Micro Application Example

Closed-Loop Positioning Control with standard Drives

Micro Automation Set 1

Page 2: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Table of Contents

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 2/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Note The Micro Automation Sets are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The Micro Automation Sets do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are correctly used. These Micro Automation Sets do not relieve you of the responsibility of safely and professionally using, installing, operating and servicing equipment. When using these Micro Automation Sets, you recognize that Siemens cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Micro Automation Sets at any time without prior notice. If there are any deviations between the recommendations provided in these Micro Automation Sets and other Siemens publications – e.g. Catalogs – the contents of the other documents have priority.

Warranty, liability and support We do not accept any liability for the information contained in this document.

Any claims against us – based on whatever legal reason – resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Micro Automation Set shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (“wesentliche Vertragspflichten”). However, claims arising from a breach of a condition which goes to the root of the contract shall be limited to the foreseeable damage which is intrinsic to the contract, unless caused by intent or gross negligence or based on mandatory liability for injury of life, body or health. The above provisions does not imply a change in the burden of proof to your detriment.

Copyright© 2008 Siemens IA and DT. It is not permissible to transfer or copy these Micro Automation Sets or excerpts of them without first having prior authorization from Siemens IA and DT in writing.

Page 3: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Table of Contents

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 3/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Foreword Micro Automation Sets are functional and tested automation configurations based on IA/DT standard products for easy, fast and inexpensive implementation of automation tasks for small-scale automation. Each of the available Micro Automatic Sets covers a frequently occurring subtask of a typical customer problem in the lower performance range.

The sets help you obtain answers with regard to required products and the question how they function when combined.

However, depending on the system requirements, a variety of other components (e.g. other CPUs, power supplies, etc.) can be used to implement the functionality on which this set is based. For these components, please refer to the respective SIEMENS IA and DT catalogs. The Micro Automation Sets are also available at:

http://www.siemens.de/microset

Page 4: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Table of Contents

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 4/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Table of Contents

Table of Contents ......................................................................................................... 4

1 Fields of Application and Benefits................................................................ 5 1.1 Automation problem.......................................................................................... 5 1.2 Automation solution – Set 1.............................................................................. 6 1.3 Fields of application .......................................................................................... 8 1.4 Benefits............................................................................................................. 8

2 Configuration .................................................................................................. 9

3 Hardware and Software Components......................................................... 11

4 Principle of Operation .................................................................................. 13 4.1 Introduction to positioning............................................................................... 13 4.2 Block libraries for moving linear and rotary axes ............................................ 19 4.3 Configuring the G110 frequency inverter........................................................ 23 4.4 Optimizing the positioning operation............................................................... 25 4.4.1 Optimization with regard to the moment of inertia .......................................... 25 4.4.2 Optimization of the travel profile ..................................................................... 27

5 Configuring the Startup Software ............................................................... 29 5.1 Preliminary remark.......................................................................................... 29 5.2 Downloading the startup code ........................................................................ 29 5.3 Configuring the CPU 224XP PLC ................................................................... 30 5.4 Preparing the archiving function ..................................................................... 34 5.5 Loading the TP 177micro Touch Panel .......................................................... 35 5.6 Parameterizing the G110 frequency inverter .................................................. 36

6 Live Demo...................................................................................................... 38 6.1 Setting up the wire-wound coils ...................................................................... 40 6.2 Feeding in the wire ......................................................................................... 41 6.3 Automatic mode.............................................................................................. 42 6.3.1 Production of 10 wire rods with a length of 2m............................................... 42 6.3.2 Premature termination of the production process........................................... 43 6.4 Cutting wire rods of variable length (manual mode) ....................................... 44 6.5 Immediate stopping of the feed motion........................................................... 45 6.5.1 Stopping using the stop button of the TP 177micro........................................ 47 6.5.2 Stopping using the hardware stop button (emergency stop) .......................... 48 6.6 Data logging.................................................................................................... 49 6.7 Optimizing the positioning process ................................................................. 50

7 Technical Data .............................................................................................. 53

Page 5: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Fields of Application and Benefits

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 5/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

1 Fields of Application and Benefits

1.1 Automation problem

A wire cutting machine is to produce a customer-specific number of wire rods with customized length.

After equipping the machine with the desired wire-wound coil, the management of the coil’s type and available capacity is to be voltage-protected, the positioning axis unwinds the desired length from the wire-wound coil and cuts the wire. This operation is repeated according to the number entered together with a production ID.

After completing the production job, voltage-resistant buffering has to be performed for all specific production data to read it from a PC once a day and to archive them there within the scope of quality assurance.

After feeding in the wire prior to production, the wire is to be located in front of the cutting device.

Figure 1-1

Type2 Type3Type1

CutterWire-wound coil

Page 6: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Fields of Application and Benefits

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 6/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

1.2 Automation solution – Set 1

With the aid of the TP177micro Touch Panel, all material data of the available wire-wound coils that is relevant to the production can be stored as a recipe in the voltage-resistant memory module of the S7-200 CPU 224XP. The following information is stored under the designation of the wire-wound coil:

• Wire size

• Length of the pieces of wire to be cut of the corresponding job

• Material capacity of the wire-wound coil (initial value)

• Production ID of the job (initial value)

Prior to production, the wire-wound coil to be used for the production has to be selected via the TP177micro Touch Panel.

While feeding in the wire, a block that runs in the S7-200 CPU 224XP controls the G110 frequency inverter via the analog interface in such a way that the wire comes to a standstill after passing an inductive sensor and that the positioning axis is thus homed.

An HTL encoder reports the traveled distance of the axis to the S7-200 CPU 224XP in the form of pulses.

After entering the production ID and the number of pieces of wire to be produced using the TP177micro Touch Panel, a block running in the S7-200 CPU 224XP causes the frequency inverter to move the positioning axis by the desired wire length. Via a digital output signal, the S7-200 CPU 224XP subsequently controls a cutting device that cuts the wire.

This operation is repeated according to the entered number. After completion or premature termination of the job the following production parameters are stored in the voltage-resistant memory module of the S7-200 CPU 224XP.

• Time and date stamp of the production job

• Diameters of the wire rods

• Length of the pieces of wire

• Quantity of the residual material on the coil

• A unique production ID for the job

• Actual number of cut wire rods

The thus buffered information can be read out via a serial link, for instance with the aid of a PC/PPI cable and the S7-200 Explorer STEP7 Micro/WIN tool and stored as a csv file.

When selecting a new wire-wound coil via the TP177micro Touch Panel, the remaining capacity of the previous coil that has been permanently updated during production is written to the recipe of the relevant material

Page 7: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Fields of Application and Benefits

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 7/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

data. Since the recipe is also stored in the voltage-resistant memory module of the S7-200 CPU 224XP, the remaining capacity of the old wire-wound coil is again available when it is reused in the cutting device.

If the remaining capacity of the wire-wound coil falls below a specific value, a warning is displayed on the TP 177micro Touch Panel. And if the amount of wire is not sufficient for the planned job, the entered number of wire rods is reduced to the possible number and this fact is also reported via the TP.

Figure 1-2

6

4

85

321

s

HzHz12345678910

ON123

PFMJ

OG

s SIMATIC PANEL

TOU

CH

TP 177 micro S7-200 CPU 224XP

SINAMICS G110 with BOP Asynchronous motor with HTL encoder

LOGO! Power SIMATIC PXI inductive sensor

1 2 3

4

5

6

7 NC contact

7s

WINDOWS-based system

8

Page 8: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Fields of Application and Benefits

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 8/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

1.3 Fields of application

The Micro Automation Set is particularly suitable for industrial applications requiring the positioning of objects. The product combination in conjunction with the software library enables a cost-effective positioning solution, for example, in the following applications:

• Cutters, for example, for pipes

• Conveyors

• Feeders

• Lifting stages

• Rotary tables

• Hoisting devices

1.4 Benefits

• Simple solution for positioning a linear axis (horizontally or vertically) or a rotary axis.

• Clearly reduced engineering overhead by providing a command library for STEP 7 Micro/WIN.

• The use of a particularly sturdy control algorithm ensures that a manual optimization of the position control is not necessary even if there are strong load fluctuations.

• Realization of the drive task without comprehensive control engineering know-how. The SIMATIC S7-200 takes the position control.

• Engineering and commissioning of the S7-200 and the position controller with only one software tool: STEP 7 Micro/WIN.

• Cost-effective and high-performance solution with SINAMICS G110.

• In addition to your control problem, the S7-200 can also solve multiple automation problems.

• Visualization and control of the process via the TP 177micro Touch Panel.

Page 9: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuration

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 9/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

2 Configuration

Connection diagram Figure 2-1

L1NPE

L1 L2 L3

U1V1W1

1 2 3 4 5 6 7 8 9 10

1M 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 2M 1.0 1.1 1.2 1.3 1.4 1.5 M L+

1M 1L+ 0.0 0.1 0.2 0.3 0.4 0.5 2M 2L+ 0.5 0.6 0.7 1.0 1.1 PE M L+M I V M +A +B

L+M

L+M

2

3

1

wht blu red blk

Connector of the encoder cablecontact side (not solder side)

1

2

PRO

FIB

US

cabl

e

PC/P

PI o

rU

SB/P

PI c

able

WINDOWS-based system for configuring and data archiving

AB K

J

HM

GFE

D

CL

SIMATIC S7-200 – inputs: Via the preassembled encoder cable, the rotary pulse encoder is connected to the HSC4 high-speed counter that uses the I0.3 and I0.4 inputs. The D-sub connector of the encoder cable was removed.

The signal cable of the inductive sensor is connected to I0.6.

I0.0 was used for the OFF button.

SIMATIC S7-200 – outputs: The inverter with analog input receives its frequency setpoint via the analog voltage output of the controller (terminals M, V). A shielded cable has to be used. On the inverter, the analog signal is applied to terminal 9 and the associated analog reference ground is applied to terminal 10 of the signal interface. The analog reference ground and the ground of the 24V supply are jumpered on the inverter (terminals 7, 10).

Page 10: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuration

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 10/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

The “start motor” command is applied at digital output Q1.0 of the controller. It is connected to terminal 3 of the inverter’s signal interface.

The “reversal” signal is applied at digital output Q1.1 of the controller. It is connected to terminal 4 of the inverter’s signal interface.

SINAMICS G110 frequency inverter In primary circuit, the connection of the frequency inverter to the 230V mains is a single-phase connection.

The asynchronous motor operated in delta connection is connected in secondary circuit.

NOTICE Please observe that the phase angle of the encoder pulses A and B correlates with the phase angle L1, L2 and L3 of the motor supply. If correct positioning is not possible, the problem can possibly be solved by reversing the encoder tracks or two motor phases. If the motor does not run in the desired direction, encoder tracks and two motor phases have to be reversed.

24V supply The 24VDC power supply of the devices is provided by a LOGO! Power 1.3A.

Protection An RCBO Type A is used for protection.

Page 11: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Hardware and Software Components

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 11/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

3 Hardware and Software Components

Products Table 3-1

Component No. MLFB / order number Note

RCBO 1 5SU1154-7KK06 LOGO! Power 24V/1.3A 1 6EP1331-1SH02 SIMATIC S7-200 (CPU 224XP)

1 6ES7214-2BD23-0XB0

TP 177micro Touch Panel 1 6AV6640-0CA11-0AX0 SINAMICS G110, frequency inverter

6SL3211-0AB12-5UA1

SINAMICS G110, frequency inverter with integrated EMC filter

1 6SL3211-0AB12-5BA1 Alternatively

Low-voltage asynchronous motor

1 1LA7070-4AB10-Z H57 Motor with rotary pulse encoder, 1024 pulses per revolution

Encoder cable for rotary pulse encoder

1 6SX7002-0AN30-1AC0 Remove D-sub connector!

SIMATIC PXI350 INDUCTIVE SENSOR 40X40MM

1 3RG4141-3AB01

Pushbutton, red, 1NC 1 3SB3203-0AA21 MC 291 MEMORY MODULE, 256 KBYTES

1 6ES7291-8GH23-0XA0

Accessories Table 3-2

Component No. MLFB / order number Note

Basic Operator Panel (BOP) for SINAMICS G110

1 6SL3255-0AA00-4BA1

Page 12: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Hardware and Software Components

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 12/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Configuration software/tools Table 3-3

Component No. MLFB / order number Note WinCC flexible micro 1 6AV6610-0AA01-2CA8 Step 7 Micro/Win 1 6ES7810-2CC03-0YX0 PC/PPI cable

6ES7901-3CB30-0XA0

USB/PPI cable 1

6ES7901-3DB30-0XA0

Alternatively; can also be used for loading the TP177 micro

SINAMICS MICROMASTER SIZER

1 6SL3070-0AA00-0AG0 Optional

Page 13: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 13/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

4 Principle of Operation

4.1 Introduction to positioning

What does “closed-loop controlled positioning” mean? In the context of this application, the following definitions can be provided:

When “positioning”, an electrically driven component of a device or plant approaches a defined local point or angle by means of a linear or rotary motion or the component is moved by the distance Δs or the angle Δφ.

When the positioning is “closed-loop controlled”, the motion is performed in a closed control loop in which path and velocity (motor speed) are the controlled variables. The disturbance variables are differing load torques.

The SIMATIC S7-200 transfers the “velocity” controller output to the frequency inverter as an analog voltage that is interpreted by the frequency inverter as a setpoint frequency according to its parameterized V/f characteristic. Considering the slip of the asynchronous motor depending on the load torque, a specific speed is set. According to this speed, the component to be positioned travels a smaller or larger number of path or angle increments. They are detected by the rotary pulse encoder that is located directly on the motor shaft and supplied to the controller via its high-speed counter inputs.

From this information and including the setpoint values “position”, “positioning speed” and “acceleration (torque)”, a control algorithm counting the encoder pulses calculates the necessary “velocity” controller output. This results in a velocity profile whose processing finally leads to an exact positioning. Figure 4-1

Controller Controlled system

Frequency inverter, asynchronous motorPosition

VelocityAcceleration (torque)

Analog value0 – 10V

Manipulated value

Reference variable

Load torqueDisturbance variable

Controlled variable

PositionVelocity

Encoder pulses

Control withMicroPos blocks

What is the difference between absolute and relative positioning? When absolute positioning is used, you directly specify the target position to be approached. When relative positioning is used, you enter a path length by which the component is to be moved.

Page 14: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 14/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

To enable absolute positioning, it is required that the zero point of your travel path (home position) be defined once in advance. The counter with which the pulses of the rotary pulse encoder are counted is adjusted to the position of the physical axis, .i.e. it is set to a defined value (preferably 0) at a defined local point. Homing is not necessary for relative positioning. Figure 4-2: Example of absolute/relative positioning

0

-100

-200 100

200

-300 30

0

400

500

Travel range (mm)

Home position

Target positionSource position(not relevant)

Absolute positioning

Target position

+600mm

Source position

Relative positioning

What is the difference between a linear and a rotary axis? • Linear axis:

A linear axis is particularly suitable for linear motions in the horizontal or vertical plane. For the distance traveled during positioning, the blocks assume the “length” dimension. Depending on the velocity or ratios of dimensions, the user applies the corresponding parameters (position, velocity, etc.), for example, to mm, cm or inch.

Page 15: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 15/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

An important parameter of the linear axis is the correlation between the physical variable “distance traveled” and a motor or rotary pulse encoder revolution. The parameter thus considers gear, belt, spindles, etc. that eventually convert the rotary motion to a linear motion. Figure 4-3: Example of a linear axis, distance traveled

One revolution = 1024 encoder pulses

40mm

Shortest detectable travel path = 40mm / 1024 ≈ 0.039mm

The Map_Ind_Lin library is used for the linear axis. The names of all blocks have “Lin_” as a prefix.

• Rotary axis: The rotary axis – also referred to as a “modulo axis” – designates a type of positioning where a rotary motion is repeated after each completed motional sequence. Taking this fact into account, the position value of the drive-end, moved component is specified in angular degrees 0 ≤ φ < 360.0 and reset to 0 after each “rotation”.

For the unique detection of the absolute position, the rotary axis additionally features a rotation counter that is adjusted each time the axis is moved – irrespective of whether the positioning is absolute or relative or whether the rotary axis is moved in jog mode. Without homing, the rotation counter is set to 0 when restarting the controller. With homing, the rotation counter is set to a value that corresponds to the specified reference angle.

If you specify, for instance, an angle of +740° for the physical local point x0 when homing, the rotation counter has the value +2 in x0.

An important parameter of the rotary axis is the correlation between the physical variable “angle traveled” and a motor or rotary pulse encoder revolution. The parameter thus considers gear, belt, spindles, etc. that finally represent the ratio.

Page 16: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 16/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Figure 4-4: Example of a rotary axis, angle traveled

One motor revolution = 1024 encoder pulses

Smallest detectable angle of revolution= 28° / 1024 ≈ 1′ 38″

φ = 28°

The following specifics have to be considered for a rotary axis:

– Absolute positioning with preset direction of rotation At the drive end, the target position has to be approachable with a maximum of one “rotation” (φ < 360.0°). Larger angle settings cause a termination of the job. Negative angle settings are also not permissible. The direction of rotation is to be specified by an – compared to a linear axis – additional direction parameter.

Figure 4-5: Example of a rotary axis, absolute positioning

Home position Source position

Target position

Positioning to 270° in negative direction

Home position Source position

Target position

Positioning to 270° in positive direction

– Absolute positioning on the shortest path The positioning is performed as in the above case. The software

Page 17: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 17/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

calculates the shortest path to the target and selects the direction of rotation accordingly.

– Relative positioning Both angle settings > 360.0° and negative angles are possible. Figure 4-6: Example of a rotary axis, relative positioning

Source position

Target position

Positioning by 630° in positive direction

The Map_Ind_Rot library is used for the rotary axis. The names of all blocks have “Rot_” as a prefix.

What is a travel profile? Depending on the purpose, travel profiles describe various characteristics (path, velocity, acceleration, moment, power, etc.) that describe a desired motional sequence. The time or the path is mostly plotted on the abscissa.

The following applies to a positioning operation by means of the MAP Ind blocks:

• Acceleration is always performed from zero and the component is always decelerated to a standstill.

• The steepness of acceleration ramp and deceleration ramp is identical

• The controlled variable for the required acceleration/deceleration is the moment.

Page 18: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 18/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Figure 4-7: Travel profile

Velo

city Time

Path

Time

Forwards/upwards

Backwards/downwards

Torq

ue

Time

Horizontal axis

Vertical axis

Generator operation

For system optimization, the two “MAP_Ind_...” libraries offer a “…_Com_Monitor” block with which alternatively the dependencies M(t), v(t) and s(t) can be displayed as travel profiles in STEP 7 MicroWin.

What is the difference between a horizontal and a vertical axis? While the “horizontal axis” merely requires that the forces of acceleration/deceleration and the friction forces be considered parallel to the direction of motion for a mass to be moved, the gravitational force of the mass to be moved has to be additionally considered for the vertical axis. This requires the provision of a larger torque from the inverter to achieve the same accelerating/decelerating torques as for the horizontal axis. Figure 4-7 shows a qualitative representation of the torque characteristics of the horizontal and vertical axis for identical accelerations.

Page 19: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 19/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Under which circumstances does the motor become the generator? Whenever energy stored in the system is to be degraded, the motor becomes the generator. The following energies have to be mentioned:

• Potential energy (due to a suspended load)

• Kinetic energy (due to moving masses)

Energy released when lowering a load or decelerating a flywheel that would drive the motor from the mechanical end has to be degraded by the inverter as power loss. The inverter copes with smaller powers without additional measures. Larger powers require braking resistors or power recovery has to be provided. Figure 4-7 shows the time intervals of generator operation. The hatched areas under the torque characteristics are proportional to the energy to be degraded.

4.2 Block libraries for moving linear and rotary axes

Overview of available positioning blocks Figure 4-8

Lin_Init_horizontal

Lin_Init_vertical

Lin_MoveJog

Lin_Home

Lin_MoveAbs

Lin_MoveRel

Lin_StopMotion

Rot_Init

Rot_MoveJog

Rot_Home

Rot_MoveAbs

Rot_MoveRel

Rot_StopMotion

Lin_Com_Monitor Rot_Com_Monitor

Lin_Control Rot_Control

MAP_Ind_Lin libraryfor linear axis

MAP_Ind_Rot libraryfor rotary axis

The library description also included in Micro Automation Set 1 provides a detailed block description. The MAP_Ind_Lin library for linear axes is used for this application. The following sections briefly describe its blocks.

Page 20: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 20/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Task of the “Lin_Init_horizontal” block This application describes a horizontal material transport. For this reason, the “Lin_Init_horizontal” block is used here. The initialization block combines those input and output parameters that refer, so to speak, to all further blocks of the library and that are used by the positioning’s control algorithm. Furthermore, the user-specific units of measurement are standardized in this block.

Motor characteristics, absolute upper limits for velocity and torque1 and the transfer factor indicating which feed corresponds to the linear motion of a motor revolution are mainly entered in “Lin_Init_horizontal”.

“Lin_Init_horizontal” has to be processed once before the remaining blocks – which have to be called cyclically – are executed for the first time. Trigger “Lin_Init_horizontal” with SM0.1.

Task of the “Lin_MoveJog” block Using the “Lin_MoveJog” block, you realize manual mode. The block features two bit inputs for jog mode (“JogPos” and “JogNeg”). Accelerating/decelerating torque and a limit velocity can be parameterized at the block.

Task of the “Lin_Home” block To enable absolute positioning, the three-dimensional travel path has to be synchronized with the controller’s position counter. This is achieved by assigning a specific value to a defined point of your travel path (= home position). This is done during runtime of the automation program. “Lin_Home” offers two referencing variants:

• Searching for the home position For searching the motor is started with “Execute” block parameter =1 and the required direction of rotation (“Direction” parameter = ±1). If the moving component is detected by a sensor at the user-defined home position (“RPS” signal), a specific reference value (“Home_Position”) is assigned to the current position with this event. The detection of the sensor is performed via its positive or negative edge. The sensor can, for example, be an inductive proximity switch or a photoelectric barrier. Your user program has to be designed in such a way that the sensor is always approached from the same direction when homing to eliminate its detection width.

In this “wire cutting machine” application example, homing is performed when feeding in the wire or before the first cutting operation as shown in the graphic representation below. The distance “proximity switch – cutter” (with minus sign) is entered as a position value of the home

1 Upper limits are not even exceeded during operation if higher values are parameterized in the blocks initiating a motion.

Page 21: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 21/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

position. Thus the current wire position = 0mm if the wire tip is located exactly at the cutter.

Figure 4-9: Home position search

Wire-wound coil Cutter

Proximity switch forwire detection

Detection width

v(t)

s(t)

Home position

RPS signal active

Start of homing(if feed-in has already been performed)

Start of homing(if feed-in has not yet been performed)

End of homing

1)

The offset to the home position at the end of homing is known to the system and will beconsidered in the next positioning (first wire cut after homing).

1)

• Setting the home position. When setting the home position, the motor is stopped. 0 has to be specified for the “Direction” block parameter. If the block detects a positive edge at “Execute”=1 at the “RPS” input parameter, the current position is set to a parameterizable reference value (“Home_Position”).

In the “wire cutting machine” application example described in this document, the home position is set to the value 0 whenever the wire tip is located exactly at the cutter after a completed wire cut.

For the home position search, accelerating/decelerating torque and a limit velocity can be parameterized at the block.

Task of the “Lin_MoveAbs” block Initiated by a positive edge at the “Execute” input parameter, the motor starts from the current position for a closed-loop-controlled approach to the end point specified via the “Position” input parameter. A prerequisite for absolute positioning is previous homing with the “Lin_Home” block.

Accelerating/decelerating torque and a limit velocity can be parameterized at the block.

Page 22: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 22/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Task of the “Lin_MoveRel” block Initiated by a positive edge at the “Execute” input parameter, the motor starts at the current position to approach the point whose distance from the starting point is specified by the “Distance” input parameter on a closed-loop-controlled basis. Previous homing using the “Lin_Home” block is not required in this case.

Accelerating/decelerating torque and a limit velocity can be parameterized at the block.

Task of the “Lin_StopMotion” block “Lin_StopMotion” is used to stop a currently active motion – irrespectively of the specific MAP Ind block that triggered it. The block offers two variants for stopping:

• Stopping via the “AUS3” inverter digital input. The steepness of the deceleration ramp is set when parameterizing the inverter. The stop is triggered by a positive edge at the “Execute_Off3” input parameter.

• Stopping via the “Lin_StopMotion” block. This variant is used in this application. The steepness of the deceleration ramp is set by the “Decel_Torque_Ramp” input parameter of the block. The stop is triggered by a positive edge at the “Execute_Ramp” input parameter.

It is not only possible to use both variants for stopping alternatively, they can also be used together in one program.

The block monitors the deceleration times (separate monitoring of both variants for stopping). The upper limits can be parameterized. When the limits are violated, the “Time_Exceeded” output bit parameter is set.

Task of the “Lin_Control” block • The block uses a status word to inform the user on all system states

and limit value violations:

– Motor stopped

– Maximum moment reached

– Axis not synchronized

– Pulse counter overflow

– Direction conflict (rotary pulse encoder ↔ motor phase angle)

– Following error exceeded

– System not initialized

• The value of the current position is available to the user in the “Act_Position” output parameter.

Page 23: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 23/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

• Whenever the motor is stopped from the perspective of the MAP Ind blocks, a “Brake” bit output is set to a logic “1”. For example, a holding brake or the pulse enable for the inverter can then be controlled.

Task of the “Lin_ComMonitor” block In the commissioning phase the “Lin_ComMonitor” block supports the user in optimizing the dynamic response. The block alternatively records (parameterizable)

• moment

• velocity

• position

in real time to be able to subsequently represent their time characteristics in the STEP7 Micro/Win trend display.

A positive edge at the “Start” bit input parameter starts the recording. Where the data is to be stored is communicated to the block via the “pTableStart” input parameter by means of a pointer. The block records 249 REAL values in the 8ms grid. In the trend display, subsequently view the “Out” output parameter of the block.

Note A parameter description of the MAP Ind blocks is available not only in the library description of this Micro Automation Set, but also in STEP7 Micro/WIN directly as a comment in the relevant protected MicroPos block.

4.3 Configuring the G110 frequency inverter

Parameterization steps Due to the universality of the SINAMICS frequency inverters, the adaptation to a specific application requires that the inverter be parameterized. This setting procedure is facilitated by the fact that many applications can be operated with the factory default settings if quick commissioning has previously been performed. If the condition at delivery from the plant of the inverter you are using has been changed, it can be reset to the factory default settings without difficulty. If quick commissioning is set, only the parameters whose adaptation is absolutely necessary can be selected during the parameterization. To meet the specific requirements of this application, application-specific parameterizations are necessary after the reset to factory default settings and after quick commissioning. Finally, save the values to the EEPROM of the inverter and, if necessary, save the entire parameterization to the BOP. This enables you to reload the parameters to the inverter at any time if required without having to reenter them or to transfer the parameters to other identical inverters.

Page 24: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 24/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

To parameterize the inverter, we recommend the following procedure: Table 4-1

No. Step

1. Resetting to factory default settings (if condition at delivery from the plant has been changed)

2. Quick commissioning. 3. Application-specific parameterizations. 4. Saving parameters to the inverter’s EEPROM. 5. Transferring parameter set to BOP for reuse.

Changing parameters All steps listed above are merely sequences of parameter settings. They can be performed, for example, using the Basic Operator Panel (BOP) that is simply plugged onto the inverter2. Figure 4-10

To change a parameter via the BOP, proceed as follows:

2 The BOP can be plugged in any inverter mode.

Page 25: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 25/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Operator input sequence step Note

1. Go to parameterization mode.

2. Select the parameter to be changed.

3. Display the parameter value.

4. Change the parameter value.

When you press FN, you can change each decade individually.

5. Apply the value.

These operations have to be performed for each parameter.

6. Select the display (0000).

7. Exit parameterization mode.

Documents for the SINAMICS G110 The following documents are available for the SINAMICS G110: Table 4-2

Document ID number:

Getting Started Guide 21696936 Operating Instructions 22102965 Parameter List 20977026

4.4 Optimizing the positioning operation

4.4.1 Optimization with regard to the moment of inertia

Relating to all MAP Ind blocks, the Inertia parameter (moment of inertia) influencing the system dynamics that cannot be easily deduced from motor catalogs or mechanical system requirements like all other input values can be either calculated or determined empirically. The calculation of the moment of inertia of the entire moved system component required by the Lin_Init_horizontal block as an input parameter is difficult. The following sections describe a way to determine the moment of inertia empirically.

Page 26: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 26/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Start value for the moment of inertia Experience has shown that the tenfold mass inertia of the motor is a good start value. Before commissioning, enter this value for the Inertia parameter at the Lin_Init_horizontal block. For the motor’s mass inertia, please refer to the motor catalog. Accordingly, a value of 0.00052kgm2 results for the motor from Table 3-1.

Optimization process with the aid of the “Lin_ComMonitor” block To assess the dynamic response of your system, the graphical representations of the trend curves v(t) and s(t) are alternatively suitable. Consider in particular the end of the positioning operation. If the moment of inertia is set optimally (Figure 4-12), neither distinctive overshoot (Figure 4-11) nor a “gradual vanishing” (Figure 4-13) of the corresponding curve should occur. Figure 4-11

v(t)

s(t)

Overshoot!

Overshoot!

Figure 4-12

v(t)

s(t)

Optimum characteristic

Optimum characteristic

Page 27: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 27/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Figure 4-13

v(t)

s(t)

Gradual vanishing!

Gradual vanishing!

The time characteristic v(t) is also suitable for controlling or optimizing the velocity. It shows whether the velocity parameterized at the relevant block is actually reached.

4.4.2 Optimization of the travel profile

The travel profile is essentially defined by the technological application and an energetic optimization. Determining factors are

• the time within which the positioning operation has to be completed,

• acceleration and deceleration whose upper limits are determined by the motor performance, the application’s mechanical system and the actual process and

• the power demand of the application.

The travel profile can be adjusted to the application as follows: Figure 4-14

t

v(t)

Slope is determined by... • rated torque of the motor•Accel_Torque or Torque_Limit block parameter (0...200%)

Maximum velocity is determined by...•Velocity_Limit block parameter (unit of length/s)

Page 28: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Principle of Operation

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 28/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

The absolute maximum velocity of the linearly moved component eventually depends on the rated speed relating to the motor frequency. Since the 4-pole motor of this application can be controlled by the inverter with a maximum of 100Hz, its highest speed is 2700 min-1. This speed – converted to the linear motion of the application – results in the maximum velocity that can be limited with the Velocity_Limit parameter.

The Accel_Torque or Torque_Limit block parameters for limiting the motor torque are indicated as percentages of the rated torque. A torque of up to 200% can be used for a 4-pole motor.

The example in the figure below shows four possible travel profiles that all position over the same distance, i.e. the integrals over the curves v(t) from the starting point to the end point of the motion are identical. Friction losses are negligible.

Figure 4-15: Different travel profiles for the same positioning

t

t

t

v(t), M(t)

v(t), M(t) v(t), M(t)

t

v(t), M(t)

M = 200%

vmax(at 100Hz)

vmax/2

M = 100%

vmax/2

vmax/2

M = 50%

• Green profile – Maximum motor utilization – Minimum positioning time – Maximum power consumption

• Yellow, blue and red profile – Motor not fully utilized – Positioning times extend from yellow to red – Power consumption corresponds to half the green profile

Page 29: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 29/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

5 Configuring the Startup Software

5.1 Preliminary remark

For the startup, we offer you software examples with test code and test parameters as a download. The software examples support you during the first steps and tests with your Micro Automation Sets. They enable quick testing of the hardware and software interfaces between the products described in the Micro Automation Sets.

The software examples are always assigned to the components used in the set and show their basic interaction. However, they are not real applications in the sense of technological problem solving with definable properties.

Note At this point, it is assumed that the necessary configuration software has been installed on your development system (PG, PC, laptop computer) as shown in Table 3-3 and that you are familiar with handling this software.

The hardware according to Table 3-1 is mounted, wired as shown in Figure 2-1 and the power supply of all involved components is ensured.

5.2 Downloading the startup code

The software example is available on the HTML page from which you have downloaded this document. Table 5-1

No. File name Content

1 Set1_s7-200_V1d0_en.zip STEP 7 Micro/WIN project for the wire cutting machine (….mwp file)

2 Set1_WinCCflex_Visu_V1d0_en.zip WinCC flexible project for the TP (….hmi and ….LDF files).

3 map_ind_V1.19.zip Libraries of the drive blocks for linear and rotation angle positioning (map_ind_lin.mwl and map_ind_rot.mwl files)

Note The map_ind_rot.mwl library is not used in the software example. It is only offered for download to complete the picture.

Page 30: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 30/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

5.3 Configuring the CPU 224XP PLC

Step-by-step instructions for configuring the controller Table 5-2

No. Instruction Remark

1. Connect a free COM port or a USB port of the development system to port 0 of the S7-200 controller. Use the PC/PPI or USB/PPI cable for the connection. Use the following switch positions for the PC/PPI cable:

PC/PPI or USB/PPI cable

Development system

2. In “PG/PC Interface”, select

“Start>Settings>Control Panel” and make the following settings: • Access point of the application:

Micro/WIN PC/PPI cable(PPI) • Transmission rate:

19.2kbps • Local connection: COM or USB

(depending on the cable) • Advanced PPI deactivated Multi-master network deactivated

Instead of using the control panel, the interface can also be selected from STEP 7 Micro/WIN by selecting “Set PG/PC Interface”.

3. Start STEP 7 Micro/WIN and open the mwp project file.

4. If you are using a motor type deviating from table 3-1, you have to adjust the input parameters of the Lin_Init_horizontal block (= rated motor data). The block is located in network 1 of the MicroPOS subprogram.

5. Check whether the values of the

parameters declared in the “USER” data area are compatible with the mechanical system of your wire cutting machine.

The following table provides an explanation of the “USER” data area (Table 5-3).

1 2 3 4 5 6 7 8 0 0 0 0 1 0 0 0

Page 31: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 31/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Instruction Remark

6. Select “File>Download…” or use the corresponding icon to transfer the project to the S7-200 controller. In the transfer dialog box, ensure that the • program blocks, • data blocks, • system data and • recipes are transferred.

7. Select “PLC>RUN” or the corresponding icon to set the S7-200 controller to “RUN” mode.

8. • In the operation tree, right-click “Libraries” and open the dialog box for adding/deleting libraries.

• Add the drive blocks for linear positioning to the library. Follow the explanations in the respective window.

It is only necessary to add blocks to the library if you want to add library blocks that have previously not been included in the program code to the user program. In this example, these are, for instance, the “Lin_Init_vertical” or “Lin_MoveAbs” blocks.

Parameters of the wire cutting machine On the one hand, all technological parameters of the wire cutting machine are declared in the USER data block; on the other hand, they also exist in the “Parameters” status table for commissioning purposes. Before the first commissioning check whether the values – in particular the velocities and torques – are suitable for your mechanical system. The following table explains the parameters.

Page 32: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 32/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Table 5-3

Parameter Explanations

Technological parameters dist_BERO_cutter: VW32 Distance between proximity switch and cutter (mm).

The proximity switch is to be installed between the drive wheels and the cutter. dist_BERO_cutter has to be entered as a negative value.

dist_BERO_cutter

Schneidemechanismus(cutter)

induktiver Näherungsschalter

absolute Position 0+ -

cutter_down_time: VW34 Indicates how long the cutter remains in the cutting position

(value x 10ms). The cutter knows two logic states: • Parking position (at top, control with FALSE) • Cutting position (at bottom, control with TRUE)

cut_delay: VW40 In automatic mode, the feed of the next wire rod is started only after this delay (value x 10ms). This is to prevent that the feed starts before the cutter has returned to parking position. The cutter has no end position detection.

Other parameters coil: VW114 Preset coil (1-4) whose recipe data is used for operation

after a data block transfer to the controller. minimum: VD76 If the remaining capacity of the coil becomes less than this

limit value(m), a warning is output on the TP. Velocity parameters

V_Ref: VD1004 Homing velocity (mm/s) Jog_slow: VD1008 Slow jog mode velocity (mm/s) Jog_fast: VD1012 Fast jog mode velocity (mm/s)

Page 33: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 33/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Parameter Explanations V_Pos: VD1016 Positioning velocity (mm/s)

Torque parameters3 T_Ref: VD1028 Accelerating/decelerating torque for homing (%) Torque_Jog_slow: VD1032 Accelerating/decelerating torque for slow jog mode (%) Torque_Jog_fast: VD1036 Accelerating/decelerating torque for fast jog mode (%) T_Pos: VD1040 Accelerating/decelerating torque for positioning (%) T_Stop: VD1048 Decelerating torque when stopping by means of stop

button on the TP or hardware stop button during homing or a positioning operation (%).

Parameters for the Lin_Init_horizontal initialization block Torque_Limit: VD1100 Maximum permissible accelerating/decelerating torque (%).

The torque parameter values of the other drive blocks always have to be smaller than/equal to this value. Otherwise, the relevant drive block reports an error.

Velocity_Limit: VD1108 Maximum permissible velocity (mm/s). The velocity parameter values of the other drive blocks always have to be smaller than/equal to this value. Otherwise, the relevant drive block reports an error.

s_per_rev: VD1112 The feed of the wire per motor revolution has to be entered here (mm/rev). For a positioning accuracy < 1mm, s_per_rev < 40 mm/rev should apply.

Inertia: VD1116 Moment of inertia; see chapter 4.4

3 The percentage data of the torque refers to the motor’s rated torque that is listed in the motor data sheets and that the MAP Ind blocks calculate from the further motor rating parameterized at the “Lin_Init_horizontal” block. Entries from 0…200% are possible for the torque.

Page 34: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 34/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

5.4 Preparing the archiving function

Table 5-4

No. Instruction Remark

1. Connect a free COM port or a USB port of the development system to port 0 of the S7-200 controller. Use the PC/PPI or USB/PPI cable for the connection. Use the following switch positions for the PC/PPI cable:

PC/PP or USB/PPI cable

Development system

2. In Windows, start

S7-200 Explorer by selecting “Start>SIMATIC>S7-200 Explorer” or by double-clicking the corresponding icons.

3. Click the S7-200 CPU and select the 256 KB memory module. In the right window, right-click “DAT Configuration 0(DAT0)” and select “Create Shortcut”. (The “Open File on Upload” option has to be deactivated)

4. A shortcut to the “Data-Log” file in the 256

KB memory module is now automatically created on the desktop.

5. On the desktop, create a link to the

Micro/WIN installation path (default: “Drive”: Program Files\Siemens\MicroSystems\Data Logs).

The logged data from the memory module

is moved to the path as a csv file

when double-clicking .

1 2 3 4 5 6 7 8 0 0 0 0 1 0 0 0

Page 35: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 35/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

5.5 Loading the TP 177micro Touch Panel

Table 5-5

No. Instruction Remark

1. Connect a free COM port or a USB port of the development system to the RS485 interface of the TP 177micro. Use the PC/PPI cable or the USB/PPI cable. On the PC/PPI cable, set a baud rate of 115200 baud. This corresponds to the following switch positions:

Development system

PC/PPI or USB/PPI cable

TP 177micro

2. Start WinCC flexible and open the hmi project file.

3. Call the transfer dialog box by selecting “Project>Transfer>Transfer Settings…” or by using the respective icon.

4. Adjust the transfer settings according to the cable you are using. When using the PC/PPI cable, select the used COM port of your development system and set the baud rate to 115200 baud.

5. Set the TP 177 Micro to Transfer mode. This is done by selecting the “Transfer” button after the “bootloader” sequence. The download of the WinCC flexible project can be started when a “Transfer….” dialog box is displayed on the TP.

6. Start the project file transfer.

7. Use the PROFIBUS cable to connect the RS485 interface of the touch panel to port 1 of the S7-200 controller.

S7 -224 XP CPUS7 -224 XP CPU TP 177micro

PROFIBUS cable

1 2 3 4 5 6 7 8 1 1 0 0 0 0 0 0

Page 36: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 36/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

5.6 Parameterizing the G110 frequency inverter

For the procedure, please refer to chapter 4.3. The following section lists only the parameters you have to change with regard to the factory default settings for this application example. For the parameterization, please follow the order specified in the table below.

Parameter changes in the SINAMICS G110 Table 5-6

Parameter

No. Value Remark

Resetting to factory default settings P0010 30 Commissioning parameter: Factory setting P0970 1 Start of the reset of all parameters to default values

Quick commissioning P0003 3 Access level: Expert P0010 1 Commissioning parameter: Quick commissioning P0305 1.34 Rated motor current (A) (for delta connection), see rating plate P0307 0.25 Rated motor power (kW), see rating plate P0308 0.78 Rated power factor of the motor (cos φ), see rating plate P0310 50 Rated motor frequency (Hz) for the specific motor data, see rating plate P0311 1350 Rated motor speed (min-1), see rating plate P1082 100.00 Maximum frequency (Hz) (100Hz for 4-pole motor, 50Hz for 2-pole motor) P1120 0.00 Acceleration time (determined by the controller) P1121 0.00 Deceleration time (determined by the controller) P3900 1 End of quick commissioning (among other things, resets P0003 to 1)

Application-specific parameterizations P0003 3 Access level: Expert P0760 200.00 y2 value ADC scaling (%) (100% for 2-pole motors) P1240 0 Configuration of Vdc controller: Vdc controller disabled

Saving parameters to the inverter’s EEPROM P0971 1 Transfer of values from RAM to EEPROM

Transferring parameter set to BOP for reuse P0010 30 Commissioning parameter: Factory setting P0802 1 Parameter transfer from SINAMICS → BOP P0003 1 Access level: Standard

Page 37: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Configuring the Startup Software

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 37/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

NOTICE If you are using a motor type that differs from the ones listed in Table 3-1, the following parameters have to be additionally considered during quick commissioning:

• P0304 rated motor voltage (V) (for delta connection), see rating plate • P0335 rotor cooling: 1 = self-ventilated, 2 = separately ventilated In this application example, the values of these parameters are already covered by the factory default settings and thus not listed in the above table.

Parameter transfer from BOP → SINAMICS G110 When you have transferred the inverter parameter set to the BOP as shown in Table 5-6, you can reload it from the BOP to the inverter very easily if required or distribute it to other inverters.

Table 5-7

Parameter

No. Value Remark

Transferring parameter set from the BOP to the frequency inverter P0003 3 Access level: Expert P0010 30 Commissioning parameter: Factory setting P0803 1 Parameter transfer from BOP → SINAMICS

Saving parameters to the inverter’s EEPROM P0971 1 Transfer of values from RAM to EEPROM P0003 1 Access level: Standard

Page 38: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 38/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

6 Live Demo

Overview To facilitate understanding, the functions and features of Micro Automation Set 1 are shown in the form of a sample application.

If the components have been correctly configured as described in chapter 5, the program code can be tested. Figure 6-1: Live demo overview

Optimizing the dynamic response

Setting up the wire-wound coils

Feeding in the wire

Producing 10 wire rods with a length of 2m (automatic mode)

Immediate stopping of the feed motion using the stop button of the TP 177micro

Cutting wire rods of variable length (manual mode)

Immediate stopping of the feed motion using the hardware stop button (e.g. emergency stop)

Data logging

Start

End

Basic information on operating the TP 177micro Table 6-1

Definition Example

Input values: Input or input/output fields are designated by a white background. Output values: Mere output fields are marked by a gray background.

Input/output field

Output field

Page 39: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 39/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Definition Example

Grayed out buttons: Buttons with grayed out labeling indicate that the action associated with the button is locked for programming reasons. For example, automatic mode can only be set after the wire has been fed in.

Not grayed out

Grayed out

Navigation buttons: The navigation buttons for changing the screens/statuses are located on the bottom screen edge. The screens are structured as shown on the right. In case of voltage recovery or restart of the controller, the system branches to the “feed in” screen. In the currently selected screen, the background of the navigation buttons is black and they cannot be operated.

settings

recipe admin.

feed in

automatic

manual

production

Automatic mode selected Graphic: A graphic in the TP screens shows the wire cutting machine’s condition of motion.

Standstill

Cut

Feed active(the sectors within the coilsrotate and the wire movesforward.)

Deleting old archive data Delete any old logged data from the memory module and old csv log files before the live demo scenarios.

Page 40: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 40/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Table 6-2

No. Step Remark

1. Double-click .

Memory module is read out and deleted. 2.

Double-click . Directory of csv log files is opened.

3. Delete all csv files in the directory.

The logging was configured in such a way that the log data in the memory module is deleted when reading out the 256 KB memory module in a csv file.

6.1 Setting up the wire-wound coils

Setting up the wire-wound coil means defining the recipe data of the individual material types and selecting the coil to be used for the current operation.

Procedure Table 6-3

No. Step Remark

1. On the TP 177micro, select the “recipe admin.” screen.

2. Use the arrow keys to select the wire-wound coil you want to use. Four data records (recipes) are available.

3. If necessary, change the recipe data of the selected wire-wound coil. Core rod diameter: Merely used as a material characteristic. Its value is not included in any calculation. Core rod length: Indicates the length of the steel rods that are cut in automatic mode when selecting the corresponding recipe. Residual material: Depending on the material consumption, the controller automatically reduces the displayed residual material quantity. It can be overwritten by the user at any time, e.g. when changing the coil. Production ID: Each production job, consisting of n steel rods, is given a production ID. The user enters an initial value the controller automatically increments per job. The initial value must be > 0 since production ID 0 is reserved for manual production.

Page 41: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 41/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Step Remark

4. If required, change the residual material quantity on the coil; when the quantity is less than this value, a message not requiring acknowledgement is triggered on the TP. The limit value of the residual material quantity is independent of the selected wire-wound coil.

Reading and writing the recipe data Each time a wire-wound coil is newly selected, the remaining coil capacity of the previous coil is saved to its recipe stored in the memory module and the recipe data of the new coil is loaded from the memory module to the controller.

Manual recipe data modifications are transferred to the PLC and written to the memory module with leaving the recipe administration.

6.2 Feeding in the wire

Procedure Table 6-4

No. Step Remark

1. On the TP 177micro, select the “production” screen + “feed in”.

The text “not yet fed in!” flashes. 2. Use the start button (transport wheels start)

and put the end of wire between the transport wheels.

When the end of wire reaches the proximity switch, the feed is stopped. The flashing text changes to a permanent display of “fed in!”. From now on, the current feed is also always displayed on the top of the screen.

Page 42: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 42/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Display of the current feed The current feed is the distance between the wire tip and the cutter. Since the proximity switch – referring to the normal conveying direction – is located in front of the cutter, the value of the current feed after completing the feed-in operation is negative and slightly smaller than the distance between the proximity switch and the cutter. When cutting the first wire rod to length in automatic mode, the already existing negative feed resulting from the feed-in operation is considered.

Repetition of the feed-in operation If a feed-in operation is to be performed when the proximity switch is already occupied by the wire – this can, for instance, be the case after power off/on of the controller – the drive wheels start backwards when pressing the start button. If the proximity switch then detects the start of the wire (negative edge), it is reversed and stopped when the wire tip is detected again (positive edge).

6.3 Automatic mode

6.3.1 Production of 10 wire rods with a length of 2m

Procedure Table 6-5

No. Step Remark

1. Go to automatic production and enter 10 for the “number of core rods”. Subsequently, start the production using the start button. The distance between steel rod tip position and cutter position is always displayed as current feed (here -198mm). In this case, the first steel rod is thus moved forward by 2198mm and then cut.

Page 43: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 43/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Step Remark

2. As soon as the job has started, the production ID of the batch is displayed. While processing the job, the number of already cut steel rods (actual value) is permanently updated and displayed. The steel rod is cut when the “current feed” corresponds to the required rod length (here 2000mm). With each new feed after cutting, the feed value is reset to 0. The remaining capacity on the coil is updated after each cut.

The above figure graphically indicates the feed and cut operations.

3. After the cutting job has been completely processed, setpoint and actual value of the cut steel rods are identical (here =10). The production job is terminated with the Protocol button. The production data of the job is then written to the memory module. Alternatively, you can later increase the number of steel rods to be cut before the job is logged. If you enter, for example, 15 as a new setpoint and restart the job, 5 additional rods are cut. The production ID remains unchanged.

After pressing the Protocol button, the controller is ready for the entry of a new job.

6.3.2 Premature termination of the production process

Procedure Table 6-6

No. Step Remark

1. Start a cutting job in automation mode as described in section 6.3.1. Select the number of steel rods to be cut, for example again =10.

Page 44: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 44/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Step Remark

2. Before completing the job – for instance during the feed of the sixth rod – press the “End” button.

The “End” button flashes and thus indicates the premature termination of the job.

The currently processed rod is still cut to the defined length. The cutting process is interrupted.

3. Terminate the production job by selecting the Protocol button. The production data of the job is then written to the memory module. Alternatively, you can undo the termination of the production by again pressing the “End” button and by selecting the start button to continue the original job.

6.4 Cutting wire rods of variable length (manual mode)

Aside from automatic mode, the application also offers manual production. In manual mode, the wire feed is realized by a jog mode (both forwards and backwards) with two velocities. Cutting is performed by a button on the TP. Also manual mode requires that the steel wire be “fed in” (scenario as shown in section 6.2). This enables the user to accurately display the current feed or the desired wire length on the TP 177micro and to set the feed or length using jogging.

Page 45: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 45/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Procedure Table 6-7

No. Step Remark

1. Go to “manual production” mode (only possible if wire has previously been “fed in”).

The displayed “current feed” indicates the distance between wire tip position and cutter. If the wire tip is located exactly at the cutting tool (e.g., immediately after a cut), the feed = 0mm.

2. To cut a steel rod with a length of 2000mm also in this mode, use the jog buttons to move the wire in such a way that a “current feed” of 2000mm is displayed on the TP.

You can move forward or backward, jog quickly or slowly and make corrections as often as desired. If the “current feed” ≤ 0, i.e. if no wire is under the cutting tool, the “cut” button cannot be used.

3. Press the “cut” button. The cutting tool is controlled while you

keep the button pressed.

After completing the cut, the “residual material” is updated on the TP. The cut is automatically logged with production ID 0.

6.5 Immediate stopping of the feed motion

In the “feed in” and “automatic production” modes, a triggered feed motion can be stopped immediately using a…

• stop button on the TP 177micro,

• hardware button.

In both cases, the stopping is realized by the “Lin_StopMotion” block whose decelerating torque can be parameterized. While, after a stop via the TP 177micro, the original motion can be continued using the start button on the TP, the program branches to a fault condition requiring acknowledgement (“Emergency Stop” message) when stopping by means of the hardware button; after acknowledgement this condition inevitably leads to “feed in”.

Page 46: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 46/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

! WARNING

The hardware stop button must not necessarily be used as an actuating element of an emergency stop circuit, even if this is provided by its mechanical and electrical design. The hardware button merely intervenes in the control software. It does not interrupt the voltage of the motor circuit. Please observe the safety philosophy to be applied in your plant.

Page 47: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 47/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

6.5.1 Stopping using the stop button of the TP 177micro

Procedure Table 6-8

No. Step Remark

1. Go to “feed in” mode (section 6.2) or to “automatic production” (section 6.3).

2. During the relevant mode, press the “Stop” button on the TP. a. Response when feed active:

The motor is immediately decelerated to a standstill with the decelerating torque parameterized at the “Lin_StopMotion” block (T_Stop variable in the “Parameters” status table).

Response when feed motor stopped:This is, for example, the case when the cut is currently being performed in automatic mode. The subsequent feed motion that normally follows the cut is not performed.

3. Continue the original operation using the “Start” button.

In automatic production, the current job cannot be aborted by means of the stop button on the TP. If you want to cancel the job after the currently fed rod is cut to length, use the “End” button (flashes after the selection) to select the abort and to subsequently restart the drive using the start button. Use the hardware stop button for an immediate abort of the current job and automatic production (see section 6.5.2).

Page 48: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 48/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

6.5.2 Stopping using the hardware stop button (emergency stop)

Procedure Table 6-9

No. Step Remark

1. Go to “feed in” mode (section 6.2) or to “automatic production” (section 6.3).

2. During the corresponding mode, press the hardware stop button. a. Response when feed active:

The motor is immediately decelerated to a standstill with the decelerating torque parameterized at the “Lin_StopMotion” block (T_Stop variable in the “Parameters” status table).

Response when feed motor stopped:This is, for example, the case when the cut is currently being performed in automatic mode. The subsequent feed motion that normally follows the cut is not performed.

3. An Emergency Stop message is displayed

on the TP 177micro. 4. If you have used a latching (emergency

stop) button instead of the hardware stop button, release it.

5. Acknowledge the message on the TP.

Acknowledgement

After acknowledging the message, it disappears and the “feed-in” screen is displayed on the TP.

6. “Feed in” the wire as described in section 6.2.

Log data When stopping with the hardware stop button, forced logging of the job data is performed. All rods of the respective job cut until the stop event are considered. Please check this within the scope of the data logging in chapter 6.6.

Page 49: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 49/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

6.6 Data logging

Read out the log data from the memory module at regular intervals.

Procedure Table 6-10

No. Step Remark

1. Double-click .

Directory of csv log files is opened. A file with current date/time stamp in the file name does not yet exist.

2. Double-click .

The memory module is read out and deleted. The log data is written to the above directory as a csv file. If the directory is opened, it can be directly checked whether the csv file is created (may take several seconds).

The csv log file has a date/time stamp in the file name: (2) – DAT Configuration 0 (DAT0) – tt.mm.jjjj hh-mm.csv

3. Open the csv log file.

(Example):

Page 50: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 50/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

6.7 Optimizing the positioning process

The process is optimized by examining the trend curves v(t) and/or s(t).as described in chapter 4.4. The optimization is performed for a positioning in automatic mode. The trend curves are triggered by pressing the start button in automatic mode.

Note In the case described in the following table, the motor was operated without additional external moments of inertia.

Procedure Table 6-11

No. Step Remark

1. Open the “Parameters” variable table and select a positioning speed for the optimization that is as large as possible (V_Pos=400.0). Set the speed in the “Parameters” status table. Please note that the “V_Pos” parameter is smaller than/equal to the “Velocity_Limit” parameter. Start the optimization process with the tenfold moment of inertia (inertia) of the motor. This value (10*0.00052=0.0052kgm2.) has already been stored in VD1116.

2. Select the “Test” variable table. Activate Lin_Com_Monitor. In “selected_value”, specify what you want to monitor (2=v(t), 3=s(t)). Enable Lin_Com_Monitor with “Com_Monitor =1”.

3. In “recipe administration”, select a steel rod length of 400mm for the wire-wound coil used for optimization. On the one hand, this ensures that the specified positioning speed is reached and, on the other hand, that the entire positioning process is short enough (< 1.992s) to be completely monitored by the Lin_Com_Monitor block.

Page 51: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 51/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Step Remark

4. A requirement for recording a trend curve is that the “Done” output of the “Lin_Com_Monitor” block has “1” status (does not apply to the first recording process).

5. Go to automatic production and enter 1 for

the “number of core rods”. Subsequently, start the production using the start button. The positioning starts and Lin_Com_Monitor is triggered.

6. Go to the “Optimization” status table and use

to go to the trend view. By selecting

, you can stop the recording to make, for example, a screen shot.

7. Go to the “Parameters” status table and

change the following parameters: • Inertia: 0.00416kgm2 • M10.0: “1” (is reset automatically)

To ensure that the “Inertia” parameter takes effect at the “Lin_Init_horizontal” block, the init block has to be processed once. You achieve this with a positive edge at the M10.0 flag. This makes a system restart with renewed feed in unnecessary.

Page 52: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Live Demo

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 52/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

No. Step Remark

8. To move the axis again, proceed as follows: • Press the “Protocol” button • Enter “number of core rods” = 1 • Press the “Start” button As can be seen in the marked frame, the overshoot behavior could be optimized.

If necessary, repeat steps 7 and 8 with changed inertia and iteratively approach the optimum.

9.

Note The smaller the inertia, the smaller its influence on the system dynamics. Thus the trend curves for your application may deviate more or less strongly from the pictures in this application.

Page 53: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Technical Data

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 53/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

7 Technical Data

LOGO! Power 24V 1.3 Table 7-1

Criterion Technical data Additional note

Supply voltage 85 to 264VAC Output voltage 24VDC (setting range 22.2 to

26.4VDC )

Output current 1.3A Dimensions (W x H x D) mm 54 x 90 x 55

SIMATIC S7-200 CPU 224XP Table 7-2

Criterion Technical data Additional note

Supply voltage 20.4 to 28.8VDC Current consumption 900mA Inputs/outputs 14DI/10DO + 2AI EPROM user data 16 Kbytes Dimensions (W x H x D) mm 140 x 80 x 62

SINAMICS G110 Table 7-3

Criterion Technical data Additional note

Supply voltage 1 200-240VAC ±10% Input frequency 47-63Hz Output frequency 0-650Hz Output power 0.25kW Rated output current 1.7A Efficiency 90-94% Overload capability 150% Dimensions (H x W x D) mm 150 X 90 X 116

4-pole asynchronous motor Table 7-4

Criterion Technical data Additional note

Rated power 0.25kW Rated voltage Δ/Y 230/400V Rated current Δ/Y 1.34/0.77A Rated frequency 50Hz

Page 54: Micro Application Example · 2018. 3. 27. · Micro Application Example Closed-Loop Positioning Control with standard Drives Micro Automation Set 1

Technical Data

Micro Automation Set 1 ID Number 21063595

V2.0 16.07.2008 54/54

Cop

yrig

ht ©

Sie

men

s A

G 2

008

All

right

s re

serv

ed

Set

01_D

ocTe

ch_2

d0_e

n.do

c

Criterion Technical data Additional note

Rated speed 1350min-1 Moment of inertia 0.00052kg m2 Shaft height 71mm Weight Approx. 5kg

Proximity switch Table 7-5

Criterion Technical data Additional note

Number of conductors 3 conductors Type of design Cubic 40mm x 40mm Connector M12 connector Rated operating distance sn 25 or 40mm Selectable Operating voltage 10-65VDC Rated operational current Ie 300mA Displays for Switching status,

supply voltage

Degree of protection IP 65

TP 177micro Touch Panel Table 7-6

Criterion Technical data Additional note

Supply voltage 24VDC 20.4…28.8V Nominal current 0.24A Memory Flash

256 KB usable for user

Required configuration tool WinCC flexible Micro V 2004 SP1 and higher

Display STN, 4 blue levels 5.7" 320 x 240 pixels (W x H)

Interface RS485 (max. 0.1875Mbps) Dimensions (W x H) 212mm x 156mm Degree of protection (front/rear)

IP 65/20