Mechanical Maintenance Department-Balance of Power, Adani Power
-
Upload
nemish-kanwar -
Category
Engineering
-
view
87 -
download
0
Transcript of Mechanical Maintenance Department-Balance of Power, Adani Power
Boiler
Fuel Oil Pump House
CW Pump House
Compressed Air System
Hydrogen Plant
Raw water pump house
DG Set
MMD-BOP 2
BALANCE OF PLANTS
74 meters long.
two passes with platen super heaters.
The boiler's four corners are designated as
A,B,C,D for communication purpose
BOILER
At bottom, leftover ash eliminated from
chimney and electrostatic precipitator (esp) is
collected in bottom ash hopper
collected ash mixed with water is sent to the
ash water pond.
FIRST PASS
From 22 metres to 37 meters the furnace is
situated
The furnace is divided into17 partitions
designated as AA, A, AB, B, BC till HH from top
to bottom.
Partitions designated with single letters have
inlets through which raw materials like coal,
air, water and different oils are sent through.
Oils are pumped using oil guns.
FIRST PASS
From 56metres to 74 the final super heaters
exist along with platen heaters and roof
heaters.
There exist water walls all along the boiler.
There exist soot blowers at particular height to
blow the ash that is left over after combustion
process
Contains the economiser, low temperature super heater, low
temperature re-heater, air pre heater, force draft fan, induced
draft fan and scanner fan.
The second pass focuses primarily on increasing efficiency.
SECOND PASS
The boiler is initiated by firing light diesel oil (LDO) along with air and coal.
LDO is pumped through the oil guns that are situated at the eight corners in a tangential direction.
LDO is used until the temperature reaches 400 degrees Celsius after which high fluid oil (HFO) is used.
The gases that are produced after combustion of coal are called flue gas which is used up in economizer and Pre-heaters
WORKING OF A BOILER
The dam water enters through the economiser
through feed pump.
Gets pre heated in the economizer and enters the
bottom ring header from where the water enters
the spiral water walls in the boiler in pass 1.
The water walls heat the water and send them
over to roof heater and then to low temperature
super heater next to the platen heater and then
to final super heater where most of it is
converted to super critical fluid.
FIRST PASS
This super critical fluid comes back to boiler
to reheat through re-heater line.
This liquid passes through the economiser in
pass 2 then to low temperature re-heater
Then back to final super heater
SECOND PASS
The soot blowers blow the ash with help of
steam to the bottom ash hopper.
The air preheater heats the secondary air
along with primary air so that the efficiency is
increased. Secondary air is used when there is
excess need of air in the furnace. This
secondary air is blown through force draft fan.
The scanner fan present in the boiler is used
to cool the sensors present in the boiler
The induced draft fan is used to remove or
suck the flue gas from the boiler
Providing Auxiliary Ignition Energy to coal-air mixture
Total Ignition Energy = Inherent Ignition Energy + Auxiliary
Ignition Energy
When heat becomes stable, heat available from combustion
of coal exceeds Total Ignition Energy, no more Auxiliary
Energy is required
MMD-BOP 14
FUEL OIL SYSTEM
Unloading through Unloading pumps.
Storing in Storage tanks.
Transferring to Day oil Tanks
MMD-BOP 15
FUEL OIL HANDLING SYSTEM
Circulate CW in condenser and condensing turbine exhaust
system
Discharge valve is hydraulic operated
Discharge water used to cool motor windings
MMD-BOP 17
COOLING WATER SYSTEM
Manufacture KIRLOSKAR BROTHERS LIMITED
Pump type BHM135, Single stage, Self water lubricating pump
Motor Rating 3600 KW
Speed 330 RPM (NOM)
Make WEG
Motor Weight 35300 KG
Pump Discharge 39825 M^3/HR
Total Head 26 M
Pump Ef ficiency 92 %
Pump Input 3049.73 KW
Type Three phase induction motor
Power 3600 kw
Speed 330 rpm
Frequency 50Hz
Duty S1
Voltage 11kv
Current 245.5 amp
Insulation class F
Ef ficiency 96(-2%)
MMD-BOP 18
CW PUMP SPECIFICATION