MIL8013_instructionManual
-
Upload
masud-alam -
Category
Documents
-
view
753 -
download
129
Transcript of MIL8013_instructionManual
Purchase Order No. :
The following instructions should be thoroughlyreviewed and understood prior to installing,operating or performing maintenance on thisequipment. Throughout the text, safety and/or
caution notes will appear and must be strictly adhered to,otherwise, serious injury or equipment malfunction could result.
Instruction Manual
INS/8013/REV-B/03-2006
ISO 9001 : 2000Certificate : 04100 2002 0157
MIL 8013
Electropneumatic Valve Positioner
MIL Controls Limited
2
the air supply contains large amounts of moisture, make
provision to remove it before the air reaches the filter-
regulator in the supply piping. Adjust the regulator
to required reduced actuator supply pressure.\
Output Air: The 1/4" NPT output pressure connectionis located on the relay and is marked by an arrow. Use1/4" OD tubing between this connection and theconnection in the actuator diaphragm case.
Installation**
**Warning :De-energise the electrical and pneumatic circuits, prior to any servicing or maintenance. Ensure all pneumaticand electrical connections are provided correctly, and the cover is in place, before energising the positioner
Note: Easily replaceable pressure gauges for air sets and externally mounted pressure gauges of positionersare normally dismantled, separately packed and bound to the actuator yoke as a precaution against transitdamages. This may be noted while opening the boxes.
Figure 1 - Mounting
Caution : The equipment has left the factory in a perfect
condition as regard safety. The notes and warnings
in these "Instructions" must be observed by the user
if this state is to be maintained and hazard-free
operation of the equipment assured.
Caution: For flame proof instruments, the positioner
cover should not be opened in the hazardous area,
when energised.
Location
Two factors should be considered for the location of
the positioner:
1. Temperature: Avoid locations which are subject
to wide ambient temperature variations. If control
valve is subject to subfreezing temperature, special
provision must be made for drying positioner air
supply.
2. Vibration: If possible, avoid locations where vibration
occurs.
The positioner may be used for either direct (air-to-
close) or reverse (air-to-open) diaphragm actuators. The
direction of actuator stem motion for an increase in
diaphragm pressure determines the mounting of the
positioner on the actuator.
On direct actuators, the positioner is mounted to the
left of the actuator stem and the positioner backlever
extends to the right of the positioner.
On reverse actuators, the mounting bracket is turned
over; the positioner is mounted to the right of the
actuator stem and the backlever is positioned to extend
to the left of the positioner.
Air Piping (Fig. 1)
Supply Air: The 1/4" NPT air supply connection is
located on the relay and is marked by an arrow. Use
1/4" OD tubing for piping supply air to the positioner.
On long runs, use larger diameter tubing or pipe. If
Caution: Do not place watches or delicate instruments
near the positioner since it employs a powerful Alnico
V Magnet.
Mounting (Fig. 1)
The positioner is rigidly mounted on the actuator
mounting pad by means of a mounting plate.
3
Linkage Assembly (Fig. 2)
When the positioner has been mounted
on the actuator, the take-off clamp is
attached to the actuator stem at a point
which permits full actuator stem travel.
The turnbuckle is installed in a vertical
position between the clamp rod and
the clevis. The lower end of the
turnbuckle has been machined round
to identify the right hand thread which
engages the turnbuckle screw.
Installation (Cont....)
Figure 2 - Take-Off Clamp S/A
General
The positioner is a force-balance
electropneumatic device which provides
an accurate means of obtaining a valve
stem position directly proportional to
a DC input signal. In addition, the
positioner provides a convenient means
of split-ranging controller output signal
for sequential operation of two control
valves by a single controller. It may
have either direct or reverse action on
either direct or reverse actuators.Figure 3
Diagrammatic of Operation
Direct Action
With direct positioner action, an increase
in the input signal produces a force on
the beam, moving the flapper to cover
the nozzle. The increase in nozzle back
pressure increases positioner output
pressure to the actuator. The resultant
valve stem motion is transmitted to the
force-balance spring, extending the
spring until the force exerted on the
beam balances the opposing force of
the coil. As these two forces equalize,
Operation (Fig. 3,4)
Take-off Clamp
Clevis (28)
Turnbuckle (60)
Turnbuckle Screw (62)Locknut (61)
Clamp Rod (63)(Take-Off-Linkage)
Clamp Screw(64)
Figure 4 - Cross Sectional View
745916 46 8 12 41 6 52B 49
50
44
39
11
40 5B 5A 5C
3
31B3531A
31D
72 7131G1524
321420 22
3 - Cover5A - Upper pole piece5B - Lower pole piece5C - Magnet
6 - Adjusting screw(Force balance spring)
8 - Spring (Force balance)11 - Biasing Spring
AdjustingScrew (Zero)
12 - Force Balance Spring \Adjusting Nuts
14 - Case15 - Terminal board (S/A)16 - Nozzle20 - Relay (S/A)22 - Mounting bracket24 - Cover plate
(Stroke adjustment)31A - Lever (Stroke adjustment)
31B - Pin (Lever stroke adj.)31D - Pinion31G - Index lockscrew
32 - Stroke lever (S/A)35 - Back lever adapter (S/A)39 - Spring bracket40 - Coil (S/A)41 - Beam44 - Machine screw (Coil stop)46 - Flapper
49 - Flexure50 - Flexure
52B - Biasing spring59 - Metering tube (S/A)71 - Bearing post
(Back lever adapter)72 - Bearing post
(Lever stroke adjustment)74 - Flame arrestor
4
CIRCLIP
PINION
(31D)
INDEX LOCK SCREW
(31G)
RELAY (S/A)
(20)
BACK LEVER
LEVER (31A)
(STROKE
ADJUSTMENT)
INDEX
STROKE
LEVER (S/A)
(32)
Adjustments (Fig.2, 4, 4A, 4B)
nozzle back pressure decreases. The system then is in
equilibrium and positioner output is stabilized at an
amount necessary to maintain the desired control valve
plug position.
When the forces on beam are in equilibrium, there is,
theoretically, no flow of air into or out from the relay.
Actually, a small bleed is provided between supply and
output to increase relay responsiveness.
Reverse Action
With reverse positioner action, an increase in the input
signal produces a decrease in output pressure.
Operation (Fig. 3,4) (Cont....)
Figure 4A
Figure 4B
BIASING SPRING ADJUSTING
SCREW (ZERO)
(11)
BIASING
SPRING
(52B)
BEAM
(41)
TERMINAL
BOARD (S/A) (15)
FLAPPER(46)
(12)
FORCE BALANCE SPRING
ADJUSTING NUTS
(8)
SPRING
(FORCE BALANCE)
(16)
FORCE BALANCE SPRING
ADJUSTING SCREW
(5C)
MAGNET
(40) COIL S/A
5
Stroke: Matches the valve stem travel to a given
range of positioner input signal. This adjustment is
accomplished by loosening the index lockscrew (31 G)
and rotating the pinion (31 D) with a screwdriver until
the index is at the correct stroke value.
Force-Balance Spring: Primarily an adjustment for
calibrating the stroke scale to compensate for variation
in coil strength. A full input signal change should fully
stroke the valve stem when the index is at the correct
stroke value. If valve stem travel is less than rated stroke,
loosen locknut and turn adjusting screw (6) counter-
clockwise. Retighten locknut.
Biasing Spring: Exerts a force on the beam to
establish proper position of the stroke levers with respect
to the positioner Input signal range. The stroke lever
(32) should be parallel to the slot in the stroke adjust-
ment lever (31 A) at midpoint of the positioner input
signal. This parallelism is obtained by adjusting of biasing
spring adjusment screw (11).
Turnbuckle: Matches valve stem position with
input signal. This adjustment is made, with controller
output signal at midrange, by rotating the turnbuckle
(60) until the valve stem is at midstroke. After making
adjustment, tighten the locknut (61)
Adjustments (Fig.2, 4, 4A, 4B)
Calibration
MIL 8013 Positioners, when furnished with MIL valves,
are factory mounted and calibrated for the rated stroke,
the action and the DC input signal range specified.
Note: No further calibration is required in the field.
In the event a positioner is supplied for field mounting,
or reversal of the positioner action in the field is
required, the following steps should be taken after first
making certain the valve is properly adjusted:
Step 1. Mount positioner, connect input signal leads,
air piping and linkage assembly as directed
under installation.
Step 2. Loosen index lockscrew (31 G) and rotate the
pinion (31 D) with a screwdriver until the
stroke index is opposite the marking on the
stroke scale corresponding to the rated
stroke of the valve.
Step 3. With proper supply pressure to the positioner;
set controller for midpoint of positioner input
signal range; e.g., 12 mA for a signal range
of 4-20 mA.
Step 4. Adjust biasing spring (52 B) (See
"Adjustments") until the inside edge of the
stroke lever (32) is parallel to the slot in the
stroke adjustment lever (31 A).
Step 5. Rotate the turnbuckle (60) until the valve
is at midstroke and recheck parallelism of
stroke and stroke adjustment levers. If nece-
ssary, repeat Steps 4 and 5 until the levers
are parallel and the valve is at midstroke
with the controller at midpoint of output
signal range.
Step 6. Set controller for minimum of positioner input
signal range (eg: 4 mA) and observe valve
position as indicated on the valve travel plate.
Step 7. Change controller setting for maximum of
positioner input range (eg: 20 mA) and check
valve stem travel. If more than rated stroke,
loosen lock-nut and turn force-balance spring
adjusting screw (6) clockwise; If less than
rated stroke, turn adjusting screw
counterclockwise, until valve indicator disk
indicates correct valve position. Tighten
locknut.
Step 8. Set controller for midpoint of positioner input
signal range and check to make certain that
stroke lever is still parallel to the slot in the
stroke adjustment lever and valve is at mid-
stroke. If incorrect, repeat Steps 4 to 8 until
the positioner input signal range matches the
rated stroke of the valve and, with positioner
input signal at midrange, the levers are parallel
when the valve is at midstroke.
Relay (Fig. 5)
Metering Tube
The metering tube for the nozzle air supply is furnished
with a clean-out plunger which forces a small wire
through the jewel orifice.
Disassembly
The metering tube body may be removed without remo-
ving the relay from the instrument case. If further
disassembly of the relay is required, proceed as follows:
Step 1. Disconnect air supply and output tubing.
Maintenance
6
Step 2. Unscrew the four mounting screws and
remove relay from instrument case.
Step 3. Remove holding screw and drop spring and
plug from relay body.
Step 4. Remove six screws holding relay cap, dia-
phragm S/A, bellofram plate S/A. gasket and
spring to relay body.
Step 5. Clean parts with soft cloth. Use solvent if
oil or grease is present. (Do not use solvent
on diaphragm or gasket). Blow out port with
clean air.
Reassembly
Step 1. Replace spring and position gasket on relay
body.
Step 2. Reassemble and align holes in relay cap,
diaphragm S/A and bellofram plate S/A. Insert
two screws, 1800 apart, through this assembly.
Step 3. Position assembly on spring and then, being
careful to align holes, exert sufficient down-
ward pressure on this assembly to engage
screws in relay body. Make certain that gasket
is properly seated before tightening screws.
Step 4. Insert remaining screws, replace relay plug,
spring and holding screw in relay body.
Step 5. Establish desired relay position and fasten
relay to instrument case.
Nozzle
To clean nozzle, shut off air supply; loosen screw
holding flapper to beam. Remove flapper and unscrew
nozzle from case. Clean nozzle with solvent and
blow out hole with clean air, Screw nozzle into case,
replace flapper on beam and tighten screw.
Beam alignment
The beam has been aligned at the factory and should
not require realignment unless the flexures are damaged
or it becomes necessary to replace the coil.
To Replace Flexures:
Step 1. Remove positioner from valve.
Step 2. Remove positioner cover and disconnect (or
unsolder *) coil leads from the terminal board.
Step 3. Disengage the end of the force balance spring
attached to the force balance spring
adjusting screw.
Step 4. Remove the two upper pole piece screws and
lift the entire operating mechanism from
the case.
Step 5. Remove biasing spring screw, releasing biasing
spring from the beam.
Step 6. Remove four screws joining flexures, upper
pole piece and beam.
Maintenance (Cont ....)
Figure 5 - Relay
7
Figure 6 - Coil Replacement
Step 7. Replace damaged flexures and reattach beam
to upper pole piece with flexures and screws.
Do not tighten scews.
Step 8. Replace coil, if necessary, and/or realign beam
as described in following sections.
To Replace Coil (Fig. 6)
Step 1. Same as Steps 1 to 6 for replacing flexures.
Step 2. Unscrew coil and machine screws, freeing coil
from beam.
Step 3. Attach replacement coil loosely to the beam
with coil and machine screws.
Note: Machine screw (44) should not extend into the
coil bobbin.
Step 4. Reattach beam to upper pole piece with
flexures and screws. Do not tighten screws.
Step 5. Align beam.
To Align Beam (Fig. 7)step 1. Insert 1/8" diameter rod into alignment hole
and underneath the beam, as near as possible
to the the coil, a wedge which is 5/32" high
and 1/32" in thickness (Fig. 7). Rod and
wedge material should be nonmagnetic.
Step 2. Tighten lower screws (two) of inner flexure
and lower screws (two) of outer flexure to
beam and upper pole piece, respectively.
Step 3. Replace operating mechanism in case. Position
biasing spring bracket and tighten in position
with two mounting screws.
Step 4. Exerting downward pressure on beam
between 5/32" high wedge and nozzle,
tighten four remaining flexure screws.
Step 5. Tighten the coil screw and remove alignment
rod and wedge.
Step 6. Adjust machine screw (44) so that flapper
travel is 1/32".
Step 7. Reattach biasing spring (52 B) to beam with
biasing spring nut.
Step 8. Engage force balance spring (8) with force
balance spring adjusting screw (6).
* Only in case of a positioner incorporated with intrinsic security circuit. This operation must be carried out outside of any hazardous location.
Maintenance (Cont....)
Figure 7 - Beam Alignment
8
Terminal Board Replacement
If it becomes necessary to change the terminal board,
proceed as follows.
Step 1. Remove operating mechanism from case as
described in Steps 1 through 4 for replacing
flexures.
Step 2. Unscrew the two screws holding terminal
board to case.
General
The following conditions are necessary for trouble free
operation:
1. Proper supply pressure, i.e., 20 psi or 35 psi.
2. Proper electrical current for input signal.
3. Proper size nozzle and metering tube as indicated
below and stamped on the component.
disassemble and clean relay (see “Main-
tenance”).
Electrical Circuits
After checking pneumatic circuit, the electrical circuit
should be checked with an ohmmeter as follows:
Step 1. Disconnect controller signal leads from
positioner.
Step 2. Connect ohmmeter leads to positioner
terminal posts and check positioner circuit
resistance with value indicated on serial plate.
Step 3. Disconnect (or unsolder *) coil lead from
positive terminal and connect it to one of
the ohmmeter leads. Connect other
ohmmeter lead to negative terminal. Coil
resistance value should approximate to 173
Ohms +_ 5%
Step 4. If coil resistance is approximately correct but
positioner circuit resistance is not, replace
terminal board. If coil resistance is not correct
replace coil.
Step 5. Remove ohmmeter lead from negative
terminal and connect it to machine screw
(44), check for short in coil. Replace coil if
ohmmeter indicates a value other than infinite
resistance.
Caution : All Maintenance work to be carried out outside
the hazardous area if instrument is Flame Proof /
Explosion proof certified.
* Only in case of a positioner incorporated with intrinsic
security circuit. This operation must be carried out outside
of any hazardous location
Maintenance (Cont....)
Trouble Shooting
NozzleNumber
20 psi Supply 35 psi Supply
11 11 11
13 12 11
15 13 12
18 13 12
24 13 13
MILActuator
Size
4. All components fastened firmly as required.
5. Machine screw (44) adjusted to allow approximately
1/32" flapper travel.
Pneumatic Circuit
In the event of faulty operation of the positioner, where
the cause is not readily apparent, check air system as
follows:
Step 1. Exert sufficient force on the flapper to cover
the nozzle. Valve stem should travel its full
stroke.
Step 2. If response is other than indicated in the
above steps, push cleanout plunger of
metering tube. Inspect for plugged nozzle.
Check to see metering tube body is properly
seated in the relay. If difficulty still persists,
Step 3. Install new terminal board and fasten
securely to case.
Step 4. Insert operating mechanism in case and
tighten screws.
Step 5. Engage the force-balance spring with force
balance spring adjusting screw.
Step 6. Connect (or soft-solder *) coil leads.
9
Split Range
In a SPLIT-RANGE assembly, the choice of the type of
connection (in series or parallel) and the characteristics
of the positioners equipping each valve, depend on the
controller output signal and impedance of the circuits.
When the positioner is ordered specifically for split-
range operation, a force balance spring with one-half
the standard rate is supplied.
The table below gives for each case (double or triple
split-range, connection of positioners in series or parallel),
the coefficient to be applied to the actual stroke value
of the equipped valve in order to obtain the adjustment
value to be indicated on the stroke scale of each positioner.
In certain cases it is possible to have standard positio-
ners operating in split-range.
When this is so, our Engineering Department supplies
all the information necessary for the choice of the
material or its eventual transformation.
Note:The indicated maximum strokes taken into account the adjusting possibilities given with a standard 8013 positioner.
Stroke AdjustmentValve
TripleSplit - Range
(3 Valves)
Actual Stroke x 1.3max. stroke: 2" (50.8 mm)
Actual Stroke x 2.6max. stroke: 1" (25.4 mm)
DoubleSplit - Range
(2 Valves)
Stroke AdjustmentValve
Actual Strokemax. stroke: 3" (76.2 mm)
Actual Stroke x 2max. stroke: 11/2" (38.1 mm)
Figure 8 - Split Range Options
Equipment for hazardous atmosphere
These standards are divided into two groups ac-
cording to two types of protection
1. Flameproof housing positoners : If because of a
failure, an internal part of the positioner causes
a spark, this can ignite the hazardous mixture
contained in the case. Thus the characteristics of
this case are calculated in order that it could resist
to the pressure developed during the internal
explosion and prevent the transmission of the
explosion to the environmental hazardous
atmosphere of the housing.
2. Positioners for intrinsically safe circuit : This protection
system which applies to a complete circuit but not
to a single and isolated device, is particularly due
Protection Standards
to the fact that no spark, no thermal effect produced
according to the test conditions recommended by
the standard regulation, can produce the ignition
of a given hazardous atmosphere.
3. Tight equipment for non-hazardous atmosphere :
8013 positioner is also available as "Weather Proof"
so as to protect the positioner against dust and
stream of water. Devices manufactured under the
reference "Weather Proof" (protection against dust
and stream of water) meet specification requirements
of IS 13947.
Caution: Do not open loosen screws of the instruments,
in flame proof atmosphere, for any repair or main-
tenance work. The instrument has to be taken outside
the hazardous area.
10
a) Hazardous atmosphere
1. Flame proof to Gr. IIA, II B as per IS2148 (With
Weather proof IP55 Certification)
Certifications for 8013 Positioners
2. Intrinsically safe Gr. IIC as per IS 5780 (With Weather
proof IP65 Certification)
b) Non-Hazardous atmosphere
1. Weather proof IP65 as per IS 2147
Electrical circuit
The installation must be in accordance with the
selected standard for the protection against
explosion.
CONNECTING SIGNAL LEADS
1. They are introduced in the case through the conduit
connection located on the side. (¾" or ½" NPT)
2. Connections to the terminal board should be made
respecting the polarities engraved on this terminal
board.
Connecting coil leads to the terminal board
This connection determines the device action.
Direct action : A signal increase produces an output
pressure increase.
Reverse action : A signal increase produces and
output pressure decrease.
The diagram of figure-9 shows the position of the coil
leads and the connecting terminals used for the terminal
board for each action of the device.
Electrical Circuits
The positioner has been factory calibrated for the action
required by the customer. If action is not specified, the
positioner is factory calibrated for direct action.
Changing of action :
1. Reverse the positions of the coil leads to the terminal
board (See diagram of figure 9)
2. In case of intrinsically safe circuit replace the coil
by another one corresponding to the new action.
Caution: Incase of flame proof housing device, the
positioner case should not be opened when the device
is energized.
Note 1 : The standards concerning electrical equip-
ment utilized in hazardous atmospheres can
be identified with serial plate fastened to
the side.
Note 2 : Besides the mark corresponding to the
positioner action, coils always have a color
code permitting the identification of the
nominal resistance. In the event of coil removal
be sure that the colour code of the new coil
is identical with the old one eg : 4-20 mA
coil with colour code blue.
Note3 : Be sure that leads connecting the coil to the
terminal-board do not block the beam
motion.Figure 9 - Coil Leads Position
Cross the leads over the beam
REVERSE ACTIONDIRECT ACTION
Branch Offices
NEW DELHI
MIL Controls Limited
KSB House, A-96, Sector 04,
Gautam Budh Nagar,
Noida 201 301, India
Tel: 91 (0)120 2541091 to 93, 2541501 to 03
Fax: 91 (0)120 2550567, 2525626
Email: [email protected]
MUMBAI
MIL Controls Limited
126, Maker Chamber III, Nariman Point,
Mumbai - 400 021, India.
Tel: 91 (0)22 56588787,
56588757 to 59, 56588761
Fax: 91 (0)22 56588788
Email: [email protected],
KOLKATA
MIL Controls Limited
2nd Floor, 30 Circus Avenue,
Kolkata 700 017, India
Tel: 91 (0)33 22470473, 22400117, 22400418
Fax: 91 (0) 33 22470588
Email: [email protected], [email protected]
CHENNAI
MIL Controls Limited
Guindy House, 2nd Floor,
95, Annai Salai,
Chennai 600 032, India
Tel: 91 (0)44 22352571 to 72, 22300629
Fax: 91 (0)44 22352749
Email: [email protected]
VADODARA
MIL Controls Limited
4-B, Ramakrishna Chambers,
Productivity Road,
Vadodara 390 005, India
Tel: 91 (0)265 2330532, 2333226
Fax: 91 (0)265 2314693
Email: [email protected]
PUNE
MIL Controls Limited
KSB Pumps Limited
D-II Block, MIDC
Chinchwad
Pune - 411 019
Tel: 91 (0)20 2740 9100
Fax: 91 (0)20 2747 0890
Overseas Sales Offices
CHINA
KSB-Shanghai Office
Rm. D-E1. 26/F., Zao-Feng Universe Building,
No. 1800 West Zhongshan Road, Shanghai,
P.R. China. Post Code: 200235.
Tel: (86)-21-6440 1668 Ext. 832
Fax: (86)-21-6440 0228
FINLAND
KSB Finland Oy
Savirunninkatu 4, FI-04260
Kerava, Finland
Tel: 358 10 288 5427
Fax: 358 10 288 5685
HONG KONG
KSB Limited
17/F, Chuang’s City Tower,
39 Morrison Hill Road,
Causeway Bay, Hong Kong
Tel: 852 2147 1220
Fax: 852 2147 1230
Email: [email protected]
MALAYSIA
KSB Malaysia Pumps & Valves SDN BHD
11A, Jalan PJU 3 / 47, Sunway Damansara
47810 Petaling Jaya,
Selangor Darul Ehsan, Malaysia.
Tel: 60-03 7781 3026
Fax: 60-03 7781 3020
Email: [email protected]
MIDDLE EAST
KSB Middle East FZE,
PO Box 18315
Jebel Ali, Dubai, UAE.
Tel: 9714-8830455
Fax: 9714-8830456
SINGAPORE
KSB Singapore (Asia Pacific) PTE Ltd
25 Tagore Lane, 02-08/09
Singapore Godown, Singapore 787602
Tel: 65 6555 0366
Fax: 65 6553 3500
Email: [email protected]
TAIWAN
KSB Taiwan Co Ltd
Virtuoso Enterprise Building, 12F-1, No.380,
Fushing South Road, Sec. 1, Taipei 106,
Taiwan, ROC
Tel: 886-2 2755 5858
Fax: 886-2 2703 3366
Email: [email protected]
REGD. OFFICE & WORKS /
SPARE PARTS & AFTERSALES DEPARTMENTS
MIL Controls Limited
Meladoor , Mala
PIN 680 741, Thrissur Dist., Kerala, India
T: 91 (0)480 2890272, 2890772, 2891773
F: 91 (0)480 2890952
E: [email protected], [email protected],
W: www.milcontrols.com
MARKETING HEAD OFFICE
MIL Controls Limited
N.H. 47, Thaikkattukara P.O., Aluva
PIN 683 106, Ernakulam Dist, Kerala, India
T: 91 (0)484-2624955, 2624876, 2628041
F: 91 (0)484-2623331
E: [email protected], [email protected]
MIL Controls Ltd.
A KSB Company