MConfigPro Manual
-
Upload
edwin-f-marcano-m -
Category
Documents
-
view
217 -
download
0
Transcript of MConfigPro Manual
-
7/31/2019 MConfigPro Manual
1/50
00-02-060208-31-06
Section 50
MConfigProConfiguration Software
Installation and Operations Manual
-
7/31/2019 MConfigPro Manual
2/50
In order to consistently bring you the highest quality, full featured products, we reserve the right to change ourspecifications and designs at any time. The latest version of this manual can be found at www.fwmurphy.com.
Please read the following information before installing.
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT:
Read and follow all installation instructions.
Please contact FW MURPHY if you have any questions.
-
7/31/2019 MConfigPro Manual
3/50
Table of Contents
About MConfigPro.................................................................................................................. 1Installing MConfigPro............................................................................................................. 1
System Requirements..................................................................................................1Installation Instructions.................................................................................................2
Installing USB Driver .............................................................................................................. 4MConfigPro Application GUI Overview................................................................................ 6
Launching the Application ............................................................................................6Menus and Tool Bars ...................................................................................................6Opening Wizard ...........................................................................................................8Saving Files..................................................................................................................9Navigating MConfigPro ..............................................................................................10
Main Menu List Screen Definitions..................................................................................... 12Version and Security ..................................................................................................12Digital Inputs ..............................................................................................................14Digital Outputs............................................................................................................16Digital Assignments....................................................................................................17Analog Inputs .............................................................................................................18
Analog Outputs ..........................................................................................................20Thermocouple ............................................................................................................21Setpoints ....................................................................................................................22Global Timers.............................................................................................................24Maintenance Timers...................................................................................................26Events ........................................................................................................................27Startup .......................................................................................................................29RPM Controls.............................................................................................................30Control Outputs..........................................................................................................32States.........................................................................................................................34Miscellaneous ............................................................................................................36PID.............................................................................................................................38Comm Port Settings...................................................................................................40
-
7/31/2019 MConfigPro Manual
4/50
Guidelines for Configuring MConfigPro............................................................................. 41
Defining the System...................................................................................................41System of Protection..................................................................................................42System of Operation ..................................................................................................42System of Interface ....................................................................................................43
Configuration Download Instructions ................................................................................ 43Comm. Port Settings..................................................................................................43
-
7/31/2019 MConfigPro Manual
5/50
Section 50 00-02-060208-31-06 - 1 -
About MConfigPro
MConfigPro is a pc-based configuration software for the Centurion controller. The easy-to-useinterface enables you to modify features of the Centurion such as:
sequence of operation
setpoint s
timers
faults
displays
File transfer utilities for configuration and firmware upgrades are provided so that once theconfiguration is set, it may be downloaded from your pc to the Centurion via a serial or USBconnection.
Installing MConfigPro
System Requirements
A serial port (RS485/232) or USB 1.1 connection is required for transferring the configurationfrom MConfigPro to the Centurion.
While the MConfigPro software will function on any pc or laptop running Windows, it will notperform transfers using the USB driver unless the operating system supports USB. USBsupported operating systems include Win98SE, NT, and XP.
Serial transfers using standard communication ports (COM1, COM2) should be possible on allWindows platforms.
The MConfigPro software and USB driver provide efficient use of your hard drive, using only 3-5 MB of disk space after installation.
-
7/31/2019 MConfigPro Manual
6/50
Section 50 00-02-060208-31-06 - 2 -
Installation Instructions
Follow the steps below to install the MConfigPro software on a pc or laptop.
1. Insert the MConfigPro CD into the CD drive of your computer. The installationmenu is displayed.
2. Select Install MConfigPro from the menu. An Installation Wizard is launched.Click on [Next] to continue.
3. The License Agreement for the product is displayed. You may print theagreement by clicking on the [Print] button displayed beneath the agreement.
4. Once you have read the License Agreement, click the I agree with the terms inthe license agreement. Then click [Next].
5. You will be asked for a destination folder for the program. You may accept thesuggested directory or you may select a different directory by clicking the[Change] button and browse to the destination folder. Once the destination folderis determined, click [Next] to continue.
-
7/31/2019 MConfigPro Manual
7/50
Section 50 00-02-060208-31-06 - 3 -
6. The Wizard is now ready to install the program. Click on the [Install] button tobegin. This may take several minutes.
7. When the installation is complete, the following screen appears. Click [Finish].
-
7/31/2019 MConfigPro Manual
8/50
Section 50 00-02-060208-31-06 - 4 -
Installing USB Driver
If you will be using a USB connection device to download the configuration into the Centurioncontroller, you will need to install the USB driver. Follow the instructions listed below to installthe USB Driver.
1. Insert the MConfigPro CD into the CD drive of your computer. The installation
menu is displayed.
2. Select Install USB Driver from the menu. An Install Driver dialog box displaysa destination folder for the program. You may accept the suggested directory oryou may select a different directory by clicking the [Browse] button to locate thedestination folder.
3. Once the destination folder is determined, click [Install].
-
7/31/2019 MConfigPro Manual
9/50
Section 50 00-02-060208-31-06 - 5 -
4. The following dialog box will appear to indicate Microsoft has not tested thedevice driver with the XP operating system.
The manufacturer of the royalty-free USB driver has elected not to seek WindowsLogo approval. Therefore, you should read the message carefully and
understand the impact it may have on critical systems before acceptingresponsibility for continuing with the installation.
Select [Continue Anyway] to continue with the installation of the USB driver.
5. Because the device driver installs two items, the Software Installation dialogbox will appear a second time. Select [Continue Anyway].
6. Once the driver is installed the following dialog box will appear. Click [OK].
7. From the MConfigPro Installation Menu, select Exit.
-
7/31/2019 MConfigPro Manual
10/50
Section 50 00-02-060208-31-06 - 6 -
MConfigPro Application GUI Overview
This section provides instructions for launching the MConfigPro application, identifies theapplication features that are accessible through the menu bar, and defines general navigation.
Launching the Application
To launch the application you may either double-click the MConfigPro application iconlocated on your desktop, or select MConfigPro Design from the list of programs under yourStart menu. The following dialog box is displayed.
Click on the [Run] button to launch the application.
NOTE: You may turn off this dialog box from displaying each time youlaunch the application by de-selecting the check box Always ask beforeopening this file, located in the lower left corner.
Menus and Tool Bars
The tools provide one-click access to creating a new file, opening an existing file, saving thecurrently displayed file, or printing the current file. These same functions are available from the
File drop-down menu.
-
7/31/2019 MConfigPro Manual
11/50
Section 50 00-02-060208-31-06 - 7 -
The View drop-down menu provides a list of configurable settings that may be viewed orchanged. These same settings are also displayed and available in the Main Menu Listwindow of the user interface when a configuration file is being displayed.
Selecting Options displays a dialog box that allows you to select the boards you are using.
The Tools menu allows you to upload from or download to the Centurion device.
Help provides a link to the FW Murphy website, and will launch an e-mail when Contact Usis selected. At this time, there is no online help available.
-
7/31/2019 MConfigPro Manual
12/50
Section 50 00-02-060208-31-06 - 8 -
Opening Wizard
When you click on the new file icon or select File/New from the menus, the Opening Wizard isdisplayed. It contains three tabs labeled New, Existing, and Recent.
The New tab contains several templates to use as guidelines for setting up reciprocatingcompressors, screw compressors, and pumps. There is also a Blank template to be used for
setting up new files and does not contain any pre-configured data.
The Existing tab displays the current location where files are being stored. You may selectfrom this list or browse to locate the desired file.
The Recent tab displays the most recent files that have been created or updated.
-
7/31/2019 MConfigPro Manual
13/50
Section 50 00-02-060208-31-06 - 9 -
Saving Files
When saving files you may select a file extension specific to the type of equipment you areconfiguring. This helps to differentiate the file types when you are browsing through the filenames. There are four file extensions to choose from.
.mcp Generic (default)
.cfr Reciprocating Compressor.cfs Screw compressor
.cfp Pump
The default file extension .mcp is used unless a different extension is specified. To select adifferent extension, click the Save as type: pull-down menu and select the desired extension.
-
7/31/2019 MConfigPro Manual
14/50
Section 50 00-02-060208-31-06 - 10 -
Navigating MConfigPro
Navigating the MConfigPro application interface is versatile and easy. It contains two mainwindows, or sections of information. The left window contains the Main Menu List of availablefeatures and settings available for configuration. This is the same list that is displayed on theView pull down menu. When a new file is created, the Main Menu List is the only windowdisplayed until a process is selected.
-
7/31/2019 MConfigPro Manual
15/50
Section 50 00-02-060208-31-06 - 11 -
Selecting items from the Main Menu List will populate the remaining window with theappropriate information. In most cases, the window will contain three sections of information. Inthe upper left, a list of processes (A) or options is displayed. When you click on any of theseoptions, the corresponding data fields (B) are displayed in the upper right section. You mayclick on these fields and enter the appropriate configuration information. The upper rightsection may also contain helpful guidelines for entering data.
The bottom portion (C) of the window contains the same information as the upper right, but in aspreadsheet format containing all the entries listed in the upper section. You may edit eitherthe upper or lower sections as desired.
-
7/31/2019 MConfigPro Manual
16/50
Section 50 00-02-060208-31-06 - 12 -
Main Menu List Screen Definitions
This section provides field definitions for each item in the Main Menu List and can be used as areference when setting up your configuration files. An example of each screen will bedisplayed, followed by a table listing all editable fields and their descriptions.
Version and Security
-
7/31/2019 MConfigPro Manual
17/50
Section 50 00-02-060208-31-06 - 13 -
Field DescriptionVersion Non-editable, system generated. The Revision number reflects the
version of MConfigPro that created the file or last updated it. If theversion is different from the current MConfigPro version, choosingFile/Save will update the file version to that of the currentMConfigPro version.
Date Non-editable, system generated. Date reflects the date of the lastsave (or creation date). This is updated with the current date whenSave or Save As is chosen from the File menu.
Time Non-editable, system generated. This Time reflects the time of thelast save (or creation time). This is updated with the current Timewhen Save or Save As is chosen from the File menu.
Description 15 character description of your choice to identify the configuration.
Standard SecurityPassword
Allows access to all setup menus except the super user menu.
Must be zero or range from 100 to 65535 and cannot be the same asthe Super User Password. Entering a value of 0 disables thepassword and provides no security.
NOTE: Passwords are required for the Centurion display only.Passwords have no function within the Centurion controller.
Super User Password Allows access to all setup menus, super user menu and providesadditional functions like Reset Fault History which should not beavailable to most operators.
Must be a range from 100 to 65535 and cannot be zero or the sameas the Standard Security Password.
-
7/31/2019 MConfigPro Manual
18/50
Section 50 00-02-060208-31-06 - 14 -
Digital Inputs
-
7/31/2019 MConfigPro Manual
19/50
Section 50 00-02-060208-31-06 - 15 -
Field DescriptionDescription Entries are provided for each of the 32 digital input devices. The
system generated names may be changed to a more descriptivename of your choice. The field length for description is 17 characters.
In Use Active inputs must be set to In Use in order to show up onsubsequent configuration screens. Once the input is set to In Use,
the entry turns to bolded text.Type NO = Normally Open
NC = Normally ClosedEnable Delay Check to enable delay.Delay Type Debounce provides a timed condition for processing the digital
input. The input must be active for the duration of the delaybefore it will be recognized as active by the controller application.Once recognized, the digital input must be inactive for theduration of the delay before it will be recognized as inactive bythe controller application.This type of signal condition is useful in process conditions such
as unstable tank levels. Pulse provides a timed transition condition for processing the
digital input. The input will reset the timer each time the inputchanges condition. If the input does not change conditions in thedelay period specified, the controller will signal the event system.Pulse Delay Type also provides tracking counters for number oftransitions and last and current pulse duration. This information isavailable on the Centurion display.
Delay (Secs) Number of seconds associated with the delay
-
7/31/2019 MConfigPro Manual
20/50
Section 50 00-02-060208-31-06 - 16 -
Digital Outputs
Field DescriptionDescription Entries are provided for each of the 10 digital output devices. The
system generated names may be changed to a more descriptivename of your choice. The field length for description is 17 characters.
In Use Active outputs must be set to In Use in order to show up onsubsequent configuration screens. Once the output is set to In Use,the entry turns to bolded text.
Type NO = Normally OpenNC = Normally Closed
-
7/31/2019 MConfigPro Manual
21/50
Section 50 00-02-060208-31-06 - 17 -
Digital Assignments
Field State DescriptionEntries are provided for each of the 11 digital assignments.
2 Start Annunciation start delay
Alarm Annunciation - alarm
Shutdown Annunciation fault anytime (not state specific)10-13 Running Annunciation warm-up, stop (electric motor types
need to rely on motor out)12 Loaded Annunciation run loaded3 Preheat Output - preheat4,17 Lube Output pre-lube / post-lube7 Crank crank only7-13 Ignition Output crank ! crank stop stop7-13 Fuel Output crank ! crank stop stop
Description
9-14 Motor on Output
Value List of In Use digital outputs to select from.
-
7/31/2019 MConfigPro Manual
22/50
Section 50 00-02-060208-31-06 - 18 -
Analog Inputs
-
7/31/2019 MConfigPro Manual
23/50
Section 50 00-02-060208-31-06 - 19 -
Field DescriptionDescription Entries are provided for each of the 20 analog input devices. The
system generated names may be changed to a more descriptivename of your choice. The field length for description is 17 characters.
In Use Active inputs must be set to In Use in order to show up on
subsequent configuration screens. Once the input is set to In Use,the entry turns to bolded text.
Type 0-5V
4-20mA
Differential (calculated)Dec. Choose from 0-3 decimal places. Only selectable for inputs 13-20.Moving Average Choices are 1, 2, and 4. Adjust to settle unstable readings.Offset Raw Count Offset, the lowest reading expected from the device.Span The span from the lowest to highest reading expected from the
device.Min Minimum engineering scale. In most cases, 0 addresses a typical
application and is the default value. These values are represented as0 to 10,000 (0.00 to 100.00%). The decimal is implied. For analoginputs, the engineering units are completely at the discretion of theuser. An example might be:A PXT-100 would have a Min=0 and Max=100 (PSIG)A PXT-30V30 would have a Min=-14.7 and Max=30 (PSIG)
NOTE: Used to define the input scaled in engineering units. Dualscales are not supported.
Max Maximum engineering scale. These values are represented as 0 to10,000 (0.00 to 100.00%). The decimal is implied.
NOTE: Used to define the input scaled in engineering units. Dualscales are not supported.
Units Defines the unit type, span, min, and max. When no other unit ofmeasure is applicable, blank can be selected.
PSI
F
C
RPM
KPa
VDC Amp
mV
mA
Hg
WC %
-
7/31/2019 MConfigPro Manual
24/50
Section 50 00-02-060208-31-06 - 20 -
Analog Outputs
Field DescriptionDescription Entries are provided for each of the 6 analog output devices. The
system generated names may be changed to a more descriptive
name of your choice. The field length for description is 17 characters.In Use Active outputs must be set to In Use in order to show up onsubsequent configuration screens. Once the output is set to In Use,the entry turns to bolded text.
Type 0-20 mA
4-20 mAOffset Raw Count Offset, the lowest reading expected from the device.Span Raw Count Span, the span from the lowest to highest reading
expected from the device.Min Minimum engineering scale. In most cases, 0% addresses a typical
application and is the default value. Analog outputs use relative
terms of Percent (%) for Min and Max because the position istypically 0% output or 100% output with some proportional change inbetween.
Max Maximum engineering scale. In most cases, 100% addresses atypical application and is the default value.
-
7/31/2019 MConfigPro Manual
25/50
Section 50 00-02-060208-31-06 - 21 -
Thermocouple
Field DescriptionDescription 16 entries are provided for thermocouple devices. The system
generated names may be changed to a more descriptive name ofyour choice.
In Use Active devices must be set to In Use in order to show up onsubsequent configuration screens. Once the device is set to In Use,the entry turns to bolded text.
Type J Type - Typical for most general purpose applications; providesgreater accuracy.K Type - High temperature applications; less accuracy.
Offset Range is -20 to +20
-
7/31/2019 MConfigPro Manual
26/50
Section 50 00-02-060208-31-06 - 22 -
Setpoints
There are 128 configurable setpoints that may be edited. Setpoints further configure variablerange input types such as mpu, analog, or thermocouple by defining a threshold, exception orany other out-of-limit event that may require action. Multiple setpoints are often applied to aprocess and they may be configured as often as needed to meet changing conditions.Common alarm and shutdown setpoints a user might configure include:
High Shutdown
Low Warning
Open Warning
High Warning
Low Shutdown
Setpoints may also be configured for other processes besides alarm and shutdown settings.For example, a setpoint provides a less flexible, but simpler alternative to controlling thepumps start and stop functions.
-
7/31/2019 MConfigPro Manual
27/50
Section 50 00-02-060208-31-06 - 23 -
Field DescriptionDescription 128 setpoints are provided. The system generated names may be
changed to a more descriptive name of your choice. The field lengthfor description is 17 characters.
In Use Active setpoints must be set to In Use in order to show up onsubsequent configuration screens. Once the device is set to In Use,
the entry turns to bolded text.Signal Type Signal type of setpoint
Unused Analog
Thermocouple
RPM
Battery V (tenths)
PIDBase Base information is determined by Signal Type selection:
Analog = list of in use analog devices to select fromThermocouple = list of in use thermocouple devices to select fromRPM = RPM speed source specified in Miscellaneous dialogBattery V (tenths) = External DC voltage supply as measured by thecontroller represented as XX.X VoltsPID = list of in use PID devices to select from. Output from PID 1thru 4.
GT/LT In reference to value of setpoint.
GT = Greater Than
LT = Less ThanValue Value of setpoint.
-
7/31/2019 MConfigPro Manual
28/50
Section 50 00-02-060208-31-06 - 24 -
Global Timers
Generally, global timers affect process I/O and the arming of associated events. All eventtypes can be associated with, and locked out by Bx, C, or Sx timers.
-
7/31/2019 MConfigPro Manual
29/50
Section 50 00-02-060208-31-06 - 25 -
Field DescriptionDescription There are 13 available global timers.
B1 The first global timer used for delaying an eventcondition detection. The timer starts in a running State (10-13) depending on which ones have been marked In Use.
B1 is also known as the Lockout timer.
B2 The second global timer used for delaying an eventcondition detection. B2 is also known as a secondaryLockout Timer. This timer runs in parallel with B1.
C The delay allowing a clear reading before beginningtesting for the arming of Class C events. The typical timefor most applications is 2 seconds.
S1 thru S5 Users have up to five (5) options to assignadditional special global timers to signals. The Sx timers
begin concurrently with the Bx timers. NF No Flow: The global delay used for delaying the
triggering of a no flow event. This global no flow timer isenabled after B1 expires, and begins timing after theexpiration of any of the pulse transition times configured inthe digital input dialog.
Test Time given to allow for maintenance testing of enddevices without triggering a fault or shutdown condition.The timer initiates when switched to test mode.
Ignition on Delay Time delay before the assigned
ignition output turns on. This is typically used to delayignition until engine crank rollover can occur.
Fuel On Delay Time delay before the assigned fuelvalve output is turned on. This is typically used to delayfuel until ignition has been turned on.
Ignition Off Delay Time delay before the assignedignition output turns off. This is typically used to burnremaining fuel vapors after the fuel valve is turned off.
Value Timer value.
-
7/31/2019 MConfigPro Manual
30/50
Section 50 00-02-060208-31-06 - 26 -
Maintenance Timers
Field DescriptionDescription 10 entries are provided for maintenance settings for timer duration.
The system generated names may be changed to a more descriptivename of your choice. The field length for description is 17 characters.
In Use Maintenance timers must be set to In Use in order to show up onsubsequent configuration screens. Once the timer is set to In Use,the entry turns to bolded text.
Value (Hours) Timer value units specified in hours.
-
7/31/2019 MConfigPro Manual
31/50
Section 50 00-02-060208-31-06 - 27 -
Events
Field DescriptionDescription 128 programmable events are provided. The system generated
names may be changed to a more descriptive name of your choice.
The description name will be displayed on the Centurion controllerwhen there is an event. The field length for description is 23characters.
In Use Events must be set to In Use in order to show up on subsequentconfiguration screens. Once the event is set to In Use, the entryturns to bolded text.
Event Type Event type:
Unused
Alarm activates alarm banner and alarm output (if assigned)but does not affect process
Message same as alarm except the alarm output is notactivated
Stop Interrupts process and begins shutdown. Once process isstopped, the state engine recycles. (State 1 Panel Ready)
Fault SD fault shut down. Interrupts process and beginsshutdown. Activates shutdown banner and snapshot page iscaptured. Faults are first out.
-
7/31/2019 MConfigPro Manual
32/50
Section 50 00-02-060208-31-06 - 28 -
Field Description
ESD emergency shut down. Same as Fault SD except theprocess stops and state engine skips all other steps andproceeds to state 19 (Shutdown).
Class Refers to the Global Timers
A always B1 or B2 C
S1 thru S5
NFEvent Clear Action required to clear the fault or event:
Requires Ack
Requires Reset
Self ClearingSignal Type Unused
Digital
Setpoint State Tmr Exp
Maint Tmr Exp
Sequence
NF Timer ExpSignal Signal options are based on Signal Type
Unused = unavailable
Digital = list of digital in use devices to choose from
Setpoint = list of in use setpoints to choose from
State Tmr Exp = PANEL READY, STOP ENGINE, orSHUTDOWN
Maint Tmr Exp = list of in use maintenance timers tochoose from
Sequence = None, Overcrank, Crank Fault, PowerUp,Start, Stop, Reset, CAN Comms Fail
NF Timer Exp = Global NF Timer
-
7/31/2019 MConfigPro Manual
33/50
Section 50 00-02-060208-31-06 - 29 -
Startup
Field DescriptionAuto Start When set to Yes, automatically proceeds from state 1 (Panel Ready)
to next In Use state when no shutdown conditions exist.Enable Remote onPower Up
Yes or No
Remote Mode EnableDigital Input
None or list of In Use digital inputs
Use single DigitalInput to Start/Stop
Yes or No
Start (or Start/Stop)Digital Input
None or list of In Use digital inputs
Stop Digital Input None or list of In Use digital inputsReset Digital Input None or list of In Use digital inputs
Use single Setpointto Start/Stop
Yes or No
Start (or Start/Stop)Setpoint
None or list of In Use setpoints
Stop Setpoint None or list of In Use setpoints
-
7/31/2019 MConfigPro Manual
34/50
Section 50 00-02-060208-31-06 - 30 -
RPM Controls
-
7/31/2019 MConfigPro Manual
35/50
Section 50 00-02-060208-31-06 - 31 -
Field DescriptionDescription 5 entries are provided for RPM controls.
RPM Control Output
Cooldown RPM
Warmup RPM
Wait to Load RPM Run Loaded RPM
Signal Type Signal Type options are based on the RPM type listed in Description
RPM Control Output = Control Output
Cooldown RPM = none
Warmup RPM = none
Wait to Load RPM = none
Run Loaded RPM = noneValue Value of Signal Type:
For RPM Control Output, a list of In Use Control Outputs
For other Signal types, the target RPM control setpoint for thatState
-
7/31/2019 MConfigPro Manual
36/50
Section 50 00-02-060208-31-06 - 32 -
Control Outputs
Control Outputs allow you to define up to eight (8) outputs to augment control not otherwisedefined by digital output assignments. These outputs may be defined as analog output, digitaloutput, single pulsed digital output, or two pulsed digital outputs.
Note that Control Outputs 1 through 4 are directly related to Proportional Integral Derivative
(PID) calculation loops and are further defined in the PID dialog screens. For example, PID 1 isassigned its control from Control Output 1, PID 2 from Control Output 2, and so on.
-
7/31/2019 MConfigPro Manual
37/50
Section 50 00-02-060208-31-06 - 33 -
Field DescriptionDescription 8 entries are provided for configurable control outputs. The system
generated names may be changed to a more descriptive name ofyour choice. The field length for description is 17 characters.
In Use Active outputs must be set to In Use in order to show up onsubsequent configuration screens. Once the output is set to In Use,
the entry turns to bolded text.Ctrl Output Type None
Analog
2 Pulsed Digital
1 Pulsed Digital
DigitalOutput 1 List of In Use digital or analog outputs. Dependent on Ctrl Output
Type selected.Output 2 List of In Use digital outputs. This selection is only available for Ctrl
Output Type 2 Pulsed Digital
Increase Max on Time Assign value to increase Max On Time. Set limit of maximum on-timefor increase pulses.Increase OFF Time Set fixed off-time for Increase pulses.Incr. ChangeoverPulse ON Time
Set fixed on-time for single pulse on direction change for increase.
Incr. ChangeoverPulse OFF Time
Set fixed off-time for single pulse on direction change for increase.
Decrease Max Ontime
Set limit of maximum on-time for Decrease pulses.
Decrease OFF Time Set fixed off-time for Decrease pulses.Decr. Changeover
Pulse ON Time
Set fixed on-time for single pulse on direction change for Decrease.
Decr. ChangeoverPulse OFF Time
Set fixed off-time for single pulse on direction change for Decrease.
Increase/Decrease Pulse Settings
For Increase Settings
Available when the "Ctrl Output Type" is set to 1 or 2 pulsed digital.
For Decrease Settings and Changeover
Available when the "Ctrl Output Type" is set to 2 pulsed digital.
-
7/31/2019 MConfigPro Manual
38/50
Section 50 00-02-060208-31-06 - 34 -
States
States 6 thru 8 (A) are designated for engine cranking and therefore perform differently thanother states. When State 8 (Crank Rest) either times out or meets the permissive, it recyclesback to State 6 (Crank Stop). This cycle will continue until a permissive is met in State 7(Crank).
States 10 thru 13 (B) are the Running states. States 11 and 12 work in tandem to perform loadand unload functions. When State 11 (Wait to Load) times out or meets the permissive, it thencycles to State 12. When State 12 (Run Loaded) times out or meets the permissive it cyclesback to State 11. This cycle will continue until an event or Stop occurs.
To prevent the cycle, set the time in State 12 to 65535 and do not use a permissive.
-
7/31/2019 MConfigPro Manual
39/50
Section 50 00-02-060208-31-06 - 35 -
Field DescriptionState 1. Panel Ready
2. Start Delay3. Preheat4. Prelube5. Start Valve
6. Crank Stop7. Crank8. Crank Rest9. Motor On10. Warmup11. Wait to Load12. Run Loaded13. Cool Down14. Stop Engine15. Motor Off16. Stop Valve
17. Post Lube18. Restart Delay19. ShutdownThe state names can be changed. The field length is 13 characters.
NOTE: Crank must have a permissive. Crank Stop andCrank Rest will not proceed on to other states.
Description The system generated names may be changed to a more descriptivename of your choice. The field length is 13 characters.
In Use Active states must be set to In Use in order to show up onsubsequent configuration screens. Once the state is set to In Use,the entry turns to bolded text.
Timer (Secs) When set to 65535, there is No TimeoutPermissive Type Digital Input
Setpoint Timer Expiration
Maint Timer Exp
NF Timer ExpPermissive When any permissive type is chosen, a list of In Use items for that
base is shown.Ctrl Out 1 Value can be 0-100, or if -1, leave alone.
Ctrl Out 2 Value can be 0-100, or if -1, leave alone.Ctrl Out 3 Value can be 0-100, or if -1, leave alone.Ctrl Out 4 Value can be 0-100, or if -1, leave alone.Ctrl Out 5 Value can be 0-100, or if -1, leave alone.Ctrl Out 6 Value can be 0-100, or if -1, leave alone.Ctrl Out 7 Value can be 0-100, or if -1, leave alone.Ctrl Out 8 Value can be 0-100, or if -1, leave alone.
-
7/31/2019 MConfigPro Manual
40/50
Section 50 00-02-060208-31-06 - 36 -
Miscellaneous
-
7/31/2019 MConfigPro Manual
41/50
Section 50 00-02-060208-31-06 - 37 -
Field DescriptionDescription 13 miscellaneous entries are provided:
Number of Crank Attempts
Magnetic Input Teeth
RPM Source
Crank EndZero RPM Error Signal Oil Pressure Source
Water Temperature Source Suction Pressure Source
Discharge Pressure Source
Ignition Off in Crank Rest Fuel Off in Crank Rest
Core Temp Adjustment (tenths)
Expansion Temp Adjustment (tenths)
Temperature Units
Signal Type Signal Type is based on which entry is selected in Description. Notall entries use signal types.
RPM Source = None, Analog, Magnetic Input
Crank EndZero RPM Error Signal = None, Digital, Setpoint Oil Pressure Source = None, Analog
Water Temperature Source = None, Analog, Thermocouple Suction Pressure Source = None, Analog
Discharge Pressure Source = None, AnalogValue Value data is based on which entry is selected in Description. Not all
entries require a value.
Number of Crank Attempts number of crank attempts
Magnetic Input Teeth number of flywheel teeth Ignition Off in Crank Rest Yes or No
Fuel Off in Crank Rest Yes or No Core Temp Adjustment (tenths) adjustment degrees in
tenths
Expansion Temp Adjustment (tenths) adjustmentdegrees in tenths
Temperature Units C (Celsius) or F (Fahrenheit)
-
7/31/2019 MConfigPro Manual
42/50
Section 50 00-02-060208-31-06 - 38 -
PID
Up to four (4) Proportional Integral Derivative (PID) calculation loops may be configured inMConfigPro. A PID provides a constant feedback loop, in which the PID can correct for ameasured process variable against a desired setpoint , output the corrective action to theprocess and wait for and recalculate the next measurement. The ultimate goal of the PID is toreduce the error to zero.
During the time a PID is enabled, the PID always overrides control output settings found in thestates dialog. Recall that PID 1 assumes control of control output 1, PID 2 assumes control ofcontrol output 2, and so on.
Field DescriptionDescription 4 entries are provided to setup PIDs. The system generated names
may be changed to a more descriptive name of your choice. The field
length for description is 13 characters.
In Use Active PIDs must be set to In Use in order to show up onsubsequent configuration screens. Once the PID is set to In Use,the entry turns to bolded text.
Flag Increase Flag increase on increasing difference
Decrease Flag decrease on increasing difference
-
7/31/2019 MConfigPro Manual
43/50
Section 50 00-02-060208-31-06 - 39 -
Field DescriptionEnable Type Not Enabled
All States
Run Loaded State
All Running StatesFeedback Type None
Analog Thermocouple
RPM
PIDFeedback Base Options based on the feedback type.Setpoint The desired goalthe target feedback base value.RampTime (250ms) Time interval for the PID to calculate error.Deadband Value around the setpoint during which the PID will not calculate
error.Minimum Output Percentage as minimum output.Maximum Output Percentage as maximum output.
Proportional The output value that is proportional to the change of error.Integral To prevent the PID from oscillating or overshooting the setpoint,
assign a value to reset the system to produce zero error, or nudgethe process variable to the setpoint . This value is typically set tozero.
Derivative Value to rate of change of error. This value is typically set to zero.MaxRate of Change Percentage rate of change over which would cause harm to the
system.Override Type None
Digital Setpoint
Override Signal Options based on the Override Type.Override RampAmount
Determine the increments in a given direction (positive or negative)that the setpoint should be altered to regain balanced processes. Inthe example of the discharge and suction pressure application, thisvalue would indicate how much the PID should resist its goal inreaching the setpoint.
Override Ramp Time Time interval value to wait before making the next adjustmentOverride Max Change A maximum allowed change. This represents the total amount of
change allowed into or out of the ramp amount from the setpoint. Themaximum change value should be large enough to effect change.
-
7/31/2019 MConfigPro Manual
44/50
Section 50 00-02-060208-31-06 - 40 -
Comm Port Settings
Field DescriptionDescription Modbus Address Port 1
Comm Port 1
Delay Modbus Reply Port 1 (ms)
BaudRate Port 1 Comm Port 2 Delay Modbus Reply Port 2 (ms)
BaudRate Port 2Value Based on entry selected in description
Comm Port 1 = RS232 or RS485
BaudRate Port 1 = 9600, 19200, 38400, 57600, or 115200 Comm Port 2 = RS232 or RS485
BaudRate Port 2 = 9600, 19200, 38400, 57600, or 115200
-
7/31/2019 MConfigPro Manual
45/50
Section 50 00-02-060208-31-06 - 41 -
Guidelines for Configuring MConfigPro
This section provides guidelines for setting up common configuration items in MConfigProsuch as inputs, outputs, setpoints, timers, alarms, and events, etc. for pumps, reciprocatingcompressors, and screw compressors. For detailed screen/field information, refer to thechapter titled Main Menu List - Screen Definitions.
There is a logical sequence to follow when configuring the Centurion. These sequences will beexplained in four separate topics. They are:
Defining the System
System of Protection
System of Operation
System of Interface
Defining the System
The first step in defining the system is to gather information for setting up your analog and/ordigital devices and control outputs. For your convenience, you may want to make a checklist ofthis information for entering into MConfigPro. Once this information has been entered, it will beavailable for subsequent configuration options.
The following items from the Main Menu List allow you to define the system. Refer to thechapter titled Main Menu List - Screen Definitions for information on field options you will beentering.
I/O Scheme
Define the I/O scheme of devices you have:
Digital Input/Output devices
Analog Input/Output devices
Control Output
Define Control Outputs, based on control type (analog, digital, 1 or 2 pulsed digital)
Global Timers
What are the manufacturers suggested specifications for protection to create the necessary
setpoints? This information can usually be found in the equipment manual that came with theproduct.
Maintenance Timers
What are the recommended intervals for maintenance? This information can usually be foundin the equipment manual that came with the product.
-
7/31/2019 MConfigPro Manual
46/50
Section 50 00-02-060208-31-06 - 42 -
System of Protection
This portion of the configuration allows you to setup events to define when a system willindicate an alarm, a message, or will be shutdown. It also allows for defining how an alarm iscleared.
Shutdowns may be defined by the following types:
Stop a controlled stop under normal conditions
Fault SD abnormal conditions with minimal consequences (not catastrophic)
ESD immediate emergency shutdown
The following items from the Main Menu List allow you to define the system of protection.Refer to the chapter titled Main Menu List - Screen Definitions for information on field optionsyou will be entering.
Events
What steps need to be taken to shutdown equipment on Stop, Fault SD, or ESD conditions?
What types of alarms or messages need to be defined and how will they be acknowledged?
System of Operation
The sequences to be defined for system of operation determine the day-to-day, normaloperation of your equipment. The following items from the Main Menu List allow you to definethe system of operation. Refer to the chapter titled Main Menu List - Screen Definitions forinformation on field options you will be entering.
StartupWhat are the procedures for initiating a start?
RPM Control
Consideration point: If control outputs exist, do they need RPM control?
States
States reflects all steps from evaluating conditions, to controlling start, stop, and running theequipment. The ideal operating condition is Run Loaded.
Miscellaneous
The miscellaneous menu option contains various options to be set that dont directly relate toprocess I/O. They control items such as number of crank attempts and oil pressure source andwater temperature source.
PID
PID runs as a parallel process to System of Operation. Determine at what point or state type itis enabled.
-
7/31/2019 MConfigPro Manual
47/50
Section 50 00-02-060208-31-06 - 43 -
System of Interface
This sequence determines the communication port setup for downloading the MConfigProconfiguration files. It also determines how information is displayed on the Centurion. Thefollowing items from the Main Menu List allow you to define the system of interface. Refer tothe chapter titled Main Menu List - Screen Definitions for information on field options you willbe entering.
Comm Port Settings
Determine which type of connection will be used:
USB Connection
Serial Connection (RS-232 or RS-485)
Specify behavior of communication ports. Specify how to represent various information comingfrom the comm ports.
Display ScreensThis step is only necessary if the system of interface is the Centurion display.
Configuration Download Instructions
Once your configuration files are setup, you may download them to the Centurion controllerthrough either a USB port, or serial port (Com1 or Com2).
Comm. Port Settings
Before you can download files to the Centurion controller, the communication port settings
must be established for serial ports Com1 or Com2.
-
7/31/2019 MConfigPro Manual
48/50
Section 50 00-02-060208-31-06 - 44 -
(THIS PAGE INTENTIONALLY LEFT BLANK)
-
7/31/2019 MConfigPro Manual
49/50
Section 50 00-02-060208-31-06 - 45 -
MURPHY, the Murphy logo, Centurion, and MConfigPro are registered and/or common law trademarks ofMurphy Industries, Inc. This document, including textual matter and illustrations, is copyright protected by MurphyIndustries, Inc., with all rights reserved. (c) 2005 Murphy Industries, Inc. Other third party product or trade namesreferenced herein are the property of their respective owners and are used for identification purposes only.
-
7/31/2019 MConfigPro Manual
50/50