Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ......

42
Drives Solutions www.danfoss.com/drives Instruction manual Lonworks ® 78 kbps and 1.25 Mbps Option Card VLT ® 5000 / 6000

Transcript of Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ......

Page 1: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

Drives Solutions

www.danfoss.com/drives

Instruction manual

Lonworks® 78 kbps and 1.25Mbps Option Card

VLT® 5000 / 6000VLT® 5000 / 6000

Instructions manual

175R0202 MG60E422 REV. 2003-03-06

XREF__BCNOT LOADED ON RIP

*MG60E422*

Page 2: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

LonWorks® 78 kbps and 1.25 MbpsOption Card

Instruction Manual

Page 3: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

2 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

�������Rotating shafts and electrical equipment canbe hazardous. Therefore, it is stronglyrecommended that all electrical work conformto the National Electrical Code (NEC) and alllocal regulations. Installation, start-up andmaintenance should be performed only byqualified personnel.

Factory recommended procedures, included in this manual,should be followed. Always disconnect electrical power beforeworking on the unit.

Although shaft couplings or belt drives are generally notfurnished by the manufacturer, rotating shafts, couplings andbelts must be protected with securely mounted metal guardsthat are of sufficient thickness to provide protection againstflying particles such as keys, bolts and coupling parts. Evenwhen the motor is stopped, it should be considered “alive”as long as its controller is energized. Automatic circuits maystart the motor at any time. Keep hands away from the outputshaft until the motor has completely stopped and power isdisconnected from the controller.

Motor control equipment and electronic controls areconnected to hazardous line voltages. When servicing drivesand electronic controls, there will be exposed componentsat or above line potential. Extreme care should be taken toprotect against shock. Stand on an insulating pad and makeit a habit to use only one hand when checking components.Always work with another person in case of an emergency.Disconnect power whenever possible to check controls orto perform maintenance. Be sure equipment is properlygrounded. Wear safety glasses whenever working on electriccontrol or rotating equipment.

Safety Guidelines1. The drive must be disconnected from the AC line before

any service work is done.2. The “Stop/Off” key on the local control panel of the drive

Touching electrical parts may be fatal – even after equipment has been

disconnected from AC line. To be sure that capacitors have fully dis-

charged, wait 14 minutes after power has been removed before touching

any internal component.

�������

does not disconnect the equipment from the AC line andis not to be used as a safety switch.

3. Correct protective grounding of the equipment must beestablished. The user must be protected against supplyvoltage and the motor must be protected againstoverload in accordance with applicable national and localregulations.

4. Ground currents are higher than 3 mA.

Warnings Against UnintendedStart1. While the drive is connected to the AC line, the motor

can be brought to a stop by means of external switchclosures, serial bus commands or references. If personalsafety considerations make it necessary to ensure thatno unintended start occurs, these stops are not sufficient.

2. During programming of parameters, the motor may start.Be certain that no one is in the area of the motor ordriven equipment when changing parameters.

3. A motor that has been stopped may start unexpectedlyif faults occur in the electronics of the drive, or if anoverload, a fault in the supply AC line or a fault in themotor connection or other fault clears.

4. If the “Local/Hand” key is activated, the motor can onlybe brought to a stop by means of the “Stop/Off” key oran external safety interlock.

NOTE:It is responsibility of user or person installingdrive to provide proper grounding and branchcircuit protection for incoming power andmotor overload according to National ElectricalCode (NEC) and local codes.

The Electronic Thermal Relay (ETR) is UL listed. VLTs provideClass 20 motor overload protection in accordance with theNEC in single motor applications, when VLT 6000 parameter117 (VLT 5000 parameter 128) is set for ETR Trip 1 andparameter 105 is set for rated motor (nameplate) current.

Page 4: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

3MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Table of Contents

OverviewIntroduction ............................................................................................. 5About This Manual .................................................................................. 5Assumptions ........................................................................................... 5What You Should Already Know ............................................................ 5References .............................................................................................. 5LonWorks Overview ................................................................................ 6LON Concept ........................................................................................... 6Applications ............................................................................................ 6VLT LonWorks Option Card .................................................................... 7Node Arrangements ................................................................................ 7Message Passing .................................................................................... 7Collision Detection ................................................................................. 8Network Management ............................................................................. 8Routers and Bridges ............................................................................... 9

InstallationWiring Installation ................................................................................... 10Card Installation ...................................................................................... 10Tools Required ........................................................................................ 10VLT LonWorks Option Card.......................................................................11Installation Instructions ......................................................................... 12Network Initialization of LonWorks Option Card .................................. 19LonMark XIF Files ................................................................................... 19

Twisted Pair Network Configuration78 kbps and 1.25 Mbps Transformer Coupled Twisted Pair Model ....... 20Double Terminated Bus Topology ........................................................... 20Terminator Switch ................................................................................... 20Performance Specification ...................................................................... 21Communication on TP/XF-78 and TP/XF-1250 Channels ...................... 21

Diagnostic LEDsLonWorks Card Diagnostic LEDs ........................................................... 22Status LED ............................................................................................... 22Service LED ............................................................................................. 22Service LED Patterns and Descriptions ................................................. 23

Page 5: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

4 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Interface/Network VariablesVLT Adjustable Frequency Driveand LonWorks Network Configuration ................................................... 24Network Drive Control Input ................................................................... 24Drive Feedback to Network ..................................................................... 27Drive Status Bit Definitions ..................................................................... 28Network Timer Functions ....................................................................... 30VLT Parameter Access ............................................................................ 31Parameter Access Error Codes ............................................................... 32Parameter Access Command and Response Examples........................ 32Standard Object Support ........................................................................ 34Alarm Descriptions .................................................................................. 35

ParametersParameter List ......................................................................................... 36Parameter Description ............................................................................. 36

Decommissioning VLT Adjustable Frequency DriveDecommissioning VLT Drive from LonWorks Network ......................... 39

Page 6: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

5MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

This manual is intended to be used for bothinstruction and reference. It only brieflytouches on the basics of the LonWorksprotocol whenever it is necessary for gainingan understanding of the LonWorks profile fordrives and the LonWorks Option Card for theAdjustable frequency drive.

This manual is also intended to serve as aguideline when you specify and optimize your

Introduction

About ThisManual

What YouShouldAlready Know

Assumptions

This manual provides comprehensiveinstructions on the installation and set up ofthe LonWorks Option Card for the VLT 5000and the VLT 6000 Adjustable Frequency Driveto communicate over a LonWorks network.

For specific information on installation andoperation of the adjustable frequency drive,refer to the VLT 5000 Installation, Operationand Instruction Manual or VLT 6000Installation, Operation and Instruction Manual.

Portions of this manual are printed with thepermission of the Echelon Corporation and theNational Electrical Contractors Association ofthe USA (NECA).

Echelon®, LonTalk®, Neuron® and LonWorks®

are registered trademarks of the EchelonCorporation. VLT® is a registered trademarkof Danfoss Inc.

The Danfoss LonWorks Option Card isdesigned to communicate with any controllernode that supports the interfaces defined in

this document. It is assumed that you havefull knowledge of the capabilities andlimitations of the controller node.

This manual assumes that you have acontroller node that supports the interfacesin this document and that all the requirementsstipulated in the controller node, as well as

the Adjustable Frequency Drive, are strictlyobserved along with all limitations therein.

communication system. Even if you are anexperienced LonWorks programmer, wesuggest that you read this manual in its entiretybefore you start programming, since importantinformation can be found in all sections.

References LonMaker™ for Windows® User's Guide.

VLT® 5000 Installation, Operation andInstruction Manual(Referred to as the VLT Instruction Manual inthis document.)

VLT ®6000 Installation, Operation andInstruction Manual(Referred to as the VLT Instruction Manual inthis document.)

Page 7: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

6 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

LONConcept

LonWorksOverview

Applications

LonWorks is both an existing standard andhardware developed by Echelon Corporation.Echelon's stated goal is to establish a com-modity solution to the presently dauntingproblems of designing and building controlnetworks.

The result is LonMark Interoperability whichmakes it possible for independent networkdevices to operate together over aLonWorks network. The LonMark programwas developed to address interoperabilityissues. As a result, the LonMarkInteroperability Association Task Groups(LonUsers Groups) were developed. Thetask groups determine that each device onthe network has an object definition, create

The LonWorks communications structure issimilar to that of a local area network (LAN)in that messages are continually exchangedbetween a number of processors. ALonWorks system is a determined localoperating network (LON). LON technologyoffers a means for integrating variousdistributed systems that perform sensing,monitoring, control, and other automatedfunctions. A LON allows these intelligentdevices to communicate with one anotherthrough an assortment of communicationsmedia using a standard protocol.

LON technology supports distributed, peer-to-peer communications. That is, individual

network devices can communicate directlywith one another without need for a centralcontrol system. A LON is designed to movesense and control messages which aretypically very short and which containcommands and status information thattrigger actions. LON performance is viewedin terms of transactions completed persecond and response time. Control systemsdo not need vast amounts of data, but theydo demand that the messages they sendand receive are absolutely correct. The criticalfactor in LON technology is the assuranceof correct signal transmission and verification.

An important LonWorks benefit is thenetwork’s ability to communicate acrossdifferent types of transmission media. TheNEURON chip is the heart of the LonWorkssystem. The NEURON chip's commu-nication port allows for the use oftransceivers for other media (such as coaxand fiber optic) to meet special needs.

LonWorks control devices are called nodes.Physically, each node consists of a NEURON

chip and a transceiver. With proper design,the nodes become building blocks that can

be applied to control a variety of tasks, suchas lighting or ventilating, integrating a varietyof communications media.

The tasks which the nodes perform aredetermined by how they have beenconnected and configured. Becausehardware design, software design, andnetwork design may be independent in aLonWorks-based system, a node’s functioncan be programmed to accommodate thenetworks in which it will be used.

standards and models to be used byparticular applications and create a commonplatform for presenting data. A standardnetwork variable type (SNVT) facilitatesinteroperability by providing a well definedinterface for communication betweendevices made by different manufacturers.The VLT Adjustable Frequency Drivesupports the node object and controllerstandard object definitions of LonMarkInteroperability.

Customers are currently using LonWorks forprocess control, building automation, motorcontrol, elevator operation, life safetysystems, power and HVAC distribution andsimilar intelligent building applications.

Page 8: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

7MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

MessagePassing

NodeArrangements

LonWorks nodes can be addressed eitherindividually or in groups. A group can containup to 64 nodes, and one LonWorks networkcan support 255 groups. Furthermore, anynode can be part of 15 different groups. Asubnet, very similar to a group, can contain127 nodes. A domain is the largestarrangement of nodes with a single domainable to handle 255 subnets. Thus a domaincan handle 32,385 separate nodes. A singlenode may be connected to no more than twodomains.

The group structure has the advantage ofallowing a number of nodes to be reached atonly one address. This method reduces the

record keeping inside each chip to a minimum,allowing faster operation. However, highefficiency individual addressing can be doneat all levels of a LonWorks system. Theaddress table of a node contains entries forthe group type and size and tells the nodehow many acknowledgments to expect whenit sends a message. It also tells the NEURON

chip which domain to use and the node groupmember number, which identif ies anacknowledgment as coming from the node.The address also contains a transmit timer, arepeat timer, a retry counter, a receive timer,and the group ID.

There are a number of trade-offs betweennetwork efficiency, response time, security,and reliability. Generally, LonWorks defaults tothe greatest degree of safety and verificationfor all communications over the LON network.The LonTalk protocol, built into the chips, isthe operating system that coordinates theLonWorks system. It offers four basic typesof message service.

The most reliable service is acknowledged (orend-to-end acknowledged service), where amessage is sent to a node or group of nodesand individual acknowledgments are ex-pected from each receiver. If anacknowledgment is not received from all des-tinations, the sender times out and re-triesthe transaction. The number of retries andtime-out duration are both selectable. Ac-

VLT LonWorksOption Card

The Danfoss VLT LonWorks option card iscomprised of a control card with a NEURON

chip and a memory card. When installed intothe VLT adjustable frequency drive, the unitenables the drive to communicate with otherdevices on the LON. The VLT drive is designedto provide precision control of standardinduction electrical motors. The drive receivesthree reference signals along with start/stopand reset commands from the network. Thedrive also receives a 16-bit control word thatprovides full operational control of the drive.(See Network Drive Control Input for additionaldetails.)

In response, the drive provides 16 outputnetwork variables containing important driveand motor data. (See Drive Feedback toNetwork.) Output to the network includesdrive status, current, voltage, motor andinverter thermal status, and alarms andwarnings.

LonWorks supports many different types oftransmission media. A LonWorks networkphysical layer option can be transformercoupled twisted pair (78 kbps and 1.25Mbps), free topology, link power, power line,RF, RS-485, fiber optic, coaxial, or infrared.

The VLT LonWorks option supports fourtransmission media with three versions of theVLT LonWorks option card. The VLTLonWorks option card versions are:

1. Free topology, which also operates ona link power network.

2. 78 kbps transformer coupled twistedpair.

3. 1.25 Mbps transformer coupled twistedpair.

A router is required to interface to a LonWorksnetwork when not supported by one of thethree option card versions.

Page 9: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

8 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

CollisionDetection

NetworkManagement

Depending on the level of a given application,a LonWorks network may or may not requirethe use of a network management node. Anetwork management node performsmanagement functions, such as:

• Find unconfigured nodes anddownload their network addresses.

• Stop, start, and reset nodeapplications.

• Access node communication statistics.• Configure routers and bridges.• Download new applications programs.• Extract the topology of a running

network.

The LonTalk protocol uses a unique collisionavoidance algorithm which allows anoverloaded channel to carry near to itsmaximum capacity, rather than reducing itsthroughput due to excessive collisionsbetween messages. When using acommunications medium that supportscollision detection, such as twisted pair, theLonTalk protocol can optionally canceltransmission of a packet as soon as a collisionis detected by the transceiver. This option

allows the node to immediately retransmit anypacket that has been damaged by a collision.Without collision detection, the node wouldwait the duration of the retry time to noticethat no acknowledgment was received. At thattime it would retransmit the packet, assumingacknowledge or request/response service.For unacknowledged service, an undetectedcollision means that the packet is not receivedand no retry is attempted.

knowledgments are generated by the networkhost processor without intervention of the ap-plication. Transaction IDs are used to keeptrack of messages and acknowledgments sothat the application does not receive dupli-cate messages.

An equally reliable service is request/response,where a message is sent to a node or groupof nodes and individual responses are ex-pected from each receiver. Incomingmessages are processed by the applicationon the receiving side before a response isgenerated. The same retry and time-out op-tions are available as with acknowledgedservice. Responses may include data, so thatthis service is particularly suitable for remoteprocedure call or client/server applications.

Next in reliability is unacknowledged repeated.Messages are sent multiple times to a nodeor a group of nodes with no responseexpected. This service is typically used whenbroadcasting to large groups of nodes whentraffic generated by all the responses wouldoverload the network.

The final method in reliability is unac-knowledged, where a message is sent onceto a node or group of nodes and no responseis expected. This option is typically used whenthe highest performance is required, networkbandwidth is limited, and the application isnot sensitive to the loss of a message.

MessagePassing(continued)

Page 10: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

9MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Routers andBridges

A router (or bridge) is a special node thatconsists of two connected NEURON chips, eachconnected to a separate channel (see figurebelow). Routers and bridges pass packetsback and forth between these channels. Thereare four types of routers. A repeater is thesimplest form of router, simply forwarding allpackets between the two channels. A bridgesimply forwards all packets which match itsdomains between the two channels. Using abridge or repeater, a subnet can exist acrossmultiple channels. A learning router monitorsthe network traffic and learns the networktopology at the domain/subnet level. Thelearning router then uses its knowledge toselectively route packets between channels.Like a learning router, a configured routerselectively routes packets between channelsby consulting internal routing tables. Unlike alearning router, the contents of the internalrouting tables are specified using networkmanagement commands.

Initially, each router sets its internal routing tablesto indicate that all subnets could lie on either sideof the router. Suppose that node 6, in the figurebelow, generates a message bound for node 2.Learning router 1 initially picks up the message.It examines the source subnet field of themessage and notes in its internal routing tables

Learning RoutersSource: Echelon Corp.

that subnet 2 lies below it. The router thencompares the source and destination subnet IDsand, since they are different, the message ispassed on. Meanwhile, learning router 2 alsopasses the message on, making an appropriatenotation in its internal routing tables regarding thelocation of subnet 2.

Suppose now that node 2 generates anacknowledgment. This acknowledgment ispicked up by learning router 1, which now notesthe location of subnet 1. Learning router 1examines its internal routing tables, and, notingthat subnet 2 lies below, passes the messageon. When the message appears on subnet 2, itis noted by both node 6 (the destination) andlearning router 2. Learning router 2 does not passit on but merely notes that subnet 1, like subnet2, lies somewhere above. Learning router 2 willnot learn of the existence or location of subnet 3until a message is originated from there. Subnetscannot cross routers. While bridges andrepeaters allow subnets to span multiplechannels, the two sides of a router must belongto separate subnets. Since routers are selectiveabout the packets they forward to each channel,the total capacity of a system can be increasedin terms of nodes and connections.

9 10 11 12

1 2 3 4

5 6 7 8

R

R

Channel

Channel

Channel

Subnet 1

Subnet 3

Subnet 2

LearningRouter 1

LearningRouter 2

Page 11: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

10 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

WiringInstallation

VLT adjustable frequency drivecontains dangerous voltageswhen connected to line power.After disconnecting from line,wait at least 14 minutes beforetouching any electrical com-ponents.

Only a competent electricianshould carry out electricalinstallation. Improper installationof motor or VLT can causeequipment failure, serious injuryor death. Follow this manual,National Electrical Code (USA)and local safety codes.

��������

������

������Electronic components of VLTadjustable frequency drives aresensitive to electrostatic dis-charge (ESD). ESD can reduceperformance or destroy sensitiveelectronic components. Followproper ESD procedures duringinstallation or servicing toprevent damage.

It is responsibility of user orinstaller of VLT adjustablefrequency drive to provide propergrounding and motor overloadand branch protection accordingto National Electrical Code (USA)and local codes.

�������

WWWWWiringiringiringiringiringThe adjustable frequency drive generates acarrier frequency with a pulse frequencybetween 3 kHz and 14 kHz. This results inradiated frequency noise from the motorcables. It is very important that the LonWorkscable be isolated as much as possible fromthe drive output cabling to the motor. Useshielded wire rather than twisted-pair. Do notrun LonWorks cabling and motor cables inparallel or in close proximity to one another.Ensure that the drive is properly grounded.

The following section describes the installationprocedures for the LonWorks option card (seefollowing illustration). For additional informationon installation and operation of the VLTadjustable frequency drive, refer to the VLTInstruction Manual.

CardInstallation

ToolsRequired

Flat-head screw driverTorx T-10 screw driverTorx T-20 screw driver

Page 12: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

11MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

VLT LonWorks Option Card(Free Topology Model)

LEDsTerminalConnector

Service PinSwitch SW1 Mounting Hole

LEDs

TerminalConnector

Service PinSwitch SW3

TerminatorSwitch

RibbonCableSocket(to MemoryBoard)

RibbonCableSocket(to ControlBoard)

Memory Board

RibbonCableSocket(to drivecontrolboard)

LonWorks Control Board

HostChip

DriveMemory

Page 13: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

12 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Installation Instructions

1. Access toControlCardCassette

• Remove control wiring by unpluggingconnector terminals (A).

• Remove grounding clamps (B) byremoving two screws holding each inplace. Save screws for reassembly.

• Loosen two captive screws (C) securingcassette to chassis.

2. DisconnectControlCardCassette

IP20/NEMA 1 and Bookstyle• Remove Local Control Panel (LCP) by

pulling out from top of display (A) byhand. LCP connector on panel backwill disconnect.

• Remove protective cover by gentlyprying with a screw driver at notch (B)and lift cover out of guide pin fittings.

IP54/NEMA 12• Open front panel of drive by loosening

captive screws and swing open.• Disconnect Local Control Panel (LCP)

cable from drive control card.

(A)

(B)

(A)

(B)

(C)

Page 14: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

13MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

• Lift control card cassette from bottom.• Unplug two ribbon cables (A) and (B)

from control board.• Unhinge cassette at top to remove.

3. RemoveCassetteand RibbonCables

NOTERibbon cables will need to bereconnected to same connec-tions from which removed.

4. ChassisGroundConnections

• Location of holes to mount groundingstrips can vary with drive configuration.When applicable, remove mountingscrews and washers located in chassisusing Torx T-20 screw driver and savefor reassembly. Otherwise, groundingstrips attach with screws and washersprovided, as shown in step 5.

NOTEGround strips are used on 208 Vdrives of 22 kW (30 HP) or lessand on 460 V drives of 45 kW(60 HP) or less. For all otherdrives, go to step 6.

(A)

(B)

Page 15: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

14 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

• Align ground strips over screw holes.Strip with fewest contact points mountson cable side of chassis. Tabs ongrounding strips point toward outsideof chassis.

• Replace screws removed in step 4 andadd additional screws and washersprovided, as necessary. Tighten to0.9 Nm (8 in-lbs) using Torx T-20 screwdriver.

5. InstallChassisGroundConnections

GroundStrips

• Attach ribbon cables betweenLonWorks control card and memorycard.

• Be sure exposed wire portion of ribboncable (A) is facing front of socket (B).Do not remove blue insulation coveringend of ribbon cable.

• Pull up collar (C) of ribbon cable socket,insert cable and push collar closed.

• Repeat procedure for all ribbon cables.

IP20/NEMA 1 and IP54/NEMA 12• Remove terminal connector from

terminal block (D) and connect toterminal block (E) at this time for easeof access.

6. InstallRibbonCablesbetweenOptionCards

(D)

(E)

Page 16: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

15MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

• Insert edge of LonWorks cards into slotin side of cassette and align screwholes.

9. InsertLonWorksCard

• Route ribbon cables from LonWorksmemory card through slot at side ofcontrol board cassette.

8. RibbonCableRouting

7. RemoveLCP Cradle

IP20/NEMA 1 and Bookstyle• Carefully push in tabs at corners of LCP

cradle to release clips. Pull out todisengage clips and lift cradle free.

Page 17: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

16 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

11. InstallRibbonCable onVLT ControlBoard

• Be sure not to twist or crimp ribboncables.

• Insert cables into correspondingsockets and fasten in accordance withdirections in step 5.

IP20/NEMA 1 and Bookstyle• Insert cradle clips into holes in cassette.• Push down on cradle to snap it into

place.

12. InstallLCP Cradle

• Secure LonWorks card with 3self-tapping screws and washersprovided using Torx T-10 screw driver.Tighten to 8 in-lbs (0.9 Nm).

10. SecureLonWorksCard

Page 18: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

17MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

• Connect ribbon cables.• Connect control card cassette to hinge

at top of drive and fit into chassis.

14. InstallRibbonCables

NOTERibbon cables must be recon-nected to same connections fromwhich removed.

IP20/NEMA 1 and IP54/NEMA 12• Spring tension clip (A) is used as a cable

strain relief and ground point forshielded cable.

• Insert clip through inner wall of chassisat slot provided.

• Compress spring into clip at outer wallof chassis.

13. InstallSpringTensionClip

(A)

Page 19: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

18 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

15. InstallControl CardCassette

16. Plug inTerminalConnector

NOTEShielded cable is recommended.Ground shielded cable at springtension clip location or ground atcable clamp by removing cableinsulation at contact point. Do notuse connector terminal 61.

• Fasten control card cassette byalternately tightening two captivescrews (A). Tighten to 0.9 Nm (8 in-lbs).

• Route control wires through clampfasteners (B) and secure clamps withtwo screws.

• Connect control terminals (C) by firmlypressing them into connectorreceptacles.

(A)

(B)

(C)

• Connect signal wire NET A to terminal79 and NET B to 80 of terminalconnector. (In free topology model,connections can be reversed.)

IP20/NEMA 1 and IP54/NEMA 12• Plug network connector into terminal

block at side of control card cassette.• Insert LonWorks cable between inner

wall of chassis and spring tension clip.

Bookstyle• Remove knockout from top of drive (A).• Route control wires through clamp

fasteners (B) on cable plate and secureclamps with screws. Tighten to 0.9 Nm(8 in-lbs).

• Secure cable plate to drive with screwsand screw holes provided. Tighten to0.9 Nm (8 in-lbs).

• Plug network connector (C) intoterminal block at top of control cardcassette. (A)

(B)

(C)

Shield

61N

ET

B

80

NE

T

A

79

7980

61

Page 20: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

19MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

NetworkInitializationof LonWorksOption Card

LonMarkXIF Files

A LonMark interface file (.XIF extension)provides the host processor with deviceinformation. With this, it is possible to designa LonWorks network without the adjustablefrequency drive being physically present.The VLTLON.XIF can be downloaded fromthe Internet site www.danfoss.com/drives. TheLonWorks option card does not contain aninternal interface file.

Echelon Corporation has also developed a setof free plug-ins available through their web siteat www.echelon.com/plugin/default.htm. Alsointended for network design, these plug-insprovide easy access to screens which simplifythe process of manually setting up the drive,testing, and monitoring operation.

The drive may also be added to the networkupon initialization.

The LonWorks option card contains a NEURON

chip with a unique address. After hardwareinstallation, initialize the LonWorks option card.Addressing nodes on the LonWorks networkis performed at installation time by aninstallation tool or network management tool.Addressing requires the retrieval of a node’sNEURON ID. The NEURON ID is a 48 bit numberthat identifies every manufactured NEURON

chip. There are several methods by which thenetwork software will initialize the driveautomatically. The network can recognize thedrive without action beyond properinstallation. The card is then ready to beprogrammed for network operation. The VLTLonWorks option supports three additionalmethods of addressing a node:

1. Service Pin - There are twomomentary-contact service switches thatsend the NEURON ID over the network. If thenetwork software prompts the action, press

either service pin (SW1 or SW3) to transmitthe NEURON ID over the network. The servicepin locations are shown in the illustration inTerminator and Service Switch Locations inthis manual.

2. Query and Wink - The LonWorks optioncard is shipped with a domain of “0” andsubnet of “1.” Upon receiving the winkcommand, the on-board green status LEDflashes so that the installer can locate thenode. The chip sends out its Neuron ID overthe network in response to the querycommand.

3. NEURON ID Label - The VLT LonWorksoption card has a NEURON ID label thatdisplays the NEURON ID as a 12 digithexadecimal number. The installer canmanually enter the NEURON ID duringinstallation.

The VLT LonWorks network interface consistsonly of SNVTs. The SNVTs support theLonMark Controller Profile along with VLTconfiguration, control and monitoringcapabilities. Any combination of SNVTs canbe used to operate the VLT.

Page 21: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

20 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

The terminator switch location for the 78 kbpsor 1.25 Mbps Transformer Coupled TwistedPair model is shown below.

78 kbps and1.25 MbpsTransformerCoupledTwisted PairModel

The 78 kbps and 1.25 Mbps TransformerCoupled Twisted Pair model system isdesigned to support doubly terminated bustopology.

TERMINATION TERMINATION

Doubly TerminatedBus Topology

TRANSCEIVER

Switch 1:Switch 1:Switch 1:Switch 1:Switch 1:

Network TNetwork TNetwork TNetwork TNetwork Termination ONermination ONermination ONermination ONermination ONThe VLT LonWorks node isterminated.

Network TNetwork TNetwork TNetwork TNetwork Termination OFFermination OFFermination OFFermination OFFermination OFFThe VLT LonWorks node is not

terminated. Factory setting.

Terminatorand ServiceSwitchLocations

78 kbps and 1.25 Mbps LonWorksControl Card

TTTTTerminator Switcherminator Switcherminator Switcherminator Switcherminator SwitchService Pin SwitchesService Pin SwitchesService Pin SwitchesService Pin SwitchesService Pin Switches

Page 22: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

21MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

PerformanceSpecification

The table below provides a summary of theperformance specifications for the 78 kbps and

Communica-tion on TP/XF-78 andTP/XF-1250Channels

1Typical conditions are 20°C (68°F), +5 VDCsupply voltage, normal wire temperature,and 64 evenly distributed nodes.

2Worst case conditions are the combinedeffect of worst case conditions of all theabove performance parameters — nodesper channel, network bus length, stublength, temperature, etc.

3The stub length in the table assumes a mutualcapacitance of 56 pF/m (17 pF/ft) for thetwisted pair stub cable. Actual lengths maybe shorter or longer depending on theactual, measured value.

It is necessary to terminate theIt is necessary to terminate theIt is necessary to terminate theIt is necessary to terminate theIt is necessary to terminate theends of a TP/XF-78 or TP/XF-1250ends of a TP/XF-78 or TP/XF-1250ends of a TP/XF-78 or TP/XF-1250ends of a TP/XF-78 or TP/XF-1250ends of a TP/XF-78 or TP/XF-1250twisted pai r bus to min imizetwisted pai r bus to min imizetwisted pai r bus to min imizetwisted pai r bus to min imizetwisted pai r bus to min imizerrrrreflections. Failureflections. Failureflections. Failureflections. Failureflections. Failure to terminate thee to terminate thee to terminate thee to terminate thee to terminate thebus wi l l degrade networkbus wi l l degrade networkbus wi l l degrade networkbus wi l l degrade networkbus wi l l degrade networkperformance.performance.performance.performance.performance.

������

1.25 Mbps transformer-coupled twisted pairchannels.

PerformancePerformancePerformancePerformancePerformance TP/XF-78TP/XF-78TP/XF-78TP/XF-78TP/XF-78 TP/XF-1250TP/XF-1250TP/XF-1250TP/XF-1250TP/XF-1250SpecificationsSpecificationsSpecificationsSpecificationsSpecificationsTransmission Speed 78kbps 1.25Mbps

Nodes per Channel 64 64

Network Bus Wiring UL Level IV, 0.65 mm (22 AWG) shielded

Network Stub Wiring UL Level IV, 0.5 mm (22 or 24 AWG) shielded

Network Bus LengthTypical 1 2000m (6,560 ft) 500m (1,640 ft)Worst case 2 1330m (4,360 ft) 125m (410 ft)

Maximum Stub Length 3 3m (10 ft) 0.3m (0 to 70°C)

1 ft (32°F to 158°F)

Network Terminators Required at both ends of the network

TemperatureOperating 0 to 70°C (64 nodes) 0 to +70°C (64 nodes)

(32°F to 158°F) (32°F to 158°F)

Non-operating –40 to +85°C (44 nodes) –20 to +85°C (32 nodes)(–40°F to +185°F) (–4°F to +185°F)

–40 to +70°C (20 nodes)(–40°F to +158°F)

Electrostatic Dischargeto Network Connectors

No Errors to 15,000 V to 15,000 VNo Hard Failures to 20,000 V to 20,000 V

Isolation between Networkand I/O Connectors

0 - 60Hz (60 seconds) 1,000 VRMS 1,000 VRMS0 - 60Hz (continuous) 277 VRMS 277 VRMS

Page 23: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

22 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

The Status LED patterThe Status LED patterThe Status LED patterThe Status LED patterThe Status LED patterns arns arns arns arns are:e:e:e:e:

ONONONONONThere is power on the board butthere has not been anycommunication to an input networkvariable in the last 2 seconds.

Flashing 10 times per secondFlashing 10 times per secondFlashing 10 times per secondFlashing 10 times per secondFlashing 10 times per secondThere is regular networkcommunication to the VLT's inputnetwork variables.

Flashing intermittentlyFlashing intermittentlyFlashing intermittentlyFlashing intermittentlyFlashing intermittentlyThere is network communication tothe VLT's input network variables butinput network variables are receivedat a period greater than 2 seconds.

Flashing 5 times per secondFlashing 5 times per secondFlashing 5 times per secondFlashing 5 times per secondFlashing 5 times per secondThe response to the networkmanagement “Wink” command. TheVLT LonWorks node must be reset toleave the wink state.

OFFOFFOFFOFFOFFNo power on board or hardware fault.

LonWorksCardDiagnosticLEDs

The LonWorks board includes two LEDs todisplay the communication status of theboard, display the state of the NEURON chip,and respond to the network management

LEDsLEDsLEDsLEDsLEDs

“wink” command. The onboard LEDs are theService LED (LED 1, red) and the Status LED(LED 2, green).

Status LED

Service LED The Service LED displays the state of theNEURON chip. The following table shows theService LED patterns for various states anddefines their meaning.

Page 24: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

23MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

LED Pattern Operation DescriptionContinuously ON Power-up of Neuron 3120xx

chip-based node or Neuron 3150 chip-based node with any PROM

Use EEBLANK and follow reinitialization procedure.

Continuously OFF Power-up of Neuron 3120xx chip-based node or Neuron 3150 chip-based node with any PROM

Indicates bad node hardware.

ON for one second at power-up followed by approximately 2 seconds OFF, then stays ON

Power-up/Reset May be caused by Neuron chip firmware when mismatch occurs in application checksum.

Indicates watchdog timer resets occurring.

Possible corrupt EEPROM.

For Neuron 3150 chip-based node, use EEBLANK and follow reinitialization procedure.

Flashing at 1 second intervals Anytime Indicates node is unconfigured but has an application. Proceed with loading node.

Brief flash at power-up. OFF duration approximately 10 seconds after which stays ON

Using EEBLANK or Neuron 3150 chip-based node

Indicate completion of blanking process.

Brief flash at power-up. OFF duration approximately 1 to 15 seconds, depending on application size and system clock. LED then begins flashing at 1 second intervals.

First power-up with new PROM on Neuron 3150 chip-based custom node. Unconfigured firmware state exported.

Indicates unconfigured state.

Brief flash at power-up followed by OFF

Node is configuring and running normally.

Short flash every 3 seconds Anytime

Service LEDPatterns andDescriptions

Service LED Pattern Descriptions

Page 25: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

24 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

VLT adjustablefrequency driveand LonWorksNetworkConfiguration

The VLT LonWorks option card supportsLonMark network design to improveinteroperability. The Controller Object containsthe VLT Adjustable Frequency Drive profile.The configuration parameters are network

Network Variable Inputs to VLT

Function SNVT type Variable Name Units Max Min

Start/Stop SNVT_lev_disc nviStartStop Boolean Start Stop

*Reset fault SNVT_lev_disc nviResetFault Boolean Reset Enable

Reference 1 SNVT_lev_percent nviRefPcnt 0.005% 163.835 –163.840

Reference 2 SNVT_angle_vel nviRefRads 0.1 rad/sec 3276.7 –3276.8

Reference 3 SNVT_freq_hz nviRefHz 0.1 Hz 6553.5 0

Control word SNVT_state nviControlword 16 Boolean NA NA

* Reset on a transition from 0 to 1. A “0” must be sent after reset to enable the next reset.

NetworkDriveControlInput

The most common functions for controllingthe VLT Adjustable Frequency Drive from theLonWorks network are made readily available.Those functions and their descriptions arepresented in the table below. The control wordfunction accesses additional drive capabilitiesfor network control.

The choice of open loop or closed loopoperation of the drive is selected in parameter100, Configuration.

Using nviRefPcnt, the drive's reference isexpressed as a percentage of the referencerange. The range is set using parameters 204,Min. Reference and 205, Max. Reference. Inopen loop operation, reference represents thedrive's desired output speed. In this case, setMin. Reference to 0 Hz and Max. Referenceequal to Max. Frequency in parameter 202.

In closed loop operation, reference representsthe desired setpoint. It is recommended thatparameters 204 and 205 be set equal toparameters 201, Min. Frequency and 202,Max. Frequency.

All references provided to the drive are addedto the total reference value. If reference is tobe controlled by the LonWorks bus only,ensure that all other reference inputs are zero.This means that digital input terminals and

variable inputs to the VLT. Configuration ofparameters needs setting only one time,usually at installation.

Start/Stop and Reset faultSNVT_lev_disc. ST_OFF and ST_NUL areinterpreted as low or “0.” ST_LOW, ST_MED,ST_HIGH, and ST_ON are interpreted as highor “1.”

NOTETo optimize network performanceand for proper drive operation,use only one of following inputreference commands.

Reference 1Network variable nviRefPcnt is a signed value.It represents the desired percentage of theVLT drive's reference range.

analog input terminals should not be used forreference signals. The default setting (0%)should be maintained for preset references inparameters 211 (215) through 214 (218). Also,in closed loop operation, the default setting(0.0) should be maintained for drive setpointsin parameters 418 (215) and 419 (218).

VLT 5000 parameters are shown in parenthesis, where applicable.

Page 26: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

25MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

BitBitBitBit 111100000000 ON 1ON 1ON 1ON 101010101 ON 2ON 2ON 2ON 202020202 ON 3ON 3ON 3ON 303030303 EnableEnableEnableEnable04040404 RampRampRampRamp05050505 Ramp EnableRamp EnableRamp EnableRamp Enable06060606 StartStartStartStart07070707 ResetResetResetReset08080808 ONONONON09090909 ONONONON10101010 ValidValidValidValid11111111 Slow downSlow downSlow downSlow down12121212 Catch upCatch upCatch upCatch up131313131414141415151515 ReversingReversingReversingReversing

BitBitBitBit SettingSettingSettingSetting 0000 111100000000 0000 Preset Ref. LSBPreset Ref. LSBPreset Ref. LSBPreset Ref. LSB01010101 0000 Preset Ref. MSBPreset Ref. MSBPreset Ref. MSBPreset Ref. MSB02020202 1111 DC BrakeDC BrakeDC BrakeDC Brake no DC Brakeno DC Brakeno DC Brakeno DC Brake03030303 0000 Coast StopCoast StopCoast StopCoast Stop no Coast Stopno Coast Stopno Coast Stopno Coast Stop04040404 1111 Quick StopQuick StopQuick StopQuick Stop no Quick Stopno Quick Stopno Quick Stopno Quick Stop05050505 1111 Freeze Freq.Freeze Freq.Freeze Freq.Freeze Freq. no Freeze Freq.no Freeze Freq.no Freeze Freq.no Freeze Freq. nviStartStopnviStartStopnviStartStopnviStartStop nviResetFaultnviResetFaultnviResetFaultnviResetFault06060606 0000 Ramp StopRamp StopRamp StopRamp Stop StartStartStartStart BitBitBitBit 0000 1111 0000 1111 DescriptionDescriptionDescriptionDescription07070707 0000 no Resetno Resetno Resetno Reset ResetResetResetReset 00000000 0000 0000 0000 Preset Ref LSBPreset Ref LSBPreset Ref LSBPreset Ref LSB08080808 0000 no Jogno Jogno Jogno Jog JogJogJogJog 01010101 0000 0000 0000 Preset Ref MSBPreset Ref MSBPreset Ref MSBPreset Ref MSB09090909 0000 no functionno functionno functionno function 02020202 1111 1111 1111 No DC BrakeNo DC BrakeNo DC BrakeNo DC Brake10101010 1111 see Parm. 805see Parm. 805see Parm. 805see Parm. 805 03030303 1111 1111 1111 No Coast StopNo Coast StopNo Coast StopNo Coast Stop11111111 0000 Relay 1 OFFRelay 1 OFFRelay 1 OFFRelay 1 OFF Relay 1 ONRelay 1 ONRelay 1 ONRelay 1 ON 04040404 1111 1111 1111 No Quick StopNo Quick StopNo Quick StopNo Quick Stop12121212 0000 Relay 2 OFFRelay 2 OFFRelay 2 OFFRelay 2 OFF Relay 2 ONRelay 2 ONRelay 2 ONRelay 2 ON 05050505 1111 1111 1111 No Freeze Freq.No Freeze Freq.No Freeze Freq.No Freeze Freq.13131313 0000 Setup LSBSetup LSBSetup LSBSetup LSB 06060606 0000 1111 0000 StartStartStartStart14141414 0000 Setup MSBSetup MSBSetup MSBSetup MSB 07070707 0000 0000 1111 ResetResetResetReset15151515 0000 no Reversingno Reversingno Reversingno Reversing ReversingReversingReversingReversing 08080808 0000 0000 0000 JogJogJogJog

09090909 0000 0000 0000 No functionNo functionNo functionNo function10101010 1111 1111 1111 Bit 10Bit 10Bit 10Bit 1011111111 0000 0000 0000 Relay 1 OnRelay 1 OnRelay 1 OnRelay 1 On12121212 0000 0000 0000 Relay 2 OnRelay 2 OnRelay 2 OnRelay 2 On13131313 0000 0000 0000 Setup LSBSetup LSBSetup LSBSetup LSB14141414 0000 0000 0000 Setup MSBSetup MSBSetup MSBSetup MSB15151515 0000 0000 0000 ReversingReversingReversingReversing

No

valu

e is

writ

ten

to t

he c

ontr

ol w

ord

N

o va

lue

is w

ritte

n to

the

con

trol

wor

d

No

valu

e is

writ

ten

to t

he c

ontr

ol w

ord

N

o va

lue

is w

ritte

n to

the

con

trol

wor

d

OFF 3OFF 3OFF 3OFF 3OFF 2OFF 2OFF 2OFF 2OFF 1OFF 1OFF 1OFF 1

0000

Ramp stopRamp stopRamp stopRamp stopFreeze out freq.Freeze out freq.Freeze out freq.Freeze out freq.

Quick stopQuick stopQuick stopQuick stopMotor coastingMotor coastingMotor coastingMotor coasting

No functionNo functionNo functionNo functionSetup 1 (LSB)Setup 1 (LSB)Setup 1 (LSB)Setup 1 (LSB)Setup 2 (MSB)Setup 2 (MSB)Setup 2 (MSB)Setup 2 (MSB)

No functionNo functionNo functionNo function

Jog 1 OFFJog 1 OFFJog 1 OFFJog 1 OFFJog 2 OFFJog 2 OFFJog 2 OFFJog 2 OFF

Data not validData not validData not validData not validNo functionNo functionNo functionNo function

1111

16161616888844442222

2562562562561281281281286464646432323232

32768327683276832768ValueValueValueValue

163841638416384163848192819281928192409640964096409620482048204820481024102410241024512512512512

No functionNo functionNo functionNo function

Control Word Bit Descriptionsfor Coast Stop

NetworkDriveControlInput(continued)

Reference 2Network variable nviRefRads is a signed value.A negative value is interpreted as zero. Itrepresents the desired output frequency of thedrive in radians/second in open loop. It is rarelyused in closed loop.

Reference 3Network variable nviRefHz is an unsignedvalue. It represents the output frequency ofthe drive in Hz in open loop. It is rarely used inclosed loop mode.

Control WordThe input network variable nviControlWord isa 16-bit word that provides additionaloperational control of the drive, as listed inthe table below. The settings shown representthe Coast Stop command

NOTEDrive always stops and ignoresserial bus commands to run whenOFF/STOP or STOP/RESETfunction is activated from drivekeypad.

The equivalent control word bit settings tostart and stop the drive (nviStartStop) and toreset after a fault (nviResetFault) are describedin the table below.

Start/Stop and Fault Reset Control WordBit Descriptions

VLT 5000 parameters are shown in parenthesis, where applicable.

The VLT 5000 allows the choice between twocontrol word profiles, selected in parameter 512,Telegram Profile. The table below defines theProfidrive control word used for transmittingcommands to the drive using the Profibusprotocol.

Profidrive Control Word BitDescriptions

Page 27: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

26 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Ramp stopThe drive output frequency ramps down to0 Hz according to time set in parameter207, Ramp Down Time.

• Factory setting is 60 sec for fanapplications and 10 sec for mostpump applications.

• Drive display shows STAND BY.• Drive can run in HAND mode or

AUTO through a digital inputcommand.

• Parameter 505, Start, determinesinteraction with input 18.

Precedence of the stop commands is:1. Coast stop2. Quick stop3. DC brake stop4. Ramp stop

Coast stopThe drive output stops immediately andthe motor coasts to a stop.

• Drive display show UN.READY (unitready) when coast stop is active.

• Drive cannot run in any mode.• Parameter 503 (502), Coasting stop,

determines interaction withinput 27.

Quick stopThe drive output frequency ramps downto 0 Hz according to time set in parameter207 (212), Ramp Down Time.

• Drive display shows STOP.• Drive cannot run in AUTO mode but

can run in HAND mode.

DC brake stopThe drive brakes the motor to a stop usingDC injection braking.

• Parameters 114 (125) and 115 (126)determine amount and time of DCcurrent applied for braking.

• Drive display shows DC STOP.• Drive cannot run in AUTO mode but

can run in HAND mode.• Parameter 504, DC Brake,

determines interaction with input27.

Page 28: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

27MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

DriveFeedback toNetwork

The VLT LonWorks option provides 16 outputvariables to the network containing importantdrive and motor feedback data. Feedback datais sent when there is a change in value. TheVLT LonWorks option will only transmit boundnetwork variables. Since some data changescontinuously, the transmission rate of thosevariables is limited. Min send time specifiesthe minimum time between transmissions ofvariables.

The Drive Outputs (1, 2, or 3) will have amaximum time between transmission set by theMax send time. This function acts as a transmitheartbeat and allows a controller node todetermine the health of the controller/VLTconnection. The Max send time function isdisabled when the configuration networkvariable nciMaxsendT is not configured or is setto “0.”

Drive statusNvoDrvStatus, nvoStatusWord, nvo-DigitalInput, nvoAlarmWord, nvoWarning1 andnvoWarning2 are all 16 bit Boolean valuesusing the SNVT_state variable type. Individualbits represent specific drive status states. Thetables provided in Drive Status Bit Definitionsdefine each bit.

Drive output 1Network variable nvoOutputPcnt provides ananalog indication of drive operation. In openloop, this is the drive output frequency inpercentage within the reference range. Toavoid negative numbers, or numbers above100%, set parameter 204, Min. Reference to0 Hz, and parameter 205, Max. Referenceequal to parameter 202, Max. Frequency.

Network Variable Outputs from VLT

Function SNVT type Variable Name Units Max Min

Drive status SNVT_state nvoDrvStatus 16 Boolean NA NA

Drive output 1 SNVT_lev_percent nvoOutputPcnt 0.005% 163.835 –163.840

Current SNVT_amp nvoDrvCurnt 0.1 amps 3276.7 0

Energy SNVT_elec_kwh nvoDrvEnrg 1 kWh 65,535 0

Power SNVT_power_kilo nvoDrvPwr 0.1 kW 6553.5 0

Statusword SNVT_state nvoStatusWord 16 Boolean NA NA

Drive output 2 SNVT_angle_vel nvoOutputRads 0.1 rad/sec 3276.7 –3276.8

Drive output 3 SNVT_freq_hz nvoOutputHz 0.1 Hz 6553.5 0

Output voltage SNVT_volt nvoVoltage 0.1 V 3276.7 –3276.8

Digital input SNVT_state nvoDigitlInput 16 Boolean NA NA

Alarm SNVT_state nvoAlarmWord 16 Boolean NA NA

Warning 1 SNVT_state nvoWarning1 16 Boolean NA NA

Warning 2 SNVT_state nvoWarning2 16 Boolean NA NA

DC voltage SNVT_volt nvoDCVolt 0.1 V 3276.7 0

Motor temp SNVT_lev_cont nvoTempMtr 0.5 % 100 0

Inverter temp SNVT_lev_cont nvoTempInvrtr 0.5 % 100 0

In closed loop, this is the drive's feedbacksignal within the reference range. For bestoperation, set Min. Reference to equalparameter 413 (414), Min. Feedback, andMax. Reference to equal parameter 414 (415),Max. Feedback.

Drive output 2 and Drive Output 3Output 2 is useful in open loop to report thedrive's output frequency in rad/sec. Output 3in open loop reports the drive's output in Hz.Note that in closed loop nvoOutputHz willreport the actual Feedback and not the outputfrequency. For best results, set Min. Referenceto 0 Hz and Max. Reference equal to Max.Frequency. These variable are rarely used inclosed loop.

VLT 5000 parameters are shown in parenthesis, where applicable.

Page 29: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

28 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Bit Value 0 1 Bit Value 0 100 32768 33 OFF 33 ON 00 3276801 16384 32 OFF 32 ON 01 1638402 8192 29 OFF 29 ON 02 819203 4096 27 OFF 27 ON 03 409604 2048 19 OFF 19 ON 04 204805 1024 18 OFF 18 ON 05 102406 512 17 OFF 17 ON 06 51207 256 16 OFF 16 ON 07 25608 128 no function 08 12809 64 no function 09 6410 32 no function 10 3211 16 no function 11 1612 8 no function 12 813 4 no function 13 4 Stopped Running14 2 no function 14 2 No Warning Warning15 1 no function 15 1 no Alarm Alarm

Bit Value 0 1 Bit Value 0 100 32768 Alarm Ctrl. Ready 00 32768 normal Unknown Fault01 16384 Alarm Drive Ready 01 16384 normal Trip Lock02 8192 Safety Open Safety Closed 02 8192 normal AMA Fault03 4096 No Alarm Alarm 03 4096 normal HPFB Timeout04 2048 04 2048 normal RS-485 Timeout05 1024 05 1024 normal ASIC Fault06 512 06 512 normal Short circuit07 256 no Warning Warning 07 256 normal SMPS Fault08 128 Not at Ref. at Ref. 08 128 normal Ground Fault09 64 Hand Mode Auto Mode 09 64 normal Overcurrent10 32 Fr. Range Warn Freq. in Range 10 32 normal Current limit11 16 Stopped Running 11 16 normal Mtr. Thermistor12 8 no used 12 8 normal Motor thermal13 4 normal Voltage Warn. 13 4 normal Undervoltage14 2 normal Current lim. 14 2 normal Overvoltage15 1 normal Therm. Warning 15 1 normal In. Phase loss

Bit Value 0 1 Bit Value 0 100 32768 normal Ref. High 00 32768 normal Autoramping01 16384 normal Ctrl. Crd. Fault 01 16384 normal Start Delay02 8192 normal Pwr. Crd. Fault 02 8192 normal Sleep Boost03 4096 normal HPFB Timeout 03 4096 normal Sleep04 2048 normal RS-485 Timeout 04 2048 normal AMA Done05 1024 normal Overcurrent 05 1024 normal AMA Running06 512 normal Current limit 06 512 normal Rev. Start07 256 normal Thermistor O.T. 07 256 no Ramp Ramping08 128 normal Motor O.T. 08 128 Forward Reverse09 64 normal Inverter O.T. 09 64 not at Ref. at Reference10 32 normal U.V. Alarm 10 32 Stopped Running11 16 normal O.V. Alarm 11 16 Remote Ref. Local Ref.12 8 normal U.V. Warning 12 8 normal OFF (HOA)13 4 normal O.V. Warning 13 4 Auto Start/stop Hand14 2 normal Input Phase Loss 14 2 normal Run Request15 1 normal Live Zero 15 1 Run Permission no Run Perm.

no function

not usednot usednot used

no functionno functionno functionno function

no functionno functionno functionno function

no functionno functionno functionno function

VLT 6000 DriveStatus BitDefinitions

nvoWarning1 nvoWarning2

nvoStatusWord nvoAlarmWord

nvoDigitalInput nvoDrvStatus

Page 30: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

29MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Bit Value 0 1 Bit Value 0 100 32768 33 OFF 33 ON 00 3276801 16384 32 OFF 32 ON 01 1638402 8192 29 OFF 29 ON 02 819203 4096 27 OFF 27 ON 03 409604 2048 19 OFF 19 ON 04 204805 1024 18 OFF 18 ON 05 102406 512 17 OFF 17 ON 06 51207 256 16 OFF 16 ON 07 25608 128 no function 08 12809 64 no function 09 6410 32 no function 10 3211 16 no function 11 1612 8 no function 12 8 Remote Local13 4 no function 13 4 Stopped Running14 2 no function 14 2 No Warning Warning15 1 no function 15 1 no Alarm Alarm

Bit Value 0 1 Bit Value 0 100 32768 Alarm Ctrl. Ready 00 32768 normal Brake Test fail01 16384 Alarm Drive Ready 01 16384 normal Trip Lock02 8192 Safety Open Safety Closed 02 8192 normal AMA Fault03 4096 No Alarm Alarm 03 4096 normal AMA OK04 2048 04 2048 normal Power Up Fault05 1024 05 1024 normal ASIC Fault06 512 06 512 normal HPFB Timeout07 256 no Warning Warning 07 256 normal RS-485 Timeout08 128 Not at Ref. at Ref. 08 128 normal Short circuit09 64 Local Bus Control 09 64 normal Power Fault10 32 Fr. Range Warn Freq. in Range 10 32 normal Ground Fault11 16 Stopped Running 11 16 normal Over current12 8 no used Stall, Autostart 12 8 normal Torque limit13 4 normal Voltage Warn. 13 4 normal Motor Thermal14 2 normal Current lim. 14 2 normal Motor Overload15 1 normal Therm. Warning 15 1 normal Inverter Overload

Bit Value 0 1 Bit Value 0 100 32768 normal Brake Test Fault 00 32768 normal Ramping01 16384 normal Ctrl. Crd. Fault 01 16384 normal AMT02 8192 normal Pwr. Crd. Fault 02 8192 normal Start Fwd/Rev03 4096 normal HPFB Timeout 03 4096 normal Slow down04 2048 normal RS-485 Timeout 04 2048 normal Catch up05 1024 normal Overcurrent 05 1024 normal FB High06 512 normal Torque limit 06 512 normal FB Low07 256 normal Thermistor O.T. 07 256 normal Current High08 128 normal Motor O.T. 08 128 normal Current Low09 64 normal Inverter O.T. 09 64 normal Freq. High10 32 normal U.V. Alarm 10 32 normal Freg. Low11 16 normal O.V. Alarm 11 16 normal Brake Test OK12 8 normal U.V. Warning 12 8 normal Braking Max.13 4 normal O.V. Warning 13 4 normal Braking14 2 normal Input Phase Loss 14 2 normal Discharge OK15 1 normal No motor 15 1 normal Out Freq. Range

not usednot usednot used

no functionno functionno functionno function

no functionno functionno functionno function

no functionno functionno functionno function

nvoDigitalInput nvoDrvStatus

nvoStatusWord

nvoWarning1

nvoAlarmWord

nvoWarning2

VLT 5000 DriveStatus BitDefinitions

Page 31: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

30 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Min send timeSets the minimum period betweentransmissions for all output network variables,using the network variable nciMinSendT. Thisfunction is used to keep the transmission ofvariables that change continuously fromdominating the network communication.

Max receive timeThis drive function is replaced by the valueset in parameter 803, Bus Time Out. TheLonWorks option will initiate bus time outactivities when the time set in parameter 803expires without receiving an input networkvariable directed to the drive. This acts like aLonWorks receive heartbeat. The action takenby the drive is determined by the settingselected in parameter 804, Bus time outfunction. See the parameter descriptionsection of this manual. The value ofnciMaxReceiveT has no effect on theoperation of the drive.

NetworkTimerFunctions

Max send timeThis function sets the maximum time betweentransmissions for the network variables DriveOutput 1, 2, and 3 using the configurationnetwork variable nciMaxSendT. It can be usedby the controller to monitor the health of theVLT and controller connection. It acts like aLonWorks send heartbeat.

The Max send time function is disabled whennciMaxSendT is not configured or set to “0.”

Function SNVT Variable Units Max Min Defaulttype Name

Min send SNVT nciMin- time 0 days 0 days 0 daystime _elapsed SendT 0 hours 0 hours 0 hours

_tm 1 min 0 min 0 min5 sec 0 sec 0 sec535 msec 100 msec1 500 msec

30 msec2

Max SNVT nciMax- time 0 days 0 days 0 daysreceive _elapsed ReceiveT 18 hours 0 hours 0 hourstime _tm 12 min 0 min 0 min

15 sec 1 sec 0 sec0 msec 0 msec 0 msec

(Off)

Max SNVT nciMax- time 0 days 0 days 0 dayssend _elapsed SendT 0 hours 0 hours 0 hourstime _tm 1 min 0 min 0 min

5 sec 0 sec 0 sec535 msec 100 msec1 0 msec

30 msec2 (Off)

1 78 kbps transformer coupled twisted pair and 78 Kbps free topology transceiver models.2 1.25 Mbps transformer coupled twisted pair transceiver model.

Network Timer Functions

Page 32: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

31MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

A controller node can monitor or modify anyVLT parameter by supporting the Parameteraccess command and the Parameter accessresponse functions. These functions allow acontroller complete access to the features ofthe VLT and the ability to configure drives withpredefined settings, using the networkvariables nviParamCmd and nvoParamResp.

The following definitions describe how thefields of SNVT_preset are used by the VLTLonWorks option:

LearnThis field contains the function code for theVLT. The values for this field are:

LN_RECALL (0),LN_LEARN_CURRENT (1),LN_LEARN_VALUE (2), andLN_REPORT_VALUE (3).

LN_RECALL (0) andLN_REPORT_VALUE (3)are interpreted as read commands.

LN_LEARN_CURRENT (1) andLN_LEARN_VALUE (2)are interpreted as write commands.

Any other value in this field will result in anerror message in the Parameter accessresponse.

SelectorThis field contains the VLT parameternumber, written in decimal notation, that isto be written or read. Requests forundefined parameters will result in an errormessage in the Parameter access esponse.

VLTParameterAccess

The controlling device should compare theparameter number of the responsemessage to the requested parameternumber to determine that the informationreceived is the requested information andnot a response to another controller or fromanother VLT.

ValueThis array contains the parameterinformation to and from the VLT. All VLTparameters use 16 bit signed or unsignedvalues. The most significant 2 hex bytes ofdata will be stored in value [0] and the leastsignificant 2 hex bytes of data will be storedin value [3]. In the event of an errormessage, the VLT will send 0xff in value [0]and an error code in value [3]. The errorcodes are defined in the section ParameterAccess Error Codes in this manual.

NOTEConsult Conversion Index inthe VLT Instruction Manualparameter table for correctconversion factor for reading andwriting to and from drive.

Day, Hour, Minute, Second, MillisecondThe time fields are not supported by theVLT LonWorks option. The VLT will respondto parameter access requests as soon asthey are received. Any values in the timefields of the Parameter access commandwill be ignored. All time fields will be set to“0” in the Parameter access response.

Function SNVT type Variable Name

Parameter access command SNVT_preset nviParamCmd

Network Variable Output from VLT

Network Variable Input to VLT

Function SNVT type Variable Name

Parameter access response SNVT_preset nvoParamResp

Page 33: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

32 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Parameter Access Error Codes

Exception Code Interpretation

1 Illegal function for the addressed node

2 Illegal data address (i.e., illegal parameter number)

3 Illegal data value

6 Busy

Example 1:

The examples below demonstrate use of theparameter access command and parameteraccess response functions of the controllernode. In the examples, the controller node hasa parameter access command SNVT_presetcalled nvoParamCmd and a parameteraccess response SNVT_preset callednviParamResp. In writing to the drive correctly,the access response simply repeats theentered data. In the event of an error, an errorcode is displayed in value [3]. See ParameterAccess Error Codes above.

ParameterAccessError Codes

In the event of an error message in responseto a Parameter access command (see VLTParameter Access), the VLT sends 0xff in value

bit [0] and an error code in value [3]. Errorcode definitions are presented in the tablebelow.

ParameterAccessCommandandResponseExamples

Parameter 971 must be set toSTORE ACTIVE SETUP forentering data values throughLonWorks parameter accesscommand in order to savechanges in drive. See parameter971 in Parameter Descriptionssection of this manual.

NOTEConsult conversion index in theVLT Instruction Manual parametertable for correct conversionfactor for reading and writing toand from drive.

������

The controller node writes 30 seconds toparameter 206 (205), Ramp time up of theVLT. Conversion index is 0, so the conversionfactor is 1.0 (VLT 5000 conversion factor -2)).

The controller node access command sendsthe following parameter write request to theVLT.

nvoParamCmd.learn=LN_LEARN_CURRENTnvoParamCmd.selector = 206nvoParamCmd.value[0] = 0nvoParamCmd.value[1] = 0nvoParamCmd.value[2] = 0nvoParamCmd.value[3] = 1E hex (30decimal)

The controller node receives the followingparameter access response from the VLT.

nviParamResp.learn =LN_LEARN_CURRENTnviParamResp.selector = 206nviParamResp.value[0] = 0nviParamResp.value[1] = 0nviParamResp.value[2] = 0nviParamResp.value[3] = 1E hexnviParamResp.day = 0nviParamResp.hour = 0nviParamResp.minute = 0nviParamResp.second = 0nviParamResp.millisecond = 0

VLT 5000 parameters are shown in parenthesis, where applicable.

Page 34: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

33MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

A controller node writes [2] (REFERENCE[UNIT]) to parameter 007 (009), Large DisplayReadout, of the VLT.

The controller node sends the followingparameter write request to the VLT.

nvoParamCmd.learn =LN_LEARN_CURRENTnvoParamCmd.selector = 7nvoParamCmd.value[0] = 0nvoParamCmd.value[1] = 0nvoParamCmd.value[2] = 0nvoParamCmd.value[3] = 2

Example 2:

Time 1 - The controller node receives thefollowing parameter access response from theVLT.

nviParamResp.learn =LN_LEARN_CURRENTnviParamResp.selector = 7nviParamResp.value[0] = 0nviParamResp.value[1] = 0nviParamResp.value[2] = 0nviParamResp.value[3] = 2nviParamResp.day = 0nviParamResp.hour = 0nviParamResp.minute = 0nviParamResp.second = 0nviParamResp.millisecond = 0

Example 3:

Example 4:

A controller node writes 18.0 Hz to VLTparameter 201, Output Frequency Low Limit.The conversion index is -1, so the conversionfactor is 0.1.

The controller node sends the followingparameter write request to the VLT.

nvoParamCmd.learn =LN_LEARN_CURRENTnvoParamCmd.selector = 201nvoParamCmd.value[0] = 0nvoParamCmd.value[1] = 0nvoParamCmd.value[2] = 0nvoParamCmd.value[3] = B4 hex (180decimal)

The controller node receives the followingparameter access response from the VLT.

nviParamResp.learn =LN_LEARN_CURRENTnviParamResp.selector = 201nviParamResp.value[0] = 0nviParamResp.value[1] = 0nviParamResp.value[2] = 0nviParamResp.value[3] = B4 hexnviParamResp.day = 0nviParamResp.hour = 0nviParamResp.minute = 0nviParamResp.second = 0nviParamResp.millisecond = 0

A controller node reads the value of parameter407 (411), Switching Frequency, in the VLT.The value stored in parameter 407 is 10 kHz.The conversion index is 2, so the conversionfactor is 100.

The controller node sends the followingparameter read request to the VLT.

nvoParamCmd.learn = LN_RECALLnvoParamCmd.selector = 407nvoParamCmd.value[0] = 0nvoParamCmd.value[1] = 0nvoParamCmd.value[2] = 0nvoParamCmd.value[3] = 0

The controller node receives the followingparameter access response from the VLT.

nviParamResp.learn = LN_RECALLnviParamResp.selector = 407nviParamResp.value[0] = 0nviParamResp.value[1] = 0nviParamResp.value[2] = 0nviParamResp.value[3] = 64 hex (100decimal)nviParamResp.day = 0nviParamResp.hour = 0nviParamResp.minute = 0nviParamResp.second = 0nviParamResp.millisecond = 0

VLT 5000 parameters are shown in parenthesis, where applicable.

Page 35: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

34 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

StandardObjectSupport

The VLT LonWorks option supports twostandard objects and three SNVTs, per theLonMark standard object philosophy. Thestandard objects are the Node Object(containing the Object request, Object status,and Object alarm) and the Controller object,(containing the network variables describedin the preceding sections). The Object requestis a LonMark device used to obtain status andalarm information from a node.

It is not necessary for a controller to supportthe Node Object network variables. TheObject request, Object status and Objectalarm provide status and alarm informationfor controllers that only support this type offunctionality. The status and alarm functionsdescribed in the preceding sections containmore drive specific information than Objectstatus and Object alarm.

1. The VLT sends an Object statuscontaining drive status informationand an Object alarm containing faultinformationin response to thefollowing Object requests:

RQ_NORMAL,RQ_UPDATE_STATUS, andRQ_UPDATE_ALARM.

Network Variables for Node Object Support

Function SNVT type Variable Name Input/Output

Object request SNVT_obj_request nviRequest Input

Object status SNVT_obj_status nvoStatus Output

Object alarm SNVT_alarm nvoAlarm Output

A controller node error is written to VLTparameter 201, Output Frequency Low Limit,with 80.0 Hz when the high limit is 60 Hz. Theconversion index is -1, with conversion factor 0.1.

The controller node sends the followingparameter write request to the VLT.

nvoParamCmd.learn =LN_LEARN_CURRENTnvoParamCmd.selector = 201nvoParamCmd.value[0] = 0nvoParamCmd.value[1] = 0nvoParamCmd.value[2] = 3 hexnvoParamCmd.value[3] = 20 hex (800decimal)

The controller node receives the followingparameter access response from the VLT.

nviParamResp.learn = LN_NULLnviParamResp.selector = 201nviParamResp.value[0] = 0nviParamResp.value[1] = 0nviParamResp.value[2] = 0nviParamResp.value[3] = 3 (illegal datavalue)nviParamResp.day = 0nviParamResp.hour = 0nviParamResp.minute = 0nviParamResp.second = 0nviParamResp.millisecond = 0

The nviRequest.object_id should be setto “1” (controller node). The networkuses nviRequest, nvoStatus andnvoAlarm variables for these functions.

2. The VLT sends an Object statuscontaining a bit map of supportedstatus fields in response to all otherObject requests, including undefinedrequests.

3. The VLT Object status supports thefollowing status fields: invalid_id,invalid_request,open_circuit,out_of_service, electrical_fault,comm_failure, manual_control, andin_alarm. All other fields are alwaysset to “0.”

4. The VLT sends an Object alarmfollowing any set or reset of a drivefault condition.

5. The Object alarm supports theAL_ALM_CONDITION andAL_NO_CONDITION alarm types.

Example 5:

Page 36: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

35MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

2 22 AMA failed3 18 HPFB timeout4 17 Serial communication timeout5 16 Short circuit6 15 Switch mode fault7 14 Ground fault8 13 Overcurrent9 12 Current limit

10 11 Motor thermistor11 10 Motor overtemperature12 9 Inverter overload13 *8 Undervoltage14 **7 Overvoltage15 4 Mains failure

Bit number

Alarm number

Alarm Description

0 23 Brake test failed1 X Trip locked2 22 AMA tuning not OK3 21 AMA tuning OK 4 20 Power up fault5 19 ASIC fault6 18 HPFB timeout7 17 Standard bus timeout8 16 Short circuit9 15 Switch mode fault

10 14 Ground fault11 13 Overcurrent12 12 Torque limit13 11 Motor thermistor14 10 Motor overload15 9 Inverter overload

Bit number

Alarm number

Alarm Description

★ Factory setting

VLT 6000AlarmDescriptions

Alarm numbers and descriptions thatcorrespond to nvoAlarmWord bit numbers are

shown in the table below. See the VLT 6000Instruction Manual for more details.

***** also bit 10 of nvoWarning 1

********** also bit 11 of nvoWarning 1

VLT 5000 parameters are shown in parenthesis, where applicable.

VLT 5000AlarmDescriptions

Alarm numbers and descriptions thatcorrespond to nvoAlarmWord bitnumbers are shown in the table below.

See the VLT 5000 Instruction Manualfor more details.

Page 37: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

36 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

ParameterDescriptions

803803803803803Bus time outBus time outBus time outBus time outBus time out Selection:

1 - 99 sec ★ 1 secFunction:Sets the duration for the bus time out function.If the set time passes without the drivereceiving a LonWorks message addressed to

★ Factory setting

it, the drive will take the action specified inparameter 804, Bus Time Out Function.

NOTEAfter time out counter is reset itmust be triggered by valid controlword before new time out can beactivated.

VLT 5000 parameters are shown in parenthesis, where applicable.

ParameterList

In addition to the parameters listed above, thedrive's control terminals issue digital inputsthat control functions similar to those providedby nviStartStop, nviResetFault, andnviControlWord. Parameters (502) 503through 508 determine how the drive

responds to commands for (quick stop,VLT 5000 only), coasting stop, DC brake,start, reverse, setup select and presetreference select. See Network Drive ControlInput in this manual and the VLT InstructionManual for more information.

Conversion Data

PNU Parameter Description Default Value Range Index Type

803 Bus time out 1 sec 1 - 99 sec. 0 3

804 Bus time out function no function 0 3

805 Bit 10 function Bit 10 = > CTW ACT 0 6

927 Parameter edit Enable 0 6

928 Process control Enable 0 6

970 Edit setup Active Setup 0 5

971 Store data values no action 0 5

Page 38: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

37MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

804804804804804TTTTTime out functionime out functionime out functionime out functionime out function

Selection:★ Off

(NO FUNCTION) [0]Freeze output frequency

(FREEZE OUTPUT FREQ.) [1]Stop with auto restart

(STOP) [2]Output frequency = JOG freq.

(JOGGING) [3]Output frequency = Max. freq.

(MAX SPEED) [4]Stop with trip

(STOP AND TRIP) [5]Control without DeviceNet

(NO COM OPT CONTROL) [6]Select set-up 4

(SELECT SET UP 4) [7]

Function:The time out timer is triggered at the firstreception of a valid control word, i.e.,bit 10 = ok.

The time out function can be activated in twodifferent ways:

1. The drive does not receive aLonWorks command addressed to itwithin the specified time.

2. Parameter 805 is set to “bit 10 = 0time out” and a control word with “bit10 = 0” is sent to the drive.

The VLT remains in the time out state untilone of the following four conditions is true:

1. A valid control word (Bit 10 = ok) isreceived and the drive is resetthrough the bus, the digital inputterminals or the local control panel.(Reset is only necessary when thetime out function Stop w/trip isselected.) Control via LonWorks isresumed using the received controlword.

2. Local control via the local controlpanel is enabled.

3. Parameter 928, Access to processcontrol, is set to Disabled.Normal control via the digital inputterminals and the RS-485 interface isnow enabled.

★ Factory setting

4. Parameter 804, Bus time out function,is set to Off.Control via LonWorks is resumed andthe most recent control word is used.

Description of Selections:

• Freeze output frequency. Maintainpresent output frequency untilcommunication is resumed.

• Stop with auto restart. Stop andautomatically restart whencommunication is resumed.

• Output frequency = JOG freq. Drivewill produce JOG frequency set inparameter 209 (213), Jog frequency,until communication is resumed.

• Output frequency = Max. freq. Drivewill produce maximum outputfrequency (set in parameter 202,Output frequency) untilcommunication is resumed.

• Stop with trip. Drive stops andrequires a reset command before itwill restart.

• Control without LonWorks. Control viaLonWorks is disabled. Control ispossible via digital input terminalsand/or standard RS-485 interfaceuntil LonWorks communication isresumed.

• Select setup 4. Setup 4 is selected inparameter 002 (004), Active setup,and settings of setup 4 are used.Parameter 002 (004) is not reset tothe original value whencommunication is resumed.

VLT 5000 parameters are shown in parenthesis, where applicable.

Page 39: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

38 MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

Data Value:Preprogrammed (FACTORY SETUP) [0]Setup 1 (SETUP 1) [1]Setup 2 (SETUP 2) [2]Setup 3 (SETUP 3) [3]Setup 4 (SETUP 4) [4]

★ Active Setup (ACTIVE SETUP) [5]

★ Factory Setting

805805805805805ContrContrContrContrControl Wol Wol Wol Wol WororororordddddBit 10 FunctionBit 10 FunctionBit 10 FunctionBit 10 FunctionBit 10 Function

Selection:No function

(NO FUNCTION) [0]★ Bit 10 = 1: control word active

(BIT 10 = 1 >CTW ACTIVE) [1]Bit 10 = 0: control word active

(BIT 10 = 0 >CTW ACTIVE) [2]Bit 10 = 0: bus time out

(BIT 10 = 0 >TIME OUT) [3]

Function:According to the drive's standardcommunications profile, control word andspeed reference will be ignored if bit 10 of thecontrol word is 0. Parameter 805 lets the userchange the function of bit 10. This is sometimes necessary, as some masters set all bitsto 0 in various fault situations. In these cases,it makes sense to change the function of bit10 so that the VLT is commanded to stop(coast) when all bits are 0.

Description of Selections:• No function. Bit 10 is ignored, i.e.,

control word and speed reference arealways valid.

• Bit 10 = 1 >CTW active. The controlword and speed reference areignored if bit 10 = 0.

• Bit 10 = 0 >CTW active. The controlword and speed reference areignored if bit 10 = 1. If all bits of thecontrol word are 0, the VLT reactionwill be coasting.

• Bit 10 = 0 >time out. The time outfunction selected in parameter 804 isactivated when bit 10 is 0.

Data Value:Disable (DISABLE) [0]

★ Enable (ENABLE) [1]

This parameter determines LonWorks controlof the drive. When Enable is selected, driveparameters 503 through 508 determine theinteraction between various LonWorks anddigital drive input commands. See theVLT Instruction Manual for details.

When this parameter is set to Store activesetup, LonWorks downloaded parameters arewritten to EEPROM and stored. Store editsetup stores the setup selected in parameter970. Store all setups stores all setups inparameter 970. When finished (appx. 15 sec.),it automatically returns to No action. Anyparameters values written via the serial buswith No action selected are lost when poweris removed from the drive. The function is onlyactivated with the VLT in stop mode.

Data Value:Disable (DISABLE) [0]

★ Enable (ENABLE) [1]

This parameter determines if LonWorks canbe used to access and edit drive parameters.

927927927927927Parameter editParameter editParameter editParameter editParameter edit

928928928928928PrPrPrPrProcess controcess controcess controcess controcess contrololololol

970970970970970Edit setup selectEdit setup selectEdit setup selectEdit setup selectEdit setup select

971971971971971StorStorStorStorStore data valuee data valuee data valuee data valuee data value

Data Value:★ No action (NO ACTION) [0]

Store all setups(STORE ALL SETUPS [1]

Store edit setup(STORE EDIT SETUP) [2]

Store active setup(STORE ACTIVE SETUP) [3]

With Bit 10 = 0 >CTW activeselected, nviStar tStop andnviResetFault commands will notfunction.

������

This parameter selects the setup being edited,through either the drive control panel orLonWorks. The drive may operate in onesetup while editing another. Active setupselects the parameter being edited as thesetup controling drive operation.

Page 40: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

39MG.60.E4.22 - VLT is a registered Danfoss trademark

VLT® 5000 / VLT® 6000

DecommissioningVLT Drive fromLonWorksNetwork

������Specific procedures must befollowed when removing VLTdrive from LonWorks network.Failure to adhere to stepsdescribed can result in driveentering inoperable state.

The VLT drive cabling connector must bedisconnected prior to removing the drive fromthe LonWorks network configuration toprevent corruption of the drive EEPROMprocessor. Decommission the drive from thenetwork in accordance with the followingprocedure.

1. Use LonWorks software configurationtool to remove bindings from drivefunction blocks.

2. Use LonWorks software configurationtool to remove drive function blocksfrom all drive variables.

3. Disconnect LonWorks cabling fromdrive input terminal.

4. Use LonWorks software configurationtool to remove drive device fromnetwork.

Improper decommissioning of the drive mayresult in locking up the drive with the displayreading as follows.

Try to reinitialize drive by removing power untildisplay does blank. Reapply power. If drivefunctions are not restored, order the DanfossEEBLANK Kit (P/N 175L4167) to restore theEEPROM functionality.

FailedOPTION ERROR:

1: NO OPT. RESPONSE

Page 41: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure
Page 42: Mbps Option Card Lonworks Instruction manual · 2013-12-06 · 5000 / 6000 VLT ® 5000 / 6000 ... the network has an object definition, create The LonWorks communications structure

Drives Solutions

www.danfoss.com/drives

Instruction manual

Lonworks® 78 kbps and 1.25Mbps Option Card

VLT® 5000 / 6000VLT® 5000 / 6000

Instructions manual

175R0202 MG60E422 REV. 2003-03-06

XREF__BCNOT LOADED ON RIP

*MG60E422*