rated duration of short-circuit
Control voltage
Loss of service continuity category
Rated insulation level Short-duration power frequency withstand voltage, 1 min. Lightning impulse withstand voltage
Earthquake protection2 Horizontal seismic withstand3
Vertical seismic withstand
Humidity R.H. Water vapour pressure
1.2.3.4.
5.
Internal Arc Classification will not be applicable.General use, class B on the upper floor or roof of building according to JEM-TR 144.Static acceleration of horizontal is 3.92 m/s2 at base of structure.Please contact a Mitsubishi Electric representative regarding requirements for rated busbar currents of 2,000A.Select a product with a rating equal to or above the total of load current running on the vertical busbar. In addition,please consider future increases in unit capacity, additional system compatibility,and conditions for these installations.Other control voltages including A.C. are also available.
[kV, rms]
[Hz]
[kV, rms]
[kV, peak]
[A, rms]
[kA, rms]
[kA, peak]
[sec]
[V,AC/DC]
[℃]
[m]
[%][kPa]
[m/s2] [m/s2]
MS
IEC 62271-2001, JEM1425
16 22
45 60
630, 1250, 2000, 3150
25, 31.5, 40
0.5, 1
DC48, 100, 110, 125, 2205
LSH
IEC 62271-2001, JEM1225
10 16
30 45
400, 630, 800, 1250, (2000)4
40
0.5
AC100/110, 200/220V
3.6 7.2
50, 60
50 Hz: 2.5×Ik , 60 Hz: 2.6×Ik
Indoor, Outdoor
Indoor:max. IP4X, Outdoor:max. IP33
-5 ~ 40
max.1000
max. 95average 2.2
9.803.23
Ur
fr
Ud
Up
Ir
Ik
Ip
tk
IEC
JEM
LSC2B-PM
MW/MWG
LSC2B-PI
PW/PWG
LSC1 LSC2A-PI LSC2A-PM
CW
SectionalView
Structure
IP codes
Interfacebetween
Enclosure andCircuit Breaker
(Example of feeder panel) (Example of feeder panel)
●All compartments for busbars, circuit breakers and cables are separated by partition plates made of metal.
●Bush ing fo r the ma in c i rcu i t passage between compartments (for the MWG Series, the main circuit has insulation coating).
●All compartments for busbars, circuit breakers and cables are separated by partition plates made of metal or insulation materials.
●Bushing used for the main circuit passage between compartments (for the PWG Series, the main circuit has insulation coating).
●Small number of compartments
●No partition plates
●Low protective class even with partition plates
●Main circuit: Automatic connection
●Control circuit: Manual connection
●Automatic shutters for touch protection are applied between main contacts of circuit breaker and enclosure.
●Main circuit: Automatic connection
●Auxiliary circuit: Manual connection
●Automatic shutters for touch protection are applied between main contacts of circuit breaker and enclosure.
●Main circuit: Automatic connection
●Control circuit: Manual connection
2XCT
2XCT
VCB R
S
T
VCB
T
S
RVCB
VCB 2XCT
2XCT
Circuit breaker compartmentCablecompartment
Busbarcompartment
Bushing
Shutter
Circuit breakercompartment
Partition plate
Busbarcompartment
Busbar
Busbar
Partitionplate
JEM 1425 IEC 62271-200
Rated Voltage
Rated Power Frequency Withstand Voltage
Rated Lightning ImpulseWithstand Voltage
Loss of Service Continuity Category
Rated Short-time Withstand Current
Rated peak Withstand Current
Internal Arc Classification (IAC)
3.6
16
45
7.2
22
60
3.6
10
40
7.2
20
60
Cubicle LSC1, LSC2A-PI, LSC2A-PM
Compartment
Metalclad
LSC2B-PI
LSC2B-PM
25, 31.5, 40
50Hz: 2.5×Ik, 60Hz: 2.6×Ik
25, 31.5, 40
50Hz: 2.5×Ik, 60Hz: 2.6×Ik
Optional type tests <subject to agreement between manufacturer and user>
Mandatory type tests, where applicable
Ur
Ud
Up
Ik
Ip
●Enclosure: IP2X (Ø12mm) or less
●Partition: IP2X (Ø12mm) or less (excluding CW, LSC1, LSC2A-PI, LSC2A-PM)
●Protective plates between control room and main circuit: IP1X (Ø50mm)
IEC:Max. LSC2B-PM
JEM:Metal-Clad
IEC:Max. LSC2A-PM
JEM:Class M5
[kV, rms]
[kV, rms]
[kV, peak]
[kA, peak]
[kA, rms]
Various construction grades
Comparison table between JEM 1425 and IEC 62271-200
5 6
3 SECTION VIEW OF “MS”2 VACUUM CIRCUIT BREAKER
Manufacturer
Type designation
Applied standard
Rated voltage
Rated frequency
[kV, rms]
[Hz]
[A]
[kV, rms][kV, peak]
[kA, rms]
[kA, rms]
[sec]
[A, rms]
[kA, rms]
[cycles]
[kA, peak]
[V DC]
[A]
[sec]
[A]
[A]
[kg]
Rated insulation level Short-duration power frequency withstand voltage, 1 min. Lightning impulse withstand voltage
Rated operating sequenceO–3 min–CO–3 min–CO
O–0.3 sec–CO–3 min–COCO–15 sec–CO
6/10-VPR-□□C1
Mitsubishi Electric
Rated short-time withstand current
Rated peak withstand current
Rated duration of short-circuit
Rated cable-charging breaking current
Rated short-circuit breaking current
Rated normal current (self-cooling)
25, 31.5, 40
3
63, 78.8, 100
48, 100, 110, 125, 2202
630, 1250, 2000, 3150
Closing control current (at 110 V DC)
Tripping control current (at 110 V DC)
Auxiliary switch (contacts)
3.4
3.4
5a, 5b
1.2 (peak 6 A)Approx. 6 (after closing)
22
60
Closing operation Motor current (at 110 V DC) Spring charging time
Weight 630, 1250 A: 140 2000 A: 160 3150 A: 210
IEC 62271-100, JEC2300
50, 60
3.6 7.2Ur
fr
Ir
Ud
Up
Ik
Ip
tk
Ic
Isc
Ua
M
3
10, 25
25, 31.5, 40
50 Hz: 2.5×Ik , 60 Hz: 2.6×Ik
Rated break time
Rated short-circuit making current
Rated control voltage
1.
2.
Rated short-circuit breaking current25 kA31.5 kA40 kAOther control voltages including A.C. are also available
VPR-25C/32C/40C
□□□□□□
234
520
*1 When rated current is 3,150A or higher, the circuit breaker installation position changes to the lower part of the panel.*2 When rated current is 3,150A or higher, W=1,000.*3 According to the rated current, W=700 is available.
Incoming panel*1
CT
SAR
VT
VCB20kA
2000A
1970
2300
EVT
VCB20kA
2000A
1970
W=800*2
Feeder panel-2
Bus Tie/EVT panel
W=800*2
W=800
Feeder panel-1
VCB20kA630A
VCB20kA630A
CT
CT
1970
W=800*3
VCB31.5/40kA1250A
VCB31.5/40kA1250A
CT
CT
1970
2300
2300
2300
50 505050
7 8
5 SECTION VIEW OF “LSH”4 VACUUM MAGNETIC CONTACTOR
Manufacturer
Type designation
Applied standard
Rated voltage
Rated insulating voltage
Rated frequency
[kV, rms]
[kV, rms]
[Hz]
[A]
[kV, rms][kV, peak]
[kA, rms]
[V AC/DC]
[A]
[A]
[kg]
Rated insulation level Short-duration power frequency withstand voltage, 1 min. Lightning impulse withstand voltage
□□F○VN1
Mitsubishi Electric
Rated short-circuit breaking current
Rated operational current (self-cooling)
40 (Power fuse)
100, 110, 200, 220
200, 400
Closing control current (at 100V DC)
Tripping control current (at 100V DC)
Auxiliary switch (contacts)
Operation system
4.8
3.5 (Mechanical latch type)
2a, 2b
6.6
7.2
20
60
Weight200 A: 90 400 A: 90 (for 3.3 kV) 100 (for 6.6 kV)
IEC 60470
50, 60
Ur
fr
Ie
Ud
Up
Isc
Ua
M
Rated control voltage
Electrical hold type,Mechanical latch type
1. Power fuse rating20 A50 A100 A150 A200 A300 A400 AContactor rating200 A400 A
□□□□□□□□□□□□□□
○○
0011234
24
2505000
Unit
Vacuum Magnetic Contactor
Combination unit (power fuse and vacuum contactor)
Interlock lever
●Normal/Test
Vacuum contactor
Power fuse
VT
CT
Control power supply switch
CTD (power supply with draw-out capacitor tripping device)
Option
Multi-tier (3.3kV) Multi-tier (6.6kV)
1300
VTCT PFVMC
ZCT
busbar
2300
2300
1500
360
210
ZCT
VMC
CT
busbar
1500
ZCT
VMC
2300
50
50
50
busbarPFCT VT3.3kV,3-tier
3.3kV,4-tier (unit depth: 1,500)
6.6kV,2-tier
*For 6.6kV models, the maximum number of tiers is 3.Standard Structure
VT PF
ZCT
1500
busbarPFCT VTVMC
ZCT
VMC
VT
CT
PF
1300
50
2300
50
2300
W700
W700
360
210
Note: 4-tier units are equipped with a ventilation duct.
The unit is equipped with a ventilation duct when the vertical busbar rating of the panel is 700A.
Note:
For 3-tier units, a ventilation duct is equipped when the vertical busbar rating of the panel is 700A .When the busbar rating is 2,000A, the unit is equipped with a partition in the horizontal busbar compartment and ventilation ducts in upper and lower parts of the rear cover.
*1
*2
Notes:
9 10
6 CONSTRUCTION
1. Operation for Vacuum Circuit Breaker 4. Single line diagram
5. Arrangement
6. System compatibility
1. TEST/DISCONNECTED position. 2. Connect the plug so as to may move to the CONNECTED position.
3. Move to the CONNECTED position. 4. The plug cannot be pulled out at the CONNECTED position.
2. Grounding busbar
Grounding busbars installed in each panel can be easily connected onsite using bolts.
3. Control circuit
The auxiliary relay, terminal block and other devices are mounted in the control room at the front of the panel. For connections between panels and across doors, this is designed to enable simple connections via connectors.
Grounding busbar connection Control circuit connection between panels
Connector for connections between panels
Grounding busbar
Connection point between panels
VMC
ZCT100/5A
VMC
VMC
ZCT
ZCT
3×CT3×CT
2×VT
VCBVCB
2×CT
ZCTZCT
VCB
CR
CR
VMC2×CT
2×CT
2×CT
ZCT
VMC
VMC
ZCT
ZCT
VCB
ZCT
CR
3×LA
SINGLE LINE
2×CT
2×CT
2×CT
E.BUS
INCOMING
N P
5
800
AN P
4
800
AN P
N P
3
800
A
B
N P
N P
N P
1
700
A
B
C
FL
PANEL NO.
SIDE SPACE700
N P
N P
N P
6
700
A
B
C
450
N P
2
MSMSMSLSH LSHBUS Transfer Panel
A
SIDE SPACE700
FRONT VIEW
50
Connection with Mitsubishi Electric Type “MS” switchgear
(1) When the position of horizontal busbar in the MS switchgear is same as that of LSH
(2) When the position of horizontal busbar in the MS switchgear is not same as that of LSH
LSH
M/C M/C
70050
Example: Top view
LSH
Bustransferpanel
700450
● An auxiliary frame (W=50) is required to connect the MS switchgear with the LSH
● The depth of the auxiliary frame must be same as that of the MS switchgear.
● A bus transfer panel (W=450) is required.
● The depth of the bus transfer panel must be same as that of the MS switchgear.
11 12
7 OUTLINE DIMENSION
1. MS
VCBs
2000
1200
2000
3150
910/940
980/1010
970
1040
1200
1250
1200
1360
1200/1250
2000
1200/1250
250×1 line
250×1 line
325×1 line
325×1 line
Bus duct
325×1 line
Bus duct
Bus duct
500
600
1000
1100
1000
1000
1100
1500
800
800
800
800
800
800
800
1000
1670
1970
1670
1970
1970
1970
1970
1970
2000
2300
2000
2300
2300
2300
2300
2300
1340
1470
1370
1500
1660
1710
1670
1940
2730
*3
*3
*5
*5
*5
600
120025VPR-
25C
2000
3000/315031.5/40VPR-32/40C
Installedswitchgear Model
Breakingcurrent
(kA)
Ratedcurrent
(A)
Panel busbarcurrent
(A) Width Depth*1 Height
Indoor Outdoor
Panel dimensions (mm) Panel external dimensions (mm) Panel weight/Calorific value (incl. circuit breakers)
Max. lead-in cable size (XLPE mm2)×No. of linesWeight (kg)
J/S(=W)Indoor*2 Outdoor Indoor Outdoor Indoor Outdoor
2300*4
〈Standard Outline dimensions〉
Detailed view of foundation
Hole for power cable*2 Hole for control cable
150
50
90133 400 103
5383
7575
Pan
el w
idth
Depth
*4
Indoor type
FL
Front
Front
Door
M16 bolt*3
Cover
Pan
el w
idth
283400283 90
5015
0
80 80
Depth
7575
*4 M16 bolt*3
FL
Embedded frame*3
Outdoor type
Interior door
Exterior door
2. LSH
Maintenance space (min.)(mm)Front: 1,800Rear : 1,200Side : 700
Maintenance space (min.)(mm)Front: 1,800Rear : 700Side : 700
150
Embedded frame*1
Foundation bolt: M12*1
105
145
145
145
Hole for power cable
Hole for control cable
(Dim
ensio
n of
indo
or ty
pe +
150
)
3535
52
30
52
30
(Dimension of indoor type + 159)
275 192200192
Outdoor type
Indoor type
〈標準外形寸法〉〈Standard Outline dimensions〉
Voltage
3kV
~800A
~1250A
~1250A
700
1300
1500
1459*2
1659*3
800*1 2300*4 2720
2
3
4
2
3
4
2
36kV
Current No. of tiers Width
Indoor Outdoor
Depth
Indoor Outdoor
Height
Indoor Outdoor
Weight (kg)J/S(=W)
Indoor Outdoor
Panel weight/Calorific valuePanel dimensions
Detailed view of foundation
Hole for control cable
Hole for power cable*2
600
750
900
600
750
900
700
900
1200
1350
1600
1200
1350
1600
1300
1500
700
950
1200
1200
1700
2200
1200
1700
31
105
Hole forcontrol cable
122 225
70
560
275 103
1300(1500)
50
700
100
100
500
Hole for power cable
50
Foundation bolt: M12*1
Channel base*1Front
Front
*1 Available as an option.
50
150
Channel base*3
Maintenance space (min.)(mm)Front: 1,800Rear : 700*1
Side : 700
Maintenance space (min.)(mm)Front: 1,800Rear : 1200*1
Side : 700
2
2
2
2
1
2
1
1
No. installed
*1 For insertion/removal of devices from the rear, dimensions shall be decided according to separate arrangements.*2 Size of lead-in hole may vary from these dimensions when the lead-in cable has more than three lines. *3 Available as an option.*4 This dimension is the panel width minus 200mm for the main circuit cable holes.
*1 For side panel of both ends. 30mm should be added to each ends.*2 Roof depth is 1,729mm.*3 Roof depth is 1,929mm.*4 Excluding a height of 50mm for the channel base.
*1 Depth increases by 300mm when applying two cable lines.*2 Depth increases by 30mm (optional) in the case of a rear door.*3 For indoor panels only, a 700mm configuration is possible. *4 For two-tier panels with cable lead-in from the top of the panel, the cable processing box (500×500mm [H×D]) may be mounted at the top of the panel. *5 For rated current of 2,000A and above, bus duct connections are standard.
13 14
9 ACCESSORIES8 MP Relay
Protection
Measurement
Control
CB monitoring
Fail-safe andself-diagnostics
History
CC-Link transmission(option)
CDL transmission(option)
Transducer outputs(option)
4~20mA DC output of various measurements (Wh and varh are pulse outputs)
Transmission of various measurements, protection data, ON/OFF status of circuit breaker, and reception of remote control signals
Time-to-trip and fault voltage/current of last 5 faults (time-to-trip is the elapsed time from detection of the fault to the protective relay operation)
Transmission of various measurements, protection data, ON/OFF status of circuit breaker, and reception of remote control signals
Circuit breaker operation monitoring
A, DA, DAmax, V, W, DW, DWmax, Wh, var, varh, Hz, cosΦ, A0, V0, V0max
'50, 51, 67, 51G(using ZM-type ZCT or 3 x CT residual circuit), 27, 59, 6446, 49(Motor Protection only)
Function Description
ON/OFF of circuit breaker, REMOTE/LOCAL control mode selection, enable trip output contact, enable CB closing during a fault, setting of general purpose inputs and outputs, CB-ON delay timer
ON/OFF output of circuit breaker, TRIP output monitoring (using sequential logic), CPU condition, memory, AD converter, internal power supply, ratio check of analogue circuit
Standard equipping of MP Series digital multi-relays realizing even higher reliability
For the protective control device, MP Series digital multi-relays equipped with protection/control functions are adopted. Failsafe/Accident diagnosis functions are equipped, realizing an even high level of reliability. Furthermore, adding an optional transducer/transmission function and overall computerization of the power distribution equipment simplifies the interface with the central monitoring and control equipment.
High reliability
●The MP Series digital multi-relay centralizes measurements, protection and control functions into one unit, reducing wiring inside the panel by 50%.
●As a result of adopting the MP Series digital multi-relay and wide-range CT, it is not necessary to replace the CT in response to load changes. In addition, through adopting a composite CT*1 (optional), it is possible to achieve simplification of the ZCT high-voltage cable processing.
●MP Series digital multi-relays have five kinds of overcurrent protection properties equipped as standard, and it is not necessary to replace the relay.
High functionality
9 8 7 6
250
160
4
5
1
2
3
11
12
10
13
14
16
15
17
Draw-out handle for withdrawable equipment
Manual charging handle for VCB closing spring
Test Terminals test plug set for secondary circuit of VT & CT
Lifter with bucket for withdrawable equipment
Control circuit extension cable for withdrawn
VCB / VMC ON / OFF testing
Earthing switch operating handle
Standard accessories
Draw-out handle Test plug set Lifter with bucket
Control circuit extension cable
Optional accessory
Lifter
Bucket
Earthing truck ( Upper Terminal*1 )
1. STANDARD ACCESSORIES
2. OPTIONAL ACCESSORIES
Optional earthing devices are available for
safety during cable and busbar maintenance
and/or inspection.
3. EARTHING DEVICES
An earthing truck with fault-making
capability which has the same operating
mechanism as the circuit breaker.
Earthing truck for switchgear
1
2
3
4
5
6
7
8
Select switch (back, down)
Circuit breaker On switch
Circuit breaker Off switch
Remote switch
Local switch
Reset switch
Test switch
Set switch
Circuit breaker forced off switch
Input/Output 16P connector (connector No. CN2)
Input/Output 20P connector (connector No. CN3)
9
19
18
17
16
15
14
10
11
12
13
23
20
21
22
Liquid-crystal display (LCD)When there is a failure with the liquid crystal or lamps, it is possible to replace the LCD only.
Circuit breaker On lamp (red or green)
Circuit breaker Off lamp (green or red)
Failure display lampMinor failure: Orange; Serious failure: RedSystem emergency lamp (red)
Select switch (next, up)
Mode switch (right)
Mode switch (left)
Connector for transmission, transducer communicationsCC-Link: 5P connector; Transducer: 18P connector
Optional unitAn optional unit for transducer or CC-Link transmission can be installed.Empty case when no optional unit is installed.
Power supply partWhen there is a power-supply failure, it is possible to replace the power-supply part only.
Separated terminal block (power supply, VT, CT, ZCT)The terminal block can be removed by loosening screws at both ends. However, with the terminal block removed, there is no short-circuit function of the CT input part.
*1 Composite CT: A molded multi-type CT combining the wide-range CT and ZCT.
*1 Lower terminal is also available.