MICO ® - Mineral Insulated Cables KME Italy S.p.A. MICO ® [I]

Transcript of MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages...

Page 1: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO® - Mineral Insulated CablesK

ME

Ital

y S.

p.A

.M

ICO

® [I]

Page 2: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO® Characteristics 4

Light duty cables

Heavy duty cables

Applications and advantages 5

Fire resistance 6

Mechanical resistance 9

Technical data 10

Mineral insulated cable Twisted 20

Complete installation 21

Mineral cables termination 22

Fixing systems 23

LSF sheathed Mineral cables 23

Tools 23

Installation 24

Junction boxes 28

Waterproof straight through joint 29

Applications Industrial area 30

Approvals 31

Mineral Insulated Heating Cables 32

Industrial applications 33

Building applications 34

Technical data 34

What is KME

A major European industrial group which for more than a hundred years has been a leading force in the world of copper processing industryWorld leader in semi-finished copper productsKME Group is the world’s largest manufacturer of semi-finished copper and copper alloy products (excluding copper wire), with a share of 30% of the European market and 7% worldwide

Major production sitesThe Group boasts 14 production sites strategically located in the 5 European countries with the largest semi-finished products markets, as well as in China.

A hundred years of historyKME Group has deep roots in the history of European industry: it was founded and first quoted on the stock mar-kets in the 19th century.

Our product range includes a complete assortment of semi-finished copper and copper alloy products designed for use in numerous applications. We keep an open dialogue with our customers, so that we can work together to develop resourceful, economical solutions for all kinds of copper applications, old and new.

Roofing systemsKME offers copper as a basic material for architecture and building: surfaces and systems for roo-fing and facade cladding and for the draining of rainwater.

Copper Industrial TubesA high level of quality characterizes our copper tubes; their characteristics have been studied to meet the needs of various industrial applications: air conditioning and refrigeration systems, con-struction of boilers, making of high-frequency coaxial cables, fittings and the solar heating industry.

Brass and copper rodsKME has the widest range of brass and copper rods on the market, in every size and shape, for all fields of application, from architecture to the electrical industry.

Special productsWe are able to create highly technological products: piping systems for the marine industry, tube bundles, mineral insulated cables, special extruded and drawn products in every size and shape, and finished machined parts based on the customer’s design.

Plumbing systemsHigh performance copper tubes, both bare and covered, which are ideal for any plumbing and heating application in the building sector as well as for the distribution of medical gases in the healthcare industry.

Industrial Rolled productsKME manufactures rolled products made of copper, brass, bronze and other copper-based alloys in every shape and size and with different surface treatments in order to meet the requests from many industrial sectors.

Engineered productsKME is a worldwide leader in the supply of copper and special alloy components for the continuous casting of steel and non-ferrous metals, just as it is a qualified and professional partner in the desi-gning of these systems.

WATERPROOF STRAIGHT THROUGH JOINT

Page 3: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

Characteristics Applications and advantages

54

MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper cores, from 1 to 400 mm2, melting point 1082°C Magnesium Oxide (MgO) as electrical insulation, due to its high performance at high

temperature (melting point 2600°C) high quality DHP copper sheath, manufactured starting from tubes extruded and drawn only

(not welded), melting point 1082°C LSF additional outer covering. Such flame retardant poliolephin is characterised by high

performance in corrosion resistance and low smoke emission.

MICO® Cable range is divided into: Light duty cables (300/500 V) from 2 to 7 cores, from 1 to 4 mm2 size Heavy Duty Cables (450/750 V) from 1 to 19 cores, 400 mm2 maximum size for single

core, 25 mm2 maximum size up to 4 cores.

Production process held by KME foresee many steps of diameter reduction (both drawings and rollings) separated by high temperature annealing. Long lead time (average is 8 weeks) grants high quality cable at the end of the process: strong compression of MgO powder (density about 2 kg/cm3) allows very high values of insulation resistance (also if burned, 180° bended or flattened) and thermal conductivity. Therefore current ratings are higher than soft skin cables, especially at high temperature.

LIGHT DUTY CABLES

Mineral Insulated cables – Light duty cable (300/500 V) – is the best solution for electric circuits installed at sight, in historical or relevant buildings, both indoor and outdoor. Due to their small dimensions, they can be installed quickly and easily. Copper outer sheath, who-se cross section is designed to be used as earth conductor, protects the cable from any mechanical stress like impacts, bending or flattening, giving at the same time a beautiful esthetical aspect to the cable. MICO® is not only a simple cable but, combining its use with the large range of copper and brass accessories, designed by KME, it can be considered as a complete wiring system.

HEAVY DUTY CABLES

The increasing of nominal voltage (450/750 V), due to higher thickness of copper outer sheath and Magnesium Oxide insulation, allows KME Mineral Insulated heavy duty cables to be installed in every critical environment, due to high humidity degree, or wherever the installation is dangerous due to possible mechanical damages. Wide manufacturing range, similar to soft skin wiring cable range, allow heavy duty cables design whenever big power is required.

Mineral cables are more efficient than standard wiring cables, in terms of resistance to thermal effects: this means that core cross sections (and cable outer diameters as well) can be reduced, under the same conditions of current ratings.

FIRE RESISTANCE – weaker situation is copper melting point(1082°C) MICO® is the safest cable, it can withstand to severe fire, water and mechanical tests as foreseen by British (LPCB), European and australian stan-dards

EMERGENCY SYSTEMS – MICO® is the only cable to go on wor-king also during a fire, so to supply (for at least 120 minutes, maximum time 3 hours) emergency lamps, acoustic alarms, sprinklers, automatic doors, eleva-tors and so on

FIRE DETECTION – MICO® cables allow fire controller units to recei-ve signals by fire detectors also during a fire. MICO® twisted cables (for signal transmission), in addition to MICO® light duty cables (for power supply), are able to match technical requirements by most popular fire detection systems

BUS SYSTEMS – world leaders like ABB or Schneider Electric alrea-dy tested and approved MICO® as suitable cable for distribution in their bus systems, limiting MICO® specification in fire hazardous areas or in historical buildings, where standard bus cables need are not recommended

HISTORICAL BUILDINGS – standard electrical plant can deeplyimpact aesthetical aspect of old buildings: where integrity of original structure must be saved and hidden installation is not allowed (or its cost would be too much), MICO® is the perfect solution for an installation at sight. You can also trust on copper capacity of disappearing, day after day, if used on particular environment like stone, brick, wood.

TUNNELS – emergency lights and fan coils are required to go on workingalso during a fire, to allow people using emergency exits. In order to save their life, MICO® is really able to withstand high temperatures during a car fire.

Page 4: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

Fire resistance

CWZ

76

Furnace

TunnelsFan coils, exit LEd ligths, emergency and standard lighting can continue to work if powered by MICO®

Standard soft skin fire re-sistant cable before fire test

Temperature inside furnace according to standard ISO 91 curve: after 90’ it’s 1020°C (German fire test according to DIN 4102), after 120’ it’s 1050°C (Australian fire test according to AS 3013). Same test executed in Italy to classify MICO® as REI 90

Standard cable failure after few minutes of fire test

Soft skin cable insulation cracks and falls down after some mechani-cal hits

This is how soft skin fire resistant cable remains after few minutes of fire: would you trust on it ?

MICO® cable during fire test (950°C for 180 minutes)

MICO® cable during water test (650°C for 15 minutes, then water crush trough sprinklers)

MICO® cable during mechani-cal test (950°C again for 15 minutes then mechanical impact directly on the cable)

MICO® cables after all test: power supply is still granted

CinemaEmergency circuit - exit lamp still going on during a fire, if all systems are powered by MICO®

Page 5: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

Building applicationsEmergency circuit - single core cables on fire proof cable conduit, to supply each level of building Elevator power supply

Mechanical performance

Industrial applications

98

Flattening test: cable cross section reduced by 50%, connected to power - no breakdown

Bending test: 180° bending on one side (bending radius = 6 times cable diameter), 180° bending on opposite side, then connected to power - no breakdown

Elevator/Lift

Fire resistant cable conduit

Page 6: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

1110

2 H 1.5 2 H 2.5 2 H 4 2 H 6 2 H 10 2 H 16 2 H 25 3 H 1.5 3 H 2.5 3 H 4 3 H 6 3 H 10 3 H 16 3 H 25 4 H 1.5 4 H 2.5 4 H 4 4 H 6 4 H 10 4 H 16 4 H 25 7 H 1.5 7 H 2.512 H 1.512 H 2.519 H 1.5

2 x 1.5 2 x 2.5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10 3 x 16 3 x 25 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10 4 x 16 4 x 25 7 x 1.5 7 x 2.512 x 1.512 x 2.519 x 1.5

HEAVY DUTY CABLES (450/750 V) - Multi core H cables

HEAVY DUTY CABLES (450/750 V) - Single core H cables

7.98.79.8

10.912.714.717.1

8.39.3

10.411.513.615.618.2

9.110.111.412.714.817.320.110.812.114.115.616.6

9.410.211.312.414.216.219.1

9.810.811.913.015.117.620.210.611.612.914.216.319.322.612.313.615.617.618.6

1.381.782.262.763.574.515.641.381.782.262.763.574.515.641.381.782.262.763.574.515.641.381.781.381.781.38

11.496.904.312.871.721.080.69

11.496.904.312.871.721.080.69

11.496.904.312.871.721.080.69

11.496.90

11.496.90

11.49

12.4914.5617.6120.9326.7434.1143.3913.6216.1419.3423.1130.2838.0747.3715.7718.4722.9026.7434.3644.4256.0120.7324.7331.8537.6441.59

1.381.180.980.820.640.510.401.271.070.890.750.570.450.361.090.930.750.640.500.390.310.830.700.540.460.41

750610480370280205150670520420350245180135560445350270205145110385310210175155

12001200120016001600160016001200120016001600160016001600120016001600160016001600160016001600160016001600

0.2250.2680.3450.4310.6080.8451.1380.2420.3130.4050.5160.7331.0111.3810.2980.3740.4960.6230.8841.2361.7520.4310.5570.6850.8780.928

0.2560.3060.3880.4780.6620.9071.2380.2740.3540.4500.5650.7911.1001.4870.3330.4180.5450.6770.9461.3371.8950.4770.6090.7460.9701.044

XG 2H1.5 XG 2H2.5 XG 2H4 XG 2H6 XJ 2H10 XJ 2H16 XK 2H25 XG 3H1.5 XG 3H2.5 XG 3H4 XJ 3H6 XJ 3H10 XJ 3H16 XM 3H25 XG 4H1.5 XG 4H2.5 XJ 4H4 XJ 4H6 XJ 4H10 XK 4H16 XM 4H25 XJ 7H1.5 XJ 7H2.5 XJ 12H1.5 XK 12H2.5 XM 19H1.5

10101010222

1010102222

10102222222222

RAD 2H1.5RAD 2H2.5RAD 2H4RAD 2H6RAD 2H10RAD 2H16RAD 2H25RAD 3H1.5RAD 3H2.5RAD 3H4RAD 3H6RAD 3H10RAD 3H16RAD 3H25RAD 4H1.5RAD 4H2.5RAD 4H4RAD 4H6RAD 4H10RAD 4H16RAD 4H25RAD 7H1.5RAD 7H2.5RAD 12H1.5RAD 12H2.5RAD 19H1.5

M20M20M20M20M25M25M32 M20M20M20M25M25M25M40M20M20M25M25M25M32 M40M25M25M32M32M40

10101010222

1010102222

10102222222222

XGFT 2H1.5 XGFT 2H2.5 XJFT 2H4 XJFT 2H6 XKFT 2H10 XMFT 2H16 XMFT 2H25 XGFT 3H1.5 XJFT 3H2.5 XJFT 3H4 XJFT 3H6 XKFT 3H10 XMFT 3H16 XMFT 3H25 XGFT 4H1.5 XJFT 4H2.5 XJFT 4H4 XKFT 4H6 XKFT 4H10 XMFT 4H16 XMFT 4H25 XJFT 7H1.5 XJFT 7H2.5

101022222

10222222

1022222222

RAD 2H1.5RAD 2H2.5RADT 2H4RADT 2H6RADT 2H10RADT 2H16RADT 2H25RAD 3H1.5RADT 3H2.5RADT 3H4RAD 3H6RADT 3H10RADT 3H16RAD 3H25RAD 4H1.5RADT 4H2.5RAD 4H4RADT 4H6RADT 4H10RADT 4H16RAD 4H25RAD 7H1.5RAD 7H2.5

M20M20M25M25M32 M40M40M20M25M25M25M32 M40M40M20M25M25M32 M32 M40M40M25 M25

101022222

10222222

1022222222

1N031N051N051N071N081N091N121N031N051N061N071N091N101N131N051N061N071N081N091N121N141N071N081N091N101N11

2N062N062N082N092N102N122N142N062N072N082N092N112N132N152N072N082N092N102N122N142N162N092N102N122N132N14

1P031P041P051P071P081P101P121P041P051P061P071P091P111P131P051P061P071P081P101P121P141P061P071P091P111P12

2P042P052P062P072P092P112P132P052P062P072P082P102P122P132P062P062P082P092P112P132P142P072P082P112P122P12

T05MT06MT08MT10MT12MT14MT17MT06MT07MT09MT11MT13MT15MT18MT07MT09MT11MT12MT14MT17MT19MT10MT12MT14MT15MT16M

1 H 1.5 1 H 2.5 1 H 4 1 H 6 1 H 10 1 H 16 1 H 25 1 H 35 1 H 50 1 H 70 1 H 95 1 H 120 1 H 150 1 H 185 1 H 240 1 H 300 1 H 400

1 x 1.51 x 2.51 x 41 x 61 x 101 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 400

4.905.305.906.407.308.309.60

10.7012.1013.7015.4016.8018.4020.4023.3026.0030.00

6.206.607.207.708.809.80

11.1012.2013.6015.2017.4018.8020.4022.9025.8028.5032.50

1.381.782.262.763.574.515.646.687.989.44

11.0012.3613.8215.3517.4819.5422.57

11.496.904.312.871.721.080.690.490.340.250.180.140.110.090.070.060.04

5.786.447.708.93

10.6813.1616.9620.2324.7330.9036.6942.5949.4857.4769.3984.55

105.97

2.982.682.241.931.611.311.020.850.700.560.470.400.350.300.250.200.16

2030174014201200

950730540440350275215185155125

988080

12001200120012001200120012001600160016001600160016001600160018001800

0.0900.1110.1430.1760.2350.3190.4430.5810.7640.9861.2791.5601.8672.3153.0203.8105.006

0.1070.1280.1660.2020.2680.3560.4850.6270.8161.0441.3671.6581.9742.4603.1863.9865.199

XG 1H1.5 XG 1H2.5 XG 1H4 XG 1H6 XG 1H10 XG 1H16 XG 1H25 XG 1H35 XJ 1H50 XJ 1H70 XJ 1H95 XK 1H120 XK 1H150 XK 1H185XM 1H240 T 1H300 T 1H400

1010101010101010222222222

RAD 1H1.5RAD 1H2.5RAD 1H4RAD 1H6RAD 1H10RAD 1H16RAD 1H25RAD 1H35RAD 1H50RAD 1H70RAD 1H95RAD 1H120RAD 1H150RAD 1H185RAD 1H240RAD 1H300RAD 1H400

M20M20M20M20M20M20M20M20M25 M25 M25 M32M32M32M40M40M40

1010101010101010222222222

XGFT 1H1.5 XGFT 1H2.5 XGFT 1H4 XGFT 1H6 XJFT 1H10 XJFT 1H16 XKFT 1H25 XKFT 1H35 XMFT 1H50

1010101022222

RAD 1H1.5RAD 1H2.5RAD 1H4RAD 1H6RADT 1H10RADT 1H16RADT 1H25RADT 1H35RADT 1H50

M20M20M20M20M25M25M32M32M40

1010101022222

1N011N011N011N011N021N031N051N061N081N091N101N111N131N141N15

2N012N012N012N042N052N062N072N082N102N112N132N142N152N162N17

1P011P011P011P011P021P041P051P061P071P091P111P121P131P141P15

2P012P012P012P032P042P052P062P072P082P102P112P122P132P142P15

T01MT01MT02MT01UT02UT03UT04UT05UT06UT07UT08UT09UT10UT11UT12UT13UT14U

LIGHT DUTY CABLES (300/500 V) - Multi core L cables

CABLE TECHNICAL DATA PLAIN SEALS EARTH TAIL SEALS CLIPS AND SADDLES

2 L 1 2 L 1.5 2 L 2.5 2 L 4 3 L 1 3 L 1.5 3 L 2.5 4 L 1 4 L 1.5 4 L 2.5 7 L 1 7 L 1.5 7 L 2.5 2 T 1 2 T 1.5 2 T 2.5

2 x 12 x 1.52 x 2.52 x 43 x 13 x 1.53 x 2.54 x 14 x 1.54 x 2.57 x 17 x 1.57 x 2.52 x 12 x 1.52 x 2.5

5.105.706.607.705.806.407.306.307.008.107.608.409.705.105.706.60

6.407.007.909.207.107.708.807.608.309.609.109.90

11.206.407.007.90

1.131.381.782.261.131.381.781.131.381.781.131.381.781.131.381.78

17.2411.49

6.904.31

17.2411.49

6.9017.2411.49

6.9017.2411.49

6.9017.2411.49

6.90

6.047.129.41

12.157.568.93

10.688.78

10.2112.8311.5713.3317.42

6.047.129.41

2.852.421.831.422.281.931.611.961.691.341.491.290.992.852.421.83

100100100100100100100100100100

800 600 500

190015001100

80015001200

90013001000

700

100100100

190015001100

1200120012001200120012001200120012001200120012001200120012001200

0.1030.1320.1800.2490.1310.1660.2250.1600.2040.2720.2230.2890.4170.1030.1320.180

0.1240.1550.2060.2800.1540.1920.2580.1850.2320.3080.2580.3260.4590.1240.1550.206

XG 2L1 XG 2L1.5 XG 2L2.5 XG 2L4 XG 3L1 XG 3L1.5 XG 3L2.5 XG 4L1 XG 4L1.5 XG 4L2.5 XJ 7L1 XJ 7L1.5 XJ 7L2.5 XG 2L1 XG 2L1.5 XG 2L2.5

10101010101010101010222

101010

RAD 2L1RAD 2L1.5RAD 2L2.5RAD 2L4RAD 3L1RAD 3L1.5RAD 3L2.5RAD 4L1RAD 4L1.5RAD 4L2.5RAD 7L1RAD 7L1.5RAD 7L2.5RAD 2L1RAD 2L1.5RAD 2L2.5

M20M20M20M20M20M20M20M20M20M20M25M25M25M20M20M20

10101010101010101010222

101010

XGFT 2L1 XGFT 2L1.5 XGFT 2L2.5 XGFT 2L4 XGFT 3L1 XGFT 3L1.5 XGFT 3L2.5 XGFT 4L1 XGFT 4L1.5 XGFT 4L2.5 XJFT 7L1 XJFT 7L1.5 XJFT 7L2.5 XGFT 2L1 XGFT 2L1.5 XGFT 2L2.5

10101010101010101010222

101010

RAD 2L1RAD 2L1.5RAD 2L2.5RAD 2L4RAD 3L1RAD 3L1.5RAD 3L2.5RAD 4L1RAD 4L1.5RAD 4L2.5RAD 7L1RAD 7L1.5RAD 7L2.5RAD 2L1RAD 2L1.5RAD 2L2.5

M20M20M20M20M20M20M20M20M20M20M25M25M25M20M20M20

10101010101010101010222

101010

1N011N011N011N031N011N011N021N011N021N031N031N031N051N011N011N01

2N012N022N042N052N032N042N052N042N052N062N052N062N072N012N022N04

1P011P011P011P031P011P011P021P011P021P041P031P041P051P011P011P01

2P012P022P032P042P022P032P042P032P032P052P042P052P062P012P022P03

T01MT02MT03MT05MT02MT03MT04MT03MT04MT05MT05MT05MT08MT01MT02MT03M

CA

BLE

TY

PE

CO

RE

x C

OR

E SI

ZE

(mm

2)

BA

RE

CA

BLE

DIA

MET

ER (

mm

)

LSF

CA

BLE

DIA

MET

ER

(mm

)

CO

RE

DIA

MET

ER

(mm

)

CO

RE

RES

ISTA

NC

E (O

hm

/km

)

CO

PP

ER S

HEA

THSE

CTI

ON

(mm

2)

CO

PP

ER S

HEA

THR

ESIS

TAN

CE

(Oh

m/k

m)

NO

MIN

AL

LEN

GTH

(m)

TOLE

RA

NC

E 5

%

CO

IL D

IAM

ETER

(mm

)

BA

RE

CA

BLE

WEI

GTH

(kg

/m)

LSF

CA

BLE

WEI

GTH

(kg

/m)

PLA

IN S

EALS

KIT

PC

S P

ER P

AC

K

PC

S P

ER P

AC

K

EAR

TH T

AIL

SEA

LS K

IT

ISO

BR

ASS

GLA

ND

SA

TEX

AP

PR

OV

ED

ISO

TH

REA

DD

IMEN

SIO

N

ISO

TH

REA

DD

IMEN

SIO

N

PC

S P

ER P

AC

K

PC

S P

ER P

AC

K

SIN

GLE

CLI

PS

(50

pcs

/pac

k)

BA

RE

SAD

DLE

S

(50

PCS/

PAC

K)

LSF

SAD

DLE

S(5

0 PC

S/PA

CK

)

EAR

TH B

ON

DIN

GC

LAM

PS

(10

PCS/

PAC

K)

LSF

SIN

GLE

CLI

PS

(50

PCS/

PAC

K)

II 2

G E

x eb

IIC

Gb

E

x d

b II

C G

b

II 2

D E

x tb

IIIC

Db

IP

65

Tam

b -2

0 °

C ÷

+7

0 °

C

Serv

ice

Tem

p.:

-20

°C

÷ +

25

0 °

C.

ISO

BR

ASS

GLA

ND

SA

TEX

AP

PR

OV

ED

II

2G

Ex

eb II

C G

b

Ex

db

IIC

Gb

II 2

D E

x tb

IIIC

Db

IP

65

Tam

b -2

0 °

C ÷

+7

0 °

C

Serv

ice

Tem

p.:

-20

°C

÷ +

25

0 °

C.

Page 7: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Resistance R (Ω/km)Cabletype2L1

2L1.52L2.52L43L1

3L1.53L2.5

30 °C18.81112.575

7.7014.479

18.81112.575

7.701

70 °C21.65614.477

8.8665.157

21.65614.477

8.866

105 °C24.14516.141

9.8855.749

24.14516.141

9.885

0.0880.0830.0790.0750.0910.0860.079

Reactance X (Ω/km) Impedance Z (Ω/km)30 °C

18.81112.576

7.7024.480

18.81112.576

7.702

70 °C21.65614.477

8.8665.157

21.65614.477

8.866

105 °C24.14516.141

9.8855.749

24.14516.141

9.885

Above indicated values are valid also for multi-core cables with 4 & 7 conductors

Light duty multi-core cables (500 V): resistance, reactance & impedance

Resistance R (Ω/km)Cabletype

2H1.52H2.52H42H6

2H102H162H25

30 °C12.575

7.7014.7913.2001.9021.1950.756

70 °C14.477

8.8865.5163.6852.1901.3760.870

105 °C16.141

9.8856.1504.1092.4411.5340.970

0.1010.0940.0880.0830.0790.0750.073

Reactance X (Ω/km) Impedance Z (Ω/km)30 °C

12.5767.7024.7923.2011.9041.1980.759

70 °C14.478

8.8665.5163.6862.1911.3780.873

105 °C16.142

9.8856.1504.1102.4421.5360.973

Above indicated values are valid also for all the other types of multi-core cables (with 3, 4 ,7, 12 & 19 conductors).

Heavy duty two-core cables (750 V): resistance, reactance & impedance

Resistance R (Ω/km)Cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

30 °C12.576

7.7024.7923.2021.9031.1960.7570.5460.4040.2810.2040.1630.1330.1090.0860.0760.075

70 °C14.478

8.8665.5163.6862.1901.3770.8710.6280.4650.3230.2340.1860.1520.1230.0960.0840.063

105 °C16.142

9.8856.15

4.1092.4421.5350.9710.7000.5180.3600.2600.2070.1690.1370.1060.0920.069

0.1390.1280.1200.1120.1040.0980.0930.0890.0850.0830.0800.0780.0770.0760.0760.0750.075

Reactance X (Ω/km) Impedance Z (Ω/km)30 °C

12.5777.7034.7933.2041.9061.2000.7630.5540.4130.2930.2190.1800.1540.1330.1150.1070.095

70 °C14.478

8.8675.5183.6872.1931.3800.8760.6350.4730.3330.2470.2020.1700.1450.1230.1130.099

105 °C16.142

9.8868.6504.1112.4441.5380.9750.7060.5250.3690.2720.2210.1850.1570.1310.1190.103

Single-core triplet cables: resistance, reactance & impedance

Resistance R (Ω/km)Cabletype

Cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

30 °C

Reactance X (Ω/km) Impedance Z (Ω/km)

Single-core cables laid side by side: resistance, reactance & impedance

12.617.7404.8313.2411.9421.2360.7970.5870.4460.3230.2460.2060.1770.1540.1320.1220.104

12.577.7024.7923.2021.9031.1960.7570.5460.4040.2800.2030.1610.1320.1070.0830.0730.054

12.537.6654.7553.1661.8671.1610.7220.5120.3710.2490.1720.1320.1040.0830.0630.0560.038

R S T14.518.9055.5553.7252.2291.4160.9110.6690.5060.3640.2760.2290.1950.1680.1420.1300.110

14.478.8665.5163.6862.1901.3770.8710.6280.4640.3220.2330.1850.1510.1220.0950.0820.061

14.448.8295.4803.6492.1541.3410.8360.5940.4310.2900.2010.1550.1220.0960.0720.0620.042

70 °CR S T

16.189.9246.1894.1482.4811.5741.011

0.740.5580.4010.3020.2490.2120.1810.1520.1370.115

16.149.8856.1504.1092.4421.5350.9710.7000.5170.3590.2590.2060.1680.1350.1040.0900.067

16.109.8486.1134.0732.4061.4990.9350.6650.4830.3260.2270.1750.1380.1080.0810.0680.046

105 °CR S T

30 °CR S T

70 °CR S T

105 °CR S TR S T

0.1600.1490.1400.1320.1240.1170.1120.1070.1030.0990.0960.0930.0900.0860.0820.0780.077

0.1390.1280.1200.1120.1040.0980.0930.0890.0850.0830.0800.0780.0770.0770.0770.0760.076

0.1610.1500.1420.1350.1270.1210.1170.1130.1100.1080.1060.1050.1040.1040.1040.1030.103

12.617.7424.8333.2441.9461.2420.8050.5970.4570.3380.2640.2260.1990.1770.1550.1450.129

12.577.7034.7933.2041.9051.2000.7620.5530.4130.2920.2180.1790.1530.1320.1130.1050.094

12.547.6674.7573.1681.8711.1670.7310.5240.3870.2710.2020.1690.1470.1330.1220.1170.110

14.528.9065.5573.7272.2331.4210.9180.6770.5160.3780.2920.2480.2160.1900.1660.1530.136

14.488.8675.5173.6872.1931.3800.8760.6340.4720.3330.2460.2010.1690.1440.1220.1120.098

14.448.8315.4823.6522.1581.3470.8440.6040.4450.3090.2270.1870.1600.1410.1270.1210.112

16.189.9256.1904.1502.4841.5791.0170.7480.5680.4130.3170.2670.2310.2020.1750.1610.142

16.149.8866.1514.1112.4441.5380.9750.7060.5240.3680.2710.2200.1850.1560.1300.1180.102

16.109.8506.1154.0752.4091.5040.9430.6750.4960.3430.2500.2030.1720.1500.1320.1240.114

1312

Page 8: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Resistance R (Ω/km)Cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

30 °C

Single-core cables laid at the distance of a diameter: resistance, reactance & impedance

12.617.7434.8333.2441.946

1.240.8030.5930.4530.3320.2570.2170.1900.1690.1480.1390.120

12.577.7034.7933.2031.9051.1990.7600.5500.4090.2870.2100.1700.1420.1200.1000.0930.075

12.547.7674.7283.1691.8701.1650.7280.5190.3790.2590.1850.1470.1210.1050.1410.0850.069

R S T14.528.9075.5573.7272.2321.4200.9160.6740.5120.3720.2850.2390.2070.1820.1580.1470.126

14.488.8675.5183.6872.1921.3790.8740.6320.4690.3280.2390.1930.1600.1340.1100.0990.079

14.448.8315.4823.6522.1571.3450.8410.6000.4380.2990.2120.1680.1370.1160.0970.0880.071

70 °CR S T

16.189.9256.1914.1502.4841.5781.0150.7450.5640.4080.3100.2590.2220.1940.1670.1540.131

16.149.8866.1514.1112.4431.5370.9730.7030.5210.3640.2650.2130.1760.1460.1180.105

0.83

16.109.8506.1154.0752.4081.5020.9400.6710.4900.3340.2370.1860.1510.1260.1030.0920.073

105 °CR S T

Cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

Reactance X (Ω/km) Impedance Z (Ω/km)30 °C

R S T70 °C

R S T105 °C

R S TR S T0.2030.1920.1830.1750.1670.1600.1540.1500.1450.1400.1360.1330.1290.1230.1160.1120.108

0.1820.1710.1630.1560.1480.1410.1360.1320.1290.1260.1230.1210.1200.1990.1170.1150.115

0.2050.1940.1860.1790.1710.1650.1610.1570.1540.1520.1500.1490.1470.1470.1450.1430.142

12.617.7454.8373.2481.9531.2500.8170.6110.4750.3600.2890.2530.2270.2050.1830.1720.155

12.577.7054.7963.2071.9111.2070.7720.5660.4290.3130.2440.2090.1850.1680.1530.1460.135

12.547.6704.7623.1741.8781.1770.7460.5430.4100.3010.2390.2090.1900.1790.1680.1620.152

14.528.9075.5603.7312.2391.4290.9280.6900.5320.3980.3150.2730.2430.2180.1940.1820.163

14.488.8675.5203.6912.1971.3860.8840.6450.4860.3510.2690.2280.1990.1780.1600.1510.139

14.448.8315.4853.6562.1641.3550.8560.6200.4650.3360.2600.2240.2010.1870.1730.1660.160

16.189.9276.1944.1542.4891.5861.0260.7600.5830.4310.3390.2910.2570.1940.2030.1900.170

16.149.8886.1544.1142.4481.5430.9830.7160.5370.3850.2920.2450.2130.1460.1660.1560.142

16.109.8526.1184.0792.4141.5110.9540.6890.5140.3670.2810.2380.2110.1260.1780.1700.159

Voltage drop (mV/Am)cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

30 °C21.78013.340

8.3005.5503.3002.0701.3100.9500.7000.4900.3500.2800.2300.1900.1500.1300.099

Voltage drop in single-core triplet cables

cos φ = 1 cos φ = 0.8

70 °C25.08015.360

9.5506.3803.7902.3801.5101.0900.8100.5600.4000.3200.2600.2100.2100.1500.110

105 °C27.96017.12010.650

7.1204.2302.6601.6801.2100.9000.6200.4500.3600.2900.2400.1800.1600.120

30 °C17.57010.800

6.7604.5502.7401.7601.1500.8500.6500.4800.3700.3100.2600.2300.2000.1800.160

70 °C20.21012.420

7.7705.2203.1402.0101.3000.9600.7300.5300.4100.3400.2800.2500.2500.1900.170

105 °C22.51013.830

8.6505.8103.4902.2301.4401.0600.8100.5800.4400.3700.3100.2700.2300.2100.170

Voltage drop (mV/Am)cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

30 °C21.78013.340

8.3005.5503.3002.0701.3100.9500.7000.4900.3500.2800.2300.1900.1500.1300.099

Voltage drop in single-core cables laid side by side

cos φ = 1 cos φ = 0.8

70 °C25.08015.360

9.5506.3803.7902.3801.5101.0900.8100.5600.4000.3200.2600.2100.2100.1500.110

105 °C27.96017.12010.650

7.1204.2302.6601.6801.2100.9000.6200.4500.3600.2900.2400.1800.1600.120

30 °C17.57010.800

6.7604.5502.7401.7601.1500.8500.6500.4800.3700.3100.2600.2300.2000.1800.160

70 °C20.21012.420

7.7705.2203.1402.0101.3000.9600.7300.5300.4100.3400.2800.2500.2500.1900.170

105 °C22.51013.830

8.6505.8103.4902.2301.4401.0600.8100.5800.4400.3700.3100.2700.2300.2100.170

1514

Page 9: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Voltage drop (mV/Am)cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H2401H3001H400

30 °C21.79013.340

8.3005.5503.3002.0601.3200.9600.7200.5100.3800.3100.2600.2300.2000.1800.150

Voltage drop in single-core cables laid at the distance of a diameter

cos φ = 1 cos φ = 0.8

70 °C25.08015.360

9.5606.3903.8002.3901.5201.1000.8200.5800.4300.3500.2900.2500.2100.1900.160

105 °C27.96017.13010.660

7.1204.2402.6701.6901.2200.9100.6400.4700.3800.3200.2700.2200.2000.170

30 °C17.63010.870

6.8304.6202.8101.8301.2100.9200.7200.5500.4400.3800.3400.3100.2800.2700.240

70 °C20.27012.480

7.8305.2903.2102.0801.3701.0300.8000.6100.4800.4200.3700.3300.3000.2800.250

105 °C22.57013.890

8.7105.8703.5602.2901.5101.1300.8800.6600.5200.4400.3900.3500.3100.2900.260

Voltage drop (mV/Am)cabletype

2L12L1.52L2.52L43L1

3L1.53L2.5

30 °C37.62025.15015.400

8.96032.58021.78013.340

Voltage drop in Light duty multi-core cables (500 V)

cos φ = 1 cos φ = 0.8

70 °C43.31028.95017.73010.310

37.5125.08015.360

105 °C48.29032.28019.77011.50041.82027.96017.120

30 °C30.20020.22012.420

7.26026.16017.51010.750

70 °C34.76023.26014.280

8.34030.10020.15012.370

105 °C38.74025.93015.910

9.29033.55022.46013.780

Above indicated values are valid also for multi-core cables with 4 & 7 conductors.

Voltage drop (mV/Am)cabletype

2H1.52H2.52H42H6

2H102H162H25

30 °C25.15015.400

9.5806.4013.8002.3901.510

Voltage drop in Light duty multi-core cables (750 V)

cos φ = 1 cos φ = 0.8

70 °C28.95017.73011.030

7.3704.3802.7501.740

105 °C32.28019.77012.300

8.2204.8803.0701.940

30 °C20.24012.430

7.7705.2203.1402.0001.300

70 °C23.28014.300

8.9306.0003.6002.2901.480

105 °C25.95015.930

9.9406.6704.0002.5401.640

Above indicated values are valid also for all the other types of multi-core cables (with 3, 4 ,7, 12 & 19 conductors).

single-core H (750 V) M.I.C. bare, exposed to touch or covered with thermoplastic material (metal she-ath maximum temperature 70°C). For bare cables we must multiply by 0.9. Cables sheaths are connected to the ends.

cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H240

(A)223040516992

120147182223267308352399466

(A)2636476082

109142174215264317364416472552

(A)2634455777

102132161198241289331377426496

(A)2636476082

109142174215264317364416472552

(A)3243567195

125162197242294351402454507565

(A)2636476082

109142174215264317364416472552

nominal conductor

cross section

mm2 2 cables

(A)

212837

223040516992

120

233140

2534455777

102133

multi-core H (750 V) e L (500 V) M.I.C. bare, exposed to touch or covered with thermoplastic material (metal sheath maximum temperature 70°C). For bare cables we must multiply by 0.9.

cable in air, spaced from wall or ceiling or on platform

192635

212837486586

112

500 V1.52.54

750 V1.52.546

101625

Table I/1

triplet cables in

air

laid side by side cables in air

horizontal spaced cables in air

vertical spaced cables in air

laid cables in air, fixed on wall or

ceiling

triplet cables in air, fixed

on wall or ceiling

(A)2837496284

110142173213259309353400446497

(A)2534455777

102133163202247296340388440514

(A)233141527092

120147181221264303346392457

(A)212837486586

112137169207249286327371434

13-1415-16 *

13-1415-16 *

1415-16 *

1415-16 *

1111A *

1111A *

3 cables 2 cables 3 cables 2 cables 3 cables 2 cables 3 cables 2 cables 3 cables 3 cables

Table II/1

cable in air, fixed on wall or ceiling

3-14-15-16 * 11-11A *

253344

2637476082

109142

3 cables

(A)

2 cables

(A)

3 cables

(A)serie

* Installation methods taken from 3rd edition of CEI 64-8/5 norm, table 52 C

1716

Page 10: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

single-core H (450/750 V) M.I.C. bare, not exposed to touch (metal sheath maximum temperature 105°C). - Correction factor for bundle is not required.

cabletype

1H1.51H2.51H41H6

1H101H161H251H351H501H701H95

1H1201H1501H1851H240

(A)2838506487

115150184228279335385441500584

(A)33456076

104137179220272333400460526596697

(A)3243567196

127164200247300359411469530617

(A)33456076

104137179220272333400460526596697

(A)40547089

120157204248304370441505565629704

(A)33456076

104137179220272333400460526596697

Table I/2

triplet cables in

air

laid side by side cables in air

horizontal spaced cables in air

vertical spaced cables in air

laid cables in air, fixed on wall or

ceiling

triplet cables in air, fixed

on wall or ceiling

(A)35476178

105137178216266323385441498557624

(A)3142557096

127166203251307369424485550643

(A)3041536791

119154187230280334383435492572

(A)2635475981

107140171212260312359410465544

13-1415-16 *

13-1415-16 *

1415-16 *

1415-16 *

1111A *

1111A *

3 cables 2 cables 3 cables 2 cables 3 cables 2 cables 3 cables 2 cables 3 cables 3 cables

nominal conductor

cross section

mm2 2 cables

(A)

263546

2635475981

107140

283851

3242557096

127166

multi-core H (750 V) e L (500 V) M.I.C. bare, not exposed to touch (metal sheath maximum temperature 105°C). Correction factor for bundle is not required

cable in air, spaced from wall or ceiling or on platform

243344

2635475981

107140

500 V1.52.54

750 V1.52.546

101625

Table II/2

Table III Correction factor k1 for room temperature different from 30° C

cable in air, fixed on wall or ceiling

3-14-15-16 * 11-11A *

314154

33456076

104137179

3 cables

(A)

2 cables

(A)

3 cables

(A)serie

* Installation methods taken from 3rd edition of CEI 64-8/5 norm, table 52 C

room temperature

°C10152025

35404550

55606570

75808590

95

bare cable or covered by ther-moplastic material exposed to

touch

bare cable not exposed to touch

70 °C1.261.201.141.07

0.930.850.760.67

0.570.45

--

----

-

105 °C1.141.111.071.04

0.960.920.880.84

0.800.750.700.65

0.600.540.470.40

0.32

Nominal copper sheath resistance (Ω/km)RatedVoltage

Cross-Sectionmm2

500 V

750 V

11.52.54

1.52.546

10162535507095

120150185240300400

1 cond

2.9812.6772.2381.9311.6141.3101.0160.8520.6970.5580.4700.4050.3480.3000.2480.2040.163

2 cond2.8552.4221.8331.4191.3811.1840.9790.8240.6450.5050.397

3 cond2.2791.9311.614

1.2661.0680.8920.7460.5690.4530.364

4 cond1.9641.6891.344

1.0930.9340.7530.6450.5020.3880.308

7 cond1.4911.2930.990

0.8320.697

12 cond

0.5410.458

19 cond

0.414

Nominal copper sheath resistance

1918

Page 11: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Mineral insulated cable TWISTED - code:2T1.5 Complete Installation

Numbers of conductors 2 x 1.5 mm²

Insulation (MgO)

Diameter over copper sheath (5.7 mm)

Red LSF additional sheath (7.2 mm)

In 100 mtrs coils

Voltage rating

Conductors resistance (max.)

Nominal sheath resistance (screen)

Nominal capacitance conductor to conductor

Nominal capacitance one conductor to sheath at 1 kHz

Nominal capacitance between conductorsand copper sheath at 1 kHz

Nominal inductance (loop) at 10 MHz

Attenuation at 1 MHz

Attenuation at 10 MHz

Nominal chatacteristic impedance

Manufatured following the requirements of BS 6207

On request KME is able to produce twisted cables 2T1 and 2T2.5 and also shielded MI cables with double insulation

Dimensional characteristics

Electric characteristics

1

2

3

4

500 V

12.1 ohm/km

2.7 ohm/km

164.5 pF/m

243.5 pF/m

384.4 pF/m

436.0 μH/m

- 19.0 dB/km

- 52.0 dB/km

50 ohm

Building management systems Fire detection systems Closed circuit television Fire telephone systems Data networks

2120

1

2

3

4

Using this option:- Assembling and fixing is speeder- Customer saves time, avoiding termination time- KME quality and guarantee is assured

Power supply

Junction box

Switch/socket

Lamp

Fixing clips

Mico® cable 2L1.5

MICO®

Page 12: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

Plain seals

It’s original MICO® termination type, characterised by minimum volume and minimum cost and execution time.Since it doesn’t foresee the connection of outer copper sheath, inside the junction box, to the earth system, it’s frequently used in public lighting to connect to double insulated lights and, for industrial applications in ATEX area, within brass RAD ISO glands

Earth tail seals

Fixing systemsMineral cables termination

Polyolefin extruded protection on the cable, available in red, orange, white and black colour, is required when: There are aggressive substances and therefore there’s danger for corrosion. Typical LSF cables usage

is in chemical, pharmaceutics and oil industries. Specific colour must identify the circuit type, like, for instance, LSF red to identify all cables part of

fire detection systems Specific LSF colour is considered as the best solution for cable camouflage.

Tools1

2

3 4

5

678

9

10

11

1) Small bender lever ZBLS (10 mm < Ø <16 mm)

2) Large bender lever ZBLL (Ø >16 mm)

3) Large ringer ZRL

4) Small rotary stripper (for 2L1 and 2L1.5 cables) ZSUS

5) Spare blade for small stripper ZSUSB

6) Crimping tool for G – M20 seals ZDC20

7) Crimping tool for J/K – M25/32 seals ZDC25

8) Plate type crimper for M – M40 seals ZDD 40

9) Large universal stripper ZSU

10) Spare blade for large stripper ZSUB

11) Straightener ZBSS (Ø <10 mm)

Copper outer sheath can be directly connected to earth system inside junction box by an annealed wire, already welded on brass pot.Also metallic junction box is connected as well by mechanical connection to outer sheath by brass glands, tightened through a locknut. Earth tail seals can so avoid an unpleasant outer earth connection.A correct execution of earth connection is extremely important for MICO® system, more than all other standard cables, since MICO® is the only cable to be installed at sight, exposed directly to touch also under 2.5 m of height, due to its structural mechanical resistance.

Gland bodyCompression ring

Backnut

MICO® Cable

Gland

Stub capBrass pot

Seal

Sleeving

Tipical connection

2322

Inside Junction boxes or enclosures, using standard hubs, MICO system is connected to standard wiring system. Earth tail seal and brass gland (by mechanical connection to metal enclosures) assure perfect connection to earth/ground system. MICO brass glands are IP65 waterproof approved.

II 2G Ex eb IIC Gb Ex db IIC Gb II 2D Ex tb IIIC Db IP65 Tamb -20 °C ÷ +70 °C

Service Temperature: -20 °C ÷ +250 °C.

LSF sheathed Mineral cables

Page 13: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

Installation

24

For the correct and complete installation procedure and execution of the terminations procedure carefully fol-low what reported extensively in the full document “Instructions - Mineral Insulated Cable (MICO®) and their Terminations” available in full on the website www.kme.com or by e-mail at [email protected]. This document shows all KME accessories required and detailed procedures to fully execute transportation, installation and termination of Mineral Insulated Cable (MICO®), accompanied by technical data, tips and detailed illustrations about.

The mineral insulated cable is normally supplied in a self-supporting coil having an inner diameter of 500,1200 and 1450 mm, depending on the outer diameter of the cable. To properly carry out the coils is possi-ble to build a simple unwinder, using a metal profile or of wooden boards such as used for the support ofcommon cables.

Before fixing, the cable it must be straightened by hand or by using a straightener or a tube bender; thefinal straightening can be performed using a block of wood and a hammer, or with a rubber hammer; a me-tal hammer should never be used directly on the cable sheath to avoid compromising the mechanical andelectrical characteristics of the sheath.

When the temperature of the sheath of a cable MICO®, taking account of the ambient temperature and theincrease in temperature due to the current, does not exceed 70°C, one can choose between the bare cableand the cable coated in LSF; for temperatures of the sheath more than 105°C, one must choose the barewire; for continuous operating temperatures of above 250°C must be take account what described aboutthe GF sealant.

The MICO® cables can operate at temperatures above -200°C, without be susceptible to adverse effects;on the other hand, cracks can occur on the additional coating in LSF at temperatures below -20°C withoutaffect the functionality of the cable. This is why you should not run the installation of coated cable with extracover in LSF at temperatures below -20°C.

Termination execution

Cut the end of the cable by a small saw; place the stripper on the cable and tighten it: the blade must be in contact with the copper outer sheath and the V shaped clamp must be tightened on the cable by its screw, so to let the tool spin round with the cable without stopping it.

Start rotating the tool pushing it towards the inner part of the cable; avoid the rolling up of the copper shaving on the conductors, fixing it on the suitable hook.When you have stripped enough copper sheath, you can insert the pliers to cause the drop of the copper sha-ving.

Regulationscrew

“V” fixed

Mobil“V”

Blade

25

Clean the conductors and insert the gland components (body, double cone and press cone).Only for use in explosion-proof applications, glands and seals shall be ATEX (or IECEx) marked. For applications in potentially explosive areas (zone 1 and zone 21) use only RAD ISO or RAD GAS fittings marked as follows:

II 2G Ex eb IIC Gb Ex db IIC Gb

II 2D Ex tb IIIC Db IP65

Tamb -20 °C ÷ +70 °C

Service Temperature: -20 °C ÷ +250 °C.

Page 14: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

2726

Cut some lengths of sleeving and, after removing eventual exceeding sealant, place them on the stub cap.

NO YES YES

Remove from the brass pot the Magnesium Oxide shattered during previous operation.Check with a Megger, at 500 Vcc, that cable insulation resistance is higher than 100 MΩ; then pour the sealant inside the brass pot.

After pulling the conductors by a pliers, place the stub cap as close as possible to the brass pot, then start crimping using the suitable tool.

In case that the fitting/housing coupling is subjected to vibrations it is necessary, in order not to cause brea-kage of the cable, to make a compensation bend in the vicinity of the housing. In case of ATEX applications the fitting/housing coupling shall guarantee at least 5 threads and the minimum housing thickness must be greater than or equal to 10 mm, moreover, the lock nut (see last figure) is not present in these coupling.The seal is guaranteed by the full tightening of the metal double cone through the cone press and is entrusted to the care of the installer.

Screw the self threaded brass pot on the cable sheath, placing the inner part of the hole on the copper sheath.

To make a termination, you need the following components (in addition to the cable, of course): seal, gland, sea-lant, eventual LSF shroud (if cable is LSF required), and the following tools: stripper, spare blades, crimping tool.

Check MICO® cables general brochure for tools dimension or technical manual for MICO® cables installation.

Gland

Conductor

Sleevings Junction box Wall

Mineral insulated cablecopper sheath

LSF shroud

Brasslocknut

Seal

LSF sheathed Mineral cables

Page 15: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

MICO®

Junction boxes Waterproof straight through joint

BRASS line COPPER line

2928

In order to complete MICO® system range, KME produces also 2 ranges of valuable metal junction boxes: in sandblasted brass and in copper. The first one is manufactured after melting, the second through assembly and welding of semi-finished products coming from KME divisions standard production.Production dimensions for junction boxes are:83 x 117 x 63 mm (small type) in our stock both for brass and copper; 132 x 191 x 72 mm (large type) in stock only for brass. Copper junction boxes can be manufactured according to any desired dimension by the Customer. All junction boxes can be supplied with a holed panel, so to install behind it all series of mounting frames and relative switches and sockets.

cable type cable type cable typeL L L

2L12L1.52L2.52L43L1

3L1.53L2.54L1

4L1.54L2.57L1

7L1.57L2.5

2H1.52H2.52H42H6

2H102H162H253H1.53H2.53H43H6

3H103H16

3H254H1.54H2.54H44H6

4H104H164H257H1.57H2.5

12H1.512H2.519H1.5

50505050505050505050707070

50505050707080505050707070

100505070707080

10070707080

100

L L

Gland GlandFerrules Insulating sleeving

KME speedseal (minimum 3 wrappings)

Brass tube

Page 16: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Applications Industrial area

Emergency and safety circuits

3130

Approvals

MICO® fire resistant cable is approved according:IEC 60331 - 3 hours - 750°CLPCB 6387 - 3 hours 950°C + mechanical and water testAS/NZS 3113 - 2 hours up to 1050°C + mechanical tests

Certificate No 427a to BS 6387:2013 (C,W,Z) EN 60702-1: 2002

KME glands ATEX approved

II 2G Ex eb IIC Gb Ex db IIC Gb II 2D Ex tb IIIC Db IP65 Tamb -20 °C ÷ +70 °C

Service Temperature: -20 °C ÷ +250 °C.

Page 17: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

3332

Industrial applications

Frost protection or heating of an industrial process can be easily achieved by electric heat tracing.Mineral insulated heating cables becomes the best choice when: required specific power and/or process temperature is high metal cable systems are preferred due to environmental characteristics of installation site specific installation method requires circular or small diameter cables long cuts are required.

KME Italy, starting from usual project data, is able to offer power calculation, select the right cable type and, if required, supply complete heating units, ready to be connected to power supply.

Low temperatures inside refrigerator cells can slowly destroy basement of the building: to avoid this, it’s extremely important to foresee an efficient and everlasting heating system, to compensate thermal los-ses through the insulation. Characteristics of Mineral insulated heating systems match exactly with over described specifics.

Refrigerator cell indoor

Thermal insulation

Heating cablesWelded grid

ConcreteBasement

Heating cable

Pre-stamped copper strip

Thermal insulationGlass fibre tape

Junction

Flange

Warning label

Power supply connection

Entry kit

Brass gland

Heating cable

Valve

Pavement

Mineral Insulated Heating Cables

CORETYPE

Copper (C)Kumanal (K)Copper (C)

Kumanal (K)Copper (C)

Kumanal (K)Nickel/Chrome 80/20 (T)Nickel/Chrome 80/20 (T)

SHEATHTYPE

Copper (C) + Polyethilene (HDPE)Copper (C) + Polyethilene (HDPE)

Copper (C)Copper (C)

Copper Nickel (CN)Copper Nickel (CN)

AISI 321 (I)Inconel 600 (INC)

MAX OPERATINGTEMPERATURE

110° C110° C250° C250° C400° C400° C600° C800° C

CABLECODE

CC / HDPEKC / HDPE

CCKCCNKNTI

TINC

COLD LEAD IN FOR POWER SUPPLY CONNECTION

Cold cable type

COPPER1H2.51H6

1H101H161H25

COPPER + HDPE1H2.5/ HDPE1H6/ HDPE

1H10/ HDPE1H16/ HDPE1H25/ HDPE

Cross sectionsize

mm2

2.56

101625

Ø copper outersheath

mm

5.306.407.308.309.60

Ø HDPE outersheath

mm

6.607.708.809.80

11.10

Ø core

mm

1.782.763.574.515.64

COPPER NICKEL1H2.5 CN1H6 CN

1H10 CN1H16 CN1H25 CN

AISI 3211H2.5 CI1H6 CI

OUTER SHEATH IN COPPER AND HDPETipocavo

KC 2700/HDPEKC 2000/HDPEKC 1600/HDPEKC 1250/HDPEKC 800/HDPEKC 630/HDPEKC 450/HDPEKC 315/HDPEKC 220/HDPEKC 140/HDPEKC 100/HDPE

CC 88/HDPECC 63/HDPECC 40HDPECC 25/HDPECC 17/HDPECC 11/HDPECC 7/HDPECC 4/HDPE

ResistanceΩ/km a 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm4.34.45.14.45.15.65.65.96.16.56.8

4.34.85.05.36.26.56.97.5

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

OUTER SHEATH IN COPPERCabletype

KC 2700KC 2000KC 1600KC 1250KC 800KC 630KC 450KC 315KC 220KC 140KC 100

CC 88CC 63CC 40CC 25CC 17CC 11CC 7CC 4

ResistanceΩ/km at 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm2.72.83.52.83.54.04.04.34.54.95.2

2.73.23.43.74.64.95.35.9

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

Cabletype

KN 1600KN 1000KN 630KN 400KN 250KN 160

CN 63CN 40CN 25CN 17CN 11CN 7CN 4

ResistanceΩ/km at 20° C

1.6001.000630400250160

634025171174

Ø outer sheathmm3.23.43.74.04.44.9

3.23.43.74.64.95.35.9

Ø coremm0.570.720.911.141.451.81

0.590.740.941.131.381.782.25

OUTER SHEATH IN COPPER NICKELAND CORE IN KUMANAL (K) OR COPPER (C)

Cabletype

TINC 10KTINC 6300TINC 4000TINC 2500TINC 1600TINC 1000TINC 630TINC 400TINC 250TINC 160

Cabletype

TI 10KTI 6300TI 4000TI 2500TI 1600TI 1000TI 630TI 400TI 250TI 160

Ø outer sheathmm3.23.23.23.43.63.94.34.75.36.5

ResistanceΩ/km at 20° C

10.0006.3004.0002.5001.6001.000630400250160

Ø coremm0.380.480.610.770.961.211.491.872.373.03

OUTER SHEATH IN INCONEL 600 OR SS.NICKEL-CHROME CORE

Page 18: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Road ramps, both for vehicles or persons, outdoor surfaces, helicopters landing areas, hothouses and football grounds: heating in these areas are made by mineral insulated units, buried in concrete or deep in the ground (5 - 10 cm depth, step 15 – 20 cm) in order to achieve an homogeneous thermal distribution.If the system is workmanlike installed, it’s safe, eternal, easy to be managed and controlled; neverthe-less, in case of breaking, it cannot create anyway same big damages like traditional hot water systems.Underfloor heating of the buildings guarantees excellent comfort, due high quality in heat distribution. These systems, sometimes inconve-nient due to high cost of domestic electric power, are recently stron-gly developed with alternative power sources, like photovoltaic energy production

Building applications

1) Concrete2) Moisture barrier

3a) Thermal insulation3b) Edge thermal insulation4) Protective barrier5) Welded grid6) Copper strip for cable fixing7) Mineral insulated heating cable8) Concrete protection9) Final pavement

10) Cold joint of heating cable11) Probe of temperature controller12) Temperature controller junction box13) Power supply junction box for heating cable

Power supply

1

23a

4

512

13

1110 967

83b

3534

Earth

Phase

Neutral

Earth

Earth tail seals GFT 1H2.5

Cold lead in cable “A” type 1H2.5/LSF orange

Cold lead in cable “B” type 1H2.5/LSF orangeDouble wall, blackthermoshrinkable tape

Heating cable, blackorange plastic shroudsfor glands protection

3000 mm

3000 mm

Bare heating cable

150 mm

150 mm

Cold joint

Bare cold cableISO 20 glands IP 67completed with locknut

CORETYPE

Copper (C)Kumanal (K)Copper (C)

Kumanal (K)Copper (C)

Kumanal (K)Nickel/Chrome 80/20 (T)Nickel/Chrome 80/20 (T)

SHEATHTYPE

Copper (C) + Polyethilene (HDPE)Copper (C) + Polyethilene (HDPE)

Copper (C)Copper (C)

Copper Nickel (CN)Copper Nickel (CN)

AISI 321 (I)Inconel 600 (INC)

MAX OPERATINGTEMPERATURE

110° C110° C250° C250° C400° C400° C600° C800° C

CABLECODE

CC / HDPEKC / HDPE

CCKCCNKNTI

TINC

COLD LEAD IN FOR POWER SUPPLY CONNECTION

Cold cable type

COPPER1H2.51H6

1H101H161H25

COPPER + HDPE1H2.5/ HDPE1H6/ HDPE

1H10/ HDPE1H16/ HDPE1H25/ HDPE

Cross sectionsize

mm2

2.56

101625

Ø copper outersheath

mm

5.306.407.308.309.60

Ø HDPE outersheath

mm

6.607.708.809.80

11.10

Ø core

mm

1.782.763.574.515.64

COPPER NICKEL1H2.5 CN1H6 CN

1H10 CN1H16 CN1H25 CN

AISI 3211H2.5 CI1H6 CI

OUTER SHEATH IN COPPER AND HDPETipocavo

KC 2700/HDPEKC 2000/HDPEKC 1600/HDPEKC 1250/HDPEKC 800/HDPEKC 630/HDPEKC 450/HDPEKC 315/HDPEKC 220/HDPEKC 140/HDPEKC 100/HDPE

CC 88/HDPECC 63/HDPECC 40HDPECC 25/HDPECC 17/HDPECC 11/HDPECC 7/HDPECC 4/HDPE

ResistanceΩ/km a 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm4.34.45.14.45.15.65.65.96.16.56.8

4.34.85.05.36.26.56.97.5

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

OUTER SHEATH IN COPPERCabletype

KC 2700KC 2000KC 1600KC 1250KC 800KC 630KC 450KC 315KC 220KC 140KC 100

CC 88CC 63CC 40CC 25CC 17CC 11CC 7CC 4

ResistanceΩ/km at 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm2.72.83.52.83.54.04.04.34.54.95.2

2.73.23.43.74.64.95.35.9

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

Cabletype

KN 1600KN 1000KN 630KN 400KN 250KN 160

CN 63CN 40CN 25CN 17CN 11CN 7CN 4

ResistanceΩ/km at 20° C

1.6001.000630400250160

634025171174

Ø outer sheathmm3.23.43.74.04.44.9

3.23.43.74.64.95.35.9

Ø coremm0.570.720.911.141.451.81

0.590.740.941.131.381.782.25

OUTER SHEATH IN COPPER NICKELAND CORE IN KUMANAL (K) OR COPPER (C)

Cabletype

TINC 10KTINC 6300TINC 4000TINC 2500TINC 1600TINC 1000TINC 630TINC 400TINC 250TINC 160

Cabletype

TI 10KTI 6300TI 4000TI 2500TI 1600TI 1000TI 630TI 400TI 250TI 160

Ø outer sheathmm3.23.23.23.43.63.94.34.75.36.5

ResistanceΩ/km at 20° C

10.0006.3004.0002.5001.6001.000630400250160

Ø coremm0.380.480.610.770.961.211.491.872.373.03

OUTER SHEATH IN INCONEL 600 OR SS.NICKEL-CHROME CORE

CORETYPE

Copper (C)Kumanal (K)Copper (C)

Kumanal (K)Copper (C)

Kumanal (K)Nickel/Chrome 80/20 (T)Nickel/Chrome 80/20 (T)

SHEATHTYPE

Copper (C) + Polyethilene (HDPE)Copper (C) + Polyethilene (HDPE)

Copper (C)Copper (C)

Copper Nickel (CN)Copper Nickel (CN)

AISI 321 (I)Inconel 600 (INC)

MAX OPERATINGTEMPERATURE

110° C110° C250° C250° C400° C400° C600° C800° C

CABLECODE

CC / HDPEKC / HDPE

CCKCCNKNTI

TINC

COLD LEAD IN FOR POWER SUPPLY CONNECTION

Cold cable type

COPPER1H2.51H6

1H101H161H25

COPPER + HDPE1H2.5/ HDPE1H6/ HDPE

1H10/ HDPE1H16/ HDPE1H25/ HDPE

Cross sectionsize

mm2

2.56

101625

Ø copper outersheath

mm

5.306.407.308.309.60

Ø HDPE outersheath

mm

6.607.708.809.80

11.10

Ø core

mm

1.782.763.574.515.64

COPPER NICKEL1H2.5 CN1H6 CN

1H10 CN1H16 CN1H25 CN

AISI 3211H2.5 CI1H6 CI

OUTER SHEATH IN COPPER AND HDPETipocavo

KC 2700/HDPEKC 2000/HDPEKC 1600/HDPEKC 1250/HDPEKC 800/HDPEKC 630/HDPEKC 450/HDPEKC 315/HDPEKC 220/HDPEKC 140/HDPEKC 100/HDPE

CC 88/HDPECC 63/HDPECC 40HDPECC 25/HDPECC 17/HDPECC 11/HDPECC 7/HDPECC 4/HDPE

ResistanceΩ/km a 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm4.34.45.14.45.15.65.65.96.16.56.8

4.34.85.05.36.26.56.97.5

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

OUTER SHEATH IN COPPERCabletype

KC 2700KC 2000KC 1600KC 1250KC 800KC 630KC 450KC 315KC 220KC 140KC 100

CC 88CC 63CC 40CC 25CC 17CC 11CC 7CC 4

ResistanceΩ/km at 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm2.72.83.52.83.54.04.04.34.54.95.2

2.73.23.43.74.64.95.35.9

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

Cabletype

KN 1600KN 1000KN 630KN 400KN 250KN 160

CN 63CN 40CN 25CN 17CN 11CN 7CN 4

ResistanceΩ/km at 20° C

1.6001.000630400250160

634025171174

Ø outer sheathmm3.23.43.74.04.44.9

3.23.43.74.64.95.35.9

Ø coremm0.570.720.911.141.451.81

0.590.740.941.131.381.782.25

OUTER SHEATH IN COPPER NICKELAND CORE IN KUMANAL (K) OR COPPER (C)

Cabletype

TINC 10KTINC 6300TINC 4000TINC 2500TINC 1600TINC 1000TINC 630TINC 400TINC 250TINC 160

Cabletype

TI 10KTI 6300TI 4000TI 2500TI 1600TI 1000TI 630TI 400TI 250TI 160

Ø outer sheathmm3.23.23.23.43.63.94.34.75.36.5

ResistanceΩ/km at 20° C

10.0006.3004.0002.5001.6001.000630400250160

Ø coremm0.380.480.610.770.961.211.491.872.373.03

OUTER SHEATH IN INCONEL 600 OR SS.NICKEL-CHROME CORE

CORETYPE

Copper (C)Kumanal (K)Copper (C)

Kumanal (K)Copper (C)

Kumanal (K)Nickel/Chrome 80/20 (T)Nickel/Chrome 80/20 (T)

SHEATHTYPE

Copper (C) + Polyethilene (HDPE)Copper (C) + Polyethilene (HDPE)

Copper (C)Copper (C)

Copper Nickel (CN)Copper Nickel (CN)

AISI 321 (I)Inconel 600 (INC)

MAX OPERATINGTEMPERATURE

110° C110° C250° C250° C400° C400° C600° C800° C

CABLECODE

CC / HDPEKC / HDPE

CCKCCNKNTI

TINC

COLD LEAD IN FOR POWER SUPPLY CONNECTION

Cold cable type

COPPER1H2.51H6

1H101H161H25

COPPER + HDPE1H2.5/ HDPE1H6/ HDPE

1H10/ HDPE1H16/ HDPE1H25/ HDPE

Cross sectionsize

mm2

2.56

101625

Ø copper outersheath

mm

5.306.407.308.309.60

Ø HDPE outersheath

mm

6.607.708.809.80

11.10

Ø core

mm

1.782.763.574.515.64

COPPER NICKEL1H2.5 CN1H6 CN

1H10 CN1H16 CN1H25 CN

AISI 3211H2.5 CI1H6 CI

OUTER SHEATH IN COPPER AND HDPETipocavo

KC 2700/HDPEKC 2000/HDPEKC 1600/HDPEKC 1250/HDPEKC 800/HDPEKC 630/HDPEKC 450/HDPEKC 315/HDPEKC 220/HDPEKC 140/HDPEKC 100/HDPE

CC 88/HDPECC 63/HDPECC 40HDPECC 25/HDPECC 17/HDPECC 11/HDPECC 7/HDPECC 4/HDPE

ResistanceΩ/km a 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm4.34.45.14.45.15.65.65.96.16.56.8

4.34.85.05.36.26.56.97.5

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

OUTER SHEATH IN COPPERCabletype

KC 2700KC 2000KC 1600KC 1250KC 800KC 630KC 450KC 315KC 220KC 140KC 100

CC 88CC 63CC 40CC 25CC 17CC 11CC 7CC 4

ResistanceΩ/km at 20° C

2.7002.0001.6001.250800630450315220140100

88634025171174

Ø outer sheathmm2.72.83.52.83.54.04.04.34.54.95.2

2.73.23.43.74.64.95.35.9

Ø coremm0.440.510.570.650.810.911.081.291.541.932.28

0.50.590.740.941.131.381.782.26

Cabletype

KN 1600KN 1000KN 630KN 400KN 250KN 160

CN 63CN 40CN 25CN 17CN 11CN 7CN 4

ResistanceΩ/km at 20° C

1.6001.000630400250160

634025171174

Ø outer sheathmm3.23.43.74.04.44.9

3.23.43.74.64.95.35.9

Ø coremm0.570.720.911.141.451.81

0.590.740.941.131.381.782.25

OUTER SHEATH IN COPPER NICKELAND CORE IN KUMANAL (K) OR COPPER (C)

Cabletype

TINC 10KTINC 6300TINC 4000TINC 2500TINC 1600TINC 1000TINC 630TINC 400TINC 250TINC 160

Cabletype

TI 10KTI 6300TI 4000TI 2500TI 1600TI 1000TI 630TI 400TI 250TI 160

Ø outer sheathmm3.23.23.23.43.63.94.34.75.36.5

ResistanceΩ/km at 20° C

10.0006.3004.0002.5001.6001.000630400250160

Ø coremm0.380.480.610.770.961.211.491.872.373.03

OUTER SHEATH IN INCONEL 600 OR SS.NICKEL-CHROME CORE

HEATING CABLE COLD CABLE "A" and "B"V

W

Type

CC40/HDPE

2CC17/HDPE

CC63/HDPE

CC88/HDPE

CC88/HDPE

KC220/HDPE

KC450/HDPE

KC630/HDPE

KC1600/HDPE

m

215

200

163

142

125

80

60

45

33

Type

1H2.5/LSFA

2H2.5/LSFA

1H2.5/LSFA

1H2.5/LSFA

1H2.5/LSFA

1H2.5/LSFA

1H2.5/LSFA

1H2.5/LSFA

1H2.5/LSFA

m

3

3

3

3

3

3

3

3

3

Seal

GFT

GFT

GFT

GFT

GFT

GFT

GFT

GFT

GFT

Surface size

32 m2

36 m2

25 m2

20 m2

25 m2

15 m2

10 m2

9 m2

5 m2

Surface size

41 m2

51 m2

35 m2

28 m2

31 m2

21 m2

14 m2

12 m2

7 m2

W/m2

180

200

192

195

175

200

195

205

200

W/m2

142

140

137

139

138

142

139

155

142

Step

15 cm

18 cm

14 cm

15 cm

20 cm

19 cm

17 cm

20 cm

15 cm

Step

19 cm

25 cm

20 cm

20 cm

25 cm

26 cm

23 cm

27 cm

20 cm

Gland

RN 1/2"

RN 1/2"

RN 1/2"

RN 1/2"

RN 1/2"

RN 1/2"

RN 1/2"

RN 1/2"

RN 1/2"

229

230

230

230

230

230

230

230

230

Sheathtemperature (°C) Snow melting (3 cm/hour)

Frost protectionor de-icing

Permanent Start up

5.830 6.540 7.200 8.150 4.800 5.480 3.900 4.500 4.300 5.100 3.000 3.000 1.950 1.950 1.870 1.870 1.000 1.000

Permanent Start up

35 37 32 35 39 42 42 46 47 52 36 36 35 35 42 42 38 38

NOTES: 1) brass glands RAD ISO 20 are IP67 waterproof and dust protected and are completed by suitable locknut 2) cold lead in cold cables are completed by protection shrouds type CO1, orange coloured3) start up powers were calculated basing upon a start up temperature of +5°C

Page 19: MICO Mineral Insulated Cables · 2019-07-25 · MICO® Characteristics Applications and advantages 4 5 MICO® Mineral Insulated Cable is composed by: ETP solid (not stranded) copper

Manufacturing plant and sales office:KME Italy S.p.A.Via della Repubblica, 25755051 Fornaci di Barga (LU) Italy