Maximize Your Data Center for Virtualization Initiatives

24
by Schneider Electric – Philip Fischer– March 2011 Virtualization: Optimized Power and Cooling to Maximize Benefits

description

Presentation focuses on the impact virtualization initiatives have on the data center and more importantly the critical physical infrastructure supporting the data center. Virtualization is an IT strategy that can easily and quickly impact, with potential negative consequences, the reliability and availability of the data center. Understand the effects and some considerations in the implementation of virtualization.

Transcript of Maximize Your Data Center for Virtualization Initiatives

Page 1: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Philip Fischer– March 2011

Virtualization: Optimized Power and Cooling to Maximize Benefits

Page 2: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Increasing Pressure

Energy and servicecost control

Increasing availability expectations

Regulatory requirements Server

consolidation

Dynamic power variation

Uncertainlong-term plans for capacity or density

… on data center planning and operation

We created – and continue to improve a new way to plan, design, install, manage, and maintain data centers

In response …

Cloud computing

Energy efficiency Virtualization

Page 3: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

● Increased CPU utilization and efficiency● Typical server utilization rate: ~10-15% (usually higher in storage)

● Virtualized utilization rate: Up to 80%

● Server consolidation ● Decreased need to purchase additional servers

● Increased rack space● Reduced data center space requirements

● Improved continuity and disaster recovery● Virtualized servers can be mirrored in case of failure

● Reduced labor costs ● Easier hardware provisioning and maintenance

Virtualization Benefits

Page 4: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

● Virtualization always increases efficiency

● I don’t need to worry about power and cooling when virtualizing

● High density and high efficiency cannot coexist

● Virtualization requires high density data centers

Virtualization Myths

Page 5: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Power Density

Dynamic Power /Cooling

Rapid Scalability

Availability Architecture Changes

Virtualization Impacts Operations

Impacts and Challenges of Virtualization

Despite theses challenges, =S= firmly believes virtualization is the right solution.

Page 6: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Server

Virtual Applications Capabilities●Power off/on as needed●Move to larger compute resources ●Consolidate to select servers

●Save Energy●Disaster Recovery

Challenges●Dynamic and migrating (high-density) loads●Underloading from consolidation●Need to ensure capacities down to the rack level

●Power●Cooling●Physical space

Rack 1

Power

Cooling

Security

Environment

Rack 2

Power

Cooling

Security

Environment

Rack 3

Power

Cooling

Security

Environment

Server

Server

Server

Server

Server

Server

Server

Vapp 1

V App 2

V App 3

V App 5

V App 4

Impacts and Challenges of Virtualization

Page 7: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Virtualization: Good for Cooking Dinner?

Higher Densities per rack create Power and Cooling Problems

Page 8: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Virtualization: Enough Power for a Neighborhood

~ 30kW Power draw ~ 30kW Power draw

Page 9: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Philip Fischer– March 2011

Challenges to Maximizing Virtualization

Page 10: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Constant loads Stable cooling Migrating high-density loads Unpredictable cooling

BEFORE virtualization AFTER virtualization

Challenge 1:Power Density

•Virtualization instantly drives up power densities at a rack level

•Cooling challenge•Per tile airflow of 300-600 cfm hard to maintain

•Raised flooring and perimeter cooling not the right choice

•Power distribution Challenge•Need new breakers

•New voltage supply levels

•Weight-bearing capacities should be reviewed

Page 11: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Challenge 2:Dynamic Power/Cooling Is Mandatory

●Use power-capping with integration of DCIM and VM

●Need cooling system which can dynamically regulate cooling capacity

●DCIM works with VM Manager allowing for informed decision making

Constant loads Stable cooling Migrating high-density loads Unpredictable cooling

BEFORE virtualization AFTER virtualization

Page 12: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Impact of Virtualization on Oversizing

LoadLoad

CapacityPower/coolingCapacityPower/cooling

LoadVirtualized Load

LoadOriginalLoad

Original

LoadVirtualizedLoad

Virtualized

LoadLoadLoad

VirtualizedLoad

Virtualized

LoadVirtualizedLoad

Virtualized

Page 13: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Challenge 3:Rapid Scalability Becomes Critical

●Speed of provisioning new "servers" is super fast

●Need agile infrastructure to cope●Capacity management tools for real-

time monitoring and analysis of information about the three essential capacities of the data center:

●Power●Cooling●Physical space

●Stranded capacity = inefficiency

Virtual server N

Physical Host

Virtual server 1

Virtual server 2

Virtual server N

Cooling

Power

Virtual server 3

Virtual server N

Page 14: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Challenge 4:Availability Architecture Changes

●Data center physical infrastructure should be designed based on the fault-tolerant nature of the virtualization IT model

●Redundancy is less important to physical infrastructure if IT is highly fault tolerant

●Consider N+1 architecture

Page 15: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Challenge 5:Virtualization Impacts Operations

●Initially, virtualization leads to consolidation….but be prepared for rapid growth

●Rapidly changing demand and capacity requires tools to keep operations up and running

●Physical servers are now a capacity element just like power and cooling

●Supply while traditionally being just power, cooling and physical space now includes servers and the network bandwidth

Page 16: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Virtualization Challenges to Power and Cooling Infrastructure

Challenge SolutionPower Density Increases Containment and High Voltage

Distribution

Dynamic Migrating Loads Planning and Implementation Software

Underloading of Power and Cooling Systems

Scalable Power and Cooling

Availability Architecture Design data center pods to Need (2N, N+1, etc.)

Virtualization Impacts Operations

Simulation and Capacity Management Tools

Page 17: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

$193,123Before Virtualization

Source: TradeOff Tool - TT9 Rev 0 “Virtualization Energy Cost Calculator”

Optimized power & cooling• 60 kW capacity• Data center load 88%

• PUE = 1.6

Annual electric bill

Simple Case StudyImplementing Virtualization in a data Center

54%savings

27%

36%

●Average 7 kW / rack

●DX air conditioning

●No redundancy

●$0.12 / kW hr

●Right-sized power & cooling

●Close-coupled cooling

●Use blanking panels

●High-efficiency UPS (96%)

$89,251After NCPI

Improvements

$140,305After Virtualization

Before virtualization●120 kW data center capacity ●90 kW IT load (75% loaded)●59 kW total server load

(66%)

●PUE = 2.0

After virtualization• 53 kW IT load (42% loaded)• 22 kW total server load• 75% servers virtualizable• Server consolidation ratio 20:1

• PUE= 2.5

Page 18: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Why Integrate Virtualization and Datacenter Management?●Automate

● Virtual machine migration when an issue arises in the physical infrastructure

●Solve the issue● Of keeping virtual machines running during physical infrastructure

incidents

●Map dependencies● Of physical servers to physical infrastructure

●Ensure your enterprise applications● perform with the highest availability and performance

●Build up business continuity● through improved disaster recovery solutions and deliver high availability

throughout the datacenter

Page 19: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

DCIM Definition

●A data center infrastructure management (DCIM) system collects and manages information about a datacenter’s assets, resource use and operational status.

●This information is then distributed, integrated, analyzed and applied in ways that help managers meet business and service-oriented goals and optimize their datacenter’s performance.

●In practice, DCIM systems may vary widely in focus, and complete solutions are likely to consist of a framework or suite of products, from one or many suppliers, that are designed to interoperate or complement each other.

●The close interworking of IT and mechanical/electrical systems will increasingly lead to the deployment of solutions that span data-center facility infrastructure, physical IT assets, and virtual IT assets.

Page 20: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Virtualization Management

Virtual Machine and Server Management

Provisioning

Migration

Resource ManagementSystem Monitoring

System Security and Access Control

Programmatic Interfaces

DataCenter Management

POWER

UPS

Rack Distribution

Centralized

COOLING

InRow

Overhead

Raised Floor

SECURITY

Camera

Access Control

Contact Points

Environmental

Temperature

Humidity

Water/Smoke

Virtualization Management

Data Center Management

Integrated Management

APC InfraStruxure Operations

Microsoft System Center

Virtual Machine

Manager 2008

Page 21: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

●Identify issues in system design or operation that compromise efficiency and recommend solutions:

●Row-based cooling●Scalable UPS●Predictive management tools

●Estimate potential efficiency gains to enable return-on-investment (ROI) calculations for capital expenditures

●Data Center Electrical Efficiency Assessment service

What can you do?

●Assess the impact of consolidation & virtualization strategy

● Effect of under-loaded CRACs, chillers, generators● Potential hotspots

Page 22: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Carbon Footprint

Quickly determine costs, efficiency, carbon footprint by …

●Size●Density●Redundancy ●Architecture

Power/Cooling EfficiencyCapital Cost

Early Planning Tools

TOOLS™

Critical planning guidance before you commit

Make informed decisions…BEFORE you design your data center

FAST and EASY

Page 23: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011 Go Go to latest online

version of this toolClick to resume presentation

DoneCore | Virtualization-Consolidation | Rev 0

Page 24: Maximize Your Data Center for Virtualization Initiatives

APC by Schneider Electric – Pjilip Fischer – March 2011

Claim the efficiency

●To deliver maximum energy savings of virtualization●To maximize reliability and predictability of virtualized environment