MicroTron Auto2
description
Transcript of MicroTron Auto2
MicroTron Auto-Monitoring & Dosing System for Cooling Tower Water Treatment
We know that open cooling tower systems offer perfect conditions for proliferation
and dissemination of bacteria such as Legionella.
While it is not possible to completely remove this risk without removal of the system,
it is possible to manage the risk. Taking a ‘Zero Tolerance’ approach to bacteria
control is particularly important for management in high profile, high risk sites. At the
heart of any cooling water risk management plan is the chemical dosage system.
Inter-Chemicals offer full range of dosing control equipment that can be tailored to
suit all applications. Our equipment packages are classified as below:
Key Components:
1.0 MicroTron Controller (Model: LCFB-2AD)
� Microprocessor control for Cooling Tower conductivity monitoring.
� Standard electrodes in ¾” SCH 80 PVC female slip tees.
� Standard Tower Conductivity Probes: TE-4A: 150psi (10.3 bar)/ 140ºF (58ºC)
Max
� Conductivity Control: 0-5000 µS/cm scale
� Accuracy: +/- 1%
� Feed Timers (Selectable)
• Pulse: 0-99 min, 59sec run time, 1-99 counts
• % of time: 0-99 min, 59sec run time, 1-99% time
• Feed with Bleed: Limit timer 0-99 min, 59 sec
• Post Feed Bleed: Limit timer 0-99 min, 59 sec cycle, 1-99% of bleed cycle
• Tower Biocide Timer: 28 day programmable with pre-bleed and bleed lockout
functions
‘ taking a zero tolerance
approach to bacteria control,
delivers piece of mind…’
� Enclosure: Heavy duty NEMA 4X type high impact thermoplastic with
padlockable gasketed Lexan viewing door.
2.0 Peristaltic Pump (Model: MP2-R) : 3 units
� Adjustable speed
� IP 65 rating enclosure
� Maximum Capacity: 1 litre/hour.
� Maximum pressure: 3 bar (43.5psi)
Liquid Ends Material Component Standard
Roller Tube EDPM
Fittings PP
Foot Filter AISI 316
Injection Valve AISI 316 - Viton
Discharge Tube PE 4 x 6 mm (0.15” x 0.23”)
Suction Tube Clear PVC 4 x 6 mm (0.15” x 0.23”)
3.0 Flow Assembly with Injection Points
� Burkert 2/2-way Solenoid Valve type 5281.
� Chemical Injection socket
� Sensor holder socket
� PVC check valve
� Isolation ball valve
� Sampling Ball Valve
4.0 PP Board with pipe bracket
� Dimensions: W 400mm x H 800 mm
� Fully assemble system and fixed to the board
5.0 Applications
� Re-circulating water systems.
� Cooling Tower water treatment system
� Auto bleed-off with conductivity control
� Fully automated chemical feed and biocide control
Recommended for High Risk/High Profile sites such as Hotels,
hospitals, shopping centres, high-rise CBD buildings as well as