EN 50173-X: THE MISSING LINKIssue 5
1A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕEN 50173-X: The Missing Link
The birth ofintegrated cabling standards
for converged networks
BS
6701
BS
7671
DESIGNPLANNING
INSTALLATION
INSPECTIONTESTING
BS
EN 5
0346
BS
EN 5
0174
-1
BS
EN 5
0174
-2
BS
EN 5
0174
-3
BS
EN 5
0173
-2
BS
EN 5
0173
-3
BS
EN
501
73-4
BS
EN 5
0173
-5
BS
EN 5
0310
BS
EN 5
0173
-1 This service pack (SP1) containscorrections/amendments implemented on
22nd February 2007.
The slides affected are marked with a red square inthe top right corner (as shown above). Each
amended slide indicates why the change was made.
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Mike Gilmore
Mike Gilmore
Managing Directore-Ready Building
Standards Activities
Mobile: +44 (0) 7860 110563 e-mail: [email protected]
MemberJTC1 SC25 WG3: Generic Cabling
Convenor JTC1 SC25 WG3 CITG: Cabling Implementation Task Group
JTC1 SC25 WG3 IPTG: Industrial Premises (Cabling) Task Group
Convenor TC215 WG1: IT Cabling
TC215 WG1 PT Industrial Premises Cabling
Secretary TC215 WG1 PT Data Centre Cabling
ChairmanTCT7: Telecommunications - Installation Requirements
Chairman TCT7/-/1: Cabling infrastructure design, planning and commissioningTCT7/-/3: Cabling: Infrastructure standards - UK implementation panel
Technical and Standards DirectorFibreoptic Industry Association
FIAwww.fia-online.co.uk
EN 50173-X: The Missing Link
EN 50173-X: THE MISSING LINKIssue 5
2A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
OverviewThe New Standards
EN 50173-X: The Missing Link
Fundamental changesEN 50173-X Inter-relationships
External relationshipsConformance
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Fundamental ChangesThe New Standards
EN 50173-X: The Missing Link
EN 50173-1 Ed.2 (2007) General requirements
EN 50173-2 Ed.1 (2007) Office premises
Information technology - Generic cabling systems
EN 50173-1 Ed.1 (2002) General requirementsand office areas
Final draft (voting 03/11/06)
EN 50173 Ed.1 (1995) Customer premisescabling
Final draft (voting 03/11/06)
EN 50173-4 Ed.1 (2007) Homes
EN 50173-5 Ed.1 (2007) Data centres
Final draft (voting 03/11/06)
Final draft (voting 03/11/06)
EN 50173-3 Ed.1 (2007) Industrial premises
6MP Draft (comment 05/01/07)
EN 50173-X: THE MISSING LINKIssue 5
3A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Inter-relationships: OfficeThe New Standards
EN 50173-X: The Missing Link
TO
TO
TO
TO
TO
TO
CP
CPFD
BD
FD
TO
TO
TO
TO
TO
TO
CP
CPFD
BD
FD
CDENI
EO
EO
EO
EO
EO
EO
LDP
LDPZD
ZD
MDENI
ENTI
OFFICE PREMISES
DATA CENTRE
Penetration point
Adduction
Adduction
ENTIPenetration point
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Inter-relationships: OfficeThe New Standards
EN 50173-X: The Missing Link
TO
TO
TO
TO
TO
TO
CP
CPFD
BD
FD
TO
TO
TO
TO
TO
TO
CP
CPFD
BD
FD
CDENI
EO
EO
EO
EO
EO
EO
LDP
LDPZD
ZD
MDENI
ENTI
OFFICE PREMISES
DATA CENTRE
Penetration point
Adduction
Adduction
ENTIPenetration point
Buildingbackbone
cablingsubsystemspecified
byEN 50173-1
Campusbackbone
cablingsubsystemspecified
byEN 50173-1
Horizontalcabling
subsystemspecified
byEN 50173-2
Zone distributioncabling subsystem
specifiedby
EN 50173-5
Main distributioncabling subsystem
specifiedby
EN 50173-5
Network accesscabling
subsystemspecified
byEN 50173-5
KEY Generic cabling subsystem cabling Possible additional cabling
Building DistributorCampus DistributorConsolidation PointExternal Network InterfaceEquipment Outlet
ABBREVIATIONS
BDCDCPENIEO
Floor DistributorLocal Distribution PointMain DistributorTelecommunications OutletZone Distributor
FDLDPMDTOZD
EN 50173-X: THE MISSING LINKIssue 5
4A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Inter-relationships: IndustrialThe New Standards
EN 50173-X: The Missing Link
CDENI
EO
EO
EO
EO
EO
EO
LDP
LDPZD
ZD
MDENI
ENTI
INDUSTRIAL PREMISES
DATA CENTRE
Penetration point
Adduction
Adduction
ENTIPenetration point
TO
TOFD
ID
TO
TOID
BD
TO
TOFD
ID
TO
TOID
TO
TOFD
ID
TO
TOID
BDTOID
EN 50173-3 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Inter-relationships: IndustrialThe New Standards
EN 50173-X: The Missing Link
CDENI
EO
EO
EO
EO
EO
EO
LDP
LDPZD
ZD
MDENI
ENTI
INDUSTRIAL PREMISES
DATA CENTRE
Penetration point
Adduction
Adduction
ENTIPenetration point
TO
TOFD
ID
TO
TOID
BD
TO
TOFD
ID
TO
TOID
TO
TOFD
ID
TO
TOID
BDTOID
Intermediatecabling
subsystemspecified byEN 50173-3
Buildingbackbone
cablingsubsystemspecified
byEN 50173-1
Campusbackbone
cablingsubsystemspecified
byEN 50173-1
Floorcabling
subsystemspecified
byEN 50173-3
KEY Generic cabling subsystem cabling Possible additional cabling
Building DistributorCampus DistributorExternal Network InterfaceEquipment OutletFloor Distributor
ABBREVIATIONS
BDCDENIEOFD
Intermediate DistributorLocal Distribution PointMain DistributorTelecommunications OutletZone Distributor
IDLDPMDTOZD
Zone distributioncabling subsystem
specifiedby
EN 50173-5
Main distributioncabling subsystem
specifiedby
EN 50173-5
Network accesscabling
subsystemspecified
byEN 50173-5
EN 50173-X: THE MISSING LINKIssue 5
5A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ EO
EO
EO
EO
EO
EO
LDP
LDPZD
ZD
MDENI
DATA CENTRE
Adduction
ENTIPenetration point
EN 50173-5 Ed.1 (2007)
FD
BD
FD
ENI
ENTIPenetration point
AdductionMULTI-TENANT PREMISES
Inter-relationships: HomesThe New Standards
EN 50173-X: The Missing Link
HOMES
EN 50173-4 Ed.1 (2007)
BO
TOHDENI
ENTIPenetration point
Adduction CO
BO
TO
CO
SHD
SHD
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Inter-relationships: HomesThe New Standards
EN 50173-X: The Missing Link
EO
EO
EO
EO
EO
EO
LDP
LDPZD
ZD
MDENI
DATA CENTRE
Adduction
ENTIPenetration point
FD
BD
FD
ENI
ENTIPenetration point
AdductionMULTI-TENANT PREMISES
HOMES BO
TOHDENI
ENTIPenetration point
Adduction CO
BO
TO
CO
SHD
SHD
Secondaryhome
cablingsubsystem
specified byEN 50173-4
Homecabling
subsystemspecified
byEN 50173-4
Network access cablingspecified byEN 50173-4
Buildingbackbone
cablingsubsystemspecified
byEN 50173-1
Zone distributioncabling subsystem
specifiedby
EN 50173-5
Main distributioncabling subsystem
specifiedby
EN 50173-5
Network accesscabling
subsystemspecified
byEN 50173-5
KEY Generic cabling subsystem cabling Possible additional cabling
Broadcast OutletBuilding DistributorCampus DistributorControl OutletExternal Network InterfaceFloor Distributor
ABBREVIATIONS
BOBDCDCOENIFD
Home DistributorLocal Distribution PointMain DistributorSecondary Home DistributorTelecommunications OutletZone Distributor
HDLDPMDSHDTOZD
EN 50173-X: THE MISSING LINKIssue 5
6A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
EN 50173-X Inter-relationshipsThe New Standards
EN 50173-X: The Missing Link
ENI
ENTI
Adduction
FD
EN 50173-1 Ed.2(2007)
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EOMD
ENTI
Penetration point
EN 50173-5 Ed.1 (2007)
ZD LDP
CD BD
ENI
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
EN 50173-X Inter-relationshipsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1 Ed.2(2007)
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
ENI
ENTI
Adduction
FD
EOMD
ENTI
Penetration point
ZD LDP
CD BD
ENI
Premises-specific cabling
Cabling performance
Components
StructureReference Implementations
Channel selection
Interface selection
Backbone cabling
Cabling performance
Components
StructureReference Implementations
Channel limits (all)Link limits (all)
Requirements (all)
Environment
MICE Classification
EN 50173-X: THE MISSING LINKIssue 5
7A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
External Relationships: -1The New Standards
EN 50173-X: The Missing Link
EN 50173-1 Ed.2(2006)
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
ENI
ENTI
Adduction
FD
EOMD
ENTI
Penetration point
ZD LDP
CD BD
ENI
EN 50346: Installed tests
Component standards
Backbone cabling
Cabling performance
Components
StructureReference Implementations
Channel limits (all)Link limits (all)
Requirements (all)
Environment
MICE Classification
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
External Relationships: -XThe New Standards
EN 50173-X: The Missing Link
EN 50173-1 Ed.2(2007)
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
ENI
ENTI
Adduction
FD
EOMD
ENTI
Penetration point
ZD LDP
CD BD
ENI
EN 50174: Installation
Premises-specific cabling
Cabling performance
Components
StructureReference Implementations
Channel selection
Interface selection
EN 50173-X: THE MISSING LINKIssue 5
8A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
External Relationships: WANThe New Standards
EN 50173-X: The Missing Link
ENI
ENTI
Adduction
FD
EOMD
ENTI
Penetration point
ZD LDP
CD BD
ENI
xD
Transport Distribution
Accessnetwork
(external)
Accessnetwork(internal)
Access network
ETSI AT-I
Lastcabinet
Operatorsite
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
ConformanceThe New Standards
EN 50173-X: The Missing Link
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
CONNECTINGHARDWARE
AT SPECIFIEDINTERFACES
OTHERCONNECTINGHARDWARE
STRUCTURE
Design
Attachment of appropriate components to conformant links
Reference implementations
CHANNELPERFORMANCE
LOCAL SAFETY RULES
• parameters to be measured• sampling levels to be applied• marginal results
EN 50174 series
ADMINISTRATION
INSTALLATION
QUALITY ASSURANCE
BS 6701
THERE ARE NO CONFORMANCE REQUIREMENTS IN EN 50173-1
EN 50173-X: THE MISSING LINKIssue 5
9A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Selection and ApplicationThe New Standards
EN 50173-X: The Missing Link
Services and ApplicationsSelecting the StandardApplying the Standard
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Services and ApplicationsThe New Standards
EN 50173-X: The Missing Link
INFORMATION TECHNOLOGY
SERVICES BCT ICT CCCB
APPLICATIONS BCT ICT CCCB
Broadcastcommunications
technology
Informationcommunications
technology
Command, controlcommunications
in buildings
IEEE 802.3CaTV
Satellite
Terrestial
HEINZ 57 Variety
PCMA
PCMA
Process control,monitoring
and automation
HEINZ 57 VarietyEN 50090 IEC/EN 61784-X
EN 50083
EN 50173-X: THE MISSING LINKIssue 5
10A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Selecting the StandardThe New Standards
EN 50173-X: The Missing Link
APPLICATIONS
EN 50173-4EN 50173-3EN 50173-2 EN 50173-5
OFFICE INDUSTRIAL HOMES DATA CENTREPREMISES
ICT PCMA BCT CCCBICT ICT
SERVICES
ICT
BCT
CCCB
ICT ICT
BCT
CCCB
BCT CCCBPCMAICT
CCCB
PCMA
ICT
BCT
1 cablingsubsystem
2 cablingsubsystems
1 cablingsubsystem
EN 50173-1 Ed.2
2 cabling subsystems
2000 metres 10000 metres 2000 metres 10000 metres
2 cablingsubsystemsSTRUCTURE
DIMENSIONING
HOSPITALS?
AIRPORTS?
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Applying the StandardThe New Standards
EN 50173-X: The Missing Link
EN 50173-4EN 50173-3EN 50173-2 EN 50173-5
33 pages37 pages 46 pages29 pages
EN 50173-1 Ed.2
126 pages
EN 50174-1
EN 50174-2 EN 50174-3
BS 6701
EN 50346
BS 7671
Please supply cabling in accordance with
Choose the CHANNELS and CHANNEL CONFORMANCE approach
EN 50173-X: THE MISSING LINKIssue 5
11A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Components and CablingThe New Standards
EN 50173-X: The Missing Link
ICT ComponentsBCT Components
CCCB ComponentsChannels
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
ICT Balanced ComponentsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1
EN 50173-5
Cables Connecting Hardware
Category 5, 6 and 7
EN 50173-2EN 50173-3EN 50173-4
EN 61076-3-104
ScreenedUnscreened
EN 50173-3
EN 60603-7-2EN 60603-7-4
EN 60603-7-3EN 60603-7-5EN 60603-7-7
Category 5Category 6
Category 7
Housing
TO (4 pr)
TO (2 pr)
EO
Category 5EN 61076-2-101
EN 61076-3-104
EN 60603-7-4 EN 60603-7-5EN 60603-7-7
Category 6
Category 7
EN 50173-5 ENIEN 60603-7-2EN 60603-7-4
EN 60603-7-3EN 60603-7-5EN 60603-7-7
Category 5Category 6Category 7
RJ45
Tera
RJ45
Tera
RJ45
M12D-coded
IEC 61076-3-106
IEC 61076-3-106
IEC 61076-3-106
Connecting HardwarePerformance Style
Variant 4
Variant 4 was missed off theslide (although it was always
explained in the presentation).All the references to IEC 61076-3-106 in the following slides are
also Variant 4
“D-coded” addedfor clarity
EN 50173-X: THE MISSING LINKIssue 5
12A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
ICT Optical Fibre ComponentsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1
EN 50173-4
Cables
OM1, OM2, OM3
EN 50173-2
EN 50173-5
EN 50173-5
OS1, OS2All silica
MMF
SMF
CablesConnecting Hardware
TO IEC 60874-19-1 SC-D
Style
EN 50173-3 TO EN 61754-20 LC-D
Housing
EN 50173-2
EN 50173-3IEC 61076-3-106 OMx, OSx
OMx, OS1
EN 50173-4Not specified Not specified
EO
ENI
≤ ≤ ≤ ≤ 2 MMF EN 50377-7-11111 SMF EN 50377-7-42 SMF EN 50377-7-2≥ ≥ ≥ ≥ 2 OF EN 61754-7
LC-DLC
LC-DMPO EN 50173-5 OM2, OM3
OS1, OS2
IEC 61076-3-106
MMFENI SMF
EN 50377-7-2EN 50377-7-3 LC-D APC
LC-D IEC 61076-3-106
OM1 OM2 OM3 OS1
Multimode OF Singlemode OF
850 nm1300 nm
Attenuationcoefficient (max)
3,5 dBkm-1 1,5 dBkm-1
1,0
1,0850 nm1300 nm
Modal bandwidth OFL (MHz.km min)
200500
500500
1500500
850 nm1300 nm
Modal bandwidth LL (MHz.km min)
--
--
2000-
50/125 or 62.5/125
850 nm1300 nm
Propagation delay (ns.m-1 max) 5
1310 nm
1550 nm
1310 nm1550 nm 5
Wavelength Wavelength50/125
OS1
5
OS1
5
OS20,40,4
5
1383 nm0,4
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
PCMA Optical Fibre ComponentsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1
Cables
OP1, OP2MMFPlastic
OH1MMFPlastic clad
CablesConnecting HardwareStyle
EN 50173-3 TO
Housing
EN 50173-3 OP1, OP2, OH1
OP1 OP2 OH1Multimode OF
850nm1300nm
Attenuationcoefficient (max)
(dBkm-1)
850nm1300nm
Modal bandwidth OFL (MHz.km min) -
-150150
5ffs
*/1000
850nm1300nm
Propagation delay (ns.m-1 max) 5
Wavelength
200/230
--
4010
40ffs
650nm 200 100 ffs
650nm 10 80 ffs
Cladding dia */490
EN 61754-20 LC-D IEC 61076-3-106
The previous issueindicated “Not specified”.
This was incorrect.
EN 50173-X: THE MISSING LINKIssue 5
13A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
BCT Balanced ComponentsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1 Category BCT-B
EN 50173-4 EN 61076-3-104EN 60603-7-7 Category 7IEC 61076-3-106BO RJ45
Tera
Cables Connecting Hardware
Connecting HardwareScreenedUnscreened Housing Performance Style
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
BCT Coaxial ComponentsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1 Category BCT-C
EN 50173-4 BO
Cables Connecting Hardware
Connecting HardwareScreened Style
EN 61169-24EN 61169-2 Type 9,52
Type F
EN 50173-X: THE MISSING LINKIssue 5
14A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
CCCB Balanced ComponentsThe New Standards
EN 50173-X: The Missing Link
EN 50173-1 Category CCCB
EN 50173-4 CO Not specified
Cables Connecting Hardware
Connecting HardwareScreenedUnscreened Housing
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Balanced Cabling Channels: IThe New Standards
EN 50173-X: The Missing Link
CCCB
BCT-B (1-pr channel)
A
B
C
D
E
F
0.01 0.1 1 10 100 600 1000 MHz
600 MHz
1000 MHz
250 MHz
100 MHz
16 MHz
1 MHz
100 kHz
100 kHz
Tran
smis
sion
Cla
ss
EN 50173-4
EN 50173-2
EN 50173-5
EN 50173-3
A-F
A-F
D-F, BCT-B and CCCB
A-F
Horizontal D
Floor D
Home/Secondary Home D
Main Distribution EZone Distribution E
Minimum Implementations
Intermediate D
EN 50173-X: THE MISSING LINKIssue 5
15A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Balanced Cabling Channels: IIThe New Standards
EN 50173-X: The Missing Link
CCCB
BCT-B (1-pr channel)
A
B
C
D
E
F
0.01 0.1 1 10 100 600 1000 MHz
600 MHz
1000 MHz
250 MHz
100 MHz
16 MHz
1 MHz
100 kHz
100 kHzTr
ansm
issi
on C
lass
Classes D, E and FInsertion lossReturn lossNEXT (pp and PS)ELFEXT (pp and PS)ACR (pp and PS)
Operating voltagePower feeding
ResistanceResistance unbalance
Propagation DelaySkewTCLELTCTLCoupling attenuation
Class BCT-BInsertion lossReturn loss
TCLELTCTLCoupling attenuation
-L. -M, -H
Propagation Delay
Class CCCBInsertion loss
Operating voltagePower feeding
ResistanceResistance unbalance
Propagation Delay
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Optical Fibre Cabling Channels: IThe New Standards
EN 50173-X: The Missing Link
10
1 10 100 200 300 500 2000
8
6
4
2
0
OF-2000
OF-500
OF-300
1 10 100 200 300 500 2000
4
3
2
1
0
5
OF-2000
OF-500
OF-300
1 10 100 200 300 500 2000 5000 10000
OF-10000
OF-5000OF-2000
OF-500
OF-300
6
5
4
3
2
1
0
MMF: OM1, OM2, OM3
Cha
nnel
Inse
rtio
n Lo
ss (d
B)
Cha
nnel
Inse
rtio
n Lo
ss (d
B)
850 nm 1300 nm
1310/1550 nm SMF: OS1, OS2
ALL-SILICA
ALL-SILICA
Channel length (m)
EN 50173-X: THE MISSING LINKIssue 5
16A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Optical Fibre Cabling Channels: IIThe New Standards
EN 50173-X: The Missing Link
PLASTIC
MMF: OP1 20
1 10 25 50 100
16
12
8
4
0
OF-50
Cha
nnel
Inse
rtio
n Lo
ss (d
B)
650 nm24
OF-100
OF-25
PLASTIC
MMF: OP2 20
1 10 25 50 100 200
16
12
8
4
0
OF-200
OF-50
Cha
nnel
Inse
rtio
n Lo
ss (d
B)
650 nm24
OF-100
OF-25
10
1 10 25 50 100 200
8
6
4
2
0
OF-200
OF-50
Cha
nnel
Inse
rtio
n Lo
ss (d
B) 850/1300 nm
12
OF-100
OF-25
Channel length (m)
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Optical Fibre Cabling Channels: IIIThe New Standards
EN 50173-X: The Missing Link
PLASTIC
MMF: OH1 20
1 10 25 50 100 200
16
12
8
4
0
OF-200
Cha
nnel
Inse
rtio
n Lo
ss (d
B)
650 nm24
OF-100 10
1 10 25 50 100 200
8
6
4
2
0
OF-200
Cha
nnel
Inse
rtio
n Lo
ss (d
B) 850/1300 nm
12
OF-100
Channel length (m)
EN 50173-X: THE MISSING LINKIssue 5
17A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Coaxial Cabling ChannelsThe New Standards
EN 50173-X: The Missing Link
Classes D, E and FInsertion lossReturn lossNEXT (pp and PS)ELFEXT (pp and PS)ACR (pp and PS)
Operating voltagePower feeding
ResistanceResistance unbalance
Propagation DelaySkewTCLELTCTLCoupling attenuation
Class BCT-BInsertion lossReturn loss
TCLELTCTLCoupling attenuation
-L. -M, -H
Propagation Delay
Class BCT-CInsertion lossReturn loss
Screening attenuation
-L. -M, -H
Propagation DelayOperating voltagePower feeding
Resistance
BCT-B (1-pr channel)
F (4-pr channel)
0.01 0.1 1 10 100 600 1000 3000 MHz
600 MHz
1000 MHz
Tran
smis
sion
Cla
ss
BCT-C
AB
CD
E 250 MHz100 MHz
16 MHz1 MHz
100 kHz
EN 50173-X: THE MISSING LINKIssue 5
18A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Introduction to MICEEN 50173-X:
The Missing Link
Classifying the EnvironmentExtending the MICE
Channel SelectionComponent Selection
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕLate September 2002 Mechanical Ingress Climatic/Chemical Electromagnetic
M I C EThe MICE System
Classifying the EnvironmentEN 50173-X:
The Missing Link
pr-EN 50173-2 January 2002 - Scope: Industrial Environmentpr-EN 50173-2
February 2002 - Scope: Industrial Premisespr-EN 50173-2
IP-rating Mechanical Climatic Electromagnetic
Early September 2002 - Environmental Classification
December 2002
Re-designationof
EN 50173-2as
EN 50173-3
DevelopmentISO/IEC 24702
DevelopmentTIA/EIA-1005
PublishedQ4, 2006
PublishedQ1, 2007
EN 50173-X: THE MISSING LINKIssue 5
19A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Expanding the MICEEN 50173-X:
The Missing Link
ENI
ENTI
Adduction
FD
EOMD
ENTI
Penetration point
ZD LDP
CD BD
ENI
EN 50173-1 Ed.2(2007)
Environment
MICE Classification
Different locations within a channel may be subject to different environmental conditions
The local conditions, to which the cabling components within the channel are exposed,shall be used to determine the applicable environmental classification(s).
With regard to temperature the local environment is considered to be the operatingtemperature of the cabling.
IngressMechanical
ClimaticElectromagnetic
M1 M2 M3I1 I2 I3C1 C2 C3E1 E2 E3
HarshBenign
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Mechanical - MEN 50173-X:
The Missing Link
Shock/bump1
Peak acceleration 40 ms-2 100 ms-2 250 ms-2
Note 1
M1 M2 M3
Vibration1
Displacement amplitude (2 Hz to 9 Hz) 1,5 mm 7,0 mm 15 mm
Acceleration amplitude (9 Hz to 500 Hz) 5 ms-2 20 ms-2 50 ms-2
Tensile force These aspects of environmental classification is installation-
specific and should be considered in association with EN50174-2 and the appropriate component specification.
Crush/linear distance 45 N/25 mm min. 1100 N/150 mm min. 2200 N/150 mm min.
Impact 1 J 10 J 30 J
Bump: the repetitive nature of the shock experienced by the channel shall be taken into account.
Torsion
Bending
Flexibility
The operating environment “Mx” is defined by the worst parameter
EN 50173-X: THE MISSING LINKIssue 5
20A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Ingress - IEN 50173-X:
The Missing Link
Particulate ingress (dia. max) 12,5 mm 50 µµµµm 50 µµµµm
I1 I2 I3
Immersion None
Liquid jet• intermittent• ≤≤≤≤ 12,5 l/min• ≥≥≥≥ 6,3 mm jet• >>>> 2,5 m distance
Liquid jet• intermittent• ≤≤≤≤ 12,5 l/min• ≥≥≥≥ 6,3 mm jet• >>>> 2,5 m distance
Immersion• ≤≤≤≤ 1 m• ≤≤≤≤ 30 minutes)
The operating environment “Ix” is defined by the worst parameter
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Climatic/Chemical - CEN 50173-X:
The Missing Link
Ambient temperature -10° C to +60° C -25° C to +75° C -40° C to +75° C
C1 C2 C3
Rate of change of temperature
0 >>>> 5 x104 aqueous-ng >>>> 5 x104 aqueous-g
0,1° C per minute 1° C per minute 3° C per minute
Humidity 5 % to 85 % (non-condensing)
5 % to 95 % (condensing)
5 % to 95 % (condensing)
Solar radiation 700 Wm-2 1100 Wm-2 1100 Wm-2
Sodium chloride (salt/sea water) 0 <<<< 0,3 <<<< 0,3
Oil (dry-air concentration) 0 <<<< 0,05 <<<< 0,5
Liquid pollution (concentration x 10-6)
Sodium stearate (soap)
0 ffs ffsDetergent
0 Temporary PresentConductive materials
The type of oils is installation-specific and should beconsidered in association with EN 50174-2 and the
appropriate component specification.
C1 C2 C3
The operating environment “Cx” is defined by the worst parameter
EN 50173-X: THE MISSING LINKIssue 5
21A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Climatic/Chemical - CEN 50173-X:
The Missing Link
Hydrogen sulphide <<<< 0,003/<<<< 0,01 <<<< 0,05/<<<< 0,5 <<<< 10/<<<< 50
Sulphur dioxide <<<< 0,01/<<<< 0,03 <<<< 0,1/<<<< 0,3 <<<< 5/<<<< 15
Gaseous pollution (mean/peak concentration x 10-6)
Sulphur trioxide (ffs)
Chlorine wet (>50 % humidity)
Chlorine dry (<50 % humidity)
C1 C2 C3
Hydrogen chloride
Hydrogen fluoride
Ammonia
Oxides of Nitrogen
Ozone
<<<< 0,01/<<<< 0,03 <<<< 0,1/<<<< 0,3 <<<< 5/<<<< 15
<<<< 0,0005/<<<< 0,001 <<<< 0,005/<<<< 0,03 <<<< 0,05/<<<< 0,3
<<<< 0,002/<<<< 0,01 <<<< 0,02/<<<< 0,1 <<<< 0,2/<<<< 1,0
−−−−/<<<< 0,06 <<<< 0,06/<<<< 0,3 <<<< 0,6/<<<< 3,0
<<<< 0,001/<<<< 0,005 <<<< 0,01/<<<< 0,05 <<<< 0,1/<<<< 1,0
<<<< 1/<<<< 5 <<<< 10/<<<< 50 <<<< 50/<<<< 250
<<<< 0,05/<<<< 0,1 <<<< 0,5/<<<< 1 <<<< 5/<<<< 10
<<<< 0,002/<<<< 0,005 <<<< 0,025/<<<< 0,05 <<<< 0,1/<<<< 1
The operating environment “Cx” is defined by the worst parameter
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Electromagnetic - EEN 50173-X:
The Missing Link
4 kV
E1 E2 E3
Electrostatic discharge
Contact (0,667 µC)
Air (0,132 µC) 8 kV
Radiated RF – AM
80-1000 MHz 3 Vm-1 10 Vm-1
1400-2000 MHz 3 Vm-1
2000-2700 MHz 1 Vm-1
Conducted RF
150 kHz - 80 MHz 3 Vm-1 10 Vm-1
EFT/B (comms) 500 V 1000 V
Surge - Signal, line to earth
500 V 1000 VTransient ground potential difference
Magnetic field
50/60 Hz
60 Hz - 20 kHz ffs
1 Am-1 10 Am-1 30 Am-1
The operating environment “Ex” is defined by the worst parameter
EN 50173-X: THE MISSING LINKIssue 5
22A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Component SelectionEN 50173-X:
The Missing Link
For each M, I, C, or E group, the classification of a given environment is
determined by the most demanding parameter within the M, I, C or E group
The MICE classification shall be used for the selection of:
components and/or protection afforded to them
installation techniques to be applied to the channel in order to provide protection
The selection of components
based on the specific demands of each of the parameters within the M, I, C, or E group
possibly less demanding than the overall classification of the group
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Balanced Channel SelectionEN 50173-X:
The Missing Link
EN 50173-1 Ed.1 (2002)
Insertion loss
Return loss
NEXT (pp and PS)
ELFEXT (pp and PS)
ACR (pp and PS)
Operating voltage
Power feeding
Resistance
Resistance unbalance
Propagation Delay
Skew
EN 50173-1 Ed.2 (2007)
Insertion loss
Return loss
NEXT (pp and PS)
ELFEXT (pp and PS)
ACR (pp and PS)
Operating voltage
Power feeding
Resistance
Resistance unbalance
Propagation Delay
Skew
Unbalance attenuation TCL
ELTCTL
Coupling attenuation
Unscreenedcabling
Screened cabling
E1 E2 E3
Base Base+10 dB
Base+20 dB
D, E, F and BCT-B
Classes
The required transmission performance Class shall be met for all environmental classifications specified for the channel.
EN 50173-X: THE MISSING LINKIssue 5
23A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Planning and InstallationLinkages
EN 50173-X: The Missing Link
Conforming to EN 50174-X:2001The Influence of BS 6701:2004
Linkage to BS 7671The Future of EN 50174-X
The Impact o f EN 50173-X
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Conforming to EN 50173-XLinkages
EN 50173-X: The Missing Link
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
CONNECTINGHARDWARE
AT SPECIFIEDINTERFACES
OTHERCONNECTINGHARDWARE
STRUCTURE
Design
Attachment of appropriate components to conformant links
Reference implementations
CHANNELPERFORMANCE
LOCAL SAFETY RULES
• parameters to be measured• sampling levels to be applied• marginal results
EN 50174 series
ADMINISTRATION
INSTALLATION
QUALITY ASSURANCE
BS 6701
THERE ARE NO CONFORMANCE REQUIREMENTS IN EN 50173-1
EN 50173-X: THE MISSING LINKIssue 5
24A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Conforming to EN 50174-XLinkages
EN 50173-X: The Missing Link
• parameters to be measured• sampling levels to be applied• marginal results
EN 50174 series
ADMINISTRATION
INSTALLATION
QUALITY ASSURANCE
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
EN 50174-2
Information technology - Cabling installation-Part 2: Installation planning and practices inside buildings
EN 50174-1Information technology - Cabling installation-Part 1: Specification and Quality Assurance
Information technology - Cabling installation-Part 3: Installation planning and practices outside buildings
EN 50174-3
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
The Influence of BS 6701:2004Linkages
EN 50173-X: The Missing Link
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
BS 6701:2004
ADDITIONALUK-SPECIFIC
CONFORMANCEREQUIREMENT
BS EN 50173-4 Ed.1
BS EN 50173-3 Ed.1
BS EN 50173-2 Ed.1
BS EN 50173-5 Ed.1
• parameters to be measured• sampling levels to be applied• marginal results
ADMINISTRATION
INSTALLATION
QUALITY ASSURANCE
EN 50174 series
TOTAL
EN 50173-X: THE MISSING LINKIssue 5
25A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Linkage to BS 7671Linkages
EN 50173-X: The Missing Link
ADDITIONALUK-SPECIFIC
CONFORMANCEREQUIREMENT
BS 7671
BS
6701
BS
7671
DESIGNPLANNING
INSTALLATION
INSPECTIONTESTING
BS
EN 5
0346
BS
EN 5
0174
-1
BS
EN 5
0174
-2
BS
EN 5
0174
-3
BS
EN 5
0173
-2
BS
EN 5
0173
-3
BS
EN
501
73-4
BS
EN 5
0173
-5
BS
EN 5
0310
BS
EN 5
0173
-1
BS 6701:2004
BS EN 50173-4 Ed.1
BS EN 50173-3 Ed.1
BS EN 50173-2 Ed.1
BS EN 50173-5 Ed.1
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
The Future of EN 50174-XLinkages
EN 50173-X: The Missing Link
EN 50174-2: Ed.1: 2000
Information technology - Cabling installation-Part 2: Installation planning and practices inside buildings
EN 50174-1 Ed.1: 2000Information technology - Cabling installation-Part 1: Specification and Quality Assurance
Information technology - Cabling installation-Part 3: Installation planning and practices outside
buildings
EN 50174-3 Ed.1: 2003
Foreword1 Scope2 Normative references3 Terms, definitions and abbreviations4 Requirements for installers of telecommunications equipment and telecommunications cabling5 Requirements for owners of premises housing telecommunications systems
Bibliography
BS 6701:2004 Telecommunications equipment and telecommunications cabling -Specification for installation, operation and maintenance
INSTALLER
OWNERS OFPREMISES
may delegate the responsibilities specified to authorized persons e.g designers, specifiers, operators and maintainers
of the telecommunications systems.
the person/organization undertaking the physical installation of the cabling
EN 50174-1 Ed.2: 2007
EN 50174-2 Ed.2: 2007
EN 50173-X: THE MISSING LINKIssue 5
26A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
The Future of EN 50174-1Linkages
EN 50173-X: The Missing Link
Foreword1 Scope2 Normative references3 Terms, definitions and abbreviations4 Requirements for planning installations of information technology cabling5 Requirements for installers of information technology cabling...
EN 50174-1 Ed.2: 2007 Information technology - Cabling installation-Part 1: Specification and Quality Assurance
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
The Future of EN 50174-2Linkages
EN 50173-X: The Missing Link
Foreword1 Scope2 Normative references3 Terms, definitions and abbreviations4 Requirements for planning installations of information technology cabling5 Requirements for installers of information technology cabling6 Segregation of metallic information technology cabling and mains power cabling..X1 Office premisesX2 Industrial premisesX3 HomesX4 Data centres..
EN 50174-2 Ed.2: 2007 Information technology - Cabling installation-Part 2: Installation planning and practices inside buildings
EN 50173-X: THE MISSING LINKIssue 5
27A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ BS
EN 5
0310
The Impact of EN 50173-XLinkages
EN 50173-X: The Missing Link
DESIGNPLANNING
INSTALLATION
INSPECTIONTESTING
BS
EN 5
0346
BS
EN 5
0174
-1
BS
EN 5
0174
-2
BS
EN 5
0174
-3
BS
EN 5
0173
-1
BS
EN 5
0310
BS
6701
BS
7671
DESIGNPLANNING
INSTALLATION
INSPECTIONTESTING
BS
EN 5
0346
BS
EN 5
0174
-1
BS
EN 5
0174
-2
BS
EN 5
0174
-3
BS
EN 5
0173
-2
BS
EN 5
0173
-3
BS
EN
501
73-4
BS
EN 5
0173
-5
BS
EN 5
0310
BS
EN 5
0173
-1
EN 50174-1 Ed.2: 2007
EN 50174-2 Ed.2: 2007
INCREASED COMPONENT/SYSTEM
SUPPLIER FOCUS
SIMPLIFIEDSYSTEM/INSTALLER
WARRANTIES
STREAMLINEDTRAINING/QUALIFICATIONS
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
AdministrationLinkages
EN 50173-X: The Missing Link
Text being considered for 5MP draft of EN 50174-1
JointsPathwaysSpaces
Cords/jumpers
Termination points
Fire barriers
Cabinets/frames Cables Closures
Bonds - functional earthBonds - protective earth
Iden
tifie
rsLa
bels
Rec
ords
Iden
tifie
rsLa
bels
Rec
ords
Iden
tifie
rsLa
bels
Rec
ords
Iden
tifie
rsLa
bels
Rec
ords
Iden
tifie
rsLa
bels
Rec
ords
Fixed cablingCord connectionsService delivery
M MM
EE
EA
EAA
Labelled both ends
Labelling with unique identification not required. National or local regulation applies.
Labelled at entrances
MManualEElectronicAAutomated
Level1
Level2
Level3
Level4
Level5
No. of fixed cables 2-50 51-500 501-10000 >>>> 10001
Level 1Level 2Level 1Level 1Level 3
Homes Multi-tenant residential premisesOffice premisesIndustrial premisesData centres
Level 2Level 3Level 2Level 2Level 3
Level 3
Level 3
Level 4Level 4Level 4Level 4
Level 3Level 3
MINIMUM ADMINISTRATION REQUIREMENTS
EN 50173-X: THE MISSING LINKIssue 5
28A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Segregation - ILinkages
EN 50173-X: The Missing Link
the electromagnetic environment complies with the levels defined in the EN 61000-6 series forconducted (e.g. from power lines) and radiated disturbances (power lines)
the mains power supply is “non-deformed” but has high frequency content consistent with theswitching and operation of connected equipment in accordance with the EN 61000-6 series
national regulations for safety may contain different segregation requirements• safety has highest priority but the more stringent requirement shall take precedence
premises-specific clauses may contain modified segregation requirements
manufacturers' instructions requiring more stringent installation practices shall be followed
Screened Unscreened Coaxial/twinaxial
Segregation Classification Coupling attenuation30-100 MHz
TCL30-100 MHz
Screening attenuation30-100 MHz
d
c
b
a
≥≥≥≥ 80 dB
≥≥≥≥ 55 dB
≥≥≥≥ 40 dB
<<<< 40 dB
≥≥≥≥ 60-10*log(f) dB (ffs)
≥≥≥≥ 50-10*log(f) dB (ffs)
≥≥≥≥ 40-10*log(f) dB
<<<< 40-10*log(f) dB
≥≥≥≥ 85 dB
≥≥≥≥ 55 dB
≥≥≥≥ 40 dB
<<<< 40 dBIf the cable performance is unknown then it shall be assumed to meet the requirements of Segregation Classification “a”Cables meeting Category 7/BCT-C meet Segregation Classification “d”Screened cables meeting Category 5/6 meet Segregation Classification “c” and may deliver performance of “d”Unscreened cables meeting Category 5/6 meet Segregation Classification “b” and may deliver performance of “c” or “d”
IT cable
ASSUMPTIONS
Text being considered for 5MP draft of EN 50174-2
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Segregation - IaLinkages
EN 50173-X: The Missing Link
the electromagnetic environment complies with the levels defined in the EN 61000-6 series forconducted (e.g. from power lines) and radiated disturbances (power lines)
the mains power supply is “non-deformed” but has high frequency content consistent with theswitching and operation of connected equipment in accordance with the EN 61000-6 series
national regulations for safety may contain different segregation requirements• safety has highest priority but the more stringent requirement shall take precedence
premises-specific clauses may contain modified segregation requirements
manufacturers' instructions requiring more stringent installation practices shall be followed
Screened Unscreened Coaxial/twinaxial
Segregation Classification Coupling attenuation30-100 MHz
TCL30-100 MHz
Screening attenuation30-100 MHz
d
c
b
a
≥≥≥≥ 80 dB
≥≥≥≥ 55 dB
≥≥≥≥ 40 dB
<<<< 40 dB
≥≥≥≥ 70-10*log(f) dB (ffs)
≥≥≥≥ 60-10*log(f) dB (ffs)
≥≥≥≥ 50-10*log(f) dB
<<<< 50-10*log(f) dB
≥≥≥≥ 85 dB
≥≥≥≥ 55 dB
≥≥≥≥ 40 dB
<<<< 40 dBIf the cable performance is unknown then it shall be assumed to meet the requirements of Segregation Classification “a”Cables meeting Category 7/BCT-C meet Segregation Classification “d”Screened cables meeting Category 5/6 meet Segregation Classification “c” and may deliver performance of “d”Unscreened cables meeting NEW Category 5/6 meet Segregation Classification “b” and may deliver performance of “c” or “d”
IT cable
ASSUMPTIONS
Text being considered for 5MP draft of EN 50174-2
EN 50173-X: THE MISSING LINKIssue 5
29A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Segregation - IILinkages
EN 50173-X: The Missing Link
Solid metalliccontainment
See Note 4
Open metalliccontainment
See Note 1
SegregationClassification
Separation w/oEM barrier
0 mm35 (ffs) mm d 55 mm
0 mm50 (ffs) mm c 80 mm
0 mm80 (ffs) mm b 100 mm
0 mm300 mm a 300 mm
Powerfactor
(P)
Electrical circuittype No. of circuits
0,420 A, 230 V 1-phase
1-5
16-15
3-phase cables are treated as 3 off 1-phase cablesMore than 20 A are treated as multiples of 20ALow voltage AC or DC power supply cables are treated based upon current ratings i.e. a 100 A 50 VDC cable = 5 off 20 A cables (P = 1)
Powerfactor
(P)446-60
561-75
6>>>> 75
216-30
331-45
Powerfactor
(P)No. of circuits No. of circuits
Text being considered for 5MP draft of EN 50174-2
Screening performance (DC-100 MHz) equivalent to steel tray (duct without cover) of 1,0 mm wall thickness and no more than20% equally distributed perforated area.
Screening performance (DC-100 MHz) equivalent to welded mesh steel basket of mesh size 50 mm x 100 mm (ladder is excluded)
Screening performance (DC-100 MHz) equivalent to a steel conduit of 1,5 mm wall thickness. Separation specified is in additionto that provided by any divider/barrier.
The upper surface of installed cables shall be at least 10 mm below the top of the barrier.
12
3
4
Perforated metalliccontainment
See Notes 2 and 3
28 mm
40 mm
50 mm
150 mm
S
The final text of the 5MPdraft contains
amendments to Notes 2and 3 as shown here.
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Segregation - OfficesLinkages
EN 50173-X: The Missing Link
Text being considered for 5MP draft of EN 50174-2
Information technology
cabling distribution
point
Termination point
Mains power cabling
No segregation for EMI
≤≤≤≤ 15 metres
Information technology cabling
Separation (A) = S x P
The segregation requirements are relaxed in proximity to termination points that provide connection toterminal equipment (i.e. the telecommunications outlets of EN 50173-2 or their equivalent within application-specific cabling designs). The relaxation is to allow information technology cabling and mains power cablingto be installed in close proximity in small cross-sectional area cable management systems such as trunkingand pillars.Provided that the applicable power cabling factor (P) is no greater than 1, the value of A = 0 mm for a distanceof up to 15 m from the termination point.NOTE 1 National regulations may require a barrier or greater separation.NOTE 2 Certain combinations of information technology cabling and mains power cabling products may allow the relaxationdistance to be increased in accordance with the instructions provided by their suppliers. Such implementations lie outside the scopeof this standard and may restrict the flexibility of the pathways to be used for other products.
EN 50173-X: THE MISSING LINKIssue 5
30A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
The Future of BS 6701Linkages
EN 50173-X: The Missing Link
BS 6701:2004
BS EN 50174-3 Ed.1
BS EN 50174-2 Ed.2
BS EN 50174-1 Ed.2BS 6701:2007
BIP 0007
CITA - Construction Industry Trade AllianceCITA (Council for Information on Tranquillisers and Antidepressants)
Commission on International and Trans-Regional AccreditationCouncil For Involuntary Tranquilliser AddictionCanadian Institute for Theoretical Astrophysics
Communicationsand Information Technology Association
EN 50173-X: THE MISSING LINKIssue 5
31A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
TestingLinkages
EN 50173-X: The Missing Link
Conforming to EN 50346:2002Amendment of EN 50346
Marginal Results
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Conforming to EN 50346:2002Linkages
EN 50173-X: The Missing Link
EN 50346: 2002 Information technology - Cabling installation - Testing of installed cabling
IEC 61935-1:2000
Clause 4 General requirements
Clause 5 Balanced cabling
SMF
MMF Internal requirements
IEC 61280-4-2
Clause 6 Optical fibre cabling
EN 50173-X: THE MISSING LINKIssue 5
32A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Amendment 1 of EN 50346Linkages
EN 50173-X: The Missing Link
EN 50346 Edition 1.1:2007 Information technology - Cabling installation - Testing of installed cabling
IEC 61935-1:2000
Clause 4 General requirements
Clause 5 Balanced cabling
Clause 6 Optical fibre cabling ISO/IEC 14763-3
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Amendment 2 of EN 50346Linkages
EN 50173-X: The Missing Link
EN 50346 Edition 1.2:200X Information technology - Cabling installation - Testing of installed cabling
IEC 61935-1:200XClause 5 Balanced cabling
Balanced cablingInsertion lossReturn lossNEXT (pp)
ELFEXT (pp)
ACR (pp)
Operating voltagePower feeding
ResistanceResistance unbalance
Propagation DelaySkewTCLELTCTLCoupling attenuation
PSNEXT
PSELFEXT
PSACR
EN 50173-X: THE MISSING LINKIssue 5
33A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Marginal ResultsLinkages
EN 50173-X: The Missing Link
EN 50173-4 Ed.1 (2007)
EN 50173-3 Ed.1 (2007)
EN 50173-2 Ed.1 (2007)
EN 50173-5 Ed.1 (2007)
CONNECTINGHARDWARE
AT SPECIFIEDINTERFACES
OTHERCONNECTINGHARDWARE
STRUCTURE
CHANNELPERFORMANCE
LOCAL SAFETY RULES
• parameters to be measured• sampling levels to be applied• marginal results
EN 50174 series
ADMINISTRATION
INSTALLATION
QUALITY ASSURANCE
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Acceptance of Marginal ResultsLinkages
EN 50173-X: The Missing Link
Performance limit Measurementaccuracy
Test resultspread
Minimallycompliantproduct
Non-compliantproduct
Supercompliantproduct
PASS
* PASS
* FAIL
FAIL
EN 50173-X: THE MISSING LINKIssue 5
34A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Impact of Marginal ResultsLinkages
EN 50173-X: The Missing Link
Performance limit
Measurementaccuracy
Test resultspread
Test resultspread
Super-compliantproductONLY
Marginal results OK Marginal results denied
Minimallycompliantproduct
Non-compliantproduct
Super-compliantproduct
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Range of Marginal ResultsLinkages
EN 50173-X: The Missing Link
Performance limit
Minimallycompliantproduct
Non-compliantproduct
Super-compliantproduct
Measurementaccuracy
Non-compliantproduct
Super-compliantproduct
Test resultspread Test result
spread
EN 50173-X: THE MISSING LINKIssue 5
35A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
The Imminent FutureEN 50173-X:
The Missing Link
Wireless and CCCB OverlaysNew Parameters
New ClassesNew Categories
CLC TRs for User Groups
MICE
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
MICEEN 50173-X:
The Missing Link
EN 50173-1 Edition 2.1
MICE Annex (Explanatory)
To be deleted and to reference ISO/IEC TR (or CLC TR)
EN 50173-X: THE MISSING LINKIssue 5
36A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
Wireless OverlaysEN 50173-X:
The Missing Link
EN 50173-2 Edition 1.1
EN 50173-3 Edition 1.1
EN 50173-5 Edition 1.1
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
CCCB OverlaysEN 50173-X:
The Missing Link
EN 50173-2 Edition 1.1
EN 50173-3 Edition 1.1
EN 50173-5 Edition 1.1
EN 50173-X: THE MISSING LINKIssue 5
37A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
New Parameters: IEN 50173-X:
The Missing Link
Balanced cablingInsertion lossReturn lossNEXT (pp)
ELFEXT (pp)
ACR (pp)
Operating voltagePower feeding
ResistanceResistance unbalance
Propagation DelaySkewTCLELTCTLCoupling attenuation
PSNEXT
PSELFEXT
PSACR
ACR-F (pp ACR Far End)PS ACR-F (PSACR Far End)ACR-N (pp ACR Near End)PS ACR-N (PSACR Near End)
EN 50173-1 Edition 2.1
EN 50346 Edition 1.2
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
New Parameters: IIEN 50173-X:
The Missing Link
Balanced cablingInsertion lossReturn lossNEXT (pp)
ELFEXT (pp)
ACR (pp)
Operating voltagePower feeding
ResistanceResistance unbalance
Propagation DelaySkewTCLELTCTLCoupling attenuation
PSNEXT
PSELFEXT
PSACR
PS ANEXT (worst pair)PS ANEXT (mean)PS A ACR-F (worst pair)PS A ACR-F (mean)
Alien crosstalk
EN 50173-1 Edition 2.2
EN 50346 Edition 1.2
EN 50173-X: THE MISSING LINKIssue 5
38A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
New ClassesEN 50173-X:
The Missing Link
CCCB
BCT-B (1-pr channel)
A
B
C
D
E
F
0.01 0.1 1 10 100 1000 MHz
600 MHz
1000 MHz
250 MHz
100 MHz
16 MHz
1 MHz
100 kHz
100 kHz
Tran
smis
sion
Cla
ss EA500 MHz
FA1000 MHz
EN 50173-1 Edition 2.2
EN 50173-2 Edition 1.2
EN 50173-3 Edition 1.2
EN 50173-5 Edition 1.2
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
New CategoriesEN 50173-X:
The Missing Link
Cables Connecting Hardware
Category 5, 6 and 7
Category 6A and 7A
EN 50173-1 Edition 2.2
EN 50173-2 Edition 1.2
EN 50173-3 Edition 1.2
EN 50173-5 Edition 1.2
EN 50173-X: THE MISSING LINKIssue 5
39A or B
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ
CLC TRs for User GroupsEN 50173-X:
The Missing Link
EN 50173-1 General requirements
EN 50173-2 Office premises
EN 50173-4 Homes
EN 50173-5 Data centres
EN 50173-3 Industrial premises
HOSPITALS?
AIRPORTS?
CLC TR 50xxx Application Notes
EN 50174-1
EN 50174-2
EN 50174-3
EN 50346
EN 50310
CONTENTS
The New Standards
Introduction to MICE
Linkages
The Imminent Future
© 2006 The Cabling Partnershipwww.it-cabling.com www.e-readybuilding.com
P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
Overview
Selection and Application
Components and Cabling
Testing
Planning and Installation
ϕ The End