Mini IO Controller - Maxon Solutions

2
Turn your Smartmax M2M HSPA Smart Modem Solution into a cost-effective mini RTU with the I/O Interface Controller. When used in conjunction with Maxon’s Smartmax Modem for data telemetry, the I/O Interface Controller provides wide-ranging flexibility for system integrators and users for automating and controlling innumerable field applications. Local or remote programming of the I/O Interface Controller can be done via the Smartmax’s built- in Web Interface. The fully featured web interface includes programming of the DNP3 settings and I/O status updates via SMS. The SmartMax connects directly to the IO board via a ribbon connection, while the I/O controller can be wired to collect data automatically and connect directly to sensors, meters, loggers or process equipment. 081112 TRANSFORM THE SMARTMAX INTO A POWERFUL COST-EFFECTIVE MINI REMOTE TERMINAL UNIT Smartmax I/O Board Features • 6 Digital Inputs (1 configurable as pulse input) • 2 Analogue Inputs • 4 Digital Outputs • 1 Pulse Input • DNP3/SMS Settings configurable via web page inside Smartmax Modem. • I/O Board controllable via DNP3, SMS, or using inbuilt web page. • SDK (Software Development Kit) is available for the Smartmax HSPA Modem (Product Code: MA-2010) * Not to scale CHOOSE WELL... CHOOSE WISELY... CHOOSE MAXON... M2M HSPA Smart Modem Solution - The Mini I/O Controller MA-3020 is a fully labelled , robust enclosure that secures the I/O Board. This solution provides an all-in-one product.

description

Mini IO Controller is covered with robust plastic case and screw terminal connections. It is meant for sturdy connection, analog and digital interfaces of Smartmax modems. I/O controller provides high range flexibility when attached with Maxon's Smartmax Modem for data transmission and helps in controlling limitless applications. Smartmax’s built-in Web Interface or via the maXconnect portal helps for local or remote programming of I/O interface controller.

Transcript of Mini IO Controller - Maxon Solutions

Page 1: Mini IO Controller - Maxon Solutions

Turn your Smartmax M2M HSPA Smart Modem Solution into a cost-effective mini RTU with the I/O Interface Controller. When used in conjunction with Maxon’s Smartmax Modem for data telemetry,

the I/O Interface Controller provides wide-ranging flexibility for system integrators and users for automating and controlling innumerable field applications.

Local or remote programming of the I/O Interface Controller can be done via the Smartmax’s built-in Web Interface. The fully featured web interface includes programming of the DNP3 settings and

I/O status updates via SMS.

The SmartMax connects directly to the IO board via a ribbon connection, while the I/O controller can be wired to collect data automatically and connect directly to sensors, meters, loggers or

process equipment.

0811

12

TRANSFORM THE SMARTMAX INTO A POWERFUL COST-EFFECTIVE MINI REMOTE TERMINAL UNIT

Smartmax I/O Board Features• 6 Digital Inputs (1 configurable as pulse input)

• 2 Analogue Inputs

• 4 Digital Outputs

• 1 Pulse Input • DNP3/SMS Settings configurable via web page inside Smartmax Modem.

• I/O Board controllable via DNP3, SMS, or using inbuilt web page. • SDK (Software Development Kit) is available for the Smartmax HSPA Modem (Product Code: MA-2010)

* Not

to s

cale

CHOOSE WELL... CHOOSE WISELY... CHOOSE MAXON...

M2M HSPA Smart Modem Solution - I/O Board: MA-4020

The Mini I/O Controller MA-3020 is a fully labelled , robust enclosure that secures the I/O Board. This solution provides an all-in-one product.

Page 2: Mini IO Controller - Maxon Solutions

www.maxon.com.au

Metering

Water

Road Signs

Power

Security

Transport

M2M HSPA Smart Modem Solution - I/O Board: MA-4020

T | +612 8707 3000 F | +612 8707 3001 E | [email protected] 36A Gibson Avenue, Padstow NSW Austral ia 2211 www.maxon.com.au

Environmental Specifications• Normal Operation Temperature -20 to 60° C

• Extreme Operation Temperature -25 to 75° C

Connections• 6 x Digital Inputs (INPUT 0 ~ INPUT 5 in terminal block)

• 4 x Digital Outputs (OUTPUT 0 ~ OUTPUT 3 in terminal block)

• 2 x Analog Inputs (ANALOG 0 and ANALOG 1)

• 1 x Pulse Input (INPUT 0)

• 1 x Case Open

• 1 x Battery (Monitor Battery Level)

• 1 x 20 Pin Terminal Block (SmartMax Interface)

Compliance• RoHS Compliant

Frequency Bands• WCDMA/HSPA 850MHz, 900MHz, 1900MHz, 2100MHz

• GSM/GPRS/EDGE 850MHz, 900MHz, 1800MHz and 1900MHz

General Features• Packet Data

• 2 Way SMS

• Remote SMS diagnostics & reset

• Embedded TCP/IP, UDP/IP STACK

• In-built periodic reset

• External DC Powered

• Support VPN Server and Client Mode

• Dynamic DNS

• Supports DNP3 (Outstation) using extension I/O board

• Rugged Metal Casing for industrial use

• In-Built Web Interface

• Programmable scheduler to control WAN connection

• Telnet support

• Save and restore modem configuration from a file

• FOTA - Firmware upgrade over the air

• External antenna connectivity to maximise HSPA coverage

• External LED to show Network and Connection status

Dimensions• 210mm X 1100mm X 650mm (with connectors)

Connection Specifications6 Digital Inputs Characteristics

· VIH (Input voltage high range): 2 ~ 24V

· VIL (Input voltage low range): -2 ~ 0.8V

· Ri (Input impedance): more than 5 kΩ

· Rd (Internal pull-up): 47 kΩ for short to ground detection

· Input chatters are filtered by S/W setting

1 Pulse at Input 0

· Frequency range 0 ~ 1000 Hz

· Accuracy (25°C) 0.05 % of span

· Temperature stability 0.005 % / °C

· Input impedance 47kΩ

4 Digital Outputs

· MOSFET switch to ground

· Ro (Output resistance): less than 300 m Ω

· VOpen (maximum allowed output voltage on open): 24 VDC

· IOut (maximum allowed switching current to ground): 1A

· Switching time < 10 msec

· Chatter free

2 Analog Inputs

· 12bit resolution

· Accuracy: Typical ±0.25% ; Worst Case ±1%

· Maximum sampling rate: 10 sample/sec

· Input signal type: one of 0~20mA, 0~5V, or 0~10V

· (The input type is selected by the jumper “PULSE” on the connected Smartmax and INPUT# on the I/O board)

· Input impedance for the signal type 0 ~ 20mA < 100Ω

· Input impedance for the signal type 0 ~ 10VDC > 10K Ω