    Introduction

    Line up:

    Outdoor : 4, 5, 6HP

    Indoor : same as SMMS*

    The

    new MiNi-SMMS:best performances for commercialand more private spaces.

    The great VRF traditional flexibility, reliability and energysavings can fit any room demanding application.

    Precise efficiency and control required by smaller offices,shops and quiet space applications are now available.

  • 7/30/2019 MINI SMMS

    3/37

    Design Keywords

    Superior COP (4.61/ 4HP) & high reliability

    achieved by TOSHIBAs unrivalled SMMS Technology

    Quiet operation can be further enhanced with PMV kit

    in indoor space

    Compact & Light weight outdoor unit

    Wide range of indoor unit line-up (81 variation)

    Quiet sound design of outdoor unit

    Various optional control gives great benefit and solution

  • 7/30/2019 MINI SMMS

    4/37

    Product Category

    HP 2 3

    4 5 6 8 10 48Inverter Multi

    Mini-SMMS

    Super-MMS

    2 to 4 indoor

    Max. 6 to 9 indoor

    Light Commercial

    Residential

  • 7/30/2019 MINI SMMS

    5/37

    Outdoor unit line-up

    Outdoor4HP 5HP 6HP

    Model Name MCY- MAP1401HT MAP-0501HT MAP-0601HT

    Cooling capacity (kW) 12.1 14.0 15.5

    Heating capacity (kW) 12.5 16.0 18.0Connectable indoor

    unit6 8 9

    Outdoor Diversity : 80% to 130%

  • 7/30/2019 MINI SMMS

    6/37

    Compact & Light Weight

    The extreme compactness and lightweight allows easytransportation and installation on balcony or faades with a:

    70% volume reduction*

    60% footprint reduction

    * over the standard SMMS condensing unit 5HP.

    Height1,340mm

    Depth320mmWidth

    900mm

    Weight

    117kg

  • 7/30/2019 MINI SMMS

    7/37

    TOSHIBA DAIKIN Melco SANYO MITSUBISHI HVY

    No.1 No.1 No.3 No.4 No.5

    0.288m2 0.288m20.314m2

    0.320m2

    0.359m2

    Outdoor unit : Foot print

    Summary

  • 7/30/2019 MINI SMMS

    8/37

    Reliability

    TWIN ROTARY COMPRESSOR

    Toshiba

    Twin Rotary

    Traditional

    Compressor

    New design DC Twin Rotary compressor delivers stable performances with

    minimum friction: ideal for noise-sensitive applications.

    The outdoor unit is almost imperceptible.

    DC Twin Rotary Compressor

    Low vibrations Super quiet operations

    High reliability

    Latest Inverter technology with the Intelligent Power Drive Unit

    (IPDU): more and smaller steps for more accurate control.

    It ensures optimised repetition of the sinusoidal supply current

    waves at the desired frequency.

    Vector Inverter technology

    Wave generated by vector IPDU inverter

  • 7/30/2019 MINI SMMS

    9/37

    3.16 2.95 3.10

    2.85

    3.21 3.00 3.35

    3.10 2.90

    Heating

    DAIKIN (Super

    Multi PLUS)

    Cooling

    HeatingAverage

    3.39

    -

    Average - - 3.30

    - - 3.40

    Cooling

    Cooling

    Heating

    Cooling

    TOSHIBA

    DAIKIN

    (VRV -S)

    Average

    Average

    Heating

    MITSUBISHI ELE.

    SANYO

    MITSUBISHI HVY

    Fujitsu General

    3.42 3.46 3.39

    3.50 3.87 3.73

    - - 3.20

    Heating - 3.95 -

    Average - 3.85

    -

    Heating

    Cooling

    4.34 4.10 3.84Average 4.20 3.88 3.62

    Cooling

    - 3.91

    - 3.74

    3.72

    4.06 3.66

    -

    Average -

    - 3.52 -Cooling

    Heating

    -

    3.04 3.05

    4.61 4.00 3.71

    4.45 4.02 3.53

    3.33

    64.29 4.03 3.35

    5H.P. 4

    COP comparison

  • 7/30/2019 MINI SMMS

    10/37

    Average COP

    2.00

    2.50

    3.00

    3.50

    4.00

    4.50

    5.00

    TOSHIBA

    DAIKIN

    (VRV

    2-S)

    DAIKIN

    (Sup

    erMultiP

    LUS)

    Melco

    SANY

    O

    MITS

    UBISHI

    HVY

    Fujits

    uGe

    neral

    Company

    4HP5HP6HP

    4HP/5HP No.1

    COP!!!!Average COP

  • 7/30/2019 MINI SMMS

    11/37

    Difference of With & Without PMV kit

    PMV-Kit

    Only for quiet space

    SW setting

    Without

    PMV-Kit

    With

    PMV-Kit

  • 7/30/2019 MINI SMMS

    12/37

    Common with S-MMS indoor units

    13 type x 10 capacity

    = 81 variations

    New Compact 4way cassette (60X60) is connectable !

    Indoor unit line-up

  • 7/30/2019 MINI SMMS

    13/37

    Cassette TypeDuct Type

    Floor Type

    High Wall Type

    PMV kit

    PMV

    PMV

    PMVPMVPMV

    PMV

    PMV kit can be used for 6 type of indoor units.

    Indoor unit with PMV kit

  • 7/30/2019 MINI SMMS

    14/37

    Line up of indoor unit

    OLine-up, New model * Available for PMV_Kit (Quieter place)

    (HP) 0.8 1.0 1.3 1.7 2.0 2.5 3.0 3.2 4.0 5.0

    (kW) 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0

    1 4Way-cassette(600*600) * * * * *2 4Way-cassette 3 2Way-cassette 4 1Way-cassette * * * * * *5 Concealed Duct standard 6 Slim Duct * * * * *7 Ducted Hi Static 8 Celling 9 Hi Wall (1 series) * * * * * *

    10 Hi Wall (2 series) * * *11 Floor Cabinet * * * * * *12 Floor Concealed 13 Floor Standing

  • 7/30/2019 MINI SMMS

    15/37

    PMV Kit

    (Mitsubishi / Daikin)

    Mitsubi

    shi

    DaikinDaikin

    -Easy installation (Compact design)

    - Quieter operation

    - Drain treatment free

    Body size

    161H X 226W X 58D

  • 7/30/2019 MINI SMMS

    16/37

    Selection &Installation of PMV Kit

    Length between PMV kit and indoor unit2m to 10m

    Connection cable : 10m (Accessory)

    Indoor unit capacity type Pipe diameter

    RBM-PMV0361E 007, 009, 012 type 6.4mm

    RBM-PMV0901E 015, 018 type 6.4mm

    024 type 9.5mm

  • 7/30/2019 MINI SMMS

    17/37

    Branching joints and headers

    Common with SMMS branch kit

    Model Name Usage Appearance

    Y-shapeRBM-BY53E Below 6.4HP

    Branching joint

    RBM-BY103E 6.4HP or more

    4-branching

    headerRBM-HY1043E Below 7.8HP

    8-branching

    headerRBM-HY1083E 7.8HP or more

  • 7/30/2019 MINI SMMS

    18/37

    :PMV unit

    Y Branch after header branch

    Header after Header branch

    (Toshiba unique technology)

    Header Branch after Y joint

    (Toshiba unique technology)

    Flexible joint combination

  • 7/30/2019 MINI SMMS

    19/37

    Without PMV kit

    Furthest equivalent length (L1+L2+c) 125m

    Max. main pipe equivalent length (L1) 65m

    Total extension (real length) (L1+L2+a+b+c) 180m

    Height difference (H1)

    Upper outdoor unit 30m

    Lower outdoor unit 20m

    Height difference (H2) Indoor - Indoor 15m

    Furthest length from 1st branching (L2+c) 35m

    Max. length of indoor connecting pipe ( c ) 15m

    Top

    Allowable Piping Design

    L1a

    b

    c

    L2

    H2

    H1

  • 7/30/2019 MINI SMMS

    20/37

    With PMV kit

    Furthest equivalent length (L1+L2+c+f) 80m

    Max. main pipe equivalent length (L1) 50m

    Total extension (real length) (L1+L2+a+b+c+d+e+f) 150m

    Height difference (H1)

    Upper outdoor unit 30m

    Lower outdoor unit 20m

    Height difference (H2) Indoor (PMV) Indoor

    (PMV)

    15m

    Furthest length from 1st branching (L2+c) 15m

    Max. length of indoor connecting pipe (c+f) 15m

    Max. length between PMV kit and indoor (e/d/f) 2 to 10m

    Allowable Piping Design

    L1a

    b

    c

    L2

    H2

    H1

    d

    e

    f

    PMV Kit

  • 7/30/2019 MINI SMMS

    21/37

    -20

    -10

    0

    10

    20

    30

    40

    50

    Heating

    15.5C WB

    -15 C WB

    Operating temperature range

    Mini-SMMSCooling

    43 C DB

    -5 C DB

  • 7/30/2019 MINI SMMS

    22/37

    (dB)

    6

    49/50 50/52 51/53

    4 5

    DAIKIN(VRV-S)

    51/52

    H.P.

    TOSHIBA

    52/53 53/5454/56DAIKIN (Super Multi PLUS) 51/53 52/54MITSUBISHI ELE. - 50(47)/52 -

    53/54SANYO 51/52 52/53MITSUBISHI HVY - 53 -

    56Fujitsu General - -

    Outdoor : Sound level

    Cooling/Heating

  • 7/30/2019 MINI SMMS

    23/37

    All units connections are based on TCC Link control scheme.This protocol for interfacing with the full control range is a standard as likeas the SMMS controllers:

    SMMS control solutions availableAutomatic network addressing TCC-Link connections with non-polarised wiring

    Technologies is nothing without control

    Wired remote

    controller

    Simple remote

    controller

    Weekly timer

    Wireless remote

    controller kit

    Central remote

    controller

    ON/OFF controller

  • 7/30/2019 MINI SMMS

    24/37

    Outdoor Option control : Sound reduction

    TCB-PCMO2E

    4HP 5HP 6HP

    Normal (dB) 49/50 50/52 51/53

    Sound reduction mode (dB) 46/48 46/48 47/49

    Optional PCB for outdoor unit

    Snow mode / Mode selection / External master ON/OFF control

    are also available by TCB-PCMO2E, (option P.C.Board)

    55.5 X 60 mm

    For Quieter place

    Night operation

  • 7/30/2019 MINI SMMS

    25/37

    Outdoor Option control : Error output

    TCB-PCIN2EOptional PCB for outdoor unit

    - Error output

    - Operation signal output

    TCB-PCDM2E

    Optional PCB for outdoor unit

    - Standard (2 steps)

    - Expansion (4 steps)

    79 X 73 mm

    Demand control

    71 X 85 mm

  • 7/30/2019 MINI SMMS

    26/37

    TCC-LINK main BUSCentral controller

    TCB-SC642TLE2

    Max 64 indoors

    ON OFF controller

    TCB-CC163TLE2

    Max 16 indoors

    Central control with VRF (SMMS/SHRM)

  • 7/30/2019 MINI SMMS

    27/37

    Piping Design Program.Put together a complete system by simplyclicking on the icons.

    Pipe connection and sizing

    Specific details of selected unitsExport function (PDF; AutoCAD)

    Multiple system management

    Automatic regeneration

    Indoor unit fan speed indication

    Diagnostic software.For commissioning and service engineers.

    Diagram of refrigerant circuit

    Evualuation of indoor/outdoor units

    Operating parameters downloading

    Detailed informations for intant analysis.

    With Toshiba everything is easer.

  • 7/30/2019 MINI SMMS

    28/37

    Appendix

  • 7/30/2019 MINI SMMS

    29/37

    No. Name Model name Remarks1 Main wired remote controller RBC-AMT31E Previous :AMT21E

    2 Simple wired remote controller RBC-AS21E2

    3 Weekly timer RBC-EXW21E2

    4 Wireless remote controller kit TCB-AX21U(W)-E2 For 4-way

    5 Wireless remote controller kit RBC-AX22CE2 For ceiling, 1way-SH6 Wireless remote controller kit TCB-AX21E2 For others

    7 Central remote controller TCB-SC642TLE2 Max. 64 indoor unit

    8 ON/OFF controller TCB-CC163TLE2 Max. 16 indoor unit

    9 Remote sensor TCB-TC21LE2

    10 Network adaptor TCB-PCNT20E Optional PCB11 1:1 model connection interface TCB-PCNT30TLE2 for indoor unit

    12 Remote location ON/OFF control box TCB-IFCB-4E2 For indoor unit

    13 External master ON/OFF control board TCB-PCMO2E Optional PCB

    14 Power peak-cut control board TCB-PCDM2E for outdoor unit

    15 Error output control board RCB-PCIN2E

    Local control Central control Add-On control

    Control Option Line-up (1)

  • 7/30/2019 MINI SMMS

    30/37

    No. Name Model name Remarks

    1 Touch screen controller BMS-TP0640ACE Max. 64 units

    2 Touch screen controller BMS-TP5120ACE Max. 512 units

    3 Touch screen controller BMS-TP640PWE Max. 64 units withenergy monitoring

    4 Touch screen controller BMS-TP5120PWE Max. 512 units withenergy monitoring

    5 TCS-Net relay interface BMS-IFLSV1E

    6 Intelligent server BMS-LSV2E

    7 Intelligent server software BMS-STCC01E

    8 Energy monitoring relay interface BMS-IFWH3E

    9 Digital I/O relay interface BMS-IFDD01E

    10 LON interface TCB-IFLN640TLE Max. 64 units per I/F

    11 BACnet gateway BMS-**** Max. 128 units

    Stand-alone network control Open network control

    Control Option Line-up (2)

  • 7/30/2019 MINI SMMS

    31/37

    Indoor Unit Type Model NameCompact 4-way Cassette Type (600X600) RBC-UM11PG(W)E

    4-way Cassette Type RBC-U21PG(W)-E2

    RBC-UW136PG (AP0071- 0121)

    2-Way Cassette Type RBC-UW266PG (AP0151- 0301)

    RBC-UW466PG (AP0361-0561)

    SH 1seires : RBC-US165PG (AP0151-0181)

    1-Way Cassette Type SH 1 series : RBC-US265PG (AP0241)

    YH 1 series : RBC-UY135PG (AP0071-0121)

    SH 2 series : RBC-US21PGE (AP0152-0242)

    1-way cassette (MMU-AP0122SH/0182SH/0242SH)

    Optional parts

    Front air discharge unit (TCB-BU21HWE)

    Panel Option Line-up

  • 7/30/2019 MINI SMMS

    32/37

    Name Model Name Remarks

    Super Long Life Filter TCB-LF1601UE

    High Efficiency Filter 65 TCB-UFM1601UE Be used with TCB-GFC1601UE

    High Efficiency Filter 90 TCB-UFH1601UE

    Fresh Air and Filter Chamber TCB-GFC1601UE2

    Fresh Air Inlet Box TCB-GB1601UE2 Be used with TCB-GFC1601UE

    Auxiliary Fresh Air Flange TCB-FF101URE2 Can be used to slim duct

    Spacer for Height Adjustment TCB-SP1601UE

    Air Discharge Direction Kit TCB-BC1601UE

    4-Way Air Discharge Cassette (MMU-AP***1H)

    Indoor unit option Line-up (1)

  • 7/30/2019 MINI SMMS

    33/37

    Name Model Name Remarks

    Spacer for Height Adjustment (TBD)

    Fresh Air Chamber (TBD)

    Fresh Air Inlet Box (TBD)

    Air Discharge Direction Kit (TBD)

    Compact 4-Way Cassette (MMU-AP***1MH)

    Name Model Name Remarks

    Drain Pump Kit TCB-DP22CE

    Elbow Piping Kit TCB-KP12CE (AP0151- 0181) Necessary accessories when

    TCB-KP22CE (AP0241- 0481) Using drain pump kit

    Under Ceiling (MMC-AP***1H)

    Indoor unit option Line-up (2)

  • 7/30/2019 MINI SMMS

    34/37

    Name Model Name Remarks

    TCB-UFM11BFCE (AP0071-0121/AP0241-0301) AP0241-0301 use 2 pcs.

    TCB-UFM21BFCE (AP0151-0181/AP0361-0561) AP0361-0561 use 2 pcs.

    High Efficiency TCB-UFM11BE (AP0071-0121)

    Filter 65 TCB-UFM21BE (AP0151-0181) For underside

    TCB-UFM31BE (AP0241-0301) suction

    TCB-UFM41BE (AP0361-0561)

    TCB-UFH51BFCE (AP0071-0121/AP0241-0301) AP0241-0301 use 2 pcs.

    TCB-UFH61BFCE (AP0151-0181/AP0361-0561) AP0361-0561 use 2 pcs.

    High Efficiency TCB-UFH51BE (AP0071-0121) For

    Filter 90 TCB-UFH61BE (AP0151-0181) underside suction

    TCB-UFH71BE (AP0241-0301)

    TCB-UFH81PE (AP0361-0561)

    RBC-UD281PE(W) (AP0071-0121)

    Ceiling Panel RBC-UD501PE(W) (AP0151-0181) Half panel for

    RBC-UD801PE(W) (AP0241-0301) underside suction

    RBC-UD1401PE(W) (AP0361-0561)

    Concealed Duct Standard type (MMD-AP***1BH)

    Indoor unit option Line-up (3)

  • 7/30/2019 MINI SMMS

    35/37

    Name Model Name Remarks

    TCB-CA281BE (AP0071-0121)

    Suction Canvas TCB-CA501BE (AP0151-0181) For underside

    TCB-CA801BE (AP0241-0301) suction

    TCB-CA1401BE (AP0361-0561)TCB-FC281BE (AP0071-0121)

    Filter Chamber TCB-FC501BE (AP0151-0181) For rear suction

    TCB-FC801BE (AP0241-0301)

    TCB-FC1401BE (AP0361-0561)

    TCB-FK281BE (AP0071-0121)

    Filter Kit for Underside TCB-FK501BE (AP0151-0181) For underside

    TCB-FK801BE (AP0241-0301) suction

    TCB-FK1401BE (AP0361-0561)

    Concealed Duct Standard type (MMD-AP***1BH)

    Indoor unit option Line-up (4)

  • 7/30/2019 MINI SMMS

    36/37

    Name Model Name Remarks

    TCB-UFM1D-1E (AP0181/0481) AP0481 use 2 pcs.

    High Efficiency Filter 65 TCB-UFM2D-1E (AP0241-0361) Use 2 pcs.

    TCB-UFH5D-1E (AP0181/0481) AP0481 use 2 pcs.

    High Efficiency Filter 90 TCB-UFH6D-1E (AP0241-0361) Use 2 pcs.

    TCB-PF1D-1E (AP0181/0481) AP0481 use 2 pcs.

    Long Life Pre-Filter TCB-PF2D-1E (AP0241-0361) Use 2 pcs.

    TCB-FCY21DE (AP0961)

    Filter Chamber TCB-FCY31DE (AP0241-0361)TCB-FCY51DE (AP0481)

    Drain Pump Kit TCB-DP31DE (AP0181-0481)

    High Static Duct (MMD-AP***1H)

    Indoor unit option Line-up (5)

  • 7/30/2019 MINI SMMS

    37/37