Medium Voltage (MV) Accessories CatalogLINKING ACCESSORIES TO CAbLE SOLuTIONS
Linking power grids to sustainability
OBG-03635_PrysmianCover.indd 1 5/24/12 8:37 AM
OBG-03635_PrysmianText.indd 24 5/24/12 8:36 AM
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1
A40
6 20
19-0
2-21
1
A brand of the
Applications Prysmian offers a new line of indoor and outdoor polymerterminations available for 5kV, 15KV, 25/28KV and 35KVapplications. The ColdFit™ outdoor PCT (with sheds) andindoor PICT (without sheds) are medium voltage cold shrink polymer terminations designed for fast, easy and reliable installation.
The new ColdFit™ terminations shrink evenly on the cable as the inner support core is removed. The top mastic waterseal is built into the ColdFit™ termination. No complicated assembly or heat is required. Simply pull out the support core and allow the termination to shrink in order to createa tight void free interface between the termination and the cable. This also provides a superior moisture seal.
All of the Prysmian PCT and PICT terminations meet or exceed the stringent requirements mandated by the IEEE standard 48 for class 1 specification. Specifications and Ratings
IEEE - IEEE 48 Class 1
Design Features UNIT CONSTRUCTIONBoth the silicone polymer housing and the stress relief material are assembled on a spiral support tube. This enables the installer to apply the termination on the cable with a high degree of ease and accuracy. The top mastic water seal is built into the ColdFit™ termination.
EXTERNAL HOUSING The silicone polymer housing has a superior memory along with excellent tracking and weathering resistance.
STRESS CONTROL Stress control is maintained using a material with a high permitivity constant (High K), which provides a uniform stress relief in critical areas.
RANGE COVERING CAPABILITYThe PCT and PICT terminations cover a broad range of cable sizes and voltages with the fewest number of units.
Design Features continued... OUTDOOR SHED DESIGN Three designs for superior performance under all conditions.
- Four sheds for 15KV outdoor. - Six sheds for 25/28KV outdoor. - Eight sheds for 35KV outdoor. INSTALLATION The PCT and the PICT series are designed to give consistent proper positioning of the unit. Additionally, the pull down base gives greater flexibility and sealing when used on jacketed concentric neutral cables.
ColdFit™ Medium Voltage Cold Shrink Terminations
Conductor
Cable Insulation Silicone Housing
Stress Relief Tube
Integrated Mastic Seal
Insulation Shield
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1
A40
6 20
19-0
2-21
2
A brand of the
ColdFit™ Medium Voltage Cold Shrink Terminations
PRODUCT NOTES:
The above dimensions are approximate and subject to normal manufacturing tolerances.
All metric (SI) dimensions are derived from a soft conversion.
Type PCT15 PCT25 PCT35 PICT15
Sizes Available * 1,2,3,5,6 3,4,5,6 5,6 1,2,3,5,6
Voltage Rating (kV) 15 25/28 35 15
Number of Sheds 4 6 8 0
Minimum Strike Distance (In) 11.6 14.5 16.8 8.4
Creepage Distance (In)Max. Design Voltage to Ground (kV)
15.09.5
22.816
30.022
8.49.5
(Partial Discharge) 13 21 30 13
Lightning Impulse (BIL) 110 150 200 110
10 Sec Wet (60 Hz) (kV) 45 60 80 --
1 Minute Dry (60 Hz) (kV) 50 65 90 50
6 Hour Dry (60 Hz) (kV) 35 55 75 35
DC Withstand 15 Min. Dry (kV) 75 105 140 75
Technical Specifications Ease of Installation
*Cable dimensions per AEIC CS8, compressed conductor. For all other constructions, verify that actual dimensions of the cable fall within Insulation Diameter tolerances.
2. Placement of Termination
3. Support Core Removal 4. Completed Assembly
1. Final Cable Prep
The PCT and PICT terminations provide electrical stress control by utilizing a flexible tube with a high permittivity dielectric constant. The stress relief tube is pre-assembled under the polymer housing. As the core is removed, both the tube and the housing shrink onto the cable in exactly the right position. When energized the electrical field is refracted through the stress relief tube and housing as shown above. The mastic top seal is integrated into the termination body.
Stress Distribution
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1
A40
6 20
19-0
2-21
3
A brand of the
ColdFit™ Medium Voltage Cold Shrink Terminations
Part No. Cable Range (Insulation Diameter)
#of Sheds 5kV 100% 5kV 133% /
8kV 100% 8kV 133% 15kV 100% 15kV 133%
PICT15X1-CF0.57" to 0.98"
14.5 mm to 25 mm
None1/0
to 3/0 #1 AWG to 3/0
#1 AWG to 3/0
#2 AWG to 3/0
#2 AWG to 3/0
PICT15X2-CF0.67" to
1.10"17 mm
to 28 mmNone
4/0 to 250 kcm
3/0 to 250 kcm
1/0 to 250 kcm
#1 AWG to 250 kcm
#2 AWG to 250 kcm
PICT15X3-CF0.85" to
1.50"21.5 mm
to 38 mmNone
350 kcm to500 kcm
250 kcm to500 kcm
4/0 to 500 kcm
4/0 to 500 kcm
2/0 to 500 kcm
PICT15X5-CF1.08" to
1.97"27.5 mm
to 50 mmNone
750 kcm to 1000 kcm
750 kcm to 1000 kcm
500 kcm to 1000 kcm
350 kcm to 750 kcm
350 kcm to 750 kcm
PICT15X6-CF1.41" to 2.56"
36 mm to 65 mm
None
Larger Conductor
Sizes Available
Larger Conductor
Sizes Available
Larger Conductor
Sizes Available
1000 to 1500kcm
1000kcm to 1500kcm
Ordering Information
ColdFit Indoor Terminations - 5kV to 15kV
Part No. Cable Range (Insulation Diameter)
# of Sheds 5kV 100% 5kV 133% /
8kV 100% 8kV 133% 15kV 100% 15kV 133%
PCT15X1-CF0.57" to 0.98"
14.5 mm to 25 mm
41/0
to 3/0#1 AWG to 3/0
#1 AWG to 3/0
#2 AWG to 3/0
#2 AWG to 3/0
PCT15X2-CF0.67" to
1.10"17 mm to 28 mm
4 4/0 to
250 kcm3/0 to
250 kcm1/0 to
250 kcm#1 AWG to 250 kcm
#2 AWG to 250 kcm
PCT15X3-CF0.85" to
1.50"21.5 mm to
38 mm4
350 kcm to 500 kcm
250 kcm to 500 kcm
4/0 to 500 kcm
4/0 to 500 kcm
2/0 to 500 kcm
PCT15X5-CF1.08" to
1.97"27.5 mm to
50 mm4
750 kcm to 1000 kcm
750 kcm to 1000 kcm
500 kcm to1000 kcm
350 kcm to 1000 kcm*
350 kcm to 1000 kcm*
PCT15X6-CF1.41" to 2.56"
36 mm to 65 mm
4
Larger Conductor
Sizes Available
Larger Conductor
Sizes Available
Larger Conductor
Sizes Available
1000 to 1500 kcm
1000 kcm to 1500 kcm
ColdFit Outdoor Terminations - 5kV to 15kV
The Prysmian Terminations can also be supplied with: Copper or aluminum lugs - (1 hole or 2 hole)Copper or aluminum pin terminals and also Bi-metallic pin terminals
Replace X with J for Jacketed Concentric Neutral CablesReplace X with M for Copper Tape Shielded CablesReplace X with L for LC Shielded Cables
* For Copper Lugs
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive| Johnstown, Ontario K0E 1T1
© PRYSMIAN - A Brand of The Prysmian Group 2019. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued February 2019.
A40
6 20
19-0
2-21
4
A brand of the
ColdFit™ Medium Voltage Cold Shrink Terminations
The Prysmian Terminations can also be supplied with: Copper or aluminum lugs - (1 hole or 2 hole)Copper or aluminum pin terminals and also Bi-metallic pin terminals
Part No. Cable Range (Insulation Diameter)
# of Sheds 25kV 100% 25kV 133% / 28kV
100% 28kV 133%
PCT25X2-CF40.67"
to 1.10"17 mm
to 28 mm4 #2 AWG to 2/0 AWG #2 AWG to 2/0 AWG #2 AWG to #1 AWG
PCT25X3-CF4
0.85" to 1.50"
21.5 mm to 38 mm
4 3/0 AWG to 350 kcm 3/0 to 250 kcm 1/0 to 250 kcm
PCT25X5-CF4
1.08" to 1.97"
27.5 mmto 50 mm
4 250 kcm to 1000 kcm 3/0 to 800 kcm 2/0 to 800 kcm
PCT25X6-CF4
1.41" to 2.56"
36 mm to 65 mm
4 750 kcm to 1500 kcm 500 kcm to 1500 kcm 500 kcm to 1500 kcm
ColdFit Outdoor Terminations - 25kV to 35kV
Replace X with J for Jacketed Concentric Neutral cablesReplace X with M for Copper Tape Shielded CablesReplace X with L for LC Shielded Cables
* For this size termination a shear bolt lug with outer diameter of 1.25” should be used on 1/0-4/0 AWG cables to create a tight seal at the top of the termination.
Part No. Cable Range (Insulation Diameter)
# ofSheds 35kV 100% 35kV 133%
PCT35X3-CF 0.75" to 1.15" 19mm to 24mm 8 1/0 AWG to 2/0 AWG 1/0 AWG
PCT35X5-CF 1.08" to 1.70" 27.5 mm to 41 mm 8 1/0 AWG* to 500 kcm 2/0 AWG to 500 kcm
PCT35X6-CF 1.41" to 2.20" 36 mm to 56 mm 8 400 kcm to 1500 kcm 250 kcm to 1250 kcm
ColdFit Outdoor Terminations - 35kV
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 A
404
2019
-02-
22
5
A brand of the
5-35 kV ELASPEED™ Compact Splice
Description The new Elaspeed™ Compact Splice (25% shorter in length) is a low-profile, range-taking, 105°C-operating-temperature cable splice. It is designed to splice tape shield, wire shield, LC shield, UniShield, JCN and flat strap shielded cables. Compact structure allows for installation in confined areas and requires less cable to be prepared. The insulation is made from ethylene propylene rubber (EPR) on a vertical triple extruder which maintains its concentricity to tight tolerances. It is tested as a cable (partial discharge and AC withstand) to ensure long and trouble-free operation under a wide variety of applications and conditions.
Design Features UNIFORM CUTBACK DIMENSIONSThe Elaspeed™ Compact Splice is expanded to allow ‘parking’ on one side of the splice area, over the cable jacket. Installer errors during cable preparation are minimized, because cutbacks for jacket, shield, semiconductor and insulation are identical for both cables to be spliced.
WATERTIGHT INSTALLATION Major accessory users are concerned that ingress of water in damaged cable jackets and unsealed splices can lead to premature failures. The Elaspeed™ Compact Splice has successfully passed IEEE 404-2012, the industry standard for splices. The Elaspeed™ Compact Splice has passed external water pressure tests of 45 psi. In addition, the tight interface between the cable and splice body can withstand internal pressures up to 30 psi. Internal mastic seals ensure that even cable jacket damage will not allow water to enter the splice area.
SMALL PROFILEElaspeed™ Compact Splices behave like EPR cable when it comes to bending in tight manhole situations. Splices can be bent to the same radius as the cable on which it is applied. This small profile consumes less racking space as well.
Design Features continued...
RANGE-TAKING CAPABILITY The splice can easily accommodate different types of insulation (EPR to XLPE), different insulation thicknesses (175 mil to 220 mil, or 260 mil to 345 mil), as well as different conductor sizes and metals.
Why Use Elaspeed™ Compact Splices?
25% SHORTERElaspeed™ Compact Splices are 25% shorter in length which makes it easier to park in tight manholes, requires less cable to prepare and reduces storage space over traditional splice kits.
SPEEDAn Elaspeed™ Compact Splice can be performed in 30 minutes or less, saving time and money over other splices.
TESTING All Elaspeed™ Compact Splices are pre-tested as cable to ensure that the splice will maintain the integrity of the electrical system. The Elaspeed™ EPR insulation system provides the highest dielectric strength over the full voltage range as well as the highest BIL available from any splice technology.
SAFETY
Elaspeed™ Compact Splices utilize cold shrink technology, which requires no open flames, eliminating the problems associated with handling and transporting gas bottles.
RELIABILITY AND REPEATABILITY Elaspeed™ Compact Splices are reliable because they always shrink uniformly, and there is only one part to shrink – the triple-extruded body.
PRE-PACKAGED WITH SHEARBOLT CONNECTORSPrysmian Shearbolt connectors are designed to be compatible with Prysmian Elaspeed™ Compact Splice Kits. Two superior technologies provide for a quick and easy installation that saves time and cost over traditional methods.
6
A brand of the
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 A
404
2019
-02-
22
Notes:
1. When selecting kits at the top end of the use range, check for proper fit over jacket
2. The selection guide is based on jacketed concentric neutral cables. When using LC or copper tape shield cables, the range my be extended upwards
3. Prysmian Elaspeed™ Compact Splices meet IEEE 404-2012 specifications.
4. Contact your Prysmian sales representative for more information, including data on size transition limits
5. If Crimp Connectors are used Prysmian must verify the length of the crimp connector.
Splice Part Number Designation
Size selection is based on typical URD cable parameters:
- Class B Compressed Round Copper conductor.
- AEIC minimum insulation diameters.
- One-third concentric neutral.
- Concentric neutral wires not being brought out for grounding or fault current protection.
- Encapsulated jacket.
- XLPE or EPR Shielded Power Cable.
If the cable design or installation is based on other parameters, the recommended splice size may change.
The “15” in the splice part number indicates the rated volt-age for the splice. Note that 15kV splices are used for 5kV and 8kV. This splice will simply provide more protection for the respective voltage classes.
The “D”, “E”, “F”, “H”, “IP” or “I” in the splice part number denotes the size parameter of the splice. All of the splices for 5 thru 28kV have a built in electrode for stress control, which is denoted by the small “e” in the part number.
The “J” in the splice part number indicates a jacketed splice. Splices may be ordered without a jacket, in which case the “J” would not be included in the splice part number.
The “B” and “C” in the part number indicates the equivalent metallic ground shield size.
- “B” is equal to #3 AWG.
- “C” is equal to 1/0 AWG.
- All of the splices are supplied with C size shield, with the exception of the smallest “D” size splice which has a B size shield.
- Splices may be ordered without a ground shield, in which case the Letter B or C should not be included in the part number.
Splice Selection and Ordering
When selecting splice kits at the top end of the use range, check for proper fit over jacket. If standard splicing practice includes bringing out the neutral wires for grounding and/or fault protection, this will significantly increase the overall diameter of the cable and can change the recom-mended splice size.
© PRYSMIAN - A Brand of The Prysmian Group 2019. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifi-cations are not contractually valid unless authorized by Prysmian Group. Issued February 2019.
Product Number Cable Range Shearbolt Range Insulation Diameter Jacket Diameter
Minimum Maximum
5kV Elaspeed™ - 100% Insulation Level (90 mils)
15SDJCe-C 3/0 - 250 #2-250 0.68" 1.26"
15SEJCe-C 250 - 500 1/0 - 500 0.75" 1.34"
15SFJCe-C 500 - 750 350 - 750 0.91" 1.73"
15SIPJCe-C 750 - 1250 750 - 1250 1.09" 2.05"
5kV Elaspeed™ - 133% Insulation Level (115 mils)
15SDJCe-C 3/0 - 250 #2-250 0.68" 1.26"
15SEJCe-C 4/0 - 500 1/0 - 500 0.75" 1.34"
15SFJCe-C 350 - 750 350 - 750 0.91" 1.73"
15SIPJCe-C 750 - 1250 750 - 1250 1.09" 2.05"
15kV Elaspeed™ - 100% Insulation Level (175 mils)
15SDJCe-C #2 - 3/0 #6 - 3/0 0.68" 1.26"
15SEJCe-C 1/0 - 250 #2 - 250 0.75" 1.34"
15SFJCe-C 4/0 - 500 1/0 - 500 0.91" 1.73"
15SHJCe-C 250 - 500 1/0 - 500 0.96" 1.81"
15SIPJCe-C 500 - 750 350 - 750 1.09" 2.05"
15SIJCe-C 750 - 1250 750 - 1250 1.26" 2.44"
15kV Elaspeed™ - 133% Insulation Level (220 mils)
15SDJCe-C #2 - 2/0 #6 - 3/0 0.68" 1.26"
15SEJCe-C* #2 - 4/0 #2 - 250 0.75" 1.34"
15SFJCe-C 3/0 - 500† 1/0 - 500 0.91" 1.73"
15SHJCe-C 4/0 - 500† 1/0 - 500 0.96" 1.81"
15SIPJCe-C 350 - 750 350 - 750 1.09" 2.05"
15SIJCe-C 750 - 1250 750 - 1250 1.26" 2.44"
25kV Elaspeed™ - 100% Insulation Level (260 mils)
25SDJCe-C #1 - 1/0 #6 - 3/0 0.68" 1.26"
25SEJCe-C #1 - 2/0 #6 - 3/0 0.75" 1.34"
25SFJCe-C 1/0 - 350 1/0 - 500 0.91" 1.73"
25SIPJCe-C 250 - 500 1/0 - 500 1.09" 2.05"
25SIJCe-C 500 - 1000 500 - 1000 1.26" 2.44"
25kV Elaspeed™ - 133% Insulation Level (320 mils)
25SDJCe-C N/A #6 - 3/0 0.68" 1.26"
25SEJCe-C N/A #6 - 3/0 0.75" 1.34"
25SFJCe-C 1 - 4/0 1/0 - 500 0.91" 1.73"
25SIPJCe-C 3/0 - 500 1/0 - 500 1.09" 2.05"
25SIJCe-C 350 - 1000 500 - 1000 1.26" 2.44"
35kV Elaspeed™ - 100% Insulation Level (345 mils)
35SHJC-C 1/0 - 250 #2 - 250 0.96" 1.81"
35SIPJC-C 1/0 - 500 1/0 - 500 1.09" 2.05"
35SIJC-C 750 - 1250 750 - 1250 1.26" 2.44"
35kV Elaspeed™ - 133% Insulation Level (420 mils)
35SHJC-C 1/0 - 250 #2 - 250 0.96" 1.81"
35SIPJC-C 1/0 - 500 1/0 - 500 1.09" 2.05"
35SIJC-C 750 - 1250 750 - 1250 1.26" 2.44"
PRODUCT NOTES: For 25kV applications revert to 35kV part numbers.Sizes are based on AEIC and ICEA specifications for typical compressed conductor, jacketed, 1/3 neutral cables.* These kits will not fit #2 solid conductor† For copper tape sheilded cables this range can be extended to 750kcmil
5-35kV ELASPEED™ Compact Splices
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com A
405
2015
-10-
13
7
Shearbolt®Connectors Fast Reliable Medium Voltage Connections
Description
Prysmian Mechanical Shearbolt Connectors are designed to cover a wide range of conductor sizes from 6 AWGto 1250 kcmil. Individual sizes cover ranges from 6 AWG-3/0, 2 AWG–250 kcmil, 1/0 AWG –500 kcmil, 350–750 kcmil, 500-1000 kcmil and 750–1250 kcmil. The unique stepless Shearbolt design has no predetermined breaking points in the connector thread. Bolts always break flush with the surface of the connector body.
The design provides excellent performance and features not found in other mechanical connectors. They meet ANSI C119.4 and withstand the 40% pull out force (ANSI Class 2) required by IEEE-404. No compression dies or mechanical crimp tooling are required for installation. Following cable preparation, simply slide the connector over the conductor and tighten the bolts until they shear off.
Prysmian Mechanical Shearbolt Connectors are dual-rated (AL/CU) and tin-plated to resist corrosion. Compatible with the full line of Prysmian Elaspeed™ cold-applied splice kits, they offer the best medium voltage cable splicing solution.
Ratings
• ANSI C119.4-2004• ANSI Class 2 (40% RBS)• Dual-Rated (AL/CU)
Electrical Property
• Current Cycle Test - Class A @ 284oF (140oC) Conductor• Mechanical Pullout Test -Class 2
Stepless Technology
The stepless Shearbolt has no pre-set shear points in the threads and makes use of the maximumnumber of bolt threads possible to apply a compressive force to the conductor. The stepless technology ensures that the bolt will shear off below the surface of the connector, eliminating the need for filing sharp metal edges.
Friction Disc
As the bolt is tightened, the friction disc at the base of the bolt makes contact with the conductor and no longer rotates. The bolt rotates freely above the friction disc without putting torque on the conductor. This allows the shearbolt to apply the optimum amount of contact force without damaging even finely stranded conductors.
Hex Key Bolts
No special tools are required to install the connector since the shearbolts are equipped with hex key fittings. Only 5 mm, 6 mm, or 8 mm standard hex keys are needed.
Compatibility
Prysmian shearbolt connectors are designed to be compatible with Prysmian Elaspeed™ cold-applied splice kits. Two superior technologies provide for a quick and easy installation that saves time and cost over tradition methods.
A40
5 20
15-1
0-13
8Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com
© PRYSMIAN - A Brand of The Prysmian Group. 2015 All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued October 2015.
FEATURE ADVANTAGE BENEFIT
Wide application range Reduced number of connectors to accommodate cable sizes from #6 to 1,250 kcmil
Reduces accidental use of the wrong connector
Each connector covers multiple conductor sizes Range-taking in each connector Reduced inventory
Step-less shearhead bolts Installs with simple ratchet-type socket wrench or cordless impact wrench
Eliminates need for heavy crimp tooling and special dies
Bolts are continuous shearing Bolts shear at or below the connector surface No time-consuming filing is needed
Friction disk stops rotating upon conductor contact Provides increased contact force Will not damage fine stranded conductors
Compact, smooth body design Compatible with Prysmian Cold Shrink Elaspeed™ Splices
An engineered system providing years of trouble-free performance
Torque-controlled shearhead bolts Sheared head gives positive indication of correct installation
Provides positive feedback that the connection is fully tightened
Heavy-duty design Connector bodies are made of high strength, tin-plated aluminum alloy
Provides long service life under normal operation conditions with reserve capacity.
Centering rings for small diameter conductors Minimizes voltage stresses at transition from connector body to cable insulation.
No separate metal inserts required - less parts to handle.
Factory filled oxide-inhibiting compound Abrades and penetrates the conductor oxides Generates low initial contact resistance and long term reliabilty
Knurled Inner bore Unique profile breaks through oxides and grips conductor strands
Generates low contact resistance & increases mechanical pullout strength. Meets Class 2, 40% RBS of the conductor.
Solid center stop Mechanical barrier is impervious to oil Accommodates transition applications from polymeric to PILC cable
Dual-rated Designed and tested for use on both aluminum and copper conductors
Ideal for aluminum to copper conductor transitions
No crimping required No crimping dies, crimp tooling or calibration of crimp tool required
Easy installation - particularly in confined spaces
Transitions between conductor sizes One connector can easily accommodate size transitions
Eliminates use of adapters that can impede electrical conductivity
Shear Bolt Connectors
CatalogDescription
Part Number
ConnectorRange
AWG / kcmil
Connector Length w/Centering Rings
Inches (mm)Connector O.D.
Inches (mm) Hex
Key SizeNumber of Bolts
6-3/0 ALSB CUS53825 #6 to 3/0 2.95 (75) .95 (24) 5 mm 2
2-250 ALSB CUS53821 2-250 4.41 (112) 1.10 (28) 5 mm 41/0- 500 ALSB CUS53783 1/0 to 500 5.12 (130) 1.30 (33) 6 mm 4
350-750 ALSB CUS53826 350 to 750 6.93 (176) 1.65 (42) 8 mm 6
500 -1000 ALSB CUS53919 500 to 1000 7.83 (199) 2.05 (52) 8 mm 6
750 -1250 ALSB CUS53828 750 to 1250 10.15 (258) 2.10 (53) 8 mm 8
CatalogDescription
Part Number
ConnectorRange
AWG / kcmil
Connector Length w/Centering Rings
Inches (mm)Connector O.D.
Inches (mm) Hex
Key SizeNumber of Bolts
2-250-ALSB2 CUS53939 #2-250 5.98 (152) 1.10 (28) 5 mm 2
4/0-500-ALSB2 CUS53829 4/0-500 6.32 (161) 1.30 (33) 6 mm 2
500-750-ALSB2 CUS53942 500-750 7.54 (192) 1.65 (42) 8 mm 3750-1000-ALSB2 CUS53943 750-1000 8.37 (213) 205 (52) 8 mm 3
1000-1250-ALSB2 CUS53945 1000-1250 8.37 (213) 2.05 (52) 8 mm 3
Two Hole Shear Bolt Lugs
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1
2016
-04-
12
9
200A Loadbreak Elbow Series(15kV/25kV/35kV)
Product Features Molded External Shield - 1/8-inch thick, peroxide-cured EPDM conductive jacket is abrasive resistant and is an integral component of the deadfront design.
EPDM Insulation - peroxide-cured provides superior stress-relaxation characteristics and assures long life under high ambient temperatures. Compatible with all solid dielectric cable insulations and shields.
Molded Conductive Insert - controls electrical stress and shields the compression connector.
Operating Eye - permits energized loadmake / loadbreak operations with suitable hot-stick tool. Designed and tested to withstand 500-lb static pull and 10 ft-lb torsion forces.
Compression Lug - meets all requirements of ANSI C119.4 for Class A connectors.
Test Point - allows for the installation of faulted circuit indicators and will indicate the presence of voltage when integrated with a high-impedance device.
Cable Entrance - the semi-conductive rubber continues the cable's insulation shield and helps control internal voltage stress. The interference fit along the cable insulation surface provides proper creep distance and dielectric strength.
Grounding Tabs -provides a means to connect a drain wire to ensure deadfront construction.
White-Black-White ID Band -identifies elbow as having a 3Ø rating for switching and fault-close.
Operating Interface -designed to mate with any component manufactured to the requirements of IEEE Std. 386. (Fig. 5)
Locking Ring -secures the elbow to mating product. Initial pull-off force required to unseat from mating groove in bushing insert produces fast break necessary for loadbreak switching.
Loadbreak Probe -tin-plated copper body provides current path and reliable loadmake/loadbreak switching operations.
General Information
Loadbreak Elbows provide utilities with products having high reliability and low maintenance expense.
The elbow, when mated with a loadbreak bushing product meeting the requirments of IEEE Standard 386, is suitable for energized loadmake / loadbreak operations by a qualified lineman using an 8' shotgun-type hot stick.
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 10
2016
-04-
12
Underground ConnectorsGeneral Information
Underground connectors provide utilities with products having high reliability and low maintenance expense.
Separable connector bushing inserts and elbows are designed for use with single-conductor, concentric neutral power cables having extruded insulation shielding. With shield adapter products, the elbow can be used with cables having a metallic tape shield, wire shield, or lead sheath with tape or extruded insulation shielding.
All insulating and conducting rubber components are made of a special formulation of an EPDM elastomer using a peroxide curing process. The material and curing process provides superior
elastomer stress relaxation characteristics under high ambient temperatures and contributes to reliable, long-time operation in either above-ground or subsurface installations.
Elbow connector/bushing insert combinations are suitable for energized loadmake/loadbreak operations by a qualified lineman using an 8’ shotgun-type hot stick.
All elbow/bushing insert combinations are designed for use with subsurface (submersible to 6-feet of water) or pad-mounted installations.
8.3/4.4 - 25/28 kV Class Underground Connectors
General Information
- 10,000-amp fault-closing capability- Piston-operated fault-close action- Standard elbow and bushing insert loadbreak principle- 1/8" thick molded shields- Peroxide-cured EPDM compounds- Full compliance with IEEE Standard 386 (Fig. 5)
Where to Use
15 kV loadbreak products are designed for operation on, and connection to, 15 kV Class (95 kV BIL systems) where the voltage ratings listed on this page are not exceeded.
25/28 kV loadbreak products are designed for operation on and connection to 25/28 kV class, 125 kV BIL systems where the volt-age ratings listed on this page are not exceeded.
21.1/36.6 kV Underground Elbow Connectors
General Information
- 10,000 ampere fault-closing capability- Standard elbow and bushing loadbreak principle- Molded shields- Peroxide-cured EPDM compounds- Full compliance with IEEE Standard 386- 35kV Large Interface- Purple cuffs for quick 35kV identification
Where to Use
35 kV loadbreak elbows are designed for operation on, and connection to, 35 kV Class (150 kV BIL systems) where the voltage ratings listed on this page are not exceeded.
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive| Johnstown, Ontario K0E 1T1
© PRYSMIAN - A Brand of The Prysmian Group 2016. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued January 2016.
11
2016
-04-
12
RATINGS
15 kV 25/28 kV 35 kV
Max. continuous voltage:8.3 kV phase-to-ground14.4 kV phase-to-phase
16.2 kV phase-to-ground28 kV phase-to-phase
21.1 kV phase-to-ground36.6 kV phase-to-phase
Continuous current: 200-amp rms 200 amp rms 200 amp rms
SHORT-TIME CURRENT RATINGS
0.17-second duration 10,000-amp rms symmetrical 10,000 amp rms symmetrical 10,000 amp rms symmetrical
3.00-second duration 3,500-amp/rms symmetrical 3,500 amps rms symmetrical 3,500 amps rms symmetrical
INSULATION WITHSTAND VOLTAGES
Basic Impulse Level(1.2 x 50 µsec wave)
95 kV crest 125 kV crest 150 kV crest
60 Hertz (1-minute) 34 kV rms 45 kV rms 50 kV rms
DC (15-minutes) 53 kV 84 kV 103 kV
Corona extinction voltage(3-picocoulombs) 11 kV rms 21.5 kV rms 26 kV
ALL VOLTAGE CLASSES SWITCHING
10 loadmake/loadbreak operations at 200 amps with 90% parallel and 10% series
resistance - reactance load at 0.8 power factor.
1-phase and 3-phase circuits 8.3 kV phase-to-ground, 14.4
kV maximum across the open contacts.
1-phase and 3-phase circuits 15.2 kV phase-to-ground, 26.3
kV maximum across the open contacts.
1-phase and 3-phase circuits 21.1 kV phase-to-ground, 36.6
kV maximum across the open contacts.
ALL VOLTAGE CLASSES FAULT CLOSURE
10,000 amps rms symmetrical, 10 cycles
(0.17 seconds).
One fault-close operation at 8.3 kV phase-to-ground, or 14.4 kVphase-to-phase;
10,000 amps rms symmetrical, 10 cycles,
(0.17 seconds).
One fault-close operation at 15.2 kV phase-to-ground, or 26.3 kV phase-to-phase;
10,000 amps rms symmetrical, 10 cycles,
(0.17 seconds).
One fault-close operation at 21.1 kV phase-to-ground, or 36.6 kVphase-to-phase;
10,000 amps rms symmetrical, 10 cycles,
(0.17 seconds).
ALL VOLTAGE CLASSES PRODUCTION TESTS
100% factory test for partial discharge
100% factory test for partial discharge and either AC
Hi-Pot (34kV for 60 seconds) or impulse (BIL)
(95kV 1.2 x 50µ sec.).
100% factory test for partial discharge and either AC
Hi-Pot (45kV for 60 seconds) or impulse (BIL) 125kV, 1.2 x
50 microsecond wave.
100% factory test for partial discharge and either AC
Hi-Pot (50kV for 60 seconds).
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive| Johnstown, Ontario K0E 1T1
© PRYSMIAN - A Brand of The Prysmian Group 2016. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued January 2016.
12
2016
-04-
12
Body Part No.
Cable Insulation Diameter Range (in.) 5kV 100% 5kV 133% / 8kV 100% 8kV 133% 15kV 100% 15kV 133%
15LB_3 0.498-0.730 #2 AWG - 4/0 AWG #4 AWG - 3/0 AWG #4 AWG - 2/0 AWG #4 AWG to 1/0 AWG -
15LB_4 0.635-0.905 2/0 AWG - 250 kcm 2/0 AWG - 250 kcm 1/0 AWG - 250 kcm #2 AWG - 2/0 AWG #2 AWG - 2/0 AWG
15LB_5 0.760-1.135 - - - 3/0 AWG - 250 kcm 3/0 AWG - 250 kcm
Body Part No.
Cable Insulation Diameter Range (in.) 25kV 100% 25kV 133%/28kV
100% 28kV 133%
2528LB_3 0.610-0.880 #4 AWG - #1 AWG #4 AWG -
2528LB_4 0.800-1.140 #1 AWG - 2/0 AWG #1 AWG - 2/0 AWG -
2528LB_5 0.920-1.310 3/0 AWG - 250 kcm 3/0 AWG - 250 kcm -
2528LB_5A 0.920-1.310 - - 1/0 AWG - 250 kcm
Body Part No.
Cable Insulation Diameter Range (in.) 35kV 100% 35kV 133%
35LB_5 1.020-1.310 1/0 AWG - 250 kcm 1/0 AWG - 4/0 AWG
Note: Replace " _" with "CN" for Conentric Neutral Cable Example: For a 2/0 AWG Stranded 15kV 100% Cable with CN use body 15LBCN4-200LB6
Note : Replace "_" with "CTS" for Copper Tape Shield or LC Shield CablesExample: For a 250 AWG Compact 15kV 133% Cable with LC or Copper Tape Shield use body 15LBCTS4-200LB8
Part No. Stranded / Compressed Compact / Solid
200LB1 #6 AWG #4 AWG
200LB2 #4 AWG, #3 AWG #3 AWG, #2 AWG
200LB3 #2 AWG #1 AWG
200LB4 #1 AWG 1/0 AWG
200LB5 1/0 AWG 2/0 AWG
200LB6 2/0 AWG 3/0 AWG
200LB7 3/0 AWG 4/0 AWG
200LB8 4/0 AWG 250 kcm
200A Connector Code
200A Loadbreak Elbows with Test Point
Remember to add the required lug to the body part number per the Connector Table.
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1
2016
-02-
01
13
600A Deadbreak Series(15kV/25kV)
Interchangeability The Deadbreak Elbow has been designed and tested to meet the requirement of IEEE Standard 386. Conformance to this industry standard ensures mechanical and electrical interchangeability with other products of manufacturers that are also in conformance with the standard.
General Information
The 600-amp Deadbreak Elbow and accessories offer an easy and reliable method of terminating and splicing main feeder circuits. The Deadbreak Elbow is a fully shielded, molded rubber connector.
The Deadbreak Elbow is designed to terminate power cables with copper or aluminum conductors ranging in sizes from #2 AWG to 1250 kcm. It may be installed on any 600-Amp rated (aluminum) apparatus bushing that meets IEEE Standard 386 latest revision for Separable Insulated Connectors. Cable adapters accommodate power cable insulation diameters from 0.530 to 1.935 inches.
Electrical Ratings MEETS OR EXCEEDS IEEE STANDARD 386 - Latest Revision
Continuous Current Rating (Aluminum Components) 600 amps
Voltage Class 25kV
Max Phase to Ground Voltage - Operating Voltage 15.2kV
Max Phase to Phase Voltage 26.3kV
Basic Impulse Level (1.2x50μs) 125kV
Corona Extinction (3pC) 19kV
AC Withstand Voltage (1 min.) 40kV
DC Withstand Voltage (15 min.) 78kV
24 Hour Overload 1,000 Amps rms
Short-Circuit Time Rating25,000 Amps rms symmetrical for 0.17 sec.10,000 Amps rms symmetrical for 3.00 sec.
100% Production Test
Corona (3pC) 19kV
AC Withstand (1 min.) 40kV
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 14
2016
-02-
01
600-Amp Deadbreak (15/25kV)
Features
1. Cable Adapter - Molded of peroxide cured EPDM rubber. Designedto accept specified cable insulation diameters. Radial pressure exerted on the cable insulation by the cable adapter precludes the presence of corona causing air voids along the cable adapter and cable insulation interface. The outside diameter of the cable adapter is constant for all cable adapter sizes.
2. Compression Connector -Aluminum (600 amp). Sized for thespecific conductor size. Crimped with standard tools and dies.
3. Test Point -Designed to allow voltage indication when readout is made with suitable high impedance measuring devices. Elbows areavailable with and without this feature.
4. Insulating Plug Cap -Molded of conductive peroxide cured EPDMrubber providing a continuous outer shield for the elbow. Snaps tightly over the test point and onto the elbow body.
5. Epoxy Insulating Plug -Hex nut located on top of the insulatingplug is used to tighten the plug when assembling the elbow.
6. Hex Nut -One-inch hex head is used to tighten the connection.Can also be used as a capacitive test point. See #3 above.
7. Molded External Shield -Conductive, abrasion-resistant shield of peroxide cured EPDM rubber. Provides ground shield continuity andmeets the requirements of IEEE Standard 592.
8. Drain Wire Tab -Designed to accept a single #14 AWG copper wire that can be inserted into the eye. Provides a static ground toensure deadfront construction.
9. Stress Relief Cone -Designed into the cable adapter providing electrical stress relief at the point of terminating the power cableshield. Controls the electrical field entering the elbow.
10. EPDM Insulation -Peroxide cured EPDM rubber.
11
1
2
5
3
4
9
8
7
6
10
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive| Johnstown, Ontario K0E 1T1
© PRYSMIAN - A Brand of The Prysmian Group 2016. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued January 2016.
15
2016
-02-
01
Part No.Cable Range
Insulation Diameter (In)
5kV 100% 5kV 133% / 8kV 100% 8kV 133% 15kV 100% 15kV 133% 25kV 100% 25kV 133%
1525DB_E 0.530 - 0.675 #1 AWG - 2/0 AWG #2 AWG - 2/0 AWG #1 AWG - 1/0 AWG #2 AWG - - -
1525DB_F 0.640 - 0.840 3/0 AWG - 350 kcm 2/0 AWG - 250 kcm 1/0 AWG - 4/0 AWG #2 AWG - 3/0 AWG #2 AWG - 1/0 AWG - -
1525DB_G 0.760 - 0.950 350 kcm - 500 kcm 4/0 AWG - 350 kcm 4/0 AWG - 250 kcm 2/0 AWG - 250 kcm #1 AWG - 3/0 AWG #1 AWG - 2/0 AWG -
1525DB_H 0.850 - 1.050 500 kcm 350 kcm - 500 kcm 250 kcm - 350 kcm 4/0 AWG - 350 kcm 2/0 AWG - 250 kcm 1/0 AWG - 4/0 AWG #1 AWG - 1/0 AWG
1525DB_J 0.980 - 1.180 750 kcm 500 kcm 500 kcm 350 kcm - 500 kcm 250 kcm - 350 kcm 4/0 AWG - 250 kcm 1/0 AWG - 4/0 AWG
1525DB_K 1.090 - 1.310 750 kcm 750 kcm 750 kcm 500 kcm 350 kcm - 500 kcm 350 kcm - 500 kcm 3/0 AWG - 250 kcm
1525DB_L 1.180 - 1.465 750 kcm - 1000 kcm 750 kcm - 1000 kcm 750 kcm - 1000 kcm 750 kcm 500 kcm - 750 kcm 500 kcm 250 kcm - 500 kcm
1525DB_M 1.370 - 1.630 - - - 1000 kcm -1250 kcm 1000 kcm 750 kcm 500 kcm - 750 kcm
1525DB_N 1.515 - 1.780 - - - 1250 kcm 1000 kcm - 1250 kcm 1000 kcm 750 kcm - 1000 kcm
1525DB_P 1.725 - 1.935 - - - - - 1250 kcm 1000 kcm - 1250 kcm
Note: Replace " _" with "CN" for Conentric Neutral Cable Example: For a 1/0 AWG Compact 15kV 100% Cable with CN use body 1525DBCNF-600DB23
Note : Replace "_" with "CTS" for Copper Tape Shield or LC Shield CablesExample: For a 500 kcm 25kV Stranded 133% Cable with LC or Copper Tape Shield use body 1525LBCTSB-600DB33
Part No. Stranded / Compressed Compact / Solid Part No. Stranded / Compressed Compact / Solid
600DB22 #2 #1 600DB32 450 500/550
600DB23 #1 1/0 600DB33 500 600
600DB24 1/0 2/0 600DB34 550 650
600DB25 2/0 3/0 600DB35 600 700
600DB26 3/0 4/0 600DB36 650 750
600DB27 4/0 250 600DB38 700/750 900
600DB28 250 300 600DB39 800 –
600DB29 300 350 600DB40 900 1000
600DB30 350 400 600DB41 1000 –
600DB31 400 450 600DB44 1250 –
Connector Code Chart
600A Deadbreak T-Bodies
Remember to add the required lug to the body part number per the Connector Table.
A40
7 20
18-0
2-22
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1 16
A brand of the
MV Cable AccessoriesPre-Attached Single-Use Cable Pulling Lugs
Key Benefits
• Beveled edge for easier pulls around corners.
• Use once and then recycle along with scrap wire.
• Available in 18 sizes (8 AWG through 1000 mcm) to be used in sets to accommodate jobs of different sizes.
• Works on 600 volts through 35 KV wire and rated for both copper and aluminum wire.
• The lanyards are available in a variety of lengths to make staggering multiple wire pulls effortlessespecially through and around nineties.
• The small pulling head reduces friction - no need to oversize conduit to accommodate the pulling head.
• Installed in the factory.
• Items highlighted are for 1/C Cables (shortest lanyard)
• Additional lanyards can be added for 1/C Triplexed and Paralleled cable configurations up to 4X 1/C
Simple, Easy, Reliable, Durable, Low Cost
Prysmian Group 700 Industrial Drive | Lexington, SC 29072 | +1-800-845-8507 | website: na.prysmiangroup.com 137 Commerce Drive | Johnstown, Ontario K0E 1T1
© PRYSMIAN - A Brand of The Prysmian Group. 2018. All Rights Reserved. The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed correct at the time of issue. Prysmian Group reserves the right to amend any specifications without notice. These specifications are not contractually valid unless authorized by Prysmian Group. Issued February 2018.
A40
7 20
18-0
2-22
17
A brand of the
MV Cable AccessoriesPre-Attached Single-Use Cable Pulling LugsProduct Selection Chart
Product DescriptionCatalog Number
Maximum Loading Per Phase
SU 8 AWG Pulling Eye w/11” lanyard 98120 130
SU 8 AWG Pulling Eye w/15” lanyard 98117 130
SU 8 AWG Pulling Eye w/19” lanyard 98118 130
SU 8 AWG Pulling Eye w/23” lanyard 98119 130
SU 6 AWG Pulling Eye w/11” lanyard 98137 210
SU 6 AWG Pulling Eye w/15” lanyard 98138 210
SU 6 AWG Pulling Eye w/19” lanyard 98139 210
SU 6 AWG Pulling Eye w/23” lanyard 98140 210
SU 4 AWG Pulling Eye w/11” lanyard 98133 300
SU 4 AWG Pulling Eye w/15” lanyard 98134 300
SU 4 AWG Pulling Eye w/19” lanyard 98135 300
SU 4 AWG Pulling Eye w/23” lanyard 98136 300
SU 3 AWG Pulling Eye w/11” lanyard 98129 400
SU 3 AWG Pulling Eye w/15” lanyard 98130 400
SU 3 AWG Pulling Eye w/19” lanyard 98131 400
SU 3 AWG Pulling Eye w/23” lanyard 98132 400
SU 2 AWG Pulling Eye w/11” lanyard 98125 500
SU 2 AWG Pulling Eye w/15” lanyard 98126 500
SU 2 AWG Pulling Eye w/19” lanyard 98127 500
SU 2 AWG Pulling Eye w/23” lanyard 98128 500
SU 1 AWG Pulling Eye w/11” lanyard 98121 669
SU 1 AWG Pulling Eye w/15” lanyard 98122 669
SU 1 AWG Pulling Eye w/19” lanyard 98123 669
SU 1 AWG Pulling Eye w/23” lanyard 98124 669
SU 1/0 AWG Pulling Eye w/14” lanyard 98141 844
SU 1/0 AWG Pulling Eye w/21” lanyard 98142 844
SU 1/0 AWG Pulling Eye w/28” lanyard 98143 844
SU 1/0 AWG Pulling Eye w/35” lanyard 98144 844
SU 2/0 AWG Pulling Eye w/14” lanyard 98145 1000
SU 2/0 AWG Pulling Eye w/21” lanyard 98146 1000
SU 2/0 AWG Pulling Eye w/28” lanyard 98147 1000
SU 2/0 AWG Pulling Eye w/35” lanyard 98148 1000
SU 3/0 AWG Pulling Eye w/14” lanyard 98149 1250
SU 3/0 AWG Pulling Eye w/21” lanyard 98150 1250
SU 3/0 AWG Pulling Eye w/28” lanyard 98151 1250
SU 3/0 AWG Pulling Eye w/35” lanyard 98152 1250
Product DescriptionCatalog Number
Maximum Loading Per Phase
SU 4/0 AWG Pulling Eye w/14” lanyard 98153 1650
SU 4/0 AWG Pulling Eye w/21” lanyard 98154 1650
SU 4/0 AWG Pulling Eye w/28” lanyard 98155 1650
SU 4/0 AWG Pulling Eye w/35” lanyard 98156 1650
SU 250 MCM Pulling Eye w/14” lanyard 98157 2000
SU 250 MCM Pulling Eye w/21” lanyard 98158 2000
SU 250 MCM Pulling Eye w/28” lanyard 98159 2000
SU 250 MCM Pulling Eye w/35” lanyard 98160 2000
SU 300 MCM Pulling Eye w/14” lanyard 98161 2400
SU 300 MCM Pulling Eye w/21” lanyard 98162 2400
SU 300 MCM Pulling Eye w/28” lanyard 98163 2400
SU 300 MCM Pulling Eye w/35” lanyard 98164 2400
SU 350 MCM Pulling Eye w/14” lanyard 98165 2400
SU 350 MCM Pulling Eye w/21” lanyard 98166 2400
SU 350 MCM Pulling Eye w/28” lanyard 98167 2400
SU 350 MCM Pulling Eye w/35” lanyard 98168 2400
SU 400 MCM Pulling Eye w/14” lanyard 98169 2400
SU 400 MCM Pulling Eye w/21” lanyard 98170 2400
SU 400 MCM Pulling Eye w/28” lanyard 98171 2400
SU 400 MCM Pulling Eye w/35” lanyard 98172 2400
SU 500 MCM Pulling Eye w/14” lanyard 98173 4000
SU 500 MCM Pulling Eye w/21” lanyard 98174 4000
SU 500 MCM Pulling Eye w/28” lanyard 98175 4000
SU 500 MCM Pulling Eye w/35” lanyard 98176 4000
SU 600 MCM Pulling Eye w/14” lanyard 98177 4200
SU 600 MCM Pulling Eye w/21” lanyard 98178 4200
SU 600 MCM Pulling Eye w/28” lanyard 98179 4200
SU 600 MCM Pulling Eye w/35” lanyard 98180 4200
SU 750 MCM Pulling Eye w/14” lanyard 98181 4300
SU 750 MCM Pulling Eye w/21” lanyard 98182 4300
SU 750 MCM Pulling Eye w/28” lanyard 98183 4300
SU 750 MCM Pulling Eye w/35” lanyard 98184 4300
SU 1000 MCM Pulling Eye w/14” lanyard 98185 5000
SU 1000 MCM Pulling Eye w/21” lanyard 98186 5000
SU 1000 MCM Pulling Eye w/28” lanyard 98187 5000
SU 1000 MCM Pulling Eye w/35” lanyard 98188 5000
CONTACT INFORMATION
Inside Sales: (800) 845 8507
Fax Number: (803) 951 1126
Web: na.prysmiangroup.com
E-mail: [email protected]