MicroTron Auto2

2
MicroTron Auto-Monitoring & Dosing System for Cooling Tower Water Treatment We know that open cooling tower systems offer perfect conditions for proliferation and dissemination of bacteria such as Legionella. While it is not possible to completely remove this risk without removal of the system, it is possible to manage the risk. Taking a ‘Zero Tolerance’ approach to bacteria control is particularly important for management in high profile, high risk sites. At the heart of any cooling water risk management plan is the chemical dosage system. Inter-Chemicals offer full range of dosing control equipment that can be tailored to suit all applications. Our equipment packages are classified as below: Key Components: 1.0 MicroTron Controller (Model: LCFB-2AD) Microprocessor control for Cooling Tower conductivity monitoring. Standard electrodes in ¾” SCH 80 PVC female slip tees. Standard Tower Conductivity Probes: TE-4A: 150psi (10.3 bar)/ 140ºF (58ºC) Max Conductivity Control: 0-5000 μS/cm scale Accuracy: +/- 1% Feed Timers (Selectable) Pulse: 0-99 min, 59sec run time, 1-99 counts % of time: 0-99 min, 59sec run time, 1-99% time Feed with Bleed: Limit timer 0-99 min, 59 sec Post Feed Bleed: Limit timer 0-99 min, 59 sec cycle, 1-99% of bleed cycle Tower Biocide Timer: 28 day programmable with pre-bleed and bleed lockout functions ‘ taking a zero tolerance approach to bacteria control, delivers piece of mind…’

description

pdf

Transcript of MicroTron Auto2

Page 1: MicroTron Auto2

MicroTron Auto-Monitoring & Dosing System for Cooling Tower Water Treatment

We know that open cooling tower systems offer perfect conditions for proliferation

and dissemination of bacteria such as Legionella.

While it is not possible to completely remove this risk without removal of the system,

it is possible to manage the risk. Taking a ‘Zero Tolerance’ approach to bacteria

control is particularly important for management in high profile, high risk sites. At the

heart of any cooling water risk management plan is the chemical dosage system.

Inter-Chemicals offer full range of dosing control equipment that can be tailored to

suit all applications. Our equipment packages are classified as below:

Key Components:

1.0 MicroTron Controller (Model: LCFB-2AD)

� Microprocessor control for Cooling Tower conductivity monitoring.

� Standard electrodes in ¾” SCH 80 PVC female slip tees.

� Standard Tower Conductivity Probes: TE-4A: 150psi (10.3 bar)/ 140ºF (58ºC)

Max

� Conductivity Control: 0-5000 µS/cm scale

� Accuracy: +/- 1%

� Feed Timers (Selectable)

• Pulse: 0-99 min, 59sec run time, 1-99 counts

• % of time: 0-99 min, 59sec run time, 1-99% time

• Feed with Bleed: Limit timer 0-99 min, 59 sec

• Post Feed Bleed: Limit timer 0-99 min, 59 sec cycle, 1-99% of bleed cycle

• Tower Biocide Timer: 28 day programmable with pre-bleed and bleed lockout

functions

‘ taking a zero tolerance

approach to bacteria control,

delivers piece of mind…’

Page 2: MicroTron Auto2

� Enclosure: Heavy duty NEMA 4X type high impact thermoplastic with

padlockable gasketed Lexan viewing door.

2.0 Peristaltic Pump (Model: MP2-R) : 3 units

� Adjustable speed

� IP 65 rating enclosure

� Maximum Capacity: 1 litre/hour.

� Maximum pressure: 3 bar (43.5psi)

Liquid Ends Material Component Standard

Roller Tube EDPM

Fittings PP

Foot Filter AISI 316

Injection Valve AISI 316 - Viton

Discharge Tube PE 4 x 6 mm (0.15” x 0.23”)

Suction Tube Clear PVC 4 x 6 mm (0.15” x 0.23”)

3.0 Flow Assembly with Injection Points

� Burkert 2/2-way Solenoid Valve type 5281.

� Chemical Injection socket

� Sensor holder socket

� PVC check valve

� Isolation ball valve

� Sampling Ball Valve

4.0 PP Board with pipe bracket

� Dimensions: W 400mm x H 800 mm

� Fully assemble system and fixed to the board

5.0 Applications

� Re-circulating water systems.

� Cooling Tower water treatment system

� Auto bleed-off with conductivity control

� Fully automated chemical feed and biocide control

Recommended for High Risk/High Profile sites such as Hotels,

hospitals, shopping centres, high-rise CBD buildings as well as

remote locations. Recognised as industry best practice.