ME3 Manual Mobile Cabinetpdfs.findtheneedle.co.uk/19325..pdf · ME3 Manual (Mobile Cabinet).doc 26...
Transcript of ME3 Manual Mobile Cabinetpdfs.findtheneedle.co.uk/19325..pdf · ME3 Manual (Mobile Cabinet).doc 26...
ME3 Mobile Cabinet Three PhaseFrequency Converter,
Operation and Maintenence.
ME3 Mobile Cabinet Manual Rev 1
web - www.magnuspower.co.uk
e-mail - [email protected]
ME3 Mobile Cabinet Three Phase Frequency Converter - Manual
Magnus Power
Magnus Power29 - 30 Brunel Road, St Leonards on Sea, East Sussex, TN38 9RT. United Kingdom
Telephone +44 (0) 1424 853 013 (Sales & Service)+44 (0) 1424 853 464 (all other Enquires)
Fax +44 (0) 1424 853 2 268
29 - 30 Brunel Road, Churchfields Industrial Estate, St. Leonards-on-SeaEast Sussex. TN38 9RT. United KingdomSales & Service : 01424 853 013 All Other Departments : 01424 853 464 Fax : 01424 852 [email protected] [email protected]
ME3 Manual (Mobile Cabinet).doc 26 July 2006
2
CONTENTS
SPECIFICATION 3
OPERATING RESTRICTIONS AND SAFETY ADVICE 3
INSTALLATION AND COMMISSIONING 4
Installation Procedure 5
GENERAL ARRANGEMENT 6
CONTROL PANEL 7
Pushbutton Controls 7
Mimic Diagram Indicators 7
SWITCHGEAR COMPARTMENT 8
Auxiliary Power Supply Switch 8
FIRST START UP 9
NORMAL OPERATION 9
Standby Condition 9
Starting Up 10
Shutting Down 10
Restarting after a Supply Interruption 10
ALARM CONDITIONS 11
Overload 11
Over Temperature 11
Short Circuit 12
Inverter Fault 12
UNREPORTED PROBLEMS 13
ELECTRICAL MEASUREMENTS 13
MAINTENANCE 13
Preventive Maintenance 13
Corrective Maintenance 14
Warranty Repair 14
ME3 Manual (Mobile Cabinet).doc 26 July 2006
3
SPECIFICATION
Three Phase + Neutral 380/400/415V 50Hz
Voltage Tolerance +/-10%
Input Requirement
Frequency Tolerance +/-5%
Three Phase + Neutral 115V Phase-Neutral
Frequency 200V Phase-Phase
400Hz +/-1%
The maximum load permitted on any phase is one third of the total output rating
There is no requirement for the load to be balanced on all phases
Output Capability
The output neutral is linked to mains earth (ground) internally. This link may be removed if floating output is required, or if the output neutral is to be grounded elsewhere.
0 to 40 degrees, derating to 30 degrees at 2000m
40 to 60% RH (recommended)
0 to 90% RH (extreme)
Operating Environment
Below 55dBA at 1m
OPERATING RESTRICTIONS AND SAFETY ADVICE
Ensure adequate air circulation around the unit in normal operation, for correct
function of the cooling fans. Allow for the dissipation of waste heat produced
by the Converter, which will amount to around 10% of its output rating when
operating at full load. Do not attempt parallel operation of the Converter output
with any other power source.
Dangerous voltages are present at numerous points within the Converter,
and great care should be taken if running with any of the covers removed.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
4
The DC Busbars are alive at 750V dc during Converter operation. A
fault current of hundreds of amps is available within the DC Circuitry,
and great care should be taken if using tools in this area when there is
any possibility of charge remaining. Discharge Resistors are connected
across the DC Busbars, and these will take about 2 minutes to complete
their task after power is removed.
INSTALLATION AND COMMISSIONING
Installation includes positioning the Converter, the provision of input and output
cables and an input isolator, and connection of the input and output cables to the
Converter terminals. Installation is normally carried out by the customer, or by
an electrical contractor working on behalf of the customer.
Magnus Power recommends that the system is commissioned by one of their
engineers after installation, but the customer may opt to carry out this work. It
consists of checks on the operating environment, the voltage and phase rotation
of the incoming supply, input and output connections at the Converter, and the
earth (ground) connection. Internal plug-and-socket connections are checked
for correct mating. After initial start-up of the system, its operation will be
checked and any necessary adjustments made. Finally a demonstration of the
operation of the system will be offered, and a commissioning status report will
be prepared.
If Magnus Power does not carry out commissioning, it is recommended that
when power is applied for the first time, the Output Circuit Breaker is left set to
Off. The procedure is described elsewhere in this document.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
5
Installation Procedure
Position the Converter at the required location, and ensure that its weight is
adequately supported. Allow at least 400mm clearance at the rear for air
circulation, and for access to the circuit breakers (inside narrow door at rear). A
similar clearance will be needed at the front, for ventilation and to allow an
operator to reach the control panel.
Access to the sides of the machine is not required during normal operation, but
may be needed for maintenance purposes. If flexible input and output cables of
suitable length are fitted during installation, it will be possible to move the
machine on its casters between a normal service position where it takes up least
space, and a maintenance position offering all round access.
The input and output terminals are at the lower rear of the cabinet behind a
removable terminal cover, which may be drilled for cable access. Connect the
output (load) and input (supply) cables as indicated by the terminal labels,
ensuring a sound supply earth (ground) connection to the earth terminal.
It is common practice for the neutral of any ac supply system to be grounded
(earthed) at its source, and for the converter input this link is usually made by the
supply authority at their substation. In accordance with this principle, the output
neutral of the Converter is grounded internally. If you require floating output, or
if your distribution system has an existing neutral earthing link, you will need to
remove the internal link. Instructions for removal of the link will be provided on
request.
When installation is complete, refit the terminal cover, to prevent casual access
to the electrical connections.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
6
GENERAL ARRANGEMENT
ME3 Manual (Mobile Cabinet).doc 26 July 2006
7
CONTROL PANEL
Indications are given by a mimic diagram, and a four-line alphanumeric display.
The pushbuttons on the mimic diagram control the operation of the Converter,
and the buttons below the display allow scrolling of its contents.
The first two lines of the display provide measurements of input and output
values, and the third and fourth lines give status messages.
During normal operation of the Converter, the mimic diagram will show no
indications, and the status display will read “Power System – OK” and
“P.S. Use – nnn Days”.
Pushbutton Controls
Start Output (green)
Stop Output (red, press both)
Reset Alarm Indication (“R”)
Scroll Status Display (up and down)
Scroll Meter Readings (up and down)
Mimic Diagram Indicators
Supply Voltage Low (red, in left hand box on mimic diagram)
Output Off (red, in right hand box on mimic diagram)
1 2
1 2 3 2
4
5
6
7
ME3 Manual (Mobile Cabinet).doc 26 July 2006
8
SWITCHGEAR COMPARTMENT
Access to this area is via the narrow door at the rear of the Converter, to the
right of the terminal cover. It contains the Auxiliary Power Supply Switch, the
Input Circuit Breaker and the Output Isolator.
Setting either the Input Circuit Breaker or the Output Isolator to the Off position
will prevent output, but various parts of the Converter will remain alive, including
the input terminals. To ensure that all connections are dead, isolate the
Converter elsewhere and wait at least two minutes to allow stored voltages to
decay before touching any internal component.
Auxiliary Power Supply Switch
The Converter includes a small rechargeable battery, which ensures a continued
supply of power to the control electronics during supply transients, or extreme
step changes of load. The Auxiliary Power Supply Switch controls the flow of
power from the battery to the control electronics, and should be switched off
during a planned disconnection of the Converter from the Supply of more than 1
hour, to avoid unnecessary discharge of the battery.
If the battery becomes discharged as a result of an unexpected break in the
supply, such as a power cut outside working hours, it will be recharged
automatically when the supply is restored.
If the Auxiliary Power Switch is left set to Off then the Converter will appear to
operate normally, but it may shut down unnecessarily during supply transients or
under extreme load conditions.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
9
FIRST START UP
Before starting the Converter for the first time after installation, set the Output
Isolator to Off. Set the Auxiliary Power Switch to On, and check that the mimic
diagram indicates Supply Voltage Low and Output Off. After connecting power
with the Input Circuit Breaker On, check that the Supply Voltage Low indicator
(red light in the left hand box on the Control Panel) goes off within 10 seconds.
If this does not happen, set the Input Circuit Breaker to Off, and seek technical
advice.
If the Control Panel illuminates as described, allow the starting sequence to
complete to the Standby Condition as described in the following paragraph, and
then continue through Starting Up and Shutting Down. The Output Isolator may
now be closed, and the Converter may be used as described under Normal
Operation.
NORMAL OPERATION
Standby Condition
On application of input power, either externally or by setting the Auxiliary Power
Switch and the Input Circuit Breaker to On, the Converter will initialise. During
this process, which may take up to 30 seconds to complete, there may be an
indication of Supply Voltage Low before the display changes to Output Off.
This is the Standby condition, in which the Converter is ready to run but is not
producing any output. The status message display will read “Inverter Off” and
the audible alarm will sound. Press the Reset button to silence the alarm and to
clear the status message.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
10
Starting Up
Press the green Start Output button to commence operation. The mimic diagram
indication will change from Output Off to no indications, and if the Output
Circuit Breaker is On, power will be supplied to the load.
The status messages will read “Power System - OK” and “P.S Use – nnn
Days”.
Shutting Down
Press both of the red Stop Output buttons. The Converter will revert to the
Standby condition, and the mimic diagram indication will change from no
indications to Output Off. The status message display will read “Inverter Off”
and the audible alarm will sound. Press the Reset button to silence the alarm and
clear the status message.
Disconnect the load (if required) by setting the Output Isolator to Off.
Remove Converter input power (if required) by setting the Input Circuit Breaker
to Off, or by setting the Auxiliary Power supply switch to Off and isolating
elsewhere.
Restarting after a Supply Interruption
If a power cut occurs during normal operation, then when power is restored the
Converter will initialise to the Standby condition. The status message display
will read “Inverter Off” and the audible alarm will sound. Press the Reset button
to silence the alarm and to clear the status message.
Press the green Start Output button to commence operation. The mimic diagram
indication will change from Output Off to no indications and if the Output
ME3 Manual (Mobile Cabinet).doc 26 July 2006
11
Isolator is On, power will be supplied to the load.
The status messages will read “Power System - OK” and “P.S. use – nnn
Days”.
ALARM CONDITIONS
Overload
The status messages will be “WARNING” and “Overload” and the audible
alarm will sound. Press the Reset button to silence the alarm and to clear the
status message.
If either the magnitude or the duration of the overload is beyond the capability of
the Converter, it will shut down to the Standby condition. Extreme overload
conditions may cause the Converter to shut down completely, in which case a
Supply Voltage Low indication will also be given.
Investigate and if necessary remove the cause of the overload, observing any
necessary safety precautions before making adjustments to wiring. Restart the
Converter by pressing the green Start Output button on the mimic diagram.
Over Temperature
The status messages will be “WARNING” and “Over Temperature” and the
audible alarm will sound. The Converter will shut down to the Standby
condition.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
12
Press the Reset button to silence the alarm and to clear the status message, and
check for any obstruction of the air inlets or outlets around the Converter. If no
such cause can be found, it may be that a cooling fan has failed and will require
replacement.
Restart the Converter by pressing the green Start Output button.
Short Circuit
The status messages will be “WARNING” and “Short Circuit” and the audible
alarm will sound. The Converter will shut down to the Standby condition.
Press the Reset button to silence the alarm and clear the status message.
Remove the cause of the short circuit, taking any necessary safety precautions
before making adjustments to wiring.
Restart the Converter by pressing the green Start Output button.
Inverter Fault
The status messages will be “WARNING” and “Inverter Fault” and the audible
alarm will sound. The Converter will shut down to the Standby condition.
Press the Reset button to silence the alarm and clear the status message, and
restart the Converter by pressing the green Start Output button.
This error condition has a number of possible causes, and may be triggered by
an internal fault. If the failure is repeated it is likely that the Converter will require
repairs. Do not make further attempts to restart the Converter.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
13
UNREPORTED PROBLEMS
Some error conditions will cause the Converter to disconnect itself from the
incoming supply, and the resulting absence of internal power will prevent the
display of any message or indication. It will be impossible to start the Converter
until the problem has been solved.
The most likely cause during commissioning or after any changes to the site
electrical installation is a phase rotation fault, and other possibilities are
significant undervoltage or overvoltage of the supply. Any of these causes will
require remedial action either by an electrician or by the supply authority.
It is also possible that an internal fault will prevent starting, in which case a
service visit by an experienced engineer will be required.
ELECTRICAL MEASUREMENTS
The first two lines of the alphanumeric display can provide a number of
indications, including running time since last started, input and output voltage,
and output current as a percentage of the maximum allowed.
The scroll buttons allow these values to be displayed in sequence.
MAINTENANCE
Preventive Maintenance
The intake fans draw air in through vents at the front of the Converter. Exhaust
fans discharge the air through vents at the rear of the unit.
At suitable intervals, check that any visible fans are operating normally, and that
the air intakes are clear of any accumulation of fluff or dust.
ME3 Manual (Mobile Cabinet).doc 26 July 2006
14
Corrective Maintenance
Spare parts are available from Magnus Power, and these can be fitted without the
use of special tools. Provided the fault was correctly diagnosed, the Converter
will return to normal operation after replacement of the defective part. In some
cases, best results will be achieved by carrying out specialised adjustment
procedures requiring the use of standard electronic test equipment.
For some failures, the defect and the effect may be in different places; for
example a faulty output from a control printed circuit board may cause failure of
one of the main power components. If only the power component is replaced,
the failure will be repeated.
Because of the high MTBF of these Converters, it will be difficult for an on-site
engineer responsible for only a small number of systems to become familiar with
troubleshooting. The most cost-effective repair option will usually be to have
the fault repaired by an experienced field service engineer. If immediate return to
service after a breakdown is a priority, then a standby unit should be held on
site.
Warranty Repair
The standard Magnus Power warranty covers the cost of any repair that
becomes necessary due to failure while in normal use during the specified
warranty period, usually 12 months. It is unlikely that any unit will be out of
order for more than 2 working days after having been reported as faulty.
____________________________________________________________
___
29 - 30 Brunel Road, St Leonards-on-Sea, East Sussex, TN38 9RT. United KingdomSales - 01424 853013 - All Other Departments - 01424 853464 - Fax - 01424 852268
Registered in England, Registered office Unit 12, Clivemont Road, Cornwallis Ind. Est. Maidenhead SL6 7BZ. Registration No. 4977339. VAT Registration No. GB 829 4203 28