Medium Voltage Distribution Catalogue | 2014 LBSkit

32
LBSkit Medium Voltage Distribution Catalogue | 2014 MV Indoor switches and disconnectors up to 36 kV

Transcript of Medium Voltage Distribution Catalogue | 2014 LBSkit

Page 1: Medium Voltage Distribution Catalogue | 2014 LBSkit

LBSkitMedium Voltage DistributionCatalogue | 2014

MV Indoor switchesand disconnectors up to 36 kV

Page 2: Medium Voltage Distribution Catalogue | 2014 LBSkit
Page 3: Medium Voltage Distribution Catalogue | 2014 LBSkit

1

LBSkit Contents

The experience of a world leader 2

The product’s advantages 3

Technical characteristics 4

Dimensions and weightsfor 12-24 kVfor 36 kV

556

Safety of peopleBy switchgearBy operating mechanism safety

778

Operating mechanisms 9

Auxiliaries 10

Interlocks 11

Installation Guides 12

Selection Guide for 12-24 kVSwitch function 1 to 24 kV, 630 AFuse-switch function 1 to 24 kV, 630 ADisconnector function 1 to 24 kV

13131415

Order form for 12-24 kVComponents

1616

Selection Guide for 36 kVSwitch function 36 kV, 630 AFuse-switch function 36 kV, 630 ADisconnector function 36 kV, 630-1250 A

21212223

Order form for 36 kVComponents

2424

AMTED306003EN.indd

Page 4: Medium Voltage Distribution Catalogue | 2014 LBSkit

2

LBSkit The experience of a world leader

The Schneider Electric group’s experience extends over 35 years in SF6 technology for Medium Voltage switchgear.

This gives you the advantage of unique experience, that of a world leader, with over 2,700,000 SF6 Medium Voltage units installed throughout the world.

Putting this experience at your service and remaining attentive to your requirements is the spirit of active partnership that we want to develop in offering you the LBSkit.

LBSkit is a product to let you develop harmonized functions equipped with SF6 breaking technology switchgear. These functions allow you to produce all your Medium Voltage substation requirements up to 36 kV.The result of in-depth analysis of your requirements, both now and in the future, LBSkit means that you can take advantage of all the features of both a modern and proven technology.

PE

5635

0Commercial referencesIran Tabesh tablou, Teheran utilityRussiaMEL, Moscow utilityCanada AVAD, OntarioSweden KL Industry, Eon utility, FortumTurkey CIMTAV, IstanbulElpa, IstanbulELTES, AnkaraAYSAN, AnkaraAktif Energy, AnkaraEUROPOWER, AnkaraSETMAS, AnkaraELKO, AnkaraULUSOY, AnkaraUYAN, IzmirAlgeria EDIEL, AlgierThailand ASEFA, BangkokIndia Telawne Power Equipments, BombayChina Beijing Tongzhou SwitchgearEast China ElectricalGuangzhou South Power Group ElectricalBrazilPrecisa Industrial, Rio de Janeiro

AMTED306003EN.indd

Page 5: Medium Voltage Distribution Catalogue | 2014 LBSkit

3

LBSkit The product’s advantages

UpgradabilityLBSkit, a comprehensive product

b A comprehensive product covering your present and future requirements b A design adapted to the extension of your units b A catalogue of components for all your applications b A product designed to be in compliance with standards constraints b Options to anticipate the control and monitoring of your units.

CompactnessLBSkit, an optimised product

b Compact components, for reduced increment units b Rationalised space requirement for switchboard installation.

MaintenanceLBSkit, a product with reduced maintenance

b The active parts (breaking and earthing) are integrated in an SF6-filled, “sealed for life” unit

b The control mechanisms, are intented to function with reduced maintenance under normal operating conditions

b Enhanced electrical endurance when breaking.

Ease of installationLBSkit, a simple product to incorporate

b Reduced dimensions and weights b A solution adapted to cable connection b Simplified switchboard busbar connection.

Ease and safe to operateLBSkit, a well-proven product

b A three position switch to prevent incorrect operating b The earthing disconnector has full closing capacity b Positive breaking of position indicators b Clear and animated display mimics b Switching lever with an “anti-reflex” function.

LBSkit: a product designed with control and monitoring in mindLBSkit is perfectly adapted to control and monitoring applications. Motorised, option available, LBSkit combines with remote control interface. You, therefore, benefit from a ready-to connect unit that is easy to incorporate providing guaranteed operation.

LBSkit: a product with adapted fuse-switch protectionWith the LBSkit, Schneider Electric proposes components for MV protections with fuses. Fusarc CF fuse range is an excellent solution to protect various types devices such as MV transformers, motors, capacitors, public and industrial distribution networks.

AMTED306003EN.indd

Page 6: Medium Voltage Distribution Catalogue | 2014 LBSkit

4

LBSkit Technical characteristics

General characteristicsRated voltage (kV) 7.2 12 17.5 24 36Insulation level *

50 Hz - 1 min(kV r ms)

Insulation 20 28 38 50 70Isolation 23 32 45 60 80

1.2/50 ms(kV peak)

Insulation 60 75 95 125 170Isolation 70 85 110 145 195

Short-time withstand current Switch (kA/1 s) 25 630 A

20 630 A16 630 A12.5 630 A

Disconnector (kA/1 s) 25 630 - 1250 A 1250 A20 630 - 1250 A16 630 - 1250 A12.5 630 - 1250 A

Maximum breaking capacityTransformer off load (A) 16Cables off load (A) 31.5 50 Switch (A) 630 Fuse-switch ** (kA) 25 20

The making capacity is equal to 2.5 times the short-time withstand current.(*) Equipped referring to installation guide, and setting up at an altitude below 1000 m. (**) Depending on fuse characteristics, and on using of Schneider Electric Fusarc CF fuses.

EnduranceUnits Mechanical

enduranceElectrical endurance

SwitchFuse-switch

IEC62271-1031000 operationsClass M1

IEC62271-103100 breaks at In, p.f. = 0.7Class E3

Disconnector IEC 62271-1021000 operations

TemperaturesThe products must be stored in a dry area free from dust and with limited temperature variations

b for stocking: from –40°C to +70°Cb for working: from –5°C to +40°Cb other temperatures, consult us

StandardsLBSkit units meet all the following recommendations:

b Switch:IEC62271-103: High voltage switches - Part 1: switches for rated voltages above 1 kV and less or equal to 52 kV.

b Disconnector:IEC 62271-102: High-voltage alternating current disconnectors and earthing switches.

b Switch /disconnector: IEC 62271-200: A.C. metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to including 52 kV.

b VPIS:IEC 62271-206: High-voltage prefabricated switchgear and controlgear assemblies-Voltage presence indicating systems

In addition to its technical characteristics, LBSkit is designed for indoor applications, and meets requirements concerning human safety as well as ease of installation, operation and protection of the environment.

PE

5636

0

Switch and earthing switch 12-24 kV

PE

5637

3

Switch and earthing switch 36 kV

AMTED306003EN.indd

Page 7: Medium Voltage Distribution Catalogue | 2014 LBSkit

5

LBSkit

LBSkit 12-24 kV630 A switch - 630 A disconnector Weight: 50 kg

Below view Side view Front view

DE

5715

1

72D

E58

867

202

940

840

365

350220 200 200

417.5

213

190

1250 A disconnector Weight: 51 kg

Below view Side view Front view

DE

5715

3

72

DE

5886

8

191

940 365

350220 200 200

417.5

213

190

840

Dimensions and weightsfor 12-24 kV

AMTED306003EN.indd

Page 8: Medium Voltage Distribution Catalogue | 2014 LBSkit

6

LBSkit 36 kV630 A switch - 630 A disconnector (width 750 mm) Weight: 75 kg

Below view Side view Front view

DE

5883

1

DE

5886

9 1342.5 720700

290

307.6

136

207 395.5

352.595 350 350

1250 A disconnector (width 750 mm) Weight: 76 kg

Below view Side view Front view

DE

5883

3

DE

5887

0 1342.5 720700

279

307.6

136

207 395.5

352.595 350 350

630 A disconnector (width 1000 mm) Weight: 75.5 kg

Below view Side view Front view

DE

5883

5

DE

5887

1 1342.5 970950

290

307.6

136

207 395.5

352.595 350 350350

1250 A disconnector (width 1000 mm) Weight: 76.5 kg

Below view Side view Front view

DE

5883

7

DE

5887

2 1342.5

279

307.6

352.595 350 350970950

136

207 395.5

350

LBSkit Dimensions and weightsfor 36 kV

AMTED306003EN.indd

Page 9: Medium Voltage Distribution Catalogue | 2014 LBSkit

7

LBSkit Safety of peopleBy switchgear

Switch or disconnector and earthing switchb Gas tightnessThe three rotating contacts are placed in an enclosure filled with gas to a relative pressure of 0.4 bar (400 hPa) for LBSkit 12-24 kV and 1 bar (1000 hPa) for LBSkit 36 kV. It satisfies “sealed pressure system” requirements and seal tightness is always factory checked.

b Operating safety v the switch may be in one of three positions: “closed”, “open”, or “earthed”,

representing a natural interlocking system that prevents incorrect operation.Moving-contact rotation is driven by a fast-acting mechanism that is independent of the action of the operator.

v the device combines the breaking and disconnection functions. v the earthing switch placed in the SF6 has a short-circuit making capacity,

in compliance with standards. v any accidental over-pressures are eliminated by the opening of the safety

membrane, in which case the gas is directed toward the back of the unit, away from the operator.

MT2

0184

Closed position Open position Earth position

6102

9N

Switch 12-24 kV

PE

5635

7

Switch 36 kV

AMTED306003EN.indd

Page 10: Medium Voltage Distribution Catalogue | 2014 LBSkit

8

LBSkit Safety of peopleBy operating mechanism safety

Reliable operating mechanismb Switchgear status indicator: Fitted directly to the drive shaft, these give a definite indication of the contact’s position. (appendix A of standard IEC 62271-102).b Operating lever: This is designed with an anti-reflex device that stops any attempt to re-open the device immediately after closing the switch or the earthing disconnector.b Locking device: Between one and three padlocks enable the following to be locked:v access to the switching shaft of the switch or the circuit breakerv access to the switching shaft of the earthing disconnectorv operating of the opening release push-button.

Simple and effortless switchingMechanical and electrical controls are side by side on the front of the panel including the schematic diagram indicating the device’s status (closed, open, earthed):b Closed: the drive shaft is operated via a quick acting mechanism, independent of the operator. No energy is stored in the switch, apart from when switching operations are taking place.For combined switch fuses, the opening mechanism is armed at the same time as the contacts are closed.b Opening: the switch is opened using the same quick acting mechanism, operated in the opposite direction.For a combined switch fuses unit, opening is controlled by: v a push-buttonv a fault.b Earthing: a specific control shaft enables the opening or closing of the earthing contacts. Access to this shaft is blocked by a cover that can be slid back if the switch is open but which remains locked in place if it is closed.

Voltage Presence Indicating SystemVPIS complies with IEC 62271-206 standard allowing to indicate the voltage presence on each phase with LEDs. Designed for harsh environments so that to guarantee high reliability in MV swithgears worldwide.

Insensitivity to the environmentb An internal sealed enclosure, contains the active parts of the LBSkit (switch, earthing disconnector). It is filled with SF6 in accordance with the definitions in IEC recommendation 62271-200 for “sealed pressure systems”. Sealing is systematically checked in the factory. b Parts are designed in order to obtain optimum electrical field distribution.

PE

5635

1

Operating mechanism cover for LBSkit 12-24 kV

PE

5636

6

AMTED306003EN.indd

Page 11: Medium Voltage Distribution Catalogue | 2014 LBSkit

9

LBSkit Operating mechanisms

Double-function operating mechanism CITb Switch function Independent-operation opening or closing by lever or motor.b Earthing-switch function Independent-operation opening or closing by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close.b Auxiliary contactsv switch (2 O + 2 C) *v switch (2 O + 3 C) and earthing switch (1 O + 1 C).b Motor option

Double-function operating mechanism CI1b Switch function v independent-operation closing by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to close.v independent-operation opening by push-button (O) or trip units.b Earthing-switch function Independent-operation closing and opening by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close.b Auxiliary contactsv switch (2 O + 2 C) v switch (2 O + 3 C) and earthing switch (1 O + 1 C).b Opening releasesv shunt trip.

Double-function operating mechanism CI2b Switch function v independent-operation closing in two steps:1 - operating mechanism recharging by lever or motor2 - stored energy released by push-button (I) or trip unit.v independent-operation opening by push-button (O) or trip unit.b Earthing-switch functionIndependent-operation closing and opening by lever.Operating energy is provided by a compressed spring which, when released, causes the contacts to open or close.b Auxiliary contactsv switch (2 O + 2 C) * v switch (2 O + 3 C) and earthing switch (1 O + 1 C).b Opening release shunt tripb Closing release shunt tripb Motor option

Double-function operating mechanism CSb Switch and earthing-switch functionsDependent-operation opening and closing by lever.b Auxiliary contactsv disconnector (2 O + 2 C).

Example of functions Type of operating mechanism assembled with the switch

Load break switch CIT CI2Disconnector CSFuse switch combination CI2

(*) Included with the motor option.

PE

5636

1P

E56

362

PE

5636

3P

E56

364

AMTED306003EN.indd

Page 12: Medium Voltage Distribution Catalogue | 2014 LBSkit

10

LBSkit Auxiliaries

Motor option and releases for switch-unitsThe operating mechanisms CIT and CI2 may be motorised.

Un DC AC (50/60 Hz)Power supply (V) 24 48 110 220Motor option

(W) 200(VA) 200

Operating time for CIT (s) 1 to 2 1 to 2and charging time for CI2 (s) 4 to 7 4 to 7Opening releases

Shunt trip (W) 200 250 300(VA) 750

Response time (ms) 35 35Closing release

Shunt trip (W) 200 250 300(VA) 750

Response time (ms) 55 55

Example of applications for main line switching

Types of operating mechanismWithout motor With motor

Manual operation With lever CITWith push button CI2Remote control

For network management without need of quick opening and closing

CIT

For network management for quick switching (generator, loop) or transformer protection

CI2

PE

5636

4

AMTED306003EN.indd

Page 13: Medium Voltage Distribution Catalogue | 2014 LBSkit

11

LBSkit Interlocks

Functional interlocksThese comply with IEC recommendation 62271-200.In addition to the functional interlocks, each disconnector and switch include built-in padlocking capacities (padlocks not supplied).

Switch/disconnector built-in interlocksb The switch can be closed only if the earthing switch is open and the access panel is in closed position.b The earthing switch can be closed only if the switch is open.b The access panel for connections can be opened only if the earthing switch is closed.b The switch is locked in the open position when the access panel is removed. The earthing switch may be operated for tests.

Key-type interlocks

Type C4: transformer protection

DE

5861

5

S

SO

O

Aimb To prevent the closing of the earthing switch on a transformer protection unit unless the LV circuit breaker is locked in “open” or “disconnected” position.b To prevent the access to the transformer if the earthing switch for transformerprotection has not first been closed.

Type P1: ring units

DE

5862

0

X

O

O

X

Aimb To prevent the closing of an earthing switch if the switch of the other unit has not been locked in the “open” position.

Type A3: ring units

DE

5861

6

O

O

Aimb To prevent the closing of the earthing switch of a load-side cubicle unless the line-side switch is locked “open”.

MT2

0240

EN

Legend for key-type interlocks:no key free key captive key panel or door

AMTED306003EN.indd

Page 14: Medium Voltage Distribution Catalogue | 2014 LBSkit

12

LBSkit Installation Guides

The Installation Guides have been written for “Panel Builders” who have to design, realize, inspect and maintain own functions with LBSkit in compliance with international standards of the International Electrotechnical Commission (IEC).

The Installation Guides are single documents covering the assembly of LBSkit and related components and recommendations. They are intended for Panel Builders who want to develop their own functions, then a range using LBSkit.

An international standard such as the IEC 62271-200 “A.C. metal-enclosed switchgear and controlgear for rated voltage above 1 kV and up to including 52 kV” specifi es extensively the rules to comply with to ensure safety and predicted operational characteristics for all types of electrical applications. As the standard must be extensive and has to be applicable to all types of products and technical solutions in use worldwide, the text of the IEC rules is complex, and not presented in a ready-to-use order. The standard can not therefore be considered as a working handbook, but only as a reference document.

Electrical equipment should be designed, realized and used only by qualifi ed persons, and “Installation Guides” should not be viewed as suffi cient instructions for those who are not qualifi ed to design, realize, use or maintain the components discussed. Although reasonable care has been taken to provide accurate and authoritative information in these documents, no reponsibility is assumed by Schneider Electric for any consequences arising from the use of that material.

PE56370

Ref: EIGED306001EN

PE40623

Ref: CG0021EN

PE56372

Ref: 07897615EN for LBSkit 12-24 kV Ref: 51254701EN for LBSkit 36 kV

AMTED306003EN.indd

Page 15: Medium Voltage Distribution Catalogue | 2014 LBSkit

Operating mechanism

Assembled switch and operating mechanism without motor (basic offer)Assembled switch and operating mechanism with motor (basic offer)Auxiliary voltage: 24 VDC

48 VDC

110 VDC

220 VAC

Coil kitsCoil type:

Auxiliary voltage: 24 VDC

48 VDC

110 VDC-220 VAC

Operating mechanism cover

Auxiliary contacts: 4 AC : 2O-2C switch

7 AC : 2O-3C switch+ 1O-1C earthing switch

Operating mechanism handle

Upper field distributors

Connection for one cable (3 pieces per unit)

Capacitive dividers

Voltage presence indicator Operating voltage: 3.1 to 5.9 kV

6 to 8.9 kV9 to 17.9 kV18 to 24 kV

Voltage presence indicator wiring

Busbar field distributors

Interlocking and lock kits

Lock type:

Interlocking type: A3

P1

(*) See drawing in Installation Guide

13

CIT CI1 CI2

3730109AU

3730109AV

3730109AW

3730109AX

3730109AC

Without Opening release

3730304B+ 3730333A

3730304B+ 3730335A

3730304B+ 3730332A

51238920FA(1 piece)

3730109AB

3730109AY

3730109AZ

3730109BA

3730109BB

3730109AD

Without

3730300B

3730300B+ 3730301B

51238920FA(1 piece)

Included in motorized

switch

51238920FB(1 piece)

3730300B

3730300B+ 3730301B

51238920FB(1 piece)

3730307B

3730307B+ 3730308B

51238920FE(1 piece)

3730300B

3730300B+ 3730301B

51238920FE(1 piece)

Metal cover manufactured by customer *

3730307B

3730307B+ 3730308B

51238920FE(1 piece)

3728693

LBSkit Selection Guide for 12-24 kVSwitch function 1 to 24 kV, 630 A

Opening/closingrelease

(included in motorized switch)

Opening/closingrelease

3730305B+ 3730338A

3730305B+ 3730340A

3730305B+ 3730337A

Without

3736435

3 pieces out of 51238497FA

3 pieces out of 51238495FA

VPI 62404

VPI 62407

BBV 19686

3729742 (include 3 pieces)

3730352B + 37314403730351B + 3731440

3730352B + 37316403730351B + 3731640

Included in motorized

switch

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Without

VPI 62405

VPI 62408

Tubular key type

Flat key type

1 piece out of51238920FA

1 piece out of51238920FA

1 piece out of51238920FB

1 piece out of51238920FB

1 piece out of51238920FE

1 piece out of51238920FE

1 piece out of51238920FE

AMTED306003EN.indd

Page 16: Medium Voltage Distribution Catalogue | 2014 LBSkit

Operating mechanism

Assembled switch & operating mechanism without motor (basic offer)

Assembled switch & operating mechanism with motor (basic offer)Auxiliary voltage: 24 VDC

48 VDC

110 VDC

220 VAC

Coil kitsCoil type:

Auxiliary voltage: 24 VDC

48 VDC

110 VDC-220 VAC

Operating mechanism cover

Auxiliary contacts: 4 AC : 2O-2C switch

7 AC : 2O-3C switch+ 1O-1C earthing switch

Operating mechanism handle

Upper field distributors

Earthing switch 2 kA for DIN fuses 12 kV > Ur ≤ 24 kV for DIN fuses Ur ≤ 12 kV

DIN fuse holder and field distributors

Capacitive dividers

Fuse trip system

Voltage presence indicator Operating voltage: 3.1 to 5.9 kV

6 to 8.9 kV9 to 17.9 kV18 to 24 kV

Voltage presence indicator wiring

Busbar field distributors

Interlocking and lock kitsLock type:

Interlocking type: A3

P1

C4

(*) See drawing in Installation Guide

14

LBSkit Selection Guide for 12-24 kVFuse-switch function 1 to 24 kV, 630 A

CI1 CI2

3730109AC

Without Opening release

3730304B+ 3730333A

3730304B+ 3730335A

3730304B+ 3730332A

3730109AY

3730109AZ

3730109BA

3730109BB

3730109AD

1 piece out of51238920FC

3730300B

3730300B+ 3730301B

1 piece out of51238920FC

3730306B

3730306B+ 3730308B

1 piece out of51238920FF

3730300B

3730300B+ 3730301B

1 piece out of51238920FF

Metal cover manufactured by customer *

3730306B

3730306B+ 3730308B

1 piece out of51238920FF

3728693

Opening/closing release

(included in motorized switch)

Opening/closing release

3730305B+ 3730338A

3730305B+ 3730340A

3730305B+ 3730337A

Without

Included in earthing switch kit (3 pieces)

Included in earthing switch kit (3 pieces)

51238922FA

3 pieces out of51238497FA

3 pieces out of51238495FA

BBV 19686

3729742 (3 pieces included)

3730352B + 3731440

3730351B+ 3731440

Tubular key type

Flat key type

3730352B + 3731640

3730351B + 3731640

Included in motorized

switch

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

3 pieces out of51238498FA

Included in earthing switch kit (3 pieces)

51238921FA51238921FA

3730350B +

BBV23780+ 3731439

3730350B +

BBV23781+ 3731639

VPI 62404

VPI 62407VPI 62405

VPI 62408

51238922FB

CIT

3730109AU

3730109AV

3730109AW

3730109AX

3730109AB

3730300B

3730300B+ 3730301B

Without Without

Included in motorized

switch

Metal cover manufactured by customer *

Metal cover manufactured by customer *

1 piece out of51238920FG

1 piece out of51238920FG

AMTED306003EN.indd

Page 17: Medium Voltage Distribution Catalogue | 2014 LBSkit

(*) See drawing in Installation Guide

Operating mechanism

Assembled switch and operating mechanism (basic offer)Rated current: 630 A

1250 A

Operating mechanism cover

Auxiliary contacts: 4 AC : 2O-2C switch

Operating mechanism handle

Upper field distributors (3 pieces per unit)

Connection for one cable (3 pieces per unit)

Capacitive dividers

Voltage presence indicator Operating voltage: 3.1 to 5.9 kV

6 to 8.9 kV9 to 17.9 kV18 to 24 kV

Voltage presence indicator wiring

Busbar field distributors

15

LBSkit Selection Guide for 12-24 kVDisconnector function 1 to 24 kV

CS

3730109AE

1 piece out of 51238920FD

3730300B

Metal cover manufactured by customer *

3730109AF

3728693

3736435

3 pieces out of 51238497FA

3 pieces out of 51238495FA

BBV 19686

3729742 (3 pieces included)

VPI 62404

VPI 62407VPI 62405

VPI 62408

AMTED306003EN.indd

Page 18: Medium Voltage Distribution Catalogue | 2014 LBSkit

16

LBSkit Order form for 12-24 kVComponents

Reference Quantity minimum to order

Quantity (1)

Switches (basic offer)

DE

5884

0 Load-break switch 630 A With CIT mechanism 3730109AB 2With CI1 mechanism 3730109AC 2With CI2 mechanism 3730109AD 2

Motorized switches (basic offer)

DE

5884

1 Motorized switch CIT 24 VDC+7AC 3730109AU 148 VDC+7AC 3730109AV 1110 VDC+7AC 3730109AW 1220 V 50 Hz+7AC 3730109AX 1

Motorized switch CI2 24 VDC+7AC+O/C coils 3730109AY 148 VDC+7AC+O/C coils 3730109AZ 1110 VDC+7AC+O/C coils 3730109BA 1220 V 50 Hz+7AC+O/C coils 3730109BB 1

Disconnectors (basic offer)

DE

5884

2 Disconnector 630 A With CS mechanism 3730109AE 2Disconnector 1250 A With CS mechanism 3730109AF 2

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 19: Medium Voltage Distribution Catalogue | 2014 LBSkit

17

LBSkit Order form for 12-24 kVComponents (continued)

Reference Quantity minimum to order

Quantity (1)

Auxiliary contactFor switch without motor

DE

5884

3 For CIT, CI1, CI2 4:2O-2C/Switch 3730300B 17:2O-3C/Switch + 1O-1C/Earth. sw. 3730300B + 3730301B 1 + 1

For CI1, CI2 with coil 4:2O-2C/Switch 3730307B 17:2O-3C/Switch + 1O-1C/Earth. sw. 3730307B + 3730308B 1 + 1

For fuse-switch without motor

DE

5884

3 For CI1, CI2 4:2O-2C/Switch 3730300B 17:2O-3C/Switch + 1O-1C/Earth. sw. 3730300B + 3730301B 1 + 1

For CI1, CI2 with coil 4:2O-2C/Switch 3730306B 17:2O-3C/Switch + 1O-1C/Earth. sw. 3730306B + 3730308B 1 + 1

For disconnector

DE

5884

3 For CS 4:2O-2C/Switch 3730300B 1

CoilFor switch or fuse-switch without motor

DE

5884

4 Coil for CI1 24 VDC 3730304B + 3730332A 1 + 148 VDC 3730304B + 3730333A 1 + 1110 VDC 3730304B + 3730335A 1 + 1220 V 50 Hz 3730304B + 3730335A 1 + 1

Coils for CI2 24 VDC 3730305B + 3730337A 1 + 148 VDC 3730305B + 3730338A 1 + 1110 VDC 3730305B + 3730340A 1 + 1220 V 50 Hz 3730305B + 3730340A 1 + 1

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 20: Medium Voltage Distribution Catalogue | 2014 LBSkit

18

LBSkit Order form for 12-24 kVComponents (continued)

Reference Quantity minimum to order

Quantity (1)

Accessories Description

DE

5884

5 Operating handle 3728693 20

DE

5884

6 Earthing switch (25 kA) 3932567 1

DE

5884

8

DE

5884

7D

E58

849

Fig. 1

Fig. 2

Fig. 3

3 busbar field distributors (fig. 1) 3729742 1024 upper field distributors (fig. 2) 51238497FA 118 field distributors/fuse holders for DIN fuses (fig. 3) 51238498FA 1

DE

5885

0 Cable connection for field distributor 3736435 75

DE

5885

1 Voltage presence indicator 3.1 to 5.9 kV VPI62404 146 to 8.9 kV VPI62405 149 to 17.9 kV VPI62407 1418 to 24 kV VPI62408 14

DE

5885

2

321G

UP

Voltage presence wiring BBV19686 50

DE

5885

3 12 capacitive dividers/Insulators 51238495FA 112 post insulators 51238496FA 1

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 21: Medium Voltage Distribution Catalogue | 2014 LBSkit

19

LBSkit Order form for 12-24 kVComponents (continued)

Reference Quantity minimum to order

Quantity (1)

Accessories Description

DE

5885

5 Earthing switch 2 kA for DIN fuses 12 kV > Ur ≤ 24 kV(no need to order 51238498FA)

51238922FA 1

Earthing switch 2 kA for DIN fuses Ur ≤ 12 kV(no need to order 51238498FA)

51238922FB 1

DE

5885

6 Fuse trip system 51238921FA 1

DE

5885

7 Mechanism cover (complete with mimic diagram and shutters)

4 covers for switch unit with CIT 51238920FA 14 covers for switch unit with CI1 51238920FB 14 covers for switch unit with CI2 51238920FE 14 covers for fuse-switch unit with CI1 51238920FC 14 covers for fuse-switch unit with CI2 51238920FF 14 covers for fuse-switch unit with CIT 51238920FG 14 covers for disconnector unit with CS 51238920FD 1

DE

5886

6

Round key type

Standard key type

Interlockings A3 Tubular key type 3730351B + 3731440 1 + 1A3 Flat key type 3730351B + 3731640 1 + 10 P1 Tubular key type 3730352B + 3731440 1 + 1P1 Flat key type 3730352B + 3731640 1 + 10 C4 Tubular key type 3730350B + BBV23780

+ 37314391 + 5 + 5

C4 Flat key type 3730350B + BBV23781 + 3731639

1 + 3 + 3

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 22: Medium Voltage Distribution Catalogue | 2014 LBSkit

20 AMTED306003EN.indd

Page 23: Medium Voltage Distribution Catalogue | 2014 LBSkit

Operating mechanism

Assembled switch and operating mechanism without motor (basic offer)Assembled switch and operating mechanism with motor (basic offer)Auxiliary voltage: 24 VDC

48 VDC

110 VDC

220 VAC

Coil kitsCoil type:

Auxiliary voltage: 24 VDC

48 VDC

110 VDC-220 VAC

Operating mechanism cover

Auxiliary contacts: 4 AC : 2O-2C switch

7 AC : 2O-3C switch+ 1O-1C earthing switch

Operating mechanism handle

Upper field distributors

Connection for one cable (3 pieces per unit)

Capacitive dividers (3 pieces per unit)

Voltage presence indicator Operating voltage: 25-36 kV **

Voltage presence indicator wiring

Busbar field distributors

Interlocking and lock kits

Lock type:

Interlocking type: A3

P1

(*) See drawing in Installation Guide(**) Please consult us for 38.5 kV

21

CIT CI1 CI2

51000162S

51000162T

51000162U

51000162V

51000162B

Without Opening release

3730304B+ 3730333A

3730304B+ 3730335A

3730304B+ 3730332A

51000162K

51000162W

51000162X

51000162Y

51000162Z

51000162C

Without

3730300B

3730300B+ 3730301B

Included in motorized

switch

3730300B 3730307B

3730307B+ 3730308B

3730300B

3730300B+ 3730301B

Metal cover manufactured by customer *

3730307B

3730307B+ 3730308B

51000861

Opening/closingrelease

(included in motorized

switch)

Opening/closingrelease

3730305B+ 3730338A

3730305B+ 3730340A

3730305B+ 3730337A

Without

3736435

3 pieces out of 51238497FA

51257952

VPI62406

51257931

3727841 (3 pieces included)

3730352B + 37314403730351B + 3731440

3730352B + 37316403730351B + 3731640

Included in motorized

switch

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Without

LBSkit Selection Guide for 36 kVSwitch function 36 kV, 630 A

Tubular key type

Flat key type

S1B77526 S1B77526 S1B77529 S1B77529 S1B77530 S1B77530 S1B77530

3730300B+ 3730301B

AMTED306003EN.indd

Page 24: Medium Voltage Distribution Catalogue | 2014 LBSkit

Operating mechanism

Assembled switch and operating mechanism without motor (basic offer)Assembled switch and operating mechanism with motor (basic offer)Auxiliary voltage:

24 VDC

48 VDC

110 VDC

220 VAC

Coil kitsCoil type:

Auxiliary voltage: 24 VDC

48 VDC

110 VDC-220 VAC

Operating mechanism cover

Auxiliary contacts: 4 AC : 2O-2C switch

7 AC : 2O-3C switch+ 1O-1C earthing switch

Operating mechanism handle

Upper field distributors

Earthing switch 2 kA

DIN fuse holder and field distributors

Capacitive dividers (3 pieces per unit)

Fuse trip system

Voltage presence indicator Operating voltage: 25-36 kV **

Voltage presence indicator wiring

Busbar field distributors

Interlocking and lock kitsLock type:

Interlocking type: A3

P1

C4

(*) See drawing in Installation Guide(**) Please consult us for 38.5 kV

22

CI1 CI2

51000162B

Without Opening release

3730304B+ 3730333A

3730304B+ 3730335A

3730304B+ 3730332A

51000162W

51000162X

51000162Y

51000162Z

51000162C

3730300B

3730300B+ 3730301B

3730306B

3730306B+ 3730308B

3730300B

3730300B+ 3730301B

Metal cover manufactured by customer *

3730306B

3730306B+ 3730308B

51000861

Opening/closing release(included in motorized

switch)

Opening/closing release

3730305B+ 3730338A

3730305B+ 3730340A

3730305B+ 3730337A

Without

Included in earthing switch kit (3 pieces)

51254700B

51257952

51257931

3727841 (3 pieces included)

3730352B + 3731440

3730351B+ 3731440 3730352B

+ 3731640

3730351B + 3731640

Included in motorized

switch

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

Metal cover manufactured by customer *

3 pieces out of51238498FA

Included in earthing switch kit (3 pieces)

51254461A51254461A

3730350B +

BBV23780+ 3731439

3730350B +

BBV23781+ 3731639

VPI62406

LBSkit Selection Guide for 36 kVFuse-switch function 36 kV, 630 A

Tubular key type

Flat key type

S1B77531 S1B77531 S1B77532 S1B77532 S1B77532

Included in earthing switch kit (3 pieces)

3 pieces out of51238497FA

AMTED306003EN.indd

Page 25: Medium Voltage Distribution Catalogue | 2014 LBSkit

Operating mechanism

Front support width

Assembled switch and operating mechanism (basic offer)Rated current: 630 A

1250 A

Operating mechanism cover

Auxiliary contacts: 4 AC : 2O-2C switch

Operating mechanism handle

Upper field distributors

Connection for one cable (3 pieces per unit)

Capacitive dividers (3 pieces per unit)

Voltage presence indicator Operating voltage: 25-36 kV **

Voltage presence indicator wiring

Busbar field distributors (3 pieces per unit)

(*) See drawing in Installation Guide(**) Please consult us for 38.5 kV

23

LBSkit Selection Guide for 36 kVDisconnector function 36 kV, 630-1250 A

CS

51000162AU

3730300B

S1B77533Metal cover

manufactured by customer *

51000162AF

51000861

3736435

3 pieces out of51238497FA

51257952

51257931

3727841

VPI62406

51000162AA51000162F

750 mm 1000 mm

S1B77534Metal cover

manufactured by customer *

AMTED306003EN.indd

Page 26: Medium Voltage Distribution Catalogue | 2014 LBSkit

24

LBSkit Order form for 36 kVComponents

Reference Quantity minimum to order

Quantity (1)

Switches (basic offer)

DE

5886

0 Load-break switch 630 A With CIT mechanism 51000162K 2 With CI1 mechanism 51000162B 2 With CI2 mechanism 51000162C 2

Motorized switches (basic offer)

DE

5886

1 Motorized switch CIT 24 VDC + 4AC 51000162S 148 VDC + 4AC 51000162T 1110 VDC + 4AC 51000162U 1220 V 50 Hz + 4AC 51000162V 1

Motorized switch CI2 24 VDC + 4AC + O/C coils 51000162W 148 VDC + 4AC + O/C coils 51000162X 1110 VDC + 4AC + O/C coils 51000162Y 1220 V 50 Hz + 4AC + O/C coils 51000162Z 1

Disconnectors (basic offer width 750 mm)

DE

5886

0 Disconnector 630 A (750 mm) With CS mechanism 51000162AU 2 Disconnector 1250 A (750 mm) With CS mechanism 51000162AF 2

Disconnectors (basic offer width 1000 mm)

DE

5885

9 Disconnector 630 A (1000 mm) With CS mechanism 51000162F 2 Disconnector 1250 A (1000 mm) With CS mechanism 51000162AA 2

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 27: Medium Voltage Distribution Catalogue | 2014 LBSkit

25

LBSkit Order form for 36 kVComponents (continued)

Reference Quantity minimum to order

Quantity (1)

Auxiliary contactFor switch without motor

DE

5884

3 For CIT, CI1, CI2 4:2O-2C/Switch 3730300B 17:2O-3C/Switch + 1O-1C/Earthing switch 3730300B + 3730301B 1 + 1

For CI1, CI2 with coil

4:2O-2C/Switch 3730307B 17:2O-3C/Switch + 1O-1C/Earthing switch 3730307B + 3730308B 1 + 1

For fuse-switch without motor

DE

5884

3 For CI1, CI2 4:2O-2C/Switch 3730300B 17:2O-3C/Switch + 1O-1C/Earthing switch 3730300B + 3730301B 1 + 1

For CI1, CI2 with coil

4:2O-2C/Switch 3730306B 17:2O-3C/Switch + 1O-1C/Earthing switch 3730306B + 3730308B 1 + 1

For disconnector

DE

5884

3 For CS 4:2O-2C/Switch 3730300B 1

CoilFor switch or fuse-switch without motor

DE

5884

4 Coil for CI1 24 VDC 3730304B + 3730332A 1 + 148 VDC 3730304B + 3730333A 1 + 1110 VDC 3730304B + 3730335A 1 + 1220 V 50 Hz 3730304B + 3730335A 1 + 1

Coils for CI2 24 VDC 3730305B + 3730337A 1 + 148 VDC 3730305B + 3730338A 1 + 1110 VDC 3730305B + 3730340A 1 + 1220 V 50 Hz 3730305B + 3730340A 1 + 1

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 28: Medium Voltage Distribution Catalogue | 2014 LBSkit

26

LBSkit Order form for 36 kVComponents (continued)

Reference Quantity minimum to order

Quantity (1)

Accessories Description

DE

5884

5 Operating handle 51000861 10

DE

5886

2 Earthing switch (20 kA) 51254700A 1

DE

5884

8

DE

5886

3D

E58

849

Fig. 1

Fig. 2

Fig. 3

Busbar field distributor (fig. 1) 3727841 60 24 upper field distributors (fig. 2) 51238497FA 118 field distributors/fuse holders for DIN fuses (fig. 3) 51238498FA 1

DE

5885

0 Cable connection for field distributor 3736435 75

DE

5885

1 Voltage presence indicator 25 to 36 kV VPI62406 14

DE

5885

4 Voltage presence wiring 51257931 10

DE

5886

4 Capacitive divider/Insulator 51257952 30 Post insulator 1946501 30

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 29: Medium Voltage Distribution Catalogue | 2014 LBSkit

27

LBSkit Order form for 36 kVComponents (continued)

Reference Quantity minimum to order

Quantity (1)

Accessories Description

DE

5886

5 Earthing switch 2 kA for DIN fuses(no need to order 51238498FA)

51254700B 1

DE

5885

6 Fuse trip systems 51254461A 1

Mechanism cover (complete with mimic diagram and shutters)

Cover for switch unit with CIT S1B77526 1Cover for switch unit with CI1 S1B77529 1Cover for switch unit with CI2 S1B77530 1

DE

5885

7_w

ide Cover for fuse-switch unit with CI1 S1B77531 1

Cover for fuse-switch unit with CI2 S1B77532 1Cover for disconnector unit with CS 750 mm S1B77533 1Cover for disconnector unit with CS 1000 mm S1B77534 1

DE

5886

6

Round key type

Standard key type

Interlockings A3 Tubular key type 3730351B + 3731440 1 + 1A3 Flat key type 3730351B + 3731640 1 + 10 P1 Tubular key type 3730352B + 3731440 1 + 1P1 Flat key type 3730352B + 3731640 1 + 10 C4 Tubular key type 3730350B + BBV23780

+ 37314391 + 5 + 5

C4 Flat key type 3730350B + BBV23781 + 3731639

1 + 3 + 3

(1) Ordered quantity has to be equal or/and multiplication of “Q min” such as batch one.

AMTED306003EN.indd

Page 30: Medium Voltage Distribution Catalogue | 2014 LBSkit

28

Notes

AMTED306003EN.indd

Page 31: Medium Voltage Distribution Catalogue | 2014 LBSkit
Page 32: Medium Voltage Distribution Catalogue | 2014 LBSkit

AMTED306003EN 04-2014

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Design: Schneider Electric Industries SASPhotos: Schneider Electric Industries SASPrinted: Altavia St-Etienne - Made in France

335, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France) Tel.: +33 (0)1 41 29 70 00RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com

Schneider Electric Industries SAS

AR

T819

791

© S

chne

ider

Ele

ctric

Indu

strie

s S

AS

- A

ll rig

hts

rese

rved

This document has been printed on recycled paper

10-31-1247