Kabeldon MV Products 7.2-36 kV
© ABB Group May 27, 2014 | Slide 1
Mike Brandt / Greg Schaufelbuhl – Kabeldon - Technology Days 21-22 May 2014
Content
Introduction
ABB Kabeldon History
Terminations & Joints
MV - HDC Cable Cabinet
Questions
© ABB Group May 27, 2014 | Slide 2
Team
Mike Brandt ABB Front End Sales – Cape Town Greg Schaufelbühl ABB – Chanel Partner - Cape Town
ABB Alingsås Sweden Proven Reliability
1888 Sieverts Kabelverk in Sundbyberg.
1928 Sieverts Kabelverk taken over by LM Ericsson.
1956 Manufacturing of cable accessories moving to Alingsås.
1969 Restricted as a separate division.
1972 Kabeldon AB
Liljeholmes Kabelfabrik (later ASEA Kabel) as 50% owner.
1985 ASEA Kabel 100% owner.
1988 ABB, ASEA Brown Boveri is founded.
1995 ABB Kabeldon AB.
1996 New factory in Alingsås (Sävelund).
2004 ABB Automation Technologies AB.
2007 ABB AB.
Max Sievert 1849-1913
1956 Alingsås (Plangatan)
1996 Alingsås (Sävelund)
© ABB Group May 27, 2014 | Slide 3
ABB Alingsås Sweden Over the years………..
© ABB Group May 27, 2014 | Slide 4
Premoulded cable accessories 12-24 kV KSP
Kabeldon IP-System Termini Enclosures CDC/ SDC KRN/KRD
Overroll Connect IT
Kabeldon IP-system II
1956 1968 1977 1987 1997 1998 1999 2006 2008
HDC
One-piece joint 52 – 245 kV
Bolt technology
© ABB Group May 27, 2014 | Slide 5
Outdoor terminations: porcelain or composite.
Dry flexible terminations.
Terminations for GIS / TRF.
Premoulded joints.
Tools and accessories.
World renowned
training.
ABB CAA 52 - 420 kV Product overview
© ABB Group May 27, 2014 | Slide 6
Screened separable cable connector Kabeldon CSE-A, CSS-A 12/24 kV 36/42 kV
Connectors for XLPE-insulated 1- or 3-core cables with Al or Cu conductors, 12, 24, 36 and 42 kV.
Fits standard bushings - EN 50181 type outer cone.
Design
Premolded connector body made from three layers of rubber.
Stress grading adapter.
Supplied with bolt type cable lug and connector.
Supplied in kits of three.
Screened Separable Cable Connectors Kabeldon CSE-A, CSS-A12, 24, 36 and 42 kV
Month DD, Year | Slide 7 © ABB Group
CSE-A / CSS-A meets the requirements of: • IEC 61442 • CENELEC HD 629.1 S2
Safe, simple and fast installation.
Premolded connector body.
Cold-applied.
Cable lug and connector of bolt type.
No special tools.
Minimized cable stripping.
Small outer dimensions. Premolded connector body in
soft rubber material. Active pressure.
Fewer sizes to cope with most cable dimensions.
Complete kits. Long storage life.
Screened Separable Cable Connectors Kabeldon CSE-A, CSS-A12, 24, 36 and 42 kV
Month DD, Year | Slide 8 © ABB Group
Cable lugs with shear-off bolts.
Fixed earth conductor. Capacitive measuring point
as standard. Touch proof. Few sizes for a wide range
of cables. 95 – 240 mm² in same
connector.
Screened Separable Cable Connectors Kabeldon CSE-A, CSS-A
Month DD, Year | Slide 9 © ABB Group
12 and 24 kV
36 and 42 kV
Screened Separable Connectors Kabeldon CSE-A, CSS-A 12 kV and 24 kV
Month DD, Year | Slide 10 © ABB Group
CSE-A 12 kV Designation
Conductor cross
section (mm²)
XLPE diam. (mm)
Rated current
(A)
Bushing type
EN 50181
CSE-A 12250-01 10-16 10-12 250 A
CSE-A 12250-02 25-95 13-22 250 A
CSS-A 12250-01 10-16 10-12 250 A
CSS-A 12250-02 25-95 13-22 250 A
CSE-A 12400-01 25-70 13-20 400 B
CSE-A 12400-02 95-300 18.5-30.5 400 B
CSE-A 12630-01 25-70 13-20 630 C
CSE-A 12630-02 95-300 18.5-30.5 630 C
CSE-A 12630-03 400-630 30.5-45 630 C
CSE-A 24 kV Designation
Conductor cross section
(mm²)
XLPE diam. (mm)
Rated current
(A)
Bushing type
EN 50181
CSE-A 24250-01 10-16 13-22 250 A
CSE-A 24250-02 25-95 17-25.5 250 A
CSS-A 24250-01 10-16 13-22 250 A
CSS-A 24250-02 25-95 17-25.5 250 A
CSE-A 24400-01 25-70 17-24 400 B
CSE-A 24400-02 95-300 22.5-35 400 B
CSE-A 24630-01 25-70 17-24 630 C
CSE-A 24630-02 95-300 22.5-35 630 C
CSE-A 24630-03 400-630 30.5-45 630 C
12 and 24 kV
Screened Separable Connectors Kabeldon CSE-A 36 and 42 kV
Month DD, Year | Slide 11 © ABB Group
CSE-A 36 kV Designation
Conductor cross section
(mm²)
XLPE diam. (mm)
Rated current
(A)
Bushing type
EN 50181
CSE-A 36400-01 50-95 24.5-34 400 B
CSE-A 36400-02 95-300 27.5-42 400 B
CSE-A 36630-01 50-95 24.5-34 630 C
CSE-A 36630-02 95-300 27.5-42 630 C
CSE-A 36630-03 400-630 38-55 630 C
36 and 42 kV
CSE-A 42 kV Designation
Conductor cross section
(mm²)
XLPE diam. (mm)
Rated current
(A)
Bushing type
EN 50181
CSE-A 42400-01 50-70 24.5-34 400 B
CSE-A 42400-02 95-300 27.5-42 400 B
CSE-A 42630-01 50-70 24.5-34 630 C
CSE-A 42630-02 95-300 27.5-42 630 C
CSE-A 42630-03 400-630 38-55 630 C
© ABB Group May 27, 2014 | Slide 12
Kabeldon Screened Separable Connectors CSE-A 250 A and CSS-A 250 A, Straight and Elbow
1. Pin contact with integrated conductor connection.
2. Capacitive test point covered with cap of conductive rubber - touch proof.
3. Conductive inner deflector Faraday´s cage.
4. Bail restrain for fixing to the bushing.
5. Outer conductive layer, UV- Ozone- and tracking resistant.
6. Stress grading adapter.
7. Earth Connection.
Screened Separable Connectors Kabeldon CSS-A 250 A Straight
Month DD, Year | Slide 13 © ABB Group
1
4
6 5
3 2
7
1. Pin contact with integrated conductor connection.
2. Bail restrain for fixing to the bushing.
3. Capacitive test point covered with cap of conductive rubber - touch proof.
4. Conductive inner deflector Faraday´s cage.
5. Outer conductive layer, UV- Ozone- and tracking resistant.
6. Stress grading adapter.
7. Earth connection.
Screened Separable Connectors Kabeldon CSE-A 250 A Elbow
Month DD, Year | Slide 14 © ABB Group
1 2
6
5
4 3
7
PSSK Screen separation kit
To prevent flashover between the phases, for instance in a switchgear.
Screened Separable Connectors Accessories for CSE-A 250 A and CSS-A 250 A
Month DD, Year | Slide 15 © ABB Group
IP 250 Insulating plug • Used when energizing a
disconnected connector.
JP 250 Earth circuit connector
For short circuit protective earthing on a disconnected connector.
The 50 mm² flexible copper conductor is 1000 mm long and must be connected to earth on the opposite side.
Tested for 11.6 kA during 1 sec.
MA 250 Measurement adapter
IP 250 Screened insulating plug
IH-A 24250 Insulating hood
Screened Separable Connectors Accessories for CSE-A 250 A and CSS-A 250 A
Month DD, Year | Slide 16 © ABB Group
CU 250
Coupling piece
To connect two connectors front by front.
MA 250
Measurement adapter
• To be used on a disconnected connector
• For different type of measuring up to 5 kV DC for instance when determining phases (phase coloring)
© ABB Group May 27, 2014 | Slide 17
Kabeldon Screened Separable Connectors CSE-A 400 A Elbow
1. Insulating plug in epoxy with brass cover. Test point covered with cap of conductive rubber.
2. Pin-contact.
3. Bail restrain.
4. Cable lug with shear off bolts.
5. Conductive inner deflector Faraday´s cage.
6. Stress grading adapter.
7. Outer conductive layer, UV- Ozone- and tracking resistant.
8. Earth Connection.
Screened Separable Connectors Kabeldon CSE-A 400 A Elbow
Month DD, Year | Slide 18 © ABB Group
1
3
6
5
4
7
2
8
Screened Separable Connectors Accessories for CSE-A 400 A
Month DD, Year | Slide 19 © ABB Group
IP 400 Insulating plug Used when energizing a disconnected connector.
PSSK Screen separation kit To prevent flashover between the phases, for instance in a switchgear.
TSH Branch seal kit To achieve a sealing on each core for 3-core cable.
IH-A 24400, 42400 Insulating hood Insulating hood, of flexible rubber with outer conductive layer and a preinstalled insulating rod. To be mounted on the bushing in a switch-gear or a transformer 400 A to insulate it when a cable is temporarily disconnected but other cables are energized.
Screened Separable Connectors Accessories for CSE-A 630 A, 12 – 24 kV and 36 – 42 kV
Month DD, Year | Slide 20 © ABB Group
MA 630 Measurement adapter
• To be used on a disconnected
connector • For different type of measuring
up to 5 kV DC for instance when determining phases (phase coloring)
© ABB Group May 27, 2014 | Slide 21
Kabeldon Screened Separable Connectors CSE-A, 630 A Elbow
1. Insulating plug in epoxy with brass cover. Test point covered with cap of conductive rubber.
2. M16 bolt for connection to bushing.
3. Cable lug with shear off bolts.
4. Conductive inner deflector Faraday´s cage.
5. Stress grading adapter.
6. Outer conductive layer, UV-, Ozone- and tracking resistant.
7. Earth Connection.
Screened Separable Connectors Kabeldon CSE-A, 630 A Elbow
Month DD, Year | Slide 22 © ABB Group
1
2
5
4
3
6
7
Screened Separable Connectors Accessories for CSE-A 630 A, 12 – 42 kV
Month DD, Year | Slide 23 © ABB Group
IP 630 Insulating plug Used when energizing a cable equipped with a disconnected connector.
PSSK Screen separation kit To prevent flashover between the phases, for instance in a switchgear.
TSH Branch seal kit To achieve a sealing on each core for 3-core cable
IH-A 24630, IH-A 42630 Insulating hood Insulating hood, of flexible rubber with outer conductive layer and a preinstalled insulating rod. To be mounted on the bushing in a switchgear or a transformer 630 A to insulate it when a cable is temporarily disconnected but other cables are energized. PG 630
Bushing Bushing for voltage testing, 12–24 kV.
PG-A 630 Bushing Bushing for voltage testing, 36–42 kV.
PC 630/250 Connector Parallel coupling piece. Replaces the plug in CSE-A 630 A when making a parallel connection to CSE-A 250 A. Delivered in 3-phase kits and hex bit socket.
MA-A 630 Measurement adapter Measurement adapter used for mega ohm Ω measurements and to perform different measurements up to 5 kV DC, for example determination of phases, 630 A.
JPA V Tool for earthing device, JPB 630.
CSAP-A Surge arrestor 12–24 kV, 5 and 10 kA.
CSEP-A Parallel cable connector.
JPB 630 Earth circuit connector For short circuit protective earthing on a disconnected connector. The 120 mm² flexible copper conductor is 1000 mm long and must be connected to earth on the opposite side. Tested for 20 kA during 1 sec.
Screened Separable Connectors Parallel connector
Month DD, Year | Slide 24 © ABB Group
Screened Separable Connectors Accessories for CSE-A 630 A, 12 – 24 kV
Month DD, Year | Slide 25 © ABB Group
PC 630/250, Parallel coupling – 12–24 kV
Replaces the plug and makes it possible to install a second connector type CSE-A 250 in parallel with an already installed connector CSE-A 630-01 and CSE-A 630-02.
Supplied In kits of three including one installation tool.
Screened Separable Connectors Accessories for CSE-A 630 A, 12 – 24 kV and 36 – 42 kV
Month DD, Year | Slide 26 © ABB Group
PG 630 Bushing for Voltage testing of the cable, 12–24 kV
Used on installed CSE-A
PG-A 630 Bushing for Voltage testing of the cable, 36–42 kV Used on installed CSE-A
Screened Separable Connectors Accessories for CSE-A 630 A, 12 – 24 kV and 36 – 42 kV
Month DD, Year | Slide 27 © ABB Group
MA-A 630 Measurement adapter To be used on a disconnected connector
For different type of measuring up to 5 kV DC for instance when determining phases (phase coloring)
Screened Separable Connectors Kabeldon CSE-A and CSS-A, 12, 24, 36 and 42 kV 250, 400 and 630 A
Month DD, Year | Slide 28 © ABB Group
Cable Accessories by ABB Kabeldon Cable Cabinets 12 – 36 kV, HDC-A
© ABB Month DD, YYYY | Slide 30
Increased demand for safer grid
The hurricane “Gudrun” in 2005
75.000.000 m³ forest blew down (2500 km x 6 m stack)
More than 100,000 households were still out of power 4 days after the hurricane, it took 40 days to restore the power for all households
Sweden received 81.7 MEUR from EU’s Solidarity Foundation
The storm “Per” in January 2007
…blew down another16 Million m³
New Swedish law
After 12h interruption: each subscriber receives minimum 90 EUR, after 24h min 180 EUR
2011: Maximum interruption 24h.
Cable Accessories by ABB Kabeldon Cable Cabinets 12 – 36 kV, on demand…
© ABB Month DD, YYYY | Slide 31
Distribution via overhead line
© ABB Month DD, YYYY | Slide 32
Distribution via HDC-A
© ABB Month DD, YYYY | Slide 33
Wind power park with Kabeldon HDC-A serving as junction points
Cable Accessories by ABB Cable grid with Kabeldon Cable Cabinets HDC-A
© ABB Month DD, YYYY | Slide 34
Cable Accessories by ABB Kabeldon Cable Cabinets 12 – 36 kV, HDC-A
© ABB Month DD, YYYY | Slide 35
Cable Accessories by ABB Kabeldon Cable Cabinets 12 – 36 kV, HDC-A
Make a T-off with 12-36 kV XLPE-cable above the ground.
Applications for 250 A or 630 A.
Screened separable cable connectors with its outer surface connected to earth.
Capacitive test point at the back of the connectors.
Possible to disconnect optional cable for earthing or voltage in specific section only.
© ABB Month DD, YYYY | Slide 36
Cable Accessories by ABB HDC-A – Type test
Enclosures Impact coding test - in accordance with IEC 60529. Fulfills IP 34D. Mechanical impact test - in accordance with IEC 60439-5
”Low voltage switchgear and controlgear”. Cable connectors Fulfills CENELEC HD 629.1 S2
”Test methods and requirements on accessories for use on power cables of rated voltage from 3.6/6/7.2) up to 20.8/36(42) kV”.
Cable Accessories by ABB HDC-A – Variants
© ABB Month DD, YYYY | Slide 37
Conductor Designation A
25-95 mm² HDC-A 12250 250
25-70 mm² HDC-A 12630-01 630
95-300 mm² HDC-A 12630-02 630
400-630 mm² HDC-A 12630-03 630
12 kV
24 kV Conductor Designation A
25-95 mm² HDC-A 24250 250
25-70 mm² HDC-A 24630-01 630
95-300 mm² HDC-A 24630-02 630
400-630 mm² HDC-A 24630-03 630
Conductor Designation A
50-95 mm² HDC-A 36630-01 630
95-300 mm² HDC-A 36630-02 630
400-630 mm² HDC-A 36630-03 630
36 kV
HDC-A for wind farms
Optimized cable routing and excavation, saves money and time. Lessens the environmental impact.
Makes individual disconnection of turbine possible. If one turbine fails, others can continue to produce.
Up to three windmills can be connected to each cable cabinet.
Possibility to synchronize the voltage level directly in the cable cabinet – reduces the need for local substations.
Simplifies maintenance.
© ABB Month DD, YYYY | Slide 39
Screened connectors • 25 – 95 mm² • With capacitive measuring
point Straight through anchor bars
Fastening for padlock
Cable Accessories by ABB HDC-A 250, 12 – 24 kV. Design
Hot dip galvanized enclosure Dimensions Width 996 mm Depth 312 mm Height 1293 mm Height above ground 993 mm
Cable accessories by ABB HDC-A 250, 12 – 24 kV. Accessories
© ABB Month DD, YYYY | Slide 40
MA 250 Measurement adapter
KA 250 Transversal anchor bar
UKRA 90 Screen separation kit
IP 250 Screened insulating plug
IH-A 24250 Insulating hood
PSSK L Screen separation kit
TSH Branch seal kit
© ABB Month DD, YYYY | Slide 41
Screened connectors • 25 – 630 mm² • With capacitive test point
Hot dip galvanized enclosures Dimensions Width 996 mm Depth 522 mm Height 1293 mm Height above ground 993 mm
Straight through anchor bars
Fastening for padlock
Cable Accessories by ABB HDC-A 630, 12 – 36 kV. Design
Cable accessories by ABB HDC-A 630, 12 – 36 kV. Accessories
© ABB Month DD, YYYY | Slide 42
CSE-A Screened separable connector
IH-A 24630, IH-A 42630 Insulating hood
PG 630 Bushing
PG-A 630 Bushing
PSSK L Screen separation kit
UKRA 90 Screen separation kit
IP 630 Screened insulating plug
PC 630-3 Parallel coupling piece
PC 630-3 L Parallel coupling piece
PC 630/250 Connector
MA-A 630 Measurement adapter
JPA V Tool for earthing-for-work device
TSH Branch seal kit
KA 630 Transversal anchor bar
Kabeldon Cable Cabinet 12 – 36 kV Installation
Month DD, Year | Slide 43 © ABB Group
Min. 1.2 m
Gravel Fiber cloth
Gravel (grit size 1-8 mm) up to prefered cabinet height
Shall only be installed and operated by skilled staff familiar with cables, accessories and safe operating practices.
Before any work is carried out in the cabinet make sure that the voltage is switched off by using an open breaking point.
Always make sure that the cables are dead by measuring on the capacitive test point on the connectors.
Both 1- and 3-core cables may be installed within the same cabinet.
Always check that the cables are dead before any work is carried out.
Kabeldon Cable Cabinet 12 – 36 kV Working with HDC-A
© ABB Month DD, YYYY | Slide 44
Kabeldon is reliable junctions in power cable networks. Easier to connect cables safely. Reliable, well known, tried and tested. Used in power cable networks worldwide.
With Kabeldon you get ABB-quality all the way!
Reliable power grids with ABB. Accessible world wide through ABB. One supplier – one contact person. Professional training for safe installations.
© ABB Group May 27, 2014 | Slide 25 45
Kabeldon Medium Voltage Products
Conclusion
“We will provide companies that work with electric power with solutions which enable them to joint and connect cables easily and safely and distribute electricity”.