Mitsubishi D700 Series Vfd Brochure

download Mitsubishi D700 Series Vfd Brochure

of 33

Transcript of Mitsubishi D700 Series Vfd Brochure

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    1/33

    Buy Mitsubishi D700 VFD at MRO Stop - http://www.mrostop.com/resource-center/mitsubishi-d700-vfd

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    2/33

    F e a t u r e s

    S t a n d a r d s p e c i f i c a t i o n s

    O u t l i n e d i m e n s i o n

    d r a w i n g s

    T e r m i n a l c o n n e c t i o n d i a g r a m

    T e r m i n a l s p e c i f i c a t io n e x p l a n a t i o n

    O p e r a t i o n p a n e l P a r a m e t e r u n i t

    P a r a m e t e r l i s t

    P r o t e c t i v e f u n c t i o n s

    O p t i o n a n d p e r i p h e r a l d e v i c e s

    P r e c a u t i o n s f o r o p e r a t i o n / s e l e c t io n

    P r e c a u t i o n s f o r p e r i p h e r a l d e v i c e s e l e c t i o n

    1

    5

    7

    F R - D 7 0 0 S e r i e s S p e c i f i c a t i o n

    D i f f e r e n c e L i s t

    32

    W a r r a n t y

    I n t e r n a t i o n a lF A C e n t e r

    33

    11

    13

    16

    23

    24

    27

    Highly reliable inverter!

    Safety stop function

    Spring clamp terminal (control circuit terminal)

    Long-life design

    The FR-D700 series is compliantto the EU

    Machinery Directive withoutthe addition of

    previously required external devices.

    Operation of an external Emergency

    Stop device results in a highly reliable

    immediate shutoff of the D700's output to

    the motor.

    This safety stop function conforms to thefollowing standards.

    Enhanced function

    Compact yet equipped with highest level of function/performance!!

    150%/1Hz high starting torque by General-purpose magnetic flux vector control

    General-purpose magnetic flux vector control and auto

    tuning function are available.

    It ensures operation that requires high starting torque,

    such as transfer machine including conveyer, hoist, lift,

    etc., washing machine, and agitators.

    High torque 150%/1Hz and 200%/3Hz (3.7K or less) areachieved with slip compensation function.

    Auto tuningMany kinds of motors can be optimally controlled with

    Mitsubishi original "non-rotation "auto tuning function.

    (R1 constants tuning)

    Brake resistor can be connected

    A brake transistor is built-in to the 0.4K or more.

    Connecting an optional brake resistor increases

    regeneration capability.

    It is useful for deceleration time reduction of a machine

    with a large inertia, such as fan, and operation of lift, etc.

    With spring terminals, the wiring became easier and more secure.

    The design life of the cooling fan has been extended to 10years*1. The life of the fan can be further extended utilizing the

    its ON/OFF control.

    The design life of the capacitors has been extended to 10years by the adoption of a capacitor endures 5000 hours at

    105C surrounding air temperature*1,*2.

    Leading life check function

    Degrees of deterioration of main circuit capacitor, controlcircuit capacitor, and inrush current limit circuit can be

    monitored.

    Trouble can be avoided with the self-diagnostic alarm*4that isoutput when the life span is near.

    Password function

    Registering 4-digit password can limit

    parameter read/write.

    It is effective for parameter setting

    protection.

    EN954-1 Category 3

    IEC60204-1 Stop Category 0

    *: Main circuitterminal is screwterminal.

    Provided by the user (present) FR-D700

    S a f e t y f u n c t i o n

    i s e q u i p p e d

    E m e r g e n c y s t o p

    (example: automobile production line)

    (example: hoist)

    *1: Surrounding air temperature : annual average 40C ( free fromcorrosive gas,

    flammable gas, oil mist, dust and dirt) Since the design life is a calculated value, it is

    nota guaranteed value.

    *2: Outputcurrent : 80% of the inverter rated current

    *3: Excerptsfrom "Periodiccheck ofthe transistorized inverter"ofJEMA (JapanElectrical

    Manufacture'sAssociation)

    *4: If any one of main circuitcapacitor, control circuitcapacitor, inrush currentrestriction

    circuitor cooling fan reaches the output level, an alarmis output. Capacity of the main

    circuitcapacitor can be measured by setting parameter ata stop and turning the

    power fromoff to on. Measuring the capacity enables alarm to be output.

    The cooling fan outputs alarmby using fan speed detection.

    Life indication of critical componentsComponents

    Cooling fan

    Maincircuitsmoothing capacitor

    Printed board smoothing capacitor

    Guideline of the FR-D700 Life

    10 years

    10 years

    10 years

    Guideline of JEMA*3

    2 to 3 years

    5 years

    5 years

    E m e r g e n c y s t o p

    Only one MC is enoughnly one MC is enoughwith safety stop function!ith safety stop function!Only one MC is enoughwith safety stop function! C o s t r e d u c t i o n

    M a i n t e n a n c e o f o n e M C

    I n s t a l l a t i o n s p a c e i s r e d u c e d

    For conventional modelor conventional model...Two MCs were necessarywo MCs were necessaryFor conventional model...Two MCs were necessary H i g h c o s t

    M a i n t e n a n c e o f t w o M C s w a s

    n e c e s s a r y

    I n s t a l l a t i o n s p a c e w a s n e c e s s a r y

    Magneticcontactor(MC)Emergencystop wiring

    (example:industrial washing machine)(example: conveyer)

    (example: automated storage)

    Newfunctions and useful functions from superior models

    support all sorts of applications.

    Regeneration avoidance functionFor a pressing machine and

    fan rotated faster than the set

    speed due to the effect of

    another fan, a trip is less likely

    to occur by automatically

    increasing frequency atregeneration.

    Optimum excitation controlThis control enables the motor

    efficiency to its optimum. More

    energy saving is possible in

    applications with variable load

    torque characteristic such as

    fan and pump.

    Power failure-time deceleration-to-stop functionThe motor can be decelerated to a stop when a power

    failure or undervoltage occur to prevent the motor from

    coasting.

    For fail-safe of machine tool, etc., it is effective to stop

    the motor when a power failure occurs.

    Dancer controlEntering position detection signal of dancer roll to use

    PID control enables tension control by dancer roll.

    Traverse functionTraverse function for wind-up drum of spinning

    machine and wiredrawing machine prevents

    unevenness and deformation at thread winding.

    (example: air-conditioning fan)

    (example: pump)

    (example: pressing machine)

    (example: spindle)

    (example: textile machine) (example: wiredrawing machine)

    (1) (1)

    (3)

    (2)

    (2)

    (3) (4)

    (5)

    Highly reliableSpring structure in terminal contactsection inside prevents contact faultby vibration.

    Maintenance is unnecessaryScrewretightening is unnecessary.

    Easy wiringWiring is completed onlyby inserting wires treatedwith bar terminal (max.diameter 1.5mm)Capable of wiring withouta bar terminal.

    *: Approved safety relay unit

    *

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    3/33

    RoHS Directive compliant

    Complies with UL, cUL,EN (LVD) standards

    Human and environment-friendly inverter in compliant with

    RoHS Directive.Compliance to the EMC Directive of European Norm is easier.

    EMC filter integrated type will be added to the line (to be released).Noise filter option which is compatible with EMC Directive

    (EN61800-3 2nd EnvironmentCategory C3) is available.

    The lineup of three phase 200V/400V class goes to 15K.

    For a use in harsh environment, special unit with board coating is also available. Please contact our sales representative.For the FR-D700 series, North American (NA), EU (EC), and Chinese (CHT) specifications also are supported.

    Parameter unit FR-PU07 (option)

    An optional parameter unit (FR-PU07) can be connected as well.

    Enhanced communication function

    Mitsubishi inverter protocol and Modbus-RTUCommunication speed of RS-485 has been improved

    (communication at 38.4kbps is available)

    "Multi command mode"has been added to Mitsubishi inverter protocol

    (data processing time of the inverter has been reduced to 1/4)

    Supports Modbus RTU

    Easy setting froma personal computer usingthe FR Configurator (option)

    Connecting a personal computer and the inverter via RS-485

    communication enables setting with wizard (interactive)

    function of the FR Configurator (inverter setup software).

    In addition, a parameter setting can be converted from the FR-

    S500 series to the FR-D700 series by "Convert"function.

    "Graph"function displays monitor data in waveform.

    Enclosure surface operation panelFR-PA07 (option)

    Optional enclosure surface operation panel (FR-PA07) can be

    connected. In addition, an operation panel for the FR-E500

    series can be connected.

    RoHSDirectiverequires membernationsto guaranteethatnewelectricaland electronic

    equipmentsold in themarketafterJuly1, 2006donotcontainlead, cadmium, mercury,

    hexavalentchromium, polybrominated biphenyl (PBB) and polybrominated diphenyl ether

    (PBDE) flameretardants.

    markindicating RoHSDirectivecomplianceis printed onthepackage.

    Easily replaceable compact body

    Installation size is the same as that of the FR-S500 series which

    is the smallest model of the Mitsubishi inverter.

    Side by side installation saves space

    Space can be saved by side by side no clearance installation*.

    Easy replacement of cooling fan

    A cooling fan is provided on top

    of the inverter of all capacities

    requiring a cooling fan (1.5K or

    more).

    A cooling fan can be easily

    replaced without disconnecting

    main circuit wires.

    Combed shaped wiring cover

    Since a cover can be fitted

    after wiring, wiring work is

    easily done.

    Theoperationpanelof theinvertercannot beremoved.

    Aparameterunitconnectioncable(FR-CB20 ) is

    separatelynecessary.

    Touseaparameterunitwithbatterypack(FR-PU07BB) outsideJapan,

    ordera FR-PU07BB-L(parameterunittype indicated onthe package

    hasLat theend).

    Aparameterunitconnectioncable(FR-CB20 ) isseparatelynecessary.

    Quick setup with the setting dial

    Setting dial is the feature of Mitsubishi inverters.

    Displayed numbers can be jumped by turning the setting dial quickly, and numberscan be changed one by one by turning it slowly, enabling speedy parameter setting.

    The nonslip setting dial is easier to turn.

    Acceleration/decelerationpattern setting

    Acceleration/decelerationtime setting

    Parameter listdisplay

    Setting wizard function (example: acceleration/deceleration time setting)

    128mm

    FR-D740-0.4K FR-S540E-0.4K

    *: Usetheinverteratthe surrounding airtemperatureof 40C orless.

    *: Thiscatalog explainsbased on theJapanesespecifications.

    Consultoursalesoffice forspecificationsof eachcountry.

    FR-D740 -0.4K-

    Inverter TypeInverter Capacity 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5

    FR-D720- K

    FR-D740- K

    FR-D720S- K

    FR-D710W- K

    Three phase

    200V

    Three phase

    400V

    Single phase

    200V*

    Single phase

    100V*

    Enclosed structure (IP20)

    Totally-enclosed structure (IP40)

    Enclosed structure (IP20)

    Totally-enclosed structure (IP40)

    Enclosed structure (IP20)

    Enclosed structure (IP20)

    11 15

    *: Outputof the single-phase 200V and single-phase 100Vinput models is three-phase 200V. :Available models :Models to be released :Notavailable

    PowerSupply

    Symbol

    1

    2

    4

    Voltage

    100Vclass

    200Vclass

    400Vclass

    Symbol

    None

    C

    Protective Structure

    Enclosed-type structure IP20

    Totally enclosed structure IP40

    Symbol

    0.1Kto 15K

    Inverter Capacity

    Indicate capacity

    "kW".

    Symbol

    None

    S

    W

    Number of Power Phases

    Three-phase input

    Single-phase input

    Single-phase input

    (double voltage output)

    (1) (1) (2)

    (1)

    Filter pack FR-BFP2 (option)

    Power factor improving DC reactor, zero phase reactor, and

    capacitative filter (radio noise filter), are frequently-used units

    for an air conditioning application. The filter pack combines

    those three units are available as an option.

    (2)

    (4)

    (1) (2)

    (2) (3)

    EMC Directive compliant noise filter(3)

    (4)

    (5)

    4

    Features

    Options

    Standard

    Specifications

    Operationpa

    nel

    Parameteru

    nit

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warranty

    International

    FACent

    er

    Setting such as directinputmethod with a numerickeypad, operation status indication, and helpfunction are usable.

    Eight languages can be displayed.

    Parameter setting values of maximum of threeinverters can be stored.

    A battery pack type (FR-PU07BB(-L)) allowsparameter setting and parameter copy without

    powering on the inverter. (available soon)

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    4/33

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    5/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    6

    z Single-phase 200V power supply

    z Single-phase 100V power supply

    1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.

    2 The rated output capacity indicated assumes that the output voltage is 230V.

    3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for

    the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or

    power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection

    level and load of 100% or more may not be available.

    4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,

    the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply.

    5 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).

    6 For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.

    7 In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a three-

    phase input model. Use the motor with less load so that the output current is within the rated motor current range.

    Model FR-D720S-K 0.1 0.2 0.4 0.75 1.5 2.2

    Model FR-D720S--NA 008 014 025 042 070 100

    Model FR-D720S--EC 008 014 025 042 070 100

    Model FR-D720S-K-CHT 0.1 0.2 0.4 0.75 1.5 2.2

    Applicable motor capacity (kW)1 0.1 0.2 0.4 0.75 1.5 2.2

    Output

    Rated capacity (kVA)2 0.3 0.6 1.0 1.7 2.8 4.0

    Rated current (A) 0.8 1.4 2.5 4.2 7.0 10.0

    Overload current rating3 150% 60s, 200% 0.5s (inverse-time characteristics)

    Voltage4 Three-phase 200 to 240V

    Powersupply Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz

    Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz

    Permissible frequency fluctuation 5%

    Power supply capacity (kVA)5 0.5 0.9 1.5 2.3 4.0 5.2

    Protective structure (JEM1030) Enclosed type (IP20).

    Cooling system Self-cooling Forced air cooling

    Approximate mass (kg) 0.5 0.5 0.9 1.1 1.5 2.0

    Model FR-D710W-K 0.1 0.2 0.4 0.75

    Model FR-D710W--NA 008 014 025 042

    Applicable motor capacity (kW)1 0.1 0.2 0.4 0.75

    Output

    Rated capacity (kVA)2 0.3 0.6 1.0 1.7

    Rated current (A) 0.8 1.4 2.5 4.2

    Overload current rating3150% 60s, 200% 0.5s

    (inverse-time characteristics)

    Voltage Three-phase 200 to 230V6, 7

    Powersup

    ply Rated input AC voltage/frequency Single-phase 100 to 115V 50Hz/60Hz

    Permissible AC voltage fluctuation 90 to 132V 50Hz/60HzPermissible frequency fluctuation 5%

    Power supply capacity (kVA)5 0.5 0.9 1.5 2.5

    Protective structure (JEM1030) Enclosed type (IP20).

    Cooling system Self-cooling

    Approximate mass (kg) 0.6 0.7 0.9 1.4

    2

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    6/33

    7

    Common specifications

    Controlspecifications

    Control methodSoft-PWM control/high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control,and Optimum excitation control are available)

    Output frequency range 0.2 to 400Hz

    Frequency setting

    resolution

    Analog input0.06Hz/60Hz (terminal2, 4: 0 to 10V/10bit)0.12Hz/60Hz (terminal2, 4: 0 to 5V/9bit)

    0.06Hz/60Hz (terminal4: 0 to 20mA/10bit)Digital input 0.01Hz

    Frequencyaccuracy

    Analog input Within 1% of the max. output frequency (25C 10C)

    Digital input Within 0.01% of the set output frequency

    Voltage/frequency characteristics Base frequency can be set from 0 to 400Hz. Constant-torque/variable torque pattern can be selected

    Starting torque 150% or more (at 1Hz)...when General-purpose magnetic flux vector control and slip compensation is set

    Torque boost Manual torque boost

    Acceleration/deceleration time setting0.1 to 3600s (acceleration and deceleration can be set individually),Linear and S-pattern acceleration/deceleration modes are available.

    Braking torqueRegenerative1

    0.1K, 0.2K ... 150%,0.4K, 0.75K ... 100%,1.5K ... 50%,2.2K or more ... 20%

    DC injection brake Operation frequency (0 to 120Hz), operation time (0 to 10s), and operation voltage (0 to 30%) can be changed

    Stall prevention operation level Operation current level (0 to 200%), and whether to use the function or not can be selected

    Operationspecifications

    Frequency settingsignal

    Analog inputTwo terminalsTerminal 2: 0 to 10V and 0 to 5V are available

    Terminal 4: 0 to 10V, 0 to 5V, and 4 to 20mA are available

    Digital input Digital input and frequency setting increments can be entered from operation panel or parameter unit.

    Start signal Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.

    Input signal (five terminals)

    Following signals can be assigned toPr. 178 to Pr.182 (input terminal function selection): multi-speed selection, remotesetting, second function selection, terminal 4 input selection, JOG operation selection, PID control valid terminal,external thermal input, PU-External operation switchover, V/F switchover, output stop, start self-holding selection,forward rotation, reverse rotation command, inverter reset, PU-NET operation switchover, External-NET operationswitchover, command source switchover, inverter operation enable signal, and PU operation external interlock.

    Operational functions

    Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, automaticrestart after instantaneous power failure operation, forward/reverse rotation prevention, remote setting, secondfunction, multi-speed operation, regeneration avoidance, slip compensation, operation mode selection, offline autotuning function, PID control, computer link operation (RS-485), Optimum excitation control, power failure stop, speedsmoothing control, Modbus-RTU

    Output signalOpen collector output (one terminal)Relay output (one terminal)

    Following signals can be assigned toPr.190 and Pr.192 (output terminal function selection): inverter operation, up-to-frequency, overload alarm, output frequency detection, regenerative brake prealarm, electronic thermal relay functionprealarm, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit,PID forward/reverse rotation output, fan alarm2, heatsink overheat pre-alarm, deceleration at an instantaneous

    power failure, PID control activated, PID output interruption, during retry, life alarm, current average value monitor,remote output, alarm output, fault output, fault output 3, and maintenance timer alarm.Operating status

    For meterPulse train output(MAX 2.4kHz: one terminal)

    Following signals can be assigned toPr.54 FM terminal function selection: output frequency, output current (steady),output voltage, frequency setting, converter output voltage, regenerative brake duty, electronic thermal relay functionload factor, output current peak value, converter output voltage peak value, reference voltage output, motor loadfactor, PID set point, PID measured value, output power, PID deviation, motor thermal load factor, and inverterthermal load factor.Pulse train output (1440 pulses/s/full scale)

    IndicationOperation panel

    Parameter unit(FR-PU07)

    Operating status

    Following operating status can be displayed: output frequency, output current (steady), output voltage, frequencysetting, cumulative energization time, actual operation time, converter output voltage, regenerative brake duty,electronic thermal relay function load factor, output current peak value, converter output voltage peak value, motorload factor, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, output power, cumulativepower, motor thermal load factor, inverter thermal load factor, and PTC thermistor resistance.

    Fault definitionFault definition is displayed when a fault occurs. Past 8 fault definitions (output voltage/current/frequency/cumulativeenergization time right before the fault occurs) are stored.

    Interactiveguidance

    Function (help) for operation guide3

    Protective/warningfunction

    Protectivefunction

    Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage

    during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermaloperation, motor protection thermal operation, heatsink overheat, input phase loss45, output side earth (ground)fault overcurrent at start4, output phase loss, external thermal relay operation4, PTC thermistor operation4,parameter error, PU disconnection, retry count excess4, CPU fault, brake transistor alarm, inrush resistanceoverheat, analog input error, stall prevention operation, output current detection value exceeded4, safety circuit fault

    Warningfunction

    Fan alarm2, overcurrent stall prevention, overvoltage stall prevention, PU stop, parameter write error, regenerativebrake prealarm4, electronic thermal relay function prealarm, maintenance output4, undervoltage, operation panellock, password locked, inverter reset, safety stop

    Environment Surrounding air temperature -10C to +50C maximum (non-freezing) (-10C to +40C for totally-enclosed structure feature)6

    Ambient humidity 90%RH or less (non-condensing)

    Storage temperature7 -20C to +65C

    Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)

    Altitude/vibration Maximum 1000m above sea level, 5.9m/s2 or less at 10 to 55Hz (directions of X, Y, Z axes)

    1 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in theshortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the averagedeceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. Abrake unit (FR-BU2) may also be used.

    2 As the 0.75K or less are not provided with the cooling fan, this alarm does not function.3 This operation guide is only available with option parameter unit (FR-PU07).4 This protective function does not function in the initial status.5 This protective function is available with the three-phase power input specification model only.6 When using the inverters at the surrounding air temperature of 40C or less, the inverters can be installed closely attached (0cm clearance).7 Temperatures applicable for a short time, e.g. in transit.

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    7/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    8

    zFR-D720-0.1K to 0.75K

    zFR-D720S-0.1K to 0.75K

    zFR-D710W-0.1K to 0.4K

    zFR-D720-1.5K to 3.7K

    zFR-D740-0.4K to 3.7K

    zFR-D720S-1.5KzFR-D710W-0.75K

    (Unit: mm)

    (Unit: mm)

    1-5 hole

    5

    68

    56 5

    118

    5

    128

    Rating

    plate

    D

    4

    D1

    Inverter Type D D1FR-D720-0.1K, 0.2KFR-D720S-0.1K, 0.2KFR-D710W-0.1K

    80.5 10

    FR-D710W-0.2K 110.5 10

    FR-D720-0.4K 112.5 42

    FR-D720-0.75K 132.5 62

    FR-D720S-0.4KFR-D710W-0.4K

    142.5 42

    FR-D720S-0.75K 162.5 62

    Rating

    plate

    2-5 hole*FAN

    5

    W1

    W

    5

    5

    128

    118

    5

    D1

    D

    FR-D740-0.4K, 0.75K, FR-D710W-0.75K are not provided with the cooling fan.

    Inverter Type W W1 D D1

    FR-D720-1.5K, 2.2KFR-D740-1.5K

    108 96

    135.5 60

    FR-D740-0.4K, 0.75K 129.5 54

    FR-D740-2.2KFR-D720S-1.5K

    155.560

    FR-D740-3.7K 165.5

    FR-D710W-0.75K 149.5 54FR-D720-3.7K 170 158 142.5 66.5

    Outline Dimension Drawings

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    8/33

    9

    zFR-D720S-2.2K

    zFR-D720-5.5K, 7.5K

    zFR-D740-5.5K, 7.5K

    (Unit: mm)

    (Unit: mm)

    2-5 hole

    Rating

    plate

    128

    140

    5

    138

    6

    6

    150

    FAN

    5

    60

    145

    2-5 hole

    Rating

    plate

    6

    138

    6

    150

    208

    5

    220

    10

    68

    155

    FAN

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    9/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    10

    zParameter unit (option) (FR-PU07)

    zParameter unit with battery pack (option) (FR-PU07BB (-L))

    zEnclosure surface operation panel (option) (FR-PA07)

    67

    51

    40

    56.8

    57.8

    26.5

    4-R1

    26.5

    40

    4-4 hole

    (Effective depth of the

    installation screw hole 5.0)

    M3 screw *2

    Air-bleedinghole

    80.3

    (14.2)

    2.5

    50

    (11.45)

    25.05

    135

    83

    *1

    *1 *1

    *1

    1 When installing the FR-PU07 on the enclosure, etc., remove screws or fix the screws to the FR-PU07 with M3 nuts.2 Select the installation screw whose length will not exceed the effective depth of the installation screw hole. (Unit: mm)

    46.7

    135

    83

    186

    8.2 46.7

    44.7

    (Unit: mm)

    68

    59

    22

    22

    2-M3 screw

    45

    24

    15.5

    36

    20

    11

    (Unit: mm)

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    10/33

    11

    Terminal Connection Diagram

    Notey To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also

    separate the main circuit wire of the input side and the output side.

    y After wiring, wire offcuts must not be left in the inverter.

    Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holesin an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.

    y The output of the single-phase power input specification is three-phase 200V.

    Earth(Ground)

    Motor

    IM

    Earth (Ground)

    Three-phase

    AC power

    supply

    MCCB MC

    R/L1

    P1 P/+

    PR N/-

    S/L2

    T/L3

    U

    V

    W

    Earth

    (Ground)

    *8 Brake resistor (FR-ABR, MRS type, MYS

    type)Install a thermal relay to prevent an

    overheat and burnout of the brake resistor.

    (The brake resistor can not be connected

    to the 0.1K and 0.2K.)

    *9 It is not necessary when

    calibrating the indicator

    from the operation panel.

    Forwardrotation start

    Reverserotation start

    Middlespeed

    Highspeed

    Lowspeed

    Control input signals (No voltage input allowed)

    24VDC power supply(Common for external power supply transistor)

    Contact input common

    STR

    STF

    RH

    RM

    RL

    SD

    PC

    Relay output

    Running

    Open collector output

    Open collector output common

    Sink/source common

    RUN

    SE

    A

    B

    C

    Frequency setting signals (Analog)

    2 0 to 5VDC

    10(+5V)

    2

    3

    1

    4 4 to 20mADC

    Frequency

    setting

    potentiometer1/2W1k

    Terminal 4input(Currentinput)

    (+)(-)

    5(Analog common)

    *4 It is recommended touse 2W1k when thefrequency setting signalis changed frequently.

    *4

    *2 When using terminals PC-

    SD as a 24VDC power

    supply, take care not to

    short across terminals

    PC and SD.

    PU

    connector

    *1. DC reactor (FR-HEL)When connecting a DC reactor, remove the

    jumper across P1 and P/+

    Single-phase 100V power input model is not

    compatible with DC reactor.Control circuit terminal

    Main circuit terminal

    Sink logic

    Jumper

    *1

    *8

    *7

    *6

    *2

    *3

    *5

    Terminal functions vary

    with the input terminal

    assignment (Pr. 178 to

    Pr. 182)

    Multi-speed selection

    Terminal functions vary by

    Pr. 190 RUN terminal function

    selection

    Terminal functions varybyPr. 192A,B,C terminal

    function selection

    SINK

    SOURCE

    V I

    *5

    0 to 5VDC

    (0 to 10VDC)

    0 to 10VDC

    *5 Terminal input specifications can be changed by analoginput specifications switchover (Pr. 267). Set thevoltage/current input switch in the "V" position to selectvoltage input (0 to 5V/0 to10V) and " I" (initial value) toselect current input (4 to 20mA).To use terminal 4 (initial setting is current input), set "4"

    in any ofPr.178 to Pr.182 (input terminal functionselection) to assign the function, and turn ON AU signal.

    Voltage/current

    input switch

    Main circuit

    Control circuit

    R

    Relay output

    (Fault output)

    Brake unit(Option)

    FM

    SD

    Indicator(Frequency meter, etc.)+ -

    Moving-coil type

    1mA full-scale

    Calibration resistor

    *10 Common terminal of

    terminal SO is terminal SC.

    (Connected to terminal SD

    inside of the inverter.)

    *9

    *3 Terminal input specificationscan be changed by analoginput specificationsswitchover (Pr. 73).Terminal 10 and terminal 2are used as PTC inputterminal (Pr. 561).

    Safe stop input (Line 1)

    Safe stop input (Line 2)

    Common terminal

    Safety stop signalS1

    S2

    SC

    Safety monitor output *10SO

    Shorting

    wire

    Single-phase

    AC powersupply

    MCCB MC

    R/L1

    S/L2

    Single-phase power input *7 A brake transistor is not built-in to the0.1K and 0.2K.

    *6 Terminal P1 is not available for single-

    phase 100V power input model.

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    11/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    12

    Terminal Specification Explanation

    TypeTerminalSymbol

    Terminal Name Description

    Main

    circuit

    R/L1, S/L2,T/L3

    AC power inputConnect to the commercial power supply. Keep these terminals open when using the high powerfactor converter (FR-HC) or power regeneration common converter (FR-CV). When using single-phase power input, terminals are R/L1 and S/L2.

    U, V, W Inverter output Connect a three-phase squirrel-cage motor.

    P/+, PR Brake resistor connectionConnect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and PR.(The brake resistor can not be connected to the 0.1K and 0.2K.)

    P/+, N/- Brake unit connectionConnect the brake unit (FR-BU2), power regeneration common converter (FR-CV) or high power

    factor converter (FR-HC).

    P/+, P1 DC reactor connectionRemove the jumper across terminals P/+-P1 and connect a DC reactor.Single-phase 100V power input model is not compatible with DC reactor. Terminal P1 is not available for single-phase 100V power input model.

    Earth (Ground) For earthing (grounding) the inverter chassis. Must be earthed (grounded).

    Controlcircuit/input

    signal

    Contactinput

    STF Forward rotation start Turn on the STF signal to start forward rotation and turn it off to stop.When the STF and STR signalsare turned on simultaneously,the stop command is given.STR Reverse rotation start Turn on the STR signal to start reverse rotation and turn it off to stop.

    RH, RM, RL Multi-speed selection Multi-speed can be selected according to the combination of RH, RM and RL signals.

    SD

    Contact input common(sink) (initial setting)

    Common terminal for contact input terminal (sink logic) and terminal FM.

    External transistor common(source)

    When connecting the transistor output (open collector output), such as a programmable controller,when source logic is selected, connect the external power supply common for transistor output to thisterminal to prevent a malfunction caused by undesirable currents.

    24VDC power supply commonCommon output terminal for 24VDC 0.1A power supply (PC terminal).Isolated from terminals 5 and SE.

    PC

    External transistor common(sink) (initial setting)

    When connecting the transistor output (open collector output), such as a programmable controller,

    when sink logic is selected, connect the external power supply common for transistor output to thisterminal to prevent a malfunction caused by undesirable currents.

    Contact input common (source) Common terminal for contact input terminal (source logic).24VDC power supply Can be used as 24VDC 0.1A power supply.

    Frequencysetting

    10Frequency setting power

    supplyUsed as power supply when connecting potentiometer for frequency setting(speed setting) from outside of the inverter.

    5VDCpermissible loadcurrent 10mA

    2 Frequency setting (voltage)

    Inputting 0 to 5VDC (or 0 to 10V) provides the maximum outputfrequency at 5V (10V) and makes input and output proportional.UsePr. 73 to switch between input 0 to 5VDC (initial setting) and 0to 10VDC input.

    Input resistance 10k 1kPermissible maximum voltage20VDC

    4 Frequency setting (current)

    Inputting 0 to 20mADC (or 0 to 5V / 0 to 10V) provides themaximum output frequency at 20mA makes input and outputproportional. This input signal is valid only when the AU signal ison (terminal 2 input is invalid). UsePr. 267to switch from amonginput 4 to 20mA (initial setting), 0 to 5VDC and 0 to 10VDC. Set thevoltage/current input switch in the "V" position to select voltageinput (0 to 5V/0 to 10V).

    Voltage input:Input resistance 10k 1kPermissible maximum voltage20VDCCurrent input:Input resistance 233 5

    Maximum permissible current 30mA.

    5 Frequency setting common Common terminal for the frequency setting signals (terminals 2 or 4). Do not earth (ground).

    PTC

    thermistor

    102

    PTC thermistor inputFor connecting PTC thermistor output.When PTC thermistor protection is valid (Pr. 561 "9999"), terminal2 is not available for frequency setting.

    Adaptive PTC thermistorresistance:500 to 30k

    Controlcircuit/outputsignal

    Relay

    A, B, C Relay output (fault output)1 changeover contact output indicates that the inverter fault occurs.Fault: discontinuity across B-C (continuity across A-C), Normal: continuity across B-C (discontinuityacross A-C) Contact capacity 230VAC 0.3A (power factor = 0.4) 30VDC 0.3A

    Opencollector

    RUN Inverter running

    Switched low when the inverter output frequency is equal to orhigher than the starting frequency (initial value 0.5Hz). Switchedhigh during stop or DC injection brake operation.(Low is when the open collector output transistor is ON (conducts).High is when the transistor is OFF (does not conduct).)

    Permissible load 24VDC(Maximum 27VDC) 0.1A(a voltage drop is 3.4V maximumwhen the signal is on)

    SE Open collector output common Common terminal of terminal RUN and FU.

    Pulse

    FM For meterSelect one e.g. output frequency from monitor items. (Not outputduring inverter reset.)The output signal is proportional to themagnitude of the corresponding monitoring item.

    Permissible load current 1mA1440 pulses/s at 60Hz

    Communication

    PU connector

    With the PU connector, RS-485 communication can be made. Conforming standard: EIA-485 (RS-485) Transmission format: Multi-drop link Communication speed: 4800 to 38400bps Overall extension: 500m

    Safetystopsignal S1 Safe stop input (Line 1) S1/S2 are safe stop signals for use with in conjunction with an approved external safety unit. Both S1/

    S2 must be used in dual channel form. Inverter output is shutoff depending on shorting/openingbetween S1 and SC, S2 and SC.Remove the shorting wire before using between S1, S2 and SC terminals.

    S2 Safe stop input (Line 2)

    SOSafety monitor output(open collector output)

    This is a status signal for the safety related input signals.Low indicates 'safe state' and high is 'drive enable or fault detected'. If high is indicated when both S1 and S2 are

    open, refer to Safety stop function instruction manual (BCN-A211508-000) for diagnostics and repair action.

    (Low is when the open collector output transistor is ON (conducts). High is when the transistor is OFF(does not conduct).)

    SC Output shutoff terminal common Common terminal for terminals S1, S2 and SO. Connected to terminal SD inside of the inverter.

    Notey SetPr. 267and a voltage/current input switch correctly, then input an analog signal in accordance with the setting. Applying

    a voltage with voltage/current input switch in "I" position (current input is selected) or a current with switch in "V" position(voltage input is selected) could cause component damage of the inverter or analog circuit of output devices.

    y The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.y indicates that terminal functions can be selected usingPr. 178 to Pr. 182, Pr. 190, Pr. 192 (I/O terminal function selection).y Terminal names and terminal functions are those of the factory set.

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    12/33

    13

    Explanation of the Operation Panel

    The operation panel cannot be removed from the inverter.

    Operation mode indication

    PU: Lit to indicate PU operation mode.

    EXT: Lit to indicate External operation mode.

    (Lit at power-ON at initial setting.)

    NET: Lit to indicate Network operation mode.

    PU, EXT: Lit to indicate External/PU

    combined operation mode 1, 2.

    These turn OFF when command source is

    not on operation panel.

    Unit indication

    Hz: Lit to indicate frequency.

    (Flickers when the set frequency

    monitor is displayed.)

    A: Lit to indicate current.

    (Both "Hz" and "A" turn off when other

    than the above is displayed.)

    Monitor (4-digit LED)

    Shows the frequency, parameter number,

    etc.

    Setting dial

    (Setting dial: Mitsubishi inverter dial)

    Used to change the frequency setting

    and parameter values.

    Press to display the following.

    y Displays the set frequency in the

    monitor mode

    y Present set value is displayed during

    calibration

    y Displays the order in the faults history

    mode

    Mode switchover

    Used to change each setting mode.

    Pressing simultaneously changes

    the operation mode.

    Pressing for a while (2s) can lock

    operation.

    Determination of each setting

    If pressed during operation, monitor

    changes as below;

    Running frequency

    Output current

    Output voltage

    Operating status display

    Lit or flicker during inverter operation.

    On: Indicates that forward rotation

    operation is being performed.

    Slow flickering (1.4s cycle):

    Reverse rotation operation

    Fast flickering (0.2s cycle):

    When was pressed or the

    start command was given, but the

    operation can not be made.

    yWhen the frequency command is less

    than the starting frequency.

    yWhen the MRS signal is input.

    Parameter setting mode indication

    Lit to indicate parameter setting mode.

    Monitor indication

    Lit to indicate monitoring mode.

    Stop operation

    Used to stop Run command.

    Fault can be reset when protective

    function is activated (fault).

    Operation mode switchover

    Used to switch between the PU and

    External operation mode.

    When using the External operation mode

    (operation using a separately connected

    frequency setting potentiometer and start

    signal), press this key to light up the EXT

    indication.

    (Press simultaneously (0.5s) or

    changePr. 79setting to change to combined

    mode .)

    PU: PU operation mode

    EXT: External operation mode

    Cancels PU stop also.

    Start command

    The rotation direction can be selected by

    settingPr. 40.

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    13/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    14

    Basic operation of the operation panel

    STOP

    Operation mode switchover

    Paramete

    rsetting

    Faultshistory

    Monitor/frequencysetting

    At powering ON (External operation mode)

    PU operation mode

    (output frequency monitor)

    Parameter setting mode

    PU Jog operation mode

    Output current monitor Output voltage monitor

    Display the

    present setting

    Value change

    Value change

    Parameter write is completed!!

    Parameter and a setting value

    flicker alternately.

    Parameter clear All parameter

    clear

    Faults history clear

    Initial value

    change list

    (Example)

    (Example)

    Frequency setting has been

    written and completed!!

    and frequency flicker.

    [Operation for displaying faults history]

    Past eight faults can be displayed.

    (The latest fault is ended by ".".)

    When no fault history exists, is displayed.

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    14/33

    15

    Explanations of Parameter unit

    y The parameter unit is a convenient tool for inverter setting

    such as direct input method with a numeric keypad,

    operation status indication, and help function.

    y Eight languages can be displayed.

    y Parameter setting values of maximum of three inverters can

    be stored.

    y With the FR-PU07BB(-L), parameter check and setting

    change can be made without connecting a power supply to the

    inverter. Use AA nickel hydride batteries, AA alkali batteries, or

    AC adapter separately available as power supply.

    y Since the shape is specially designed for portable use, it is

    easy to work with the FR-PU07BB(-L) in hand. The parameter unit connection cable FR-CB20 is required for connecting to

    the inverter. (Parameter unit connection cable FR-CB203(3m) is enclosed

    with FR-PU07BB(-L).)

    To use a parameter unit with battery pack (FR-PU07BB) outside Japan, order

    a "FR-PU07BB-L" (parameter unit type indicated on the package has L at the

    end). Since enclosed batteries may conflict with laws in countries to be used

    (new EU Directive on batteries and accumulators, etc.), batteries are not

    enclosed with an FR-PU07BB-L.

    z Main functions

    Available function differs by the inverter. Please refer to the instruction manual of the inverter and the parameter unit.

    Parameter unit (FR-PU07), parameter unit with battery pack (FR-PU07BB(-L)(available soon))

    POWER lampLit when the power turns on.

    MonitorLiquid crystal display(16 characters 4 lines with backlight)Interactive parameter settingTrouble shooting guidanceMonitor (frequency, current, power, etc.)

    ALARM lampLit to indicate an inverter alarm

    occurrence.

    FR-PU07

    FR-PU07BB(-L)

    Operation keys(Refer to the table on the right)

    Key Description

    Use for parameter setting

    Press to choose the parameter setting mode.

    First priority monitor is displayed.

    In the initial setting, the output frequency is displayed.

    Operation cancel key

    Used to display the function menu.

    A variety of functions can be used on the function menu.

    Used to shift to the next item in the setting or monitoring mode.

    to Used to enter a frequency, parameter number or set value.

    Inverter operates in the external operation mode.

    Used to select the PU operation mode to display the frequency

    setting screen.

    y Used to keep on increasing or decreasing the running

    frequency. Hold down to vary the frequency.

    y Press either of these keys on the parameter setting mode

    screen to change the parameter setting value sequentially.

    y On the selecting screen, these keys are used to move the cursor.

    y Hold down and press either of these keys to advance

    or return the display screen one page.

    Forward rotation command key.

    Reverse rotation command key.

    y Stop command key.

    y Used to reset the inverter when an alarm occurs.

    y Used to write a set value in the setting mode.

    y Used as a clear key in the all parameter clear or alarm history

    clear mode.

    y Used as a decimal point when entering numerical value.

    y Used as a parameter number read key in the setting mode.

    y Used as an item select key on the menu screen such as

    parameter list or monitoring list.

    y Used as an alarm definition display key in the alarm history

    display mode.

    y Used as a command voltage read key in the calibration mode.

    Function Description

    Monitor 6 types of monitors appear by simply pressing .

    Frequency setting

    For PU operation mode and External/PU combined operation mode (Pr.79 = "3"), frequency setting is available.

    Settings is performed by the direct setting, which sets frequency directly by to , and the step setting, which

    sets frequency continuously by .

    Parameter SettingReading parameter and changing setting values are easily done. To change the setting value of an parameter, specify

    the parameter number, or select a parameter from the functional parameter list.

    Batch copy

    FR-PU07 (PU07BB) reads parameter settings of an inverter, and stores three different parameter settings.

    FR-PU07 (PU07BB) can also copy the stored parameter setting to another inverter of the same series, or verify its

    stored parameter setting against the parameter setting stored in an inverter.

    OperationSwitching between External operation mode [EXT] and PU operation mode [PU] is easy.

    Start/stop is enabled during PU operation mode and External/PU operation mode (Pr.79 = "3").

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    15/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    16

    Parameter List

    For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the

    necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made

    from the operation panel. For details of parameters, refer to the instruction manual.

    This catalog explains based on the Japanese specifications.

    POINT

    Only simple mode parameters are displayed by the initial setting ofPr. 160 Extended function display selection. SetPr.

    160 Extended function display selection as required.

    Pr. 160 Description

    9999

    (initial value)Parameters classified as simple mode can be displayed.

    0Both the parameters classified as simple mode and the parameters

    classified as extended mode can be displayed.

    Parameter

    NumberName Unit

    Initial

    ValueRange Application

    0 Torque boost 0.1% 6%/4%/3% 0 to 30%

    Set when you want to increase a

    starting torque under V/F control,

    or when the motor with a load will

    not rotate, resulting in an alarm

    [OL] and a trip [OC1].

    Initial values differ according to the

    inverter capacity. (0.75K or less/

    1.5K to 3.7K/5.5K, 7.5K)

    1 Maximum frequency 0.01Hz 120Hz 0 to 120HzSet when the maximum output

    frequency need to be limited.

    2 Minimum frequency 0.01Hz 0Hz 0 to 120HzSet when the minimum output

    frequency need to be limited.

    3 Base frequency 0.01Hz 60Hz 0 to 400Hz

    Set when the rated motor

    frequency is 50Hz.Check the motor rating plate.

    4Multi-speed setting

    (high speed)0.01Hz 60Hz 0 to 400Hz

    Set when changing the preset

    speed in the parameter with a

    terminal.

    5Multi-speed setting

    (middle speed)0.01Hz 30Hz 0 to 400Hz

    6Multi-speed setting (low

    speed)0.01Hz 10Hz 0 to 400Hz

    7 Acceleration time 0.1s 5s/10s 0 to 3600sAcceleration/deceleration time can

    be set.

    Initial values differ according to the

    inverter capacity. (3.7K or less/

    5.5K, 7.5K)8 Deceleration time 0.1s 5s/10s 0 to 3600s

    9Electronic thermal O/L

    relay0.01A

    Ratedinverter

    current

    0 to 500AThe inverter protects the motorfrom overheat.

    Set the rated motor current.

    79Operation mode

    selection1 0

    0, 1, 2, 3, 4, 6,

    7

    Select the start command location

    and frequency setting location.

    125Terminal 2 frequency

    setting gain frequency0.01Hz 60Hz 0 to 400Hz

    Frequency for the maximum value

    of the potentiometer (5V initial

    value) can be changed.

    126Terminal 4 frequency

    setting gain frequency0.01Hz 60Hz 0 to 400Hz

    Frequency for the maximum

    current input (20mA initial value)

    can be changed.

    160Extended function

    display selection1 9999 0, 9999

    Parameter which can be read from

    the operation panel and parameter

    unit can be restricted.

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    16/33

    17

    z Extended mode parameterREMARKS

    y indicates simple mode parameters.

    y The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77

    Parameter write selection.

    Func-tion

    Parameter Name Setting Range MinimumSettingIncrements

    InitialValue

    CustomerSetting

    Basicfunctions

    0 Torque boost 0 to 30% 0.1% 6/4/3% 1

    1 Maximum frequency 0 to 120Hz 0.01Hz 120Hz

    2 Minimum frequency 0 to 120Hz 0.01Hz 0Hz

    3 Base frequency 0 to 400Hz 0.01Hz 60Hz

    4 Multi-speed setting (high speed) 0 to 400Hz 0.01Hz 60Hz

    5 Multi-speed setting (middle speed) 0 to 400Hz 0.01Hz 30Hz

    6 Multi-speed setting (low speed) 0 to 400Hz 0.01Hz 10Hz

    7 Acceleration time 0 to 3600s 0.1s 5/10s2

    8 Deceleration time 0 to 3600s 0.1s 5/10s2

    9 Electronic thermal O/L relay 0 to 500A 0.01ARated

    inverter

    current

    DCinjection

    brake

    10 DC injection brake operation frequency 0 to 120Hz 0.01Hz 3Hz

    11 DC injection brake operation time 0 to 10s 0.1s 0.5s

    12 DC injection brake operation voltage 0 to 30% 0.1% 6/4%3

    13 Starting frequency 0 to 60Hz 0.01Hz 0.5Hz

    14 Load pattern selection 0 to 3 1 0

    JOG

    operation 15 Jog frequency 0 to 400Hz 0.01Hz 5Hz

    16 Jog acceleration/deceleration time 0 to 3600s 0.1s 0.5s

    17 MRS input selection 0, 2, 4 1 0

    18 High speed maximum frequency 120 to 400Hz 0.01Hz 120Hz 19 Base frequency voltage 0 to 1000V, 8888, 9999 0.1V 9999

    Acceleration/

    decelerationtime

    20Acceleration/deceleration referencefrequency

    1 to 400Hz 0.01Hz 60Hz

    Stall

    prevention

    22 Stall prevention operation level 0 to 200% 0.1% 150%

    23Stall prevention operation level

    compensation factor at double speed0 to 200%, 9999 0.1% 9999

    Multi-speed

    setting

    24 Multi-speed setting (speed 4) 0 to 400Hz, 9999 0.01Hz 9999

    25 Multi-speed setting (speed 5) 0 to 400Hz, 9999 0.01Hz 999926 Multi-speed setting (speed 6) 0 to 400Hz, 9999 0.01Hz 9999

    27 Multi-speed setting (speed 7) 0 to 400Hz, 9999 0.01Hz 9999

    29Acceleration/deceleration pattern

    selection0, 1, 2 1 0

    30 Regenerative function selection 0, 1, 2 1 0

    Frequencyjump 31 Frequency jump 1A 0 to 400Hz, 9999 0.01Hz 9999

    32 Frequency jump 1B 0 to 400Hz, 9999 0.01Hz 9999

    33 Frequency jump 2A 0 to 400Hz, 9999 0.01Hz 9999

    34 Frequency jump 2B 0 to 400Hz, 9999 0.01Hz 9999

    35 Frequency jump 3A 0 to 400Hz, 9999 0.01Hz 9999

    36 Frequency jump 3B 0 to 400Hz, 9999 0.01Hz 9999

    37 Speed display 0, 0.01 to 9998 0.001 0

    40 RUN key rotation direction selection 0, 1 1 0

    Frequency

    detection

    41 Up-to-frequency sensitivity 0 to 100% 0.1% 10%

    42 Output frequency detection 0 to 400Hz 0.01Hz 6Hz

    43Output frequency detection for reverse

    rotation0 to 400Hz, 9999 0.01Hz 9999

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    17/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    18

    Second

    functions

    44 Second acceleration/deceleration time 0 to 3600s 0.1s 5/10s2

    45 Second deceleration time 0 to 3600s, 9999 0.1s 9999

    46 Second torque boost 0 to 30%, 9999 0.1% 9999

    47 Second V/F (base frequency) 0 to 400Hz, 9999 0.01Hz 9999

    48Second stall prevention operation

    current0 to 200%, 9999 0.1% 9999

    51 Second electronic thermal O/L relay 0 to 500A, 9999 0.01A 9999

    Monitorfunctions 52 DU/PU main display data selection

    0, 5, 8 to 12, 14, 20,

    23 to 25, 52 to 55, 61,

    62, 64, 100

    1 0

    54 FM terminal function selection1 to 3, 5, 8 to 12, 14, 21,

    24, 52, 53, 61, 621 1

    55 Frequency monitoring reference 0 to 400Hz 0.01Hz 60Hz

    56 Current monitoring reference 0 to 500A 0.01A

    Rated

    inverter

    current

    Automatic

    restart

    functions 57 Restart coasting time 0, 0.1 to 5s, 9999 0.1s 9999

    58 Restart cushion time 0 to 60s 0.1s 1s

    59 Remote function selection 0, 1, 2, 3 1 0

    60 Energy saving control selection 0, 9 1 0

    65 Retry selection 0 to 5 1 0

    66Stall prevention operation reduction

    starting frequency0 to 400Hz 0.01Hz 60Hz

    Retry

    67 Number of retries at fault occurrence 0 to 10, 101 to 110 1 0

    68 Retry waiting time 0.1 to 600s 0.1s 1s

    69 Retry count display erase 0 1 0

    70 Special regenerative brake duty 0 to 30% 0.1% 0%

    71 Applied motor 0, 1, 3, 13, 23, 40, 43,50, 53

    1 0

    72 PWM frequency selection 0 to 15 1 1 73 Analog input selection 0, 1, 10, 11 1 1

    74 Input filter time constant 0 to 8 1 1

    75Reset selection/disconnected PU

    detection/PU stop selection0 to 3, 14 to 17 1 14

    77 Parameter write selection 0, 1, 2 1 0

    78 Reverse rotation prevention selection 0, 1, 2 1 0

    79 Operation mode selection 0, 1, 2, 3, 4, 6, 7 1 0

    Motorconstants

    80 Motor capacity 0.1 to 7.5kW, 9999 0.01kW 9999

    82 Motor excitation current 0 to 500A, 9999 0.01A 9999

    83 Rated motor voltage 0 to 1000V 0.1V200V/400V

    4

    84 Rated motor frequency 10 to 120Hz 0.01Hz 60Hz

    90 Motor constant (R1) 0 to 50 , 9999 0.001 9999

    96 Auto tuning setting/status 0, 11, 21 1 0

    PUconnectorcommunication 117 PU communication station number 0 to 31 (0 to 247) 1 0

    118 PU communication speed 48, 96, 192, 384 1 192

    119 PU communication stop bit length 0, 1, 10, 11 1 1

    120 PU communication parity check 0, 1, 2 1 2

    121 Number of PU communication retries 0 to 10, 9999 1 1

    122 PU communication check time interval 0, 0.1 to 999.8s, 9999 0.1s 0

    123 PU communication waiting time setting 0 to 150ms, 9999 1 9999

    124 PU communication CR/LF selection 0, 1, 2 1 1

    125Terminal 2 frequency setting gain

    frequency0 to 400Hz 0.01Hz 60Hz

    126Terminal 4 frequency setting gain

    frequency 0 to 400Hz 0.01Hz 60Hz

    Func-tion

    Parameter Name Setting RangeMinimumSetting

    Increments

    InitialValue

    CustomerSetting

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    18/33

    19

    PIDoperation

    127PID control automatic switchover

    frequency0 to 400Hz, 9999 0.01Hz 9999

    128 PID action selection 0, 20, 21, 40 to 43 1 0

    129 PID proportional band 0.1 to 1000%, 9999 0.1% 100%

    130 PID integral time 0.1 to 3600s, 9999 0.1s 1s

    131 PID upper limit 0 to 100%, 9999 0.1% 9999

    132 PID lower limit 0 to 100%, 9999 0.1% 9999

    133 PID action set point 0 to 100%, 9999 0.01% 9999

    134 PID differential time 0.01 to 10s, 9999 0.01s 9999

    PU 145 PU display language selection 0 to 7 1 0

    1465 Built-in potentiometer switching 0, 1 1 1

    Current

    detection

    150 Output current detection level 0 to 200% 0.1% 150%

    151Output current detection signal delaytime

    0 to 10s 0.1s 0s

    152 Zero current detection level 0 to 200% 0.1% 5%

    153 Zero current detection time 0 to 1s 0.01s 0.5s

    156 Stall prevention operation selection 0 to 31, 100, 101 1 0 157 OL signal output timer 0 to 25s, 9999 0.1s 0s

    160 Extended function display selection 0, 9999 1 9999

    161Frequency setting/key lock operation

    selection0, 1, 10, 11 1 0

    Automaticrestart

    functions

    162Automatic restart after instantaneous

    power failure selection0, 1, 10, 11 1 1

    165Stall prevention operation level for

    restart0 to 200% 0.1% 150%

    Currentde

    tection

    166Output current detection signal

    retention time0 to 10s, 9999 0.1s 0.1s

    167Output current detection operation

    selection0, 1 1 0

    168Parameter for manufacturer setting. Do not set.

    169

    Cumulative

    monitorclear

    170 Watt-hour meter clear 0, 10, 9999 1 9999

    171 Operation hour meter clear 0, 9999 1 9999

    Inputterminalfun

    ction

    assignment

    178 STF terminal function selection

    0 to 5, 7, 8, 10, 12,

    14, 16, 18, 24, 25,

    60, 62, 65 to 67, 9999

    1 60

    179 STR terminal function selection

    0 to 5, 7, 8, 10, 12,

    14, 16, 18, 24, 25,

    61, 62, 65 to 67, 9999

    1 61

    180 RL terminal function selection 0 to 5, 7, 8, 10, 12,

    14, 16, 18, 24, 25,

    62, 65 to 67, 9999

    1 0

    181 RM terminal function selection 1 1

    182 RH terminal function selection 1 2

    Func-tion

    Parameter Name Setting RangeMinimumSetting

    Increments

    InitialValue

    CustomerSetting

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    19/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    20

    Outputterminalfunctionassig

    nment

    190 RUN terminal function selection

    0, 1, 3, 4, 7, 8, 11 to 16,

    25, 26, 46, 47, 64, 70,

    80, 90, 91, 93, 95, 96,

    98, 99, 100, 101, 103,

    104, 107, 108,111 to 116, 125, 126,

    146, 147, 164, 170, 180,

    190, 191, 193, 195,

    196, 198, 199, 9999

    1 0

    192 A,B,C terminal function selection

    0, 1, 3, 4, 7, 8, 11 to 16,

    25, 26, 46, 47, 64, 70,

    80, 90, 91, 95, 96, 98,

    99, 100, 101, 103, 104,

    107, 108, 111 to 116,

    125, 126, 146, 147, 164,

    170, 180, 190, 191, 195,

    196, 198, 199, 9999

    1 99

    Multi-speedsetting

    232 Multi-speed setting (speed 8) 0 to 400Hz, 9999 0.01Hz 9999

    233 Multi-speed setting (speed 9) 0 to 400Hz, 9999 0.01Hz 9999

    234 Multi-speed setting (speed 10) 0 to 400Hz, 9999 0.01Hz 9999235 Multi-speed setting (speed 11) 0 to 400Hz, 9999 0.01Hz 9999

    236 Multi-speed setting (speed 12) 0 to 400Hz, 9999 0.01Hz 9999

    237 Multi-speed setting (speed 13) 0 to 400Hz, 9999 0.01Hz 9999

    238 Multi-speed setting (speed 14) 0 to 400Hz, 9999 0.01Hz 9999

    239 Multi-speed setting (speed 15) 0 to 400Hz, 9999 0.01Hz 9999

    240 Soft-PWM operation selection 0, 1 1 1

    241 Analog input display unit switchover 0, 1 1 0

    244 Cooling fan operation selection 0, 1 1 1

    Slip

    compensation 245 Rated slip 0 to 50%, 9999 0.01% 9999

    246 Slip compensation time constant 0.01 to 10s 0.01s 0.5s

    247

    Constant-power range slip

    compensation selection 0, 9999 1 9999

    249 Earth (ground) fault detection at start 0, 1 1 0

    250 Stop selection

    0 to 100s,

    1000 to 1100s,8888, 9999

    0.1s 9999

    251 Output phase loss protection selection 0, 1 1 1

    Lifediagnosis 255 Life alarm status display (0 to 15) 1 0

    256 Inrush current limit circuit life display (0 to 100%) 1% 100%

    257 Control circuit capacitor life display (0 to 100%) 1% 100%

    258 Main circuit capacitor life display (0 to 100%) 1% 100%

    259 Main circuit capacitor life measuring 0, 1 (2, 3, 8, 9) 1 0

    260 PWM frequency automatic switchover 0, 1 1 0

    Powerfailure

    stop 261 Power failure stop selection 0, 1, 2 1 0

    267 Terminal 4 input selection 0, 1, 2 1 0

    268 Monitor decimal digits selection 0, 1, 9999 1 9999

    269 Parameter for manufacturer setting. Do not set.

    295 Magnitude of frequency change setting0, 0.01, 0.10, 1.00,

    10.000.01 0

    Password

    function 296 Password lock level 1 to 6, 101 to 106, 9999 1 9999

    297 Password lock/unlock1000 to 9999 (0 to 5,

    9999)1 9999

    298 Frequency search gain 0 to 32767, 9999 1 9999

    299 Rotation direction detection selectionat restarting

    0, 1, 9999 1 0

    Func-tion

    Parameter Name Setting RangeMinimumSetting

    Increments

    InitialValue

    CustomerSetting

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    20/33

    21

    RS-485comm

    unication 338

    Communication operation command

    source0, 1 1 0

    339Communication speed command

    source0, 1, 2 1 0

    340 Communication startup mode selection 0, 1, 10 1 0

    342Communication EEPROM write

    selection0, 1 1 0

    343 Communication error count 1 0

    Secondmotor

    constant

    450 Second applied motor 0, 1, 9999 1 9999

    Remote

    Output 495 Remote output selection 0, 1, 10, 11 1 0

    496 Remote output data 1 0 to 4095 1 0

    502Stop mode selection at communication

    error0, 1, 2 1 0

    Maintenance

    503 Maintenance timer 0 (1 to 9998) 1 0

    504Maintenance timer alarm output set

    time0 to 9998, 9999 1 9999

    Communication 549 Protocol selection 0, 1 1 0

    551PU mode operation command source

    selection2, 4, 9999 1 9999

    Currentaverage

    timemonitor

    555 Current average time 0.1 to 1s 0.1s 1s

    556 Data output mask time 0 to 20s 0.1s 0s

    557Current average value monitor signal

    output reference current0 to 500A 0.01A

    Rated

    inverter

    current

    561 PTC thermistor protection level 0.5 to 30k , 9999 0.01 9999

    563 Energization time carrying-over times (0 to 65535) 1 0

    564 Operating time carrying-over times (0 to 65535) 1 0

    571 Holding time at a start 0 to 10s, 9999 0.1s 9999

    PID

    oper

    ation 575 Output interruption detection time 0 to 3600s, 9999 0.1s 1s

    576 Output interruption detection level 0 to 400Hz 0.01Hz 0Hz

    577 Output interruption cancel level 900 to 1100% 0.1% 1000%

    611 Acceleration time at a restart 0 to 3600s, 9999 0.1s 9999

    653 Speed smoothing control 0 to 200% 0.1% 0

    665Regeneration avoidance frequency

    gain0 to 200% 0.1% 100

    Protective

    functions

    872 7 Input phase loss protection selection 0, 1 1 0

    Regenerationavoidance

    function

    882Regeneration avoidance operation

    selection0, 1, 2 1 0

    883Regeneration avoidance operation

    level

    300 to 800V 0.1V400VDC/

    780VDC4

    885Regeneration avoidance compensation

    frequency limit value0 to 10Hz, 9999 0.01Hz 6Hz

    886 Regeneration avoidance voltage gain 0 to 200% 0.1% 100%

    Func-tion

    Parameter Name Setting RangeMinimumSetting

    Increments

    InitialValue

    CustomerSetting

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    21/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    22

    Free

    parameter

    888 Free parameter 1 0 to 9999 1 9999

    889 Free parameter 2 0 to 9999 1 9999

    891Cumulative power monitor digit shifted

    times0 to 4, 9999 1 9999

    Calibrationparamet

    ers

    C0

    (900)6FM terminal calibration

    C2

    (902)6

    Terminal 2 frequency setting bias

    frequency0 to 400Hz 0.01Hz 0Hz

    C3

    (902)6Terminal 2 frequency setting bias 0 to 300% 0.1% 0%

    125

    (903)6

    Terminal 2 frequency setting gain

    frequency0 to 400Hz 0.01Hz 60Hz

    C4

    (903)6Terminal 2 frequency setting gain 0 to 300% 0.1% 100%

    C5(904)6

    Terminal 4 frequency setting biasfrequency

    0 to 400Hz 0.01Hz 0Hz

    C6

    (904)6Terminal 4 frequency setting bias 0 to 300% 0.1% 20%

    126

    (905)6

    Terminal 4 frequency setting gain

    frequency0 to 400Hz 0.01Hz 60Hz

    C7

    (905)6Terminal 4 frequency setting gain 0 to 300% 0.1% 100%

    C22

    (922)56

    Frequency setting voltage bias

    frequency (built-in potentiometer)0 to 400Hz 0.01Hz 0

    C23

    (922)56

    Frequency setting voltage bias (built-in

    potentiometer)0 to 300% 0.1% 0

    C24

    (923)56

    Frequency setting voltage gain

    frequency (built-in potentiometer)0 to 400Hz 0.01Hz 60Hz

    C25

    (923)56

    Frequency setting voltage gain (built-in

    potentiometer)0 to 300% 0.1% 100%

    PU

    990 PU buzzer control 0, 1 1 1

    991 PU contrast adjustment 0 to 63 1 58

    Clearparameters

    Initialvaluechangelist

    Pr.CL Parameter clear 0, 1 1 0

    ALLC All parameter clear 0, 1 1 0

    Er.CL Faults history clear 0, 1 1 0

    Pr.CH Initial value change list

    1 Differ according to capacities.6%: 0.75K or less

    4%: 1.5K to 3.7K

    3%: 5.5K, 7.5K

    2 Differ according to capacities.

    5s: 3.7K or less

    10s: 5.5K, 7.5K

    3 Differ according to capacities.

    6%: 0.1K, 0.2K

    4%: 0.4K to 7.5K

    4 The initial value differs according to the voltage class. (100Vclass, 200V class / 400V class)

    5 Set this parameter when calibrating the operation panel built-in potentiometer for the FR-E500 series operation panel (PA02) connected with

    cable.

    6 The parameter number in parentheses is the one for use with the operation panel (PA02) for the FR-E500 series or parameter unit (FR-PU04/

    FR-PU07).

    7 Available only for the three-phase power input specification model.

    Func-tion

    Parameter Name Setting RangeMinimumSetting

    Increments

    InitialValue

    CustomerSetting

    http://../manual_D700/detail/Communication_operation_and_setting.pdf
  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    22/33

    23

    Protective Functions

    When a fault occurs, the inverter trips and the PU display automatically changes to any of the following fault or alarm indications.

    1 Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.

    2 The error message shows an operational error. The inverter output is not shut off.

    3 Warnings are messages given before fault occur. The inverter output is not shut off.

    4Alarms warn the operator of failures with output signals. The inverter output is not shut off.

    5 When faults occur, the protective functions are activated to inverter trip and output the fault signals.

    6 The external thermal operates only when the OH signal is set in Pr. 178 toPr. 182 (input terminal function selection).

    7 This protective function does not function in the initial status.

    8 Protective function activates whenPr.872 Input phase loss protection selection = "1".

    9 This protective function is available with the three-phase power input specification model only.

    Function Name Description Display

    Errormessage

    2

    Operation panel lock Appears when operation was tried during operation panel lock.

    Password locked Appears when a password restricted parameter is read/written.

    Parameter write error Appears when an error occurred during parameter writing.

    Inverter reset Appears when the RES signal is on.

    Warnings

    3

    Stall prevention (overcurrent) Appears during overcurrent stall prevention.

    Stall prevention (overvoltage) Appears during overvoltage stall prevention. Appears while the regeneration avoidance function is activated.

    Regenerative brake prealarm 7Appears if the regenerative brake duty reaches or exceeds 85% of thePr. 70 Special regenerative brake duty

    value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs.

    Electronic thermal relay function prealarm Appears when the electronic thermal O/L relay has reached 85% of the specified value.

    PU stop Appears when on the operation panel was pressed during external operation.

    Maintenance signal output 7 Appears when the cumulative energization time has exceeded the maintenance output timer set value.

    Undervoltage Appears when the main circuit power became low voltage.

    Alarms

    4 Fan alarm

    Appears when the cooling fan remains stopped when operation is required or when the speed has

    decreased.

    Fault

    5

    Overcurrent trip during acceleration Appears when an overcurrent occurred during acceleration.

    Overcurrent trip during constant speed Appears when an overcurrent occurred during constant speed operation.

    Overcurrent trip during decelerationor stop

    Appears when an overcurrent occurred during deceleration and at a stop.

    Regenerative overvoltage trip duringacceleration

    Appears when an overvoltage occurred during acceleration.

    Regenerative overvoltage trip duringconstant speed

    Appears when an overvoltage occurred during constant speed operation.

    Regenerative overvoltage trip duringdeceleration or stop

    Appears when an overvoltage occurred during deceleration and at a stop.

    Inverter overload trip(electronic thermal relay function)

    Appears when the electronic thermal relay function for inverter element protection was activated.

    Motor overload trip(electronic thermal relay function)1

    Appears when the electronic thermal relay function for motor protection was activated.

    Fin overheat Appears when the heatsink overheated.

    Input phase loss 7 89Appears if one of the three phases on the inverter input side opened. It may function if phase-to-

    phase voltage of the three-phase power input becomes largely unbalanced.

    Stall prevention Appears when the output frequency drops to 1Hz as a result of deceleration due to the excess motor load.

    Brake transistor alarm detectionThis function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged brake

    transistors. In this case, the inverter must be powered off immediately.

    Output side earth (ground) faultovercurrent at start 7

    Appears when an earth (ground) fault occurred on the inverter's output side. (detects only at a start)

    Output phase loss

    If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during inverter

    operation (except during DC injection brake operation and when output frequency is under 1Hz),

    inverter stops the output.

    External thermal relay operation6 7 Appears when the external thermal relay connected to the OH signal was activated.

    PTC thermistor operation 7Appears when resistance of PTC thermistor connected between terminal 2 and terminal 10 is more

    than the value set in Pr. 561 PTC thermistor protection level.

    Parameter storage device fault Appears when operation of the element where parameters stored became abnormal. (control board)

    PU disconnectionAppears when a communication error between the PU and inverter occurred, the communicationinterval exceeded the permissible time during the RS-485 communication with the PU connector, or

    communication errors exceeded the number of retries during the RS-485 communication.

    Retry count excess 7 Appears when the operation was not restarted within the set number of retries.

    CPU fault Appears during the CPU and peripheral circuit errors occurred./

    Output current detection valueexceeded 7

    Appears when output current exceeded the output current detection level set by the parameter.

    Inrush current limit circuit fault Appears when the resistor of the inrush current limit circuit overheated.

    Analog input faultAppears if voltage(current) is input to terminal 4 when the setting inPr.267 Terminal 4 input selection and

    the setting of voltage/current input switch are different.

    Safety circuit fault Appears when safety circuit is malfunctioning.

    to

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    23/33

    Features

    Options

    Standard

    Specificatio

    ns

    Parameter

    List

    Protective

    Functions

    TerminalConnection

    Diagram

    TerminalSpecification

    Explanation

    Outline

    Dimension

    Drawings

    Instructions

    FR-D700Series

    Specification

    DifferenceList

    Warran

    ty

    Internatio

    nal

    FACen

    ter

    Operationpanel

    Parameterunit

    24

    Option and Peripheral Devices

    By fitting the following options to the inverter, the inverter is provided with more functions.

    Rated power consumption. The power supply specifications of the FR series manual controllers and speed controllers are 200VAC 50Hz, 220V/220VAC 60Hz,

    and 115VAC 60Hz.

    Option list

    Name Type Applications, Specifications, etc.Applicable

    Inverter

    Stand-aloneshare

    d

    Parameter unit (8 languages)FR-PU07

    FR-PU04Interactive parameter unit with LCD display

    Shared among

    all models

    Parameter unit with battery pack FR-PU07BB(-L) This parameter unit enables parameter setting without connecting the inverterto power supply.

    Shared among

    all models

    (Available soon)

    Enclosure surface operation panel FR-PA07This operation panel enables inverter operation and monitoring of frequency,

    etc. from the enclosure surface Shared among

    all modelsParameter unit connection cable FR-CB20

    Cable for connection of operation panel or parameter unit

    indicates a cable length. (1m, 3m, 5m)

    DIN rail attachment FR-UDA01 to 03 Attachment for installation on DIN railCompatible with

    the 3.7K or less

    AC reactor FR-HALFor harmonic current reduction and inverter input power factor improvement

    (total power factor approx. 88%) According to

    capacitiesDC reactor FR-HEL

    For harmonic current reduction and inverter input power factor improvement

    (total power factor approx. 93%)

    EMC Directive compliant noise filter FR-E5NF EMC Directive (EN61800-3 C3) compliant noise filter400V: According

    to capacities

    Radio noise filter FR-BIF(H) For radio noise reduction (connect to the input side)Shared among

    all modelsLine noise filter FR- BSF01FR- BLF

    For line noise reduction

    Filter pack FR-BFP2Combination of power factor improving DC reactor, zero phase reactor, and

    capacitative filter

    Three-phasepower inputmodel:compatible with0.4K or biggercapacity

    Brake resistorMRS type,

    MYS typeFor increasing the regenerative braking capability (permissible duty 3%/6%ED)

    200V: For the

    0.4K or more

    High-duty brake resistor FR-ABRFor increasing the regenerative braking capability (permissible duty 10%/

    6%ED)

    For the 0.4K or

    moreBrake unit

    Resistor unit

    Discharging resistor

    FR-BU2

    FR-BR

    GZG, GRZG type

    For increasing the braking capability of the inverter (for high-inertia load or

    negative load)

    Brake unit, electrical-discharge resistor and resistor unit are used in

    combination

    Power regeneration common

    converterStand-alone reactor dedicated for

    the FR-CV

    FR-CVFR-CVL

    Unit which can return motor-generated braking energy back to the powersupply in common converter system

    According to

    capacities

    High power factor converter FR-HC

    The high power factor converter switches the converter section on/off to

    reshape an input current waveform into a sine wave, greatly suppressing

    harmonics. (Used in combination with the standard accessory.)

    Surge voltage suppression filter

    FR-ASF

    Filter for suppressing surge voltage on motor

    400V: According

    to capacities

    FR-BMF400V: For the

    5.5K or more

    FRseriesmanualco

    ntroller/

    speedcontroller

    Manual controller FR-AXFor independent operation. With frequency meter, frequency potentiometer and

    start switch.

    Shared among

    all models

    DC tach. follower FR-AL For synchronous operation (1.5VA) by external signal (0 to 5V, 0 to 10V DC)

    Three speed selector FR-ATFor three speed switching, among high, middle and low speed operation

    (1.5VA)

    Motorized speed setter FR-FK

    For remote operation. Allows operation to be controlled from several places

    (5VA)

    Ratio setter FR-FH For ratio operation. The ratios of five inverters can be set (3VA)

    Speed detector FR-FP For tracking operation by a pilot generator (PG) signal (3VA)

    Master controller FR-FGMaster controller (5VA) for parallel operation of multiple (maximum 35)

    inverters.

    Soft starter FR-FCFor soft start and stop. Enables acceleration/deceleration in parallel operation

    (3VA)

    Deviation detector FR-FDFor continuous speed control operation. Used in combination with a deviation

    sensor or synchro (5VA)

    Preamplifier FR-FA Used as an A/V converter or arithmetic amplifier (3VA)

    O

    thers

    Pilot generator QVAH-10 For tracking operation. 70V/35VAC 500Hz (at 2500r/min)

    Deviation sensor YVGC-500W-NSFor continuous speed control operation (mechanical deviation detection)

    Output 90VAC/90C

    Frequency setting potentiometer WA2W 1k For frequency setting. Wire-wound 2W 1k type B characteristic

    Analog frequency meter

    (64mm 60mm)YM206NRI 1mA

    Dedicated frequency meter (graduated to 120Hz). Moving-coil type DC

    ammeterCalibration resistor RV24YN 10k For frequency meter calibration. Carbon film type B characteristic

    FR Configurator SW3(VFD setup

    software)

    FR-SW3-SETUP-

    WESupports an inverter startup to maintenance.

    Shared among

    all models

  • 7/30/2019 Mitsubishi D700 Series Vfd Brochure

    24/33

    25

    Peripheral devices/cable size list

    Inverter typeMotorOutput

    (kW)

    Moulded Case Circuit Breaker (MCCB)1or Earth Leakage Current Breaker (ELB)2

    Magnetic

    Contactor (MC)3HIV Cables,

    etc. (mm2)5Reactor

    Reactor connection Reactor connection

    Without With Without WithR/L1,S/L2,

    T/L34

    U, V, W FR-HAL FR-HEL

    Three-P

    hase

    200V

    FR-D720-0.1K 0.1 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K 7 0.4K 7

    FR-D720-0.2K 0.2 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K 7 0.4K 7

    FR-D720-0.4K 0.4 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K 0.4K

    FR-D720-0.75K 0.75 30AF 10A 30AF 5A S-N10 S-N10 2 2 0.75K 0.75K

    FR-D720-1.5K 1.5 30AF 15A 30AF 10A S-N10 S-N10 2 2 1.5K 1.5K

    FR-D720-2.2K 2.2 30AF 20A 30AF 15A S-N10 S-N10 2 2 2.2K 2.2K

    FR-D720-3.7K 3.7 30AF 30A 30AF 30A S-N20, S-N21 S-N10 3.5 3.5 3.7K 3.7K

    FR-D720-5.5K 5.5 50AF 50A 50AF 40A S-N20, S-N21 S-N20, S-N21 5.5 5.5 5.5K 5.5K

    FR-D720-7.5K 7.5 100AF 60A 50AF 50A S-N25 S-N20, S-N21 14 8 7.5K 7.5K

    Three

    -phase

    400V

    FR-D740-0.4K 0.4 30AF 5A 30AF 5A S-N10 S-N10 2 2 H0.4K H0.4K

    FR-D740-0.75K 0.75 30AF 5A 30AF 5A S-N10 S-N10 2 2 H0.75K H0.75K

    FR-D740-1.5K 1.5 30AF 10A 30AF 10A S-N10 S-N10 2 2 H1.5K H1.5K

    FR-D740-2.2K 2.2 30AF 15A 30AF 10A S-N10 S-N10 2 2 H2.2K H2.2K

    FR-D740-3.7K 3.7 30AF 20A 30AF 15A S-N10 S-N10 2 2 H3.7K H3.7KFR-D740-5.5K 5.5 30AF 30A 30AF 20A S-N20, S-N21 S-N11, S-N12 3.5 2 H5.5K H5.5K

    FR-D740-7.5K 7.5 30AF 30A 30AF 30A S-N20, S-N21 S-N20, S-N21 3.5 3.5 H7.5K H7.5K

    Sing

    le-p

    hase

    200V FR-D720S-0.1K 0.1 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K 7 0.4K 7

    FR-D720S-0.2K 0.2 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K 7 0.4K 7

    FR-D720S-0.4K 0.4 30AF 10A 30AF 10A S-N10 S-N10 2 2 0.75K 7 0.75K 7

    FR-D720S-0.75K 0.75 30AF 15A 30AF 10A S-N10 S-N10 2 2 1.5K 7 1.5K 7

    FR-D720S-1.5K 1.5 30AF 20A 30AF 20A S-N10 S-N10 2 2 2.2K 7 2.2K 7

    FR-D720S-2.2K 2.2 30AF 40A 30AF 30A S-N20, S-N21 S-N10 3.5 2 3.7K 7 3.7K 7

    Sing

    le-P

    hase

    100V FR-D710W-0.1K 0.1 30AF 10A 30AF 5A S-N10 S-N10 2 2 0.75K 6, 7 8

    FR-D710W-0.2K 0.2 30AF 10A 30AF 10A S-N10 S-N10 2 2 1.5K 6, 7 8

    FR-D710W-0.4K 0.4 30AF 15A 30AF 15A S-N10 S-N10 2 2 2.2K 6, 7 8

    FR-D710W-0.75K 0.75 30AF 30A 30AF 20A S-N10 S-N10 3.5 2 3.7K 6, 7 8

    1 Select an MCCB according to the inverter power supply capacity.

    Install one MCCB per inverter.

    2 For installations in the United States or Canada, use the class T type fuse certified by the UL and cUL.

    3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is

    used for emergency stop during motor driving, the electrical durability is 25 times.

    When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with

    class AC-3 rated current for the motor rated current.

    4 When using single-phase power input, terminals are R/L1 and S/L2.

    5 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75C.

    Assumes that the surrounding air temperature is 50C or less and the wiring distance is 20m or less.

    6 When connecting a single-phase 100V power input model to a power transformer (50kVA or more), install an AC reactor (FR-HAL) so that the performance