    MiCOM M211

    Non communicating

    Measurement Centre

    ENERGY AUTOMATION& INFORMATION

    MICOM M211

    QUICK, SIMPLE MEASUREMENT

    OF SYSTEM PARAMETERS

    > Fast measurement and monitoring> Single or three phase> Input current and voltage sampling>Wide range of system parameters

    INNOVATIVE SOLUTIONS FOR THE MODERN WORLD

    In a competitive business environment, it pays to

    stay ahead of the game. AREVA T&D offers complete

    solutions for the entire energy chain, from primary

    equipment to market management software.

    THE M2X1 RANGE

    The MiCOM M2x1 range comprises:

    > M211 Non communicating Measurement Centre

    > M231 Communicating Measurement Centre

    > M241 Communicating Measurement Centre with Data Recorder

    (See separate documents for M231 and M241)

    EASYUSE CASE

    All models in the range offer the benefits of the new EasyUse case, which uses

    embedded ring current transformers, allowing cables to be passed through them

    without the need for a termination connection . The result is simpler installation and

    increased reliability of the current connection. If the cable needs to be terminated

    there is a connection block fitted.

    M211 NON COMMUNICATING MEASUREMENT CENTRE

    The M211 Non communicating Measurement Centre provides quick, reliable

    measurement and monitoring of electrical quantities in a single or three phase

    electrical distribution system. It utilises fast microprocessor sampling of the input

    current and voltage quantities to calculate a wide range of system parameters such as

    energy, power and frequency.

    Customer Benefits

    Comprehensive set ofmeasurements

    Simplified connections

    Large LCD display

    Easily programmablesettings

    AREVA T&D

  • 7/22/2019 MiCOM M211

    2/8

    2>3

    FEATURES

    > Large LCD displays up to 3 parameters

    simultaneously (see fig 1)

    > Four energy registers for four-quadrant energy

    measurement

    > Active energy metering to IEC 61036 class 1.0

    > Reactive energy metering to IEC 61268 class 2.0

    > Demand values for Current, W, VA, Var:

    present and since last reset

    > True rms measurement

    > Programmable VT and CT ratios

    > Single phase or three phase connections

    > For balanced or unbalanced loads

    > Multilingual selectable menu text

    > Compact and rugged design

    > Pulsed outputs

    M211:

    Delivers a wide range

    of measurementsat low cost

    Fig 1 Typical LCD displays

    BENEFITS

    > Wide range of measurement parameters

    > Accurate over a wide dynamic range

    > Replaces separate energy meters and

    instrumentation in cost sensitive applications

    > Easily configured to actual system parameters

    > Industry standard 96mm DIN case

    APPLICATION

    ENERGY MONITORING

    The M211 is intended for use on systems where

    energy monitoring and instrumentation are required,

    providing Volts, Amps, Watts, Vars, VA, power factor,

    and frequency, as well as metering for active and

    reactive energy.

    Demand values for current, active, reactive and

    apparent power are also provided.

    COST EFFECTIVE SOLUTIONS

    The M211 is more cost effective than using separate

    devices, saving on hole punching and wiring costs - as

    well as device costs and panel space costs.

    ELECTRICAL SYSTEMS

    The M211 can be used on single or three phase

    systems, with balanced or unbalanced loads.

  • 7/22/2019 MiCOM M211

    3/8

    FUNCTIONS

    INSTANTANEOUS MEASUREMENT

    Active Power Pa, Pb, Pc, Pt

    Reactive Power Qa, Qb, Qc, Qt

    Apparent Power Sa, Sb, Sc, St

    Power Factor Cosa, Cosb, Cosc, Cost

    Phase Voltage Ua, Ub, Uc, Ut

    Line Voltage Uab, Ubc, Uca, U3

    Current Ia, Ib, Ic, In

    Frequency F

    ENERGY MEASUREMENT

    Active Energy Wh total, import and export

    Reactive Energy VArh total,

    leading and lagging.

    DEMAND VALUES

    Phase currents

    Total active power

    Total reactive power

    Total apparent power

    24V DCPowerSupply OV

    100mspulseoutput

    R>100RPulsereceptor

    15 16

    M211 :

    Programmable CTs, VTs andpulsed ouputs can be easily configured.

    Fig 2 Pulse connections

    DEMAND CALCULATION

    The M211 is able to calculate Demand values using

    fixed, thermal and sliding window methods.

    Both Present Demand and Demand Since Last Reset

    are available.

    PULSED OUTPUTS

    The M211 has two pulsed outputs which can be set to

    correspond to any two of the four energy

    measurements.These are set via the front menu and

    can be disabled if not required. (see Fig 2)

    CONFIGURATION

    Two password controlled access levels are available.

    The following settings are password protected:

    > CT ratio

    > VT Primary

    > VT secondary

    > System connection

    > Demand calculation mode

    > Demand period

    > Energy meter resetting

    > Demand resetting

    > Pulse output configuration

  • 7/22/2019 MiCOM M211

    4/8

    4>5

    HARDWARE DESCRIPTION

    CASE

    The M211 is housed in a DIN case with maximum

    dimensions of 96mm by 96mm by 108mm.

    (See Fig4 for dimensions)

    DISPLAY

    The front panel contains an illuminated dot matrix liquid

    crystal display (LCD) with a large viewable area of

    70mm by 38mm. Four pushbuttons provide access to

    the M211 menu. See Fig 1 for typical screen views.

    REAR CONNECTIONS

    The auxiliary supply, pulsed output and measured

    voltage use plug in M2.5 terminal blocks.

    The current measuring circuit connections on the rear

    are by means of individual embedded CTs, see Fig 5.

    The current cables are passed through these CTs and

    can be terminated on a separate terminal block.

    See Fig 3 for rear case view.

    Fig 3 Rear case view

    102mm6mm

    96mm

    CT1 CT3

    CT215161718

    11258

    192021

    1314

    96mm

    Fig 4 Case outline

    EasyUse case :simplifies CT wiring connections

    Panel cutout

    Height92mm (+0.8,-0)

    Width92mm (+0.8,-0)

  • 7/22/2019 MiCOM M211

    5/8

    TECHNICAL DATA

    VOLTAGE INPUT

    Nominal phase to neutral input voltage (Un):57.74, 63.5, 120V or 230V

    (Other voltages in the range 50V to 300V phase to

    neutral are available on request)

    Measuring range with separate auxiliary supply:

    0 150% Un Burden with separate auxiliary supply:

    < 0.1VA

    Rated frequency and range:50Hz - 60Hz; 45Hz to 65Hz

    Thermal withstand 1.5 Un continuously 2 Un for 10 seconds

    CURRENT INPUT

    Rated current (In) 1A or 5A

    Measuring range 0 160% In

    Burden < 0.1VA Thermal withstand 3 In continuously

    25 In for 3 seconds

    50 In for 1 second

    ACCURACY

    Active energy IEC 61036 class 1.0

    Reactive energy IEC 61268 class 2.0

    Power 0.5% (*)

    Phase/phase voltage 1.0%

    Phase/Neutral voltage 0.5% (**)

    Phase current 0.5% (*)

    Neutral current 1.0% (*)

    Power Factor 0.5 degree

    Phase angle 0.5 degree

    MD Values 1.0%

    Frequency 10mHz

    * For these values the accuracy is % of nominal for

    0 100% of nominal and % of reading above nominal.

    ** For these values the accuracy is % of nominal for

    10 100% of nominal and % of reading above nominal.

    For voltage range 0 10% Un the maximum error is

    2% of nominal value.

    AC AUXILIARY VOLTAGE

    Input voltage 63.5, 100, 110, 115, 120,208, 220, 230 and 400 Ux

    Supply voltage range 0.8 1.2 Ux

    Burden < 5VA

    Frequency range 45Hz to 65 Hz

    PULSE OUTPUTS

    Output relay function2 relays, for activeand/or reactive energy control

    Maximum ac switching power50VA, maxima of 350Vdc or peak ac, 1A

    Maximum number of pulses4,000 per hour

    Pulse duration100mS

    Isolation4KV rms coil to contacts1.4KV across contacts

    SETTING TRANSFORMER RATIOS

    VOLTAGE RATIO

    Both the primary and secondary values of the VT

    may be set.

    Primary voltage setting

    Voltage range Voltage step

    0.1 to 15,999.9V 0.1V

    1 to 15,999kV 1V

    10 to 159.99kV 10V

    100 to 1599.9kV 100V

    Secondary voltage setting

    Voltage range Voltage step

    10 to 137V 1V

    140 to 775V 5V

    CURRENT RATIO

    Only the primary value can be altered, the secondary CT

    value is fixed at either 1A or 5A and must be specified

    with the order.

    CT ratio Step 1A CT primary rating1 to 63 1 1 to 63

    63 to 315 5 63 to 315

    320 to 630 10 320 to 630

    650 to 3150 50 650 to 3150

    4000 4000

    CT ratio Step 5A CT primary rating

    1 to 63 5 5 to 315

    63 to 315 25 325 to 1575

    320 to 630 50 1600 to 3150

    650 to 3150 250 3250 to 15750

    4000 20000

  • 7/22/2019 MiCOM M211

    6/8

    6>7

    ELECTRICAL ENVIRONMENT

    EUROPEAN LEGISLATION

    Product safety 73/23/EEC

    Compliance with the European Commission Low

    Voltage Directive.

    EN 61010-1: 2002

    Safety requirements for electrical equipment formeasurement, control and laboratory use, Part 1:

    General requirements.

    EMC Compliance 89/336/EEC

    EN62052-11:2003 Part 11 Metering equipment

    general requirements, tests and test conditions.

    Electricity Metering Equipment (ac)

    EN62053-21:2003 Particular requirements, Part 21:

    Static meters for active energy (classes 1 and 2)

    EN62053-23:2003 Particular requirements, Part 23:

    Static meters for reactive energy (classes 2 and 3)

    DESIGN

    Protection

    Compliance is demonstrated by reference

    to generic safety standards.

    Protection class II

    600V installation category II

    300V installation category III

    Pollution degree 2

    Test voltage

    3.7kV rms to EN61010-1:1990

    ENVIRONMENTAL WITHSTAND

    Climatic rating

    EN61036:1996

    EN61268: 1995

    Reference range of operation

    0C to 50C

    Nominal range of operation

    -25C to 55C

    Transit and storage

    -40C to 70C

    Humidity

    75% annual mean relative humidity

    CASE

    PC/ABS uninflammable to UL 94VO

    Dimensions 96 x 96 x 108mm

    Enclosure protection IP52 EN60529:1989

    Connection terminals IP00 EN60529:1989

    Weight 0.6kg

    CONNECTIONS

    Permissible cross section of connection leads:

    Measured quantities: 5mm2 single wire

    Auxiliary supply and outputs: 2.5mm2 single wire

    CONNECTION TABLE

    CT1

    K L

    lk

    Fig 5 Connections when using

    a pass through CT (per phase)

    Function Terminal

    AC current I1 CT1

    I2 CT2

    I3 CT3

    AC voltage UL1 2

    UL2 5

    UL3 8

    N 11

    Pulse output OUT 1 15/16

    OUT 2 17/18

    Auxiliary Supply +/AC 13

    -/AC 14

  • 7/22/2019 MiCOM M211

    7/8

    M211 X ? ? ? X 2 0 0 0 0 A

    X: Menu ConfigurableCT Secondary1: 1A5: 5A

    VT SecondaryB: 63.5V (57.7 to 69.3V L-N or 100V to 120V L-L)G: 120V (120V L-N or 208V L-V: 230V (220 to 250V L-N or 380V to 440V L-L)

    Auxiliary VoltageB: 63.5V acD: 100V acE : 110V acF: 115V acG: 120V acH: 208V acJ: 220V acV: 230V ac4: 400V acU: 24-276Vac, 24-300VdcFrequencyX: 50 60Hz

    Output2: 2 pulsed outputs

    Rear Port communications0: No communications

    Software0: Basic

    00A: Factory Defaults

    L)

    M211:

    Used by Industrial or

    Utility engineers, at low ordistribution voltage level

    INFORMATION REQUIRED WITH ORDER

  • 7/22/2019 MiCOM M211

    8/8

    SOUTH EAST ASIA

    Tel.: +65 67 49 07 77 - Fax: +65 68 41 95 55

    PACIFIC

    Tel.: +65 67 49 07 77 - Fax: +65 68 46 17 95

    CHINA

    Tel.: +86 10 64 10 62 88 - Fax: +86 10 64 10 62 64

    INDIA

    Tel.: +91 44 2431 7100 - Fax:+91 44 2434 1297

    NORTH AMERICA

    Tel.: +1 (484) 766-8100 - Fax: +1 (484) 766-8650

    CENTRAL AMERICA

    Tel.: +52 55 11 01 10 00 - Fax: +52 55 26 24 04 93

    SOUTH AMERICA

    Tel.: +52 55 11 3491 7469 - Fax:+55 11 3491 7476 FRANCE

    Tel.: +33 (0)1 40 89 66 00 - Fax: +33 (0)1 40 89 67 19

    BRITISH ISLES

    Tel.: +44 (0) 1785 27 41 08 - Fax:+44 (0) 1785 27 45 74

    NORTHERN EUROPE

    Tel.: +49 69 66 32 11 51 - Fax: +49 69 66 32 21 54

    CENTRAL EUROPE & WESTERN ASIA

    Tel.: +48 22 850 96 96 - Fax: +48 22 654 55 88

    NEAR & MIDDLE EAST

    Tel.: +971-6-556 0559 - Fax: +971-6-556 5133

    MEDITERRANEAN, NORTH & WEST AFRICA

    Tel.: +33 (0)1 41 49 88 38 - Fax: +33 (0)1 41 49 24 23

    SOUTHERN & EASTERN AFRICA

    Tel.: +27 11 82 05 111 - Fax: +27 11 82 05 220

    Our policy is one of continuous development. Accordinglythe design of our products may change at any time.Whilst every effort is made to produce up to date literature,this brochure should only be regarded as a guide and isintended for information purposes only. Its contents do notconstitute an offer for sale or advise on the application of

    any product referred to in it. We cannot be held responsiblefor any reliance on any decisions taken on its contentswithout specific advice.

    T&D Worldwide Contact [email protected]

    www.areva-td.com

    AUTOMATION-L3-M211-BR-08.06-0336c-GB

    -2006AREVA.

    AREVA,

    theAREVAlogoandanyalternativeversionth

    ereofaretrademarksandservicemarksofAREVA.

    M i C O M

    i s a r e g i s t e r e d t r a d e m e r k o f A R E V A

    T h e o t h

    e r n a m e s m e n t i o n e d

    r e g i s t e r e d o r n o t a r e t h e p r o p e r t y o f t h e i r r e s p e c t i v e c o m p a n i e s

    3 8 9 1 9 1 9 8 2 R C S P A R I S S O N O V I S I O N I T E

    P