Micro-generation in local power grids · 2014-08-21 · storing energy or altering the electricity...
Transcript of Micro-generation in local power grids · 2014-08-21 · storing energy or altering the electricity...
ISRN LUTMDN/TMHP-14/5307-SE
ISSN 0282-1990
Micro-generation in local power grids
Balancing intermittency with energy storage
and demand response
Karin Hansson och Sara Olsson
Examensarbete på Civ.ingenjörsnivå
Avdelningen för energihushållning
Institutionen för Energivetenskaper
Lunds Tekniska Högskola | Lunds Universitet
Karin Hansson
Sara Olsson
Division of Efficient Energy Systems, Department of Energy Sciences
Lund University - Faculty of Engineering
2014-06-17
Micro-generation
in local power grids
Balancing intermittency with energy storage
and demand response
Föreliggande examensarbete på civilingenjörsnivå har genomförts vid Avd. för Energihushållning, Inst för
Energivetenskaper, Lunds Universitet - LTH samt vid E.ON Elnät Sverige AB i Malmö. Handledare på E.ON Elnät
Sverige AB: Alf Larsen; handledare på LU-LTH: prof. Jurek Pyrko; examinator på LU-LTH: dr Patrick Lauenburg.
Projektet har genomförts i samarbete med E.ON Elnät Sverige AB
Examensarbete på Civilingenjörsnivå
ISRN LUTMDN/TMHP-14/5307-SE
ISSN 0282-1990
© 2014 Karin Hansson och Sara Olsson samt Energivetenskaper
Energihushållning
Institutionen för Energivetenskaper
Lunds Universitet - Lunds Tekniska Högskola
Box 118, 221 00 Lund
www.energy.lth.se
i
Abstract
Global climate change has resulted in a need for an energy transition from fossil fuels
towards renewable energy sources. Small scale power production, e.g. micro-generation
from solar and wind, is an increasing part in this transition. These energy sources have a
varying power output which does not always match the demand. This intermittent power
generation poses challenges for the electricity grid which is conventionally dimensioned
according to a rather predictable load.
There are several ways to adapt the grid to these renewable and fluctuating energy sources;
namely by curtailment of the generation, reinforcements and extensions of the grid, demand
response and/or energy storage. This report has focused on how demand response and
energy storage can balance the fluctuations in a local power grid with a high penetration of
micro-generation from photovoltaics and small wind turbines. To answer this, both a
literature study and a case study of a planned city-district in Malmö, i.e. Hyllie, have been
performed.
Main results are that the load from micro-generation in a residential area will significantly
exceed the demand at certain occasions, mainly during noon in summer. If the area consists
of a mix of commercial and residential loads, the capacity limits of the grid will not be
exceeded. The most promising solutions to handle loads that exceed the capacity of a local
grid are batteries and critical peak pricing. Currently, and likely in the near future, batteries
are considerably more expensive than grid extensions. Also, the ownership of energy
storages is limited for a grid operator.
Recommendations for the future is to account for micro-generation when planning a local
grid with undiversified demand profiles as the production can exceed the demand and hence
the grid capacity.
Keywords
Micro-generation, DSO, energy storage, demand response, power variations
ii
Sammanfattning
Den globala klimatförändringen har lett till ett behov av en energiomställning från fossila till
förnybara energikällor. Småskalig elproduktion, såsom mikroproduktion från sol och vind,
spelar en allt större roll i denna omställning. Dessa energikällor ger en varierande
elproduktion som inte alltid överensstämmer med efterfrågan. Denna intermittenta
elproduktion innebär utmaningar för elnätet som konventionellt är dimensionerat enligt en
ganska förutsägbar belastning.
Det finns flera sätt att justera elnätet till dessa fluktuerande energikällor, nämligen; styra ned
produktionen, förstärka eller bygga ut elnätet, laststyrning och/eller energilager. Denna
rapport har fokuserat på hur laststyrning och energilager kan balansera variationerna i ett
lokalt elnät med en hög andel mikroproduktion från solceller och småskaliga vindkraftverk.
För att undersöka detta, har både en litteraturstudie av möjliga lösningar, samt en fallstudie
av en planerad stadsdel i Malmö, d.v.s. Hyllie, utförts.
De viktigaste resultaten från denna studie är att belastningen från mikroproduktionen i ett
bostadsområde väsentligt kan komma att överstiga efterfrågan vid vissa tillfällen,
huvudsakligen mitt på dagen under sommartid. Om området däremot består av en
blandning av bostäder och kommersiella verksamheter, kommer belastningen inte att
överskrida kapacitetsgränsen i nätet. De mest lovande lösningarna för att hantera laster som
överstiger nätkapaciteten i ett lokalt elnät är batterier och kritisk topp-prissättning. För
närvarande, och troligen inom den närmsta framtiden, är batterier betydligt dyrare än
nätutbyggnad. Dessutom är ägandet av energilager begränsat för nätägaren.
Rekommendationer för framtiden är att mikroproduktion bör tas i beaktning vid
planeringen av ett lokalt elnät med bostadslast, då produktionen i detta fall kan överstiga
nätkapaciteten.
Nyckelord
Mikroproduktion, nätägare, energilager, laststyrning, effektvariationer
iii
Preface
This report is a master thesis of 2 x 30 ECTS credits performed during the completion of the
MSc in Environmental Engineering at the Faculty of Engineering LTH. Energy system has
been the specialisation of the authors’ Master’s program. The work, which has been
performed on behalf of E.ON, is in line with the company’s strategy of cleaner and better
energy. The thesis was carried out under supervision from Alf Larsen, E.ON Elnät Sverige
AB and prof. Jurek Pyrko, Lund University.
iv
Acknowledgements
We would like to thank our supervisors Alf Larsen at E.ON and prof. Jurek Pyrko at
Lund University, Faculty of Engineering for guiding and pushing us in the right direction
during the process. We are also grateful to Anders Gustafsson and Patrik Vukalic, both at
E.ON, for assistance in understanding how the electricity grid is planned and operated.
Ingmar Leiβe has shown a great commitment and has been a valuable support concerning
all electro-technical issues. Remigiusz Pluciennik and his associates at E.DIS in Germany
and PhD Lars Henrik Hansen at DONG Energy in Denmark have hosted our study visits
and provided eye-opening experiences from other countries. We would also like to thank
Magnus Hjern, John Blomsterlind, Anna Lundsgård, Magnus Lindström and Peder Berne
at E.ON for indispensable input and data.
Last but not least, many thanks to all the staff at E.ON Elnät in Malmö for a friendly
reception and a valuable experience!
v
List of abbreviations
CAES – Compressed air energy storage
CPP – Critical peak pricing
DR – Demand response
DSO – Distribution System Operator
EV – Electric vehicle
Li-ion – Lithium ion
NaS – Sodium sulphate
Pb-acid – Lead acid
PV – Photovoltaic
RES – Renewable energy source
SEA – Swedish Electricity Act
SMES – Superconducting magnetic energy storage
SvK – Svenska Kraftnät
T&D – Transmission and distribution
TSO – Transmission System Operator
V2G – Vehicle to grid
vi
Content
1 Introduction ................................................................................................................................... 1
1.1 Purpose .................................................................................................................................. 1
1.2 Research questions ............................................................................................................... 2
1.3 Methods ................................................................................................................................. 2
1.4 Constrains .............................................................................................................................. 3
2 Background ................................................................................................................................... 5
2.1 Micro-generation .................................................................................................................. 5
2.1.1 PV .................................................................................................................................... 6
2.1.2 Wind power ................................................................................................................... 8
2.2 The Swedish power grid .................................................................................................... 10
2.2.1 Microgrid ..................................................................................................................... 11
2.2.2 Balance responsibility ................................................................................................ 12
2.3 Load and generation duration curve ............................................................................... 12
2.4 Power quality ...................................................................................................................... 14
3 Literature study .......................................................................................................................... 15
3.1 Energy storage possibilities ............................................................................................... 15
3.1.1 Mechanical storage ..................................................................................................... 16
3.1.2 Electrical storage ......................................................................................................... 19
3.1.3 Electrochemical storage ............................................................................................. 19
3.1.4 Chemical storage ........................................................................................................ 23
3.1.5 Ownership and regulations regarding energy storage ......................................... 23
3.1.6 Market trend for energy storage ............................................................................... 24
3.2 Demand response ............................................................................................................... 26
3.2.1 Tariffs ........................................................................................................................... 27
3.2.2 Capacity markets ........................................................................................................ 29
3.2.3 Direct load control ...................................................................................................... 31
3.2.4 Electric vehicles for demand response .................................................................... 31
3.2.5 Regulations regarding demand response ............................................................... 32
3.2.6 Market trend for demand response ......................................................................... 32
3.3 Comparison of balance methods ...................................................................................... 33
vii
3.3.1 Energy storages ........................................................................................................... 33
3.3.2 Demand response methods ....................................................................................... 40
3.4 Current situation in Germany .......................................................................................... 43
3.4.1 Die Energiewende ...................................................................................................... 43
3.4.2 The perspective from a German DSO ...................................................................... 44
3.5 Concluding remarks ........................................................................................................... 45
4 Case study of Hyllie ................................................................................................................... 47
4.1 Description of the area ....................................................................................................... 47
4.2 Method ................................................................................................................................. 47
4.2.1 Model for simulations ................................................................................................ 48
4.3 Results and analysis of simulations ................................................................................. 49
4.3.1 Scenario 1 – A conventional grid .............................................................................. 49
4.3.2 Scenario 2 – A grid with alternative solutions ....................................................... 57
4.3.3 Economic feasibility ................................................................................................... 62
4.4 Concluding remarks ........................................................................................................... 63
5 Discussion .................................................................................................................................... 65
5.1 Future prospects ................................................................................................................. 65
5.2 Uncertainty parameters ..................................................................................................... 66
5.3 Recommendations for further studies ............................................................................. 67
6 Conclusions ................................................................................................................................. 69
References ............................................................................................................................................ 70
Appendix A ......................................................................................................................................... 75
Appendix B .......................................................................................................................................... 76
Scenario 1 – A conventional grid .............................................................................................. 76
Scenario 2 – A grid with alternative solutions ....................................................................... 77
Standard deviation of the residential demand ....................................................................... 77
Appendix C ......................................................................................................................................... 78
1
1 Introduction
The global climate change is one of the greatest concerns of today and numerous measures
have been taken to reduce our emissions of greenhouse gases. In Europe, the so called
20-20-20 targets have been implemented in order to tackle the situation. These targets specify
that, until 2020, the greenhouse gas emissions shall reduce by 20%, that 20% of EUs’ energy
utilisation shall be renewable and that the energy efficiency shall increase by 20%.
Consequently, a transition from centralised fossil power production to renewable
decentralised production has been initialised.
The transition towards renewable energy sources (RES) as wind and solar, is however not
effortless. This is especially due to the intermittency, i.e. the varying abundance of these
resources. These variations cause problems in the electricity balance as the supply at all times
must match the demand. The imbalance between power generation and supply can result in
waste of renewable electricity at times of over-production and shortage, which might be
compensated by fossil power at times of under-production.
Renewable intermittent production also results in new challenges for the power grid, which
conventionally is designed to transport a rather constant electricity load from centralised
generation plants to the end-users. Intermittent, decentralised power production, e.g. micro-
generation, can cause bottlenecks in the power grid. Historically, these bottlenecks have
been solved by reinforcements in the grid, so called transmission and distribution (T&D)
upgrades. However, the increasing implementation of renewable power sources has raised
the interest in alternative solutions to accomplish the same results, which are possible by
storing energy or altering the electricity demand pattern, i.e. demand response (DR) (Eyer
and Corey, 2010).
This study has been initialised by E.ON Elnät in order to investigate and evaluate different
methods for energy storage and DR to match the local electricity demand with intermittent
micro-generation.
1.1 Purpose
The purpose of this study was to investigate: 1) of what magnitude future load variations
from micro-generation and demand can be in a local distribution grid, and 2) if energy
storage and/or DR are methods able to balance these variations in order to avoid or defer
T&D investments.
This study aims to serve as a survey for how a grid could be more flexible in order to handle
a future scenario with a high penetration of micro-generation. In order to fulfil the purposes,
the district Hyllie in Malmö has been used for simulations of load variations.
2
1.2 Research questions
The following questions have been in focus and are answered throughout the report:
How does a typical load profile look like for a local grid, with residential and
commercial activities, e.g. Hyllie, as well as a high penetration of micro-
generation?
Is the conventional electricity grid dimensioned to handle micro-generation or
does further measures have to be taken in the future?
What are the most promising sustainable energy storage possibilities for a local
grid with a high penetration of micro-generation?
Which DR method is the most suitable for peak reductions?
Are DR and/or energy storage enough to balance the intermittent micro-
generation?
Can energy storage be an economically viable solution compared to
reinforcements in the grid?
How are the solutions regulated and how does this affect the implementation of
the solutions?
1.3 Methods
In co-operation with E.ON Elnät Sverige AB, this master thesis has been accomplished at
Lund University – Faculty of Engineering LTH. In order to support the study, information
has been retrieved by semi-structured interviews with experts, as well as recent publications
within the field and at study visits to Dong Energy and IBM in Denmark and E-DIS in
Germany. These countries have been visited to gain knowledge of how a high penetration of
renewable energy affects the grid and to get an understanding of the challenges and possible
solutions to these.
The information has been processed in a literature study, consisting of a comparison of
different storage and DR technologies according to technical, financial and environmental
aspects. This results in a suggestion for a distributed system operator (DSO) of suitable
storages and DR methods for peak reduction in local grids.
To investigate of what magnitude the future load variations from micro-generation and
demand can be of in a local distribution grid a case study was performed. The district Hyllie
has been chosen for the case study as it has highly set environmental and energy ambitions
to 2020 and therefore, a high level of micro-generation is expected in the district. Hourly load
data from grid-connected photovoltaics (PVs) and multi-family dwellings were received
from E.ON Elnät Sverige AB. Production data from small-scale wind turbines has been
calculated based on wind metering from SMHI and a power curve from the turbine supplier.
Data processing was executed in Microsoft Office Excel with qualified assumptions to
visualise the load profiles and power variations that potentially can occur in a local grid in
Sweden year 2020.
3
1.4 Constrains
A macro-perspective with an economic, environmental and technical approach and a time
perspective of 2020 has been considered. The report has been conducted from the viewpoint
of a DSO, accordingly E.ON Elnät Sverige AB. Hence, not how a photovoltaic system or
wind turbine should be designed or positioned from a household’s perspective. The work is
restricted to the impact from micro-generation facilities in a local grid. A planned tax
reduction in Sweden has set the limit for the size of the studied micro-generation units.
Further, the Electricity Act and market rules in Sweden have been regarded when evaluating
balance solutions. Curtailment of renewable energy during times of excess electricity has not
been investigated further as the aim is to maximise the utilisation of renewables. Overall,
sustainable development permeates the reasoning and analysis throughout the report.
4
5
2 Background
In this section, the concept and technologies of micro-generation are explained. Also, the
structure of the Swedish power grid and the theory behind load and generation duration
curves are briefly described in order to facilitate the understanding of the following analysis.
2.1 Micro-generation
Micro-generation is commonly described as small-scale production of electricity to cover the
customers own electricity needs. In the Swedish Electricity Act, SEA (1997:857), micro-
generation is mentioned in the paragraph regarding small-scale production, 4th chap. 10 §,
and here defined as a production unit with a maximum output power of 43.5 kW and a fuse
subscription of maximum 63 A. However, a tax reduction proposal from the government of
Sweden is currently on remittance and is supposed to be decided during autumn 2014. This
proposal suggests a tax reduction of 0.6 SEK/kWh for a maximum production of 30 000
kWh/year for electricity production units with a fuse of up to 100 A (The Swedish
Government, 2014). If this becomes reality, it will mean that the producer can get a tax
reduction of up to 18 000 SEK/year. An interpretation made in this report is that the
proposed subsidy consequently will lead to that the legal definition for micro-generation will
change to 100 A which corresponds to 69 kW (according to Ohm’s law; P = U * I, where
U = 3*230 V and I = 100 A).
The most common systems for micro-generation are PV and smaller wind turbines, but it can
also be small combined heat and power plants (micro-CHP) as well as small hydro power
plants (Svensk Energi, 2011). The methods for micro-generation of electricity that are
relevant for this study are of renewable and intermittent nature, as can be seen in Figure 1.
A high penetration of micro-generation connected to the local grid can cause power
variations in the grid due to the weather-dependent and unpredictable production. The
variations can result in time periods of electricity scarcity or excess electricity production. In
general, the renewable intermittent energy sources with the highest excess production are PV
followed by wave power and onshore wind power (Lund, 2006).
6
Figure 1: The classification of electricity generation used in this report. After (Larsson & Ståhl, 2012, Svensk
Energi, 2011, The Swedish Government, 2014).
2.1.1 PV
Photovoltaic, abbreviated to PV, refers to the process where sunlight is converted into
electricity (Wenham et al., 2012).
The PV technology
Semiconductors, such as silicone, are common in PVs as they are stable and act insulating at
low temperatures but as good conductors at higher temperatures. When a semiconductor is
hit by light with enough energy, electrons can be released and act as charge carriers for an
electric current. This is called the photovoltaic effect and is the main principle for PV.
(Wenham et al., 2012)
The efficiency for silicon based PVs under laboratory conditions is approximately 25%.
Despite this, the commercial cells have a significantly lower efficiency which ranges between
13 – 19%. However, research continues in order to improve efficiency, lifetime and costs, but
also to develop PVs of other semiconductors and materials, such as organic polymers, i.e.
plastics. Even so, there is presently an accepted theoretical limit for the efficiencies which is
about 30%. (Wenham et al., 2012)
Power variations caused by PV
The output power from PV depends on the irradiation of the sun. The irradiation at a certain
location varies inter-annual, annual and diurnal (time of day). The inter-annual variations
are caused by the Milanković cycles, which describe the slow variations in solar irradiation at
the surface of the Earth caused by the changes of its motion around the sun and around its
own axis (Wenham et al., 2012). Annually, the production is highest in summer and lowest in
winter. Diurnally, the peak power output from PV is generally at noon. There is also a power
Renewable
Wind power
PV
Wave power
Bio power
Hydro power
Intermittent
Wind power
PV
Wave power
Micro (max. 69 kW, max. 100 A)
Wind power PV
7
variation caused by overcast, i.e. shadowing by clouds, which depends on weather
conditions.
In order to gain the highest energy output, the PVs should have an azimuth, i.e. the angular
distance from the south, of 0° and have a tilt from the horizontal plane of 90°- α, where α is
the latitude of the location (Wenham et al., 2012). Hence, the optimal PV tilt in Malmö is 35°.
To achieve a higher output during the winter season, a more vertical angle is preferable. To
modify the peak power output during the day, the azimuth angle can be altered.
In Sweden, the instantaneous power output can amount to 150 W/m2. The annual electricity
production ranges between 50 and 150 kWh/m2 (Svensk Solenergi, 2014).
Market trends
The expansion of PV has rushed forward the last 10 years, and it will most likely continue to
do so. The technology has been improved and the prices have declined, mainly as a
consequence of increased demand due to subsidies in countries such as Germany and
Denmark (Lindahl, 2013). The declining price trend of PV in Sweden is presented in Figure 2.
Figure 2: The Swedish price trend for typical turnkey PV systems (excluding VAT) reported by Swedish
installation companies (Lindahl, 2013).
Today, the only subsidy for PV in Sweden is a contribution of 35% of the installation cost. A
future tax reduction, as mentioned above, would facilitate for private customers to get a
reasonable payback of the investment. These subsidies, together with an increasing
environmental awareness as well as decreasing PV prices, increases the incentives of
producing own renewable electricity. Hence, market trends point towards that PV
installation in Sweden will most probably increase with a remarkable rate until 2020, see
Figure 3 (Lindahl, 2013). Notable is also that it is the distributed, grid-connected installations
that increases the most.
8
2.1.2 Wind power
Wind power is the conversion of wind energy into a useful form of energy, such as using
wind turbines to make electrical power
The wind turbine technology
Wind energy is the kinetic energy of air in motion, also called wind. The wind energy in an
open-air stream is proportional to the third power of the wind speed. Hence, the available
power increases eightfold when the wind speed doubles. It is thus important to place a wind
turbine at a location with high average wind speeds. Wind turbines can be classified into
horizontal axis wind turbines or vertical axis turbines, see Figure 4. The most common
design is horizontal axis wind turbines with three blades. (Manwell et al., 2009)
Figure 4: Horizontal and vertical axis wind turbines. After (EcoWatch Canada, 2013).
Small wind turbines, also referred to as distributed wind, are wind turbines installed on-site,
most often at homes or commercial buildings, which allows the facility to generate a portion
or all of the electricity demand from the wind. The definition of small wind turbines (SWTs)
has been ever changing and differs between countries. Generally, the term describes wind
Figure 3: The cumulative installed PV and yearly installed capacity trends in Sweden (Lindahl, 2013).
9
turbines with a rated power from 6 W to 300 kW. In order to cover the annual electricity
demand of a European household, a 4 kW wind turbine is needed. (World Wind Energy
Association, 2012)
Micro-generation by wind can be performed with either horizontal axis wind turbines or
vertical axis wind turbines. However, horizontal axis turbines are the most commercial and
mature technology whereas vertical axis turbines are still under development. Nevertheless,
micro-generation by vertical axis wind turbines will, in many cases, be advantageous in
comparison to horizontal axis wind turbines. This is due to the Swedish building laws, which
state that building permits are not required for small-scale turbines with a total height less
than 20 m and rotor diameter less than 3 m. As the power output is depending on the sweep
area, it is with a vertical axis turbine design possible to increase the sweep area for the same
rotor diameter by increasing the length of the turbine blades. As mentioned, for small-scale
applications, the vertical axis turbine can be favourable because of the higher power
production and the fact that it is independent of wind directions. Furthermore, they are more
silent in operation, which is a desirable feature for urban utilisation. Horizontal axis turbines,
however, are more widespread on the market than the vertical axis turbines. (Pyrko, 2014)
Power variations caused by wind power
The output power from wind turbines depends on the wind speed, which varies with the
height above the ground and the landscapes roughness due to e.g. forests and buildings etc..
Combined, these effects cause a constantly varying pattern of winds across the surface of the
Earth as well as turbulence. The wind at a certain location varies inter-annual, annual,
diurnal (time of day) and in short-term (turbulence and gusts). Inter-annual and short-term
variations of wind speed occur randomly and are therefore difficult to predict. Annually, the
available wind power is higher during winter months compared to summer months. The
diurnal variation in available wind power is typically an increase during the day and
decrease during the hours from midnight to sunrise. The largest diurnal variations occur in
spring and summer and the smallest in winter. (Manwell et al., 2009)
Market trends
Wind turbines have evolved greatly over the last 35 years and had a strong resurgence
during the 1990s with installed worldwide capacity increasing over fivefold. During this
decade, a shift towards larger, megawatt-sized, wind turbines and a growth of offshore wind
power was observed. The evolution period is however not yet over and meanwhile the best
onshore wind sites have already been exploited, the need for efficient small-scale wind
turbines increases. For a time, the expansion of wind power has mainly consisted of larger
scale turbines, but a possible increase in small-scale wind power is to be expected (Manwell
et al., 2009). Increasing fossil fuel prices, global warming and the ever-growing electricity
demand will be the three long-term drivers of the small wind industry. The World Wind
Energy Association has observed an annual 35% market increase for small wind turbines
during recent years and based on a conservative assumption, they expect the small wind
10
market to continue to grow with a rate of 20% from 2015 to 2020, see Figure 5 (World Wind
Energy Association, 2013).
Figure 5: World market forecast to 2020 for small wind turbines (World Wind Energy Association, 2013).
2.2 The Swedish power grid
The national grid in Sweden is owned by Svenska Kraftnät (SvK), which is a state-owned
company. Electricity in the voltage range of 220 – 400 kV is transferred from the largest
producers to the regional distribution grid, see Figure 6. At the regional grids, which are
owned by the larger system operators, the DSOs, e.g. E.ON Elnät Sverige AB, the electricity
is transported at 40 – 130 kV. The high voltage levels are due to the fact that losses are lower
at higher voltages. In the next step, the voltage is transformed down to the local grid with
medium voltage level; 10 – 20 kV. Thereafter in the local grid, the voltage is further lowered
to 400 V, before entering the dwellings, where the voltage reaches the customers at 230 V. To
larger electricity consumers, such as industries, the voltage can be delivered at higher
voltages. (E.ON, 2012)
11
Figure 6: The Swedish electricity grid structure. After (E.ON, 2012).
The power grid structure can be regarded as a monopoly as it is impossible for the customer
to choose which network company they want to deliver their electricity. This monopoly,
which is geographically divided between approximately 170 electricity grid operators, is due
to the national economic inefficiency in constructing and maintaining parallel infrastructure.
However, the grid operators are monitored by the Swedish Energy Markets Inspectorate
(Ei). This authority controls that the grid operators follow the Electricity Act. This includes
regulation and controlling of the revenues, but also that the fees charged by the network
company are fair and reasonable. (Swedish Energy Markets Inspectorate, 2013)
2.2.1 Microgrid
A microgrid, also commonly written µGrid, is an electricity grid that is capable of operating
in parallel with, or islanded from the existing utility’s grid. The Microgrid Exchange Group
defines a microgrid as a group of interconnected loads and distributed energy resources
within clearly defined electrical boundaries that acts as a single controllable entity with
respect to the grid. Microgrids can be seen as modern, small-scale versions of the centralised
electricity system. Various types of distributed energy resources together with customer
demand, creates varying load profiles that are balanced by energy storage systems within the
microgrid. (Fu et al., 2013)
Microgrids are often established to achieve local energy or environmental goals set by the
community. Even though, it can also be the DSO or the residents demanding for the
microgrid. A microgrid has the potential to maximise overall system efficiency, power
quality, and energy security for critical loads. Microgrids are envisioned to be
environmentally friendly and a promising way of building net zero energy communities,
12
which have the ability to supply themselves in the event of a grid outage. This is crucial for
critical infrastructures, such as hospitals, public facilities, military bases, and emergency-
response facilities (Fu et al., 2013). An example of an existing microgrid which operates in
parallel with the utility grid is UC San Diego Campus, which self-generates approximately
90% of annual demand with CHP, PV and fuel cells (UC San Diego, 2014-04-04).
Microgrids can be seen as an alternative approach to integrate small-scale distributed energy
resources into low-voltage electricity systems. According to Navigant Research, the
microgrid market corresponded to 10 billion USD in 2013 and is projected to increase to
more than 40 billion USD annually by 2020. (Fu et al., 2013)
2.2.2 Balance responsibility
It is essential that the supply at all times matches the use of electricity. It is stated in the 8th
chap. 7 - 10 §§ that an electricity consumer is obliged to ensure that there is someone who is
financially responsible for that the national electricity system is supplied with as much
electricity that is removed at the customer’s tap point, which is measured by the DSO. This
financial obligation is called balance responsibility and lies with the electricity supplier who
can take the responsible itself or assign it to another party, through an agreement with the
transmission system operator (TSO). The TSO SvK also answers for the balance
responsibility of the national system as whole.
The balance responsible electricity suppliers place orders at the Nord Pool Spot day-ahead
market (termed Elspot) for the amount of electricity that their customers are expected to use.
If the forecasts would change, supplementary trade is possible at the intra-day market Nord
Pool Elbas. If there still are, despite the efforts of the balance responsible actors, imbalances
between purchased and use of electricity, this results in a necessity of balance power
provided by SvK. The greater the imbalances are, the greater costs for the balance
responsible party. (Fritz, 2012)
Hence, planning is of utmost importance for the actors with balance responsibility.
Intermittent electricity generation from PV and wind can cause difficulties for the balance
planning due to their somewhat stochastic nature. Also, measures for DR and energy
storages can cause planning problems as it is hard to predict the consumers’ response to
different signals (Fritz, 2012).
2.3 Load and generation duration curve
A duration curve shows the number of times during a period that a certain level is exceeded.
The duration curve can have numerous applications but the ones relevant to this report are
load and generation duration curves. The curve is constructed by organising the estimated or
measured load or generation values over a period of time, in descending order, see Figure 7.
(Vaessen, 2013)
13
Figure 7: Example of a typical load duration curve for electricity consumption during one year. After (Söder,
2013).
For the DSO, the load and generation curves play an important role when dimensioning the
power grid. The cable capacity in a grid is often dimensioned after the peak power, i.e. the
maximum point of the duration curve, marked in Figure 7. However, the maximum capacity
is seldom fully utilised, which is also implied by the figure, where this capacity only is used
a few hours a year (Söder, 2013). There is also a certain “built-in” flexibility in the grid which
makes it compatible with loads over 100% of the capacity. For example, a typical cable
designed for 5 MW loads can handle 6 MW. This situation is, nevertheless, undesirable as it
shortens the life length of the cables due to wear. A benefit with the built-in flexibility is that
an investment in grid reinforcement, or a so called T&D upgrade, might not always be
necessary if there are limited loads over 100% of the cable capacity which occur seldom.
(Vukalic, 2014)
However, more flattened load and generation duration curves would be more economic
beneficial, both regarding the grid investment but also for the customer connection fees.
(Söder, 2013)
There are several ways to optimise, and thereby flatten the load and generation curve.
Curtailment of wind and solar power production, energy storage and different types of DR
are examples of ways to affect and optimise the curves. (Vaessen, 2013)
Curtailment
Curtailment of wind and solar power production can be an option when too much electricity
is generated from these sources relative to the cable capacity in the grid and the current
demand. Already today, curtailment occurs in areas with high shares of fluctuating power
generation such as offshore wind power (Klinge Jacobsen and Schröder, 2012). When
renewable energy is curtailed, the maximum point in the generation duration curve is
14
lowered. As wind and solar power are energy production sources with low greenhouse gas
emissions it is preferable to, as far as possible, avoid down-regulation of these. Therefore,
curtailment of renewable energy production is not evaluated further in this report.
Energy storage
Energy storages that can store electricity from times of excess power production and low
demand to times with low power production and high demands, e.g. on a calm evening,
could facilitate a more even and flatter load and generation duration curve (Chen et al.,
2009).
Demand response
DR can be defined as intentional alterations in the energy demand at the end users as a
response to an external signal. The concept can include both changes in the total
consumption but also the timing of the load (Albadi and El-Saadany, 2008). DR that results in
changed load timing can affect the load duration curve and possibly create a more flattened
curve with a decreased peak power.
2.4 Power quality
Apart from the previously mentioned variations in electricity production from micro-
generation, which not always coincides with the demand, the intermittency of micro-
generation can also have consequences for the power quality in the local grids.
As stated in the Electricity Act (1997:857) 3 chap. 9 §: “the transmission of electrical power
should be of good quality”. Voltage variations, of both shorter (e.g. flicker) and longer
durations, as well as asymmetry, can be caused by power fluctuations from micro-generation
and hence lower the power quality. A poor power quality can result in wearing or breakage
of the connected electrical appliances. Despite this, a DSO cannot refuse anyone to connect
micro-generation (if they fulfil the requirements) to the grid. However, the owner of the
planned micro-generation facility has to receive permission from the DSO before the facility
can be connected to the grid. In this way, the concerned DSO can ensure that the power
quality remains at a high level even after the connection. This might cause a necessity of
reinforcements in the grid. (Svensk Energi, 2011)
15
3 Literature study
In this part of the report, the current status of the research within the field of opportunities
for stabilising intermittent power in the distribution grid will be scrutinised. The aim is to
scan the areas of energy storage and DR, in order to find viable and appropriate solutions
that can be implemented in the local grid until 2020. The literature study will begin with
brief descriptions of the possibilities and applications, as well as the legislations that regulate
them. Later on, these solutions will be further analysed regarding their viability and
sustainability. The chapter will end with a prospect from Germany and some concluding
remarks for the whole literature study.
3.1 Energy storage possibilities
Neither the technology nor the applications for using energy storages in the power grids are
novel innovations (Pieper and Rubel, 2012). However, the opportunities for energy storages
are rapidly emerging. This development have mainly been driven by the expectations for an
increased penetration of renewables and its consequences, such as the growing market for
electric vehicles (EVs), the increased interest in smart grids and DR, as well as the finical
risks coupled to T&D investments. The recent emergence of energy storage opportunities has
led to improvements in storage performance as well as cost reductions and an increased
recognition by the regulators regarding the role energy storage might play in the future
electricity market. (Eyer and Corey, 2010)
There are already many existing technologies for energy storage; some mature and some still
under development. The different technologies are in most reviewed studies classified
according to their storage method, namely:
Mechanical storage
Electrical storage
Electrochemical storage
Chemical storage
Thermal storage
The primary requirements of the energy storage technologies that are necessary to fulfil the
purpose and limitations of this report, e.g. within the time-frame of 2020, are:
Technologies that both store and deliver energy in the form of electricity
Technologies suitable for a local scale, meaning both power rating (0 - 10 MW) and
spatial measures
In Table 1, different energy storage methods are described regarding fulfilment of the
primary requirements.
16
Table 1: Energy storage possibilities and their ability to fulfil the main requirements. After (Larsson & Ståhl,
2012)
Type of storage Energy storage Fulfils primary requirements
Electricity to electricity Local scale
(<10 MW)
Mechanical Pumped hydroelectric Yes No
Compressed air energy
storage (CAES)
Yes Yes
Flywheels Yes Yes
Electrical Superconducting
magnetic energy storage
(SMES)
Yes Yes
Electrochemical Lead acid battery Yes Yes
Sodium sulphur battery
(NaS)
Yes Yes
Lithium ion battery Yes Yes
Flow battery Yes Yes
Fuel cells Yes Yes
Chemical Hydrogen Yes Yes
Methane (biogas) Yes Yes
Thermal Hot water No Yes
Phase-shift No Yes
Melting of salt No Yes
As indicated in Table 1, the thermal storages hot water, phase-shift and melting of salt are
alone unable to deliver electricity back into the electricity grid and will not be analysed
further in this report.
3.1.1 Mechanical storage
Mechanical storage systems can store energy either potentially, e.g. pumped hydroelectric
and compressed air, or kinetically, e.g. flywheels. These three storage systems will be
described in the following subsections.
Pumped hydroelectric
Pumped hydroelectric storage refers to a method where water is pumped up to a reservoir
during off-peak hours, see Figure 8. In this way, potential energy is stored. At peak hours,
the water is released back again to a lower level, passing a turbine and thus generating
electricity. This is a mature technology that has been used since the 19th century, but as the
facility requires two reservoirs situated at different levels in altitude, the technology is better
17
suited for larger storage demands, typically between 100 - 3000 MW. (Chen et al., 2009, Nair
and Garimella, 2010)
Figure 8: The pumped hydroelectric storage system (Kousksou et al., 2014).
Pumped hydroelectric is not suitable on a local scale due to its size and geographical
requirements and therefore not analysed further.
Compressed air (CAES)
The method for compressed air energy storage, or CAES, resembles the principles for gas
turbines. When the storage is charged, electricity is used for compressing air, which then is
stored in a reservoir. During discharge, the high-pressure air expands and drives a
generator, thus releasing the stored energy in the form of electricity, see Figure 9. (Cavallo,
2007)
Figure 9: The compressed air energy storage system (Kousksou et al., 2014).
Even though the principle seems rather simple, account must be taken to the heat which is
formed during the compression of the air. This both lowers the efficiency and limits the
18
capacity for safe storage (Larsson & Ståhl, 2012). To compensate the loss of efficiency, fuels
such as natural gas can be mixed with the compressed air in the discharge cycle (Ferreira et
al., 2013).
CAES is a proven technology and was first installed in 1978 in Huntorf, Germany. This
facility, which is owned by E.ON Kraftwerke, has an installed capacity of approximately 300
MW and utilises two salt caverns as reservoirs for the compressed air (E.ON, 2014).
For small-scale CAES, fabricated tanks situated above ground are proposed as more suitable
as storage reservoirs. Together with electric compressors that can be turned into generators
during discharge, an overall efficiency of approximately 50% can be reached (Ibrahim et al.,
2008). CAES of this type is however not yet a mature technology (Dunn et al., 2011).
Flywheels
In a flywheel, electricity is converted to and stored as kinetic energy, which can be released
as electricity when needed. The kinetic energy is stored in a rotating cylinder which is
supported by magnetic bearings and operates in vacuum to eliminate friction losses, see
Figure 10 (Nair and Garimella, 2010). The principles of the technology have been used for
thousands of years to store energy (Kousksou et al., 2014).
Figure 10: The flywheel energy storage system (Díaz-González et al., 2012).
Flywheels are suitable for medium to high powers discharges (kW to MW) during short
periods (seconds-minutes) with high energy efficiency in the range of 90–95% (Kousksou et
al., 2014). The major advantage of flywheels is their long life time, which makes them able of
providing several hundreds of thousands of full charge–discharge cycles (Chen et al., 2009).
Also, flywheel disposal do not have any significant environmental concerns. However, the
friction losses are high and the cost for installation and maintenance is large for flywheels
19
(Nair and Garimella, 2010). Long-term storage with flywheels is not foreseeable due to these
high friction losses.
The short discharge time of flywheels is beneficial for grid storage applications intended to
regulate and improve the power quality in the grid. Flywheels can also be used to e.g. bridge
the shift from one power source to another, for reactive power support, spinning reserve as
well as for voltage regulation. Demonstration projects prove that flywheels are applicable to
smoothing the output of wind turbine systems as well as for stabilisation in small-scale
island power grids. (Larsson & Ståhl, 2012)
3.1.2 Electrical storage
Electrical storage is either electrostatic including i.e. capacitors and super-capacitors or
magnetic/current including i.e. superconducting magnetic energy storage (SMES). In the
following section SMES is described.
Superconducting magnetic energy storage (SMES)
Magnets made of coils of superconducting cables with almost zero resistance, generally
niobiumtitane cables, can store electrical energy in a magnet field, see Figure 11. The capacity
of SMES is limited only by the rating of the power electronics. Hence, SMES can be suitable
for both smaller and larger scales. Also, the response time is quick and the lifetime, as well as
the efficiency, is high. Despite these advantages, refrigeration of the system is necessary as
the process operates at temperatures around -270°C. (Kousksou et al., 2014)
Figure 11: The principle of SMES systems (Chen et al., 2009).
3.1.3 Electrochemical storage
Electrochemical storage i.e. batteries, stores the electricity in the form of chemical energy and
are the oldest form of storage for electrical energy. The principle for regular batteries is one
or more electrochemical cells containing an electrolytic media and a positive and a negative
charged electrode. A flow of electrons occurs from the negative to the positive electrode due
to electrochemical reactions at the electrodes when the battery is discharged. However, this
process can be reversed when an external voltage is connected between the electrodes. Thus,
the battery can be recharged and used for storage applications. (Chen et al., 2009)
20
There are numerous different types of batteries. The ones that might be suitable for energy
storage in a local grid will be further described below.
Lead acid batteries
The principle of lead acid (Pb-acid) batteries is electrodes consisting of solid lead and lead
oxide. The electrolyte in which the electrodes are submerged in is sulphuric acid. During
discharge, both electrodes form lead sulphate. This technology, which has an efficiency of
about 80%, was invented already in 1859 and is the oldest and most commonly used
rechargeable electrochemical technology (Chen et al. 2009). However, the lead acid batteries
have a low energy density and a poor battery cycle life. The toxicity of lead is a major
environmental disadvantage. Despite this, there are examples where lead acid batteries are
used in power grids to prevent power shortages. The largest facility has a capacity of
40 MWh and is located in California (Larsson & Ståhl, 2012).
Even though the technology is old, there is currently ongoing research to enhance the
performance of the lead acid batteries. Some research focuses on bipolar batteries, which has
a higher battery cycle life and thus a higher tolerance for voltages that shift direction, i.e.
changes between discharge and charge state (Larsson & Ståhl, 2012). This feature can be
desirable for power grid applications as the power load is frequently shifting as a
consequence from demand and production.
Sodium sulphur batteries
The electrodes in sodium sulphur (NaS) batteries consist of liquid forms of sodium and
sulphur, separated by a solid ceramic electrolyte. When discharging, positive sodium ions
flow through the electrolyte to the sulphur, creating sodium polysulphides. To stabilise the
charge balance, electrons from the sodium flow in an external circuit, thus creating a voltage
(Divya and Østergaard, 2009). During charging of the battery, the process is reversed and the
sodium ions are released from the sulphur and can recombine with the liquid sodium. In
order for these reactions to occur, temperatures between 300 – 350 °C are required (Chen et
al., 2009). The cycle life, as well as the power density of NaS batteries, is high and the
efficiency varies between 75 – 90% (Beaudin et al., 2010).
The technology of NaS batteries is developed by the Japanese company NKG Insulators,
Ltd., who supplies battery modules with a rated power of 50 kW (NKG Insulators Ltd.,
2014). These modules can be aggregated into installations with capacities of 300 MW
(Larsson & Ståhl, 2012). According to NKG (2014), these installations only require one third
of the area that the same capacity of lead acid batteries would need.
Despite the high performance of NaS batteries, there are some drawbacks. As the process
operates at high temperatures, a heat source is required which uses some of the stored
energy and thus reduce the efficiency of the battery. Also, the battery is drawn with high
investment costs. (Beaudin et al., 2010, Chen et al., 2009)
21
There are several examples of installed facilities with NaS batteries, mainly in Japan and the
U.S., where they are used both to stabilise wind and solar farms and for peak-shaving
(Beaudin et al., 2010).
Lithium-ion batteries
The lithium-ion (Li-ion) battery consists of a cathode of lithium metal oxide and an anode of
graphitic carbon in layers. The electrolyte is lithium salts dissolved in organic carbonates. It
was Bell Labs in the 1960s that developed the technology and the first commercial lithium
ion battery were produced by Sony in 1990. In comparison with nickel–metal hybrid
batteries, lithium-ion batteries are lighter, hence able of providing more capacity and power
per volume (Chen et al., 2009). Today, Li-ion batteries have taken over a great part of the
market for small portable devices and can be found in laptops, mobile phones etc. The
advantages of the battery are the high energy density and the extremely high efficiency of
over 90% (Larsson & Ståhl, 2012).
The emergence of battery storage in the electricity grid benefits from the strong demand for
batteries in the transport sector. The high price of Li-ion batteries is despite this, the main
challenge for larger applications such as EVs and local grid applications. Another issue is the
highly flammable electrolyte, but the security questions are easier and cheaper to solve for
stationary solutions such as grid storage than for portable applications (Larsson & Ståhl,
2012). Still, due to the risk of fire or explosion, care needs to be taken to protect against over-
charge/discharge, over-current, short circuit and high temperatures (Wenham et al., 2012).
An interesting project, driven by SAFT and SatCon Power Systems in the US, concerns the
design and construction of two 100 kW Li-ion battery energy storage systems to provide
power quality for grid-connected micro-turbines (Chen et al., 2009). In the coming years for
stationary applications, Li-ion batteries in the size of 1 MW or more can be expected (Larsson
& Ståhl, 2012).
Flow batteries
In contrast to conventional batteries, flow batteries store energy in the electrolyte solutions.
The electrolyte flows through a power cell where the chemical energy is converted to
electricity. A tank with electrolyte is externally positioned and the electrolyte is usually
pumped through the cells of the reactor. The reaction is reversible, allowing the battery to be
charged, discharged and recharged. There are three different electrolytes that form the basis
of the existing designs of flow batteries currently in demonstration or in large-scale project
development; vanadium redox (VRB), zinc bromine (ZnBr) and polysulphide bromide (PSB)
batteries. (Chen et al., 2009)
The advantages with flow batteries are high capacity, long lifetime, fast response-time and
high tolerance for over-charge/discharge. The VRB flow battery is beneficial from an
environmental point of view as it have zero emissions, no charging-leakage and does not
give rise to any hazard waste materials (Larsson & Ståhl, 2012). However, the energy density
of flow batteries is rather low and therefore the majority of the development work has
22
focused on stationary applications (Chen et al., 2009). Some larger-scale projects, up to 4
MW, with flow batteries as back-up and for regulation of RES already exist around the
world. In general, the development seems to have stagnated during the last years even
though the experiences from existing projects have been successful (Larsson & Ståhl, 2012).
Fuel cells and Power to Gas
A fuel cell is charged with a fuel (hydrogen, biogas, natural gas, methanol or petrol), unlike
batteries that are charged with electricity. In addition to the fuel, an oxidant, e.g. air, chlorine
or chlorine dioxide, is required in order to generate electricity.
The technology was first discovered in 1838 and have since that been regarded as highly
potential. Even so, it has still not become competitive enough. Fuel cells are at present time a
very expensive storage technology and have a relatively low round-trip efficiency. An
advantage with fuel cells is the wide storage power range of 0 - 50 MW. (Chen et al., 2009)
To be able to store electricity from the grid as well as deliver electricity to the grid, the fuel
cell has to be reversible or combined with other technologies. For example, fuel cells in
combination with electrolysis, which converts electricity to hydrogen, can be considered as
an electrical grid storage system which both stores and delivers electricity (Ibrahim et al.,
2008).
Hydrogen based energy storage
A hydrogen fuel cell uses hydrogen and oxygen to produce electricity and water. A
reversible hydrogen fuel cell uses electricity and water to produce hydrogen and oxygen.
There are two mature and developed technologies for hydrogen storage; hydrogen
pressurisation and hydrogen adsorption in metal hybrids (Kousksou et al., 2014). Hydrogen
is efficient, clean and light but is not found naturally and therefore must be produced from
primary energy sources such as electricity. Hydrogen can be stored but due to its explosive
nature, it is difficult to handle and transport. Therefore, hydrogen storage is more suitable in
isolated areas than in everyday applications (Larsson & Ståhl, 2012).
At present, hydrogen-based energy storage systems are receiving increasing attention,
particularly regarding their integration with RES (Chen et al., 2009). Hydrogen based energy
storage is regarded as one of the most promising technologies in load shifting, proved by
several demo projects with stand-alone systems including wind and PV generation
combined with hydrogen storage.
An example is the Power to Gas demonstration plant owned by E.ON, Windgas
Falkenhagen in Germany, where surplus electricity from the nearby wind power plant is
converted to hydrogen and injected into the high-pressure natural gas grid. From the
commissioning in 2013, the Falkenhagen storage plant produces up to 360 Nm3/h of
hydrogen from about 2 MW wind power, with a total plant efficiency of 58%. The location in
Falkenhagen is strategically as there is both a high penetration of wind power as well as a
high-pressure transmission natural gas pipeline in the area. The project aims to demonstrate
23
effective storage of renewable energy in the form of WindGas within the gas grid. With this
process, it is possible to use renewable electricity when and where it is generated.
(Burmeister, 2014)
The main challenge for hydrogen based storage systems which deliver power at a later
moment, is the high cost of the fuel cells (Kousksou et al., 2014).
Methane based energy storage
A possible solution to make use of excess electricity is to increase the potential of biogas
(Mohseni et al., 2012). The solution is a way to avoid curtailment of renewable electricity
production. Biogas could either be stored and used in fuel cells for electricity production, or
used as renewable fuel in the transport sector, where the demand for green fuels is ever
increasing. Moreover, utilisation of biogas reduces the net emissions of carbon dioxide.
The process is executed by producing hydrogen by water electrolysis and then allowing the
hydrogen react with carbon dioxide, thus forming methane. The benefits arise from making
use of both surplus electricity and upgrading biogas by conversion of carbon dioxide,
normally seen as waste. The potential of making biogas of electricity has been studied by
Byman and Jernelius (2012). They found that the potential of biogas production in Sweden
could be doubled, from 70 TWh to 140 TWh, by utilising excess electricity and without any
addition of new raw material to the biogas digestion process.
This is a well-known technology and there are several climate advantages, but still, the
technology is not economic viable today (Svensk Vindenergi, 2013). It might be an interesting
future possibility, especially for the southern parts of Sweden where the biogas and wind
power potential is large and the power regulation resources are limited. To use this method
as a storage system in the distribution grid, it is necessary to convert the produced biogas
back into electricity again, which is possible with fuel cells or gas turbines.
3.1.4 Chemical storage
Chemical storage concerns hydrogen and methane which, in order to fulfil the primary
requirements of the report (i.e. both store and deliver electricity) have to be combined with
other technologies such as fuel cells, see subsection Fuel cells and Power to Gas under section
3.1.3 Electrochemical storage.
3.1.5 Ownership and regulations regarding energy storage
Integration of energy storage raises the question regarding both possible investors and
operators of the facilities. According to Pieper and Rubel (2012), it is most likely that an actor
from the energy sector will act as operator due to their appropriate experiences. It is also
possible for households to own and operate facilities for storage, which is commonly
discussed as the installations of residential PV increases. From a grid perspective, it is
favorable to locate the storage as close to the generation as possible if the storage is to be
used for balancing over-production (Borg, 2012). This is nevertheless regarded as the most
expensive solution in a national economic perspective as the cost for e.g. a battery is far too
24
high in comparison to using the produced energy immediately and buying the remaining
electricity demand. This suggests that the most possible operators could be municipalities
and independent power producers as well as grid operators. A potential business-case for
increasing the profitability is to use the storage for energy trading, or so called
price arbitrage. However, due to the legislations regarding ownership unbundling, which
stipulates that power production should be separated from power transmission and
distribution, DSOs have limited possibilities to operate energy storages. (Pieper and Rubel,
2012)
As the term “energy storage” is not mentioned in Swedish laws, this causes legal
uncertainties. Stated in the law are however delineations for a DSO. As mentioned above, a
DSO is not allowed to produce or trade with electricity, according to the 3rd chap. 1a § SEA
(1997:857). Exceptions to this paragraph are, even so, possible if the production is strictly
intended to cover grid losses or if it occurs temporarily in order to compensate for lack of
electricity during blackouts. This law makes it problematical for a DSO to own and operate
energy storage if the intention is to balance renewable energy and not only to improve the
power quality or to cover grid losses.
It is however possible for a third party or an energy supplier to own the energy storage and
allowing the DSO to benefit from it. An example is the energy storage owned by the energy
company Falbygdens Energi AB, or short FEAB. The storage, which is the first energy
storage in Sweden, consists of 20 Li-ion batteries with a capacity of 75 kW (ABB, 2014). The
DSO Falbygdens Energi Nät AB, is an affiliated company of FEAB, which uses the storage
for compensation of reactive power and for peak-shaving. The costs for these grid services
are regulated between the companies (Borg, 2014).
3.1.6 Market trend for energy storage
Historically and even today, it has generally been more cost-effective to invest in expanding
the grid rather than in energy storage to meet peak loads. Consequently, the energy storage
experiences are relatively poor and the attitudes of the industry are cautious. The few
present energy storage facilities, which are mainly composed of older technologies such as
pumped hydro and CAES, generally have the purpose of decreasing the vulnerability of
energy supply. Many of these storage plants were the results of the oil embargo and the
expansion of nuclear power. (Larsson & Ståhl, 2012)
The global increase in utilisation of renewable resources for electricity generation, as well as
the development of smart grids, has led to a growing trend for the application of energy
storage in power grids (Koohi-Kamali et al., 2013). Hence, the market for energy storage is
emerging and, according to Larsson & Ståhl (2012), it is estimated to amount to
approximately 10 - 25 billion USD by year 2020, see Figure 12.
25
Figure 12: The expected market trend for energy storage. The different graphs represent the expectations from
different research institutes and consulting companies; Pike Research, SBI, BCC, Visiongain and Boston
Consulting Group (Larsson & Ståhl, 2012).
Electric vehicles
A trend which highly influences the future for energy storage is the ongoing shift from
vehicles powered by fossil fuels towards transports that emit less greenhouse gases. One
candidate among others is electrification of vehicles. Latest announcements and launches of
battery EVs and plug-in hybrid vehicles suggest that a larger number of EVs could be
deployed in the coming years. The EVs are expected to increase in number in large cities due
to the limited driving range and few charging possibilities elsewhere. Consequently, the
charging posts will initially be connected to grids in cities. A study made by
Blomsterlind (2009) demonstrates that a 10% integration of EVs in Malmö by year 2020 will
not affect the power quality in the grid and that new investments in the grid are not
required.
The batteries used in EVs today are Li-ion batteries of varying sizes. An average EV needs to
be charged about 3.5 h each day at 2.3 kW, resulting in a charge of 8.2 kWh if charged from a
standard one phase wall socket, a so called slow charge (Blomsterlind, 2009). Installation of a
fast charging post requires a new grid connection and permission. Different charging speed
classes for EVs are presented in Table 2.
26
Table 2: Charging classifications for a Li-ion battery of 8 kWh (Martinsson, 2009)
Charging class Outlet type Power
(kW)
Charging time
Slow charge 10 A, 230 V, 1 phase
16 A, 230 V, 1 phase
2.3
3.7
3 h 30 min
2 h 15 min
Semi-slow charge 16 A, 400 V, 3 phase
32 A, 400 V, 3 phase
11.1
22.2
45 min
22 min
Quick charge 63 A, 400 V, 3 phase 43.6 12 min
EVs can be seen as energy storage if they transfer power both grid-to-vehicle and vehicle-to-
grid (V2G). V2G contributes to a higher integration of variable renewables than grid-to-
vehicle does, since V2G additionally increases the capacity factors of the power plants.
However, it is currently more profitable to use the electricity for transport than in the power
sector, as it competes with high taxed and expensive conventional transport fuels (Loisel et
al., 2014). An attractive option for end users is vehicle-to-building concepts, especially if
combined with decentralised intermittent renewable generation in the same building.
3.2 Demand response
DR is defined as changes in the electricity usage patterns at the end-user. Albadi and El-
Saadany (2008) has identified three different main end-user responses. The first is that
customers reduce the consumption of electricity at peak periods with high prices, by e.g.
turning down thermostats. During other periods, their electricity usage remains unchanged.
Also the second method includes reduced consumption during peak periods, but this
reduction is later compensated e.g. a delayed washing machine start. Thus, the loads are
moved in time. The third method is onsite electricity generation, e.g. micro-generation,
where the electricity consumption pattern may be unaltered from the end-users’ perspective.
This may however, include significant changes in the usage patterns from utility (e.g. the
DSOs’) perspective.
The programs in order to accomplish these responses can be classified into incentive based
programs and price based programs, see Figure 13.
27
Figure 13: DR classifications and examples of different methods. After (Albadi and El-Saadany, 2008, Aalami
et al., 2010, Pyrko, 2005).
The difference between the two main classifications, shown in Figure 13, is that the price-
based programs are based upon tariffs where the prices for using electricity vary according
to the supply cost (Aalami et al., 2010). The incentive-based programs, on the other hand,
offer the participants some sort of compensation for the DR, such as an electricity bill
discount. If the participant in an incentive based program does not follow the program, the
compensation is defaulted and the participant might be punished (Albadi and El-Saadany,
2008). In this way, the incentive-based DR programs employ more “carrot or stick” methods.
3.2.1 Tariffs
The tariffs, or pricing models, are price-based DR methods used by network operators to get
paid for grid services as well as to control the consumption of energy. This can be performed
by varying low and high prices during different times of the day, week or year. If the price
signals are strong enough, the power usage will be moved by the customers. In this way, an
indirect DR is reached. Important is that the fee for distribution has to be objective and non-
discriminatory, according to 4th chap. 1 § SEA (1997:857).
Time-of-use pricing
The time-of-use pricing offers low and high prices at different hours of the day, week or
year. The network operator can use this type of pricing to restrict the power usage in the
system in order to avoid bottlenecks and overloading of the grid. A network operator that
currently offers time-of-use pricing is Vattenfall. Their pricing model have a higher fee for
distribution during peak load hours (winter Nov-Mar, weekday Mon-Fri and daytime 06-22)
and a lower price at all other hours (Vattenfall, 2014).
28
Load pricing
Load pricing is a way to adapt the pricing to reflect the actual costs. Load pricing gives
incentives for the customer not to use a lot of electricity-driven devices at the same time. If
the customer is active, the demand profile will be evened out. For the local DSO, this means a
lowered power subscription to the overlaying network owner, hence resulting in a lower
cost. A way to design load pricing is that the customer pays an average value for the three
highest measured power peaks during each month. A disadvantage with load pricing is that
a customer with a low and even power usage most of the month and a couple of occasional
peak loads might pay more than a customer that have a high but even power usage. (Pyrko,
2005)
An analysis made by Vattenfall in 2004 studied load pricing based on experiences from
Sollentuna Energi, which has implemented load pricing. In the analysis, three different
customer groups with different fuse subscriptions, namely 16 A, 20 A and 25 A respectively,
were studied. The result was that there were no significant changes in the consumption
pattern and that manual regulation of the load had low priority for the customers. However,
according to the analysis, the potential would be higher with automatic regulation of the
customer’s load. The study also showed that it would be possible for the customer to save
approximately 500 SEK annually by lowering the monthly peak demand. (Pyrko, 2005)
Dynamic pricing
Dynamic pricing includes flexible tariffs that reflect the current or predicted load situation in
the electricity grid.
Critical peak pricing
With critical peak pricing (CPP), the variable fee for distribution is predefined with a higher
price at critical hours to stimulate decreased consumption. The consumer is informed in
advance that the price will be raised during a certain period of time and can choose to react
on the signal. CPP is beneficial as it is easy for the customers to understand. Furthermore, the
customer do not need to be aware of the price at the non-critical hours. This method does not
give any price indications about the load situation during occasions that are not defined as
critical. In Sweden, CPP has been tested in the Market Design-program, which was
initialised year 2000 by Svensk Energi, Ei and Energy Norway. The result was that 20% of the
customers (household customers) accepted the price model and in average, their power
usage was halved at critical hours (Damsgaard and Fritz, 2006).
Real-time pricing
Real-time pricing reflects the actual system and market conditions. The price is hourly
varying and exposed to the customers, who needs to be active and take decisions to move
their loads. This pricing model includes a high degree of flexibility and DR but only works
for customers that have a smart and hourly electricity meter. There is a risk of counteraction
and confusion if both the electricity supply fee and the distribution fee are real-time based.
(Pyrko, 2005)
29
3.2.2 Capacity markets
The deregulated Nordic electricity markets of today are so called energy-only markets,
meaning that the electricity producer only receives payment for the amount of delivered
energy (NEPP, 2011). Hence, all investments in production or flexible demand are based
upon the expected electricity spot prices. In order to ensure the capacity, there are currently
administrative confirmed backup reserves for power and disturbance when the market fails.
These facilities receive compensation whether they are used or not. The aim is however that
this solution will be phased out for a more market-based solution where the available
amount of capacity reserves is optimised. The current legislation regarding backup reserves
will be eliminated until 2020, and the issue is then supposed to be solved by the market
participants. It is important that these reserve markets are separated from the spot market as
the prices at the spot market otherwise would be evened out and hence lowering the
incentives for new investments, both in production and DR. (Fritz, 2012)
Capacity markets are different to the energy-only markets as it in principle means that all
installed capacity has a value, regardless if it is used or not. When the capacity is unused, the
owner is compensated for the capital cost which otherwise would have been covered by the
variable revenue. The compensation, which is based on demand and supply, is settled at an
auction. However, there are certain levels of how much installed capacity that can be
compensated. Otherwise, the electricity consumer might be forced to pay for unnecessary
capacity. (Fritz, 2012)
For a DSO, a capacity market would mean that T&D upgrade investments could be deferred
or avoided completely. This can be achieved by trading flexibility as a commodity on the
capacity market. In order to do so, the DSO must forecast the demand to see when and
where the flexible demand is needed to not overload the grid infrastructure. This can be seen
in Figure 14, where a typical residential load close to the capacity limit of the grid is
presented and where a power cut, i.e. a load reduction due to flexible demand is performed.
30
Figure 14: A load curve where a planned “power cut” is reached through a flexible demand of ∆P (Dybdal
Cajar and Hansen, 2014).
After the DSO has mapped its flexibility demand, a request for flexibility can be submitted to
the market place. An aggregator with a flexibility portfolio, containing contracts with
electricity consumers who are flexible in their demand (e.g. households, industries, EV pools
and community services), can then offer the DSO a bid for a certain flexibility capacity.
Exactly how this market should be implemented and operated is however still uncertain.
The iPower project in Denmark, which runs between 2011 and 2016, is a project aimed to
reduce the business uncertainty regarding the potentials of the flexible market system.
Currently, Dong Energy, who is a partner in the iPower project, tests the control and
operation of the market. In this pilot study, Dong Energy, which acts as both DSO and
aggregator, has flexibility contracts with medium-sized industries and community services
such as water pumping stations. The market based trading platform called FLECH, short for
FLExibilty Clearing House, which currently is under development, is intended to be used as
a market place to facilitate trade with demand flexibility between the aggregator and the
DSO, see Figure 15. (Birke et al., 2013)
31
Figure 15: The concept of FLECH. The grey arrows represent actions taking place at FLECH (Dybdal Cajar and
Hansen, 2014).
Similar to Nord Pool, the flexibility trading at FLECH is divided into two steps. In the first
step, the Capacity Reservation market, a long-term reservation is made to ensure that there
is enough flexibility to cover the DSO’s demand request. If the flexibility capacity proves to
be insufficient, the DSO might be forced to reinforce the grid. The second step constitutes of
a short-term Reserve Activation market where the activation part is scheduled and
contracted. After the operation, where the contracted flexibility should have been dispatched
by the aggregator, the actual delivered flexibility is metered and the aggregator receives
payment from the DSO. (Dybdal Cajar and Hansen, 2014)
The regional transmission organisation PJM Interconnection in the east of the U.S
implemented a capacity market called the Reliability Pricing Model in 2007. Experiences
show that DR and production can compete equally at this market. (JPM, 2014)
3.2.3 Direct load control
Direct load control is the classical incentive based DR program. It is performed by asking
customers if they are willing to participate, meaning that they accept that the DSO at times
can shut down the customer’s equipment for a compensating payment or rate discount. The
remotely controlled equipment, e.g. air conditioner, electric heater or heat pump, can be shut
down on a short notice. Some question marks remain regarding how the DSO should finance
the compensating payment and who should invest in the control equipment needed for
automatic regulation of the demand (Damsgaard and Fritz, 2006).
3.2.4 Electric vehicles for demand response
As the penetration of EVs currently is low, there is no well-developed practice or strategy for
planning the time of charging (Loisel et al., 2014). Although, there are potentials of using EVs
as flexible demand since the charging is movable in time. Optimal would be if charging take
place during the night or during periods of high wind and sun inflows. Nevertheless, this is
today performed on an individual basis which depends on personal behaviour, preferences
and economics. Individual based charging patterns can for example be that many people
32
plug in their EVs when getting home from work, leading to a peak charging at evening time.
As the residential electricity consumption usually is high in the evenings, this load will
coincide with the individual based charging of EVs. To even out the predicted high
electricity withdrawal at peak load hours, the charging can be controlled by the DSO and
thus located to base load hours. An alternative is that an aggregator of EVs can implement
smart strategies for recharging batteries. The results of a German study by Loisel et al. (2014),
demonstrate positive effects of charging batteries in a controlled way. The effects included
enabling an increased penetration of renewables, especially PV, since they generate stronger
daily fluctuations compared to wind variations, which are of shorter duration.
3.2.5 Regulations regarding demand response
The expression demand response is not mentioned in SEA (1997:857). However, DR in the
form of grid tariffs is regulated in chapter 4 in SEA. The grid tariffs has to be objective and
non-discriminating, according to 4th chap. 1 § SEA. That the tariffs shall be non-
discriminating infers that all customers within the same customer-type should be offered the
same tariffs and that no particular customer should be favoured.
Since 2012, Ei regulates the DSOs’ profits by setting revenue cap during each four-year
period. This aims to provide fair tariffs for the customers as the DSOs operates under
monopoly within each grid area. (Swedish Energy Markets Inspectorate, 2012)
According to article 15.4 in the European Union’s Energy Efficiency Directive (2012/27/EU),
network tariffs shall provide signals for optimal energy infrastructure utilisation and power
savings in order to contribute to a higher overall efficiency. This can be interpreted as a legal
instrument to push for demand response.
3.2.6 Market trend for demand response
The trend for pricing models in Sweden, based on a study consisting of interviews with six
DSOs, demonstrates that load-based pricing most likely will be extensively conformed in the
coming years. At the same time, there is an ongoing change towards simpler pricing models
and fewer types of subscriptions. The differences in the pricing models between the DSOs
result in a need for a joint pricing model design standard. Other trends that the participating
DSOs identify to impact the design of future pricing models are increased micro-generation
and reduced energy consumption. (Lydén et al., 2011)
DR has been subject of discussion for a long time but has not yet been realised in larger scale
in Sweden. The actors on the energy market are generally positive to DR. The method is
mature but so far, the market and administrative structure have been insufficient. The
decision taken by the Swedish government of phasing out the backup reserves does create
the necessary basic prerequisites for further progress. Still, the political approach and the
way forward have to be clarified for a more rapidly development. Fully applied DR can in
the future balance the power variations in the range of 1 - 3 hours but it does not solve the
complete need of back up reserves. (NEPP, 2013)
33
In 2011, NEPP stated in a synthesis report regarding capacity mechanisms that there are two
ways to proceed if the aim is to create regulatory incentives for maintaining and investing in
less-frequently used generation and in DR. The two ways are either to stay to the
energy-only market design and add a strategic capacity reserve or to do a fundamental
change that affects all the actors, such as the PJM market design in the US. (NEPP, 2011)
3.3 Comparison of balance methods
Comparisons between the above described methods for balancing demand and intermittent
production are presented below. The aim is to conclude which methods that are the most
suitable for peak reductions in a local grid such as the one in Hyllie, which is further
investigated in the case study.
3.3.1 Energy storages
There are several important features to take into consideration when evaluating the
performance of the energy storages, such as technical, economic and environmental aspects.
Technical aspects
The following technical characteristics of different energy storage methods are presented in
Table 3:
Energy density - The ability to store energy in relation to the volume of the whole
storage system. This criterion is important when space is limited.
Round trip efficiency (RTE) - The relation between the energy input and output.
Power capacity - How much power that can be stored. This capacity is often larger
than the power that actually can be delivered as discharge often is incomplete
Duration - The time during which the energy storage can discharge at its rated
power.
Response time – The time it takes for the energy storage to release or absorb energy
Maturity - The progress phase the energy storage currently is in. This feature is here
graded into three different maturity levels: developing; meaning methods that are
currently under research, pilot; methods that are being tested and demonstrated and
commercial, corresponding to mature methods that already are employed.
34
Table 3: Technical characteristics for the proposed storage methods
Storage
technology
Energy
densitya
(Wh/L)
Efficiencyb
(%)
Power
capacityc
(MW)
Durationd
Response
timee
Maturityf
CAES 3 - 6 40 - 80 3 - 400 h - days 1 - 15 min Commercial
Flywheel 20 - 80 80 - 99 0.25 s - 15 min ms - s Pilot
SMES 0.2 – 2.5 85 - 99 0.1 - 10 ms - 5 min ms Pilot
Pb-acid 50 - 80 70 - 92 0 - 40 s - 3 h ms Commercial
NaS 150 - 250 75 - 90 0.05 - 8 s - h ms Commercial
Li-ion 200 - 500 85 - 90 0 - 0.1 min - h ms - s Pilot
Flow
battery
16 - 60 65 - 85 0.3 - 15 s - 10 h ms Developing
Fuel cells 500 – 3 000 20 - 70 0 - 50 s - days ms - min Developing
a After (Chen et al., 2009) b After (Ferreira et al., 2013) c, f After (Kousksou et al., 2014) d, e After (Chatzivasileiadi et al., 2013)
In order to create peak reductions of the electrical load in a local grid, the energy storage
must fulfil specific spatial requirements as the space often is limited. This is of utmost
importance when the storage is to be situated in a property, such as a residential building or
an office. It is also of great matter if the area is of urban character where land often is
expensive. With regard to spatial measures, CAES and SMES are unsuitable technologies in a
dense area due to their low energy densities, which implies larger spatial requirements.
The efficiency is rather high for all studied technologies except for fuel cells, which are
under development and still has a relatively poor efficiency. It seems unlikely that this
situation will change drastically until 2020.
As power capacities over 10 MW already have been excluded, all methods in Table 3 are in
suitable capacity ranges for a local grid. Even so, CAES, flywheels, SMES and flow batteries
are technologies that might be of too large capacity for a single property with micro-
generation as the maximum installed capacity for micro-generation, according to the
assumptions in the report, is approximately 70 kW, which thus corresponds to the maximum
need for energy storage capacity. However, for balancing a whole district, larger capacities of
a few MW are needed. For this application, even storages with lower capacities can be used if
they are aggregated into storage units.
Energy storages intended to smooth the output from renewable micro-generation requires a
duration time in the range of hours due to the diurnal nature of the generation. Hence,
35
storage technologies such as flywheels and SMES have too short duration times to be
suitable for balancing micro-generation from PV.
All technologies presented in Table 3 have quick response times which is preferable for
unpredictable power supply such as wind power or when PV modules are temporally
affected by overcasting and thus cause rapid variations of the power output. However,
concerning flywheels, both the duration of the discharge as well as the response time is short
which implies that this storage method might be more suited for short-time regulations, such
as voltage regulation.
Flow batteries and fuel cells are still under development and it is unsure whether they are
mature enough until year 2020.
Hence, considering to the technical aspects solely, Pb-acid-, NaS- and Li-ion batteries are the
most suitable storage technologies.
Economic aspects
A key for energy storages to provide economic incentives is the spread between the costs for
charging and the income that can be obtained during discharge. Both the capital costs and
other expenses for maintenance, operation and efficiency losses have to be covered by this
price spread (Pieper and Rubel, 2012). Following aspects concerning the economics of the
energy storages are presented in Table 4:
The cost – the investment cost per power capacity and the cost per energy capacity.
Maintenance – The required maintenance on a scale ranging from 1 - 5, where 1
implies a high maintenance claim and 5 implies no need.
Cycle life - The number of charge cycles the energy storage can provide.
36
Table 4: Economic characteristics for the proposed storage methods
Storage
technology
Power capacity
costa, c
(€/kW)
Energy
capacity costb
(€/kWh)
Maintenancec
Cycle lifed
(cycles)
CAES 290 - 1450 1 - 70 3 30 000+
Flywheel 250 3 620 3 1 000 000
SMES 220 7 230 2 100 000+
Pb-acid 220 290 3 500 - 1 200
NaS 720 - 2 170 220 - 360 3 2 000 - 5 000
Li-ion 2 890 1 800 5 1 000 –
10 000
Flow battery 430 - 1 080 100 - 720 1 – 3 2 000 - 13 000
Fuel cells 2 000 - 6 600 1 - 10 1 1 000 - 10 000
a, b After (Kousksou et al., 2014). USD converted and rounded off to EUR (currency 1 USD = 0.723 EUR
2014-04-25) c After (Chatzivasileiadi et al., 2013) d After (Ferreira et al., 2013)
The power capacity cost and the energy capacity cost differs widely between some
technologies, especially considering flywheels and SMES where the power cost is low
whereas the energy cost is high. The reason becomes clear when regarding the cycle life of
the technologies in Table 4. Also, SMES systems require cooling which further increases the
kWh cost.
The cycle life is a technical factor that influences the economic performance. Many cycle
lives spread the capital cost for the storage which results in a lower cost per kW. It is
important to consider the usage frequency of the planned storage when choosing storage.
The cycle life can be lowered for some technologies by improper or disrupted charging.
Flywheels show a remarkably high number of cycles which is suitable for power quality
regulations.
Regarding the power capacity cost, fuel cells and li-ion batteries are presently the most
expensive options. However, as the technologies continue to develop, e.g. that the efficiency
for fuel cell improves, these costs will probably sink and they might become economic
feasible in the future.
The required amount of maintenance is also a factor that varies between the technologies
and is of great matter as it highly affects the variable costs during the life time of the storage.
In this regard, Li-ion batteries require the least maintenance whereas SMES, flow batteries
and fuel cells requires the most.
37
Among all energy storages studied, lead-acid batteries have the most favourable economic
performance with low costs, both measured per cycle and per useful energy output.
Furthermore, the required maintenance is acceptable.
As most methods for storing electricity still are, and will most likely continue to be rather
expensive in the viable time-frame, it is important to take into account the aggregated
benefits and synergies of energy storages. Even though this report is focused on peak
shaving/valley filling to provide a more constant load even with installed intermittent micro-
generation, there are several synergies from energy storages that can provide a more positive
cost-estimate. As mentioned previously, peak shaving can create possibilities for T&D
deferral which can be seen as a profit due to the interest rate. Furthermore, distributed
storage can, according to Ferreira et al. (2013), provide other benefits in a local network, e.g.:
Demand side management – end-users can minimise their electricity costs by
installing a smaller storage to their micro-generation facility and then buy and sell
electricity at off-peak respectively peak hours
Loss reductions – the efficiency of the network increases as the usage is decreased
during peak load hours and increased during off-peak hours
Area control – preventing unintended transfer of energy from one area to another
Distributed storage might also, to a limited extent, provide contingency and black start
services. For the DSO, the synergies that are the most economic beneficial are the possible
T&D deferral, loss reductions as well as area control. With a higher level of area control, fees
for transferring energy to the overlaying grid can be reduced.
Despite the aggregated benefits that arise from energy storages distributed in the grid, the
investment costs are still high and the DSO might not be able to cover these costs with the
grid tariffs. A possible solution is that either a third party, such as an aggregator, or an end-
user connected to the grid, such as a property owner, owns and operates the energy storage.
As these actors have the legal possibility to trade with electricity, see section 3.1.5 Ownership
and regulations regarding energy storage, these revenues can provide economic incentives. As
the benefits with energy storages are still available for the DSO, the incentives for the storage
owner can increase if the DSO pays a compensation for the acquired benefits. Another
possible solution is if another company within the DSOs’ corporate group, e.g. an electricity
supplier such as E.ON Försäljning Sverige AB, owns the storage and uses it for price
arbitrage, whereas the DSO, e.g. E.ON Elnät Sverige AB rents services from the storage.
However, price arbitrage requires a differentiated, higher electricity price to become viable.
To conclude, the costs for energy storages are very high and currently, the least expensive
alternative is lead-acid batteries. However, as many technologies are under research and
development, the situation might have changed until 2020.
38
Environmental aspects
One major aspect when evaluating the sustainability of different energy storages is their
environmental performance. Otherwise, even though the electricity generation might be
sustainable and environmental friendly, this may be compensated by a high environmental
impact from the energy storage. Also, the environmental friendliness affects the public
acceptance towards energy storage installations. In Sweden and other Nordic countries, the
majority of the population prefers to pay more for sustainable energy production rather than
employing generation with high emissions (Ibrahim et al., 2008). Thus, the environmental
aspects can, to a certain limit, be regarded as more important than the economic aspects.
Even though the social aspects are not investigated further in this report, some safety aspects
must be considered in order to evaluate whether the energy storages can be situated in a
local grid area.
In Table 5, the following aspects are presented for the different storage methods:
Recyclability – The recyclability of the materials used in the storage where high
indicates that most parts of the storage are recyclable and leave small amount of
remains whereas low means poor recyclability.
Metal availability – The abundance of scarce metals measured in both the amount of
available reserves (year 2009) and years left of reserves with constant usage in the
same rate as 2009. Hence, the number of years left of one particular reserve might
change drastically due to alterations in usage.
Emissions – Emissions of greenhouse gases to the atmosphere during usage of the
storage.
Hazardous – Potential health and environmental hazards of the storage, e.g.
flammability, toxicity and magnet fields.
Overall environmental influence – The environmental impact of the storage with all
mentioned environmental aspects taken into consideration.
39
Table 5: Environmental and safety aspects for the proposed storage technologies
Storage
technology
Recyclabilitya
Metal availabilityb
(kton/years)
Emissionsc Hazardousd
Overall
environmental
influencea,d
CAES - (Not
applicable)
- (Not applicable) Yes Flammable/
Explosive
High
Flywheel High Titanium
(5 280/31.8)
No No Low
SMES - (Not
available)
Lead
(79 000/20.8)
Bismuth
(320/55.2)
Barium
(190 000/24.5)
Copper
(550 000/35.0)
Strontium
(6 800/13.3)
Yttrium
(540/60.7)
No Strong
magnet
fields
Medium
Pb-acid
battery
High Lead
(79 000/20.8)
No Flammable/
Explosive
Toxic
(Lead)
Medium
NaS
battery
High Sodium
(3 300 000/6 000)
No Flammable/
Explosive
Low
Li-ion
battery
High Lithium
(4 100/149.6)
No Flammable/
Explosive
Low
Flow
battery
Medium Vanadium
(13 000/216.7)
Zinc
(180 000/15.9)
No Toxic
(Bromine)
Medium
Fuel cells
(Hydrogen)
Medium
Nickel
(70 000/43.5)
Titanium
(5 280/31.8)
Zirconium
(51 000/37.5)
No Flammable/
Explosive
Low
a After (Chatzivasileiadi et al., 2013) b After (Beaudin et al., 2010) c After (Ferreira et al., 2013) d After (Chen et al., 2009)
40
Of the studied storage technologies, CAES has the highest environmental impact, see
Table 5. The reason is mainly the emissions of greenhouse gases during discharge, where
natural gas is combusted. Hence, by using fossil fuels in storage methods, the environmental
benefits from renewable energy production are counterbalanced. Also, utilisation of
compressed gases is drawn with explosion hazards and the storage of these gases can, in
some cases, require natural formations as caverns.
Flywheels, NaS batteries, Li-ion batteries and hydrogen driven fuel cells account for the
lowest environmental impacts among the studied storages. Even so, there are drawbacks
also with these technologies. Several of these employ compounds which are bound to be
scarce in the coming decades with the same consumption rates as today. If these storage
methods become commercialised in larger scales, these rates will most likely increase. Thus,
the number of years we can exploit these reserves will be even further limited. On the other
hand, the recyclability of the storage compounds is medium to high, implying that all new
devices must not originate from primary reserves but from recycled materials. The second-
hand market for energy storages is also likely to grow, especially due to the increased
employment of EVs. This can also cause a reduced cost for installing energy storages such as
Li-ion batteries.
The storage methods characterised by a medium overall environmental impact in Table 5 are
SMES, Pb-acid and flow batteries. In a purely environmental perspective, SMES can be
regarded to have a low environmental impact as it is free from emissions and risks for toxic
leakage. However, SMES induces strong magnetic fields which can pose health hazards for
people living nearby, making it unsuitable for usage in an urban area. Furthermore, SMES
contains numerous compounds with limited availability, such as lead, barium and
strontium.
Both Pb-acid and flow batteries contain toxic ions of e.g. lead and bromine. These ions can
leak to the environment during handling and improper recycling, causing health hazards for
both humans and other organisms. Lead, which is a heavy metal, accumulates in organic
tissue and causes cumulative effects higher up in the ecosystem. These storage technologies
do also contain metals of poor availability.
Conclusions that can be drawn when evaluating the environmental aspects solely, are that
fuel cells, flywheels, Li-ion- and NaS-batteries are the most environmental sustainable
solutions.
3.3.2 Demand response methods
The criterions and approaches when evaluating DR methods differ in comparison to the ones
relevant for energy storage as the environmental aspect is less central and the legal aspect, as
well as the objective of the DR method, is more significant.
41
Tariffs
When comparing different tariffs it is of importance to evaluate if the tariffs will fulfil the
aim of the implementation as well as concerning the legal regulations. In this report, the aim
for the suggested tariffs is peak reductions in order to even out power variations, which is
compared in Table 6. The peak reduction is to be interpreted as demand moved from peak
hours to off-peak hours. An article made by Stromback et al. (2011) is based on results from
100 different DR pilot projects which include 290 000 residential participants worldwide. The
results for Europe are presented in Table 6. Hence, these values are based on customers with
different heating sources. Load pricing was not included in the study and hence, data has
been gathered from a study by Pyrko (2005) where the customers of one Swedish energy
company were participating.
Table 6: Potential peak reduction with different pricing models
Pricing model Peak reduction
(Without
automation)
(%)
Peak reduction
(With
automation)
(%)
Customer
financial
savings
potential
(%)
Critical peak
pricinga
24 31 6
Time-of-Usea 9 16 5
Real-Time-
Pricinga
13 9 13
Load pricingb 5 - (Not available) 10.5 - 18
a (Stromback et al., 2011) b (Pyrko, 2005)
CPP seems to reduce the demand peaks the most among the studied tariffs in Table 6. For
CPP with automation the peak reduction potential is larger than without automation due to
that customers do not always respond to the price signal if it is not automated. To 2020 all
white goods and customer electronics on the market would probably not include a chip for
automated control. Although, Hurley et al. (2013) believes that cost-effective technology for
DR from residential customers is a widespread reality until 2020.
In France, CCP has been in use since 1996 and is available for customers who subscribe for
more than 6 kW. Tempo is a CPP in France that the DSO has the right to impose, on short
notice, when they see that a critical peak is approaching. 1.2% of the grid customers in France
use this tariff, currently mainly families with electric heating that is automated controlled
after the CPP. The peak reduction due to CPP for the entire country during critical days is at
the most 300 MW. The customers are informed through an interface where different colors
correspond to different pricing levels. The highest pricing level is nine times larger than the
lowest level. Tempo requires that the customers, the day before, know what color the next
day will receive. The DSO makes this information available on the Internet at 17:30 the day
before and also sends this information by an email or SMS to the customers who have
42
registered their interest. Moreover, all the Tempo customers have a box in their home which
at 20:00 lights up red, white or blue according to the next day's price range. (Ek and
Hallgren, 2012)
To be considered furthermore, is if the customers are willing to be controlled by the DSO. If
the customer saving potential is large enough, the acceptance towards pricing tariffs with
automation possibly increases. As the customer saving potential is rather low for CPP it may
be easier to implement this pricing model without automation.
The study made by Pyrko (2005) regarding load pricing, states that this tariff only reduces
demand peaks with 5%. However, this tariff is likely to be implemented in 2016 - 2017 by
E.ON as it is regarded as objective and non-discriminatory and therefore the most promising
tariff to accomplish peak-reductions within the legal demands. This tariff necessitates hourly
metering for all participants, which is not presently installed to all customers. Hourly
metering is available on request to all customers, but multi-family dwellings might have to
use templates if they have a common meter for electricity.
Time-of-use tariffs can be suitable when customers have their own batteries (Pieper and
Rubel, 2012). The battery can be charged when the price is low and discharged when the
price is high, hence creating a business-case for the customer. Time-of-use tariffs are by E.ON
regarded as somewhat discriminating as some customers run businesses that are depending
of a certain time period of the day.
In order to reach the aim of the tariffs, it is important that the customers understand the
difference between energy and capacity and the reason to the DSO wants to change the fee
for distribution before launching a capacity based tariff. Therefore, it would be preferable if
all DSOs launch capacity tariffs at the same time in order to facilitate the information
campaigns towards the customers.
Capacity markets
Capacity markets can result in joint benefits for both the network operator and the electricity
supplier. The energy balance can be solved for the electricity supplier whereas the bottleneck
problems can be solved for the DSO. Capacity markets can also enable interactions between
DSOs and aggregators, which could facilitate a breakthrough for DR on a larger scale,
especially as one contract that includes several customers is easier to administrate than one
contract with each customer.
Evaluations made by Hurley et al. (2013) regarding projects in the U.S. demonstrate that the
advance of DR has shown the strongest progress where the participating customers have
received a firm monthly payment. This is because business models based on infrequent
events with high prices have shown to be too risky and unpredictable to rely on to give
incentives for sufficient DR participation. In order to promote both different customers and
types of loads, existence of various streams of revenue have shown to be effective, e.g. to
43
integrate renewable intermittent resources it is favourable if the revenue can reward the
speed and accuracy of the DR.
This reasoning might suggest a tariff such as a CPP with a rebate system. This means that,
during hours of critical peaks, the participating customers are paid for the consumption
quantities that they manage to avoid in comparison to their predicted levels of consumption
(Stromback et al., 2011). The number of occasions, as well as the lengths of these, can in
advance be contracted between the participant and the aggregator. Hence, a CPP with rebate
can be suitable for the capacity market. However, the study by Stromback et al. (2011) states
that CPP without rebate leads to a larger peak reduction than CPP with rebate.
Consideration thus needs to be taken to whether a large number of participants with lower
individual reductions or fewer participants with higher individual reductions are desired in
order to complete the peak reduction.
The customers’ understanding for new tariffs, e.g. CPP, might be enhanced when they are
launched in combination with a capacity market as it allows capacity to be traded as a
regular product.
Even so, contracted DR on a capacity market gives rise to the question as to what will
happen if a customer does not follow the contract during hours of DR activation. Most likely,
electricity customers will not agree to a contract if a risk of punishment exists. Therefore, it is
possible that instead the aggregator will be punished by an indemnity. Thus, it is important
that the aggregator provide adequate attractive incentives, e.g. rebates, to their participants.
Direct load control
Direct load control is a method for DR that is unsuitable for residential customers with
district heating. This is because the demand that is regulated by the DSO should preferable
not affect the residents in an undesired way as the remaining energy demand might be
strongly related to the behaviour. For example, a customer in the middle of the evening
cooking will most likely not prefer if the oven suddenly were to shut down. Due to the
unsuitability to implement direct load control to all customers, indirect load control e.g.
tariffs is to be preferred.
3.4 Current situation in Germany
Currently, Germany is the world's leading country in installed PV capacity and the third
leading country in installed wind power capacity (Masson et al., 2013, Global Wind Energy
Council, 2014). Therefore, a prospect of the situation in Germany might shed some light over
the challenges that can be expected if a high penetration of intermittent generation becomes
reality in Sweden. If not otherwise stated, the following information has been gathered from
a visit to E.DIS AG in Germany, hosted by Pluciennik (2014).
3.4.1 Die Energiewende
In Germany, a unique transition from nuclear power and fossil fuels to RES begun in 2011 in
order to enable for the country to reach its national target of 35% renewable electricity by
44
2020. This transition, known as die Energiewende, has caused a rapid change, especially
regarding nuclear power. Already a month after the decision to implement the transition,
8 GW of nuclear power was shut down. Until 2022, an additional amount of 10 GW will be
closed down. (Steele and Niemi, 2013)
The Energiewende has consequently caused a swift expansion of RES, mainly from PV and
wind. This expansion has also been driven by the feed-in tariffs, which was first introduced
in 1991 and guaranteed the producers of renewable energy a reserved price for their
electricity. This subsidy answered to 80 – 90% of the price for the end-users. As a result of the
fluctuating prices, investors became reluctant to further investments in renewable power
generation. A new regulation for renewable energy and feed-in tariffs, the EEG, was
introduced in 2000. One of the main differences from the previous regulation is that each
type of generation was given a certain feed-in tariff. Furthermore, the EEG feed-in tariff also
depends on the installed power and when the facility was applied for. The tariffs are settled
over a period of 20 years. During this period, the tariffs decrease due to the estimated cost
reductions for the facilities. Because of the long running time as well as the previous
mentioned parameters, there are numerous of different tariffs. (Steele and Niemi, 2013)
3.4.2 The perspective from a German DSO
Because of strong incentives for investments in both smaller and larger renewable electricity
generation due to the feed-in tariffs in combination with the ever decreasing technology
costs, the construction rate of new facilities is extremely high. Neuhardenberg, a PV farm in
the north-east Germany with an installed capacity of 138.9 MW, is one example of this. The
facility was completed in three weeks after the building permit was granted. These fast
construction rates pose challenges for the DSO which, according to the EEG 1 chap. 1 §,
“shall immediately and as a priority connect installations generating electricity from
renewable energy sources”. Interim solutions are however possible and necessary as the
planning and construction of new connections often require several years.
E.DIS AG, which is majority-owned by E.ON, is one of the largest DSOs in Germany and
operates the main part of the gas and electricity network in the north-east region. In this area,
renewable energy from wind and PV accounts for 73% of the total electricity generation. This
corresponds to approximately 7 000 MW installed renewable power. As the regional peak
demand amounts to 2 500 MW, the generation solely from wind and PV is three times higher
than the demand some days. Consequently, the electricity grid has to be dimensioned
according to the power production and not after the demand. The high penetration of
renewables and the requirement to connect these energy sources cause high grid fees for the
customers, even though the main part of the load originates from the electricity producers.
Another consequence with the high share of intermittent generation is the difficulties in
attracting investors to base load and back-up power plants in order to balance the fluctuating
generation.
45
As the power production in this region often generously exceeds the demand, DR is not
regarded as a solution to balance the supply. Therefore, smart meters with higher measuring
resolution for the electricity consumption have not gained a high attention. However, this is
only a regional situation and smart meters will be installed throughout Germany until 2016.
Electricity meters with a low, e.g. monthly resolution, obstruct the implementation of DR
tariffs such as CPP and load pricing as these tariffs are dependent on frequent
measurements.
In order to handle the high loads and avoid overloading the grid, E.DIS operates the grid
according to a regime where grid optimisation has the highest priority. The optimisation of
the grid includes temperature monitoring of the lines and intelligent control of the reactive
power. When grid optimisation is insufficient, reinforcements and extensions of the grid are
necessary. As mentioned, these solutions requires a substantial amount of time and
investments and as the DSO acts on a regulated market, the revenue-cap is not allowed to
include investments in the grid due to future loads. The last option in this regime is
curtailment, where generation units over 100 kW are step-wise curtailed through radio
ripple control according to a network security management program based on the current
load situation.
The load reductions caused by curtailment of the highest peak loads are not proportional to
the loss of energy. A peak reduction of 20% corresponds only to a 3% loss in energy
production in this region. Higher production losses due to curtailment are not economical
and therefore alternative solutions are under investigation. An example of this is the energy
storage project in Falkenhagen, see section 3.1.3 Electrochemical storage. Further pilot projects
with battery storage are planned. However, the costs for batteries are still high, e.g. the price
for a 10 MW Li-ion battery storage is currently 20 times higher than investing in a medium-
voltage grid extension (Schäfer, 2014).
Regarding ownership of the energy storages, the regulations are very similar to Sweden and
a DSO is only allowed to own storage to cover the distribution losses. Concerning
households, the German situation is more economic beneficial as, since 2013, customers with
their own micro-generation are granted subsidies when owning batteries. (Schäfer, 2014)
3.5 Concluding remarks
When comparing the methods for energy storage and DR, it is noticeable that different
methods are suited for different applications in different scales. On a local scale, suitable
methods aiming to reduce load variations due to micro-generation and demand are batteries,
such as NaS or Li-ion, and tariffs like CPP. NaS and Li-ion batteries are suitable because of
their favourable technical and environmental aspects. Regarding their economic qualities,
they are still very expensive. Therefore, Pb-acid batteries might be an alternative with respect
to the economic features.
46
CPP is a tariff, which in previous experiments has shown ability to reduce peak loads the
most effective, both with and without installed automation.
This tariff, in combination with a rebate that rewards peak reductions, has shown to provide
a more predictable response from the participating customers. A predictable response is
beneficial for capacity markets as the market then would be more reliable and thus provide a
higher economic safety for the actors at the capacity market, i.e. DSOs and aggregators.
47
4 Case study of Hyllie
In order to estimate the future load variations in the local grid, Hyllie in Malmö has been
studied. This is to simulate an actual worst case for the electricity grid and get an
understanding of the magnitude of power variations caused by micro-generation.
4.1 Description of the area
The city of Malmö has highly set environmental and energy ambitions for the city. In 2009
the two strategies, Miljöprogram för 2009-2020 and Energistrategi Malmö were adopted, stating
that Malmö should act to become the world leader in sustainable urban development by
2020. The district Hyllie is one of Malmö’s largest developing areas. Fully developed, the
area will include approximately 9 000 residential units and nearly as many workplaces. To
achieve the high goals in the environmental and energy strategy for Malmö, it is required
that Hyllie takes important steps and leads the transition towards a sustainable city. To reach
the ambitions for the area, a climate contract containing the common goals for Hyllie was
developed and signed by E.ON, VA SYD and the city of Malmö in 2011. The goals in the
climate contract are to be reached by 2020 and the ones that are of relevance for this report
are:
The energy supply in Hyllie shall consist of 100% renewable or recycled energy by
2020. A significant proportion of the energy is to be supplied by locally produced
renewable energy, such as solar and wind energy.
The energy flows shall rest on smart infrastructure such as smart grids.
Smart solutions for EVs shall be established in the area.
Hyllie is chosen for the case study of this report because a high penetration of micro-
generation is expected in order to achieve the goal for the district of 100% locally produced
renewable energy to 2020. As E.ON Elnät is the DSO in Hyllie, it is within their interest to
learn whether micro-generation can cause power variations that affect the electricity grid and
how these variations can be balanced by energy storage and DR. The district Hyllie is to be
seen as an example which, in the future, could represent any urban area with a high
penetration of micro-generation in a grid owned by E.ON Elnät.
4.2 Method
The case study is based upon the assumption that PV and small-scale wind turbines are
installed on rooftops in Hyllie. This may be regarded as a best case in order to achieve the
goals of the climate contract but worst case for a conventionally built electricity grid.
Scenario 1 represents a conventional grid whereas scenario 2 consists of a grid with
alternative solutions (DR and energy storage). Within each scenario, both a residential case
and a total area case is simulated. A 20% penetration of EVs is considered, as smart solutions
for EVs are planned to be established in the area according to the climate contract. In
scenario 1, the EVs are considered as an uncontrollable load from the DSOs’ perspective, in
contrast to scenario 2, where the charging of the EVs is controlled.
48
As Hyllie is a developing area, there are still many uncertainties regarding the planning and
design. Therefore, a model has been constructed upon assumptions for the number and
design of the buildings, as well as the expected penetration of EVs. The model is described in
general in the following subsections. More detailed assumptions can be found in Table 8
Appendix A.
4.2.1 Model for simulations
The electricity grid in Hyllie consists in total of three loops connected to the primary medium
to low voltage (MV/LV) substation. The present large electricity consuming facilities in
Hyllie are connected separately, i.e. one of the three loops contains the shopping mall, one
contains the exhibition centre as well as the arena and one contains residential customers and
offices. Until 2020, more residential houses, as well as other facilities, are expected and even
more consumers are expected by 2030.
New grid infrastructure is to be planned and constructed in the coming years. Therefore, it is
of interest to investigate both how large the power variations can be in a loop with only
residential customers as well as for the total area.
All simulations and calculations were performed in Microsoft Office Excel 2007.
Assumptions for electricity demand
In Hyllie year 2020, the electricity demand is assumed to originate from 4 500 apartments,
4 500 workspaces, three schools, one public bath, one shopping mall (namely Emporia), one
hockey arena, one exhibition hall and one railway station. All facilities in the area are
assumed to have district heating and thus, the heating does not affect the electricity load for
these facilities.
Hourly electricity demand data from five newly built residential buildings, consisting of 95
apartments, as well as a school, all in Västra Hamnen in Malmö, were used when simulating
the load. As the computed medians of the residential electricity demand is close to the mean
values, the residential demand is normal distributed and hence, the mean value is reliable,
see Figure 38 in Appendix B.
Electricity demand data for the public bath was collected from an existing bath in Malmö.
Other demand data of existing facilities such as Emporia, the arena and offices, were based
on actual metering in Hyllie. The decrease in consumption of electricity due to expected
future energy efficiency measures is assumed to be compensated by an increase in number of
electrical appliances. Hence, the power consumption by 2020 is assumed to equal the
consumption by year 2013/2014.
According to Sköldberg et al. (2010), a 20% penetration of EVs is expected until 2020 and
consequently, considering the plans for the parking lots in Hyllie, there will be about 2 170
parking lots with EV charging possibilities. Hourly data for the charging of EVs was gained
from charging profiles, see Figure 39 and Figure 40 in Appendix C.
49
Assumptions for micro-generation
As the land in the area is owned by the municipality, the simulated micro-generation units
are located on the buildings’ rooftops. Each micro-generation unit has an installed capacity
of maximum 69 kW, see Appendix A. Hourly PV production data for July 2013 and January
2014 were collected from E.ONs smart home pilot project Hållbarheten in Malmö. The PV
modules are there positioned facing south at rails with a 25° declination. No further
shadowing due to e.g. wind turbines is considered.
In addition to the PV modules, small-scale wind turbines with rated power of 2 kW were
positioned on all rooftops to obtain a worst case future scenario. The wind turbines were
imagined to be positioned in a line with four rotor diameters in between to avoid wake
effect, i.e. lowering the power output from the turbines downstream, and shadowing of the
PV modules. Four small-scale wind turbines per residential building and ten wind turbines
per commercial building were assumed in the model. Hourly wind velocities at an altitude of
10 m for July 2013 and January 2014, at the airport Sturup near Malmö, were collected from
SMHI. Together with the power curve for the wind turbine Windon 2 kW, the hourly power
output was calculated.
Assumptions for balance solutions
The balance solutions applied in scenario 2 were ranked by firstly applying DR in the form of
CPP for all residential customers with an assumed 24% peak reduction during peak hours
and secondary, if required, peak shifting with battery storage was applied. DR was not
applied to the commercial buildings as their loads are mainly during the day and harder to
shift without affecting the business.
The battery was assumed to be charged only during excess production from the micro-
generation.
4.3 Results and analysis of simulations
This part of the report is divided into two main sections. The first is the scenario with a
conventional grid, i.e. without any of the solutions from the literature study implemented
into the grid. The second part is the scenario that represents a grid with the alternative
solutions that, according to the literature study, were the most suitable for a local grid, i.e.
batteries and CPP.
4.3.1 Scenario 1 – A conventional grid
This scenario simulates a conventional grid year 2020 with a high penetration of micro-
generation and 20% penetration of uncontrollable charged EVs.
Residential
The total load in the grid can be visualised by regarding micro-generation as a “negative”
demand. Hence, the total load duration curve can be plotted. In Figure 16, the load duration
curves with (net load) and without micro-generation (demand), are plotted for 4500
apartments with non-controllable EV parking lots in July.
50
Figure 16: The load duration curves for 4500 apartments during July.
The demand curve in Figure 16 can be regarded as a “business-as-usual” scenario, whereas
the net load curve might represent a future scenario where all residential buildings are
equipped with micro-generation. A conclusion that can be drawn is that the grid utilisation
factor changes significantly between the two scenarios. The scenario with micro-generation
results in unused grid capacity at period of times and an over-used grid at other times.
Another interesting observation is that the peak load in the scenario with micro-generation
has increased to approximately 7 MW. This is interesting as the grid historically has been
dimensioned only regarding to the predicted demand in an area.
Figure 17 shows the monthly summer load profiles for electricity demand and generation
from PV and small wind turbines, respectively.
Figure 17: Demand and micro-generation loads for 4500 apartments during July.
-8
-6
-4
-2
0
2
4
6
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand
Net load
0
1
2
3
4
5
6
7
8
9
10
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
PV
Demand
Wind
51
In Figure 17, the fluctuations from the different loads can clearly be observed. Both the
demand and the PV profiles indicate more regular and predictable variations, in comparison
to the wind. There is a clear distinction of the demand profiles between weekdays and
weekends. The electricity production is much larger for the PV compared to the wind power
in the studied case and it is clear that the PV generation exceeds the demand at times during
a summer month.
The intermittences in Figure 17 are presented diurnally in Figure 18, which shows the
fluctuations during one day in July with high output from the micro-generation facilities.
The curve for the demand is an average summer day in July, with error bars representing the
standard deviations.
Figure 18: Demand and micro-generation loads for 4500 apartments during one day in July.
Observed in Figure 18 is that the PV generation is highest at noon. During summer time, the
demand is rather even at daytime and approximately 1 MW lower at night. This behaviour is
probably due to that a large percentage of the residents having vacation, resulting in a
smoother demand profile with lower peak demands and a higher diversity factor. The short
error bars indicate a low variation between the days. Hence, the plotted average value is
representative.
A penetration of 20% EVs where charging is uncontrollable by the DSO, causes a slightly
higher demand in the evenings but this will not affect the grid significantly.
A way to harmonise the PV generation curve with the demand is to angle the PVs towards
west and east. However, this will most likely cause a reduction in the energy output from the
PVs. A suggestion for a DSO is to provide incentives, so that the constructor positions the
PVs towards these directions. The incentives can for example be to provide a higher grid
compensation payment during mornings and evenings, which compensates for the loss in
production.
0
1
2
3
4
5
6
7
8
9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
PV
Wind
Demand+EV
Demand
52
Figure 19 presents the monthly net summer load including micro-generation, in order to
visualise to what magnitude the power variations can be in the grid.
Figure 19: The net load profile for 4500 apartments during July.
A high penetration of micro-generation will cause variations between -7 MW and 3 MW
where the negative sign implies generation exceeding the demand and thus a net export of
electricity to the grid. However, theoretically the direction of the current is not of great
importance for the grid but it might not be dimensioned for the increased load originating
from the micro-generation, in this case 4 MW. In practise, the grid can accept a slight higher
load than it is dimensioned for but this will have consequences for the lifetime of the grid
and the grid appliances due to thermal properties. The margins for over-loading decrease in
the summer as the outdoor temperature increases. Thus, the excess production from PV is
highest when the margins are low. There is however a limit for how much the grid can allow
as fuses are positioned in connection to the network stations.
In order to study how the “worst” day, i.e. the day with the highest negative net load, the
day corresponding to the peak at hour 301 in Figure 19, is presented in Figure 20.
-8
-6
-4
-2
0
2
41
25
49
73
97
12
1
14
5
16
9
19
3
21
7
24
1
26
5
28
9
31
3
33
7
36
1
38
5
40
9
43
3
45
7
48
1
50
5
52
9
55
3
57
7
60
1
62
5
64
9
67
3
69
7
72
1
Load
(M
Wh
/h)
Time (h)
53
Figure 20: The net load profile for 4500 apartments during one day in July.
As can be seen in Figure 20, there will be hours with both excess and underage of micro-
generation. As mentioned previous, the excess load might exceed the dimensioning point of
the grid. The conventional solution in this situation is to reinforce the grid. This creates a
space for alternative solutions that can balance the load.
The corresponding curve for the day with highest micro-generation in January is displayed
in Figure 21.
Figure 21: The net load profile for 4500 apartments during one day in January.
When comparing to the summer net load, the winter load has a smaller amount of energy
that exceeds the electricity demand. Also, this load curve shows a more intermittent
behaviour, which can be explained by the wind variations, see Figure 35 in Appendix B.
These fluctuations might be hard to balance with DR due to the relatively short durations
which requires a quick response time for the end-users.
-8
-6
-4
-2
0
2
4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
-2
-1
0
1
2
3
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
54
Total area
A district like Hyllie contains a mixture of activities with both residential and commercial
buildings, resulting in different electricity demand profiles.
Figure 22 displays the load duration curves for the whole area, both with (net load) and
without micro-generation (demand).
Figure 22: The simulated load duration curve for Hyllie during July 2020.
Observed when comparing the load duration curve for the residential area in Figure 16 with
the total area in Figure 22, is that a larger part of the micro-generation is absorbed within the
studied area when it contains a mixture of demand profiles. When studying only Figure 22,
the grid seems to be not fully utilised for the situation with micro-generation and the peak
demand is lowered compared to the situation without micro-generation. To be considered is
also the winter months when the grid is fully utilised, see Figure 36, Appendix B. When
disregarding the peaks in the load duration curve, the curve representing the area with
micro-generation it is smoother than the curve representing only the demand. The peaks
might be balanced by batteries and peak pricing, hence creating an almost flat curve, which
is desirable for the DSO.
In Figure 23, the load variations for July regarding both demand and micro-generation is
visualised.
-4
-2
0
2
4
6
8
10
12
14
16
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand
Net load
55
Figure 23: Demand and micro-generation loads for Hyllie during July 2020.
The PV generation will exceed the total demand of Hyllie at some occasions, mainly in
weekends, see Figure 23. This is due to that the demand of the office buildings is very low
during weekends. Another observation is that the peaks for the demand and the PV
generation generally occur at the same time, i.e. at noon. This is a significant difference
comparing to the corresponding graph for only the residential load in Figure 17.
A day during a weekend in July with average demand and “worst case” generation is
presented in Figure 24. The demand is represented as an average during a weekend day as,
according to Figure 23, it is most likely that the “worst case” imbalance will occur then.
Figure 24: Demand and micro-generation loads for Hyllie a weekend day in July 2020.
During this day, the local electricity production exceeds the demand of the district at noon.
The expected number of EVs in the district will, when charging is uncontrollable, contribute
0
2
4
6
8
10
12
14
16
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand
PV
Wind
0
1
2
3
4
5
6
7
8
9
10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
Demand+EV
Demand
PV
Wind
56
to an increase of the electricity demand during daytime, consequently absorbing some of the
micro-generation.
In Figure 25, the net load profile for Hyllie during July is presented.
Figure 25: The net load profile for Hyllie during July 2020.
At some occasions, the district Hyllie will be unable to utilise all the produced electricity. At
these hours, the electricity will be transported away and utilised in another part of the grid
area. A future concern for the DSO is if all districts within a city have a high penetration of
micro-generation. If this situation occurs, the excess electricity will be transported higher up
in the grid, resulting in higher losses and penalty fees.
The net load profile for Hyllie at the “worst” day in July is presented in Figure 26.
Figure 26: The net load profile for Hyllie during one day in July 2020.
-4
-2
0
2
4
6
8
10
12
14
1
25
49
73
97
12
1
14
5
16
9
19
3
21
7
24
1
26
5
28
9
31
3
33
7
36
1
38
5
40
9
43
3
45
7
48
1
50
5
52
9
55
3
57
7
60
1
62
5
64
9
67
3
69
7
72
1
Load
(M
Wh
/h)
Time (h)
-4
-3
-2
-1
0
1
2
3
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Load
(M
Wh
/h)
Time (h)
57
The amount of excess energy due to micro-generation is lower for the whole area than for the
residential area only, see Figure 20. Also, the highest power peak originates from the high
demand, thus not the micro-generation. As can be seen in the load duration curve, Figure 36
Appendix B, the grid must be dimensioned to handle loads in the range of 18 MW. Hence,
the micro-generation will not, in this situation, cause any capacity problems for the DSO.
4.3.2 Scenario 2 – A grid with alternative solutions
In all figures presented in this section, a 20% penetration of EVs with DSO controllable
charging is included in the demand. The solutions for energy storage and DR is visualised
whenever balancing is possible.
Residential
The changes in the demand as a response to CPP and controllable EV charging are presented
in Figure 27 for a summer day. Even though it would be most beneficial if the EV charging
took place at noon, in order to absorb more of the micro-generation, this might not be
possible in the residential area as most people are at work at noon. Therefore, the charging is
shifted to night-time as the demand is lower then.
Figure 27: Demand and micro-generation loads with controllable EVs and CPP for one day in July 2020.
Figure 27 clearly demonstrates that neither the controllable load from EVs nor CPP is enough
to balance the micro-generation in a residential area.
As the highest demand (6 MW) is reached in January, see Figure 37, Appendix B, the grid
must be dimensioned to handle this load. As this seldom occurs, it is acceptable if the cables
have a capacity of 5 MW due to economic aspects. Figure 28 presents the same summer day
as shown in Figure 27 but in Figure 28, it is obvious that the net load will exceed this capacity
of the grid. Therefore, also energy storage has been included in the figure. To keep the load
at an acceptable level for the grid, the storage in this case needs to have a rated capacity of
0
1
2
3
4
5
6
7
8
9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
PV
CPP
Demand
Demand+EV
Wind
58
1.8 MW. Hence, the provided storage capacity is 1.5 MW if the efficiency of the battery is
85%.
In Figure 29, the net load for the winter day with highest production is simulated.
Figure 28: The net load profiles for loads during a summer day in July in a residential area with different
balancing solutions.
Figure 29: The net load profiles for loads during a winter day in January in a residential area with different
balancing solutions.
As shown in Figure 28, it is possible to keep the load within the capacity limits of the grid by
employing both DR in the form of CPP and a battery with a capacity of 1.5 MW. These
alternative solutions can provide a higher tolerance of unforeseen events and a lower wear of
the cables.
In winter, only DR is required in order to maintain the load within the desired range of -5 to
5 MW, see Figure 29.
-8
-6
-4
-2
0
2
4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
Net load
CPP
Storage
-2
-1
0
1
2
3
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
Net load
CPP
59
The above proposed solutions result in the summer load duration curves presented in
Figure 30. In this figure, the residential demand without installed micro-generation is also
represented.
Figure 30: The load duration curves for July in a residential area with different solutions.
When comparing the load duration curves including balance solutions for a summer month,
it can be seen that CPP alone balances some intermittences while combined with battery
storage, it is possible to reduce the peak loads in a residential area. Thus, capacity margins in
the grid are provided.
Total area
The following simulations for the total area of Hyllie year 2020 include EV parking lots
divided into three segments; residential, office and shopping. Only the residential parking
lots are controllable by the DSO as the EV charging for other segments are difficult to shift
due to their operating time which is mainly during daytime.
In Figure 31, the demand for the whole area is shifted with controllable EVs and CPP, in
order to follow the micro-generation load.
-8
-6
-4
-2
0
2
4
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand
CPP + Storage
CPP
Net load
60
Figure 31: The micro-generation and demand profile with DR for the total area during one day in July.
The residential controllable EVs are able to shift part of the demand from the evening to the
night, whereas the uncontrollable EVs increase the demand at noon, see Figure 31. CPP can
possibly absorb a part of the peak caused by micro-generation in a district with a mixture of
facilities. The load that can be shifted by CPP is illustrated in Figure 32 for a summer day and
in Figure 33 for a winter day.
Figure 32: The net load profile with DR for the total area during one day in July.
0
1
2
3
4
5
6
7
8
9
10
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
Demand+EV
Demand
CPP
Wind
PV
-4
-3
-2
-1
0
1
2
3
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24Load
(M
Wh
/h)
Time (h)
Net load
CPP
61
Figure 33: The net load profile with DR for the total area during one day in July.
Figures 32 and 33 show that even with a high penetration of micro-generation in the whole
area, the load from PV and small wind turbines does not result in net load greater than the
highest demand. Despite this, an over production of electricity will occur occasionally during
summer. However, this load will not exceed the capacity of the grid. Subsequently, no
energy storage is needed for peak reduction in districts with diversified demand profiles.
During winter, when the output from PV is low whereas the output from wind is higher,
batteries are unsuitable due to the short term variations in the wind pattern which cause
wearing of the battery and hence shorten the life time.
Furthermore, Figure 33 illustrates the difficulties with finding a suitable tariff that suits the
irregular wind output. A time-of-use tariff would here be hard to implement whereas a more
dynamic pricing would be more suitable. It would also be beneficial with automated devices
due to the rapid changes in the weather.
The load duration curve for Hyllie in July with CPP is presented in Figure 34.
0
2
4
6
8
10
12
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
Net load
CPP
62
Figure 34: The load duration curve for July in Hyllie with and without DR and micro-generation.
Figure 34 shows that CPP on a monthly basis, only slightly evens out the load duration
curve. Furthermore, with micro-generation during summer, the maximum peak is lowered
and a main part of the load curve is more flat.
4.3.3 Economic feasibility
In order to calculate whether battery storages with a total capacity of 1.8 MW, as needed
according to Figure 28, located downstream the MV/LV substations, are an economic
investment, it is compared with the costs for a grid upgrade. The costs for the respective
investments are presented in Table 7, where the price for reinforcement includes new cables
with a length of 5 km as well as control cables. The price for extension includes all costs
related to constructing a 5 km new loop i.e. secondary substations, trafo and cables. The
expected battery lifetimes in Table 7 are calculated based on the cycle life of the batteries, see
Table 4, and the number of cycles during one year. The number of cycles during one year is
based on the expected number of occasions that the net load in the residential area exceeds 5
MW, which is approximately 80 occasions each year.
Table 7: Investment cost and lifetime of T&D grid upgrades and different batteries
Measure T&D upgrade Battery (1.8 MW)
Reinforcementa Extensiona NaS Li-ion Pb-acid
Cost
(€)
680 000 1 120 000 1 270 000-
3 910 000
5 200 000 370 000
Lifetime
(year)
40 40 50 100 10
a After (EBR, 2013).
According to Table 7, neither NaS nor Li-ion batteries are economic options to a T&D-
upgrade when comparing only the investment cost. However, if also the lifetime is
considered, NaS is economic comparable to a grid extension. The long expected lifetime of
-4
-2
0
2
4
6
8
10
12
14
16
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand
CPP
Net load
63
the batteries are due to the seldom usage as they are only intended to be used to reduce
peaks that exceeds the grid capacity. If they would be located in the dwellings and not
owned by the DSO, they would most likely be used more often as it would be desirable to
store all over-production, hence resulting in a shorter lifetime.
A viable alternative is Pb-acid batteries. The lifetime of these batteries is however short
which causes the annual cost to be higher than a T&D upgrade. Consequently, this is a
temporary solution that can defer a T&D upgrade. The profitability of an upgrade deferral is
however currently small due to the presently low interest rate. Even so, the future interest is
hard to predict and thus, the grid update deferral might become more profitable in the near
future. Also, the battery prices are likely to decrease due to development and market
expansion.
4.4 Concluding remarks
The conventional dimensioning of the grid infrastructure in Hyllie will be able to
support a future scenario with a maximum penetration of micro-generation, i.e. the
total load will not increase.
The business-case for balance solutions in the area of Hyllie is rather to smooth the
load duration curve with energy storage and DR in order to be able to connect more
customers to the same loop. It would then be possible to avoid investment in T&D
upgrade.
If an area of only residential structures is to be planned, consideration must be taken
to micro-generation as this has been proven to be able to cause higher loads than the
demand itself.
With the prices of today, investments in battery storages in the studied grid instead of
T&D upgrades are not economical without subsidies.
64
65
5 Discussion
In this section, the future prospects for solutions to balance micro-generation as well as the
challenges for a DSO are discussed. Furthermore uncertainty parameters are analysed. In the
end of the section recommendations for further studies are suggested.
5.1 Future prospects
The penetration of micro-generation is dependent on the development of incentives to
promote small-scale generation. Hence, it is hard to predict the magnitude of the future
power variations in the local grid. Despite this, it is important for a DSO to be prepared for a
future which is unlike the situation the past century where the grid capacity is solely based
on the demand. To prepare for an alternative future is especially important due to the long
life-time and high cost of the grid infrastructure. Moreover, grid costs will become harder to
allocate as an increased self-supply of electricity will result in that fewer consumers will use
the grid. Therefore, the future grid must be cheaper in order for the grid fees to remain at an
acceptable level, which is regulated by the revenue cap controlled by Ei. The obvious
solution is to optimise the load in order to improve the degree of utilisation.
A way to optimise the load is to provide incentives for both producers and consumers to
adjust their load in accordance with the current capacity situation in the local grid. This
incentives have to come from the DSO as they are the grid responsible party and hence
negative affected by the intermittencies. Without incentives, customers act blindly and
sometimes create problems for the network without knowing it and without having to pay
for it additionally. Hence, DR with dynamical pricing where grid-users pay for their used
capacity is an important part when optimising the degree of utilisation. In some cases, DR
will not be enough to stabilise the local grid, as for example the simulated grid with only
residential customers, see Figure 27. In these situations other alternative solutions are
required to maintain the load within the grids capacity limits.
Energy storage is one alternative that recently has gained a lot of attention. Theoretically,
batteries could be the solution for most grid related problems. However, due to the high
prices which are unlikely to sink below an acceptable level until 2020, it is more realistic to
install batteries with only the capacity of reducing the worst peaks. In reality at present,
batteries are expensive and the ownership is regulated so that it is not economical for the
DSO to invest in storage. Therefore, with today’s circumstances a suggested strategy for a
DSO is rather to send price-signals to micro-generators to invest in energy storages.
Moreover, in the future beyond 2020 with decreasing battery prices storage most likely will
become viable. Furthermore, the increasing market for EVs might ultimately lead to a
secondary market for batteries which can be either recycled or reused as peak shaving
storages. Also, the cost for batteries can be allocated to different services and actors e.g. DSO
and electricity supplier, as storages often provide synergies with several benefits.
To coordinate all flexible capacity, e.g. flexible customers, EVs and storages, as well as to
ensure that the DSO receives the acquired flexibility, a capacity market is a promising
66
solution. However, there are still many uncertainties to solve for capacity markets to become
reality. Examples of uncertainties are who would like to take the role as an aggregator, how
the flexibility deliveries can be assured and how the unpredictable renewable production
loads will be forecasted? Hence, a larger scale capacity market in Sweden seems remote until
2020.
Local balances with even load profiles may be both positive and negative for the DSO.
Beneficial is a reduced need of grid investments due to bottleneck problems and reduced
payments to the overlaying grid. On the other hand, the DSO might have to convert their
business from handling grids that distributes electricity to a disposal grid only used during
power shortage i.e. micro-grids. However, this is from a DSOs perspective and from a
customer perspective it would be favourable.
5.2 Uncertainty parameters
As always when predicting the future, there are many uncertainties that have to be regarded
when reading the report and interpreting the results.
Concerning the micro-generation, the production data for PV and wind are gathered from
different sources. The output from PV is from actual production data from one plant during
one year. However, whether the production from this year can be used as standard has not
been investigated. The output from the small wind turbines is calculated from actual hourly
wind speed data at 10 meters and the power curve for one wind turbine. Hence, the wind
speed may differ in an area like Hyllie, both due to the altitude of which the turbines are
placed at, but also due to the turbulence caused by the roughness of the area. Also, the
power curve received from the manufacturer may be exaggerated, which causes a higher
production than in reality.
Furthermore, the simulated micro-generation is based upon assumptions that all rooftops are
covered with PV and wind turbines to a very high degree. This situation is rather unlikely to
occur by 2020. On the other hand, lesser production facilities placed on rooftops might be
compensated by more generation placed on e.g. facades and the ground. Furthermore, the
legislations concerning micro-generation are under debate and it is presently rather difficult
to interpret how large a micro-generation unit is allowed to be in order to get subsidies.
The data for the demand is also from actual measurements and thus might not completely
correspond to the future demand of Hyllie. Additionally, the heating source for all facilities
is expected to be district heating. Hence, no heat pumps are accounted for in the simulations.
It is also uncertain whether the planned amount of buildings actually will be constructed
until 2020.
All data for both generation and demand are hourly measured or calculated. Hence, shorter
variations in the interval of seconds are not represented in the figures.
67
As for DR, it is difficult to predict the actual response. Therefore, the amount of peak
reduction used in the simulations may differ if implementing DR in reality.
The assumptions for EVs are based on a rather high penetration of 20%. However, the
development of the EV market is uncertain and dependant on regulatory measures as well as
the markets for other alternative fuels, e.g. biogas and hydrogen. Furthermore, it is unsure if
the EVs will act as an added demand mainly during peak hours or if they can be operated as
electricity reservoirs for the grid.
The costs both regarding T&D upgrades and energy storages are estimated costs which are
likely to change in the coming years. The costs, especially for grid extensions, are highly
dependent on the local conditions and possible rebates.
5.3 Recommendations for further studies
Simulate the effect of micro-generation with software for grid calculations e.g.
dpPower, in order to investigate the impact on the power quality as well as to be able
to implement the study further in the business and grid planning.
Study electricity load variations for a similar or rural area with electric heating or
heat pumps as the loads are different and might be more suitable for DR.
Examine where in the grid energy storage should be located to provide most benefits
to the lowest cost.
Calculate what grid fees and electricity prices that would be necessary in order to
provide enough incentives for customers to invest in energy storages or shift their
loads.
Analyse how high the grid compensation payment would have to be altered in order
for the grid customers to place their PV panels in other azimuth angels to smooth the
output profile for the area. Is this a legal possible and realistic alternative?
Investigate how the legislations, e.g. the Electricity Act, should be developed to
provide incentives and allow the DSO to operate energy storages for peak-shaving.
Study if there can be a profitable business-case within the next few years if energy
storages are co-utilised by a DSO, electricity supplier and others.
Calculate the break-even point for curtailing versus to store energy. Can curtailment
be a sustainable solution in a life cycle-perspective compared to the required energy
for manufacturing cables or energy storages?
68
69
6 Conclusions
The main conclusions from both the literature study and the case study are presented below.
•In residential areas, the load from micro-generation can exceed the capacity of the grid. Therefore, consideration have to be taken during planning. In an existing grid, reinforcements or alternative solutions must be employed.
•In areas with mixed activities, e.g. Hyllie, the grid capacity will not be exceeded even with a high penetration of micro-generation.
Is micro-generation a problem for the local grid?
•Critical peak pricing is the most promising method for demand response when considering only the potential peak reductions.
•Li-ion and NaS batteries are the most suitable energy storage methods for local peak-shaving due to their favourable technical and environmental aspects.
Suitable balance solutions
•Battery storages are not presently an economical alternative to reinforcements/extensions of the local grid.
•Demand response is a more economical solution but this is not sufficient to reduce all intermittencies.
•It is difficult for a network operator to own a storage due to the legislations. Co-operations between a network operator and other owners are possible.
Viability of the balance solutions
70
References
AALAMI, H., MOGHADDAM, M. P. & YOUSEFI, G. 2010. Demand response modeling
considering interruptible/curtailable loads and capacity market programs. Applied Energy,
87, p. 243-250.
ABB. 2014. Energilager - här lagras vindenergi. Web page:
http://www.abb.com/cawp/seitp202/66f810ec7a1468c7c1257a2b0034bc14.aspx
Accessed: 2014-05-20.
ALBADI, M. H. & EL-SAADANY, E. F. 2008. A summary of demand response in electricity
markets. Electric Power Systems Research, 78, p. 1989-1996.
BEAUDIN, M., ZAREIPOUR, H., SCHELLENBERGLABE, A. & ROSEHART, W. 2010. Energy
storage for mitigating the variability of renewable electricity sources: An updated review.
Energy for Sustainable Development, 14, p. 302-314.
BIRKE, A., HANSEN, L. H. & HARBO, S. 2013. FLECH - General market regulations. 4 ed.:
iPower.
BLOMSTERLIND, J. 2009. Elnätets kapacitet inför elbilsladdning 2020 - En kartläggning och
konsekvensanalys inför framtida elbilsladdning med avseende på år 2020.
BORG, P. 2012. Förstudie Energilager anslutet till vindkraft. Elforsk, 12:44.
BORG, PIA. Project leader at Falbygdens Energi AB. E-mail correspondence. 2014-05-09.
BURMEISTER, STEPHAN, Power2Gas Falkenhagen, E.DIS AG, Oral communication during
study visit in Fürstenwalde, Germany. 2014-05-13
CAVALLO, A. 2007. Controllable and affordable utility-scale electricity from intermittent wind
resources and compressed air energy storage (CAES). Energy, 32, 120-127.
CHATZIVASILEIADI, A., AMPATZI, E. & KNIGHT, I. 2013. Characteristics of electrical energy
storage technologies and their applications in buildings. Renewable and Sustainable
Energy Reviews, 25, p. 814-830.
CHEN, H., CONG, T. N., YANG, W., TAN, C., LI, Y. & DING, Y. 2009. Progress in electrical
energy storage system: A critical review. Progress in Natural Science, 19, p. 291-312.
DAMSGAARD, N. & FRITZ, P. 2006. Affärsmodeller för ökad efterfrågerespons på elmarknaden.
Elforsk.
DÍAZ-GONZÁLEZ, F., SUMPER, A., GOMIS-BELLMUNT, O. & VILLAFÁFILA-ROBLES, R.
2012. A review of energy storage technologies for wind power applications. Renewable and
Sustainable Energy Reviews, 16, p. 2154-2171.
DIVYA, K. C. & ØSTERGAARD, J. 2009. Battery energy storage technology for power systems—
An overview. Electric Power Systems Research, 79, p. 511-520.
DUNN, B., KAMATH, H. & TARASCON, J.-M. 2011. Electrical Energy Storage for the Grid: A
Battery of Choices. Science, 334, p. 928-935.
DYBDAL CAJAR, P. & HANSEN, L. H.. 2014. Introduction of the FLECH solution and first
DSO service. iPower seminar and demonstration at IBM, 2014-04-08 Copenhagen.
71
E.ON. 2012. Så här funkar elnätet . Web page: http://www.eon.se/privatkund/Produkter-och-
priser/Elnat/Sa-har-funkar-elnatet/. Accessed: 2014-02-26.
E.ON. 2014. Huntorf power plant. Web page: http://www.eon.com/en/about-us/structure/asset-
finder/huntorf.html. Accessed: 2014-03-13.
EBR 2013. Kostnadskatalog - Lokalnät 0,4-24kV samt optonät, planeringskatalog P1. Svensk Energi
- Swedenergy AB.
EK, G. & HALLGREN, W. 2012. Bilaga A-F: Elnätstariffer - Behövs mer regler om avgifternas
utformning? The Swedish Energy Markets Inspectorate (Ei).
EcoWatch Canada. 2013. Vertical or Horizontal axis. Web page:
http://ecowatchcanada.wordpress.com/2013/09/06/vertical-axis-or-horizontal-axis/.
Accessed: 2014-06-16.
EYER, J. & COREY, G. 2010. Energy storage for the electricity grid: Benefits and market potential
assessment guide. Sandia National Laboratories.
FERREIRA, H. L., GARDE, R., FULLI, G., KLING, W. & LOPES, J. P. 2013. Characterisation of
electrical energy storage technologies. Energy, 53, p. 288-298.
FRITZ, P. 2012. Övergripande drivkrafter för efterfrågeflexibilitet - Hinder, möjligheter och
alternativa utvecklingsvägar. Elforsk.
FU, B. Q., HAMIDI, A., NASIRI, A., BHAVARAJU, V., KRSTIC, S. & THEISEN, P. 2013. The
Role of Energy Storage in a Microgrid Concept - Examining the opportunities and promise of
microgrids. IEEE Electrification Magazine.
GLOBAL WIND ENERGY COUNCIL. 2014. Global statistics. Web page:
http://www.gwec.net/global-figures/graphs/. Accessed: 2014-05-21.
IBRAHIM, H., ILINCA, A. & PERRON, J. 2008. Energy storage systems—characteristics and
comparisons. Renewable and Sustainable Energy Reviews, 12, p.1221-1250.
JPM. 2014. Demand response. Web page: http://www.pjm.com/markets-and-
operations/demand-response.aspx. Accessed: 2014-05-09.
KLINGE JACOBSEN, H. & SCHRÖDER, S. T. 2012. Curtailment of renewable generation:
Economic optimality and incentives. Energy Policy, 49, p. 663-675.
KOOHI-KAMALI, S., TYAGI, V., RAHIM, N., PANWAR, N. & MOKHLIS, H. 2013.
Emergence of energy storage technologies as the solution for reliable operation of smart power
systems: A review. Renewable and Sustainable Energy Reviews, 25, p. 135-165.
KOUSKSOU, T., BRUEL, P., JAMIL, A., EL RHAFIKI, T. & ZERAOULI, Y. 2014. Energy
storage: Applications and challenges. Solar Energy Materials and Solar Cells, 120, p. 59-
80.
LARSSON, Ö., STÅHL, B. 2012. Lösningar på lager - Energilagringstekniken och framtidens
hållbara energiförsörjning. Vinnova.
LINDAHL, J. 2013. National Survey Report of PV Power Applications in Sweden - 2012. Ångström
Solar Center, Uppsala University.
72
LOISEL, R., PASAOGLU, G. & THIEL, C. 2014. Large-scale deployment of electric vehicles in
Germany by 2030: An analysis of grid-to-vehicle and vehicle-to-grid concepts. Energy
Policy, 65, p. 432-443.
LUND, H. 2006. Large-scale integration of optimal combinations of PV, wind and wave power into
the electricity supply. Renewable Energy, 31, p. 503-515.
LYDÉN, P., SÄMFORS, O. & FRITZ, P. 2011. Lokalnätstariffer - Struktur och utformning. Sweco
Energuide AB.
CAESAR, K. & MORLAND, C.. 2007. Hyllievångs trafikfunktionsprogram. Gatukontoret -
Trafikavdelningen, Malmö stad.
MALMÖ STAD. 2014. Översiktsplan för södra Hyllie – Fördjupning av översiksplan för Malmö,
Samrådsunderlag.
MANWELL, J. F., MCGOWAN, J. G. & ROGERS, A. L. 2009. Wind Energy Explained: Theory,
Design and Application, Wiley.
MARTINSSON, F. 2009. Vindkraft och elbilar på Öland år 2020 - Är smart laddning av elbilar
lösningen på ett framtida flaskhalsproblem? Master thesis, Uppsala University.
MASSON, G., LATOUR, M., REKINGER, M., THEOLOGITIS, I.-T. & PAPOUTSI, M. 2013.
Global market outlook for photovoltaics 2013-2017. European Photovoltaic Industry
Association (EPIA), European Commision.
MOHSENI, F., MAGNUSSON, M., GÖRLING, M. & ALVFORS, P. 2012. Biogas from renewable
electricity–increasing a climate neutral fuel supply. Applied Energy, 90, p. 11-16.
NAIR, N.-K. C. & GARIMELLA, N. 2010. Battery energy storage systems: Assessment for small-
scale renewable energy integration. Energy and Buildings, 42, p. 2124-2130.
NEPP 2011. Kapacitetsmekanismer: Stora volymer av intermittent produktion leder till ökat
europeiskt intresse för kapacitetsmekanismer. North European Power Perspectives.
NEPP 2013. Förutsättningar och drivkrafter för olika typer av elkunder att justera
förbrukningsmönster och minska sin elförbrukning idag och i framtiden.
NKG INSULATORS LTD. 2014. NaS batteries - Principles Web page:
http://www.ngk.co.jp/english/products/power/nas/principle/index.html. Accessed
2014-03-13.
PIEPER, C. & RUBEL, H. 2012. Electricity storage: Making large-scale adoption of wind and solar
energies a reality. Balanced Growth. Springer.
PLUCIENNIK, REMIGIUSZ, Asset manager - Renewables and CHP at E.DIS AG, Oral
communication during study visit in Fürstenwalde, Germany. 2014-05-13.
PYRKO, J. 2005. Direkt och indirekt laststyrning i samspel? Fallstudier. Department of Energy
Sciences, Lund University – LTH. ISSN: 0282-1990
PYRKO, J. (editor). 2014. Smart om smarta nät. Department of Energy Sciences, Lund
University - LTH, ISRN LUTMDN/TMHP-14/3053-SE.
73
SCHÄFER, LUTZ, Battery storage responsible at E.DIS AG, Oral communication during study
visit in Fürstenwalde, Germany. 2014-05-13
SKANSKA. 2013. Klipporna - nya utsikter i Hyllie. Web page: http://www.skanska.se/sv/ny-
lokal/kontorslokaler/hyllie-klipporna/hyllie-klipporna-500kvm/. Accessed: 2014-06-
03.
SKÖLDBERG, H., LÖFBLAD, E., HOLMSTRÖM, D. & RYDÉN, B.. 2010. Ett fossiloberoende
transportsystem år 2030 – Ett visionsprojekt för Svensk Energi och Elforsk. Elforsk 10:55
SOYLU, S. 2011. Electric Vehicles - The Benefits and Barriers, InTech.
STEELE, A. & NIEMI, M. 2013. Die Energiewende - Den tyska energiomställningen. FORES
Policy Paper.
STROMBACK, J., DROMACQUE, C. & YASSIN, M. H. 2011. The potential of smart meter
enabled programs to increase energy and systems efficiency: a mass pilot comparison. Vaasa
ETT.
SWEDISH ENERGY MARKETS INSPECTORATE. 2013. Network price regulation Web page:
http://ei.se/en/Electricity/Network-price-regulation/. Accessed: 2014-02-26.
SWEDISH ENERGY MARKETS INSPECTORATE (Ei). 2012. Elnät och nätprisreglering. Web
page: http://www.energimarknadsinspektionen.se/sv/el/Elnat-och-natprisreglering/
Accessed: 2014-05-30.
SVENSK ENERGI 2011. Anslutning av mikroproduktion till konsumtionsanläggningar– MIKRO.
SVENSK SOLENERGI. 2014. Fakta om solenergi. Web page:
http://www.svensksolenergi.se/fakta-om-solenergi. Accessed: 2014-03-07.
SVENSK VINDENERGI 2013. På väg mot ett förnybart elsystem - möjligheter till 2030 Rapport
med tre möjliga utvecklingsvägar för elproduktion och elanvändning fram till 2030.
SÖDER, L. 2013. På väg mot en elförsörjning baserad på enbart förnybar el i Sverige: En studie om
kraftsystemets balansering: Version 3.0.
THE SWEDISH GOVERNMENT. 2014. Lagrådsremiss Skattereduktion för mikroproduktion av
förnybar el. FINANCE, M. O. (ed.).
TRINA SOLAR LTD. 2011. TSM-PC05 – The Universal Solution. Product data sheet.
UC SAN DIEGO. 2014. Microgrid: Keeping the Lights On. Web page:
http://alumni.ucsd.edu/s/1170/emag/emag-interior-2
col.aspx?sid=1170&gid=1&pgid=4665. Accessed: 2014-05-08.
VAESSEN, P. 2013. Smart grid and the load or generation duration curve. Web page:
http://smartgridsherpa.com/blog/smart-grid-and-the-load-or-generation-duration-
curve. Accessed: 2014-05-07.
VATTENFALL. 2014. Elnätspriser. Web page: http://www.vattenfall.se/sv/elnatspriser.htm.
Accessed 2014-03-10.
VUKALIC, PATRIK, Grid planner at E.ON Elnät Sverige AB. Oral communication. 2014-04-
10.
74
WENHAM, S. R., GREEN, M. A., WATT, M. E., CORKISH, R. & SPROUL, A. 2012. Applied
photovoltaics, Routledge.
WORLD WIND ENERGY ASSOCIATION 2012. Small Wind World Report 2012.
WORLD WIND ENERGY ASSOCIATION 2013. Small Wind World Report Update 2013.
75
Appendix A
Assumptions used for calculations in the case study of Hyllie year 2020 are presented in
Table 8.
Table 8: Assumptions for simulations of a residential area and the district Hyllie year 2020
Residential Total area
Facilities 4500 apartments 4500 apartments
4500 workspaces
3 schools
1 public bath
1 shopping mall (Emporia)
1 hockey arena
1 exhibition hall
1 railway station
Buildings 237 residential buildings
19 apartments/dwellingsa
13 office buildingsb
Rooftop area 480 m2/residential buildingc 930 m2/office buildingd
Electric vehicles 20% penetration by 2020e
Charging profilesg
0,65 cars/householdf
585 EV parking lots
2 170 EV parking lotsh
(Emporia: 1000, residential:
585, office: 585)
Micro-
generation
(Max. 69 kW)
PV PV modules at rails (25° declination) equals 65% of rooftop
area
Efficiency of 14.7% i
143.3 Wp/m2 i
0° azimuth (PV modules facing south)
312 m2/residential building 312 m2/residential building,
480 m2/other building,
1300 m2/one of the schools
Wind
power
Power curve from Windon 2 kW
Four rotor diameters between wind turbines
4 wind turbines/residential
building
10 wind turbines/commercial
building
Demand response Critical peak pricing
24% peak reductions
a based on an average for five multi-family dwellings in Västra Hamnen, Malmö.
b based on number of workspaces at one of E.ON’s offices in Malmö.
c, f After (Malmö stad, 2014).
d Based on (Skanska, 2013).
e After (Sköldberg et al., 2010).
f After (Malmö stad, 2014).
g After (Soylu, 2011).
h Based on (Caesar & Morland, 2007).
i After (Trina Solar Ltd., 2011).
76
Appendix B
Scenario 1 – A conventional grid
In Figure 35 the demand and micro-generation loads for the residential case during one day
in January is illustrated.
Residential
Figure 35: Demand and micro-generation loads for 4500 apartments during one day in January.
Total area
In Figure 36, the load duration curves with (net load) and without (demand) micro-
generation for Hyllie during January are presented.
Figure 36: The simulated load duration curve for Hyllie during January 2020.
0
1
2
3
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(M
Wh
/h)
Time (h)
Demand+EV
Demand
Wind
PV
0
2
4
6
8
10
12
14
16
18
20
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand
Net load
77
Scenario 2 – A grid with alternative solutions
Residential
In Figure 37, the load duration curves with and without micro-generation, as well as with
CPP are presented for the residential area during January.
Figure 37: The load duration curves for January in a residential area with different solutions.
Standard deviation of the residential demand
Figure 38 illustrates the mean value and the standard deviations of the demand for five
residential buildings in Västra Hamnen in Malmö for one day in July.
Figure 38: Standard deviations of the electricity demand of five newly built residential buildings in Västra
Hamnen, Malmö for one day in July.
-2
-1
0
1
2
3
4
5
6
7
12
54
97
39
71
21
14
51
69
19
32
17
24
12
65
28
93
13
33
73
61
38
54
09
43
34
57
48
15
05
52
95
53
57
76
01
62
56
49
67
36
97
72
1
Load
(M
Wh
/h)
Time (h)
Demand+EV
CPP
Net load
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Load
(kW
h/h
)
Time
78
Appendix C
Charging profiles for uncontrolled charging of EVs is shown in Figure 39 and for controlled
charging of EVs in Figure 40.
Figure 39: Charging profile for uncontrolled charging of EVs (Soylu, 2011).
Figure 40: Charging profile for smoothing off-peak charging of EVs (Soylu, 2011).