MINI SMMS
Transcript of MINI SMMS
-
7/30/2019 MINI SMMS
1/37
Introduction of TOSHIBA New ProductsMini-SMMS
PRELIMINARY
-
7/30/2019 MINI SMMS
2/37
Introduction
Line up:
Outdoor : 4, 5, 6HP
Indoor : same as SMMS*
The
new MiNi-SMMS:best performances for commercialand more private spaces.
The great VRF traditional flexibility, reliability and energysavings can fit any room demanding application.
Precise efficiency and control required by smaller offices,shops and quiet space applications are now available.
-
7/30/2019 MINI SMMS
3/37
Design Keywords
Superior COP (4.61/ 4HP) & high reliability
achieved by TOSHIBAs unrivalled SMMS Technology
Quiet operation can be further enhanced with PMV kit
in indoor space
Compact & Light weight outdoor unit
Wide range of indoor unit line-up (81 variation)
Quiet sound design of outdoor unit
Various optional control gives great benefit and solution
-
7/30/2019 MINI SMMS
4/37
Product Category
HP 2 3
4 5 6 8 10 48Inverter Multi
Mini-SMMS
Super-MMS
2 to 4 indoor
Max. 6 to 9 indoor
Light Commercial
Residential
-
7/30/2019 MINI SMMS
5/37
Outdoor unit line-up
Outdoor4HP 5HP 6HP
Model Name MCY- MAP1401HT MAP-0501HT MAP-0601HT
Cooling capacity (kW) 12.1 14.0 15.5
Heating capacity (kW) 12.5 16.0 18.0Connectable indoor
unit6 8 9
Outdoor Diversity : 80% to 130%
-
7/30/2019 MINI SMMS
6/37
Compact & Light Weight
The extreme compactness and lightweight allows easytransportation and installation on balcony or faades with a:
70% volume reduction*
60% footprint reduction
* over the standard SMMS condensing unit 5HP.
Height1,340mm
Depth320mmWidth
900mm
Weight
117kg
-
7/30/2019 MINI SMMS
7/37
TOSHIBA DAIKIN Melco SANYO MITSUBISHI HVY
No.1 No.1 No.3 No.4 No.5
0.288m2 0.288m20.314m2
0.320m2
0.359m2
Outdoor unit : Foot print
Summary
-
7/30/2019 MINI SMMS
8/37
Reliability
TWIN ROTARY COMPRESSOR
Toshiba
Twin Rotary
Traditional
Compressor
New design DC Twin Rotary compressor delivers stable performances with
minimum friction: ideal for noise-sensitive applications.
The outdoor unit is almost imperceptible.
DC Twin Rotary Compressor
Low vibrations Super quiet operations
High reliability
Latest Inverter technology with the Intelligent Power Drive Unit
(IPDU): more and smaller steps for more accurate control.
It ensures optimised repetition of the sinusoidal supply current
waves at the desired frequency.
Vector Inverter technology
Wave generated by vector IPDU inverter
-
7/30/2019 MINI SMMS
9/37
3.16 2.95 3.10
2.85
3.21 3.00 3.35
3.10 2.90
Heating
DAIKIN (Super
Multi PLUS)
Cooling
HeatingAverage
3.39
-
Average - - 3.30
- - 3.40
Cooling
Cooling
Heating
Cooling
TOSHIBA
DAIKIN
(VRV -S)
Average
Average
Heating
MITSUBISHI ELE.
SANYO
MITSUBISHI HVY
Fujitsu General
3.42 3.46 3.39
3.50 3.87 3.73
- - 3.20
Heating - 3.95 -
Average - 3.85
-
Heating
Cooling
4.34 4.10 3.84Average 4.20 3.88 3.62
Cooling
- 3.91
- 3.74
3.72
4.06 3.66
-
Average -
- 3.52 -Cooling
Heating
-
3.04 3.05
4.61 4.00 3.71
4.45 4.02 3.53
3.33
64.29 4.03 3.35
5H.P. 4
COP comparison
-
7/30/2019 MINI SMMS
10/37
Average COP
2.00
2.50
3.00
3.50
4.00
4.50
5.00
TOSHIBA
DAIKIN
(VRV
2-S)
DAIKIN
(Sup
erMultiP
LUS)
Melco
SANY
O
MITS
UBISHI
HVY
Fujits
uGe
neral
Company
4HP5HP6HP
4HP/5HP No.1
COP!!!!Average COP
-
7/30/2019 MINI SMMS
11/37
Difference of With & Without PMV kit
PMV-Kit
Only for quiet space
SW setting
Without
PMV-Kit
With
PMV-Kit
-
7/30/2019 MINI SMMS
12/37
Common with S-MMS indoor units
13 type x 10 capacity
= 81 variations
New Compact 4way cassette (60X60) is connectable !
Indoor unit line-up
-
7/30/2019 MINI SMMS
13/37
Cassette TypeDuct Type
Floor Type
High Wall Type
PMV kit
PMV
PMV
PMVPMVPMV
PMV
PMV kit can be used for 6 type of indoor units.
Indoor unit with PMV kit
-
7/30/2019 MINI SMMS
14/37
Line up of indoor unit
OLine-up, New model * Available for PMV_Kit (Quieter place)
(HP) 0.8 1.0 1.3 1.7 2.0 2.5 3.0 3.2 4.0 5.0
(kW) 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0
1 4Way-cassette(600*600) * * * * *2 4Way-cassette 3 2Way-cassette 4 1Way-cassette * * * * * *5 Concealed Duct standard 6 Slim Duct * * * * *7 Ducted Hi Static 8 Celling 9 Hi Wall (1 series) * * * * * *
10 Hi Wall (2 series) * * *11 Floor Cabinet * * * * * *12 Floor Concealed 13 Floor Standing
-
7/30/2019 MINI SMMS
15/37
PMV Kit
(Mitsubishi / Daikin)
Mitsubi
shi
DaikinDaikin
-Easy installation (Compact design)
- Quieter operation
- Drain treatment free
Body size
161H X 226W X 58D
-
7/30/2019 MINI SMMS
16/37
Selection &Installation of PMV Kit
Length between PMV kit and indoor unit2m to 10m
Connection cable : 10m (Accessory)
Indoor unit capacity type Pipe diameter
RBM-PMV0361E 007, 009, 012 type 6.4mm
RBM-PMV0901E 015, 018 type 6.4mm
024 type 9.5mm
-
7/30/2019 MINI SMMS
17/37
Branching joints and headers
Common with SMMS branch kit
Model Name Usage Appearance
Y-shapeRBM-BY53E Below 6.4HP
Branching joint
RBM-BY103E 6.4HP or more
4-branching
headerRBM-HY1043E Below 7.8HP
8-branching
headerRBM-HY1083E 7.8HP or more
-
7/30/2019 MINI SMMS
18/37
:PMV unit
Y Branch after header branch
Header after Header branch
(Toshiba unique technology)
Header Branch after Y joint
(Toshiba unique technology)
Flexible joint combination
-
7/30/2019 MINI SMMS
19/37
Without PMV kit
Furthest equivalent length (L1+L2+c) 125m
Max. main pipe equivalent length (L1) 65m
Total extension (real length) (L1+L2+a+b+c) 180m
Height difference (H1)
Upper outdoor unit 30m
Lower outdoor unit 20m
Height difference (H2) Indoor - Indoor 15m
Furthest length from 1st branching (L2+c) 35m
Max. length of indoor connecting pipe ( c ) 15m
Top
Allowable Piping Design
L1a
b
c
L2
H2
H1
-
7/30/2019 MINI SMMS
20/37
With PMV kit
Furthest equivalent length (L1+L2+c+f) 80m
Max. main pipe equivalent length (L1) 50m
Total extension (real length) (L1+L2+a+b+c+d+e+f) 150m
Height difference (H1)
Upper outdoor unit 30m
Lower outdoor unit 20m
Height difference (H2) Indoor (PMV) Indoor
(PMV)
15m
Furthest length from 1st branching (L2+c) 15m
Max. length of indoor connecting pipe (c+f) 15m
Max. length between PMV kit and indoor (e/d/f) 2 to 10m
Allowable Piping Design
L1a
b
c
L2
H2
H1
d
e
f
PMV Kit
-
7/30/2019 MINI SMMS
21/37
-20
-10
0
10
20
30
40
50
Heating
15.5C WB
-15 C WB
Operating temperature range
Mini-SMMSCooling
43 C DB
-5 C DB
-
7/30/2019 MINI SMMS
22/37
(dB)
6
49/50 50/52 51/53
4 5
DAIKIN(VRV-S)
51/52
H.P.
TOSHIBA
52/53 53/5454/56DAIKIN (Super Multi PLUS) 51/53 52/54MITSUBISHI ELE. - 50(47)/52 -
53/54SANYO 51/52 52/53MITSUBISHI HVY - 53 -
56Fujitsu General - -
Outdoor : Sound level
Cooling/Heating
-
7/30/2019 MINI SMMS
23/37
All units connections are based on TCC Link control scheme.This protocol for interfacing with the full control range is a standard as likeas the SMMS controllers:
SMMS control solutions availableAutomatic network addressing TCC-Link connections with non-polarised wiring
Technologies is nothing without control
Wired remote
controller
Simple remote
controller
Weekly timer
Wireless remote
controller kit
Central remote
controller
ON/OFF controller
-
7/30/2019 MINI SMMS
24/37
Outdoor Option control : Sound reduction
TCB-PCMO2E
4HP 5HP 6HP
Normal (dB) 49/50 50/52 51/53
Sound reduction mode (dB) 46/48 46/48 47/49
Optional PCB for outdoor unit
Snow mode / Mode selection / External master ON/OFF control
are also available by TCB-PCMO2E, (option P.C.Board)
55.5 X 60 mm
For Quieter place
Night operation
-
7/30/2019 MINI SMMS
25/37
Outdoor Option control : Error output
TCB-PCIN2EOptional PCB for outdoor unit
- Error output
- Operation signal output
TCB-PCDM2E
Optional PCB for outdoor unit
- Standard (2 steps)
- Expansion (4 steps)
79 X 73 mm
Demand control
71 X 85 mm
-
7/30/2019 MINI SMMS
26/37
TCC-LINK main BUSCentral controller
TCB-SC642TLE2
Max 64 indoors
ON OFF controller
TCB-CC163TLE2
Max 16 indoors
Central control with VRF (SMMS/SHRM)
-
7/30/2019 MINI SMMS
27/37
Piping Design Program.Put together a complete system by simplyclicking on the icons.
Pipe connection and sizing
Specific details of selected unitsExport function (PDF; AutoCAD)
Multiple system management
Automatic regeneration
Indoor unit fan speed indication
Diagnostic software.For commissioning and service engineers.
Diagram of refrigerant circuit
Evualuation of indoor/outdoor units
Operating parameters downloading
Detailed informations for intant analysis.
With Toshiba everything is easer.
-
7/30/2019 MINI SMMS
28/37
Appendix
-
7/30/2019 MINI SMMS
29/37
No. Name Model name Remarks1 Main wired remote controller RBC-AMT31E Previous :AMT21E
2 Simple wired remote controller RBC-AS21E2
3 Weekly timer RBC-EXW21E2
4 Wireless remote controller kit TCB-AX21U(W)-E2 For 4-way
5 Wireless remote controller kit RBC-AX22CE2 For ceiling, 1way-SH6 Wireless remote controller kit TCB-AX21E2 For others
7 Central remote controller TCB-SC642TLE2 Max. 64 indoor unit
8 ON/OFF controller TCB-CC163TLE2 Max. 16 indoor unit
9 Remote sensor TCB-TC21LE2
10 Network adaptor TCB-PCNT20E Optional PCB11 1:1 model connection interface TCB-PCNT30TLE2 for indoor unit
12 Remote location ON/OFF control box TCB-IFCB-4E2 For indoor unit
13 External master ON/OFF control board TCB-PCMO2E Optional PCB
14 Power peak-cut control board TCB-PCDM2E for outdoor unit
15 Error output control board RCB-PCIN2E
Local control Central control Add-On control
Control Option Line-up (1)
-
7/30/2019 MINI SMMS
30/37
No. Name Model name Remarks
1 Touch screen controller BMS-TP0640ACE Max. 64 units
2 Touch screen controller BMS-TP5120ACE Max. 512 units
3 Touch screen controller BMS-TP640PWE Max. 64 units withenergy monitoring
4 Touch screen controller BMS-TP5120PWE Max. 512 units withenergy monitoring
5 TCS-Net relay interface BMS-IFLSV1E
6 Intelligent server BMS-LSV2E
7 Intelligent server software BMS-STCC01E
8 Energy monitoring relay interface BMS-IFWH3E
9 Digital I/O relay interface BMS-IFDD01E
10 LON interface TCB-IFLN640TLE Max. 64 units per I/F
11 BACnet gateway BMS-**** Max. 128 units
Stand-alone network control Open network control
Control Option Line-up (2)
-
7/30/2019 MINI SMMS
31/37
Indoor Unit Type Model NameCompact 4-way Cassette Type (600X600) RBC-UM11PG(W)E
4-way Cassette Type RBC-U21PG(W)-E2
RBC-UW136PG (AP0071- 0121)
2-Way Cassette Type RBC-UW266PG (AP0151- 0301)
RBC-UW466PG (AP0361-0561)
SH 1seires : RBC-US165PG (AP0151-0181)
1-Way Cassette Type SH 1 series : RBC-US265PG (AP0241)
YH 1 series : RBC-UY135PG (AP0071-0121)
SH 2 series : RBC-US21PGE (AP0152-0242)
1-way cassette (MMU-AP0122SH/0182SH/0242SH)
Optional parts
Front air discharge unit (TCB-BU21HWE)
Panel Option Line-up
-
7/30/2019 MINI SMMS
32/37
Name Model Name Remarks
Super Long Life Filter TCB-LF1601UE
High Efficiency Filter 65 TCB-UFM1601UE Be used with TCB-GFC1601UE
High Efficiency Filter 90 TCB-UFH1601UE
Fresh Air and Filter Chamber TCB-GFC1601UE2
Fresh Air Inlet Box TCB-GB1601UE2 Be used with TCB-GFC1601UE
Auxiliary Fresh Air Flange TCB-FF101URE2 Can be used to slim duct
Spacer for Height Adjustment TCB-SP1601UE
Air Discharge Direction Kit TCB-BC1601UE
4-Way Air Discharge Cassette (MMU-AP***1H)
Indoor unit option Line-up (1)
-
7/30/2019 MINI SMMS
33/37
Name Model Name Remarks
Spacer for Height Adjustment (TBD)
Fresh Air Chamber (TBD)
Fresh Air Inlet Box (TBD)
Air Discharge Direction Kit (TBD)
Compact 4-Way Cassette (MMU-AP***1MH)
Name Model Name Remarks
Drain Pump Kit TCB-DP22CE
Elbow Piping Kit TCB-KP12CE (AP0151- 0181) Necessary accessories when
TCB-KP22CE (AP0241- 0481) Using drain pump kit
Under Ceiling (MMC-AP***1H)
Indoor unit option Line-up (2)
-
7/30/2019 MINI SMMS
34/37
Name Model Name Remarks
TCB-UFM11BFCE (AP0071-0121/AP0241-0301) AP0241-0301 use 2 pcs.
TCB-UFM21BFCE (AP0151-0181/AP0361-0561) AP0361-0561 use 2 pcs.
High Efficiency TCB-UFM11BE (AP0071-0121)
Filter 65 TCB-UFM21BE (AP0151-0181) For underside
TCB-UFM31BE (AP0241-0301) suction
TCB-UFM41BE (AP0361-0561)
TCB-UFH51BFCE (AP0071-0121/AP0241-0301) AP0241-0301 use 2 pcs.
TCB-UFH61BFCE (AP0151-0181/AP0361-0561) AP0361-0561 use 2 pcs.
High Efficiency TCB-UFH51BE (AP0071-0121) For
Filter 90 TCB-UFH61BE (AP0151-0181) underside suction
TCB-UFH71BE (AP0241-0301)
TCB-UFH81PE (AP0361-0561)
RBC-UD281PE(W) (AP0071-0121)
Ceiling Panel RBC-UD501PE(W) (AP0151-0181) Half panel for
RBC-UD801PE(W) (AP0241-0301) underside suction
RBC-UD1401PE(W) (AP0361-0561)
Concealed Duct Standard type (MMD-AP***1BH)
Indoor unit option Line-up (3)
-
7/30/2019 MINI SMMS
35/37
Name Model Name Remarks
TCB-CA281BE (AP0071-0121)
Suction Canvas TCB-CA501BE (AP0151-0181) For underside
TCB-CA801BE (AP0241-0301) suction
TCB-CA1401BE (AP0361-0561)TCB-FC281BE (AP0071-0121)
Filter Chamber TCB-FC501BE (AP0151-0181) For rear suction
TCB-FC801BE (AP0241-0301)
TCB-FC1401BE (AP0361-0561)
TCB-FK281BE (AP0071-0121)
Filter Kit for Underside TCB-FK501BE (AP0151-0181) For underside
TCB-FK801BE (AP0241-0301) suction
TCB-FK1401BE (AP0361-0561)
Concealed Duct Standard type (MMD-AP***1BH)
Indoor unit option Line-up (4)
-
7/30/2019 MINI SMMS
36/37
Name Model Name Remarks
TCB-UFM1D-1E (AP0181/0481) AP0481 use 2 pcs.
High Efficiency Filter 65 TCB-UFM2D-1E (AP0241-0361) Use 2 pcs.
TCB-UFH5D-1E (AP0181/0481) AP0481 use 2 pcs.
High Efficiency Filter 90 TCB-UFH6D-1E (AP0241-0361) Use 2 pcs.
TCB-PF1D-1E (AP0181/0481) AP0481 use 2 pcs.
Long Life Pre-Filter TCB-PF2D-1E (AP0241-0361) Use 2 pcs.
TCB-FCY21DE (AP0961)
Filter Chamber TCB-FCY31DE (AP0241-0361)TCB-FCY51DE (AP0481)
Drain Pump Kit TCB-DP31DE (AP0181-0481)
High Static Duct (MMD-AP***1H)
Indoor unit option Line-up (5)
-
7/30/2019 MINI SMMS
37/37