Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter...

126
Nr. 257 454 - GB Edition: 02.14 GB Manual MPA 41xx

Transcript of Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter...

Page 1: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

1 … 1261 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Nr. 257 454 - GB

Edition: 02.14 GB

ManualMPA 41xx

Page 2: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

3 … 1262 … 126

Table of contents

Data sheet .............................................................................................................................................................3-6Approval Overview ...................................................................................................................................................7System description/variants/accessories/approvals ...........................................................................................8General technical data .............................................................................................................................................9Connection diagram...............................................................................................................................................10Technical data of outputs/inputs .....................................................................................................................11-12Flame monitoring/flame detector connection ............................................................................................... 13-14Installation MPA 411x .............................................................................................................................................15Dimensions MPA 411x ...........................................................................................................................................16Installation MPA412x .............................................................................................................................................17Dimensions MPA 412x ...........................................................................................................................................17Description of the functionsUnlocking functionExtended unlockingAccess level ............................................................................................................................................................18Description of the functionsGas valvesFlame detectorAir pressure switchGas pressure switchLimit switchParameter modeAutomatic/Parameter mode switch ......................................................................................................................19Flow chart ......................................................................................................................................................... 20-21State description .............................................................................................................................................. 22-24Parameters/Parameter change .............................................................................................................................25Parameters/Parameter description ................................................................................................................26-32Parameters/Factory settings ........................................................................................................................... 33-34Status information ................................................................................................................................................. 35MPA 4111/Version without display .................................................................................................................36-37MPA 41x2/Version with display ............................................................................................................................ 38MPA 41x2/Overview of the display modes ...........................................................................................................39MPA 41x2/Display .................................................................................................................................................. 40MPA 41x2/Operation display .................................................................................................................................41MPA 41x2/Additional display information ............................................................................................................42MPA 41x2/Display of parameterisation and service box ................................................................................... 43MPA 41x2/Information display ............................................................................................................................. 44MPA 41x2/Error display ........................................................................................................................................ 45MPA 41x2/Display of the error memory .............................................................................................................. 46MPA 41x2/Parameter display ........................................................................................................................... 47-54MPA 41x2/Reset display ..................................................................................................................................55-56Error overview for minimum indication................................................................................................................57MPA 41xx Errors without error ID ........................................................................................................................ 58MPA 41xx Error from the basic system ..........................................................................................................59-60MPA 41xx Error from the extended functions ................................................................................................ 61-63Annex .................................................................................................................................................................... 64Profibus Extension module MPA 41xx - EM 2/2 ............................................................................................... 65Profibus, Modbus, Shutter Extension module MPA 41xx - EM 2/4 ............................................................ 66-78Multifunctional modul MPA 41xx-EM 2/6 ..................................................................................................... 79-104Flame detector ............................................................................................................................................ 105-106 UV 41 ............................................................................................................................................................107-108UV 42 ............................................................................................................................................................109-110UV 4x EM 1/1 Shutter module ...................................................................................................................... 111-112FLW 20 UV ....................................................................................................................................................113-115FLW 10 IR .....................................................................................................................................................116-118FLW 41 I .........................................................................................................................................................119-120Ignition transformers DEZ ..........................................................................................................................121-123VisionBox ............................................................................................................................................................124

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Page 3: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

3 … 1262 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

µP Automatic Burner Control MPA 41xx

Automatic burner control for one-stage and modulating gas burners

DescriptionMicroprocessor-controlled automatic gas burner control for intermittent and continuous operation of one-stage at-mospheric burners or one-stage or modulating fanned burners.The program sequence and times can be customised by setting software pa-rameters.

Versions• MPA4111withoutdisplay• MPA4112withintegrateddisplay• MPA4122withmetalhousingand integrated display

ApplicationFor one-stage or modulating gas burn-ers with or without ignition gas. In particular for industrial thermoprocess-ing equipment to EN 746-2.

ApprovalsECtype-examinationcertificateaccord-ingtotheECGasAppliancesDirective:MPA41xx CE-0085BU0487

EC type-examination certificate ac-cordingtotheECPressureEquipmentDirective:MPA41xx CE0036

FMApprovedtoFM761ULRecognizedComponent perUL372,UL1998andCSAC22.2.GOST/Rostechnadzor

Suitable for applications up to SIL3.Meets the requirement according to IEC 61508(2ndEd.2011)CertifiedbyTÜVSüd

• Automatic gas burner control for one-stage burners with pilot burner or direct ignition

• Continuous operation

• Configurable program sequence

• Version with or without display

• Two independent flame detectors:Ionisation inputGate input

• Additional functions byextension modules

• Profibus

• AccessoriesFlame detectorIgnition transformersParameterisation and service box

Page 4: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

5 … 1264 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

MPA41xxautomaticgasburnersaresuitable for all types of one-stage or modulating gas burners with and with-out ignition gas.

Theflameismonitoredeitherbymeansofanionisationinput,gateinputorbothinputsforburnerswithtwoflamedetec-tor positions.

• For atmospheric burners and fan burners

• Suitableforcontinuousoperation• MPA4112/4122configurationwithoutlaptop/PCviadisplay

• Ionisationandgateinputsasflamedetectors

• ExtensionmoduleforProfibuscom-munication

Example for connection

Atmospheric burner with ignition gas output

V1 V2

Fan burner, direct ignition:V1 V2

Atmosphericburnerwith ignitiongasoutput.Aftertheheatrequestandanadjust-abledelay,theignitionisswitchedonandV1andVzareopened.After the flame has been detected, themaingasflowV2isopened.

Fanburner,directignitionofthemaingasflame.After the heat request, the fan isswitched on, and the air pressure ischeckedbythepressureswitch.Afterthe pre-aeration time has lapsed, the ignition is switched on, and the two valves V1 and V2 are opened together.

Wiring scheme

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

q

P

M

N G

qPGPE

NL1

6.3 A T(10 A F)

Ionisation

SupplyFlam

e detector

Safety chain

Operation

Fault

Ignition transform

er Flame detector 2 N

CFlam

e detector 2 NO

Air pressure switch

Heat request

Reset

Not used

V1

V2

Thewireswhichareusedfortheconnectionmustbeapprovedforambienttemperaturesofminimun75°C(167°F).

Page 5: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

5 … 1264 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error displayDisplay of the error memory

• Automaticactivationoferror messages

• Additionalinformationaboutfaults•Query of the last ten faults

Display modesOperation display

• Displayofthecurrentoperating state

• Displayoftheprogramstate• Displayofbusaddress

Info display

• Displayofflamequality• Displayof resettablecounters forstart-up,operatinghoursandop-erating cycles

Parameter display

• Password-protected functionallevels for serviceandOEMpa-rameter settings

• Settingofimportantparameterssuchas: Pre-purge timeSafety time for startup phasePost-purge timeBehaviour after flame lift-offOperating modes of V1 and V2Continuous or intermittent operation

Accessories

Flame detectorFLW 10 IRIRflamedetector for connection toionisationinput.Suitableforintermit-tent operation.

FLW 20 UVUVflamedetectorforconnectiontoionisationinput.Suitableforintermit-tent operation.

UV 41 (HE)/UV 42 UVflamedetectorforhighmechani-calload;metallicversion.Suitableforintermittent operation.

With shutter module suitable for con-tinuous operation

FLW 41 IFlame safeguard module for ionisation flamemonitoring.TheFLW41Iiscon-nected to the second flame guardinputoftheMPA41xx.When equipped with an extension module,forexampleEM2/4,suitablefor continuous operation.

The program sequence and times can bemodified on themounted display(MPA4112/MPA4122)tomatcheachapplication.AlaptoporPCisnotrequiredforthemodification.The automatic burners are protected by passwords against unauthorised access.

All settings for the MPA 41xx auto-matic gas burners can also be made bymeansofalaptop/PCviaMPAVisionBox.

Communication

MPA 41 extension module EM2/4AdditionalcircuitboardandconnectorsetforProfibusDPandModbuscom-munication.

MPA 41 extension module EM2/6 AdditionalcircuitboardforProfibusDPand Modbus communication.PWMoutput foropen loopcontrolofDC fans,voltage-/currentoutputalsoprogram state related relay outputs.

Parameter setting and serviceMPA 41 parameterisation and service boxUniversalsupportforcheckingdevicesin the field; for producing small andmedium series.

MPA Vision BoxInadditiontoMPA41parameterisationandserviceboxforsettingparametersviaaPC/laptop.

Page 6: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

7 … 1266 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Subjecttotechnicalmodificationintheinterestoftechnicalprogress.

µP Automatic Burner ControlMPA 41xx

Automatic burner control for one-stage or modulating gas burners

Technical DataRatedvoltage 115VAC-15%...+10%(dependingonthemodel) 230VAC-15%...+10%Frequency 50Hz...60HzPowerconsumption max.10VAFuse max.6.3Aslow-blow or10Afast-blowReadysignal max.1AFaultsignal max.1AGasvalves max.2AFan max.1AIgnition max.1AFlamedetectorsupply 230VAC/10mAFlame detector lonisationlonisationcurrent/operation 10-20µAShutdownsensitivity 1,2µAShort-circuitcurrentlimit approx.280µAUnlockingduetofault PushbuttonsandremoteunlockingTypeofprotection MPA4111/IP42 MPA4112/IP54 MPA4122/IP65Ambienttemperature -40°C-+70°C -20°C-+60°C(ULapproval)Ordering dataMPA4111/230VAC OrderNo.259058MPA4111/115VAC OrderNo.259062MPA4112/230VAC OrderNo.259066MPA4112/115VAC OrderNo.259070MPA4122/230VAC OrderNo.260347MPA4122/115VAC OrderNo.260355

Extension module EM2/4MPA411x OrderNo.257960EM2/4MPA412x OrderNo.257961ProfibusDP,Modbus,ShutterEM2/6MPA411x OrderNo.260751EM2/6MPA412x OrderNo.260570ProfibusDP,Modbus,Shutter,PWM,analogIn/Out

Flame detectorFLW10IR OrderNo.255216FLW20UV OrderNo.250733FLW41I OrderNo.258396UV41 OrderNo.256692UV41HE OrderNo.260575UV42 OrderNo.258385UV4x-EM1/1(Shutter) Artikel-Nr.259361

Company addressKarl Dungs GmbH & Co. KGSiemensstraße 6-10D-73660 Urbach, GermanyPhone +49 (0)7181-804-0Fax +49 (0)7181-804-166

Postal addressKarl Dungs GmbH & Co. KGPostfach 12 29D-73602 Schorndorf, Germanye-mail: [email protected]: www.dungs.com

77

148.5

152.5

152.5

77

151.5

240

80

160

Dimensions [mm]MPA 4111

MPA 4112

MPA 4122

Page 7: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

7 … 1266 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

MPA41xx from V1.1

UV4x UV4x-EM1/1 (Shutter)

Components SIL SFF PFH

X Ionisation input

3 99,48% 1,80E-09

XInputFLW2NO,FLW2NC,LDWandremote unlo-cking

3 99,38% 1,80E-09

X X UV41+ionisa-tion input

2 96,91% 1,50E-07

X XUV42+inputFLW2NO

2 96,87% 1,51E-07

X X XUV4x-EM1/1(shutter)+UV41+ionisa-tion input

3 99,35% 3,15E-08

X X XUV4x-EM1/1(Shutter)+UV42+inputFLW2NO

3 99,34% 3,15E-08

Safety Integrity Level (SIL)

Approval overview Order No.

CE FM ULrecog-nized

UL listed

CSA C22.2

Gost AGA

MPA4111/AC230V 259058 x x x x xMPA4111/AC115V 259062 x x x x x xMPA4112/AC230V 259066 x x x x xMPA4112/AC115V 259070 x x x x x xMPA4122/AC230V 260347 x x x x xMPA4122/AC115V 260355 x x -> x x x xExtension moduleEM2/2MPA41xx 256556 x x x x xEM2/3MPA41xx 257387 x xEM2/4MPA411x 257960 x x x x x (x)*EM2/4MPA412x 257961 x x (x)*EM2/5MPA412x 260743 x x x x x (x)*EM2/6MPA411x 260751 x x x x x (x)*EM2/6MPA412x 260570 x x x x x (x)*Flame detectorFLW10IR 255216 xFLW20UV 250733 xFLW41I 258396 x xUV41 256692 x x x x x xUV41HE 260575 x x x x x (x)*UV42 258385 x x x x x xUV4x-EM1/1(Shutter) 259361 x x x x x xIgnition TransformerDEZ1xx alle x (x)* xDEZ2xx alle x (x)* x

Approval overview

*onrequest

Page 8: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

9 … 1268 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

1 MPA 41xx System description

The automatic gas burner control systemsMPA41xxaresuitableforintermittent or continuous operation of gas burners with or without fan.The system parameters may be set ontheintegrateddisplay(MPA4112/MPA4122)and/orusingtheDUNGSVisionBox.Theflameiseithermonitoredusinganionisationelectrode,aDUNGSFLWXXflamedetectororDUNGSUV41flamedetectorconnectedtotheionisationelectrodeinputoroverasecondflamedetectorinputforaflamedetectorwithpotential-freetwo-way contact or by means of the DUNGSUV42flamedetector.Bothflamedetectorinputsmaybeusedindividuallyorcombined.

TheMPA41xxparameterisationandserviceboxisavailablefortheproduction of small series and for checkingthesystemwhenserviceisrequired.

Foroperationinburnernetworks,aProfibus/ModbuscommunicationovertheextensionmoduleEM-2/4orEM2/6ispossible.

Accessories

Ignitiontransformers:-DEZxxx- Connection line- Ignition line

Flamedetector:-IR:FLW10-UV:FLW20,UV41,UV42-Ionisation:FLW41I

Designation Article no. Voltage DisplayMPA4111 259058 230VAC Minimum indicationMPA4111 259062 115VAC Minimum indicationMPA4112 259066 230VAC 3-digit7-segment

displayMPA4112 259070 115VAC 3-digit7-segment

displayMPA4122 260290 230VAC 3-digit7-segment

displayMPA4122 260355 115VAC 3-digit7-segment

display

System variants

Extension modules EM-EM2/4:Shutter,ProfibusDP,Modbus

-EM2/6:Shutter,ProfibusDP,Modus,PWManalogueIN/OUT.

Page 9: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

9 … 1268 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4General MPA41XXProtectiontypeoftheplastichousing

MPA4111MPA4112

IP42IP54

Protectiontypeof metal housingMPA4122 IP65(Attention:usesuitablecablescrewconnectionsonly)AmbienttemperatureMPA41xx

-20°C...+60°C(ULApproval)-40°C...+70°C

Storageandtransport -40°C...+80°CHumidity DIN60730-1,nodewingadmissibleUsefullifeSwitchingoutputs

Minimum250,000switchingoperations

Mounting position as desiredDimensionsofMPA411xin mm

MPA4111(LxHxT):ca.152,5x148,5x77mmMPA4112(LxHxT):ca.152,5x151,5x77mm

WeightMPA411x 0,82kgDimensionsofMPA412xin mm

MPA4122(LxHxT):ca.160x240x80mm(excludingcablescrewconnection)

WeightMPA412x 2,2kg

Technical Data

Electrical dataRatedvoltage 230VAC -15%...+10%or

115VAC -15%...+10%,dependingontheversionFrequency 50Hz...60HzFuse 6.3Aslow-blowfuseor10Afast-blowfuse,integrated,exchangeableIsolation Nogalvanicisolationbetweenmainsand24VDCor5VDCElectrical connection Correct phase sequence(!)connectionandprotectiveearthconductoraccordingto

the wiring diagramThe contact protectionfortheUVsensormustbeguaranteedbymountingitintheoperating equipment

Powerconsumption(ownconsumption)

Maximum10W

Typically 115V 230VStandby 1.5W...1.8WOperation 3.4W...4.8W

WithextensioncardEM2/4Standby 3.3W...3.5WOperation 5.4W...6.3W

WithextensioncardEM2/6Standby xxW...6.3WOperation xxW...9.0W

Short-circuitcurrentIONagainstN115/230VAC

280µA

Page 10: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

11 … 12610 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Connection diagramMPA411x

Attention:

Riks of fatal electric shocks!You must interrupt the power sup-ply before removing the hood.

After having removed the hood, you might get in contact with the electrical connections in the ter-minal socket.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

q

P

M

N G

qPGPE

NL1

6.3 A T(10 A F)

Ionisation

SupplyFlam

e detector

Safety chain

Operation

Fault

Ignition transform

er Flame detector 2 N

CFlam

e detector 2 NO

Air pressure switch

Heat request

Reset

Not used

V1

V2Thewireswhichareusedfortheconnectionmustbeapprovedforambienttemperaturesofminimun75°C(167°F).

Do not remove the jumper be-tween terminals 1 and 2, which was mounted in the factory. It is required for the intended use of the automatic gas burner control system.

Connection diagramMPA 412x

1LL 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

q

P

M

N G

qPGPE

NL1

6.3 A T(10 A F)

Ionisation

SupplyFlam

e detector

Safety chain

Operation

Fault

Ignition transform

er

Flame detector 2 N

CFlam

e detector 2 NO

Air pressure switch

Heat request

Reset

Not used

V1

V2

Page 11: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

11 … 12610 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4Outputs*Designation Safety-

relatedType of output Line length Electrical data

V1Maingasvalve

● Relaycontact Max.100m 115/230VAC/2Acosϕ=1Minimumload0.5W

V2Safetygasvalve

● Relaycontact Max.100m 115/230VAC/2Acosϕ=1Minimumload0.5W

Ignition ● Relaycontact Max.100m 115/230VAC/1Acosϕ=0.4correspondsto115/230VAC/2.5Acosϕ=1

Fan Relaycontact Max.100m 115/230VAC/1Acosϕ=0.4correspondsto115/230VAC/2.5Acosϕ=1

Operation Relaycontact Max.100m 115/230VAC/1Acosϕ=1

Fault Relaycontact Max.100m 115/230VAC/1Acosϕ=1

Flame detector supply

ForUV41(HE),42FLW10,FLW20

Max.100m 230VAC/10mA*1

Technical Data

*1:Theflamedetectorisalwayssuppliedwith230VAC,eventhe115VACversion,viatheMPA41xxpowersupplyflamedetector,pin7

Thesumofthecurrentsofallsafety-relatedconsumersmustnotexceed5A!Thesumofthecurrentsofallconsumersmustnotexceed6.3A(10A),notefusevalue

Inputs*Designation Type of input Line length Electrical dataSafetychain Potential-freecontact Max.100m 115/230VAC/max.10AFlamedetector1(Ionisation)

Ionisation for one or two-probe operation

Max.10m** Thresholdvalue:approx.1.2µA

Flame detector 2 NO Switchingcontact Max.100m 115/230VAC“normally open”

Flame detector 2 NC Switchingcontact Max.100m 115/230VAC“normally closed”

Heatrequest Switchingcontact Max.100m 115/230VACAirpressureswitch Switchingcontact Max.100m 115/230VACRemoteunlocking Switchingcontact Max.100m 115/230VAC

*Thewireswhichareusedfortheconnectionmustbeapprovedforambienttemperaturesofminimun75°C(167°F).

**Fordistances>10mflamedetector2shouldtakeplace.ForspecialapplicationsIonizationlinelengthupto50mispossibleonrequest.

Page 12: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

13 … 12612 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

General informationDesignation Type of input Electrical data MPA 4111 MPA 41x2L1connectionoverex-changeable backup fuse

L1protectedbyintegratedfuse,6.3Aslow-blowor10Afast-blow

● ●

TWI interface TWI ConnectiononlyforVision-Box and parameterisation boxNOT galvanically iso-lated!

● ●

Switchforparametermode Bistable switch ON/OFFswitchinMPA(mayonlybeswitchedafterhavingremovedMPAfromthebase)

● ●

Displayunit"Multi-function switch"

In housing towards inte-grated multi-function switch

1pushbuttonwith2LED's ●

Display In housing towards inte-grated display

3x7segment+4keys ●

Spark generator connection MPA41xxdoesnothaveamountedspark generator. Suitable spark generators, see ac-cessory list.

Attention:Aspecialsparkgeneratoris required depending on the elec-trode arrangement (single-electrodeoperation).

Technical Data

Page 13: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

13 … 12612 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Single-electrode operation ionisation

Flame detector connection

Flame detector UV41 (HE) / FLW 10 IR / 20 UV

Flame monitoring system and IgnitionFlame detector 1 connection

MPA connection

15:Ignition

3:N

4:PE

5:ION

7:FLWpower

16:FLW2NO

Flame

MPA connection

15:Ignition

3:N

4:PE

5:ION

7:FLWpower

16:FLW2NO

Flame

UV41(HE)

MPA connection

15:Ignition

3:N

4:PE

5:ION*

7:FLWpower

16:FLW2NO

Flame

*WhenusingaDUNGSDEZ1xxSEOignitiontransformerforsingle-electrodeoperation,thegreen/yellow cable must be connected to terminal 5.

Two-electrode operation ionisation

Page 14: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

15 … 12614 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Flame detector connection and ignition

Flame detector 2 connection

Flame detector FLW 41I

15:Ignition

3:N

4:PE

5:ION

7:FLWpower

16:FLW2NO

Flame

Flame detector UV 42

15:Ignition

3:N

4:PE

5:ION

7:FLWpower

16:FLW2NO

Flame

Page 15: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

15 … 12614 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Installation of the MPA 41xx

InstallationoptionsfortheMPA41xx:

- direct screw connection of the base on the mounting sur-faceBreakoutmountingholes,e.g.,withasuitablescrewdriveror drill them with a drill 4.2 mm (M4)or5.5mm(M5).

-Hatrailmounting(lockingthebaseintoplaceonahatrail)

Mounting bores

Hatrailmounting

ScrewM4

ScrewM5Attention! Use only plastic screws!

Page 16: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

17 … 12616 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

148.5

77 152.5

151,5

77 152,5

Dimensions of the MPA 4111

Dimensions of the MPA 4112

ø15,7mmforProfibusconnection

ø16mmforScrewconnectionM16x1.5

Page 17: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

17 … 12616 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Installation of the MPA 41xx

InstallationoptionsfortheMPA412x:

- direct screw connection of the housing on the installation surface usingM4screws,lengthmin.20mm

M4 M4

M4 M4

240

Dimensions of the MPA 412x

225

123

80

160

37,9 40,5 26 12

M32x1.5 - 6HM32x1.5 - 6H

M16x1.5 - 6H

M16x1.5 - 6H

M16x1.5 - 6H

32

15,5

18,5

14,6

Page 18: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

19 … 12618 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Description of the functions

Unlocking functionIfMPAislocked(state0),itcanbeun-locked by pressing the unlock key. Keep thekeypressedminimum0.5s(max.5s)todistinguishthefunctionfrompos-sible EMC interfering impulses.Thesameistruefor230Vunlockingandunlockingviafieldbusmodules.

According toDINEN14459 (annexJ),the number of possible unlocking proc-essesislimitedto5in15minutes,thatmeans the automatic system denies fur-therunlockingiftheMPAhasbeenun-locked more than 5 times within a short time period. Only after a waiting time duringwhich theMPA isprovidedwithpower is itpossible tounlock theMPAagain.

The waiting time is 15 minutes or 3minutes for each unlocking.

Extended unlockingThe described limitation to 5 unlock-ing operations in 15 minutes can bereset by means of "Extended unlock-ing".Todothis,theunlockkeymustbepressedforatleast5s(max..10s)(af-ter5s,thedisplaybeginstoflash).

The"Extendedunlocking"isactiveinalloperationalstatesoftheMPA,thatmeansthatasafetycut-offwithrestartoftheMPAinoperationcanbecarriedoutviathe"Extendedunlocking"alsointhepresenceofaflame.

Extended unlocking is not possible viathe230Vunlockinginputandviafieldbusmodules!

Access levelWriteaccesstoMPAisdefinedondif-ferentaccesslevels.Each parameter is assigned to a cer-tain access level. In order to modifyaparameter,MPAmustbe in theas-signedorhigherlevel.If theaccess level isnotsufficient formodifyingaparameter,theVisionBoxreports it, or amessage ispromptedontheMPAdisplayrequestingtoen-terthevalidpassword.Inhigherlevels,theusersmustpressakeytoconfirmthat they are on site. The display is flashingfor30suntilakeyispressed;otherwise,theMPAremainsinthepre-viouslevel.In order to change the access level,enter the correct password either on thedisplay(MPA4112/MPA4122)orintheVisionBox→MPAsettings→Ac-cesslevel.

The access level is automatically re-set after 5 hours or after power failure. Exception:Iftheautomaticgasburnercontrol system makes a restart during these5hours, forexampleduetoanerror,these5hoursforthecurrentac-cesslevelarecountedagainfromthebeginning.

Note:Werecommendresettingtheac-cesslevelafterhavingconfiguredtheautomatic gas burner control system.

Level Designa-tion

Key con-firmation required

1 Dungs yes2 OEM

Expertyes

3 OEM yes4 Service yes5 Operator no

Page 19: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

19 … 12618 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Gas valvesThevalveconnectionmaybeconfig-ured,seesection"Parameterde-scription"-P38.

Flame detectorSeeAnnex-Flamedetector.

Fortheconnectionofasecondflamedetector,seesection"Parameterdescription"-P18.

Air pressure switchSeesection"Parameterdescription"-P16

Gas pressure detectorSeesection"Parameterdescription"-P18

Limit switch / POC Proof of Clo-sureSeesection"Parameterdescription"-P18

Parameter mode (manual operation)Aswitchintheconnectionchamberis used for switching between param-eter and automatic mode.TheMPAregistersaswitchingopera-tion not before a restart.

MPA 4112/MPA 4122AfterconnectingthemainssupplyinParametermode,amessagesisprompted on the display requesting you to enter the code. Enter the pass-wordforserviceorOEMlevel.

Afterhavingchangedthelevel,theselectedparametersareactivatedoneafter the other. SeechapterMPA4112/MPA4122Parameterdisplayforparametersandsequence.Theparametervaluesmaybemodi-fiedbypressingthekeys+and-.Theunlockkeyisusedforsavingthedis-playedvalue.Pressthe←keytoreturntothepreviouspositionorparameter.

Asthedisplayhastwopositionsonly,somevaluesarerepresentedinanoptimisedresolution.Ifthesetvaluecannotbedisplayedinthisresolution,thedisplayshows"––".Thevaluemay be changed in a resolution that can be displayed.Ifallparametersareset,thereisanautomatic start for checking the pa-rametervalues.Theprogramstopsinpause states; press a key to proceed (Hxisdisplayed).Thesetparametervalueswillbeap-pliedwhenreachingtheH5state.Ifyoudonotpressanykeyfor30

minutesinparametermode,thepro-gram tries a restart.

Switch on "Auto"Withthisswitchposition,theMPAis working in normal operation. If a monitored parameter was changed andnotreleasedtheMPAindicatesanerrorwith0x60.

ParameterswitchLeft"Auto"positionRight"Para"position

Page 20: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

21 … 12620 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Flow chart

The program sequence may be cus-tomised by changing the parameters.

Attention: All modifications must comply with the requirements of the valid standard.DUNGS shall not assume any liability for material or personal damage caused by improper use or parameter setting of the auto-matic gas burner control system.

*1ThemonitoringoftheLDWdependsontheoperatingmodesetinP16.*2V1canbedeactivatedviaparameterP38afterthesecondsafetytime(=interruptedstartgas)*3ThetwoinputsFlame1andFlame2canbeactivatedordeactivatedindependentlyofoneanotherperparameter

forphase1andphase2.*4Bothflameinputsmustbeoff!*5With"Flameon",itwillrunwith15minutesoffollow-upafteraregularswitch-off.After24hOFF,thesignalwillbe

activatedfor1minute.*6Theinput"Flame2NC"canalsobeconfiguredasGDW.TheGDWtoleratesfaultysignalsofupto1s.*7Thefollow-uptimealreadystartsduringthe"Post-purge"state.Ifthepost-purgeisgreaterthan/equaltothefollow-

uptime,the"Follow-uptime"statewillbeskipped.*8TheMPAcanalsorunintwo-stageoperation(P38=2).Theselectionofstage1/stage2willthenbemadevia

afieldbus(e.g.Profibus,Modbus,...).V1isalwaysopen(=stage1).V2willopenafterafieldbussetpointinput(=stage2).Intheoperatingmodes"interruptedstartgas"(P38=0)and"permanentstartgas"(P38=1),V2isalwaysON.

*9Theinput"Flame2NC"canalsobeconfiguredasProof-Of-Closure(POC)asafunctionofoutputV1orV2.ThePOCtoleratesfaultysignalsofupto1s.

*10IntheoperatingmodeP38=2(two-stageoperation),thesecondsafetytimeisskipped,andtheMPAgoesfrom"Pause3"directlytothe"Operation"state!

Page 21: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

21 … 12620 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error

Break 1

- Man

ual opera

tion

Waiting fo

r hea

t req

uest

Idle sta

te co

ntrol a

ir pres

sure

switc

h

State c

ontrol s

afety

chain

Watchdog lo

ading phas

e

Waiting fo

r air p

ressu

re

Check f

alse f

lame

Pre-ae

ration

Break 2

- Man

ual opera

tion

Pre-ignitio

nFirs

t safe

ty tim

e (SZA) -

Ignition

First s

afety

time (

SZA) - Flam

e dete

ction

Stabilis

ation fla

me A

Break 3

- Man

ual opera

tion

Second sa

fety t

ime (

SZB) *10

Second sa

fety t

ime (

SZB) - Flam

e dete

ction *1

0

Stabilis

ation fla

me B *1

0

Operatio

n Break 4

- Man

ual opera

tion

Post-ae

ration

Follow-up tim

e *7

Restar

t pro

tectio

n

Break 5

- Man

ual opera

tion

Waiting fo

r gas

presss

ure

Safety

chain

inter

rupted

Stat

enum

ber

01

23

45

67

89

1011

1213

1415

1617

1819

2021

2223

2425

Dis

play

Info

rmat

ion

Fxx

H1

01

11

11

1H

21

11

2H

32

23

3H

44

44

H5

D2

D1

P30

P31

P34

P37

P51

P52

P20

0..

0..

0..

max

.2m

inm

ax.

1min

3sm

ax.

1min

max

.1m

in0.

.1h

0..

0..1

h0,

5..

59,5

s0,

5s0.

.1h

0..

0..

29,5

s0,

5s0.

.1h

0..

0..

0..1

h0.

.1h

0..1

h0.

.0.

.0.

.1h

Safe

ty C

hain

Hea

t Req

uest

Wat

chdo

gA

larm

Ope

ratio

n"W

aitin

g fo

r Hea

t Req

uest

""F

lam

e S

tabi

l""M

ain

Flam

e O

N"

"Fla

me

ON

""F

lam

e O

N +

bac

klas

hf"

*5V1

*2V2

*10

*8*8

Igni

tion

Fan

Rel

ayPh

ase

1Ph

ase

2

Flam

e 1

and

/ or 2

*3*4

*4*4

Air

Pres

sure

Sw

itch

*1

Gas

Pre

ssur

e Sw

itch

*6

Proo

f-Of-C

losu

re*9

*9*9

*9*9

*9*9

*9*9

*9Io

nisa

tion

Inpu

t act

ive

Out

put s

igna

lO

utpu

t sig

nal a

ny o

r con

stan

t

Inpu

t sig

nal

Inpu

t sig

nal a

ny o

r con

stan

t

P32

P35

Tim

eP

50 *

7

Capt

ion

see

page

20

Page 22: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

23 … 12622 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

State descriptionMPA 41xxState xx Designation Description

00 Error Iftheautomaticgasburnercontrolsystemisinthisstate,there is an error. The display automatically shows an error message and indicatesthecurrenterror(e.g."F11")insteadofthestatenumber.

01 Manual operation - Pause 1 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).

02 Waiting for heat request The automatic control system is ready for operation but there is not any heat request.

03 Idle state control LDW (air pressure switch)

Depending on the operating mode of LDW (P16), it ischecked whether LDW reports "no air pressure". Max.waitingtime2min.→Restart.

04 Safety chain monitoring Inthisstate,itischeckedwhetherthesafetychainispo-tential-free.Thefanrelay isstillopen,andthewatchdogrelay has not yet picked up. If the safety chain is not po-tential-free,thesystemwaitsmaximumoneminutebeforetrying to restart.

05 Watchdog loading phase The safety-related watchdog -circuit is activated. If thesafetychainisinterrupted→State25.

06 Waiting for air pressure The air pressure must be applied within a state time of max.1min.,otherwise,thesystemtriestorestart.

07 External light monitoring The flamemay not be detected within the state time ofmax.1min.Otherwise,thesystemtriestorestart.

08 Pre-purge Thisstateprovidessufficientpre-purge.Bothflameinputsmustbeswitchedoffforthedurationdefinedinparameter"Pre-purge"(P30).

09 Manual operation - Pause 2 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).

10 Pre-ignition The ignition isactivated for thedurationspecified inpa-rameterP31withoutopeningvalveV1.

11 First safety time - ignition ThegasvalveV1isopenedinthisstate.ThedurationofthisstateisP32-0.5s.

Page 23: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

23 … 12622 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

State descriptionMPA 41xxState xx Designation Description

12 First safety time - flame detection Afterdeactivatingtheignition,theprocessforflamedetec-tion is started. If an ionisation current flowsor the230Vinputisswitchedon-dependingontheconfiguration-,theMPAreportsaflame.Thedurationofthisstateis0.5s.

13 Flame A stabilisation Theflamecanstabilise in thisstate.Thedurationof thestabilisationphase(P34)canbeconfigured.

14 Manual operation - Pause 3 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).

15 Second safety time ThegasvalveV2isopenedinthisstate.ThedurationofthisstateisP35-0.5s.

16 Second safety time - flame detec-tion

Theprocessfordetectingthesecondflameisstarted.Ifanionisationcurrentflowsorthe230Vinputisswitchedon-dependingontheconfiguration-,theMPAreportsflame2.Thedurationofthisstateis0.5s.

17 Flame B stabilisation Theflame2canstabiliseinthisstate.Thedurationofthestabilisationphase(P37)canbeconfigured.

18 Operation The automatic gas burner control system is now operating. Avoluntaryswitch-offafteradefinedtimecanbeactivated(P40).Ifthistimeissettoamaximumof23hoursand59minutes,theMPAisinintermittentmode.

19 Manual mode - Pause 4 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).

20 Post-purge In this state, the post-purgeof the combustion chamberis carried out (P51). The gas valves remain closed fromthis state on. The fan continues running in this state; it is switchedoffinthenextstate.

Post-purge (P51) may be interrupted by a repeated heat request if the restart protection (P52) has been set to 0 and the follow-up time (P50) has already lapsed.

Page 24: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

25 … 12624 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

State descriptionMPA 41xxState xx Designation Description

21 Follow-up time Duringthistime(P50-P51>0),aflamesignalmaybepre-sent from thepreviousmodecausedbye.g.existing re-sidual gas in the combustion chamber. The external light monitoring is only started in the following state.The follow-up time starts in the post-purge state if the post-purge is equal to or greater than the follow-up time; then the follow-up time state is skipped.

22 Restart protection In thisstate, thesystemwaitsuntilparameterP52 isfin-ished;thispreventsanimmediaterestartoftheautomaticgasburnercontrolsystemifaheatrequestisactive.Theflamemaynolongerbedetectedinthisstate;otherwise,MPAreportsanexternallighterror.

23 Manual mode - Pause 5 If theswitch ison"Para" for theparametermode,allpa-rameters are set, and the system has run through theentireprocess, theautomaticgasburner control systemstopsinthisstate.Thesetparametervaluesarenowap-plied automatically. You may reset the parameter switch to the"Auto"mode.Alternatively,youmaypressthe"Next"key(unlockkey)torestart parameter setting from the beginning. If you do not pressanykeyduring30minutes,theautomaticgasburnercontrol system restarts or indicates an error.

24 Waiting for gas pressure IftheautomaticgasburnercontrolsystemisconfiguredforuseofaGaspressureswitch,itchangestostate24whendetectingmissinggasinstates1to10.Itleavesitinstate1aftersufficientgaspressurehasbeenbuiltup.TheMPAruns through the post-purge, follow-up time and restartprotection states before changing to state 24.

25 Safety chain open The automatic gas burner control system remains in this stateduringthetimesetinparameterP20ifthesystemdoesnotdetectaclosedsafetychain.Afterthetimehaslapsed,itdecidesbasedonP15whetheritlocksimmedi-ately or tries to restart. IfthesafetychainisclosedbeforethetimeofP20haslapsed,MPAchangestostate1tocheckthesafetychainagain.Inthisstate,thefanrelayisactive,thefanisrun-ning.

Page 25: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

25 … 12624 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter changeParametertypes:1-bitparameter(U1)-setting0and1(displayedasON/OFF),nolimits8-bitparameter(U8)-valuesettingwithinvariablelimits16-bitparameter(U16)-valuesettingwithinvariablelimits.

AparametermaybemodifiedonthedisplayofMPA4112/MPA4122orviatheVisionBoxsoftwareonaPC.

Inordertochangeaparameter,youneedtosettheaccesslevelassignedto the parameter.

Thevaluemustbewithinthevariablelimits;avalueoutsidetheselimitsisnot possible. Inaccesslevel2(OEMexpert),itispossibletochangethevariableupperandlowerlimits.Thevariablelimitsmay only be changed by means of VisionBox,notontheMPAdisplay.Thevariablelimitsarerestrictedbymeansoffixedlimits.Thesefixedlimits cannot be changed.

To change a parameter that cannot bechangedduringnormaloperation,it is necessary to change to state "Waiting for heat request".Most of the parameters are moni-toredinautomaticmode(switchontheboardon"Auto").TheMPAdetectschangesofthevaluesandimmediately changes to lockout (error0x60).Anychangesmustbereleased in parameter mode incl. a manualprogramrun(seealsopa-rametertable).

Page 26: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

27 … 12626 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P11 Fieldbus address configuration

Setting the bus slave address ofMPA.Ifaninvalidaddressfortheconnect-edbusmoduleissetandtheMPAisinautomaticmode,itrestarts(er-ror0x18).

IfaninvalidvaluefortheconnectedbusmoduleissetandtheMPAisinparametermode,anerrormessageis generated. Furthermore, the set-ting "o" for the bus address is en-tered when setting the parameters.

Duringoperationanderrormessag-es,thecurrentbusaddressmaybeseenbypressingthe←key.

Valuerange:OFF(noFieldbus)0to254(e.g. Profibus adjustment rangefrom1to126)

Note:Amodifiedvaluefor thispa-rameter is not applied before a re-start or extended unlocking.

P12 Number of restart attempts or anti-os-cillation counter

Number of restart attempts of the MPA.Afterafailedlaststart,theMPAlocksandchangestolockout(faultstate0).The anti-oscillation counter is reset when returning to operating state or whenunlockingtheMPA.

Valuerange:0-5attempts

P13 Number of restart attempts when flame is missing after the start-gas flame prov-ing period

The number of restart attempts af-ter creating a flame (P12) can belimitedforthecasethattheflameisstillmissingafterthefirststart-gasflameprovingperiod.The restart counter and the anti-oscillation counter are reset when changing to the operating state or after unlocking.

Valuerange:0-5attempts

Example:P12=5,P13=1Duringthefirststartphase,noflameisgenerated→1.Restartattempt→Error idle state control LDW → 2.Restart attempt → Error idle statecontrolLDW 3.RestartattemptAfterthethirdrestartattemptLDWOK,thereisstillnoflameAutomatic gas burner control sys-tem is locked although the number ofrestartattempts(P12)hasnotyetbeen reached but the number of re-start attempts after missing flamehas been reached.

P14 Number of restart attempts after flame lift-off or missing flame after the sec-ond start-gas flame proving period

The number of restart attempts (P12) can be limited for the casethat there is a flame lift-off or thatthe flame is still missing after thesecondstart-gasflameprovingpe-riod.The restart counter and the anti-oscillation counter are reset when changing to the operating state or after unlocking.

Valuerange:0-5attempts

Example:P12=5,P14=1Flamelift-offduringoperation→ 1.Restartattempt→ Error Idle state controlLDW→ 2.Restartattempt→ Error Idle state control LDW→ 3.Restartattempt→ Aflameisnot created after the third restart at-tempt LDW OK→ Automatic gasburner control system is locked.

Page 27: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

27 … 12626 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P15 Locking with open safety chain

Ifthesafetychainisnotclosed,theMPAwaitsinstate25(safetychainopen).If the adjustable time (P20) haslapsed and the safety chain is still open, the system changes tolockout due to an error or restarts (depending on the anti-oscillationcounter).

Thissettingisalsovalidifthesafetychain is opened after state 4.

Setting:0: Restart attempt depending onthe anti-oscillation counter1:Immediatelockout

P16 Air pressure switch operating mode

Monitoring of the air pressure may beactivatedforstart-up(states6to10)and/oroperation(states13,14and 17 to 20) and/or during post-purge(state20).Alsoforidlestatecontrol(state3).

Air pressure switch operating modeSetting Air pressure moni-

toring during post-purge

Air pressuremonitoring during startup

Air pressuremonitoring during operation

Idle statecontrol

0 OFF OFF OFF OFF1 OFF OFF OFF ON2 OFF OFF ON OFF3 OFF OFF ON ON4 OFF ON OFF OFF5 OFF ON OFF ON6 OFF ON ON OFF7 OFF ON ON ON8 ON OFF OFF OFF9 ON OFF OFF ON10 ON OFF ON OFF11 ON OFF ON ON12 ON ON OFF OFF13 ON ON OFF ON14 ON ON ON OFF15 ON ON ON ON

Page 28: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

29 … 12628 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P17 Temperature control-ler operating mode

- Internal parame-ter Value will be set automatically by the MPA.

The temperature controller can be operated in the following operating modes:

Setting0:The heat request is always swit-ched OFF, independently of thehard-ware inputSetting1:The heat request is always swit-ched ON, independently of thehardware inputSetting2:TheheatrequestisOFF,however,this operating mode must be de-fned again within one minute. Oth-erwise the automatic gas burner control system switches to the set-ting3.Thiscanhappen,forexam-ple,ifthefildbuscommunicationisinterrupted.Setting3:The heat request is determined by hardware input "temperature con-troller".Setting4:The heat request isON, however,this operating mode must be de-fned again within one minute. Oth-erwise the automatic gas burner control system switches to the set-ting3.Thiscanhappen,forexam-ple,ifthefildbuscommunicationisinterrupted.

Page 29: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

29 … 12628 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P18 Flame detector 2 or gas pressure detec-tor

This parameter defineswhether asecondflamedetector,agaspres-sure detector or a limit switch for valvemonitoringisconnected.

Setting0:The inputs NO and NC are moni-toredfortheflamesignal.Thesig-nalsmustbeinverse.Setting1:Only input NO is monitored for the flamesignal.Setting2:Only input NO is monitored for the flame signal. In addition, the Gaspressure switch signal is read out on input NC.Setting3:Only input NO is monitored for the flame signal. In addition, the limitswitchsignalforvalve1isreadouton input NC.Setting4:Only input NO is monitored for the flame signal. In addition, the limitswitchsignalforvalve2isreadouton input NC.

P19 Configuration of the output operating mode

The output may be switched to dif-ferent states by means of the follow-ing parameter settings. ON means 115VACor230VAC,forallothers,OFF,i.e.0V.

Setting0:"Wait":OutputisONinstate2(wait-ingforheatrequest).Setting1:"Stable":OutputisONinstates18(operation)and19(pause4).Setting2:"Main flame ON" output is ON instates17 (flameB stabilisation) to19(pause4).Setting3:"Flame ON" Output is ON from states13 (flameAstabilisation) to19(pause4).Setting4:"Follow-up": Output is ON fromstates13 (flameAstabilisation) to19(pause4).

Whenthisstateswillbeleft,theout-putremainsforanother15minutes. This follow-up information remains activatedbeyondarestartattemptof the automatic gas burner control system,butnotifthemainssupplyisswitchedoffandonagain.In addition, the output is switchedon for one minute after 24 hours as pump blocking protection. Note:After a restartwithin 24 hours the24 hour cycle of the pump blocking protection starts new.

Page 30: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

31 … 12630 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P20 Duration of safety chain open

This parameter defines the dura-tionofstate25(safetychainopen).Time until the system restarts or changes to lockout, depending ontheanti-oscillationcounterandP15(lockingwithopensafetychain).

Valuerange:0to65535(resolutionin1/16s).

P21 Shutter test for flame detector

Theshuttertestoftheflamedetec-torisactivatedbymeansofthispa-rameter. Makesure toobserve the settingsfor parameter P33 (active FLW inphase 1) and P36 (active FLW inphase2).

Example: If P33=1 and P36=1,there is not any shutter flame testforflamedetector2.Thetestisonlyactiveinstateswith"flameON"(states12-19).Setting0:Shutterflametestinactive.Setting1:Shutterflametest forflamedetec-tor1.Setting2:Shutterflametest forflamedetec-tor 2.Setting3:Shutterflametest forflamedetec-tors 1 and2 (expert setting).Withthis setting, the test starts only ifboth flame signals report ON; itendswithsuccessifbothflamesig-nals report OFF

P22 FM mode Setting0:notactiveSetting1:Lockoutwithmissinggasandfaultof limit switch for main gas.

P30 Duration of pre-purge Thisparameterdefinesthedurationofstate8(pre-purge).

Valuerange:0to65534(resolutionin1/16s).

P31 Duration of pre-igni-tion time

Thisparameterdefinesthedurationofstate10(pre-ignition).Duringthistime, the ignition is already active,thegasvalveisclosed.

Valuerange:2to65534(resolutionin1/16s).

P32 Start-gas flame proving period / first safety time

Definesthedurationofthestart-gasflameprovingperiod.Maximum time from opening the gasvalvestodetectingaflame.

Note:This duration is divided intostates11and12.State12isalways0.5seconds.

Valuerange:16to960(resolutionin1/16s).

Attention: For FM applications thefollowingvaluesshouldnotex-ceeded.Burnerwithpilotflame:10sBurnerwithdirectignition:<2,500,000Btu/hr≤15s>2,500,000Btu/hr≤10s

Page 31: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

31 … 12630 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P33 Active flame detector(s) for start-gas flame proving period

Theparametercontrolswhichflamedetector(s) (states11 to16) is/areactivefordetectingaflame.

Note: If flame signal 2 is used,please make sure to observe thesettingforP18(flamedetector2orgaspressuredetector).

Setting:1:Onlyflamesignal1relevant2:Onlyflamesignal2relevant3:Flame1ANDflame24:Flame1ORflame2

P34 Stabilisation time A Durationofstate13"FlameAstabilisation"

Valuerange:0to65534(resolutionin1/16s).

P35 Second start-gas flame proving period

Durationofthesecondsafetytime;the time between detecting the flamesignalofthefirstsafetytimeand the maximum time is set. Maxi-mum time from opening the gas valvestodetectingaflame.

Note: This duration is divided intostates15and16.State16isalways0.5seconds.Valuerange:16to480(resolutionin1/16s).

Attention: For FM applications thefollowingvaluesshouldnotex-ceeded.Burnerwithpilotflame:10s(Settingvaluemax.160)Burnerwithdirectignition:<2,500,000Btu/hr≤15s(Settingvaluemax.240)>2,500,000Btu/hr≤10s(Settingvaluemax.160)

P36 Active flame detector(s) for phase 2

The parameter controls which flamedetector(s)(states17"FlameBstabilisation"to19"Pause4")is/areactiveinphase2fordetectingaflame.Note:Ifflamesignal2isused,pleasemakesuretoobservethesettingforP18(flamedetector2orgaspressuredetector).

Setting:1:Onlyflamesignal1relevant2:Onlyflamesignal2relevant3:Flame1ANDflame24:Flame1ORflame2

P37 Stabilisation time B Durationofstate17"FlameBstabilisation"

Valuerange:0to65534(resolutionin1/16s).

P38 Operating mode V1 V2 DefinestheoperatingmodesforgasvalvesV1andV2duringoperation.Onlyvalidforstates18(operation)and19(pause4).

0:Interruptedstartgas.V1OFF,V2ON 1:Permanentstartgas.V1andV2ON2:Two-leveloperation.V1ON,V2ON/OFF during operation; deter-mined by bus. V2 does not openduring the second start-gas flameprovingperiod!

Note: If you use setting 2, a bus con-nection isrequired. If it ismissing,restart is tried because the bus connection is monitored in the op-erating states.

Page 32: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

33 … 12632 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParametersParameter description

Parameter Designation Description Setting / Examples

P40 Standard mode dura-tion

IftheMPAisoperating,itchangesto state 2 after this time has lapsed and restarts. Aself-testduringstart-upisrequiredevery24hoursinintermittentopera-tion.Iftheheatrequestisactiveuntilthese24hourshavepassed,anautomatic restart is tried.

NOTE(ifcontinuousoperationisnotset):ThestabilisationtimesA(P34)andB(P37)areaddedtotheoperatingtime;therefore,thesetimes are deducted from the dura-tion of the normal operation if they exceed1minute.If the total of stabilisation times is longer than the duration of the normaloperation,thedurationofthenormaloperationissetto0,andMPAswitchesoffimmediatelywhenstartingoperation(state18).

Valuerange1to65534:Timeuntilrestart(reso-lutioninminutes)65535:Continuousoperation1439:Intermittentoperation

P41 Operation safety time FLW1

DefinesthedurationofthesafetytimeforMPA41xxduringoperationforflame1.Timeuntilgasvalvesclosewhenthereisnotanyflame.

Valuerange:12to48(resolutionin1/16s).

ATTENTION: The entire reaction time after there is not any flame during operationis combined of P41 and possiblereaction times of external flamedetectors,seechapter14Annex -flamedetector.

P42 Operation safety time FLW2

Definesthedurationofthesafetytimeduringoperationforflame2.Maximumtimeuntilgasvalvesclosewhenthereisnotanyflame.

Valuerange:3to48(resolutionin1/16s).

ATTENTION: The entire reaction time after there is not any flame during operationis combined of P42 and possiblereaction times of external flamedetectors,seechapter14Annex -flamedetector.

P50 Follow-up time Definesthedurationofthefollow-uptime(state21).However,thetime measurement is already start-edduringpost-purge(state20),i.e.if the follow-up time is smaller than orequaltothepost-purgetime,thefollow-up state is skipped.

Valuerange:9to65534(resolutionin1/16s).

P51 Post-purge time Definesthedurationofthepost-purgetime(state20).

Valuerange:0to65534(resolutionin1/16s).

P52 Restart protection Definesthedurationoftherestartprotection(state22).

Valuerange:0to65534(resolutionin1/16s).

Notes regard-ing P50, P51

and P52

Post-purge (P51) may be interrupted by a repeated heat request if the restart protection (P52) has been set to 0 and the follow-up time (P50) has already lapsed.

P260 and following

Internal parameters Pleasedonotchange!

Page 33: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

33 … 12632 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParameterFactory settings

Pa-ram-eter

Designation Factory setting

Unit Accesslevel

Comfortparameter setting

Min. value Max. value

P11 Field bus ad-dress configura-tion

255 SERVICE x 0 255

P12 Number of re-start attempts or anti-oscillation counter

5 OEM 0 5

P13 Number of restart attempts when flame is missing after the start-gas flame proving period

0 OEM x 0 5

P14 Number of restart attempts after a flameout or missing flame after the second start-gas flame proving period

0 OEM x 0 5

P15 Locking with open safety chain

ON OEM x

P16 Air pressure switch operating mode

15 OEM x 0 15

P18 Flame detector 2 or gas pres-sure switch

0 OEM x 0 4

P19 Configuration of the output oper-ating mode

1 SERVICE x 0 255

P20 Duration of safety chain open

960 1/16s OEM 0 65535

P21 Shutter test for flame detector

0 OEM x 0 3

P22 FM mode OFF OEMP30 Duration of pre-

purge32 1/16s OEM x 0 65534

P31 Duration of pre-ignition time

16 1/16s OEM x 0 65534

P32 Start-gas flame proving period / first safety time

16 1/16s OEM x 16 960

P33 Active flame detector(s) for start-gas flame proving period

1 OEM x 1 4

P34 Stabilisation time A

48 1/16s OEM 0 65534

Page 34: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

35 … 12634 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParameterFactory settings

Pa-ram-eter

Designation Factory setting

Unit Accesslevel

Comfortparameter setting

Min. value Max. value

P35 Second start-gas flame prov-ing period

16 1/16s OEM x 16 480

P36 Active flame detector(s) for phase 2

1 OEM x 1 4

P37 Stabilisation time B

48 1/16s OEM 0 65534

P38 Operating mode V1 V2

1 OEM x 0 2

P40 Standard mode duration

1439 min. OEM x 0 65535

P41 Operation safe-ty time FLW1

16 1/16s OEM x 12 48

P42 Operation safe-ty time FLW2

16 1/16s OEM x 3 48

P50 Follow-up time 80 1/16s OEM 16 65534P51 Post-purge time 80 1/16s x 0 65534P52 Restart protec-

tion80 1/16s SERVICE x 0 65534

Page 35: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

35 … 12634 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Status InformationMPA 41xxDesignation Description Display

via Vision-Box

Display viadisplay

General informationLockout Systemislocked ● LED

Statenumber Currentstateofthesystem,keycombination+and-

● 7-segment

Currentaccesslevel ●Flame Flame detected ● LEDManual mode Systeminmanualmode ● 7-segmentFlame quality Value>49goodflame(forionisation) ● InfoHardwareinputfortemperaturecontroller Signalfortemperaturecontrollerinput ●

Bus connection present ● 7-segmentHeatrequest Signalcombinationfrombussetpointinputandhardwareinput ● LEDInputsLDW ●Flame1 Signalfromflame1input ●Flame 2 NO Signalfromflame2_NOinput ●Flame2NC/GDW/POC Signalfromflame2_NCinputorGDWorPOC ●OutputsGasvalveV1 ●GasvalveV2 ●Ignition ●Fan ●CounterTimecounter/Lifetime counter

Time since switching on the automatic gas burner control system

Runtimemeter Fixed runtime ● InfoRuntimemeterResettable ResettableviaVisionBoxanddisplay ●

Startcounter Fixed start counter ● InfoResettablestartcounter ResettableviaVisionBoxanddisplay ●SwitchingcyclescounterV2 ● InfoInternal informationStatetimerinminutes Displayedstatetimerrunsinminutes,otherwisein1/16sec. ●Initialisation phase The automatic gas burner control system is being initialised ●Multi-function switch Is "ON" when unlock key is pressed ●Accesslevelchange CCCorvalueflashesondisplay,↵keyexpected ● 7-segmentSafetyswitch-offflag Systemislocked ●Error index Internal error counter ●Remainingstatetime is65535ifunlimitedremainingtime ●Cycl. state counter Countsin1/128scycle ●Processorload ●Nominal modulation degree No function ●Actualmodulationdegree No function ●

LED:Indicatedbyoneofthe3LEDsonthedisplay7-segment:Indicatedbyoneorseveralcharactersofthe7-segmentdisplayInfo:Displayedininformativedisplaymode

Page 36: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

37 … 12636 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

MPA 4111Version without displayTheMPA4111versionmaybeusedifthedialogviathedisplayisnotrequired or limited information is enough.

The parameters of the system are eithersetbymeansofVisionBoxorby means of the parameterisation andservicebox.

The system status is indicated by meansoftwoLEDs.

Displayunit

Yellow LED- Operation

Red LED- Fault- Flashing signal for error code-Pausestateduringparametersetting

RESET key-Unlocking- Extended unlocking-Confirmationofaccesslevelchange

Yellow LED information

LEDOFF:Fault(state0)

LEDpermanentlyON:Waitingforheatrequest(state2)untilsecondsafetytimeforflamedetec-tion(state17)andfromstatespost-purge(20)topause5(23).

FlashingLED(0.5Hz):Operation(states18and19).

FastflashingLED(2Hz):Waiting for gas pressure if gas is missing(state24)andsafetychainopen(state25).

Red LED information

FaultThedifferentflashingfrequenciesindicate the most important error codes.The remaining error codes are indi-catedbyapermanentlylitLED.

Both LED information:PasswordentryexpectedBothLEDflashingalternating

MPA4111inParametermodeAfterenteringofthepasswordbothLEDareflashingsimultariousParametercouldbechanged

Page 37: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

37 … 12636 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

...

4s Pause4s Pause

... ...LED ein

LED aus

Anzahl der LED aus, je nach Fehler-Blink-Code

1s 1s

Blink code Minimum indication

Error ID Error designation

Pleaseseethetablesaboveformoreinformationabouttheindividualerrors.1 0xA2 ERROR_SAFETY_CHAIN_OPEN2 0x60 ERROR_PARAMETERCHANGE_NOTRELEASED3 0xA7 ERROR_NOFLAME_DURING_FIRSTSAFETYTIME3 0xBC ERROR_NOFLAME_DURING_SECONDSAFETYTIME3 0xA9 ERROR_FLAME_GONE_OUT_DURING_STABILISATION4 0xA8 ERROR_FLAME_GONE_OUT_DURING_OPERATION5 0xAA ERROR_IDLESTATECONTROL_LDW5 0xAB ERROR_NO_AIR_PRESSURE6 0xA6 ERROR_EXTERNAL_LIGHT7 0x18 ERROR_EXTERNAL_APPLICATION8 0x16 ERROR_TWI_COMMUNICATIONANDLOWVOLTAGE

Parameter setting

Tochangeparameters,settheswitchintheconnectionchamberto"Para"and supply the system with power; bothLEDsareflashingalternately.EnterthepasswordandconfirmitbypressingtheRESETbutton.BothLEDsareflashingsimultaneously.The parameters may now be changed.Inparametermode,theMPAstopsinpausestates;presstheRESETbuttontocontinuetothenextstate(seestatedescription).

Attention: The changed parameters areappliedafterpause5(state23).TheflashingfrequencyoftheLEDshows the pause state and that it is requiredtopresstheRESETbutton.

Example: The pause 4 state has beenreached:theredLEDflashes4timesandisthenswitchedoffduring4 seconds.

...4s Pause4s Pause

... ...

LED ein

LED aus

Anzahl der LED ein, je nach Pausenstate

1s 1s

Information about both LEDs:

BothLEDsarelightedtwicetochecktheirfunctionalitywhenlivevoltageisapplied.

BothLEDflash(1Hz)ifyouarere-quested to press a button to change aleveloriftheautomaticgasburnercontrol system is ready for the ex-tendedunlocking(pressingabuttonafter5s,until10s).

BothLEDsflashalternatelyifthesys-tem is started in parameter mode and the password for changing the pa-rametershasnotbeenenteredyet(inVisionBoxonPC).TheRESETbuttonand the manual mode are locked.

Error code - flashing frequency

Numberofswitched-offLEDs, dependingonerrorflashcode

Numberofswitched-offLEDs, dependingonerrorflashcode

LEDON

LEDON

4s pause

4s pause

4s pause

4s pause

LEDOFF

LEDOFF

Page 38: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

39 … 12638 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

MPA 4112/MPA 4122Version with displayThecustomermaycustomizetheMPA4112/MPA4122versiononthe integrated display to match the desired burner.Allimportantparametersmaybesetby means of the four operating keys.

Theparametersofthedeviceareei-thersetbymeansofVisionBoxorbymeans of the parameterisation and servicebox.

3x7segmentdisplay

LED:Blue:HeatrequestYellow:Flamequality(flashesiftheflamequalityispoor)Red:Fault

Release buttonRESETfunctionandconfirmationofthe entry

Back

PlusIncreasesthedisplayedvalue

MinusReducesthedisplayedvalue

Dependingontheoperatingstateof the automatic gas burner control system,differentinformationisdis-played:

Page 39: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

39 … 12638 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Overview of the display modes for MPA 4112/MPA 4122

Mode:

Operation display

Error display

Info display

Displayoftheerrormemory

Parameterdisplay

Resetdisplay

Flashing display

Active:

innormaloperationifnoerrorisactive

if the automatic gas burner control system is in lockout

From operation display by pressing a shortcut

and

From operation display by pressing a shortcut

From operation display by pressing a shortcut

From operation display by pressing a shortcut

Dependingonthedisplaymode:

1.Requesttoconfirmtheaccesslevelchange2. Keeptheunlockkeydepressedformorethan5storestarttheMPA ("Extendedunlocking")

3.Processor2error,seeerrorlist4. New password after password change5. Restartofthesystem,allsegmentsandLEDsareflashing

Page 40: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

41 … 12640 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

MPA41x2 display

MPA41x2 display

▶ Displayed operating state for setting parameters and troubleshooting

Heatrequestblue

Flameyellow

Faultred

Characterblue

AttentionIllustrationin7-Segmentdisplay

1.Digits

6=

8=

0=

2. Characters

Bor.b=

Dor.d=

Ooro=

Page 41: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

41 … 12640 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

MPA 4112 display

▶ Shows the operating state of the system

11.7 Operating state

Post-purgeFollow-up timeRestartprotection

Waiting for safety chain

with open safety chain from watchdog loading phase state

Waiting for gas pressure

withinsufficientgaspressure

Flame B stabilisationOperation

SecondsafetytimeSecondsafetytime-Flame detection

FlameAstabilisation

Pre-ignitionFirst safety time - ignition First safety time -Flame detection

IdlestatecontrolLDW(airpres-sureswitch)SafetychaincheckWatchdog loading phaseWaiting for air pressure External light controlPre-purge

Waiting for heat request

Parameterswitchto"Auto",pow-er supply "On"

Page 42: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

43 … 12642 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Operation display

Additional display information

▶ Display of state number▶ Display of bus address

Displayofstatenumber

Press the keys simultaneously to changethe state display

DisplayofbusaddressorOFF

Displayofbusaddresswhilepress-ing a key

Operation display

Page 43: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

43 … 12642 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Parametersareloadedfromtheparameterisation and serviceboxintoMPA

Operation display

Display / Parameterisation and service box

▶ Display of the state of the automatic gas burner control system for parameterisation or check in the service box

TheMPAisintestmodeinitialisedbytheparam-eterisationandservicebox.Note:Theparameterandresetdisplayislockedduring the test

Page 44: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

45 … 12644 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Information display

▶ The information display is activated from the operation display (not during automatic parameter setting).

▶ The information display allows to see the flame quality, the resettable runtime meter, the resetta-ble start counter and the switching cycles counter.

▶ This mode is quit after 60 seconds due to a timeout if you do not press any key within this time period.

Info display

DisplayofflamequalityMax58<50flashingseealso:Appendix-Flamesafeguard

Displayofresettableruntimemeter Tens of thousands digit

Displayofresettableruntimemeter Hundredsdigit

Displayofresettableruntimemeter Unit

Displayofresettablestartcounter Tens of thousands digit

Displayofresettablestartcounter Hundredsdigit

Displayofresettablestartcounter Unit

DisplayofswitchingcyclecounterV2Tens of thousands digit

DisplayofswitchingcyclecounterV2Hundredsdigit

DisplayofswitchingcyclecounterV2Unit

Back to operation display

from each info display state

Back to operation display

Page 45: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

45 … 12644 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error display

▶ The error display is automatically activated if the automatic gas burner control system signalises an error.

▶ The last occurred error is displayed.

Error display

The state number is displayed as long as the plus button is pressed

The additional error note is displayed as long as the minus key is pressed

Automaticactivationifafaultisactive

The current bus address is displayed as long as the back key is pressed

Unlock

Page 46: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

47 … 12646 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Display of the error memory

▶ The error memory shows the last 10 errors.▶ The error that has occurred last is displayed.

▶ The error memory display is activated out of the operation display (not during automatic param-eter setting).

▶ The error code is displayed on the two-digit seven-segment display.

▶ This error memory display is quit after 60 s due to a timeout if you do not press any key within this time period.

▶ If there is not any error for the error position, -- is displayed.

Display of the error memory

The state number is displayed as long as the plus button is pressed

The additional error note is displayed as long as the minus key is pressed

Back to operation display

Lasterroroccurred

Ifthekeyispressed,thepreviouserrorisdisplayedalways.

From each error display state

The state number is displayed as long as the plus button is pressed

The additional error note is displayed as long as the minus key is pressed

Back to operation display

Tenth to last error

...

Page 47: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

47 … 12646 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

DisplayNumber

Parameter Valuerange

Unit

0 P30-pre-purgetime 0...99 1s1 P31-durationofpre-ignition 0...99 1s2 P32-Firststart-gasflameprovingperiod 1...60 1s3 P33-Activeflamemonitoringphase1 1...44 P35-Secondstart-gasflameprovingperiod 1...30 1s5 P36-Activeflamemonitoringphase2 1...46 P41-Operationsafetytimeforflamedetector1 06...30(=0.6...3s) 0.1s*1

7 P42-Operationsafetytimeforflamedetector2 05...30(=0.5...3s) 0.1s*1

8 P51-post-purgetime 0...99 1s9 P14-Numberofpermittedrestartsafterflamelift-offduringoperation 0...5A P13-Numberofpermittedrestartsaftermissingflame 0...5b P15-Lockingafteropeningthesafetychain 0=OFF/1=ONC P16-Operatingmodeoftheairpressuredetector 0...15d P38-OperatingmodeV1V2 0...2E P18-Flamedetector2NCmonitoring/Gaspressureswitch/POC 0...4F P40-Continuousoperation(noswitch-offafter24h) 0=OFF/1=ONh *3 P21-Shuttertestforflamedetector 0...3L P19-Outputoperatingmode"Operation" 0...4o P52-Durationofrestartprotection 0...99 1sn *2 P11-Fieldbusaddress 0...99*2

*1Adjustableinsteps: 05=0.5s 8/16 (onlypossibleforFLW2forFLW41Iwith0,19sreactiontime) 08=0.75s 12/16 (onlypossibleforFLW1,smallestpossibleadjustment) 09=0.875s 14/16 (forUV41/UV42with0.125sreactiontime) 10=1s 16/16 15=1.5s 24/16 (forFLW41Iwith0,19sreactiontime) 19=1.875s 30/16 (forUV41/UV42with0.125sreactiontime) 20=2s 32/16 25=2.5s 40/16 (forFLW41Iwith0,19sreactiontime) 29=2.875s 46/16 (forUV41/UV42with0.125sreactiontime) 30=3s 48/16

*2Usetheshortcut-and+toswitchbetweenOFF(display=oF)andtheaddress.Thesetting"o"isonlydisplayedifabusmoduleisconnected.Addressesover99mustbesetbymeansofVisionBox.

*3Thesetting"h"isonlydisplayedifcontinuousoperationisactiveorhasbeenactivatedinsettingF.

Parameter display

Parameter display

▶ After activating the automatic parameter setting, 19 parameter values must be defined; see param-eter list.

▶ This parameter setting is not quit by means of a timeout. ▶ A password is required for changing the parameters.

▶Attention: Some parameter values are displayed in another resolution than in the parameter mode using VisionBox. If it is not possible to display the parameter value in this resolution, -- is dis-played; nevertheless, the value may be changed in the resolution that can be displayed.

▶ To change service or OEM parameters, the required password or a higher-level password must be entered (e.g. all service parameters may also be changed using the OEM password).

Page 48: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

49 … 12648 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

flashing(30stimeout)

Passwordentry1stcharacter

Passwordentry2nd character

flashing(30stimeout)

Parameterswitchto"Para",power supply "On"Passwordentry

Parameter display

▶ Attention: Press the "Back" button to return to previous steps in parameter mode.If you have reached the first entry field again, press the key again to quit the parameter mode.

Page 49: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

49 … 12648 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Parameter0(P30)Pre-purgetime(0-99s/1s)

Parameter1(P31)Pre-ignition(0-99s/1s)

Parameter2(P32)Firststart-gasflameprovingperiod (0-60s/1s)

Parameter3(P33)Activeflamemonitoringphase1(1-4)

Page 50: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

51 … 12650 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Parameter4(P35)Secondstart-gasflameprovingperiod (1-30s/1s)

Parameter5(P36)Activeflamemonitoringphase2(1-4)

Parameter6(P41)Operationsafetytimeforflamedetector1(0,8-3s/0,1s)

Parameter7(P42)Operationsafetytimeforflamedetector2(0,5-3s/0,1s)

Page 51: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

51 … 12650 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Parameter8(P51)Post-purgetime(0-99s/1s)

Parameter9(P14)Numberofpermittedrestartsafterflamelift-offduringoperation(0-5)

ParameterA(P13)Numberofpermittedrestartsafternoflameatstartup(0-5)

Parameterb(P15)Lockingafteropeningthesafetychain0=NO(OFF)1=YES(ON)

Page 52: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

53 … 12652 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Parameter[(P16)Operating mode of the air pressure detector (0-15)

Parameterd(P38)OperatingmodeV1;V2(0-2)

ParameterE(P18)Flamedetector2NCmonitoring/GDW/POC(0-4)Attention:Setparameterto01ifFLW2inputisunused

ParameterF(P40)Continuous operation0=NO(OFF)1=YES(ON)

ON

OFF

Parameterh(P21)Shuttertestforflamedetector(0-3)

Page 53: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

53 … 12652 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Back to parameter0

ParameterL(P19)Outputoperatingmode(0-4)

Restartprotectionparameter(P52)Durationoftherestartprotection(0-99s/1s).

Parametern(P11)Fieldbus address (0-99)

Manual modefor checking the settings

(press+and-to-gether to switch fieldbusOn/orOff

Page 54: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

55 … 12654 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Post-purgeFollow-up timeRestartprotection

Waiting for safety chain

with open safety chain from watchdog loading phase

Waiting for gas pressure

withinsufficientgas

Flame B stabilisationOperation

SecondsafetytimeSecondsafetytime-Flame detection

FlameAstabilisation

Pre-ignitionFirst safety time - ignition First safety time -Flame detection

IdlestatecontrolLDW (airpressureswitch)SafetychaincheckWatchdog loading phaseWaiting for air pressure External light controlPre-purge

Waiting for heat request Manualoperation-Pause1

in manual mode

"Next" key

"Next" key

Manualoperation-Pause2

Manualoperation-Pause3

in manual mode

"Next" key

Manualoperation-Pause4

in manual mode

"Next" key

Manualoperation-Pause5

in manual mode

Startparameter0

ParametersettingfinishedInterruptvoltagesupplySwitchfrom"Para"to"Auto"

Manual mode for checking settings

Page 55: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

55 … 12654 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Reset display

Reset display

▶ The reset display is activated out of the operation display (not during automatic parameter set-ting).

▶ The reset display allows deleting error memory, access level, resettable runtime meter or start counter and changing the passwords for service and OEM level.

▶ This mode is quit after 60 seconds due to a timeout if you do not press any key within this time period.

▶ If the test mode of the programm- and service box is active the reset display is locked.

Activationoftheresetdisplaybysimultaneous pressing of the keys

Previousaction

Next action

Cancel the action

Action0,1,2,3

Actiontobecarriedout:0 deletestheerrormemory1 resetstheaccesslevel2 deletes the resettable

runtime meter3 deletesresettablestartcounter4 Change password forservicelevel

5 ChangepasswordforOEMlevel

Action4,5

Back to operation display

Page 56: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

57 … 12656 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Correct password

Entry1stcharacter

Incorrect password

Back to operation display

Entry2nd character

Entryofthepreviouspassword1stcharacter

Entryofthepreviouspassword2nd character

Displayofnewpassword

Displayofnewpassword

Operation display

Page 57: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

57 … 12656 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xx error table for minimum indication (MPA4111) ordered by flash codeErrorID

Internalerror

Error descriptionPlease see the tables above for more information about the individual errors.

1 0xA2 ERROR_SAFETY_CHAIN_OPEN2 0x60 ERROR_PARAMETERCHANGE_NOTRELEASED3 0xA7 ERROR_NOFLAME_DURING_FIRSTSAFETYTIME3 0xBC ERROR_NOFLAME_DURING_SECONDSAFETYTIME3 0xA9 ERROR_FLAME_GONE_OUT_DURING_STABILISATION4 0xA8 ERROR_FLAME_GONE_OUT_DURING_OPERATION5 0xAA ERROR_IDLESTATECONTROL_LDW5 0xAB ERROR_NO_AIR_PRESSURE6 0xA6 ERROR_EXTERNAL_LIGHT7 0x18 ERROR_EXTERNAL_APPLICATION8 0x16 ERROR_TWI_COMMUNICATIONANDLOWVOLTAGE

Page 58: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

59 … 12658 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xx error without error IDErrorID

Internalerror

Error description

F1flashing

LowvoltageBus connection interruptedInternal error

F2flashing x Theconnecteddisplayisinvalid

F3flashing

The password has been entered incorrectly when trying to change it or has not been con-firmedbymeansoftheunlockkey

F4flashing

Thesignaloftheremoteunlockingviabusisactivetoolong

F5 to F8 not usedF9

flashingConnection to bus missing. The bus module has been connected but there is not any con-nection to the master.

FAflashing x Failedtoreadparameter"Outputoperatingmode",theoutputfortheoperatingmodeisnot

switched

Page 59: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

59 … 12658 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xxError from the basic system (0x01 to 0x3F)ErrorID

Flash code

minimum indica-

tion

Internalerror

Error description

0x01 0 X ERROR_INTERRUPT_CYCL_STATEFRAME0x02 0 X ERROR_WD_TRIGGERING

0x03 0

ERROR_WD_HARDWAREPossiblecauseoftheerror:Too high ambient temperatureOvervoltage

0x04 0

ERROR_UNLOCKING_DENIEDPossiblecauseoftheerror:Morethan5unlockingoperationsinthelast15minutes. Remedy:Waitorextendedunlocking

0x05 0 x ERROR_ROM_TEST0x06 0 x ERROR_RAM_TEST0x07 0 x ERROR_PINSHORTCIRCUIT0x08 0 x ERROR_STACK_OVERFLOW0x09 0 x ERROR_PROGRAMMING0x0A 0 x ERROR_DI_VARIABLE0x0B 0 x ERROR_IN_TABCONTROLERROR0x0C 0 x ERROR_CONFIGURATION0x0D 0 x ERROR_CPU_TEST0x0E 0 x ERROR_EEPROM_PARAMETER0x0F 0 x ERROR_ADDRESS_TEST0x10 0 x ERROR_FUNCTION_ERRORID

0x11 0ERROR_UNDERVOLTAGEPossiblecauseoftheerror:Theadmissiblelowervoltagelimitwasnotreachedatleastforashorttime

0x12 0ERROR_POWERFAILUREPossiblecauseoftheerror:Thesupplyvoltagewasinterruptedduringstartup,operationorregularswitch-off

0x13 0

x ERROR_WD_STATUSSafetychainnotpotential-free.Possiblecauseoftheerror:The fan continues running too long. Remedy:Increasethetimefortherestartprotection

0x14 0 x ERROR_DI_SEGMENT_TEST0x15 0 x ERROR_SFRREGISTER_TEST

0x16 0

ERROR_TWI_COMMUNICATIONPossiblecauseoftheerror:ATWIbususerwasconnectedtothebusorseparatedfromthebuswhiletheMPAwasnotdisconnectedfromthemains.Remedy:ConnectorseparateauseroftheTWIbusonlyiftheMPAisdisconnectedfromthemains.Too many users are connected to the TWI bus or EMC faults occur on the TWI line. Remedy:Useshorterlinesorreducethenumberofusers

0x17 0 x ERROR_STATEFRAME_OVERLOAD

Page 60: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

61 … 12660 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xxError from the basic system (0x01 to 0x3F)ErrorID

Flash code

minimum indica-

tion

Internalerror

Error description

0x18 7

ERROR_EXTERNAL_APPLICATIONPossiblecauseoftheerror:Aswitch-offhasbeenactivatedbyanexternaluser,forexamplebyselectingthefunction"Switch-off"inthePCsoftwareoftheVisionBoxTimeoutofparametermode/manualmode(0.5hwithoutpressingakey)-de-tailerror4thbyte=0xA0An invalid fieldbusaddresshasbeenentered inP11 for the connectedbusmodule.Detailerror4thbyte=0xA1and6thbyte=setaddressP11

0x19 0 not used0x1A 0 x ERROR_SWWD_DURING_INITIALISATION0x1B 0 x ERROR_BUFFEROVERFLOW0x1C 0 x ERROR_SYNCHRONISATION_DURING_INITIALISATION

0x1D 0ERROR_PROCESSORFAILUREPossiblecauseoftheerror:ThereisstrongEMCinterferenceonMPA

0x1E 0 x ERROR_SFRREGISTER_STATEBLOCK

Page 61: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

61 … 12660 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xxError from the extended functions (0x40 to 0x9F)ErrorID

Flash code

minimum indica-

tion

Internalerror

Error description

0x40 - 0x42

reserved

0x43 0 x ERROR_TEST_IONISATIONINPUT0x44 - 0x5F

reserved

0x59

ERROR_MONITORING_INTERFACEP2Internal failureFieldbusnotconnectedorinterruptedwhileP38setting=2(externaldetarmin-ationV2)

0x60 2 ERROR_PARAMETERCHANGE_NOTRELEASEDAmonitoredparameterhasbeenchanged

0x61 ERROR_SHUTTERTEST

Page 62: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

63 … 12662 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xxError from the extended functions (0x40 to 0x9F)ErrorID

Flash code

minimum indica-

tion

Internalerror

Error description

0xA0 0 x ERROR_STATE_DURATION_TOO_LONG0xA1 reserved

0xA2 1

ERROR_SAFETY_CHAIN_OPENPossiblecauseoftheerror: The safety chain has been opened or is not closedThe wires of the safety chain are interrupted

0xA3 not used0xA4 0 x ERROR_FEEDBACK_V1_INCORRECT0xA5 0 x ERROR_FEEDBACK_V2_INCORRECT

0xA6 6

ERROR_EXTERNAL_LIGHTPossiblecauseoftheerror:Earth connection to an ionisation electrodeGasflowsoutandisburnedforexamplebyneighbouringburnersWrongconfigurationofP46andP47(totalmustbegreaterthan0.5s)DefectiveUVtubeConnectedflamedetector(UV,...)detectslightorisdefective

0xA7 3

ERROR_NOFLAME_DURING_FIRSTSAFETYTIMEAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1Possiblecauseoftheerror:Ionisation electrode incorrectly setIgnition electrodes incorrectly setInsulatedlinesoftheignitionelectrodesordefectiveionisationelectrodeGasvalvesdonotopenthegasflowConnectedflamedetector(UV,...)doesnotdetectlightorisdefectiveLinesofmainsconnectionontheMPAexchanged("N"and"L1")

0xA8 4

ERROR_FLAME_GONE_OUT_DURING_OPERATIONAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1Possiblecauseoftheerror:FlamebodydefectiveConnectedflamedetector(UV,...)doesnotdetectlightorisdefective

0xA9 3ERROR_FLAME_GONE_OUT_DURING_STABILISATIONAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1

0xAA 5

ERROR_IDLESTATECONTROL_LDWPossiblecauseoftheerror:TheairpressuredetectorisdefectiveThereisairpressureduringtheidlestatecontrol,forexampleduetoanairflowfromtheexhaustline,...Thethresholdvalueoftheairpressuredetectorissetincorrectly

0xAB 5 ERROR_NO_AIR_PRESSURE0xAC 0 x ERROR_FEEDBACK_IGNITION_INCORRECT0xAD 0 ERROR_LACKOFGAS_GDWMIN0xAE–0xAF

reserved

0xB0 0 x ERROR_TESTCIRCUIT_EXTENSION0xB1-2 reserved

0xB3 ERROR_GASVALVEFEEDBACK_FALSEAdditionalinformationbyte0:1=V1,2=V2

0xB4-5 reserved0xB6 0 ERROR_LIMITSWITCH_MAINGAS(POC)

Page 63: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

63 … 12662 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewMPA 41xxError from the extended functions (0x40 to 0x9F)ErrorID

Flash code

minimum indica-

tion

Internalerror

Error description

0xB7–0xBB reserved

0xBA ERROR_FALSEFLAME_STARTFalseflame>1min.afterheatrequest

0xBC 3ERROR_NOFLAME_DURING_SECONDSAFETYTIMEAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1

0xBD 0 ERROR_FLAMEDETECTOR_NOTSWITCHED_INVERSE0xBF 0 ERROR_SAFETY_CHAIN_NOT_POTENTIAL-FREE

Page 64: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

65 … 12664 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Annex

Setting bus adress, bus termination ................................................................................................................. 65Profibus, Modbus, Shutter Extension module MPA 41xx - EM 2/4 ............................................................ 66-78Multifunctional modul MPA 41xx-EM 2/6 ..................................................................................................... 79-104Flame detector ............................................................................................................................................ 105-106 UV 41 ............................................................................................................................................................107-108UV 42 ............................................................................................................................................................109-110UV 4x EM 1/1 Shutter module ...................................................................................................................... 111-112FLW 20 UV ....................................................................................................................................................113-115FLW 10 IR .....................................................................................................................................................116-118FLW 41 I .........................................................................................................................................................119-120Ignition transformers DEZ ..........................................................................................................................121-123VisionBox ............................................................................................................................................................124

Page 65: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

65 … 12664 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Setting the Profibus addressIf you want to connect the automatic gas burner control system to the bus,avalidProfibusaddressmustbeenteredinparameterP11.Thedisplay shows OFF during param-etersettingifyouhavenotsetanyaddress.Pressthekeys-and+toswitch to the change mode. Now set the desired address in the range from1to126.If you want to change the address lateron,itispossibleduringopera-tion.Important:Anymodificationsare applied after a restart or an extended unlocking of the automatic gas burner control system.

AbusconnectionisnotrequiredforoperatingtheMPA.Ifabusisnotconnected,theMPAcanonlyreceiveaheatrequestviathehardwareinput"Temperature controller".Ifthereisabusconnection,whichcanberecognisedbyaflashingdigitonthedisplay,theheatrequestisgivenbymeansofbit0andbit6inAB0.Ifthesystemisagainsepa-ratedfromthebus,itautomaticallychanges to reading the hardware input "Temperature controller" after one minute.

Duringoperationanderrormes-sages,thecurrentbusaddressmaybeseenbypressingthe←key.

Bus terminationAterminatorisrequiredonthefirstandlastdeviceonthebus.

The shielding of the bus cable should be placed onto PEtoavoidelectromagneticradia-tion.

Pinassignment(M12-5B-coded)

Pin no. Signal1 +5Vsupplyforbustermination2 Datalineminus(Aconductor)3 Earth4 Datalineplus(Bconductor)5 not usedThread Shielding(earthconnection)recom-

mended

Pin Socket

1

2

3

4

3

1

2 4

5 5

Page 66: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

67 … 12666 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Extension module MPA 41xx EM 2/4 Profibus DP interface,Modbus RTU / ASCII and shut-ter activation for flame detector device suitable for continuous operation

UniversalextensionmoduleforintegratingtheMPA41xxinfieldbussystemswithupto32slaves.

Integratedfunctions:-ProfibusDPinterface-ModbusRTU/ASCII-Activationforshuttermodule UV4x/Shutter

The bus protocol can be selected by meansofDIPswitch.Viathebus,commandscanbetrans-mittedtotheMPAandstatusinforma-tion can be queried.Inaddition,anoutputforactivatingthe shutter module to continuously operatetheUV4xprobesisinte-grated.

BUS protocol presettings

The4-pinDIPswitchisusedtoselectthebusprotocolandtoactivatetherespectivelinetermination.The bus protocol must be selected onlywithdeadvoltage.Modificationsare impossible during operation.

Bus protocol selection

DIP switch No. 4:

OFFposition=ProfibusONposition=Modbus

ON 1 2 3 4

Bus termination

IftheterminationisactivatedviatheDIPswitch,externalterminationresistors must not be plugged into the output connectors.

Ifaterminationisactivated,thetermi-nationofthealternativebusprotocolhastobedeactivatedinanycase.Modbus termination

DIP switch No. 1:

ONposition=Modbusterminationresistor120Ohm

Profibus termination

DIP switches No. 2 and 3:

ONposition=Profibusterminationresistor220Ohm

Setting the bus address

ThebusaddressisenteredintheP11parameter(displayindication"n").OFF is displayed if no address has been entered. Anaddressbetween1and99(upto126viaVisionBox)canbeenteredintheparametermode.Anymodi-ficationswilltakeeffectonlyafterarestart or an extended unlocking.

Duringoperationanderrormessag-es,thecurrentbusaddressmaybeseenbypressingthe←key.

Bus interruption

ModbusThe bus module requires at least one queryperminute.Ifthereisnoquery:

-safetyswitch-offifV2isactivatedviathebus

or-afteranotherminute,switchoverto

the hardware input "heat request" is done

ProfibusIf the cyclic data stream is interrupt-ed,afteraProfibusWatchdogperioddefinedbythemaster(e.g.2.5s):-safetyswitch-offifV2isactivatedviathebus

or-afteranotherminute,switchoverto

the hardware input "heat request"

Profibus data

The amount of the input and output dataisdefinedbythemodulesintheenclosedGSDfileforProfibus.

Profibus output data master to MPA

Theoutputdatahave8bits,seetable

Commandcontentsofassignedbits:

Bit 0(heatrequest)setto1bymas-ter=heatrequest.

Bit 1(highpower)setto1bymaster=V2isopenedinthestates18(opera-tion)and19(pause4)(parameter38issettovalue2).

Bit 2(remoteunlocking)setto1bymaster(atleast0.5smax.5s)=MPAisunlocked.

Bit 6(deactivateheatrequest)setto1bymaster=thebit0signal"heatrequest"isignored,theautomaticgas burner control system does not receiveaheatrequestviathebus.Theheatrequestisonlypossibleviathe hardware input.

Eight modules are integrated in the enclosedGSDfile.Fourofthem,amoduleforBasic,StandardandExtended,donotcontainanyoutputbytesbutonlyinputbytes(informa-tionaboutMPA).Thereforetheycan-notgiveanycommandstoMPA.

Bit Output byte AB00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestvia

bus)7 Reserve(pleaseset0)

Page 67: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

67 … 12666 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Profibus input data MPA to master

Input data is information about the stateoftheMPA.Theinputdatacon-tainadifferentnumberofbytes,de-pending on the data transfer module used. The lower bytes are always the same,i.e.BasictransferisincludedinStandardtransfer,Standardtransferin Extended transfer.

Basic transfer 2 bytes EB0andEB1

Standardtransfer4bytesEB0toEB3

Extendedtransfer12bytesEB0toEB11

SpecialExtended-Transfer20bytesEB0bisEB19

ThebytesEB0andEB1containbitinformation.Ifthebitissetto1,theconditionisincluded in the description of the bits.Somebitsareactiveduringthefault(markedwith"X"),othersare0.

Page 68: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

69 … 12668 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Basic transfer areaMPA 41xxBit Input byte EB0 Description During fault0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressure X

5 Input for temperature controller

Signalofthehardwareinput"Temperaturecontroller" X

6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X

Bit Input byte EB1 Description During fault0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 0

4 Temperature control-ler(hardware+bus)

Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification

X

5 not used 0

6 not used 07 Fault There is a fault in the automatic gas burner control system X

Page 69: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

69 … 12668 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Standard transfer areaMPA 41xxBit Input byte EB2 Description During fault

0-7 Statenumberorerrorcode

Current state number or error code if there is a fault X

Bit Input byte EB3 Description During fault0-7 Flame quality Qualityoftheflameoverionisationinput 0

Bit Input byte EB5 Description During fault

0-7 ResettableRuntimemeter

Byte1ofthe32-bitruntimemeter(Units)

X

Bit Input byte EB6 Description During fault

0-7 ResettableRuntimemeter

Byte2ofthe32-bitruntimemeter(Units)

X

Bit Input byte EB7 Description During fault

0-7 ResettableRuntimemeter

Highbyte(byte3)ofthe32-bitruntimemeter(Units)

X

Bit Input byte EB8 Description During fault

0-7 ResettableStartcounter

Lowbyte(byte0)ofthe32-bitstartcounter X

Bit Input byte EB9 Description During fault

0-7 ResettableStartcounter

Byte1ofthe32-bitstartcounter X

Bit Input byte EB10 Description During fault

0-7 ResettableStartcounter

Byte2ofthe32-bitstartcounter X

Bit Input byte EB11 Description During fault

0-7 ResettableStartcounter

Highbyte(byte3)ofthe32-bitstartcounter X

Extended transfer areaMPA 41xxBit Input byte EB4 Description During fault

0-7 ResettableRuntimemeter

Lowbyte(byte0)ofthe32-bitruntimemeter(Units)

X

Page 70: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

71 … 12670 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Input byte EB13 Description During fault

0-7Resettable

SwitchingcyclescounterV2

Byte1des32–bitswitchingcyclescounterV2(Unit:s)

X

Bit Input byte EB14 Description During fault

0-7Resettable

SwitchingcyclescounterV2

Byte2des32–bitswitchingcyclescounterV2(Unit:s)

X

Bit Input byte EB15 Description During fault

0-7Resettable

SwitchingcyclescounterV2

Highbyte(Byte3)ofthe32–bitswitchingcyclescounterV2(Unit:s)

X

Bit Input byte EB16 Description During fault

0-7 ResettableRuntimemeterV2

Lowbyte(Byte0)ofthe32–bitruntimemeterV2(ins) X

Bit Input byte EB17 Description During fault

0-7 ResettableRuntimemeterV2

Byte1ofthe32–bitruntimemeterV2(ins) X

Bit Input byte EB18 Description During fault

0-7 ResettableRuntimemeterV2

Byte2ofthe32–bitruntimemeterV2(ins) X

Bit Input byte EB19 Description During fault

0-7 ResettableRuntimemeterV2

Highbyte(Byte3)ofthe32–bitruntimemeterV2(ins) X

Special extended transfer areaMPA 41xxBit Input byte EB12 Description During fault

0-7Resettable

SwitchingcyclescounterV2

Lowbyte(Byte0)des32–bitswitchingcyclescounterV2(Unit:s)

X

Page 71: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

71 … 12670 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Declaration of the Profibus interfaceMPA 41xxManufactureridentification IDOXOCF1(KarlDungsGmbH&Co.KG)ASCICtype VPC3+C

SyncandfreezemodeIs supported(Synccommand:FreezealloutputsoftheaddressedslavesFreezecommand:Freezeallinputsoftheaddressedslaves)

Cycle time

Maximumtimeuntilthereisaresponsetoarequesttelegram,dependingonthebustransferrate:9.6kBit/sto500kBit/s→15bittimes1500kBit/s→20bittimes3000kBit/s→35bittimes6000kBit/s→50bittimes12000kBit/s→95bittimes

Diagnosis

TheProfibusmodulecreatesanexternaldiagnosisifitdetectsaninternaler-ror.ThediagnosisinformationoftheDPslaveconsistsofstandarddiagnosisinformation(6bytes)andauser-specificdiagnosisinformationerrornumber(2bytes).Octet1:Bit0=Diagnosisstationdoesnotexist(setsmaster)Bit1=Diagnosisstationnotready:Theslaveisnotreadyfordataexchange.Bit2=Diag.cfg_Fault:ConfigurationdatadonotmatchBit3=Diag.ext_diag:SlavehasexternaldiagnosisdataBit4=Diag.notsupported:RequestedfunctionisnotsupportedinslaveBit5=Diag.invalid_slave_response(setsslavefixedto0)Bit6=Diag.prm_fault:Wrongparameters(IDnumber,etc.)Bit7=Diag.master_lock(setsmaster):Parametersofslavearesetbyan-other masterOctet2:Bit0=Diag.Prm_req:SlaverequiresnewparametersBit1=Diag.Stat_diag:Staticaldiagnosis(bytediag-bits)Bit2=fixedto1Bit3=Diag.WD_ON:ReactionmonitoringactiveBit4=Diag.freeze_mode:FreezecommandreceivedBit5=Sync_mode:SynccommandreceivedBit6=reservedBit7=Diag.deactivated(setsmaster)Octet3:Bit0-Bit6=reservedBit7=Diag.ext_overflowOctet4:Diagmaster_add:Masteraddressaftersettingparameters(FFwith-outparametersetting)Octet5:HighbyteIDnumberOctet6:LowbyteIDnumber

Parameter Only cyclical communication supportedAutomaticbaudratedetection is supported

Page 72: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

73 … 12672 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Registration address 00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestvia

bus)7 Not used8 Not used9 Not used10 Not used11 Not used12 Not used13 Not used14 Not used15 Not used

Modbus dataModbus RTU or ASCII mode

The modbus protocol can be switched overtoASCIImode(seeprotocol)us-ingtheFunctionCode0x41.Thesettingispermanentlysavedintheslave.Standardvalue(upondelivery)ismod-busRTU.

Modbus output data master to MPA

Theoutputdatahave16bits,seetable

Command contents of assigned bits:

Bit 0(heatrequest)setto1bymaster=heatrequest.

Bit 1(highpower)setto1bymaster=V2isopenedinthestates18(opera-tion)and19(pause4)(parameter38issettovalue2).

Bit 2 (remoteunlocking) set to1bymaster(atleast0.5smax.5s)=MPAis unlocked.

Bit 6 (deactivateheatrequest)setto1bymaster= thebit 0 signal "heatrequest"isignored,theautomaticgasburnercontrolsystemdoesnotreceiveaheat request via thebus.Theheatrequestisonlypossibleviathehard-ware input.Use the followingFunctionCodes towritethesespecifications.05(0x05)WriteSingleCoil(Coil=bitatbitaddressx)06 (0x06)WriteSingleRegister (toregisteraddress)

16(0x10)WriteSingleRegister(fromregisteraddress)

IfitisnotwrittenonAB0,theMPAfunc-tionsviathehardwareinputs.

Modbus input data MPA to master

Input data is information about the state of theMPA.The inputdatacontainadifferentnumberofbytes,dependingon the used data transfer module. The lowerbytesarealwaysthesame,i.e.BasictransferisincludedinStandardtransfer,StandardtransferinExtendedtransfer. AnEBxcontains16bits.

Basic transfer 4 bytesEB0andEB1

Standardtransfer8bytesEB0toEB3

Extended transfer 24 bytesEB0toEB11

Special Extended transfer 42 bytesEB0toEB20

Special Extended-Transfer kurz 21Bytes EB21-EB31Fulluseofthe16Bitregister,contai-ningtheinformationofEB0-EB20

Use the followingFunctionCodes toread this information. 03(0x03)ReadHoldingRegisters01(0x01)ReadCoils.

Page 73: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

73 … 12672 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Basic transfer area

Bit Registration address 0 Description During Fault

0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressure X5 Input for temp. controller Signalofthehardwareinput"Temperaturecontroller" X6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X

8...15 Not used Not used 0

Bit Registration address 1 Description During Fault

0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 04 Temperaturecontroller(hard-

ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification

X

5 not used 06 not used 07 Fault There is a fault in the automatic gas burner control system X

8...15 Not used Not used 0

Bit Registration address 2 Description During Fault

0-7 StatenumberorError code

Currentstatenumber,orincaseoffault,theerrorcodeisincludedhere

X

8...15 Not used Not used 0

Standard transfer area

Bit Registration address 3 Description During Fault

0-7 Flame quality QualityofFlameSignal 08...15 Not used Not used 0

Standard transfer area

Extended transfer area

Bit Registration address 4 Description During Fault

0-7 resettable runtime meter Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X8...15 Not used Not used 0

Page 74: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

75 … 12674 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Registration address 5 Description During Fault

0-7 resettable runtime meter Byte1ofthe32-bitruntimemeter(ins) X

8...15 Not used Not used 0

Bit Registration address 6 Description During Fault

0-7 resettable runtime meter Byte2ofthe32-bitruntimemeter(ins) X

8...15 Not used Not used 0

Bit Registration address 7 Description During Fault

0-7 ResettableRuntimemeter

Highbyte(byte3)ofthe32-bitruntimemeter(ins) X

8...15 Not used Not used 0

Bit Registration address 8 Description During Fault

0-7 ResettableStartcounter

Lowbyte(byte0)ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Registration address 9 Description During Fault

0-7 ResettableStartcounter

Byte1ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Registration address 10 Description During Fault

0-7 ResettableStartcounter

Byte2ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Registration address 11 Description During Fault

0-7 ResettableStartcounter

Highbyte(byte3)ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Registration address 12 Description During Fault

0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0

Bit Registration address 13 Description During Fault

0-7 SwitchingcyclescounterV2 Byte1ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0

Bit Registration address 14 Description During Fault

0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0

Page 75: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

75 … 12674 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Registration address 15 Description During Fault

0-7 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0

Bit Registration address 16 Description During Fault

0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0

Bit Registration address 17 Description During Fault

0-7 RuntimemeterV2 Byte1ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0

Bit Registration address 18 Description During Fault

0-7 RuntimemeterV2 Byte2ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0

Bit Registration address 19 Description During Fault

0-7 RuntimemeterV2 Highbyte(byte3)ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0

Bit Registration address 20 Description During Fault

0-7 Additionalerrorinformation First additional error information byte X8...15 Not used Not used 0

Inthefollowing,theinformationislinkedtoallowthecompleteuseofthe16bitsregister.Query if the bus load is to be reduced.

Bit Registration address 21 Description During Fault

0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressure X5 Input for temperature control-

lerSignalofthehardwareinput"Temperaturecontroller" X

6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X8 Sparkgenerator Ignitionactive X9 Manual mode Manualmodeactive X10 Fan Fan relay on X11 not used 012 Temperaturecontroller(hard-

ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification

X

13 not used 014 not used 015 Fault There is a fault in the automatic gas burner control system X

Page 76: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

77 … 12676 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Registration address 22 Description During Fault

0-7 Statenumberorerrorcode CurrentstatenumberORerrorcodeifthereisafault X8-15 Flame quality Qualityoftheflameoverionisationinput 0

Bit Registration address 23 Description During Fault

0-7 ResettableRuntimemeter

Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X

8-15 ResettableRuntimemeter

Byte1ofthe32-bitruntimemeter(ins) 0

Bit Registration address 24 Description During Fault

0-7 ResettableRuntimemeter

Byte2ofthe32-bitruntimemeter(ins) X

8-15 ResettableRuntimemeter

Highbyte(Byte3)ofthe32–bitruntime meter (ins) X

Bit Registration address 25 Description During Fault

0-7 ResettableStartupcounter

Lowbyte(byte0)ofthe32-bitstart counter X

8-15 ResettableStartupcounter

Byte1ofthe32-bitstartcounter X

Bit Registration address 26 Description During Fault

0-7 ResettableStartupcounter

Byte2ofthe32-bitstartcounter X

8-15 ResettableStartupcounter

Highbyte(Byte3)ofthe32-bitstartcounter X

Bit Registration address 27 Description During Fault

0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitcyclecounterV2 X8-15 SwitchingcyclescounterV2 Byte1ofthe32-bitcyclecounterV2 X

Bit Registration address 28 Description During Fault

0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitcyclecounterV2 X8-15 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitcyclecounterV2 X

Bit Registration address 29 Description During Fault

0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimecounterV2 X8-15 RuntimemeterV2 Byte1ofthe32-bitruntimecounterV2 X

Bit Registration address 30 Description During Fault

0-7 RuntimemeterV2 Byte2ofthe32-bitcounteroperatinghoursV2 X8-15 RuntimemeterV2 Highbyte(byte3)ofthe32-bitcounteroperatinghoursV2 X

Bit Registration address 31 Description During Fault

0-7 Additionalerrorinformation First additional error information byte X8-15 Not used Not used 0

Page 77: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

77 … 12676 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Line lengths

Designation Line length Electrical dataProfibusDP Max.1200m,seeBMAMPA41xx Galvanicallyisolated4kV

Modbus Max.1000m Galvanicallyisolated4kV

Supported baud rates

Profibus

ThefollowingtableisonlyvalidforlinetypeAtoEN50170

Transfer speed kBit/s

9,6 19,2 45,45 93,75 187,5 500 1500 3000 6000 12000

max. line length in m

1200 1200 1200 1200 1000 400 200 100 100 100

Modbus

9600bauds,19200bauds,19200baudsand57600bauds

The baud rate can be changed during operation by means of the Function-Code0x41andispermanentlysavedintheslave.Therelativeparitybitcanalsobedefined.None,EvenandOddaresupported.Defaultvalues(upondelivery)are19200baudsandEvenParity.

1.1 Pin assignment (M12–5 B-coded)MPA 411x MPA 4122

Pin no. Signal1 +5Vsupplyforbustermination2 Datalineminus(Aconductor)3 Earth4 Datalineplus(Bconductor)5 not used

Thread Shielding(earthconnection)recommended

Pin Socket

1

2

3

4

3

1

2 4

5 5

Shutter

VCC A B 2 1

Bus�IN/OUT

Bus termination

Aterminationresistorisrequiredonthefirstandthelastdeviceofthebusstructure.Alternativelytointernaltermination(above),anexternalbusterminationresistor can be connected instead of another bus cable.

The bus cable shielding is to be con-nectedtoPEtoavoidelectromag-netic radiation.

Page 78: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

79 … 12678 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Flame detector device test for UV4x EM shutterTheEM2/4moduleincludesanacti-vationfortheUV4x/shutter.TheuseoftheUV4X/shutterallowstouseanUVflamedetectordeviceUV41(HE)andUV42suitableforcontinuous operation.The shutter signal can also be used for continuous operation of one or moreFLW41Iflamedetectordevice(s).

The control signal is independent from the use of the bus interface.

Connection:

Supply voltage:

24VDC

Current:

Max.200mA

Shutter frequency:

1shuttersignal/10minutes,thefrequencyisnotadjustable.

Parameter setting:

Theshuttersignalisturnedon/offbymeansoftheP21parameter(param-eter„h“inthedisplay).

+-24VDC

Page 79: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

79 … 12678 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Extension module MPA 41xx EM 2/6

The multifunctional extension module EM2/6includesthefollowingfunc-tions:

-Relayoutputsasafunctionofstate-PWMoutputforspeedcontrolofDCfanswithpowerinputbyaPWMsignal

-Voltageoutput0..10V-Currentoutput4..20mA-Profibusinterface- Modbus interface-OutputforactivationoftheEM1/1

shutter module or the continuous operationfunctionoftheFLW41l.

FortheEM2/6MPA411x,art.no.260751theseparatelyavailablemountingbaseMPA411xWB,art.no.261374isrequired.

TheEM2/6forMPA412x,art.no.260903ismountedinthemetalhousing.

Attention

ThemountingoftheEM2/6modulesmustonlytakeplacebyDUNGSorbythirdpartiesauthorisedbyDungs.

Functions

Relay outputs as a function of state:

Asafunctionoftheprogramstate,the relay contacts are closed or opened.Theexternallyappliedvolt-age is switched to random consum-ers.

Application-Signallingofoperationalstates-Activationofanalogueactuators

Byusinganalogueactuators,twoposition messages can be reported totheEM2/6.

PWM signal for activation, for ex-ample, of speed-controlled fans.

ThePWMsignalcanbemodulatedduring the "operation" state by apply-ingamainsvoltagesignal.The speed is controlled with no speed feedback.

Analogue output for current / voltage

Thecurrentsignal(4-20mA)orthevoltagesignal(0-10VAC)canbemodulatedbyapplyingamainsvolt-age signal.

Fieldbus communication

ProfibusDPandmodbusinterfaceareintegratedintotheEM2/6exten-sion module.Forthedescription,seepage70ff.EM2/4modul

Flame safeguard, shutter activa-tion for continuous operation.

TheactivationoftheEM1/1shuttermodule,whichisnecessaryforthecontinuousoperationofDUNGSUV4xandFLW41Iflamesafeguards,isintegratedintotheEM2/6(forthedescription,seepage82).

Page 80: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

81 … 12680 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Erro

rPau

se 1 W

aitin

g for h

eatin

g reques

t

Stat

ic sta

te co

ntrol L

DW

Safe

ty ch

ain ch

eck

Wat

chdog lo

adin

g phas

e

Wait

ing fo

r air

press

ure

Exte

rnal

light c

ontrol

Pre-v

entin

g

Pause

2 Pre-ig

nition

First

safe

ty ti

me (

SZA) -

Igniti

on

First

safe

ty ti

me (

SZA) -

Flam

e det

ectio

n

Stab

ilisat

ion fl

ame A

Pause

3 Seco

nd safe

ty ti

me (

SZB)

Seco

nd safe

ty ti

me (

SZB) -

Flam

e det

ectio

n *10

Stab

ilisat

ion fl

ame B

*10

Operat

ion

Pause

4

Post-ve

nting

After-b

urnin

g tim

e *7

Resta

rt pro

tecti

on

Pause

5 (e

nd of p

aram

eter

isatio

n sequen

ce)

Wait

ing fo

r gas

pre

ssure

Safe

ty ch

ain o

pen

820

Stat

e nu

mb

er0

12

34

56

79

1011

1213

1415

1617

1819

2122

2324

25D

isp

lay

Fxx

H1

01

11

11

H2

11

12

H3

22

33

H4

44

H5

D2

D1

P248

P248

P248

*101

*102

*101

"H

igh

Fire

" in

put

*10

3

"Lo

w F

ire"

inp

ut *

103

Inpu

tO

NO

ffEi

ther

"Off

" or

"C

oolin

g m

ode"

*104

"O

ther

" po

sitio

n

Ope

n or

"Oth

er"

posi

tion*

107

Ope

n or

"Oth

er"

posi

tion

*107

"V

entin

g"

or "

Oth

er"

posi

tion

*106

"Pos

t-ve

ntin

g sp

eed"

P243

"Ign

ition

pos

ition

spe

ed"

P241

"Sta

bilis

atio

n sp

eed"

P242

8 1 P30

0..1

h

"Ig

nitio

n" p

ositi

on

20 4 P51

Con

trol

m

ode

P50

*7

0..1

h

"Off

" or

"C

oolin

g m

ode"

*104

Tim

es

Spee

d(P

WM

)"P

re-v

entin

g sp

eed"

P240

"Sw

itch

mod

ulat

ion"

out

put

"

Ven

ting"

pos

ition

"Off

" or

"C

oolin

g m

ode"

*104

*105

"Off

"

Ope

n or

"O

ther

"po

sitio

n *1

07O

pen

*7) T

he a

fter

-bur

ning

tim

e st

arts

alr

eady

in t

he "

Post

-ven

ting"

sta

te. W

hen

the

post

-ven

ting

beco

mes

larg

er o

r eq

ual t

o th

e af

ter-

burn

ing

time,

the

"A

fter

-bur

ning

tim

e" w

ill b

e sk

ippe

d.

*101

) Mon

itori

ng o

f th

e "H

igh

Fire

" in

put

will

not

be

star

ted

until

the

tim

e de

fined

in P

248

has

expi

red.

. *1

02) T

he ig

nitio

n sp

eed

is a

lrea

dy s

et b

efor

e th

e en

d of

the

pre

-ven

ting

time,

thi

s tim

e be

ing

defin

ed in

P24

8. S

tart

ing

from

thi

s m

omen

t, th

e "

Hig

h Fi

re"

inpu

t w

ill n

o lo

nger

be

mon

itore

d.

*103

) Mon

itori

ng o

f th

e "H

igh

Fire

" an

d "L

ow F

ire"

inpu

ts c

an b

e ac

tivat

ed o

r de

activ

ated

via

par

amet

er P

249

. *1

04) P

249,

bits

2+

3 ca

n be

use

d to

def

ine

whe

ther

the

spe

ed is

"O

ffs"

or

whe

ther

the

fan

is w

orki

ng in

coo

ling

mod

e.

*105

) The

sta

rt v

alue

of

the

spee

d, f

ollo

win

g a

soft

war

e re

star

t, is

est

ablis

hed

via

P244

if t

he c

oolin

g m

ode

is a

ctiv

e.

*106

) P24

9 is

use

d to

est

ablis

h w

heth

er t

he "

Ven

ting"

pos

ition

is a

ctiv

ated

als

o du

ring

pos

t-ve

ntin

g.

*107

) P24

9 is

use

d to

est

ablis

h w

heth

er t

he "

Switc

h m

odul

atio

n" is

Ope

n or

con

nect

ed t

o th

e "

Oth

er"

inpu

t.

SCH

M /

TST,

09.

10.2

012

ce)

Flow

cha

rt "

EM 2

/6"

Page 81: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

81 … 12680 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4Outputs*Designation Safety-

relatedType of output Line length Electrical data

Fanactivation PWM4kHz,wit-hout detection of speed feedback

Max.10m 24VDC,safetyextralowvoltage(3lines:GND,+24VDC,PWMcontrol signal

Frequency con-verteractivation

0...10V4...20mA

Max.10m 10VDC,safetyextralowvoltage

Activationofshutter

Switchingcontact

Max.100m 24VDC,safetyextralowvoltage

Technical data

Inputs*Designation Type of input Line length Electrical data"HighFire"feedback Switchingcontact Max.100m 115/230VAC"LowFire"feedback Switchingcontact Max.100m 115/230VACPower+ Switchingcontact Max.100m 115/230VACPower- Switchingcontact Max.100m 115/230VAC

Other functions*Designation Type of input Line length Electrical dataSwitchforoption:0...10V,4…20mAorPWMoutput

Switch Plastichousing:Canonlybeswitchedoverwiththeextensionmodule dismounted.Metalhousing:No dismounting requiredAttention:Switchoveronlyin de-energised state

MODBUSinterface MODBUSbasedonRS485 Max.1000m RS485galvanicallyisolated4kVDIPswitchterminatingresistorsMODBUS

DIPswitch Foractivationordeactivation ofRS485terminatingresistors(MODBUS)

ProfibusDP Max.1200m Galvanicallyisolated4kV

* The connection cables used must be suitable for an ambient temperature of at least 75 °C (167 °F)

Page 82: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

83 … 12682 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Connector 1 (analogue On/Off 115 VAC / 230 VAC)

1:COM2:"HighFire"switchingposition3:"LowFire"switchingposition4:Automaticswitchingposition

Connector 2 (115 VAC / 230 VAC inputs)

6:N7:"LowFire"feedback8:"HighFire"feedback9:Power-10:Power+

Connector 3 (analogue out)

PWMoutput(connectorbottom)12:DGND13:PWM14:VCCout(10.5...24VDC)

Analogueoutput0...10V(switchcentre)12:DGND13:Analogueoutput0…10V14:10Vout

Analogueoutput4...20mA(switchtop)12:DGND13:Analogueoutput4...20mA14:VCCout(10.5...24VDC)

Connector 4 (bus und shutter):

16:GND/shutter-17:VCC5V(forboosterminimisation)18:B(red)19:A(green)20:GNDshutter+

Pin assignment

 

1 2 3

Switch position analogue output 4...20 mA switch top0...10 V switch centrePWM switch bottom

4

1 2 3 6 7 8 9 10 12 13 14 16 17 18 19 20

GN

D

A(grün/green)

VCC

N High Fire

Low Fire

4

260806

Comm

on

Pro�bus/Modbus

Page 83: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

83 … 12682 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Parameters

All"speed"valuesorthelikerefertothePWMcontrolsignalandhavenosignificancefortheactualspeedofthe fan.

ThevaluesP240toP244canbechangedafterentryofapassword,dependingontheaccesslevel.Readingaccessispossibleforallparameters,independentlyoftheac-cesslevel.ParametersP245toP249canbechanged without password.

ParameterscanbechangedviatheVisionBoxorthedisplayoftheMPA41x2.

Changed parameters are applied to thefancontrolafternolaterthan10s.

Overview of the fan control parametersVisionBox No. Display No. Name Meaning240 Pr0 RESERVIERT_OEM_0 Pre-venting241 Pr1 RESERVIERT_OEM_1 Ignition position242 Pr2 RESERVIERT_OEM_2 Stabilisation243 Pr3 RESERVIERT_OEM_3 Post-venting244 Pr4 RESERVIERT_OEM_4 Startvalue245 Pr5 RESERVIERT_BETREIBER_0 Min. speed246 Pr6 RESERVIERT_BETREIBER_0 Max. speed247 Pr7 RESERVIERT_BETREIBER_2 Increment248 Pr8 RESERVIERT_BETREIBER_3 Transitiontime(whenstartingpre-and

post-ventingandbeforetheendofpre-venting)

249 Pr9 RESERVIERT_BETREIBER_4 Bit functions (seedescriptionP249)

Page 84: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

85 … 12684 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParameterParameter description

Parameter Designation Description Setting / Examples

P240 Pre-venting / Activa-tion of the extension module

Theparametervalueisusedforstates5-8(starttopre-venting)oftheMPA41xx,itbeingpossibleforstate8(pre-venting)tobedivided,seeP248.RefersdirectlytothePWMcontrolsignal.

Settingfrom0.01%to100.00%*1Resolution:0.01%If the parameter has been set to >0,anextensionmodulemusthavebeenconnectedtothemainboard.Thispreventsoperationwithout an extension module by generatinganerror(0x18,seechapter10Erroroverview).Setting0:IftheEMisconnectedtotheMPA,anerrorwillbegener-ated(0x18,Erroroverview).

P241 Ignition position Theparametervalueisusedforstates8-14(ignitionandflamedetec-tion)oftheMPA41xx,itbeingpos-sibleforstate8(pre-venting)tobedivided,seeP248.RefersdirectlytothePWMcontrolsignal.

Adjustablefrom0.00%to100.00%*1Resolution:0,01%

P242 Stabilisation Theparametervalueisusedforstates15-17(secondsafetytime(SZB)andstabilisationB)oftheMPA41xx.RefersdirectlytothePWMcontrolsignal.

Adjustablefrom0.00%to100.00%*1Resolution:0.01%

P243 Post-venting Theparametervalueisusedforstate20(post-venting)oftheMPA41xx.RefersdirectlytothePWMcontrolsignal.

Adjustablefrom0.00%to100.00%*1Resolution:0.01%

P244 Start value IftheMPAisstartedbyMainsOn,thisvaluewillbeusedasstartvalue.IftheMPAchangestooneofstates21to25(after-burntimetosafetychainopen),andthecurrentspeedis0,itisstartedagainfromthestartvalue.IftheMPAchangestostate1or2(e.g.,duetocancellingtheheatrequest),andthecurrentspeedis0,itisstartedagainfromthestartvalue.RefersdirectlytothePWMcontrolsignal.

Adjustablefrom0.00%to100.00%*1Resolution:0.01%

P245 Minimum speed Minimumspeed,controlwillnotoutputasmallervalue.Allparam-etervaluesofthefancontrolmustbeaboveoratthislimit.RefersdirectlytothePWMcontrolsignal.

Adjustablefrom0.00%to100.00%Resolution:0.01%

P246 Maximum speed Maximumspeed,controlwillnotoutputalargervalue.Allparametervaluesofthefancontrolmustbebelow or at this limit.RefersdirectlytothePWMcontrolsignal.

Adjustablefrom0.00%to100.00%Resolution:0.01%

Page 85: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

85 … 12684 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

ParameterParameter description

Parameter Designation Description Setting / Examples

P247 Increment of speed change

Indicatesthevaluebywhichthedesired speed of the fan is in-cremented or decremented. The calculationiscarriedout16timespersecond,i.e.,thevalueoftheparameter is added to or subtract-edfromthecurrentvalueinthe1/16scycle.Theincrementinthetables is used for certain positions oftheinputs,seeD+andD-.

Adjustablefrom0.01%to100.00%Resolution:0,01%Calculation of the time based on the incrementTime[in1/16]=(Max[in%]-Min[in%])/Increment[in%]

Calculationoftheincrement(con-tentsP247)P247[in0.01%]=((Max[in%]-Min[in%])/(Time[ins]*16))*100

Examples:IncrementP247=40(=0.4%per1/16s)requires12.5sofminspeed=20%tomaxspeed100%.Longesttimefrom0to100%atincrementP247=1is625s.

P248 Transition time to ignition speed

Theparametervalueisusedforstate8(pre-venting)oftheMPA41xx.Indicatesatwhichtimethefanismovedtotheignitionposition.Thevaluecorrespondsto the time before the end of pre-venting(remainingpre-ventingstatetime).NOTE:MustnotbegreaterthantheP30pre-ventingtime,otherwisefaultconfigurationwith restart will be carried out.State8(pre-venting)isdividedinto3partsP248+x+P248=P30(xmustbegreaterthan1ifmonitoringisactive).AfterthefirstHighFiretime(P248):State20(post-venting)P248+x=P51(xmustbegreaterthan1ifmonitoringisactive).ThecontrolofparametersP248,P30andP50takesplaceduringthewatchdogloadingphase.Dur-ingchangesinoperation(param-eternotmonitored),Low/HighFiremonitoringcanbedisabledifP248≤P50.

Adjustablefrom0to1h.Resolution:1/16s

Page 86: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

87 … 12686 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

P249 bit functionsTheparameterincludesthePWM/analogueswitchover,theidlestatecontrol of both air pressure switches LDWLow/LDWHighandarampfunction(desiredvaluedelay).

The output of the correct signal depends on the switch position (centre=voltageoutputsignal),(bottom=PWMoutputsignal),whichmust be identical to the setting of this parameter.

The parameter is divided into 16 bits:Bit 0Setting0:PWMoutput.SetslideswitchtoPWMoutput(bot-tomposition).

Setting1:Analogueoutput.Setslideswitchtovoltage(centreposition)orcurrent(topposition).Allparametervaluesin%arenowconvertedtotheoutputoftheana-loguevalue.

Example:Apost-ventingparameterof6000gives6Vattheanalogueoutput,etc.

Bit 1Setting0:Voltageoutputactive0..10VSetting1:Currentoutputactive4..20mA

Bits 2+3:Setting0:DuringstandbyandfaultPWM=0Setting1:DuringstandbyandfaultPWM=power+/-Setting2:DuringstandbyandfaultPWM=power+/-Setting3:Errorconfiguration

Bit 4Setting0:Allrelayoutputsopen(WO)Setting1:Relay1(automaticclosed)

Bit 5Setting1:HighFireinputcontroldur-ingpre-ventingtime

Bit 6Setting1:LowFireinputcontroldur-ing ignition and stabilisation time

Bit 7 HighFireinputcontrolduringpost-ventingtime

Bit 8Setting1:HighFirerelay3closedBit 9Bit 10Bit 11Bit 12Bit 13

Theramp(desiredvaluedelay)oftheoutputsignalisactiveduringeachchangeinspeed.TheMoreHeat/LessHeatinputshavepriorityiftheyareactive.

Bit 14Reserved:Setting0

Bit 15Reserved:Setting0

} 5-bitvalue

Page 87: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

87 … 12686 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

45-bit value Duration in s

Example: if change is from 0 % to 100 %0 Jump1 3,1252 6,2503 9,3754 12,55 15,6256 18,757 21,8758 259 28,12510 31,2511 34,37512 37,513 40,62514 43,7515 46,87516 5017 53,12518 56,2519 59,37520 62,521 65,62522 68,7523 71,87524 7525 78,12526 81,2527 84,37528 87,529 90,62530 93,7531 96,875

Formulaforrampcalculation:Duration=|(olddesiredvalue-newdesiredvalue)|*5-bitvalue*1s/16

Example:

Changefrom0to100%,5-bitvalue31100%/2%*31/16s=97s

Calculation as ramp

Page 88: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

89 … 12688 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Fieldbus communicationProfibus DP

ForProfibussetting,termination,technicaldata,seepage70ff.EM2/4modul

Profibus input data MPA to master

Input data is information about the stateoftheMPA.Theinputdatacon-tainadifferentnumberofbytes,de-pending on the data transfer module used. The lower bytes are always the same,i.e.BasictransferisincludedinStandardtransfer,Standardtransferin Extended transfer.

Basic transfer 2 bytes EB0andEB1

Standardtransfer7bytesEB0toEB6

Extendedtransfer15bytesEB0toEB14

SpecialExtendedtransfer25bytesEB0toEB24

ThebytesEB0andEB1containbitinformation.Ifthebitissetto1,theconditionisincluded in the description of the bits.Somebitsareactiveduringthefault(markedwith"X"),othersare0.

Page 89: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

89 … 12688 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Basic transfer areaMPA 41xxBit Input byte EB0 Description During fault0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressureavailable X

5 Input for temperature controller

Signalofthehardwareinput"Temperaturecontroller" X

6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X

Bit Input byte EB4 Description During fault0 MoreHeat HWinputstate X1 LessHeat HWinputstate X2 HighFire HWinputstate X3 LowFire HWinputstate X

4Warningmessage:MoreandLessHeat

simultaneously

TheinputsforHeat+andHeat-aresimultaneouslyactive X

5 not used 0

6 not used 07 not used 0

Standard transfer areaBit Input byte EB2 Description During fault

0-7 Statenumberorerrorcode

Current state number or error code if there is a fault X

Bit Input byte EB3 Description During fault0-7 Flame quality Qualityoftheflameviaionisationinput 0

Bit Input byte EB1 Description During fault0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 0

4 Temperature control-ler(HW+BUS)

Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification

X

5 not used 0

6 not used 07 Fault There is a fault in the automatic gas burner control system X

Page 90: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

91 … 12690 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Input byte EB8 Description During fault

0-7 Resettableruntime meter

Byte1ofthe32-bitruntimemeter(Unit:s)

X

Bit Input byte EB9 Description During fault

0-7 Resettableruntime meter

Byte2ofthe32-bitruntimemeter(Unit:s)

X

Bit Input byte EB10 Description During fault

0-7 Resettableruntime meter

Highbyte(byte3)ofthe32-bitruntimemeter(Unit:s)

X

Bit Input byte EB11 Description During fault

0-7 Resettablestart counter

Lowbyte(byte0)ofthe32-bitstartcounter X

Bit Input byte EB12 Description During fault

0-7 Resettablestart counter

Byte1ofthe32-bitstartcounter X

Bit Input byte EB13 Description During fault

0-7 Resettablestart counter

Byte2ofthe32-bitstartcounter X

Bit Input byte EB14 Description During fault

0-7 Resettablestart counter

Highbyte(byte3)ofthe32-bitstartcounter X

Extended transfer areaMPA 41xxBit Input byte EB7 Description During fault

0-7 Resettableruntime meter

Lowbyte(byte0)ofthe32-bitruntimemeter(Unit:s)

X

Bit Input byte EB5 Description During fault0 Relaymatrixoutput

(2-bit)00=Off

01=Relay110=Relay211=Relay3

X

1

X

2Warning:Low/HighFire simultaneously

on

X

3 not used 04 not used 05 not used 0

6 not used 07 not used 0

Bit Input byte EB6 Description During faultDegreeofmodulation

in%

Page 91: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

91 … 12690 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Input byte EB16 Description During fault

0-7 SwitchingcyclescounterV2

Byte1ofthe32-bitswitchingcyclescounterV2 X

Bit Input byte EB17 Description During fault

0-7 SwitchingcyclescounterV2

Byte2ofthe32-bitswitchingcyclescounterV2 X

Bit Input byte EB18 Description During fault

0-7 SwitchingcyclescounterV2

Highbyte(byte3)ofthe32-bitswitchingcyclescounterV2 X

Bit Input byte EB19 Description During fault

0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimemeterV2(Unit:s)

X

Bit Input byte EB20 Description During fault

0-7 RuntimemeterV2 Byte1ofthe32-bitruntimemeterV2(Unit:s)

X

Bit Input byte EB21 Description During fault

0-7 RuntimemeterV2 Byte2ofthe32-bitruntimemeterV2(Unit:s)

X

Bit Input byte EB22 Description During fault

0-7 RuntimemeterV2 Highbyte(byte3)ofthe32-bitruntimemeterV2(Unit:s)

X

Special Extended transfer areaMPA 41xxBit Input byte EB15 Description During fault

0-7 SwitchingcyclescounterV2

Lowbyte(byte0)ofthe32-bitswitchingcyclecounterV2 X

Bit Input byte EB23 Description During fault0-7 Erroradditionalinfo1 First additional error info byte X

Bit Input byte EB24 Description During fault0-7 Error additional info 4 Fourth additional error info byte X

Page 92: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

93 … 12692 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Byte0Bit OutputbyteAB00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestviabus)7 Reserve(pleasesetto0)

Output data of the master to MPA

Byte10 ControlbitbusinputsActivateMore/LessHeat1 MoreHeat2 LessHeat3 Not used4 Not used5 Not used6 Not used7 Not used

Byte 20 Not used1 Not used2 Not used3 Not used4 Not used5 Not used6 Not used7 Not used

Transfer areas:A:nobytes

B:1byte

C:3bytes

Page 93: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

93 … 12692 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

FieldbusModbusForModbussetting,termination,technicaldata,seepage70ff.EM2/4modul

Modbus input dataUsethefollowingFunctionCodestoreadthisinformation:03(0x03)ReadHoldingRegisters01(0x01)ReadCoils

Page 94: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

95 … 12694 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Basic transfer area

Bit Register address 0 Description During fault0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressureavailable X5 Input for temperature control-

lerSignalofthehardwareinput"Temperaturecontroller" X

6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X

8...15 Not used Not used 0Bit Register address 1 Description During fault0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 04 Temperaturecontroller(hard-

ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification

X

5 not used 06 not used 07 Fault There is a fault in the automatic gas burner control system X

8...15 Not used Not used 0

Bit Register address 2 Description During fault0-7 Statenumberorerrorcode CurrentstatenumberORerrorcodeifthereisafault X8...15 Not used Not used 0

Standard transfer area

Bit Register address 3 Description During fault0-7 Flame quality 08...15 Not used Not used 0

Standard transfer area

Bit Register address 4 Description During fault0 MoreHeat HWinputstate X1 LessHeat HWinputstate X2 HighFire HWinputstate X3 LowFire HWinputstate X4 Warningmessage:MoreHeat/

LessHeatsimultaneouslyonX

5 Not used 06 Not used 07 Not used 0

8...15 Not used 0

Page 95: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

95 … 12694 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Extended transfer area

Bit Registration address 7 Description During fault

0-7 Resettableruntimemeter Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X8...15 Not used Not used 0

Bit Register address 5 Description During fault

0 0..1or8..9:outputstateswitchmodulation(2-bit):0=Off,01=Relay1,10=Relay2,11=Relay3

X1 X

2 Warningmessage:LowFire/HighFiresimultaneouslyon

X

3 Not used 04 Not used 05 Not used 06 Not used 07 Not used 0

8...15 Not used 0

Bit Register address 6 Description During fault

0-15 Degreeofmodulationin% X

Bit Register address 8 Description During fault

0-7 Resettableruntimemeter Byte1ofthe32-bitruntimemeter(ins) X

8...15 Not used Not used 0Bit Register address 9 Description During

fault0-7 Resettableruntimemeter Byte2ofthe32-bitruntimemeter(ins) X

8...15 Not used Not used 0Bit Register address 10 Description During

fault0-7 Resettable

runtime meterHighbyte(byte3)ofthe32-bitruntimemeter(ins) X

8...15 Not used Not used 0

Page 96: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

97 … 12696 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 11 Description During fault

0-7 Resettablestart counter

Lowbyte(byte0)ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Register address 12 Description During fault

0-7 Resettablestart counter

Byte1ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Register address 13 Description During fault

0-7 Resettablestart counter

Byte2ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Register address 14 Description During fault

0-7 Resettablestart counter

Highbyte(byte3)ofthe32-bitstartcounter X

8...15 Not used Not used 0

Bit Register address 15 Description During fault

0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitswitchingcyclecounterV2 X8...15 Not used Not used 0

Bit Register address 16 Description During fault

0-7 SwitchingcyclescounterV2 Byte1ofthe32-bitswitchingcyclescounterV2 X8...15 Not used Not used 0

Bit Register address 17 Description During fault

0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitswitchingcyclescounterV2 X8...15 Not used Not used 0

Bit Register address 18 Description During fault

0-7 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitswitchingcyclescounterV2 X8...15 Not used Not used 0

Extended transfer area

Page 97: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

97 … 12696 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 19 Description During fault

0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0

Bit Register address 20 Description During fault

0-7 RuntimemeterV2 Byte1ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0

Bit Register address 21 Description During fault

0-7 RuntimemeterV2 Byte2ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0

Bit Register address 22 Description During fault

0-7 RuntimemeterV2 Highbyte(byte3)ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0

Bit Register address 23 Description During fault

0-7 Additionalerrorinfo1 First additional error information byte X8...15 Not used Not used 0

Inthefollowing,theinformationislinkedtoallowcompleteuseofthe16-bitregister.Query if the bus load is to be reduced.

Bit Register address 25 Description During fault

0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressureavailable X5 Input for temperature control-

lerSignalofthehardwareinput"Temperaturecontroller" X

6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X8 Sparkgenerator Ignitionactive X9 Manual mode Manualmodeactive X10 Fan Fan relay on X11 not used 012 Temperaturecontroller(hard-

ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification

X

13 not used 014 not used 015 Fault There is a fault in the automatic gas burner control system X

Bit Register address 24 Description During fault

0-7 Additionalerrorinfo4 Fourth additional error info byte X8...15 Not used Not used 0

Page 98: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

99 … 12698 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 26 Description During fault

0-7 Statenumberorerrorcode CurrentstatenumberORerrorcodeifthereisafault X8-15 Flame quality Qualityoftheflameviaionisationinput 0

Bit Register address 27 Description During fault

0 Heatplus HWinputstate X1 Heatminus HWinputstate X2 HighFire HWinputstate X3 LowFire HWinputstate X4 Warningmessage:Powerplus

and minus simultaneously onX

5 Not used X6 Not used X7 Not used X

8..9 Output state switch modulati-on(2-bit):0=Off,01=Relay1,10=Relay2,11=Relay3

X

10 Warningmessage:LowandHighFiresimultaneouslyon

X

11 Not used 012 Not used 013 Not used 014 Not used 015 Not used 0

Bit Register address 28 Description During fault

0-15 Degreeofmodulationin% X

Page 99: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

99 … 12698 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 29 Description During fault

0-7 Resettableruntime meter

Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X

8-15 Resettableruntime meter

Byte1ofthe32-bitruntimemeter(ins) X

Bit Register address 30 Description During fault

0-7 Resettableruntime meter

Byte2ofthe32-bitruntimemeter(ins) X

8-15 Resettableruntime meter

Highbyte(byte3)ofthe32-bitruntimemeter(ins) X

Bit Register address 31 Description During fault

0-7 Resettablestart counter

Lowbyte(byte0)ofthe32-bitstartcounter X

8-15 Resettablestart counter

Byte1ofthe32-bitstartcounter X

Bit Register address 32 Description During fault

0-7 Resettablestart counter

Byte2ofthe32-bitstartcounter X

8-15 Resettablestart counter

Byte3ofthe32-bitstartcounter X

Bit Register address 33 Description During fault

0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitswitchingcyclecounterV2 X8-15 SwitchingcyclescounterV2 Byte1ofthe32-bitswitchingcyclescounterV2 X

Bit Register address 34 Description During fault

0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitswitchingcyclescounterV2 X8-15 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitswitchingcyclescounterV2 X

Bit Register address 35 Description During fault

0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimemeterV2(ins) X8-15 RuntimemeterV2 Byte1ofthe32-bitruntimemeterV2(ins) X

Bit Register address 36 Description During fault

0-7 RuntimemeterV2 Byte2ofthe32-bitruntimemeterV2(ins) X8-15 RuntimemeterV2 Highbyte(byte3)ofthe32-bitruntimemeterV2(ins) X

Bit Register address 37 Description During fault

0-7 Additionalerrorinfo1 First additional error info byte X8-15 Additionalerrorinfo4 Fourth additional error info byte X

Page 100: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

101 … 126100 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 38 Description During fault

0-7 Lowbyte:LSByteoftheu24articlenumberSWP1 X8-15 Highbyte:u24articlenumberSWP1 X

Bit Register address 39 Description During fault

0-7 Lowbyte:MSByteoftheu24articlenumberSWP1

X

8-15 Highbyte:indexarticlenumberSWP1 XBit Register address 40 Description During

fault0-7 Lowbyte:dayproductionMPA X8-15 Highbyte:monthproductionMPA X

Bit Register address 41 Description During fault

0-7 Lowbyte:yearproductionMPA X8-15 Highbyte:notused X

Bit Register address 42 Description During fault

0-7 Lowbyte:LSByteoftheu32devicenumberMPA X8-15 Highbyte:u32devicenumberMPA X

Bit Register address 43 Description During fault

0-7 Lowbyte:u32devicenumberMPA X8-15 Highbyte:MSByteoftheu32devicenumberMPA X

Bit Register address 44 Description During fault

0-7 Lowbyte:LSByteoftheu24articlenumberHW X8-15 Highbyte:u24articlenumberHW X

Bit Register address 45 Description During fault

0-7 Lowbyte:MSByteoftheu24articlenumberHW X8-15 Highbyte:indexarticlenumberHW X

Bit Register address 46 Description During fault

0-7 Lowbyte:LSByteoftheu24articlenumberdevice X8-15 Highbyte:u24articlenumberdevice X

Bit Register address 47 Description During fault

0-7 Lowbyte:MSByteoftheu24articlenumberdevice X8-15 Highbyte:indexarticlenumberdevice X

Bit Register address 48 Description During fault

0-7 Lowbyte:LSByteoftheu24articlenumberSWEM X8-15 Highbyte:u24articlenumberSWEM X

Page 101: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

101 … 126100 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 49 Description During fault

0-7 Lowbyte:MSByteoftheu24articlenumberSWEM X8-15 Highbyte:indexarticlenumberSWEM X

Bit Register address 50 Description During fault

0-7 Lowbyte:dayofEMproduction X8-15 Highbyte:monthproductionEM X

Bit Register address 51 Description During fault

0-7 Lowbyte:yearproductionEM X8-15 Highbyte:notusednotused X

Bit Register address 52 Description During fault

0-7 Lowbyte:LSByteoftheu32devicenumberEM X8-15 Highbyte:u32devicenumberEM X

Bit Register address 53 Description During fault

0-7 Lowbyte:u32devicenumberEM X8-15 Highbyte:MSByteoftheu32devicenumberEM 0

Bit Register address 54 Description During fault

0-7 Lowbyte:LSByteoftheu24articlenumberHW-EM X8-15 Highbyte:u24articlenumberHW-EM X

Bit Register address 55 Description During fault

0-7 Lowbyte:MSByteoftheu24articlenumberHW-EM X8-15 Highbyte:indexarticlenumberHW-EM X

Bit Register address 56 Description During fault

0-7 Lowbyte:LSByteoftheu24articlenumberdeviceEM X8-15 Highbyte:u24articlenumberdeviceEM X

Bit Register address 57 Description During fault

0-7 Lowbyte:MSByteoftheu24articlenumberdeviceEM X8-15 Highbyte:indexarticlenumberdeviceEM X

Page 102: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

103 … 126102 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Bit Register address 00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestvia

bus)7 Not used8 ActivateBusControlHeat+/-9 Heat+10 Heat-11 Not used12 Not used13 Not used14 Not used15 Not used

Bit Register address 10-15 Not used

Bit Register address 00 HWinputstatemoreheat1 HWinputstatelessheat2 HWinputstateHighFire3 HWinputstateLowFire4 Not used5 Not used6 Not used7 Not used8 Bits8..15:notused

Output dataUsethefollowingFunctionCodestowritethesespecifications.

05(0x05)WriteSingleCoil(Coil=bitatbitaddressx)06(0x06)WriteSingleRegister(toregisteraddress)16(0x10)WriteSingleRegister(fromregisteraddress)

Digital inputsUsethefollowingFunctionCodestoread this information. 04(x04)ReadInputRegisters02(0x02)ReadDiscreteInputsThis information is contained in the inputdata(seeabove).

Page 103: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

103 … 126102 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Error overviewErrorID

Internalerror

Error description

0x18

Error in external applicationCausesoftheerror:• Additional byte 1: 0xB4 (error in VisionBox) Switch-offwascausedexternally,forexamplebyselectingthe "switch-off"functioninthePCsoftwareoftheVisionBox

• Additional byte 1: 0x90 (internal MPA error P2) Additionalbyte4:0xA0timeoutparameterizationmode Additionalbyte4:0xA1invalidbusaddress Additionalbyte4:0xA2parameteradjustmenterroroftheservicecase Additionalbyte4:0xA3anti-oscillationfunctionshuttererror Additionalbyte4:0xA4extensionmoduletest(P240>0andnoEMconnected)

• Additional byte 1 0xC2 (extension module error) Additionalbyte4:0xE0parametererror(parameteroutsidethelimits) Additionalbyte4:0xE1/0xE2calibrationvaluenotsetinEEPROMornotOK Additionalbyte4:0xE3reserved Additionalbyte4:0xE4HighFireSignalmissingduringpre-venting Additionalbyte4:error0xE5configuration: -ParameterP249oneormorebitswithoutfunction -Pre-orpost-ventingtimetooshortforP248 Additionalbyte4:0xE6errorconfiguration: -P248<16(1s) -P30-2*P248<16(1s) -P51-P248<16(1s) Additionalbyte4:0xE7reserved Additionalbyte4:0xE8EM2/6notrecognized(P240=0,EM2/6connected) Additionalbyte4:0xE9wrongsignalLowFireduringignitionandstabilisation Additionalbyte4:0xEAwrongsignalHighFireduringpost-ventingtime Additionalbyte4:0xEFadditionalmodulenotcompatiblewithMPAversion

xx Forothererrors,seepage56ff.

Error displayThe error information can be displa-yedviatheMPAdisplay,theDUNGSvisionboxorviathefieldbus.

Errordisplayondisplay:seepage44

Page 104: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

105 … 126104 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Dimensions of plug-in base

190

165

151,

5

170

122

4,5 mm

x1MPA

x2EM2/6

Page 105: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

105 … 126104 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Flame detector

RequestsforoperationbyseparateflamedetectorsonMPA41xx:

Theflamedetectorsmustbetestedandapprovedformonitoringgasburners.

The reaction times must be ob-served!

Totalreactiontime=reactiontimeMPA+reactiontimeflamedetectorAproofaboutthecompliancewiththerequirementsofEN298isre-quired.

Thereactiontimeafteraflamelift-offofanexternalflamedetectormaynotbelongerthanthefirstorsecondstart-gasflameprovingperiod.WhenconnectedtoFLW1,theioni-sationbehaviourofaflamemustbesimulated(rectifiereffect).Thefollow-ingvaluesareactiveontheionisationinputandoutputoftheMPA:230VAC+10%-15%.TheinternalresistanceoftheMPAisapprox1MΩ.Forsafetyreasons,theflamesensormustworkproperlyalsowithaninternalresistanceof360kΩ.Undertheseconditions,thesimula-tioncircuitintheflamedetectormustreachatleastadirectcurrent3µA.IfanalternatingcurrentwithaDCcomponentissimulated,theDCcom-ponentshouldreachatleast25%.ThecurrentcanbederivedtoN,PEorreturnedtoNontheMPA.WhenconnectedtoFLW2,theswitchingoutputofasuitableflamedetectormustbeconnectedtoFLW2NO(115VACor230VAC).Forcontinuousoperation,FLW2NCmustalsobeconnected(EXORsignal).Theselectedflamedetectormustalsobecertifiedforcontinuousoperation.Alternatively,aflamede-tectorforintermittentoperation(onlyFLW2NO)maybeusedincombina-tionwithaDUNGSshutterincontinu-ous operation.The EMC regulations must be ob-served(EN298).Theentiresystemmust not produce inadmissible emis-sions. MPA41xxisnotgalvanicallyisolated.MPA41xxandtheflamedetectormust be connected according to the correct phase.

Attention: DUNGScannotbeheldliableiftheflamedetectorandtheautomaticburner control do not work orderly together. Especially if the electromag-neticbehaviourisnotaccordingtothe regulations or if the time-depend-entbehaviourisnotcorrect.

Thequalityoftheflamesignalisdis-playedforflameguard1asanumberbetween0and58.Evaluationoftheflamesignalisonlypossiblewithionisationflamemoni-toring,alsobymonitoringwithUV41(HE).WhenusingtheUV42,FLW10IRorFLW20UV,themaximumvalueisalways displayed.

25

ION

/ μA

20

15

10

5

0

10 20 30 40 50 60

ION vs. digits MPA41

digits

Page 106: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

107 … 126106 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Manufac-turer

Designa-tion

Type Output signal

Safety timeFlame de-tector

Total reac-tion time after flame lift-off

Intermittent

Continu-ousoperation

– Ionisation electrode

Ionisation Ionisation 0s P41 Yes Yes

DUNGS UV41(HE)

UVtube Ionisation 0.125s(=2/16s)

P41+0.125s Yes Continuous operation only to-gether with DUNGSshutter function

DUNGS UV42

UVtube Switchingoutput 230VAC

0.125s(=2/16s)

P41+0.125s Yes Continuous operation only to-gether with DUNGSshutter function

DUNGS FLW20 UVtube Ionisation 0.5s P41+0.5s Yes No

DUNGS FLW10

Flicker de-tectorwith fre-quency analysis

Ionisation 0.5s P41+0.5s Yes No

DUNGS FLW41I

Ionisation Switchingoutput 230VAC

0,19s(=3/16s)

P41+0,19s Yes Continuous operation only in con-nection with DUNGSshutter signal(e.g.EM2/4)

Flame detectors tested and authorised by DUNGS:

FlamedetectorsthatarenotincludedinthislistmustbeauthorisedbeforeusebyDUNGS

Page 107: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

107 … 126106 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

M16x1,5

94 ø44,5

ø 42

UV 41 (HE)TheUV41isaflamedetectorwithUVtubeinmetaldesignforhighme-chanical stress.TheflamedetectorisconnectedtotheionisationinputoftheMPA41xxand is suitable for intermittent opera-tion.For use in continuous operation applications,theUV4xshutterisad-ditionally required.TheadapterUV4x-EM1/xmustbeusedformountingtheUV41.Other mounting adapters upon re-quest.

Technical Data

Dimensions

UV41(HE)

UV4xEM1/xadapter

UV 41 GeneralRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <1WType of protection IP54Ambienttemperature -40°C...+60°C

-40°C...+80°CwithreducedlifetimeoftheUVtubeStorageandtransport -40°C...+80°Cmaximumstoragetimewithoutpowersupply:3monthHumidity DIN60730-1,nodewingadmissibleLifetime 10,000operatinghours(Ausführung(HE)verminderteLebensdauer)Mounting position as desiredDimensionsinmm Diameter:44.5mm

Length:94mmLengthwithUV4x-EM1:approx.128-143mm

Max. line length 10m

39,5

28,5

50

50

36

50

3628,5

G1/8"

EM1/3 EM1/4EM1/6

EM1/5EM1/7

EM1/8EM1/9

1/4"NPT 1/2"

NPT

G1/8" G3/4"

Page 108: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

109 … 126108 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

G

G

G

G

L (PIN3)

L (PIN3)

N�(PIN2)

N�(PIN2)

O�(PIN1)

O�(PIN1)

PE�(6,3x0.8)

PE�(6,3x0.8)

11

11

22

22

33

33

X101 X101

InstallationTheUV41(HE)mustbemountedascloselyaspossibletotheflametobemonitored. TheUV41(HE)EM1/3adapterfitsa1"inspectiontube;whenmountingit,makesurethattherubbersealingringenclosedwiththeUV41(HE)isinsertedbetweentheUV41(HE)andthe mounting adapter.TheUVsensorwillalsodetectex-ternallightasaflame,whichiswhytheUV41(HE)mustbemountedsuchthat,forexample,nodaylight,ignitionsparksorotherflamescanbedetected.TheUV41(HE)tubeissensitivetoimpacts,vibrations,etc.,whichiswhyitmustbemountedwithoutvibratingit.Afterthemountingworkiscomplete,all screws must be checked for tight fit.Iftemperaturesofmorethan60°CarereachedattheUV41(HE),anadapterfittedwithaquartzcoverglassand,ifnecessary,anadditionalpurging air connection must be used (uponrequest).

AttentionThe maximum allowed line lengths mustnotbeexceeded.Supplyandsignallinesmustbelaidseparately,as far as possible.

AttentionTheflamedetectorUV41(HE)isdeliveredwithoutcablescrewcon-nection. To guarantee the required traction reliefandIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcorrespondstoanAWGof16).Theprotectiveearthconductormustbe connected using an insulated femaleconnectoraccordingtoDIN46245.

Electrical connection

Connection UV 41 (HE) MPA 41xxPin1 Out Ionisation(5)Pin2 N NPin3 L Vers.FLW(7)PE

Page 109: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

109 … 126108 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

M16x1,5

94 ø44,5

ø 42

UV 42TheUV42isaflamedetectorwithUVtubeinmetaldesignforhighme-chanical stress.TheflamedetectorisconnectedtotheionisationinputoftheMPA41xxand is suitable for intermittent opera-tion.For use in continuous operation applications,theUV4xshutterisad-ditionally required.TheadapterUV4x-EM1/xmustbeusedformountingtheUV42.

Technical Data

Dimensions

UV42

UV4xEM1/3adapter

UV 42 GeneralRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <1WType of protection IP54Ambienttemperature -20°C...+60°C

-40°C...+80°CwithreducedlifetimeoftheUVtubeStorageandtransport -40°C...+80°Cmaximumstoragetimewithoutpowersupply:3monthHumidity DIN60730-1,nodewingadmissibleLifetime 10,000operatinghoursMounting position as desiredDimensionsinmm Diameter:44.5mm

Length:94mmLengthwithUV4x-EM1:approx.128-143mm

Max. line length 100m

39,5

28,5

50

50

36

50

3628,5

G1/8"

EM1/3 EM1/4EM1/6

EM1/5EM1/7

EM1/8EM1/9

1/4"NPT 1/2"

NPT

G1/8" G3/4"

Page 110: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

111 … 126110 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

InstallationTheUV42mustbemountedascloselyaspossibletotheflametobemonitored. TheUV42EM1/3adapterfitsa1"inspectiontube;whenmountingit,make sure that the rubber sealing ring enclosedwiththeUV42isinsertedbetweentheUV42andthemountingadapter.TheUVsensorwillalsodetectexter-nallightasaflame,whichiswhytheUV42mustbemountedsuchthat,forexample,nodaylight,ignitionsparksorotherflamescanbedetected.TheUVtubeissensitivetoimpacts,vibrations,etc.,whyitmustmountedinavibrationfreearea.Afterthemountingworkiscomplete,all screws must be checked for tight fit.Iftemperaturesofmorethan60°CarereachedattheUV42,anadapterfittedwithaquartzcoverglassand,ifnecessary,anadditionalpurgingairconnectionmustbeused(uponrequest).

AttentionThe maximum allowed line lengths mustnotbeexceeded.Supplyandsignallinesmustbelaidseparately,as far as possible.

Attention TheflamedetectorUV42isdeliv-ered without cable screw connection. To guarantee the required traction reliefandIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcorrespondstoanAWGof16).Theprotectiveearthconductormustbe connected using an insulated femaleconnectoraccordingtoDIN46245.

G

G

G

G

L (PIN3)

L (PIN3)

N�(PIN2)

N�(PIN2)

O�(PIN1)

O�(PIN1)

PE�(6,3x0.8)

PE�(6,3x0.8)

11

11

22

22

33

33

X101 X101

Connection UV 42 MPA 41xxPin1 Out FLW2NO(16)Pin2 N NPin3 L Vers.FLW(7)PE

Electrical connection

Page 111: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

111 … 126110 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

UV 4x EM 1/1 (shutter module)TheUV4xshuttermoduleallowscontinuousoperationoftheUV41andUV42flamesafeguards.Theshutter module is inserted between theflamesafeguardandthecorre-sponding mounting adapter.Aseparatepowersupplyisnotnecessary,asonlytheshuttersignalprovidedbytheMPA41xxviaanextensionmodule(e.g.EM2/4)mustbe connected.

Technical data

DimensionsUV 4x EM 1/1

UV 4x EM 1/1 general (Shuttermodul)Schutzkleinspannung 24VDCType of protection IP54Ambienttemperature -20°C...+60°C

-40°C...+80°C(with reduced lifetime)Storageandtransport -40°C...+80°CHumidity DIN60730-1,nodewingadmissibleLifetime 1millionswitchings(at10min/switching,20a)Mounting position as desiredDimensionsinmm Diameter:44,5mm

Length:75mmHeight:ca.101mm

Max. line length 100m

101

75

M16 x 1,5ø 44,5

ø 42

Page 112: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

113 … 126112 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

AttentionThe maximum allowed line lengths mustnotbeexceeded.Supplyandsignallinesmustbelaidseparately,as far as possible.

AttentionTheflamesafeguardUV41isdeli-veredwithoutcablescrewconnec-tion. To guarantee the required traction reliefandIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcorrespondstoanAWGof1).

AttentionAlsoiftheshutterisclosedarentoflightcanfullontheUV-cell.Throughthissafetyshutdown'scanoccureveniftheUV-cellworkscorrectly.In such case the mounting position oftheUV-cellhastobechangendora mounting adaptor with a reduced diameters has to take place.Alternativelythediametercanbereduced by additional nipple.

Electrical connection

GND+24 V DC PE

Connection UV 4x EM 1/1 MPA 41xx EM 2/xPin1 +24VDC +24VDCPin2Pin3 GND GND

The shutter module is mounted bet-weentheUV41(HE)orUV42flamesafeguard and the mounting adapter UV4xEM1/x.

Page 113: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

113 … 126112 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

FLW 20UV

TheFLW20UVisaflamedetectorwithUVtubeinplasticdesign.TheuseofaUVtubeguaranteesthatbackgroundradiation,forexamplefrom red-hot walls or parts of the mix-ingdevice,willnotbedetected.TheflamesignalintensitycanbeseendirectlyontheopticalLEDdis-playoftheflamedetector.TheFLW20UVisconnectedtotheionisationinputoftheMPA41xxandissuitableexclusivelyforintermittentoperation.TheFLWflangesaresuitableformounting.

Technical DataRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption 5.5mAOutput data Reactiontimewithflameontyp.:0.5sec.

Reactiontimewithflameout<0.5sec.Switchingoutput max.switchingcurrent15mA,

max.switchingpower0.3Wmax.switchingvoltage280VAC/400VDC

Opticevaluation Spectralregion185–260nmAlignmenttotheflame Radial,leftType of protection IP41Ambienttemperature -20°C…50°C

-20°C…60°CwithreducedlifetimeTransport and storage -20°C…60°CHumidity max.95%ofr.h.,nodewingadmissibleLifetime 10,000operatinghoursMounting position as desiredMax. line length 10m

Page 114: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

115 … 126114 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

13,5

30

115

50 55

22

31

Dimensions [mm]FLW 20 UV

FLW flange

Installation

TheFLW20UVmustbemountedascloselyaspossibletotheflametobemonitored.ItismountedbymeansofaFLWflange(height7or13mm)orofaholderwitha14mmmountingbore.Theflamedetectormustbefirmlyinserted into the holder. No external lightmustbeincidentonthesensor,anddirectviewoftheignitionsparkmustbeavoidedaswell.

Attention:The maximum allowed line lengths must not be exceeded. Supplyandsignallinesmustbelaidseparately,asfaraspossible.

Inspection openingRadial

Page 115: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

115 … 126114 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

LED

Electrical connection

Operation display LED

TheflamesignalintensityoftheflamedetectorFLW20UVisshownonthebuilt-inLED.

LED offFLWisdeadornoflameisdetected.

LED flashingFlameisdetected,theflashingpulsesoftheLEDsignallingtheflamesignal intensity – Increasingflashingpulses=higherintensity

LED permanently onFlame is detected at the highest flameintensity

Commissioning and maintenance

SincetheUVtubeissubjecttoageing,asafetycheckoftheflamedetector must be carried out dur-ing each commissioning and each maintenance.The following functions must be checked:

Start-up without flame signallingDarkentheflamedetectorduringstart-up,theautomaticburnercontrolsystem must either output a fault at the end of the safety time or perform a restart.

Start-up with flame signallingDuringthestartupattemptoftheautomaticburnercontrolsystem,theflamedetectorisexposedtoanexternalUVradiation,forexamplefromalighteroragasflame(avail-ableroomlightisnotsufficient).Theautomatic burner control system reports external light.

Burner operationCovertheflamedetectorwhiletheburner is running – depending on the parameter setting of the automatic burnercontrolsystem,alock-outorsafetyshutdown,followedbyarestartattempt,willtakeplace.

Incaseofmalfunctions,theflamedetector must be replaced. Afteraruntimeof10,000h,theflamedetector should be replaced as a preventivemeasure.AreplacementoftheUVtubeisnotpossible.

Blue,terminalnumber:N

Black,terminalnumber:5/Ion

Brown,terminalnumber:7/FLWpwr.

Page 116: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

117 … 126116 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

FLW 10IR

TheFLW10IRisaflamedetec-torequippedwithanIRsensorformonitoring burners with blue-burning flames.Theflamedetectordetectstheflickerfrequencyoftheflame.Lightraysthatemitauniformfrequencyarefilteredout. External light like that caused by glowingcomponentsorfluorescenttubesisnotdetectedasflame.TheflamesignalintensitycanbeseendirectlyontheopticalLEDdis-playoftheflamedetector.TheFLW10IRisconnectedtotheionisationinputoftheMPA41xxandissuitableexclusivelyforintermittentoperation.TheFLWflangesaresuitableformounting.

Technical DataRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption 3...4mAOutput data Reactiontimewithflameontyp.:0.5sec.

Reactiontimewithflameout<0.5sec.Switchingoutput max.switchingcurrent15mA,

max.switchingpower0.3Wmax.switchingvoltage280VAC/400VDC

Opticevaluation Spectralregion380-1150nm,maximumsensitivityat920nmAlignmenttotheflame RadialType of protection IP41Ambienttemperature -20°C…60°CTransport and storage -20°C…60°CHumidity max.95%ofr.h.,nodewingadmissibleMounting position as desiredMax. line length 10m

Page 117: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

117 … 126116 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Dimensions [mm]FLW 10IR

FLW flange

Installation

TheFLW10IRmustbemountedascloselyaspossibletotheflametobemonitored.ItismountedbymeansofanFLWflange(height7or13mm)orofaholderwitha14mmmountingbore.Theflamedetectormustbefirmlyinserted into the holder. No external lightmustbeincidentonthesensor,anddirectviewoftheignitionsparkmustbeavoidedaswell.

Attention:Themaximumallowedline lengths must not be exceeded. Supplyandsignallinesmustbelaidseparately,asfaraspossible.

13,5

30

115

50 55

22Inspection opening

Page 118: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

119 … 126118 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Electrical connection

Operation display LED

TheflamesignalintensityoftheflamedetectorFLW10IRisshownonthebuilt-inLED.

LED offFLWisdeadornoflameisdetected.

LED flashingFlameisdetected,theflashingpulsesoftheLEDsignallingtheflamesignal intensity – Increasingflashingpulses=higherintensity

LED permanently onFlame is detected at the highest flameintensity

Commissioning and maintenance

TheFLW10IRismaintenance-free.

LED

Blue,terminalnumber:N

Black,terminalnumber:5/Ion

Brown,terminalnumber:7/FLWpwr.

Page 119: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

119 … 126118 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

FLW 41ITheflamesafeguardmoduleFLW41IisconnectedtothesecondflameguardinputoftheMPA41xx.Flame monitoring is done by means of an ionisation electrode. This allows burners to be monitored viatwomeasuringpoints.Suitableforintermittentoperation,inconnection with an electronic shutter signal(e.g.EM2/3orEM2/4)alsosuitable for continuous operation.

Technical data

DimensionsFLW 41I

FLW 41I GeneralRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <3WType of protection IP54Ambienttemperature -40°C...+70°C

Storageandtransport -40°C...+80°CHumidity DIN60730-1,notdewingadmissibleMounting position as desiredDimensionsinmm(LxHxT)

approx.152,5x151,5x77mm

Weigth 0,6kgMax.linelengthtoMPA 100mMax.ionizationlinelength 10m

77

151,5

152,5

Page 120: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

121 … 126120 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

AssemblyTheFLW41canbemountedeitheron a hat rail or by means of a direct screwconnection(alldimensionsasforMPA411)

AttentionThe maximum allowed line lengths must not be exceeded.Supplyandsignallinesmustbelaidseparately.

FunctionTheFLW41Iallowsaflametobemonitored at two measuring points or twoflamestobemonitoredindepen-dently of one another.IftheshuttersignaloftheMPA41xxisconnected,theFLW41Iissuitablefor continuous operation.

Example

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

N G

G

ShuttersignalFlame signalVoltagesupplyON

77

151,5

152,5

MPA41xxFlamedetector1

FLW41IFlame detector 2

FLWOutput

toMPA

FLWPower

fromMPA

ION

N

Shutter

1(+)

2(-)

PE

N

1.0AT

Display:

Electrical connection

Page 121: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

121 … 126120 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

DEZ ignition transformers

Technology

TheDUNGSDEZareelectronichigh-performance ignition transform-ers with high-frequency oscillation technology.Comparedwithconventionalinduc-tiveignitiontransformers,theDEZare much smaller and lighter.Designsforoneortwoignitionelectrodesareavailableindifferentvoltageversions.

Application

Foroilandgasburners,ignitiontakesplace,dependingondesign,withoneignition electrode against the burner mass or with two ignition electrodes between the electrodes.

Approval

73/23/EECLow-VoltageDirective89/336/EECEMCDirective

Page 122: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

123 … 126122 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

DEZ 1xx DEZ 2xx

Parameter overview

DEZ function

TheDEZignitiontransformersareavailableintwoversions.Eitherwithahigh-voltageoutput(DEZ1xx)forignitionagainsttheburnermassorwithtwohigh-voltage

outputs(DEZ2xx)forignitionbe-tween the electrodes.Bothversionsareavailablewithdif-ferent performance data.For use in burner systems in which ignitionandionisationflamemoni-toringtakesplaceviaacommonelectrode,the"SEO"versionsmustbe used.

DEZ Versions

DEZ 100 DEZ 101 DEZ 100 SEO DEZ 101 SEO DEZ 200

High-voltageoutputs 1 1 1 1 2Mainsvoltage[VAC] 230/240 120 230 120 230/240Frequency[Hz] 50/60 50/60 50/60 50/60 50/60Currentconsumption[A] 0.3 0.5 0.3 0.5 0.14Powerconsumption[VA] 69 55 69 60 32Secondaryvoltage[kV]+/-10%

1x15 1x15 1x15 1x15 2x10

Secondaryfrequency[kHz] 10 13 10 16 10Short-circuitcurrent[mA] 30 30 30 30 20Dutycycle3min. 33% 33% 33% 33% 100%Type of protection IP54 IP54 IP54 IP54 IP54Ambienttemperatureta[°C] -20…60°C -20…60°C -20…60°C -20…60°C -20…60°CWeight[kg] 0.32 0.32 0.32 0.32 0.32Part-No. 252113 255018 257126 257127 252114

Electrical connectionConnection to the mains is made through pre-fabricated connection linesDEZ1xx/2xx,whichareavail-ableindifferentlengths.

The ignition electrodes are con-nectedviapre-fabricatedcarbonfibreignition lines. The high line resistance oftheignitionlineof10kOhm/mef-fectivelysuppressesEMCfaults.

Theignitionlinesarefittedwithaninsulated 6.5 mm angle plug on the electrode side.

DEZconnection

PowersupplyconnectionL1:blackN:blue:green-yellow

Page 123: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

123 … 126122 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Dimensions

AttentionTheoperationoftheDEZignitiontransformersproducesveryhighvoltages.Theignitiontransformersmay only be put into operation if the ignition electrodes were built into the burner/burnerchambertouch-proofandallliveconnectionsbymeansofthelinesprovidedforthispurposewere made touch-proof.

Thelengthoftheignitionline(s)mustnotexceed1m.

Connectingtheprotectiveearthismandatory.

Connectingtheprotectiveearthismandatory.Inthe"SEO"versionforsingle-elec-trodeoperation,theprotectiveearthisconnectedtoterminal5oftheMPA41xx.

DEZconnection Electrode connectionø6.3mm

Page 124: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

125 … 126124 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

VisionBoxTheVisionBoxisusedforaccesstotheMPAviaaPC.SeeVisionBoxdocumentation

Page 125: Manual MPA 41xx - Dungs · PDF fileManual MPA 41xx. 2 126 3 126 ... 22-24 Parameters/Parameter change ..... 25 Parameters/Parameter description ... • MPA 4111 without display •

125 … 126124 … 126

Prin

ted

in G

erm

any

• Edi

tion

02.1

4 • N

r. 25

7 45

4

Overview of revisions