Minimum Energy Performance Standards - Siemens · USA ... Minimum Energy Performance Standards. 4...

32
www.siemens.de/international-efficiency Minimum Energy Performance Standards MEPS regulations worldwide

Transcript of Minimum Energy Performance Standards - Siemens · USA ... Minimum Energy Performance Standards. 4...

www.siemens.de/international-efficiency

Minimum Energy Performance Standards MEPS regulations worldwide

1 www.siemens.de/international-efficiency

Introduction MEPS................................................................................................. 2

Argentina ............................................................................................................. 6

Australia ............................................................................................................... 7

Brazil .................................................................................................................... 8

Canada ................................................................................................................. 9

Chile .................................................................................................................. 10

China ................................................................................................................. 11

Colombia ............................................................................................................ 12

Europe ............................................................................................................... 13

India .................................................................................................................. 14

Israel .................................................................................................................. 15

Japan ................................................................................................................. 16

Mexico ............................................................................................................... 17

Peru ................................................................................................................... 18

Philippines .......................................................................................................... 19

Russia ................................................................................................................ 20

Saudi Arabia ....................................................................................................... 21

South Africa ........................................................................................................ 22

South Korea ........................................................................................................ 23

Switzerland ........................................................................................................ 24

Taiwan ............................................................................................................... 25

Thailand ............................................................................................................. 26

Turkey ................................................................................................................ 27

United Arab Emirates ........................................................................................... 28

USA ................................................................................................................... 29

2 www.siemens.de/international-efficiency

Warranty, liability and support

We shall not be held liable for any information provided in this document.

We accept no liability for any damage or loss caused by the applications,

information, programs, planning data, or performance data described in this

example, irrespective of the legal basis for claims arising from such damage

or loss, unless liability is mandatory. For example, according to the product

liability law, in cases of malfeasance, gross negligence, due to endangerment

of life, body or health, due to assumption of a guarantee for a product's

characteristics of state, due to malicious concealment of a defect or due to

violation of basic contractual obligations. Any claims for damages caused by

violation of basic contractual obligations, however, shall be limited to the

foreseeable damage or loss which is typically envisaged in contracts unless

there has been malfeasance or gross negligence or unless liability is

mandatory due to endangerment of life, the body or health. This does not

entail a change in the burden of proof to your disadvantage.

Copyright© 2016 Siemens AG. Reproduction or transmissions of these

examples or extracts thereof are forbidden without the express written

authority of Siemens AG.

3 www.siemens.de/international-efficiency

MEPS

On one hand, considerable emphasis is placed on energy efficiency

to protect our environment. On the other hand, a higher energy

efficiency allows companies to improve their cost position,

therefore increasing their competitiveness.

Sustainably reducing energy usage

Regarding energy efficiency, the focus has been on industrial direct-on-line

(DOL) motors from a very early stage. This is because electric drives consume

70% of the electric energy in the industry. As a consequence, electric drives

represent a huge potential when it comes to boosting efficiency. Many

countries have already created a legal framework to reduce energy

consumption in their industrial landscape – and to achieve the environmental

goals that have been set.

Standards

Initially, global standards were defined to achieve this, for instance IEC

60034-30-1 and NEMA MG1. The standards were either taken over – or

transitioned into minimum legal efficiency requirements. The term used

around the globe for these minimum efficiencies is MEPS: Minimum Energy

Performance Standards.

4 www.siemens.de/international-efficiency

Profit from MEPS

Companies operating plants especially profit from MEPS regulations as these

help them to boost their productivity. For instance, for a 110kW motor, the

energy costs represent up to 99% of the overall lifecycle costs. As a

consequence, by increasing the efficiency of a motor, the energy

consumption can be significantly reduced – and along with it, the associated

costs. Companies operating plants can sustainably benefit when investing in

energy efficiency.

Tools

Tools are available that can be used to define when it makes sense to invest in

energy efficient motors:

SIMOTICS EE Comparator

The efficiency of IE4 motors is 14% higher than for IE1. Operating costs can

be reduced with a high efficiency. A payback calculation always makes sense

in order to select the most cost-effective motor for line operation. Every

country has its own specific MEPS requirements. An overview of these

requirements is listed below, but can also be simply viewed using the

SIMOTICS EE-COMPARATOR App.

5 www.siemens.de/international-efficiency

SinaSave

Answers to questions, such as "What is the payback time when investing in a

more efficient motor?", "Does it make sense to use a variable-speed drive or a

DOL motor for my applications?", "How does the energy efficiency class of a

motor impact the cost effectiveness of the drive system?", can be found in the

web-based SinaSave tool. Based on individual operating characteristics as

well as system-specific parameters, SinaSave calculates the energy

requirements of various drive products and systems, which are then

compared with one another. Further, SinaSave tells you the payback time

when investing in an energy-efficient drive solution. Based on the investment

and operating costs as well as the energy-saving potential, this tool calculates

the expected payback time. Not only this, it also provides fast and

straightforward help for decision-making when it comes to financially

assessing the investment in energy-efficient products.

You can find SinaSave here: siemens.de/sinasave.

Low-voltage motors for every requirement

SIMOTICS low-voltage motors are available in a power range from 0.09 kW to

3500 kW – to address many efficiency standards worldwide. We can offer you

the optimum solution for every specific requirement: in addition to energy

efficient motors in compliance with specific standards, explosion-protected

motors for the highest safety standards, along with motors for specific sectors

and customers. Employing state-of-the-art product and production

technologies, these motors are especially compact – and in many cases have

the same dimensions irrespective of the particular efficiency class.

More information is available at siemens.com/niederspannungsmotoren

6 www.siemens.de/international-efficiency

Argentina

Voltage/Frequency

Voltage up to 660 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements

Exceptions

No exceptions

7 www.siemens.de/international-efficiency

Australia

Voltage/Frequency

Voltage up to 1100 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

AS/NZS 1359.5:2004 (MEPS)

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 – 185 kW

1 HP – 250 HP

2,4,6,8

IE2 mandatory since 31.03.2006

Exceptions

1. Motors designed to operate wholly immersed in a liquid;

2. Motors completely integrated into a product (for example gear, pump, fan or

compressor) of which the energy performance cannot be tested independently from

the product;

3. Pole-changing motors;

4. Duty type S2;

5. Torque motors;

6. Re-export motors (from Australia/ New Zealand).

8 www.siemens.de/international-efficiency

Brazil

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

Portaria Interministerial No. 553

INMETRO NBR 17094-1

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 110 kW

1 HP - 150 HP

8

IE2 mandatory since

08.12.2009*

0,75 kW - 150 kW

1 HP - 200 HP

6

IE2 mandatory since

08.12.2009*

0,75 kW - 185 kW

1 HP - 250 HP

2, 4

IE2 mandatory since

08.12.2009*

Exceptions

* The minimum efficiency values are close to the IE2 values defined in IEC 60034-30

Exceptions according INMETRO NBR 17094-1 / Portaria Interministerial No. 553:

1. Motors specially designed for inverter duty;

2. Motors specifically designed to operate in potentially explosive atmospheres (Ex e, Ex

d(e));

3. Duty type different to S1 or S3 (with a rated cyclic duration factor of 80 % or higher);

4. Water cooled motors;

5. Motors designed to operate wholly immersed in a liquid.

9 www.siemens.de/international-efficiency

Canada

Voltage/Frequency

Voltage up to 600 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

Energy Efficiency Act

CSA C390-10

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 150 kW

1 HP - 200 HP

2, 4, 6

NEMA Premium Efficient

mandatory since 12.04.2012

160 kW - 375 kW

215 HP - 500 HP

2, 4, 6

NEMA Energy Efficient

mandatory since 12.04.2012

0,75 kW - 375 kW

1 HP - 500 HP

8

NEMA Energy Efficient

mandatory since 12.04.2012

Exceptions

Can be operated as “NEMA Energy Efficient”:

1. Foot, foot & flange mounted motors or/and IEC design N or H;

2. Footless motors;

3. NEMA design C or IEC design H;

4. Close-coupled pump motor;

5. Fire extinguishing pumps.

Exceptions according Canada Energy Efficiency Act (EEA C390-10 since 12.04.2012)

1. Motors labeled for inverter operation;

2. Multi-speed motors;

3. Flange mounted motors except C & D design;

4. U Frame motors;

5. Two-digit NEMA frames (48-56);

6. Duty type different to S1.

10 www.siemens.de/international-efficiency

Chile

Voltage/Frequency

Voltage up to 690 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

NCh 3086 of. 2008

PE N° 7/01/2.

IEC 60034-30

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW – 7,5 kW

1 HP – 10 HP

2, 4, 6

IE1 mandatory since

04.01.2011.*

Exceptions

Exceptions according NCh 3086 of 2008

1. Motors with electromagnetic or manual brake ;

2. Motors specially designed for inverter duty.

* The engines must be certified according to the requirements for the Energy label from

the protocol PE N ° 7/01/2. The Energy label only applies to engines which are kept on store

by distributors. Motors completely integrated into a product (for example gear, pump, fan

or compressor) need label.

11 www.siemens.de/international-efficiency

China

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

GB18613-2012

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW – 375 kW

1 HP – 500 HP

2, 4, 6

IE2 mandatory since

01.09.2012

2016

0,75 kW – 5,5 kW

1 HP – 7,5 HP

2, 4, 6

IE2 mandatory since

01.09.2012

7,5 kW – 375 kW

10 HP – 500 HP

2, 4, 6

IE3 mandatory

from 01.09.2016

2017

0,75 kW – 375 kW

1 HP – 500 HP

2, 4, 6

IE3 mandatory

from 01.09.2017

Exceptions

Exceptions China Energy Label since 1.09.2012:

1. Motors completely integrated into a machine (for example pump, fan and compressor)

that cannot be tested separately from the machine;

2. Special design motors for special application environment such as application in high

altitudes exceeding 1.000 m above sea level;

3. Special design motors for special application such as smoke-extraction motors, textile

industry specified motors and etc. ;

4. Motors designed for variable conditions, such as inverter duty motor;

5. Motors with integrating brake inside;

6. Motor working duty with non S1 or S3 with a rated cyclic duration factor of 80 % or

higher;

7. Dual-windings and/or multi-windings motors;

8. 60Hz motors (only 60Hz data on rating plate);

9. IC 416 motor for DOL and VSD use.

12 www.siemens.de/international-efficiency

Colombia

Voltage/Frequency

Voltage up to 460 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements*

Exceptions

No exceptions

*but it is mandatory to declare it on the nameplate

13 www.siemens.de/international-efficiency

Europe

Voltage/

Frequency

Voltage up to 1000 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

EU regulation 640/2009

EU regulation 04/2014

IEC 60034-30-1

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 5,5 kW

1 HP - 7,5 HP

2, 4, 6

IE2 mandatory

since 16.06.2011

7,5 kW – 375 kW

10 HP – 500 HP

2, 4, 6

IE3 or IE2 with variable speed

drive mandatory since

01.01.2015

2017

0,75 kW - 375 kW

1 HP – 500 HP

2, 4, 6

IE3 or IE2 with variable speed

drive mandatory from

01.01.2017 on

Exceptions

Exceptions according to regulation (EG) 640/2009 and (EG) 4/2014:

1. Motors designed to operate wholly immersed in a liquid;

2. Motors completely integrated into a product (for example gear, pump, fan or

compressor) of which the energy performance cannot be tested independently from the

product;

3. Motors specifically designed to operate:

i) at altitudes exceeding 4.000 meters above sea-level;

ii) where ambient air temperatures exceed 60 °C;

iii) in maximum operating temperature above 400 °C;

iv) where ambient air temperatures are less than – 30 °C for any motor or less than 0 °C

for a motor with air cooling;

v) where the water coolant temperature at the inlet to a product is less than 0 °C or

exceeding 30 °C;

vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European

Parliament and of the Council;

4. Brake motors;

5. Duty type different to S1 or S6;

6. Motors specially designed for inverter duty;

7. Pole changing motors.

14 www.siemens.de/international-efficiency

India

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No regulation

Standard - IS: 12615- 2011

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements *

Exceptions

* The minimum efficiency requirements according to IS: 12615-2011 (IE3 is mentioned)

are not mandatory and only valid for energy efficient motors

in the power range of 0,75 -375 kW and 2-/4-/6-poles.

Exceptions according to IS:12615-2011:

1. Motors made exclusively for converter duty application;

2. Motors completely integrated into the machine (for example, pumps, compressors,

special machines etc.) that cannot be tested separately from the machine;

3. Motors rated for duty cycles S2, S4 and above, except if an equivalent S1 duty is

specified by the driven equipment manufacturer;

4. Slip-ring Induction Motors;

5. Single phase motors;

6. Pole-changing motors.

15 www.siemens.de/international-efficiency

Israel

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No special Regulations,

referring to European Standards (e.g. IEC 60034-30-1) and requirements

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW – 5,5 kW

1 HP – 7,5 HP

2, 4, 6

IE2 mandatory since

16.06.2011

7,5 kW – 375 kW

10 HP – 500 HP

2, 4, 6

IE3 mandatory since

01.01.2015

Exceptions

Referring to European exceptions:

1. Motors designed to operate wholly immersed in a liquid;

2. Motors completely integrated into a product (for example gear, pump, fan or

compressor) of which the energy performance cannot be tested independently from the

product;

3. Motors specifically designed to operate:

i) at altitudes exceeding 4.000 meters above sea-level;

ii) where ambient air temperatures exceed 60 °C;

iii) in maximum operating temperature above 400 °C;

iv) where ambient air temperatures are less than – 30 °C for any motor or less than 0 °C

for a motor with air cooling;

v) where the water coolant temperature at the inlet to a product is less than 0 °C or

exceeding 30 °C;

vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European

Parliament and of the Council;

4. Brake motors;

5. Duty type different to S1 or S6;

6. Motors specially designed for inverter duty;

7. Pole changing motors.

16 www.siemens.de/international-efficiency

Japan

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 50/60 Hz

Regulation/Directive/

Standard

JIC C4034-2-1: IEC 60034-2-1:2007 (MOD)

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 375 kW

1 HP – 500 HP

2, 4, 6

IE3 mandatory since

01.04.2015

Exceptions

Exceptions:

1. Explosion proof motors;

2. Special insulation (Temp class H, N, R, 250);

3. Delta-star starting;

4. Marine motors;

5. Motors designed to operate wholly immersed in a liquid;

6. High-slip motors;

7. Gate motors;

8. Canned motors;

9. Used in very low temperature (designed for lower than -20 degree C);

10. Motors, designed only for inverter duty and with forced ventilation.

17 www.siemens.de/international-efficiency

Mexico

Voltage/Frequency

Voltage up to 600 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

NOM-016-ENER-2010

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 375 kW

1 HP – 500 HP

2, 4, 6, 8

NEMA Premium Efficient

mandatory since 19.12.2010

Exceptions

No exceptions

18 www.siemens.de/international-efficiency

Peru

Voltage/Frequency

Voltage up to 480 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

NTP 399.450.2008

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements

Exceptions

No exceptions

19 www.siemens.de/international-efficiency

Philippines

Voltage/Frequency

Voltage up to 460 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements

Exceptions

No exceptions

20 www.siemens.de/international-efficiency

Russia

Voltage/Frequency

Voltage up to 690 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements

Exceptions

No exceptions

21 www.siemens.de/international-efficiency

Saudi Arabia

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 50/60 Hz

Regulation/Directive/

Standard

SASO IEC 60034-30:2013

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW – 375 kW

1 HP – 500 HP

2, 4, 6

IE2 mandatory since 01.07.2015

2017

0,75 kW – 375 kW

1 HP – 500 HP

2, 4, 6

IE3 mandatory from 01.01.2017

Exceptions

Exceptions according to SASO IEC 60034-30:2013:

1. Motors made solely for converter operation in accordance with IEC 60034-25;

2. Motors completely integrated into a machine (for example pump, fan and compressor)

that cannot be tested separately from the machine;

3. Brake motors, gear motors and wound rotor motors;

4. Motors specifically designed to operate:

i) In maximum operating temperatures above 400º C;

ii) In potentially explosive atmospheres (e.g. explosion proof motors);

iii) wholly immersed in a liquid;

iv) with a starting torque over 100% of the rated torque (e .g. gate motor & crane

motor);

v) With cooling from external equipment (e .g. air over motors, or liquid cooling

motors);

vi) In an enclosed container and part of an integrated system (e .g. canned motor).

22 www.siemens.de/international-efficiency

South Africa

Voltage/Frequency

Voltage up to 525 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements

Exceptions

No exceptions

23 www.siemens.de/international-efficiency

South Korea

Voltage/Frequency

Voltage up to 600 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

MKE-2015-28

KS C IEC60034

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 30 kW

1 HP - 40 HP

2, 4, 6, 8

IE2 mandatory since 01.01.2013

37 kW - 200 kW

50 HP - 275 HP

2, 4, 6, 8

IE3 mandatory since 01.10.2015

225 kW - 375 kW

275 HP - 500 HP

2, 8

IE2 mandatory from 01.10.2016

225 kW - 375 kW

275 HP - 500 HP

4, 6

IE3 mandatory from 01.10.2016

2018

0,75 kW - 200 kW

1 HP - 275 HP

2, 4, 6, 8

IE3 mandatory from 01.10.2018

225 kW - 375 kW

275 HP - 500 HP

2, 8

IE2 mandatory from 01.10.2016

225 kW - 375 kW

275 HP - 500 HP

4, 6

IE3 mandatory from 01.10.2016

Exceptions

Exceptions according to KS C IEC60034:

1. Motors specifically designed to operate:

i) at altitudes exceeding 1 000 meters above sea-level;

ii) where ambient air temperatures exceed 40 °C;

2. Duty type different to S1;

3. Motors specially designed for inverter duty;

4. Motors designed to operate wholly immersed in a liquid;

5. TENV and TEAO enclosure (totally enclosed non-ventilated, totally enclosed air over);

6. Pole changing motors;

7. Torque curve: Design C and D;

8. Water cooled motor as similar to TEAO.

24 www.siemens.de/international-efficiency

Switzerland

Voltage/

Frequency

Voltage up to 1000 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

SR 730.01 Energieverordnung (EnV) from 07. 12.1998 (Update: 01.08.2014)

IEC 60034-30-11

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 5,5 kW

1 HP - 7,5 HP

2, 4, 6

IE2 mandatory

since 16.06.2011

7,5 kW – 375 kW

10 HP – 500 HP

2, 4, 6

IE3 or IE2 with variable speed

drive mandatory since

01.01.2015

2017

0,75 kW - 375 kW

1 HP – 500 HP

2, 4, 6

IE3 or IE2 with variable speed

drive mandatory from

01.01.2017 on

Exceptions

Exceptions according to regulation Energieverordnung (EnV) from 07. 12.1998

(Update: 01.08.2014):

1. Motors designed to operate wholly immersed in a liquid;

2. Motors completely integrated into a product (for example gear, pump, fan or

compressor) of which the energy performance cannot be tested independently from the

product;

3. Motors specifically designed to operate:

i) at altitudes exceeding 4.000 meters above sea-level;

ii) where ambient air temperatures exceed 60 °C;

iii) in maximum operating temperature above 400 °C;

iv) where ambient air temperatures are less than – 30 °C for any motor or less than 0 °C

for a motor with air cooling;

v) where the water coolant temperature at the inlet to a product is less than 0 °C or

exceeding 30 °C;

vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European

Parliament and of the Council;

4. Motors specially designed for inverter duty.

25 www.siemens.de/international-efficiency

Taiwan

Voltage/Frequency

Voltage up to 690 V,

Frequency: 60 Hz

Regulation/Directive/

Standard

IEC60034-2-1

CNS 14400 (MEPS)

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW – 200 kW

1 HP – 275 HP

2,4,6,8

IE2 mandatory since 2015

Exceptions

1. Motors designed to operate wholly immersed in a liquid;

2. Motors completely integrated into a product (for example gear, pump, fan or

compressor) of which the energy performance cannot be tested independently

from the product;

3. Motors specially designed for inverter duty;

4. Pole-changing motors.

26 www.siemens.de/international-efficiency

Thailand

Voltage/Frequency

Voltage up to 400 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements *

Exceptions

* on a voluntary base tax benefits can be applied when installing motors with an energy

efficiency class IE3 for 2,4,6 and 8 poles motors with an output range from 0,73kW –

185kW.

No exceptions

27 www.siemens.de/international-efficiency

Turkey

Voltage/Frequency

Voltage up to 1000 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

Regulation SMG 2012/2

IEC 60034-30-1

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 5,5 kW

1 HP - 7,5 HP

2, 4, 6

IE2 mandatory since

01.01.2015

7,5 kW - 375 kW

10 HP – 500 HP

2, 4, 6

IE3 or IE2 with variable speed

drive mandatory since

01.01.2015

2017

0,75 kW - 375 kW

1 HP – 500 HP

2, 4, 6

IE3 or IE2 with variable speed

drive mandatory

from 01.01.2017

Exceptions

Exceptions according to the Turkish regulation SMG-2012/2:

1. Motors designed to operate wholly immersed in a liquid;

2. Motors completely integrated into a product (for example gear, pump, fan or

compressor) of which the energy performance cannot be tested independently from the

product;

3. Motors specifically designed to operate:

i) at altitudes exceeding 1 000 meters above sea-level;

ii) where ambient air temperatures exceed 40 °C;

iii) in maximum operating temperature above 400 °C;

iv) where ambient air temperatures are less than – 15 °C for any motor or less

than 0 °C for a motor with air cooling;

v) where the water coolant temperature at the inlet to a product is less than 5 °C or

exceeding 25 °C;

vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European

Parliament and of the Council;

4. Brake motors;

5. Duty type different to S1 or S6;

6. Motors specially designed for inverter duty;

7. Pole changing motors.

28 www.siemens.de/international-efficiency

United Arab Emirates

Voltage/Frequency

Voltage up to 690 V,

Frequency: 50 Hz

Regulation/Directive/

Standard

No standard or regulation

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

/

/

/

No minimum efficiency

requirements

Exceptions

No exceptions

29 www.siemens.de/international-efficiency

USA

Voltage/Frequency

Voltage up to 600 V,

Frequency: 60 Hz

Regulation / Directive /

Standard

Energy Conservation Standards for Commercial and Industrial Motors, Final rule:

2014

EPAct;

EISA 2007;

NEMA MG-1 Table 12-12 und Table 12-11;

Legal requirements

Year

Power range [kW]

Power range [HP]

Poles

Minimum efficiency

2016

0,75 kW - 150 kW

1 HP – 200 HP

4,6,8

NEMA Premium Efficient

mandatory from 01.06.2016 on

for NEMA Design C

0,75 kW - 375 kW

1 HP – 500 HP

2,4,6,8

NEMA Premium Efficient

mandatory from 01.06.2016 on

for NEMA Design A & B

0,75 kW - 375 kW

1 HP – 500 HP

2,4,6,8

NEMA Energy Efficient

mandatory from 01.06.2016 on

for fire pumps

30 www.siemens.de/international-efficiency

Exceptions

From June 1st 2016 on

"Electric Motors" covered under the Energy Conservation Standards for Commercial

and Industrial Motors Final rule (2014) are:

1. Single-speed, induction motor;

2. Rated for continuous duty (MG 1) operation or for duty type S1 (IEC);

3. Contains a squirrel-cage (MG 1) or cage (IEC) rotor;

4. Built in a three-digit or four-digit NEMA frame size (or IEC metric equivalent), including

those designs between two consecutive NEMA frame sizes (or IEC metric equivalent) or

an enclosed 56 NEMA frame size (or IEC metric equivalent);

5. Meets all of the performance requirements of a NEMA Design A, B, or C motor or of an

IEC Design N or H motor;

6. Partial electric motors.

Exceptions according to "Electric Motors" covered under the Energy Conservation

Standards for Commercial and Industrial Motors Final rule (2014):

1. Totally enclosed air over electric motors;

2. Multi-speed motors;

3. Inverter-only electric motors;

4. Component sets of an electric motor;

5. Liquid-cooled electric motors;

6. Submersible electric motors.

The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract.

All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.

Global Siemens Headquarters

Siemens AG

Wittelsbacherplatz 2

80333 Muenchen

Germany

Global Siemens Headquarters

Siemens AG

Lorem Sector

Henkestrasse 127

91052 Erlangen

Telephone: +49 9131 84-0

Germany

www.siemens.com/international-efficiency

Siemens AG

Industry Sector

Large Drives

Postfach 47 43

90025 Nuernberg

DEUTSCHLAND © 04.2016, Siemens AG

www.siemens.de/international-efficiency