Main catalogue Distribution Innovation - ABB Ltd · Downstr. ln [A] lcs [kA] 16 25 25 36 36 50 50...
Transcript of Main catalogue Distribution Innovation - ABB Ltd · Downstr. ln [A] lcs [kA] 16 25 25 36 36 50 50...
120165/C
Contents
The family ............................................................................................................ 2–3
Miniature circuit-breakers - General, technical data ..................................................................................... 6–9- Order data .................................................................................................... 10–19
Residual current operated circuit-breakers - Residual current operated circuit-breaker FIP2/FI4- General, technical data ....................................................................................... 20- Order data .......................................................................................................... 21
- Delayed residual current operated circuit-breakerand selective type FIKP2, FIK4 and FIS4
- General, technical data ................................................................................. 22, 23- Order data .......................................................................................................... 23
- Residual current operated circuit-breaker with integralovercurrent protection FI-LP2 and delayed type FIK-LP2
- General, technical data ................................................................................. 24, 25- Order data .......................................................................................................... 26
- Residual current monitor FISG- General, technical data ....................................................................................... 27- Order data .......................................................................................................... 27
- Residual current operated circuit-breakers for 162/3 Hz and 400 Hz- General, technical data ....................................................................................... 28- Order data .......................................................................................................... 29
Manual motor starters MS325 - General, technical data ................................................................................. 30–32- Order data .......................................................................................................... 33
Surge arresters SA4 SC/SA4 - General, technical data ................................................................................. 34, 35- Order data .......................................................................................................... 36
Disconnectors IS463 - General, technical data ....................................................................................... 37- Order data .......................................................................................................... 37
Auxiliary switches and signal contacts - General, function ................................................................................................ 38- Assembly directives ............................................................................................ 39- Technical data ..................................................................................................... 40- Order data .......................................................................................................... 41
Combi-modules - General ............................................................................................................... 42- Order data .......................................................................................................... 43
smissline accessories - Sockets .............................................................................................................. 44
- Accessories, socket ................................................................................... 45, 46
- Starter pack ....................................................................................................... 46
- Feeder element for external units ............................................................. 47, 48
- Incoming terminal block and component ................................................ 49–51
- Accessories, additional socket ................................................................. 52, 53
- UL Recognizer .................................................................................................. 54
- Power supplies ........................................................................................... 55–56
Dimensions ..................................................................................................... 57–60
Products in this catalogue comply with therelevant standards as stated, and shouldalways be installed in accordance withthe requirements of relevant regulations,standards and legislation
220165/C
Overview
2
3
4
5
6
7
8
910
1112
13
14
15
16
17
1819
20
22
23
24
1
11
10
21
Incoming supply terminal
Incoming terminal block
Cover
Supply cables
Residual current operated circuit-breaker with integralovercurrent protection
Residual current operated circuit-breaker
Manual motor starter
Miniature circuit-breaker
Plug contacts
Extension adaptor
Busbar cover
Latch
1
3
4
5
6
7
8
9
10
11
12
2
Busbar L3
Busbar L2
Busbar L1
Busbar N
Socket base
Auxiliary busbars LA
Auxiliary busbars LB
Busbar N, external
Busbar PE, external
Additional socket base
PE conductor terminal
Load conductor
13
14
15
16
17
18
19
20
21
22
23
24
320165/C
Advantages of a socket systemArguments and advantages
Straightforward combination withother modular installation units.
Time-saving
The consistent use of the smissline provides decisive advantages for planning engineers, switchgeardesigners and operators at all project stages:● Considerably simplified planning● Rapid construction and time-saving assembly by the innovative assembly.● Simple and rapid installation of units with the required numbers of poles – also with auxiliary switches.● Component replacement in seconds.● Straightforward extension possibilities.
Cost-reducing
The socket system also enables significant savings to be achieved in labour costs:● All units can be plugged in quickly by hand.
The KEMA tested plug-in technique automatically ensures safe and reliable connection to the busbar.● This new technique enables assembly and wiring time to be reduced by up to 50%:
no input wiring is necessary.● The units can be transferred simply and easily to any desired position over the entire length of the
busbar system. No special new connections are required.
Full flexibility right up to the last minute
With the socket system and free positioning possibility for the units, smissline offers everyoneparticipating in a project a flexibility never before achieved. This includes:● Long-term planning even without an exact knowledge of the final arrangement.● Rapid, simple conversion of the installation, e.g. for last minute extensions or modified performance
requirements.● Straightforward re-assignment of loads.
Ample latitude for future requirements
With its unequalled versatility and forward-looking system technology, smissline complies with all futurerequirements. Subsequent modifications for use, additions to units or system extensions are thereforepossible without difficulty.● The new plug-in technology considerably simplifies the exchange of units, e.g. for different rating
requirements.● Both, the smissline system and the proven pro M system as well as other DIN rail components may be
combined in the same switchboard cabinet.● Even a subsequent complete change in application of an overall installation can be performed quickly
and with surprisingly little work.
Tested and proven for worldwide application
smissline was developed by ABB Switzerland AG CMC Low Voltage Products and has been proven innumerous installations.
Free positioning of units.Extremely simple re-positioning.
Exchange of units within seconds.
Direct power supply via units,e.g. LS- or FI-circuit-breaker.
4041
1
Z20
152.
eps
Z20
151.
eps
Z20
153.
eps
Z20
155.
eps
Z20
154.
eps
1
0
12:240
420165/C
Power loss / internal resistance per pole
Miniature circuit-breakerPower loss / internal resistance per pole
Typ LE B LE C LP D LP G, K LPUC ZLP B LP C LPUC CRi Pv Ri Pv Ri Pv Ri Pv Ri Pv
in A � W � W � W � W � W0.5 6.34 1.59 10.45 2.611 1.55 1.55 3.5 3.501.6 0.695 1.78 1.15 2.942 0.46 1.84 0.98 3.923 0.165 1.49 0.495 4.464 0.12 1.92 0.149 2.386 0.055 2.00 0.052 1.87 0.097 3.498 0.038 2.43 0.038 2.43 0.054 3.46
10 0.013 1.30 0.013 1.30 0.013 1.30 0.0126 1.26 0.013 1.3013 0.013 2.20 0.013 2.20 0.013 2.20 0.0101 1.71 0.013 2.2016 0.007 1.79 0.007 1.79 0.007 1.79 0.0077 1.79 0.007 1.7920 0.0063 2.52 0.0063 2.52 0.0063 2.52 0.0067 2.68 0.0063 2.5225 0.005 3.13 0.005 3.13 0.005 3.13 0.0046 2.88 0.005 3.1332 0.0036 3.69 0.0036 3.69 0.0036 3.69 0.0025 3.58 0.0036 3.6940 0.0003 4.80 0.003 4.80 0.003 4.80 0.0028 4.48 0.003 4.8050 0.0012 3.00 0.0012 3.00 0.0012 3.00 0.0012 3.00 0.0012 3.0063 0.0009 3.57 0.0009 3.57 0.0009 3.57 0.0007 2.78 0.0009 3.57
4-pole residual current 2-pole residual current Combinedcircuit-breaker circuit-breaker FI-LS switches
Typ Ri Pv Typ Ri Pv Typ Ri Pvin A � W in A � W in A � W25 0.0002 5 FIP 16/10 0.0155 4 13/10 0.027 4.540 0.0024 6.5 FIP 25/30 0.0083 5.2 13/30 0.02 3.463 0.003 8.5 FIP 40/30 0.005 8 16/10 0.02 4.9
16/30 0.013 3.220/30 0.0137 5.5
Motor protection circuit-breaker MS 325
Typ Ri�
0.1 – 0.16 71.1 0.16 – 0.25 27.1 0.25 – 0.4 12.3 0.4 – 0.63 5.17 0.63 – 1 2.09 1 – 1.6 0.805 1.6 – 2.5 0.34 2.5 – 4 0.141 4 – 6.3 0.051 6.3 – 9 0.0224 9 – 12.5 0.012212.5 – 16 0.008116 – 20 0.004820 – 25 0.0035
Surge arrester SA4 / SA4 SC
Power consumption at rated voltage 1.2 W
Accessories
Resistance per Power loss perline terminal line terminalRi PV� W
Auxiliary switch and signal contact SDH, SDS, SBH, SBS 0.0065 0.24 Feeder block 0.00005 0.5 External terminal 100 A N 0.00005 0.5 External terminal 100 A PE 0.00004 0.4 External terminal 32 A N 0.00017 0.17 External terminal 32 A PE 0.00012 0.12
520165/C
4012
5
Miniature circuit-breaker MCB
General
The smissline miniature circuit-breaker LP is an energy limiting circuit-breaker with a high performance,equally suitable for industrial or domestic applications.In the event of a short-circuit it ensures excellent selectivity with upstream circuit-breakers, while thestresses imposed on the following switchgear is limited to a minimum.The high short-circuit rating of 10 kA of the smissline miniature circuit-breakers makes them ideal forthe use in fuseless distribution systems.
Major features
● High rated short-circuit capacity of 10 kA (LP)● Energy-limiting (current limiting class 3)● Snap-on neutral disconnector● Snap-on auxiliary switch and signal contact● Optimum ease of assembly and connection● Line terminals protected against accidental contact● Trip characteristic B, C, D, K, UCZ/UCC
Technical data
Series: Series:LP... LPUC...
Rated voltage Ue~: 230/400 V~ –
Rated voltage Ue=: 60 V=/1pole 125 V=1pole(Connection diagram LPDC 250 V=2polesee page 9) polarity-dependent
Rated current In: 6…63 A (C)10...63 A (B, D)0.5...63 A (K)
Trip characteristic: B, C, D, K, G CZ (semiconductor protection)
Number of poles: 1...3 1+2
Rated frequency: 162/3 ...60 Hz –
Rated short-circuit capacity Icn: 10 kA 6...50 kA
Energy limiting class: 3 –
Conductor cross-section Cu: stranded/flexible stranded/flexible– stranded/flexible, top terminal 25/16 mm2 25/16 mm2
– stranded/flexible, bottom terminal 16/10 mm2 16/10 mm2
Degree of protection: IP20 IP20
Endurance:– mechanical 20,000 20,000– electrical 4,000 4,000
Climatic resistance: DIN 50016 DIN 50016
Position of use: any any
Ambient temperature: –25 °C...+55 °C –25 °C...+55 °C
Resistance to vibrations: 5 g 5 g5...150...5 Hz 5...150...5 Hz
Standards: BSEN 60898 –
Approvals: SEV, VDE, ÖVE –
Weight per pole: 120 g 150 g
Plastic components: Free of halogens Free of halogensand cadmium and cadmium
620165/C
Release with different characteristics
Thermal release Electromagnetic releaseTrip characteristic Test current: Release time Test current: Release timeand rated current small large hold switch
Test current Test current Impact current Impact currentI1 I2 from by
B 6 to 63 A 1,13 · In > 1 h 3 · In > 0,1 s1,45 · In < 1 h 5 · In < 0,1 s
C 8 to 63 A 1,13 · In > 1 h 5 · In > 0,1 s1,45 · In < 1 h 10 · In < 0,1 s
D 10 to 63 A 1,13 · In > 1 h 10 · In > 0,1 s1,4 · In < 1 h 20 · In < 0,1 s
K 0,5 to 63 A 1,05 · In > 2 h 8 · In 10 · In > 0,2 s1,2 · In < 2 h up to 32A up 40A 12 · In 14 · In < 0,2 s1,5 · In < 2 min. up to 32A up 40A6,0 · In > 2 s (T1)
Z 0,5 to 63 A 1,05 · In > 2 h 2 · In > 0,2 s1,2 · In < 2 h 3 · In < 0,2 s1,5 · In < 2 min.6,0 · In > 2 s (T1)
Back-up protection with ABB SACE Tmax
Upstr. T1 T1 T1 T2 T3 T2 T3 T2 T2Version B C N N S S H L
Downstr. ln [A] lcs [kA] 16 25 25 36 36 50 50 70 85
LP 6..10 31 35 60 78B, C, D 13..63 10 13 20 20 31 20 44 20 50 50
Using the back-up table
These tables provide the value (in kA) for which back-up protection is ensured between a given combination of circuit-breakers. The tablescover possible combinations between ABB SACE moulded-case circuit-breakers in Tmax ranges and between the above mentioned circuit-breakers and the ABB range of miniature circuit-breakers. The values given in the table refer to a rated voltage Vn of 415 V AC forcombinations between moulded-case circuit-breakers and to a rated voltage VN of 400 V AC for combinations between moulded-case andminiature circuit-breakers.
Miniature circuit-breakerBack-up protection
Back-up protection
a) If the short-circuit current at the place of installation of a miniature circuit-breaker is not higher than the specified rated breaking capacityof the MCB, no back-up fuse link is necessary. If a back-up fuse is connected for installation reasons, its rated current may be selectedas high as required.
b) If the short-circuit current at the place of installation of the miniature circuit-breaker is higher than its breaking capacity, the rated currentsof the back-up fuse link must not exceed the values in the following table.
Maximum fuse ratings for back-up protection
Characteristic B, C, D K, G
Rated current of miniature circuit-breaker 6 A 8 A 10 A 16... 50... 0.5... 3 A 4 A 6 A 8... 16... 50...13 A 40 A 63 A 2 A 13 A 40 A 63 A
Rated breaking capacity LP 10 kA 10 kA 10 kA 10 kA 10 kA 50 kA 10 kA 10 kA 10 kA 10kA 10kA 10kA
Max. rated current ofback-up fuse link gG (A) 40 63 100 125 160 any 50 63 80 100 125 160
720165/C
4007
040
070
4007
1
10 000
1000
100
10
1
0,1
0,01
0,002
1 2 3 5 10 20 30
10 000
1000
100
10
1
0,1
0,01
0,002
1 2 3 5 10 20 30Z20
0005
.ep
s
Z20
0006
.ep
s
Miniature circuit-breakerTrip characteristic
Trip characteristic
Thermal release
Electromagnetic release
Reference temperature
Trip diagram
Characteristic B
Miniature circuit-breaker for circuitssupplying loads generating no or only minorinrush currents (boilers, electric heaters,cookers).
C
The «Standard» miniature circuit-breaker forcircuits supplying loads producing inrushcurrents particular to inductive loads (TVsets, fluorescent and discharge lamps) andfor socket outlets.
C
1.13...1.45xIn
5...10xIn
30 °C
B
1.13...1.45xIn
3...5xIn
30 °C
Trip
pin
g tim
e in
s
Trip
pin
g tim
e in
s
Multiple of rated current Multiple of rated current
820165/C
10 000
1000
100
10
1
0,1
0,01
0,002
1 2 3 5 10 20 30
10 000
1000
100
10
1
0,1
0,01
0,002
1 2 3 5 1 2 3 7 14
C
Z
Z20
0007
.ep
s
Z20
0009
.ep
s
Miniature circuit-breakerTrip characteristic
D
Miniature circuit-breaker for circuitssupplying loads producing very high inrushcurrents (transformers, capacitor banks).Main circuit-breaker for the protection ofcircuit-breakers connected downstream.
G, K
Circuit-breaker for equipment:The characteristics of these types enablethe close protection requirements forequipment to be met.
UC
Circuit breaker for equipment supplied witheither direct or alternating current.
D
1.13...1.45xIn
10...20xIn
30 °C
1.05...1.35xIn
3...5xInDC2...3xInAC
7...14xInDC5...10xInAC
Z CUC
1.13...1.45xIn
30 °C
Trip
pin
g tim
e in
s
Trip
pin
g tim
e in
s
Trip
pin
g tim
e in
s
Multiple of rated current Multiple of rated current Multiple of rated current
10 000
1000
100
10
1
0,1
0,01
0,002
1 2 7 1 2 3 8 14
K
G
12 Z20
0368
.ep
s
G K
1.05...1.35xIn 1.05...1.2xIn
7...12xIn 8...14xIn
20 °C 40 °C
920165/C
Miniature circuit-breakerSelectivity
Upstream S500-C, DRated current (A) C40 D40 C50 D50 C63 D63
Downstream Rated current (A) Max. short-circuit current (A)
B6 / C6 6 600 1200 800 1400 950 1800B10 / C10 10 550 1100 700 1300 850 1700B13 / C13 13 550 1100 700 1300 850 1700B16 / C16 16 550 1100 700 1300 850 1700B20 / C20 20 500 1000 600 1200 800 1550B25 / C25 25 450 900 550 1100 750 1400B32 / C32 32 - 900 550 1100 700 1400B40 / C40 40 - - - - 700 1400B50 / C50 50 - - - - 700 1400
On requestS500 Selectivity & Back-up protection, No. 10109/A
S500 circuit-breaker upstreamCircuit-breakers (MCBs) downstream
Should a short-circuit occur selective break action will be performed of the MCB up to thecurrent values as listed in the following table.
S500
MCBs
Discrimination
Short circuit discrimination is provided by the smissline miniature circuit-breaker up to limits given in the following table. The values refer to themean trip characteristic of the back-up fuse link.
Limits of discrimination
Rated current of miniature circuit-breaker B, C, D, K, G 6 A 8 A 10/13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 ATrip characteristicBack-up fuse link gG (VDE 0636) 20 A 600 A 560 A 520 A – – – – – – –
25 A 850 A 800 A 750 A 720 A – – – – – –40 A 1200 A 1100 A 960 A 900 A 900 A – – – – –50 A 1600 A 1400 A 1200 A 1100 A 1100 A 1000 A 1000 A – – –63 A 2400 A 2200 A 1700 A 1600 A 1500 A 1400 A 1400 A – – –80 A 8000 A 6000 A 2500 A 2300 A 2100 A 2000 A 2000 A 1700 A 1600 A 1500 A
100 A 10000 A 10000 A 3200 A 3000 A 2800 A 2600 A 2600 A 2300 A 2200 A 2000 A125 A 3 200 1) 3 200 1) 1) 9000 A 8000 A 7000 A 6000 A 5000 A 5000 A 4000 A160 A 32 00 1) 32 00 1) 1) 3200 1) 3200 1) 3200 1) 3200 1) 3200 1) 8400 A 8000 A
1) not permissible if the short-circuit current produced is higher than the rated breaking capacity.
1020165/C
4012
4
4012
5
4027
640
123
3 P
4014
8
SDHSDS
2 P
1 P
4014
9
Miniature circuit-breakerSeries LP...B
Icn kA Rated current Order data Module Packaging unit
6 6 A LP1B6-S 1 1010 10 A LP1B10-S 1 1010 13 A LP1B13-S 1 1010 16 A LP1B16-S 1 1010 20 A LP1B20-S 1 1010 25 A LP1B25-S 1 1010 32 A LP1B32-S 1 1010 40 A LP1B40-S 1 1010 50 A LP1B50-S 1 1010 63 A LP1B63-S 1 10
6 6 A LP2B6-S 2 510 10 A LP2B10-S 2 510 13 A LP2B13-S 2 510 16 A LP2B16-S 2 510 20 A LP2B20-S 2 510 25 A LP2B25-S 2 510 32 A LP2B32-S 2 510 40 A LP2B40-S 2 510 50 A LP2B50-S 2 510 63 A LP2B63-S 2 5
6 6 A LP3B6-S 3 310 10 A LP3B10-S 3 310 13 A LP3B13-S 3 310 16 A LP3B16-S 3 310 20 A LP3B20-S 3 310 25 A LP3B25-S 3 310 32 A LP3B32-S 3 310 40 A LP3B40-S 3 310 50 A LP3B50-S 3 310 63 A LP3B63-S 3 3
Neutral disconnectorsnaps onto the right side of the breaker
63 A LPN63-S 1 5
Detachable neutral conductor terminalsfor additional socketOrder data see page 52
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Order data
Circuit protection
Characteristic B
4043
2
1120165/C
4027
640
148
SDHSDS
4012
8
4012
9
4012
7
3 P
2 P
1 P
4014
9
Miniature circuit-breakerSeries LP...C
Icn kA Rated current Order data Module Packaging unit
10 6 A LP1C6-S 1 1010 8 A LP1C8-S 1 1010 10 A LP1C10-S 1 1010 13 A LP1C13-S 1 1010 16 A LP1C16-S 1 1010 20 A LP1C20-S 1 1010 25 A LP1C25-S 1 1010 32 A LP1C32-S 1 1010 40 A LP1C40-S 1 1010 50 A LP1C50-S 1 1010 63 A LP1C63-S 1 10
10 6 A LP2C6-S 2 510 8 A LP2C8-S 2 510 10 A LP2C10-S 2 510 13 A LP2C13-S 2 510 16 A LP2C16-S 2 510 20 A LP2C20-S 2 510 25 A LP2C25-S 2 510 32 A LP2C32-S 2 510 40 A LP2C40-S 2 510 50 A LP2C50-S 2 510 63 A LP2C63-S 2 5
10 6 A LP3C6-S 3 310 8 A LP3C8-S 3 310 10 A LP3C10-S 3 310 13 A LP3C13-S 3 310 16 A LP3C16-S 3 310 20 A LP3C20-S 3 310 25 A LP3C25-S 3 310 32 A LP3C32-S 3 310 40 A LP3C40-S 3 310 50 A LP3C50-S 3 310 63 A LP3C63-S 3 3
Neutral disconnectorsnaps onto the right side of the breaker
63 A LPN63-S 1 5
Detachable neutral terminalsfor additional socketOrder data see page 52
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Order data
Circuit protection
Characteristic C40
432
1220165/C
Miniature circuit-breakerSeries LP...D
Icn kA Rated current Order data Module Packaging unit
10 10 A LP1D10-S 1 1010 13 A LP1D13-S 1 1010 16 A LP1D16-S 1 1010 20 A LP1D20-S 1 1010 25 A LP1D25-S 1 1010 32 A LP1D32-S 1 1010 40 A LP1D40-S 1 1010 50 A LP1D50-S 1 1010 63 A LP1D63-S 1 10
10 10 A LP2D10-S 2 510 13 A LP2D13-S 2 510 16 A LP2D16-S 2 510 20 A LP2D20-S 2 510 25 A LP2D25-S 2 510 32 A LP2D32-S 2 510 40 A LP2D40-S 2 510 50 A LP2D50-S 2 510 63 A LP2D63-S 2 5
10 10 A LP3D10-S 3 310 13 A LP3D13-S 3 310 16 A LP3D16-S 3 310 20 A LP3D20-S 3 310 25 A LP3D25-S 3 310 32 A LP3D32-S 3 310 40 A LP3D40-S 3 310 50 A LP3D50-S 3 310 63 A LP3D63-S 3 3
Neutral disconnectorsnaps onto the right side of the breaker
63 A LPN63-S 1 5
Detachable neutral terminalsfor additional socketOrder data see page 52
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Order data
Circuit protection
Characteristic D
4013
2
4013
3
4013
1
1 P
2 P
3 P
4027
6
SDHSDS
4014
8
4014
940
432
1320165/C
Miniature circuit-breakerSeries LP...G
Icn kA Rated current Order data Module Packaging unit
50 0.5 A LP1G0.5-S 1 1050 1 A LP1G1-S 1 1050 1.6 A LP1G1.6-S 1 1050 2 A LP1G2-S 1 1010 3 A LP1G3-S 1 1010 4 A LP1G4-S 1 1010 6 A LP1G6-S 1 1010 8 A LP1G8-S 1 1010 10 A LP1G10-S 1 1010 13 A LP1G13-S 1 1010 16 A LP1G16-S 1 1010 20 A LP1G20-S 1 1010 25 A LP1G25-S 1 1010 32 A LP1G32-S 1 1010 40 A LP1G40-S 1 1010 50 A LP1G50-S 1 1010 63 A LP1G63-S 1 10
50 0.5 A LP2G0.5-S 2 550 1 A LP2G1-S 2 550 1.6 A LP2G1.6-S 2 550 2 A LP2G2-S 2 510 3 A LP2G3-S 2 510 4 A LP2G4-S 2 510 6 A LP2G6-S 2 510 8 A LP2G8-S 2 510 10 A LP2G10-S 2 510 13 A LP2G13-S 2 510 16 A LP2G16-S 2 510 20 A LP2G20-S 2 510 25 A LP2G25-S 2 510 32 A LP2G32-S 2 510 40 A LP2G40-S 2 510 50 A LP2G50-S 2 510 63 A LP2G63-S 2 5
50 0.5 A LP3G0.5-S 3 350 1 A LP3G1-S 3 350 1.6 A LP3G1.6-S 3 350 2 A LP3G2-S 3 310 3 A LP3G3-S 3 310 4 A LP3G4-S 3 310 6 A LP3G6-S 3 310 8 A LP3G8-S 3 310 10 A LP3G10-S 3 310 13 A LP3G13-S 3 310 16 A LP3G16-S 3 310 20 A LP3G20-S 3 310 25 A LP3G25-S 3 310 32 A LP3G32-S 3 310 40 A LP3G40-S 3 310 50 A LP3G50-S 3 310 63 A LP3G63-S 3 3
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
Order data
Equipment/circuit protection
Characteristic G
3 P
4013
6
4013
7
4013
5
2 P
1 P
4014
8
SDHSDS
4014
9
1420165/C
3 P
4013
6
4013
7
4013
5
2 P
1 P
4014
8
SDHSDS
4014
9
Miniature circuit-breakerSeries LP...K
Icn kA Rated current Order data Module Packaging unit
50 0.5 A LP1K0.5-S 1 1050 1 A LP1K1-S 1 1050 1.6 A LP1K1.6-S 1 1050 2 A LP1K2-S 1 1010 3 A LP1K3-S 1 1010 4 A LP1K4-S 1 1010 6 A LP1K6-S 1 1010 8 A LP1K8-S 1 1010 10 A LP1K10-S 1 1010 13 A LP1K13-S 1 1010 16 A LP1K16-S 1 1010 20 A LP1K20-S 1 1010 25 A LP1K25-S 1 1010 32 A LP1K32-S 1 1010 40 A LP1K40-S 1 1010 50 A LP1K50-S 1 1010 63 A LP1K63-S 1 10
50 0.5 A LP2K0.5-S 2 550 1 A LP2K1-S 2 550 1.6 A LP2K1.6-S 2 550 2 A LP2K2-S 2 510 3 A LP2K3-S 2 510 4 A LP2K4-S 2 510 6 A LP2K6-S 2 510 8 A LP2K8-S 2 510 10 A LP2K10-S 2 510 13 A LP2K13-S 2 510 16 A LP2K16-S 2 510 20 A LP2K20-S 2 510 25 A LP2K25-S 2 510 32 A LP2K32-S 2 510 40 A LP2K40-S 2 510 50 A LP2K50-S 2 510 63 A LP2K63-S 2 5
50 0.5 A LP3K0.5-S 3 350 1 A LP3K1-S 3 350 1.6 A LP3K1.6-S 3 350 2 A LP3K2-S 3 310 3 A LP3K3-S 3 310 4 A LP3K4-S 3 310 6 A LP3K6-S 3 310 8 A LP3K8-S 3 310 10 A LP3K10-S 3 310 13 A LP3K13-S 3 310 16 A LP3K16-S 3 310 20 A LP3K20-S 3 310 25 A LP3K25-S 3 310 32 A LP3K32-S 3 310 40 A LP3K40-S 3 310 50 A LP3K50-S 3 310 63 A LP3K63-S 3 3
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
Order data
Equipment/circuit protection
Characteristic K
1520165/C
2 P 250 V=
4014
0
4013
9
1 P 125 V=
4014
8
SDHSDS
4014
9
Icn kA Rated current Order data Module Packaging unit
50 0.5 A LPUC1Z0.5-S 1 1050 1 A LPUC1Z1-S 1 1050 1.6 A LPUC1Z1.6-S 1 1050 2 A LPUC1Z2-S 1 106 3 A LPUC1Z3-S 1 106 4 A LPUC1Z4-S 1 106 6 A LPUC1Z6-S 1 106 8 A LPUC1Z8-S 1 106 10 A LPUC1Z10-S 1 106 13 A LPUC1Z13-S 1 106 16 A LPUC1Z16-S 1 106 20 A LPUC1Z20-S 1 106 25 A LPUC1Z25-S 1 106 32 A LPUC1Z32-S 1 106 40 A LPUC1Z40-S 1 106 50 A LPUC1Z50-S 1 106 63 A LPUC1Z63-S 1 10
50 0.5 A LPUC2Z0.5-S 2 550 1 A LPUC2Z1-S 2 550 1.6 A LPUC2Z1.6-S 2 550 2 A LPUC2Z2-S 2 56 3 A LPUC2Z3-S 2 56 4 A LPUC2Z4-S 2 56 6 A LPUC2Z6-S 2 56 8 A LPUC2Z8-S 2 56 10 A LPUC2Z10-S 2 56 13 A LPUC2Z13-S 2 56 16 A LPUC2Z16-S 2 56 20 A LPUC2Z20-S 2 56 25 A LPUC2Z25-S 2 56 32 A LPUC2Z32-S 2 56 40 A LPUC2Z40-S 2 56 50 A LPUC2Z50-S 2 56 63 A LPUC2Z63-S 2 5
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Miniature circuit-breakerSeries LPUC direct current application
Order data
Equipment/circuit protection
Characteristic Z
Connection diagram single-pole (max. 125 V=) LPUC1 Connection diagram double-pole (max. 250 V=) LPUC2
1
2
1
2
3
4
Load
Mains
Load
MainsZ20
0003
.ep
s
Z20
0004
.ep
s
1620165/C
1
2
3
4
Load
Mains
Load
MainsZ20
0003
.ep
s
Z20
0004
.ep
s
4014
2
4014
1
2 P 250 V=
1 P 125 V=
4014
8
SDHSDS
4014
9
Connection diagram single-pole (max. 125 V=) LPUC1 Connection diagram double-pole (max. 250 V=) LPUC2
Load
Miniature circuit-breakerSeries LPUC direct current application
Icn kA Rated current Order data Module Packaging unit
50 0.5 A LPUC1C0.5-S 1 1050 1 A LPUC1C1-S 1 1050 1.6 A LPUC1C1.6-S 1 1050 2 A LPUC1C2-S 1 106 3 A LPUC1C3-S 1 106 4 A LPUC1C4-S 1 106 6 A LPUC1C6-S 1 106 8 A LPUC1C8-S 1 106 10 A LPUC1C10-S 1 106 13 A LPUC1C13-S 1 106 16 A LPUC1C16-S 1 106 20 A LPUC1C20-S 1 106 25 A LPUC1C25-S 1 106 32 A LPUC1C32-S 1 106 40 A LPUC1C40-S 1 106 50 A LPUC1C50-S 1 106 63 A LPUC1C63-S 1 10
50 0.5 A LPUC2C0.5-S 2 550 1 A LPUC2C1-S 2 550 1.6 A LPUC2C1.6-S 2 550 2 A LPUC2C2-S 2 56 3 A LPUC2C3-S 2 56 4 A LPUC2C4-S 2 56 6 A LPUC2C6-S 2 56 8 A LPUC2C8-S 2 56 10 A LPUC2C10-S 2 56 13 A LPUC2C13-S 2 56 16 A LPUC2C16-S 2 56 20 A LPUC2C20-S 2 56 25 A LPUC2C25-S 2 56 32 A LPUC2C32-S 2 56 40 A LPUC2C40-S 2 56 50 A LPUC2C50-S 2 56 63 A LPUC2C63-S 2 5
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Order data
Circuit protection
Characteristic C
1720165/C
4014
5
4014
3
4020
7
4020
6
1 P + NA
3 P + NA
1 P + NA
3 P + NA
4014
8
SDHSDS
4014
9
Icn kA Rated current Order data Module Packaging unit
10 10 A LP1NAB10-S 2 510 13 A LP1NAB13-S 2 510 16 A LP1NAB16-S 2 510 20 A LP1NAB20-S 2 510 25 A LP1NAB25-S 2 510 32 A LP1NAB32-S 2 510 40 A LP1NAB40-S 2 510 50 A LP1NAB50-S 2 510 63 A LP1NAB63-S 2 5
10 10 A LP3NAB10-S 4 210 13 A LP3NAB13-S 4 210 16 A LP3NAB16-S 4 210 20 A LP3NAB20-S 4 210 25 A LP3NAB25-S 4 210 32 A LP3NAB32-S 4 210 40 A LP3NAB40-S 4 210 50 A LP3NAB50-S 4 210 63 A LP3NAB63-S 4 2
Characteristic C
10 6 A LP1NAC6-S 2 510 8 A LP1NAC8-S 2 510 10 A LP1NAC10-S 2 510 13 A LP1NAC13-S 2 510 16 A LP1NAC16-S 2 510 20 A LP1NAC20-S 2 510 25 A LP1NAC25-S 2 510 32 A LP1NAC32-S 2 510 40 A LP1NAC40-S 2 510 50 A LP1NAC50-S 2 510 63 A LP1NAC63-S 2 5
10 6 A LP3NAC6-S 4 210 8 A LP3NAC8-S 4 210 10 A LP3NAC10-S 4 210 13 A LP3NAC13-S 4 210 16 A LP3NAC16-S 4 210 20 A LP3NAC20-S 4 210 25 A LP3NAC25-S 4 210 32 A LP3NAC32-S 4 210 40 A LP3NAC40-S 4 210 50 A LP3NAC50-S 4 210 63 A LP3NAC63-S 4 2
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Miniature circuit-breaker with switched neutralSeries LP...NAB, NAC
Order data
Circuit protection
Characteristic B
1820165/C
3 P + NA
4028
2
4014
8
SDHSDS
4014
9
1 P + NA
4028
1
3 P + NA
4028
0
1 P + NA
4020
8
Miniature circuit-breaker with switched neutralSeries LP...NAD / LP...NAK
Icn kA Rated current Order data Module Packaging unit
10 10 A LP1NAD10-S 2 510 13 A LP1NAD13-S 2 510 16 A LP1NAD16-S 2 510 20 A LP1NAD20-S 2 510 25 A LP1NAD25-S 2 510 32 A LP1NAD32-S 2 510 40 A LP1NAD40-S 2 510 50 A LP1NAD50-S 2 510 63 A LP1NAD63-S 2 5
10 10 A LP3NAD10-S 4 210 13 A LP3NAD13-S 4 210 16 A LP3NAD16-S 4 210 20 A LP3NAD20-S 4 210 25 A LP3NAD25-S 4 210 32 A LP3NAD32-S 4 210 40 A LP3NAD40-S 4 210 50 A LP3NAD50-S 4 210 63 A LP3NAD63-S 4 2
IIcn kAA Rated current Order data Module Packaging unit
50 0.5 A LP1NAK0.5-S 2 550 1 A LP1NAK1-S 2 550 1.6 A LP1NAK1.6-S 2 550 2 A LP1NAK2-S 2 510 3 A LP1NAK3-S 2 510 4 A LP1NAK4-S 2 510 6 A LP1NAK6-S 2 510 8 A LP1NAK8-S 2 510 10 A LP1NAK10-S 2 510 13 A LP1NAK13-S 2 510 16 A LP1NAK16-S 2 510 20 A LP1NAK20-S 2 510 25 A LP1NAK25-S 2 510 32 A LP1NAK32-S 2 510 40 A LP1NAK40-S 2 510 50 A LP1NAK50-S 2 510 63 A LP1NAK63-S 2 5
50 0.5 A LP3NAK0.5-S 4 250 1 A LP3NAK1-S 4 250 1.6 A LP3NAK1.6-S 4 250 2 A LP3NAK2-S 4 210 3 A LP3NAK3-S 4 210 4 A LP3NAK4-S 4 210 6 A LP3NAK6-S 4 210 8 A LP3NAK8-S 4 210 10 A LP3NAK10-S 4 210 13 A LP3NAK13-S 4 210 16 A LP3NAK16-S 4 210 20 A LP3NAK20-S 4 210 25 A LP3NAK25-S 4 210 32 A LP3NAK32-S 4 210 40 A LP3NAK40-S 4 210 50 A LP3NAK50-S 4 210 63 A LP3NAK63-S 4 2
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Order data
Circuit protection
Characteristic D
Characteristic K
1920165/C
1 P + NA protect
4095
9
4014
8
SDHSDS
4014
9
3 P + NA protect
4096
0
4098
7
2 P + NA protect
Icn kA Rated current Order data Module Packaging unit
10 10 A LP1NPC10-S 2 1010 13 A LP1NPC13-S 2 1010 16 A LP1NPC16-S 2 1010 20 A LP1NPC20-S 2 1010 25 A LP1NPC25-S 2 1010 32 A LP1NPC32-S 2 1010 40 A LP1NPC40-S 2 1010 50 A LP1NPC50-S 2 1010 63 A LP1NPC63-S 2 10
10 10 A LP2NPC10-S 3 510 13 A LP2NPC13-S 3 510 16 A LP2NPC16-S 3 510 20 A LP2NPC20-S 3 510 25 A LP2NPC25-S 3 510 32 A LP2NPC32-S 3 510 40 A LP2NPC40-S 3 510 50 A LP2NPC50-S 3 510 63 A LP2NPC63-S 3 5
10 10 A LP3NPC10-S 4 310 13 A LP3NPC13-S 4 310 16 A LP3NPC16-S 4 310 20 A LP3NPC20-S 4 310 25 A LP3NPC25-S 4 310 32 A LP3NPC32-S 4 310 40 A LP3NPC40-S 4 310 50 A LP3NPC50-S 4 310 63 A LP3NPC63-S 4 3
50 0.5 A LP1NPK0.5-S 2 1050 1 A LP1NPK1-S 2 1050 1.6 A LP1NPK1.6-S 2 1050 2 A LP1NPK2-S 2 1010 3 A LP1NPK3-S 2 1010 4 A LP1NPK4-S 2 1010 6 A LP1NPK6-S 2 1010 8 A LP1NPK8-S 2 10
50 0.5 A LP2NPK0.5-S 3 550 1 A LP2NPK1-S 3 550 1.6 A LP2NPK1.6-S 3 550 2 A LP2NPK2-S 3 510 3 A LP2NPK3-S 3 510 4 A LP2NPK4-S 3 510 6 A LP2NPK6-S 3 510 8 A LP2NPK8-S 3 5
50 0.5 A LP3NPK0.5-S 4 350 1 A LP3NPK1-S 4 350 1.6 A LP3NPK1.6-S 4 350 2 A LP3NPK2-S 4 310 3 A LP3NPK3-S 4 310 4 A LP3NPK4-S 4 310 6 A LP3NPK6-S 4 310 8 A LP3NPK8-S 4 3
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Miniature circuit-breaker with full protect neutralSeries LP...NPC / LP...NPK
Order data
Circuit protection
Characteristic C
Characteristic K
2020165/C
4007
5
4008
5
Residual current circuit-breakerSeries FIP2, FI4
General
The residual current circuit-breaker makes a decisive contribution to the prevention of injury to personsand damage to material caused by electric currents. It is specified in national and international standards.Modern residual current circuit-breakers already respond to the smallest currents. Disconnection takesplace within fractions of a second before danger can arise for persons, animals or material.The principle of permanent magnetic release ensures an optimum, reliable action, even with undervoltageand neutral disconnection.
Major features
● High short-circuit capacity 10 kA● Sensitive to AC and pulsating DC fault currents● 2- and 4-pole versions● Rated tripping currents 10, 30, 100 and 300 mA● Snap-on auxiliary switch and signal contacts● Rated currents 16, 25, 40, 63 A
Technical data
FIP2 FI4
Rated voltage Un: 230 V 230/400 V
Rated current In (A): 16 25 40 16 25 40 63
Rated tripping current I∆n (mA):10 ● ●30 ● ● ● ● ●100 ● ● ●300 ● ●
Number of poles: 2 4
Frequency fn: 45… 60 Hz 45… 60 Hz
Surge current withstand capability: 250 A 250 A8/20 µs 8/20 µs
Total breaking time (mean value)– for I�n 40 ms 40 ms– for 5 I�n 25 ms 25 ms
Delay time for 5 I�n: – –
Short-circuit capacity(kA): 10 kA 10 kA
Cable cross-section Cu: Cable/strand Cable/strand– Type-S, top 25/16 mm2 25/16 mm2
– Type-S, bottom 16/10 mm2 16/10 mm2
Protection class: IP 40 IP 40
Life endurance to BSEN 61008 BSEN 61008– Mechanical operations 4,000 4,000– Electrical operations 2,000 2,000
Climatic resistance to: EN 61008 EN 61008
Mounting position: any any
Ambient temperature: –25 °C… +40 °C –25 °C… +40 °C
Resistance to vibrations: 5 g 5 g5… 150… 5 Hz 5… 150… 5 Hz
Standards: BSEN 61008 BSEN 61008
Approvals: SEV, VDE, ÖVE SEV, VDE, ÖVE, SEMKO, NEMKO
Weights (approx.): 250 g 380 g
Plastic components: Free of halogens Free of halogensand cadmium and cadmium
2120165/C
FIP2 230 V~, PN
4007
8
FI4 230 V~, 3PN
4008
5
4028
9
SBHSBS
4029
1
4014
8
SDHSDS
4014
9
Rated tripping current Rated current Order data Module Packaging unit
FIP 210 mA 16 A FIP216/10-S 2 230 mA 25 A FIP225/30-S 2 230 mA 40 A FIP240/30-S 2 2100 mA 40 A FIP240/100-S 2 2
Auxiliary switch and signal contactsSDH and SDSOrder data see page 43
FI 410 mA 16 A FI416/10-S 4 130 mA 25 A FI425/30-S 4 130 mA 40 A FI440/30-S 4 130 mA 63 A FI463/30-S 4 1100 mA 40 A FI440/100-S 4 1100 mA 63 A FI463/100-S 4 1300 mA 40 A FI440/300-S 4 1300 mA 63 A FI463/300-S 4 1
Auxiliary switch and signal contactsSBH and SBSOrder data see page 41
AccessoriesOrder data from page 42
Residual current circuit-breakerSeries FIP2, FI4
Order data
2220165/C
300 mAs
30 mA10 mA
4007
4
4015
5
Delayed residual current circuit-breakerSeries FIKP2, FIK4, FIS4
Short time-delay Residual current circuit-breaker
The short time-delayed RCCB is especially suitable for unfavourable operating and mains conditions.Without influencing the personal protection function, the electronic delay suppresses unwanted ornuisance tripping, which can occur as a result of capacitive discharge currents.
Capacitive discharge currents accompanied by high current peaks can be caused by:
● Long line capacitances● Large numbers of fluorescent lamps (particularly when using electronic ballast units)● Electronic equipment and components (PC terminals, PLCs, voltage converters, etc.)● Transient line overvoltages
The short time-delay residual current circuit-breakers FIKP2 and FIK4 differ from the selective standardtype FIS4 by their significantly lower delay times. The FIKP2 and FIK4 G should therefore be used toprevent unwanted or nuisance tripping. With a preceding series connected FIS s the FIKP2 and FIK4 Gbehave in a similar, selective way to the standard FI.
Selective residual current circuit-breaker
Selective residual current circuit-breakers FIS4 s ensure selectivity with respect to following sensitive FIprotective switches.FIS4 s are only used for material protection and are therefore only available in a 300 mA version.Following FIKP2 and FIK4 likewise behave selectively if connected after an FIS4 s .
Application example for selective residual current circuit-breaker
Z20
106.
eps
FIKP2FIK4 GFI standardas personal protection
FIS4Protection of completeinstallation
Outgoing lines withoutpersonal protection
2320165/C
4007
4
4008
5
4028
9
SBHSDS
4029
1
4014
8
SDHSDS
4014
9
Delayed residual current circuit-breakerSeries FIKP2, FIK4, FIS4
Technical dataFIKP2 FIK4 FIS4
Rated voltage Un: 230 V 230/400 V 230/400 V
Rated current In (A): 40 16 40 63 25 63
Rated tripping current I∆n (mA):10 ●30 ● ● ●100 ● ●300 ●
Number of poles: 2 4 4
Frequency fn: 45… 60 Hz 45… 60 Hz 45… 60 Hz
Surge current withstand capability: 3 kA 3 kA 5 kA8/20 µs 8/20 µs 8/20 µs
Total breaking time (mean value)– for I�n 240 ms 240 ms 300 ms– for 5 I�n 35 ms 35 ms 115 ms
Delay for 5 I�n: 10 ms 10 ms 90 ms
Short-circuit capacity (kA): 10 kA 10 kA 10 kA
Cable cross-section Cu: Cable/strand Cable/strand Cable/strand– Type-S, top 25/16 mm2 25/16 mm2 25/16 mm2
– Type-S, bottom 16/10 mm2 16/10 mm2 16/10 mm2
Protection class: IP 40 IP 40 IP 40
Life endurance to BSEN 610008 BSEN 610008 BSEN 610008– Mechanical operations 4,000 4,000 4,000– Electrical operations 2,000 2,000 2,000
Climatic resistance to: BSEN 61008 BSEN 61008 BSEN 61008
Mounting position: any any any
Ambient temperature: –25 °C… +40 °C –25 °C… +40 °C –25 °C… +40 °C
Resistance to vibrations: 5g 5g 5g5… 150… 5 Hz 5… 150… 5 Hz 5… 150… 5 Hz
Standards: BSEN 61008 BSEN 61008 BSEN 61008
Approvals: SEV, VDE, ÖVE SEV, ÖVE, SEMKO SEV, ÖVE, SEMKO
Weights (approx.): 250 g 400 g 400 g
Plastic components: Free of halogens Free of halogensand cadmium and cadmium
Order dataRated tripping current Rated current Order data Module Packaging unit
FIKP2 short time-delay30 mA 40 A FIKP240/30-S 2 2
Auxiliary switch and signal contacts SDH and SDSOrder data see page 43
FIK4 short time-delay10 mA 16 A FIK416/10-S 4 130 mA 40 A FIK440/30-S 4 1100 mA 40 A FIK440/100-S 4 130 mA 63 A FIK463/30-S 4 1
FIS4 selective100 mA 25 A FIS425/100-S 4 1300 mA 63 A FIS463/300-S 4 1
Auxiliary switch and signal contacts SBH and SBSOrder data see page 41
AccessoriesOrder data from page 42
2420165/C
Residual current circuit-breakers withovercurrent protectionSeries FI-LP2, FIK-LP2
General
smissline residual current miniature circuit-breakers provide ideal protection for personnel and material inall new and existing systems.The combination of residual current and overcurrent protection in one unit makes planning simpler andalso provides economic advantages. For example, the use of a combined smissline RCBO, FI-LP2, FIK-LP2 can satisfy the minimum standard protection regulations in a home or in a specific circuit. In this casein the event of a fault current only the circuit immediately concerned is disconnected, while all othercircuits remain unaffected.
The new, short time-delay residual current circuit-breaker FIK-LP2 G is specially suitable for unfavourableoperating and mains conditions. Without influencing the personal protection function, the electronic delaysuppresses faulty tripping, which can occur as a result of capacitive discharge currents.Capacitive discharge currents accompanied by high current peaks can be caused by:
● Long line capacitances● A large number of fluorescent lamps (particularly when using electronic ballast units)● Electronic equipment and components (PC terminals, PLCs, voltage converters, etc.)● Transient line overvoltages
Major features
● Sensitive to AC and DC-pulsating fault currents● Combined overcurrent and residual-current protection in one unit● High rated breaking capacity of 10 kA● Rated residual tripping currents 10 and 30 mA● Snap-on auxiliary switch and signal contacts blocks● Short time-delay version FIK-LP2 G
4007
6
2520165/C
Residual current circuit-breakers withovercurrent protectionSeries FI-LP2, FIK-LP2
Technical data
FI-LP2 FIK-LP2
Rated voltage Un: 230 V ~ 230 V ~
Rated current In (A): 10 13 16 20 13 16 20
Trip characteristic: B, C (Page 6) C (Page 6)
Rated tripping current I�n (mA) : 10 10 10 ––30 30 30 30 30 30 30
Back-up fuse link: Page 8 (LP) Page 8 (LP)
Selectivity limits: Page 8 (LP) Page 8 (LP)
Number of poles: 2-pole (1PN) 2-pole (1PN)
Rated frequency fn: 45… 60 Hz 45… 60 Hz
Rated breaking capacity Icn: 10 kA – 230 V ~ (10–16 A) 10 kA – 230 V ~ (10–16 A) 6 kA – 230 V ~ (20–32 A) 6 kA – 230 V ~ (20–32 A)
Current limiting class: 3 3
Surge current withstand capability: 250 A-8/20ms 3 kA-8/20ms
Total disconnection time (mean value) to BSEN 61009 BSEN 61009– for I�n 40 ms 240 ms– for 5 I�n 25 ms 35 ms
Time delay for 5 I�n: – 10 ms
Cable cross-section Cu: Cable/strand Cable/strand– Type-S, top L = 25/16 mm2 L = 25/16 mm2
– Type-S, bottom L = 16/10 mm2 L = 16/10 mm2
Protection class: IP40 IP40
Life endurance BSEN 61009 BSEN 61009– Mechanical operations 4,000 4,000– Electrical operations 2,000 2,000
Climatic resistance, to: BSEN 61009 BSEN 61009
Mounting position: any any
Ambient temperature: –25 °C...+40 °C –25 °C...+40 °C
Resistance to vibrations: 5g 5g5...150...5 Hz 5...150...5 Hz
Standards: BSEN 61009 BSEN 61009
Approvals: SEV, ÖVE, VDE SEV, ÖVE, VDE
Weights (approx.): 250 g 250 g
Plastic components: Free of halogens Free of halogensand cadmium and cadmium
2620165/C
Rated tripping current Rated current Order data Module Packaging unit
FI-LP230 mA 13 A FI-LP2B13/30-S 2 210 mA 16 A FI-LP2B16/10-S 2 230 mA 16 A FI-LP2B16/30-S 2 2
Characteristic C
FI-LP210 mA 10 A FI-LP2C10/10-S 2 230 mA 10 A FI-LP2C10/30-S 2 210 mA 13 A FI-LP2C13/10-S 2 230 mA 13 A FI-LP2C13/30-S 2 210 mA 16 A FI-LP2C16/10-S 2 230 mA 16 A FI-LP2C16/30-S 2 230 mA 20 A FI-LP2C20/30-S 2 230 mA 25 A FI-LP2C25/30-S 2 230 mA 32 A FI-LP2C32/30-S 2 2
FIK-LP2 short time-delay30 mA 13 A FIK-LP2C13/30-S 2 230 mA 16 A FIK-LP2C16/30-S 2 230 mA 20 A FIK-LP2C20/30-S 2 2
Auxiliary switch and signal contactsSDH and SDSOrder data see page 41
AccessoriesOrder data from page 42
Residual current circuit-breakers withovercurrent protectionSeries FI-LP2, FIK-LP2
Order data
Circuit protection
Characteristic B
FI-LP2 230 V~, PN
4007
6
4014
8
SDHSDS
4014
9
2720165/C
Residual current sensorRC sensor FISG
General
The FISG is specifically prescribed or at least recommended for many applications. In some systems,however, there could be a danger to persons, animals or material by the tripping of a residual currentcircuit-breaker with the associated interruption of circuits. The RC-sensor is ideal for systems of this kind.It has a permanent auxiliary contact on the left-hand side, and the main circuits are not switched forthe reasons mentioned. This contact is used to operate an optical or acoustic signalling device if residualcurrents with dangerous magnitudes flow to earth.
Important note
The FISG is not a protective device in the sense of the regulations, but it is able to detect and signalresidual currents immediately. The FISG can be recognised by the red operating lever whichdistinguishes it clearly from current circuit-breakers.
Technical dataFISG
Rated voltage Un: 230/400 V
Rated current In: 40, 63 A
Rated tripping current I�n : 30 mA, 300 mA s
Auxiliary contact rated current: 1 SBH11 permanently fitted at side incl.. ZLS 930– Ith: 6 A– AC15: 2 A/230 V~ 0.5 A/400 V~
Application
● Medical devices and equipment (hospitals, etc.)● Heating, air-conditioning and ventilating systems● Cooling systems● Pump systems with important functions● Street and building site lighting● Chemical companies● Electroplating companies● Dairy plants● Joinery and wood-working● Traffic control systems
Connection example
4078
0
Rated tripping current Rated current Order data Module Packaging unit
30 mA 40 A FISG440/30-S 5 130 mA 63 A FISG463/30-S 5 1300 mA s 63 A FISG463S/300-S 5 1
One auxiliary contact SBH11 is already fitted on the unit.Further auxiliary contacts can be snapped-on.Order data see page 41
AccessoriesOrder data from page 42
Order data
Z20
019.
eps
acoustic optical
signalling
2820165/C
Residual current circuit-breaker FI4Special designs 162/3 Hz and 400 Hz
General
For special applications, where the mains frequency is other than 50 Hz, corresponding residual currentcircuit-breakers are required. CMC offers a suitable range of special designs for these cases.
Major features
● Sensitive to AC and pulsating-DC current● 4-pole breaker types● Rated tripping currents 30 and 300 mA● Snap-on auxiliary and signal contacts● Rated currents 25, 63 A
Technical data
FI4 162/3 Hz FI4 400 Hz
Rated voltage Un: 230/400 V 230/400 V
Rated current In (A): 25 63 25 63
Rated tripping current I�n (mA):30 ● ●50 ● ●300 ● ● ● ●
Number of poles: 4 4
Frequency fn: 15…18 Hz 360…440 Hz
Surge current withstand capability: 250 A 250 A8/20 µs 8/20 µs
Total disconnection time (mean value)– for I�n 40 ms 40 ms– for 5 I�n 25 ms 25 ms
Delay time for 5 I�n: – –
Short-circuit capacity (kA): 6 kA 6 kA
Cable cross-section Cu: Cable/strand Cable/strand– Type-S, top 25/16 mm2 25/16 mm2
– Type-S, bottom 16/10 mm2 16/10 mm2
Protection class: IP 40 IP 40
Life endurance to BSEN 61008 BSEN 61008– Mechanical operations 4,000 4,000– Electrical operations 2,000 2,000
Climatic resistance to: BSEN 61008 BSEN 61008
Mounting position: any any
Ambient temperature: –25 °C… +40 °C –25 °C… +40 °C
Resistance to vibrations: 5 g 5 g5… 150… 5 Hz 5… 150… 5 Hz
Standards: BSEN 61008 BSEN 61008
Approvals: SEV SEV
Plastic components: Free of halogens Free of halogensand cadmium and cadmium
4041
7
2920165/C
Rated tripping current Rated current Order data Frequency Module Packaging unit
162/3 Hz30 mA 25 A FI4-LF25/30-S 162/3 Hz 4 5300 mA 25 A FI4-LF25/300-S 162/3 Hz 4 530 mA 63 A FI4-LF63/30-S 162/3 Hz 4 5300 mA 63 A FI4-LF63/300-S 162/3 Hz 4 5
400 Hz50 mA 25 A FI4-HF25/50-S 400 Hz 4 5300 mA 25 A FI4-HF25/300-S 400 Hz 4 550 mA 63 A FI4-HF63/50-S 400 Hz 4 5300 mA 63 A FI4-HF63/300-S 400 Hz 4 5
Auxiliary and signal contactSBH and SBSOrder data see page 41
Residual current circuit-breaker FI4Special designs 162/3 Hz and 400 Hz
Order data40
289
SBHSBS
4029
1
4041
7
3020165/C
Motor protection circuit-breaker MS325Series MS 325
General
The MS325 is a circuit-breaker with a motor protection characteristic. It is intended above all forindustrial applications (MCC) or in distribution systems without a back-up fuse. It also fulfils its traditionalfunction to provide thermal overload protection and short-circuit protection for other sectors of installationtechnology.
Major features
● Compact construction● Very high rated breaking capacity● Clear indication of switching position● Phase failure protection● Temperature compensation● Test release possibility● Provision for snap-on undervoltage release● Snap-on auxiliary and signal contact blocks● Further accessories
Technical data
MS325
Rated voltage Un: 690 V~
Rated current In (A):(14 adjustment ranges 0,1...25 A): 25
Number of poles: 3
Rated frequency fn: 50...60 Hz
Rated breaking capacity Ics: 100/50 kA
Total disconnection time with short-circuit(50 kA/25 A range): 1.5 ms
Cable cross-section Cu cable or strand– Type-S, top: 1 x 10 mm2 / 2 x 4 mm2
– Type-S, bottom: max. 4 mm2
Protection class: IP20
Life endurance– Electrical operations: 100,000 (25 A, AC-3)– Mechanical operations: 100,000
Climatic resistance: IEC/CEI 68-2-30
Mounting position: any
Ambient temperature: –25 °C...+50 °C
Temperature compensation: –25 °C...+50 °C
Resistance to vibrations: 5g (50 m/s2)5...150...5 Hz
Standards: IEC 157-1, 292-1, 337-1VDE 0660, IEC 947-2, 947-4-1947-5-1 VDE 0106 Part 100SEV 1090-1, 1092-1, 1093-1
Approvals: SEV, KEMA, UL CSA
Weights (approx.): 340 g
Plastic components: Free of halogensand cadmium
4007
3
3120165/C
Motor protection circuit-breaker MS325Rated breaking capacity
Rated breaking capacity tests to IEC 947-2
Test sequence Service short circuit breaking capacity ICS Ultimate short circuit breaking capacity ICU
1. Overload release check – 2 x In
2. Short circuit test sequence O-CO-CO O-CO
3. Insulation strength 2 x Un* 2 x Un*
4. Temperature Rise Terminals, � 80K, Operating means � 35K –
5. Calibration check current 1.45 x In 2 x In
* or 1000 V, whichever is the greater.
Rated breaking capacity to IEC 947-2
Thermal release, Magnetic release, Service breaking capacity IcsAdjustment ranges Response current
(mean value) independentof thermal setting 230 V~ 400 V~ 500 V~ 690 V~
(A) (A) (kA) (kA) (kA) (kA)
0.1 – 0.16 1.6 100 100 100 1000.16 – 0.25 2.5 100 100 100 1000.25 – 0.4 4 100 100 100 1000.4 – 0.63 6.3 100 100 100 1000.63 – 1 12 100 100 100 1001 – 1,6 19 100 100 100 1001.6 – 2.5 30 100 100 100 402.5 – 4 48 100 100 60 104 – 6.3 75 100 100 40 76.3 – 9 108 100 100 30 59 – 12.5 150 100 75 27 4,512.5 – 16 192 100 60 25 416 – 20 240 100 55 22 3,520 – 25 300 100 50 20 3
Back-up protection
Maximum rated tripping currents
a) If the short-circuit current at the place of installation of a motor protection circuit-breaker MS325 is not higher than the specified servicebreaking capacity, a back-up fuse link can be omitted. If a back-up fuse is fitted for installation reasons, its rated current may be selected ashigh as required.
b) If the short-circuit current at the place of installation of a motor protection circuit-breaker MS325 is higher than its service breaking capacity,the rated current of the back-up fuse link must not exceed that given in the following table.
Thermal release, Magnetic release, Maximum rated tripping current of precedingAdjusting ranges Response current (mean value) back-up fuse gG
independent ofthermalsetting 690 V~ 500 V~ 400 V~ 230 V~
(A) (A) (kA) (kA) (kA) (kA)
0.1 – 0.16 1.60.16 – 0.25 2.50.25 – 0.4 40.4 – 0.63 6.30.63 – 1 12 Short-circuit-proof: no preliminary fuses necessary1 – 1.6 191.6 – 2.5 30 252.5 – 4 48 404 – 6.3 75 406.3 – 9 108 50 509 – 12.5 150 50 80 8012.5 – 16 192 50 80 10016 – 20 240 50 100 10020 – 25 300 50 125 125
3220165/C
The motor protection circuit-breaker MS325 is suitable for DC applications, DC1-DC5 operation.On DC the electromagnetic release responds to values 1.35 times higher than at 50 Hz. The polarity is immaterial when connecting.The MS325 can be used with the following voltages:
Thermal release, Magnetic release, Max. voltage Ue 3 poles in series Rated breaking capacityAdjustment ranges Response current1) (mean value)
independent of thethermal setting
(A) (A) (V=) (kA)
0.1 – 0.16 2.2 450 1000.16 – 0.25 3.4 420* 1000.25 – 0.4 5.4 330* 1000.4 – 0.63 8.5 270* 1000.63 – 1 16 450 1001 – 1.6 26 450 1001.6 – 2.5 40.5 450 502.5 – 4 65 450 504 – 6.3 101 450 306.3 – 9 146 450 209 – 12.5 202.5 450 2012.5 – 16 260 450 1016 – 20 325 450 1020 – 25 405 450 10
* a special design for 450V= is available
1) Values for resistive and inductive loads, T = 15 ms
Direct starter, co-ordination to IEC 947-4-1Normal start – 400 V – 50 Hz, ambient temperatures � 40 °C
50 kA type 1/type 2
Motor Motor protection Contactor Contactor Copper cable Max. permissiblecurrent for thiscombination
Power Ie Type Range of adjustment Type 1 Type 2 Minimum cablekW A A cross-section in mm2 A
0.37 1.2 MS 325 – 1.6 1.0 – 1.6 A 9 A 9 1.5 1.60.55 1.5 MS 325 – 1.6 1.0 – 1.6 A 9 A 9 1.5 1.60.75 2 MS 325 – 2.5 1.6 – 2.5 A 9 A 9 1.5 2.51.1 2.6 MS 325 – 4.0 2.5 – 4.0 A 9 A 12 1.5 4.01.5 3.5 MS 325 – 4.0 2.5 – 4.0 A 9 A 26 1.5 4.02.2 5 MS 325 – 6.3 4.0 – 6.3 A 9 A 26 1.5 6.33 6.6 MS 325 – 9.0 6.3 – 9.0 A 9 A 26 1.5 9.04 8.5 MS 325 – 9.0 6.3 – 9.0 A 9 A 26 1.5 9.05.5 11.5 MS 325 – 12.5 9.0 – 12.5 A 12 A 26 1.5 12.07.5 15.2 MS 325 – 16.0 12.5 – 16.0 A 16 A 26 2.5 16.0
11 22 MS 325 – 25.0 20.0 – 25.0 A 26 A 26 2.5 25.0
Ambient temperature � 30 °C
Connection of single-phase motors for 230 V~
Motor protection circuit-breaker MS325DC operating voltages and rated breaking capacities
M230 V ~
for:● Oil burner motors● Small fans● Valve motors● Conveyor pumps● Special drives● Batching systems, etc.
Circuit-breakers ready for fitting with special base-plate and thecorresponding plug contacts (L1 and N), according to order data page 35.
Z20
023.
eps
3320165/C
4016
0
4007
3
400 V~ 3P
4028
9
SBHSBS
4029
1
4015
0
4015
6
4015
1
Motor protection circuit-breaker MS325
Order data
Adjustment ranges in A Order data Module Packaging unit
0.1 – 0.16 MS325-0.16-S 3 10.16 – 0.25 MS325-0.25-S 3 10.25 – 0.4 MS325-0.4-S 3 10.4 – 0.63 MS325-0.63-S 3 10.63 – 1 MS325-1-S 3 11 – 1.6 MS325-1.6-S 3 11.6 – 2.5 MS325-2.5-S 3 12.5 – 4 MS325-4-S 3 14 – 6.3 MS325-6.3-S 3 16.3 – 9 MS325-9-S 3 19 – 12.5 MS325-12.5-S 3 112.5 – 16 MS325-16-S 3 116 – 20 MS325-20-S 3 120 – 25 MS325-25-S 3 1
Adapter plate for contact tobusbars with plug contacts Order data Packaging unit
– 3L ZMS915 10– 3L+N (20A reduced) ZMS923 10– 2L (reversible) ZMS919 10– 1L+N (reversible) ZMS920 10
Auxiliary switch and signal contactSBH and SBSOrder data see page 41
AccessoriesOrder data from page 42
Technical data
Rated voltage Un
– Voltage tap in MS325: 400 V~ or 230 V~– With connection leads 200 mm long (external voltage): AC voltage
Rated frequency: 50...60 Hz
Power consumption: 0,8 W
Actuation voltage (to IEC 292-1)– dropout: 0.1...0.75 Un
– pickup: > 0.85 Un
Duty cycle: 100%
Dimensions B x H x L: 20.4 x 15 x 50.6 mm
Weight: 20 g
Undervoltage release (UA)for insertion in smissline MS325– 400 V~ SMUA400 1– 230 V~ SMUA230 1
Connection supportsnap-on to smissline MS325Width 9 mm– for undervoltage release with external voltage AS 10
Dummy housingSide attachment on left to bring up to 18 mm ZLS930 10
3420165/C
Surge arrester SA4 SC/SA4General
Product description
The surge arrester «SA4/SA4 SC» is a 4-pole arrester meeting the requirements of class C to DIN VDE0675 Part 6, Part 6/A1 and Part 6/A2. It also complies with requirement class II of the internationalstandard II IEC 61643-1 (1998-02).The SA4 SC is used for the protection of low voltage consumer systems and equipment from overvoltages(DIN VDE 100) caused by remote lightning strikes or switching operations.A typical place of application is the low voltage main and subsidiary distributor, where the arrester isattached directly to the smissline busbar system.If the unit is connected correctly, the green operating lamp (LED) lights. The protection elements areprovided with thermal monitoring according to the current guidelines. In the event of an overvoltage theprotective element is disconnected from the mains and the operating lamp changes from green to red.Actuation of the mechanism can be indicated remotely via the integrated telemetry contact.This remote display is only available with the SA4 SC.
Display and maintenance
The protective elements (high power varistors) are monitored thermally. In the event of a fault this monitordisconnects the overloaded high power varistors automatically from the power supply and the operatingindication changes from green to red. This status is also indicated by the telemetry contact. In this casethe arrester should be exchanged immediately, since the following units are no longer protected againstovervoltage.If the operating indication is neither green nor red, then the connections must be checked for the presenceof the supply voltage should also be tested for.
The surge arrester requires no maintenance. A regular visual check is recommended.
Caution: For measurements of insulation in the electrical system the arrester should be disconnectedfrom the power supply, since otherwise the result can be affected by the arrester characteristics.The sticker enclosed with the corresponding note should be placed in a clear position on the distributionboard.
Dimensioning of earth conductorThe SA4/SA4 SC should be connected by the shortest possible route to the potential equalization.The earth conductor supplied with the unit can be used for this purpose. The connection must be asshort as possible. The minimum cross-section is 6 mm2.
Line routingProtected and unprotected lines (including outgoing conductors for potential equalizing) must not be laidclosely parallel. They must be separated in space or by screening, so that no overvoltage coupling fromunprotected to protected lines is possible. Line junctions must be made at right angles.
Assembly
Installation and electrical connectionThe surge arrester «SA4/SA4 SC» is installed at the input of the distribution board supplying theinstallation to be protected. It is snapped directly onto the smissline busbars immediately following theincoming power supply unit. The earth terminal of the arrester must be connected to the installation mainearthing terminal by the shortest possible route, as close as possible to the earthing conductor of theinstallation, using a conductor (as supplied) of cross section no less than 6 mm2. The operating lamp willonly show green if the connection is correct and the arrester is fully serviceable.
4073
0
3520165/C
Surge arrester SA4 SC/SA4Technical data
Surge arrester TN-S network
F1
L1
L2
L3
PE
N
Z20
013.
eps
L1
main earthing terminal bar
Connection with pre-assembled conductoror shorter
ABBSA4 SC
L2 L3 N
11 12 14
Surge arrester TN-C network
F1
L1
L2
L3
PEN
Z20
012.
eps
L1
main earthing terminal bar
Connection with pre-assembled conductoror shorter
ABBSA4 SC
L2 L3 N
11 12 14
3620165/C
Surge arrester SA4 SC/SA4
Technical data
Rated voltage: UN 230 / 400 V AC
Rated voltage: UC 275 V AC
Requirement class: to VDE 0675, Part 6 CRequirement class: to IEC 61643-1 (1998-2) II
Rated surge arrester current: Isn (8/20) multi shot 15 kA
Max. surge arrester current: Ismax (8/20) single shot 30 kA
Protection level: Up for Isn � 1.5 kVUp for Is = 5 kV � 1 kV
Response time: ta � 25 ns
Leakage current to PE (3 phase): � 1 mA
Cable cross-section: L1/L2/L3 N 16 mm2 cable / 10 mm2 litz wirePE/11/12/14 25 mm2 cable / 16 mm2 litz wire
max. pre-fusing: 125 A gL/gG / 25 kA
Telemetry contact: max. operating voltage 250 V ACmax. switching current 2 A1 changeover S11/S12 N/C, S11/S14 N/O
Temperature range: –25 ... + 60 °C
Protection class: IP 20
Limit surge arrester current per unit: Isg (8/20 µs) 90 kA
Plastic components: Free of halogens and cadmium
Order data
Type Order data Modules Packaging unit
With integrated telemetry contact SA4 SC-S 4 1
Without integrated telemetry contact SA4 4 1
AccessoriesOrder data from page 45
4073
040
731
SA4without integratedtelemetry contact
SA4-SCwith integratedtelemetry contact
3720165/C
4028
9
SBH
Load switch IS463
General
The load switch can be used instead of an incoming terminal block up to 63 A in the smissline socketsystem.The external shape and dimensions correspond with the 4-pole residual-current circuit-breaker.
The smissline IS463 load switch can be used to disconnect or connect individual loads, groups of loads orcomplete sections of the system to the power supply.
Major features
● As power supply switch● On-Off switch function● Clear switch position indication● Snap-on auxiliary contact possible● Uniform smissline design
Technical dataLoad switch IS463
Rated voltage Un: 230/400 V~
Rated current In: 63 A
Number of poles: 4
Cable cross-section Cu: Cable/strand– Type-S, top: 25 / 16 mm2
– Type-S, bottom: 16 / 10 mm2
Protection class: IP40
Life endurance mechanical/electrical: 5000 switching cycles
Mounting position: any
Ambient temperature: –25 °C...+40 °C
Standards: EN 60947
Approvals: SEV/ASE/ÖVE
Weight (approx.): 250 g
User category: AC22-A
Plastic components: Free of halogens and cadmium
Order data
Order data Modules Packaging unit
IS463-S 4 1
Auxiliary switch and signal contactSBHOrder data see page 41
AccessoriesOrder data from page 42
4015
7
3820165/C
Auxiliary switch and signal contacts
General
The auxiliary switch and signal contacts are snapped onto the left of the protective device in each case.For auxiliary and signal contacts powered via smissline auxiliary busbars LA or LB, the desired number ofcontact pins must be ordered at the same time as the device. In addition, a low current power supply maybe taken via these switches.
Function
The auxiliary contact works similarly to the main contacts. The signal contact only operates when theprotective device trips.This can be simulated with the grey test button. After each trip, the signal contact should be returned tothe starting position with the orange reset button. Auxiliary and signal contacts have contacts whichensure high switching reliability, even in systems with low voltages or low currents (PLC, signal systems,etc.).
Auxiliary contacts SDH and SBH switch at the same time as the contacts of the protective device(operated manually or automatically).
Closing contactNO joint-switching
Opening contactNC counter-switching
Signal contacts SDS and SBS switch only when the protective device is electrically tripped due to short-circuit, fault current or overcurrent (undervoltage for MS325).
Closing contactNO closes on automatic trip
Opening contactNC opens on automatic trip
4014
840
149
4028
940
291
3920165/C
Auxiliary switch and signal contactsMounting possibilities
Unit type Auxiliary contacts Signal contacts Unit switch position when assembled
Miniature circuit-breaker– LP... SDH... SDS... OFF
Residual-current circuit-breaker– FIP2 / FIKP2 / FI-LP2 / FIK-LP2 SDH... SDS... OFF
Residual-current circuit-breaker– FI4 / FIK4 / FIS4 SBH... SBS... OFF– FISG SBH... at factory integrated
Load switch– IS463 SBH... not possible OFF
Motor-protection switch– MS325 SBH... SBS... OFF
● All additional contacts are always fitted on the left of the protective device.● When an auxiliary switch and a signal contact block are used, the signal contact block must be first, snapped directly onto
the circuit-breaker.● It is not possible to mount two signal contact blocks on the same circuit-breaker.● Additional contacts of series SDH..., SDS... and SBH..., SBS... are mounted onto circuit-breakers in the «off» position.
The following can be mounted on each circuit-breaker:1 auxiliary switch block
or 1 signal contact blockor 2 auxiliary contact blocksor 1 auxiliary switch and 1 signal contact block
Auxiliary switch block
Signal contact block
SDH 11
SDH 20
SDH 02
SDH13
14
21
22
11
12
21
22
13
14
23
24
SBH 11
SBH 20
SBH 02
SBH13
14
21
22
11
12
21
22
13
14
23
24
SDS 11
SDS 20
SDS 02
SDS97
98
05
06
95
96
05
06
97
98
07
08
SBS 10
SBS 01
SBS97
9895
96
Z20
024.
eps
4020165/C
Auxiliary switch and signal contactsTechnical data
SDS /SBS SDH /SBH
Rated voltage Un: 400 V 400 V
Rated current:– Ith: 6 A 6 A– AC15 2 A/230 V / 1 A/400 V 2 A/230 V / 0,5 A/400 V– DC13 0.5 A/125 V= 0.5 A/125 V=
Minimum value (contact security): 10 mA 12 V= 10 mA 12 V=
Cable cross-section: 2 x 2.5 mm2 strand with end ferrule 2 x 2.5 mm2 strand with end ferrule
Plastic components: Free of halogens and cadmium Free of halogens and cadmium
Power supply variants in socket system
Power can be supplied to the auxiliary switch and signal contact blocks in various ways:
1. Conventional power supply by single wire or stranded wire
2. Power supply to the auxiliary busbars LA or LB via the auxiliary terminals in the power supply block
3. Connection support and auxiliary or signal contact block with power supply via auxiliary busbars LA and return via LB
Z20
025.
eps
4120165/C
Auxiliary switch and signal contacts
4014
8
4014
9
4015
040
151
4015
2
4028
9
SBHSBS
4029
1
SDHSDS
Order data
Mounted on: Order data Module Packaging unit
Miniature circuit-breaker LPAuxiliary switch contact block SDH1S and 1 Ö SDH11 0.5 102S SDH20 0.5 102Ö SDH02 0.5 10
Signal contact block SDS1S and 1 Ö SDS11 0.5 102S SDS20 0.5 102Ö SDS02 0.5 10
MS325, FI4, FIK4, FIS4, IS463, FISGAuxiliary switch contact block SBH1S and 1 Ö SBH11 0.5 102S SBH20 0.5 102Ö SBH02 0.5 10
MS325, FI4, FIK4, FIS4Signal contact block SBS1S SBS10 0.5 101Ö SBS01 0.5 10
Auxiliary switch and signal contactsConnection support
ZMS400 0.5 10
Auxiliary switch and signal contacts, connection supportDummy housingEqualization to 18 mm ZLS930 0.5 10
Auxiliary switch and signal contacts, connection supportContact pin, shortfor power supply via auxiliary busbars ZLS630 10
4220165/C
The modules are snapped directly onto the socket.
4028
7
4028
5
General
The advantage of the Combi modules is that any desired combinations of smissline units can be formedinto a unit with conventional devices. These can be replaced very quickly and keeps the downtime ofsystems to a minimum.
The Combi module is a mounting plate of 4 or 8 modules (PLE). The lower part is snapped directly ontothe smissline socket. The upper part is supported by a snap fastening on an additional DIN profile rail.The rail separation is fully variable between 125 and 150 mm.
The power supply is taken directly from the busbars at the back of the Combi module by means of anadapter plate, rated current 32 A, and fed by stranded wires to the input terminal of the unit. Auxiliary andsignal contacts can also be contacted on the auxiliary rails LA and LB.
Two versions of Combi modules are available. If more space is required, two modules can be permanentlyconnected side by side (Combi module Duo).
Selection table for mounting accessories required
smissline-T equipment MS325 3L MS325 3L+N
Adapter plate ZMS915 ZMS923Fastening ZLS518 ZLS518
Application examples from practice:
Combi-modules
4015
8
4015
9
4320165/C
4016
040
165
4015
2
4016
6
4015
9
4015
8
Combi-module
Order data
Order data Module Packaging unit
Combi module single containing:– Combi module ZLS802 4 6– DIN-profile 60 mm
Combi module DUO containing:– Combi module ZLS805 8 3– DIN-profile 133 mm
Adapter platefor contacts with busbars with plug contacts3L ZMS915 103L+N (20A reduced) ZMS923 10L1, N (In max. 20A) ZMS916 10L2, N (In max. 20A) ZMS917 10L3, N (In max. 20A) ZMS918 10L1 (In max. 32A, L1 reversible to L2, L3) ZMS920 103L+N ZMS926 10
FixierungThe fastener is required to attach the units to the combi-module.for MCBs ZLS517 1Bag of 10Stop-piece for 1-pole LP ZLS516 1
for MS or MCB ZLS518 1Bag of 10
Auxiliary switch and signal contact, connection supportContact pin, longfor use with Combi module ZLS520 10
Rafix for LPThis is required when fitting a miniature circuit-breaker smissline on to DIN rail.Bag of 10 ZLS923 1
4420165/C
4041
4
SocketsAccessories
Socket bases
The smissline-S socket system brings a completely new mounting and connection technique to distribu-tion construction. Besides the classical method of snapping units onto a 35 mm Din rail, this new family ofdevices can be snapped directly onto socket bases containing busbars. This eliminates the time consum-ing process of making cable or bolted connections to the power supply. In addition, in the event of re-arrangement or expansion, the replacement of devices in existing systems is made significantly easier.The socket sections and the wide range of accessories make it possible to plan with the capability forexpansion and to construct distribution systems of any desired size in a short period of time.
The 6- or 8-module sockets are installed either by screwing them onto any flat surface or by snappingthem onto a 35 mm DIN rail.Lateral movement or detachment of the sockets again is possible before final fixing.
To determine the required socket length the space required for● the required components● the feeder block and● spare positions must be determined.(table pages 55 and 56)
Snap mounting
Pull down the slide with a screwdriver until it latches (socket can be moved)
Press on front:Fixed position(Sockets fixed)
Major features
● Expansion to any desired length (even number of poles)● Integral busbars● Simple exchange of units● Long-term planning and problem-free extension possible● Significant time savings for mounting and connection
Technical data
Sockets
Rated voltage Un: 690 V~
Rated current In:– Busbars: 100 A– Auxiliary busbars: 40 A
Socket length (modules)– 6-module socket length 108 mm: 6– 8-module socket length 144 mm: 8
Fastening: Snapped onto 35-mm mounting railsand screw fixing
Plastic components: Free of halogens and cadmium
Order data
Order data Module Packaging unit
Socket base(Socket selection table see pages 55 and 56)- 8-module socket length 144 mm ZLS 808 8 10- 6-module socket length 108 mm ZLS 806 6 10
4077
140
772
4520165/C
4091
9
4018
240
180
4017
0
4018
3
4017
1
SocketsAccessories
Socket end-pieceTo prevent displacement of sockets and busbars (particularly when installed vertically) end-pieces can befitted at the start and finish of each row of sockets. These simultaneously ensure electrically protectedcovering of the busbar end faces and mechanical fixing of the sockets on the mounting rail.
Order data Module Packaging unit
Socket end-piecefor lateral, electrically-protected closure and ZLS730 – 2 pieces (left, right)mech. fixing of a row of sockets on the supportingrail. Width: 20 mm
Intermediate pieceThe light-grey intermediate piece matches the unit profile and fills empty module spaces. The busbarsare safely covered, so that they cannot be touched and at the same time the corresponding holes in thecover is filled up.
Order data Module Packaging unit
Intermediate piecelight-grey for electrically-protected filling of ZLS722 1 1spare socket position, 18 mm– Bag of 5
Busbar insulatorThe dark grey busbar insulator electrically isolates the interrupted busbar ends from each other, (e.g. inthe case of several residual-current circuit-breaker groups) and simultaneously identifies the isolationpoint. It conforms with the unit profile and its space requirement is 1 module.
Order data Module Packaging unit
Busbar insulatordark grey, for isolation and spacing of the ZLS239 1 10busbar interruption at the isolation point, 18 mm
Busbar coverIf component modules or spare modules are not required, the busbar cover ensures electrically-protectedcovering of the main and auxiliary busbars. The cover (4 modules) can be divided anywhere. The openingsallow voltage measurements on the busbars without removing cover.
Order data Module Packaging unit
Busbar coverelectrically-protected covering of busbars, ZLS100 1 14-module, can be divided. Suitable to acceptextension adapter ZLS101 4 x 18 mm– Bag of 5
Extension adapterThe extension adapter, single or several side by side, can be plugged into the busbar cover via the built-inholding device. This enables conventional DIN devices with 45 mm cap size to be snapped onto thesmissline socket. By plugging in several extension adapters one on top of the other, heights can beequalized in multiples of 7 mm.
Order data Module Packaging unit
Extension adapter18 mm wide, for plugging into busbar cover ZLS101 1 10ZLS100. For fixing REG units
Mounting rail adapterHeight equalization of 22.5 mm to equalize the insertion depth of mounting rail devices alongsidesmissline devices. (With the mounting rail adapters, a DIN mounting rail can be built up higher adjacent tosmissline sockets; in this way smissline and conventional devices can be combined without difficulty).
Order data Module Packaging unit
Mounting rail adapterHeight equalization 22.5 mm, for equalizing insertion depth ZLS741 1 10of mounting rail devices alongside smissline units
4620165/C
4027
7
Starter packAccessories
Starter pack General
Starter packs are available comprising socket bases with 3 or 4 main busbars already inserted asrequired. Two end pieces are also included.
Order data
Solutions available: Order data Module Packaging unit
Starter pack with 22 modules 393 mm 3P ZLS760 1Starter pack with 22 modules 393 mm 3 P + N ZLS761 1Starter pack with 24 modules 429 mm 3P ZLS750 1Starter pack with 24 modules 429 mm 3 P + N ZLS751 1Starter pack with 30 modules 537 mm 3 P ZLS762 1Starter pack with 30 modules 537 mm 3 P + N ZLS763 1Starter pack with 32 modules 573 mm 3P ZLS752 1Starter pack with 32 modules 573 mm 3 P + N ZLS753 1Starter pack with 38 modules 681 mm 3P ZLS764 1Starter pack with 38 modules 681 mm 3 P + N ZLS765 1Starter pack with 40 modules 717 mm 3P ZLS754 1Starter pack with 40 modules 717 mm 3 P + N ZLS755 1Starter pack with 48 modules 861 mm 3P ZLS756 1Starter pack with 48 modules 861 mm 3 P + N ZLS757 1Starter pack with 64 modules 1150 mm 3P ZLS766 1Starter pack with 64 modules 1150 mm 3 P + N ZLS767 1Starter pack with 80 modules 1438 mm 3P ZLS758 1Starter pack with 80 modules 1438 mm 3 P + N ZLS759 1
Busbars for the sockets and additional socket
The busbars of size 10 x 3 mm can be loaded with currents up to 100 A. They are electroplated for perfectcontact with unit plug contacts. The maximum available busbar length is 1983 mm. The same busbar typeis used regardless of whether it is internally in the socket (L1, L2, L3, N) or externally in the additionalsocket (N, PE). The busbars are inserted in to the socket from the front.
Order data Module Packaging unit
Busbars 100 Aelectroplated, 10 x 3 mm, for L1, L2, L3, N and PE ZLS200 110 10– Delivery length 1979 mm
Auxiliary busbars for the sockets
The 5 x 2 mm auxiliary busbars are intended for a common power supply to auxiliary switches and signalcontacts. They are also electroplated and are supplied in a maximum length of 1983 mm.Like the main busbars, the auxiliary busbars are inserted in holders LA and LB from the front. Naturallyonly one auxiliary busbar can be fitted.
Order data Module Packaging unit
Auxiliary busbars 40 Aelectroplated, 5 x 2 mm, for LA and LB ZLS202 110 10– Delivery length 1979 mm
4017
540
174
4720165/C
Adapter 32A and 63AAccessories
General
The incoming terminal component for non smissline devices has an installation width of one moduleof (18 mm). This adapter can be combined to multiple pole versions to meet specific needs (L1, L2, L3, N,dummy). The connecting wires can carry a maximum of 63A (In).
Order data of Adapter 32A and 63A
Description Order data Module Packaging unit
Single Adapter 32A bottom feedAdapter 32A L1 bottom feed ZLS161 1 1Adapter 32A L2 bottom feed ZLS162 1 1Adapter 32A L3 bottom feed ZLS163 1 1Adapter 32A N bottom feed ZLS160 1 1Adapter dummy element ZLS164 1 1
Single Adapter 32A top feedAdapter 32A L1 top feed ZLS177 1 1Adapter 32A L2 top feed ZLS178 1 1Adapter 32A L3 top feed ZLS179 1 1Adapter 32A N top feed ZLS176 1 1
Combination 32A bottom feedAdapter 32A L1, N bottom feed ZLS180 1 1Adapter 32A L2, N bottom feed ZLS181 1 1Adapter 32A L3, N bottom feed ZLS182 1 1Adapter 32A L1, L2, L3 bottom feed ZLS183 1 1Adapter 32A L1, L2, L3, N bottom feed ZLS184 1 1
Single Adapter 63A bottom feedAdapter 63A L1 bottom feed ZLS171 1 1Adapter 63A L2 bottom feed ZLS172 1 1Adapter 63A L3 bottom feed ZLS173 1 1Adapter 63A N bottom feed ZLS170 1 1Adapter dummy element ZLS164 1 1
Single Adapter 63A top feedAdapter 63A L1 top feed ZLS167 1 1Adapter 63A L2 top feed ZLS168 1 1Adapter 63A L3 top feed ZLS169 1 1Adapter 63A N top feed ZLS166 1 1
Combination 63A bottom feedAdapter 63A L1, N bottom feed ZLS186 1 1Adapter 63A L2, N bottom feed ZLS187 1 1Adapter 63A L3, N bottom feed ZLS188 1 1Adapter 63A L1, L2, L3 bottom feed ZLS189 1 1Adapter 63A L1, L2, L3, N bottom feed ZLS190 1 1
Combination set for multiple pole adapter ZLS174 1 1(Packets with 100 pieces for 50 adapters)
4091
3
4091
440
915
4094
1
4092
0
4091
8
4820165/C
AdapterAccessories
General
The adapter is designed for a rated current of 100A and is a plug-in module used to supply power directlyto the smissline system. The adapter can accommodate an ABB OT-M load switch with a rated currentof 80A or 100A. Power supply to the smissline system is therefore possible via a load switch. Theconstruction height of the adapter is 13 mm, which means that devices on the adapter have a 13-mmhigher shoulder than smissline devices plugged-in directly.
Major features
● Plug-in adapter solution for rated currents up to 100A● Power supply to smissline-S system via ABB load switch OT-M● Same construction height as 32A and 63A adapters for smissline-S
Technical data
Rated voltage Un: 400/690 V
Rated short-time current withstand capability Icw: 6kA
Rated current In: 100A
Space required (module): 4 (72 mm)
Rated insulation voltage Ui: 2500 V
Rated withstand voltage strength Uimp: 8000 V
Ambient temperature: 30 °C
Oder data
Type Order data Modules Packaging unit
Adapter with 3 connector leads ZLS240 4 1(L1, L2, L3)
Adapter with 4 connector leads ZLS241 4 1(L1, L2, L3, N)
SwitchLine load break switch OT-M
General
ABB SwitchLine OT-M load break switches are suitable for installation on smissline 100A externaladapters.
Order data
Type Number of poles le Th Rated current Rated current Connection400V AC22/400V AC23/400V mm2
A A A
OT80M3 3 80 80 45 2.5...50OT100M3 3 100 100 55 2.5...50OT80M4 4 80 80 45 2.5...50OT100M4 4 100 100 55 2.5...50
4092
540
926
4098
2
4098
1
4920165/C
4026
940
271
Incoming terminal blockAccessories
General
This incoming terminal block is used to connect cables dirctly to the busbars. The base-plate can be fittedwith a maximum of 4 main terminals L1, L2, L3 and N for the busbars, and 2 auxiliary terminals LA and LBfor the auxiliary busbars. The terminals act directly on the busbars and therefore fix the incoming terminalblock. Removable terminal tops permit the connection of continuous conductors (risers) while horizontalor vertical cable entry is also possible. The cover can be labelled.Instead of the incoming terminal block, the power supply can also be made via a unit (e.g. residual currentcircuit-breaker, miniature circuit-breaker or load switch).
Major features
● Horizontal or vertical connection● Connection of continuous conductors possible● Labelled cover● Power supply also possible via a unit
Standard incoming terminal blockA standard incoming terminal block whose cover provides protection against accidental contact.Construction height 50 mm. The base-plate can be fitted with a maximum of 4 main terminals L1, L2, L3and N for the busbars, and 2 auxiliary terminals LA and LB for the auxiliary busbars.
Incoming terminal block, lowFeeder block of construction height 36 mm. Auxiliary terminals LA and LB cannot be used.
Technical dataIncoming terminal block
Rated voltage Un: 400/690 V~
Rated current In:– Main terminals: 160A– Auxiliary terminals: 40A
Space required (modules): 4
Main terminals Cu: Cable Strand50 (2 x 25) (160A) 35 mm2 (125A)
Auxiliary terminals Cu: 10 6 mm2
Plastic components: Free of halogens and cadmium
Power supply left or right max. 100A.
Power supply center max. 160A.But on each side max. 100A.
4042
4 4042
5
4042
6
5020165/C
4080
8
Incoming terminal componentAccessories
General
The incoming terminal component is used to connect the feeder cable to the busbars. The incomingterminal component with an installation width of 36 mm is available as a single-pole component for lineterminals L1, L2 and L3, as well as for the neutral disconnector. The terminals act directly on the busbarsand thus fix the incoming terminal component. The incoming terminal component L1, L2, L3 and N can becombined to meet specific needs. The incoming terminal component can accommodate a maximumcable cross-section of 95 mm2 or 2 x 35 mm2.The cover can be labeled.Instead of the feeder component, the power can also be supplied via a unit (e.g. residual-current circuit-breaker, miniature circuit-breaker or load switch).
Important features
● Modular solution, individual configuration● The maximum connection cross-section per component is 95 mm2 or 2 x 35 mm2
● Full electrical protection
Technical data
Sockets
Rated voltage Un: 400/690 V~
Rated current In: 200A
Space required (modules) per component: 2
Terminals: Flexible95 mm2, 2 x 35 mm2 (200A)
Plastic components: Free of halogens and cadmium
Power supply center max. 200A.But on each side not more than 100A.
4084
7
4090
340
904
5120165/C
Incoming terminal block and componentAccessories
4080
8
Order data
Order data Module Packaging unit
unit
- Feeder component- Feeder component, line terminal L1 ZLS251 2 1- Feeder component, line terminal L2 ZLS252 2 1- Feeder component, line terminal L3 ZLS253 2 1- Feeder component, neutral disconnector N ZLS250 2 1- Feeder component, neutral disconnector N, Additional socket ZLS254 2 1- Feeder component PE, Additional socket ZLS255 2 1
4026
940
271
4017
8
Order data
Order data Module Packaging unit
Standard incoming terminal blockcomplete with main terminals, construction height 50 mm3LN ZLS224 4 13L ZLS225 4 1
Incoming terminal block, lowcomplete with main terminals, construction height 36 mm3LN ZLS228 4 13L ZLS229 4 1
Cover for standard incoming terminalZLS235 4 1
Additional section for standard incoming terminal blockAuxiliary terminals max. 210 mm2 (for auxiliary busbars LA, LB) ZLS233 – 2N-terminal for feeder block ZLS212
4090
340
904
5220165/C
4045
2
Additional socketAccessories
Additional socket
An additional socket base can easily be fitted into the system to accommodate the external N and/or PEbusbars. This enables neutral connections to be made where single pole miniature circuit-breakers areused and their neutral conductors are unswitched. Neutral terminals are clipped onto the additional socketand can be used as detachable neutral links. Only one N busbar and/or one PE busbar can be fitted. Eachsocket can be fitted with an additional socket. Because of the integral snap fastening for 35 mm Din rails,the external N or PE busbars can be fitted anywhere on the distribution panel or even separately from thesystem.Additional sockets can be covered to prevent accidental contact with live parts.
Order data Module Packaging unit
Additional socket base for external N- and PE-busbars– 8-module additional socket (suitable for 8-module sockets) ZLS811 8 10– 6-module additional socket (suitable for 6-module sockets) ZLS810 6 10
N and PE terminals
Corresponding N terminals (light blue) or PE terminals (yellow-green) are available for the power supplyand the outgoing conductors of the external N and PE busbars for cross-sections up to 10 mm2 and from16 mm2 to 50 mm2. The terminals are fitted with label holders which can be used with the marking adapteror the self-adhesive marking label (Phoenix Contact Typ SBS).
Order data Module Packaging unit
N-terminal for additional socketlight blue, for external rail– up to 10 mm2 ZLS812 10– up to 50 mm2 ZLS813 10
PE-terminal for additional socketyellow-green, for external rail– up to 10 mm2 ZLS815 10– up to 50 mm2 ZLS816 10
Insulator block
The dark grey insulator block isolates the interrupted busbar ends and simultaneously marks thedisconnection point externally.
Order data Module Packaging unit
Insulator block for additional socketdark grey, for isolation and spacing ZLS831 0.5 10of external busbars
Dummy block
The light grey dummy block fills blank terminal positions. The busbars are simultaneously protectedagainst contact.
Order data Module Packaging unit
Dummy block for additional socketlight grey, fills empty terminal positions ZLS830 0.5 10
4043
2
4043
4
4043
1
4043
3
4042
940
430
5320165/C
4043
5
4043
6
Additional socketAccessories
Cover with DIN top
The cover can be plugged into the additional socket singly or several side by side. This permitsconventional DIN units to be snapped on. The busbars are covered and protected.
Order data Module Packaging unit
Cover with DIN top for additional socketCover 18 mm wide with DIN top ZLS832 1 10
Cover with cable duct top
A cable duct cover can also be used to cover longer sections.(Tehalit duct no. SL 18050/2)
Order data Module Packaging unit
Duct cover for additional socketDuct for covering, length 144 mm ZLS833 8 10
Marking adapterfor all smissline units for 5 plug-in characters (made by Woertz)Bag of 100 ZLS823 1
Marking labelsself-adhesive, 6 x 17 mmSheet of 420 ZLS825 1
Covertransparent, for designation of all smissline units and socketsBag of 100 ZLS820 1
plus:paper labelsSheet of 160 ZLS821 1
Locking devicefor all smissline protective units
ZLS800 10
4017
2
4018
5
4018
6
5420165/C
UL Approbation for smissline materialUL Recognizer C�US File E 222110A
General
Several directives for the approval of electrical controls apply in the United States of America and Canada. They enable controls to bemanufactured according to US regulations.
The smissline plug-in system with adapters for external devices has been approved for the USA according to Underwriters LaboratoriesC � USA. Proper selection of export devices not only includes the relevant certification and compliance with the applicable regulations;the term «approved for export» also means that the devices and systems have been designed for this purpose.
smissline sortiment with C�US Approbation:
➀ Socket ZLS 808, 806➁ Busbar ZLS 200➂ End-piece ZLS 730➃ Incoming terminal block ZLS 224, 225➄ Incoming terminal element ZLS 250-253➅ Busbar isolator ZLS 239➆ Busbar cover ZLS 100➇ Extensiv adapter ZLS 101➈ Adapter from page 47
Technical data C�US
Rated voltage: 600V ACRated current (end feed): 100ARated current (center feed): 150AShort circuit rating: 50kA with fuse 150A ggl/Gg
Incoming terminal block, standard:Maximum rated voltage: 600V ACMaximum rated current: 150AMain terminal: 10 AWG to 1/0 AWG
Incoming terminal element:Maximum rated voltage: 600V ACMaximum rated current: 150AMain terminal: 8 AWG to 3/0 AWG
Adapter 30A:Rated voltage: 600V ACRated current: 30AShort circuit rating: 50kA with fuse 150A ggl/Gg
Adapter 60A:Rated voltage: 600V ACRated current: 60AShort circuit rating: 50kA with fuse 150A ggl/Gg
4090
8
➀➂ ➂
➁
➃ ➄ ➅
➇
➆ ➈
5520165/C
Power supply via units
The power supply can also be made via a unit instead of the feederblock.
Power supply direct to busbars using miniature or residualcurrent circuit-breaker terminalsParallel below:In this case the power supply cable is connected to the same endof the breaker to which its plug-in contacts are connected.It should be ensured that the operating current of all subsequentlyconnected loads does not exceed the rated current of the plugcontacts (32A for breakers up to and including 32A, 63A forbreakers above 32A and up to 63A).For best possible use of the plug contacts rated current it is best toconnect the power supply cable to the unit with the highest ratedcurrent. A feeder block should be used for higher operatingcurrents.
Power supply to busbars via a residualcurrent circuit-breaker (or load switch IS463)Top series:
The power supply in this case is connected to the opposite end ofa residual current circuit breaker to which its plug-in contacts areconnected. When using this type of feed, the busbars and thereforeall subsequent units have residual-current protection. If severalresidual current circuit-breaker groups are present, the busbarsmust be separated with the dark grey busbar insulator. Attentionmust then be paid to the regulations governing protection of theresidual-current circuit-breaker by subsequent miniature circuit-breakers.The supply can also be fed in through the 4 pole 63 A load switch.
4042
8
Power supply of auxiliary busbarsLA and LB
Power can be supplied to both auxiliary busbars via the feederblock. The two auxiliary terminals are plugged into the feeder blockas required by simply inserting them in the openings provided. Thetwo auxiliary busbars are rated up to maximum 40A. In this way,auxiliary and signal contacts can be powered via the auxiliarybusbars LA and LB.
4084
4
Power supply to the external N and PEbusbars
External N busbars enable neutral connections to be availablewhere single pole circuit-breakers are used. Where external N andPE busbars are used, the neutral or PE conductor is taken directlyto the busbar using a suitable connection terminal. Attention mustbe paid to appropriate insulation of the N busbar when installingseveral residual-current circuit-breaker groups.
4077
740
424
Power suppliesAccessories
5620165/C
AccessoriesOrder data
100A / 40A busbars / socket selection table
Modules Busbar length Order data Order data Number of socketsin mm busbar busbar 8-piece 6-piece
100A 40A
Modules Busbar length Order data Order data Number of socketsin mm busbar busbar 8-piece 6-piece
100A 40A
Planning for the incorporation of feeder block and spare places should be taken into accountThe total lengths given above were determined taking account of socket spacings and tolerances.They are not therefore necessarily a multiple of 18 mm (1 position unit).
6 104 ZLS201E6 ZLS203E6 – 18 140 ZLS201E8 ZLS203E8 1 –
11 194 ZLS201E11 ZLS203E1112 212 ZLS201E12 ZLS203E12 – 213 230 ZLS201E13 ZLS203E1314 248 ZLS201E14 ZLS203E14 1 115 266 ZLS201E15 ZLS203E1516 284 ZLS201E16 ZLS203E16 2 –17 302 ZLS201E17 ZLS203E1718 320 ZLS201E18 ZLS203E18 – 319 338 ZLS201E19 ZLS203E1920 357 ZLS201E20 ZLS203E20 1 221 375 ZLS201E21 ZLS203E2122 393 ZLS201E22 ZLS203E22 2 123 411 ZLS201E23 ZLS203E2324 429 ZLS201E24 ZLS203E24 3 –25 447 ZLS201E25 ZLS203E2526 465 ZLS201E26 ZLS203E26 1 327 483 ZLS201E27 ZLS203E2728 501 ZLS201E28 ZLS203E28 2 229 519 ZLS201E29 ZLS203E2930 537 ZLS201E30 ZLS203E30 3 131 555 ZLS201E31 ZLS203E3132 573 ZLS201E32 ZLS203E32 4 –33 591 ZLS201E33 ZLS203E3334 609 ZLS201E34 ZLS203E34 2 335 627 ZLS201E35 ZLS203E3536 645 ZLS201E36 ZLS203E36 3 237 663 ZLS201E37 ZLS203E3738 681 ZLS201E38 ZLS203E38 4 139 699 ZLS201E39 ZLS203E3940 717 ZLS201E40 ZLS203E40 5 –41 735 ZLS201E41 ZLS203E4142 753 ZLS201E42 ZLS203E42 3 343 771 ZLS201E43 ZLS203E4344 789 ZLS201E44 ZLS203E44 4 245 807 ZLS201E45 ZLS203E4546 825 ZLS201E46 ZLS203E46 5 147 843 ZLS201E47 ZLS203E4748 861 ZLS201E48 ZLS203E48 6 –49 879 ZLS201E49 ZLS203E4950 897 ZLS201E50 ZLS203E50 4 351 915 ZLS201E51 ZLS203E5152 933 ZLS201E52 ZLS203E52 5 253 951 ZLS201E53 ZLS203E5354 969 ZLS201E54 ZLS203E54 6 155 987 ZLS201E55 ZLS203E5556 1005 ZLS201E56 ZLS203E56 7 –57 1023 ZLS201E57 ZLS203E5758 1041 ZLS201E58 ZLS203E58 5 359 1059 ZLS201E59 ZLS203E59
60 1078 ZLS201E60 ZLS203E60 6 261 1096 ZLS201E61 ZLS203E6162 1114 ZLS201E62 ZLS203E62 7 163 1132 ZLS201E63 ZLS203E6364 1150 ZLS201E64 ZLS203E64 8 –65 1168 ZLS201E65 ZLS203E6566 1186 ZLS201E66 ZLS203E66 6 367 1204 ZLS201E67 ZLS203E6768 1222 ZLS201E68 ZLS203E68 7 269 1240 ZLS201E69 ZLS203E6970 1258 ZLS201E70 ZLS203E70 8 171 1276 ZLS201E71 ZLS203E7172 1294 ZLS201E72 ZLS203E72 9 –73 1312 ZLS201E73 ZLS203E7374 1330 ZLS201E74 ZLS203E74 7 375 1348 ZLS201E75 ZLS203E7576 1366 ZLS201E76 ZLS203E76 8 277 1384 ZLS201E77 ZLS203E7778 1402 ZLS201E78 ZLS203E78 9 179 1420 ZLS201E79 ZLS203E7980 1438 ZLS201E80 ZLS203E80 10 –81 1456 ZLS201E81 ZLS203E8182 1474 ZLS201E82 ZLS203E82 8 383 1492 ZLS201E83 ZLS203E8384 1510 ZLS201E84 ZLS203E84 9 285 1528 ZLS201E85 ZLS203E8586 1546 ZLS201E86 ZLS203E86 10 187 1564 ZLS201E87 ZLS203E8788 1582 ZLS201E88 ZLS203E88 11 –89 1600 ZLS201E89 ZLS203E8990 1618 ZLS201E90 ZLS203E90 9 391 1636 ZLS201E91 ZLS203E9192 1654 ZLS201E92 ZLS203E92 10 293 1672 ZLS201E93 ZLS203E9394 1690 ZLS201E94 ZLS203E94 11 195 1708 ZLS201E95 ZLS203E9596 1726 ZLS201E96 ZLS203E96 12 –97 1744 ZLS201E97 ZLS203E9798 1762 ZLS201E98 ZLS203E98 10 399 1780 ZLS201E99 ZLS203E99
100 1799 ZLS201E100 ZLS203E100 11 2101 1817 ZLS201E101 ZLS203E101102 1835 ZLS201E102 ZLS203E102 12 1103 1853 ZLS201E103 ZLS203E103104 1871 ZLS201E104 ZLS203E104 13 –105 1889 ZLS201E105 ZLS203E105106 1907 ZLS201E106 ZLS203E106 11 3107 1925 ZLS201E107 ZLS203E107108 1943 ZLS201E108 ZLS203E108 12 2109 1961 ZLS201E109 ZLS203E109
5720165/C
45 9045
35
5.5543618 66.584.5
94.5 Z20
097.
eps
45 100
55
35
5.5 66.584.5
94.5
1821
Z20
098.
eps
45 9045
355.572 66.5
84.594.5 Z
2009
9.ep
s
45 9045
35
5.57299 66.584.5
94.5 Z20
100.
eps
45 9045
35
5.554 66.584.594.5 Z
2010
2.ep
s
45
95.5
50.5
35
5.536 66.584.5
94.5 Z20
101.
eps
Dimensions (in mm)
Miniature circuit-breaker 1-, 2-, 3-pole
Neutral disconnector 3LN (FI, FIK, FIS) and load switch IS463
3LN (FISG) Motor protection circuit-breaker MS 325
Residual current circuit-breaker 1LNCombined residual current/miniaturecircuit-breaker
5820165/C
45
9045
35
5.572
66.5
90
84.5Z
2012
2.ep
s
Z20
110.
eps
45 901
45
35
5.59 9
66.5
94.584.5
45 901
45
35
5.59 9
66.584.5 Z
2011
1.ep
s
Surge arrester SA4 SC
Auxiliary contact block SDH…Signal contact block SDS…
Auxiliary contact block SBH…Signal contact block SBS…
Dimensions (in mm)
45 901
45
35
5.59 9
66.584.5 Z
2011
2.ep
s
Connection support ASDummy housing ZLS930
Adapter 100A Adapter 32A, 63A
86.7
17.75
17 13 7.55.5
35Z
2003
54.e
ps
90
72 17 13 50.55.5
Z20
0353
.ep
s
43
57
64 11
13 45 90
5920165/C
90
4.5
35
53.5
48.8
6111
4
47.5
175.43.57.3
60144
28.6
Z20
117.
eps
90
4.5
35
53.5
48.8
6111
4
47.5
175.43.57.360
108
28.6
Z20
118.
eps
45.5144
8.6 17.6 36
47
8313
3
Z20
119.
eps
45
8643
35
5.518 66.584.5
Z20
120.
eps
45
8643
35
5.518 66.584.5
Z20
121.
eps
sockets ZLS808
Sockets– 8 modules
sockets ZLS806
Sockets– 6 modules
Dimensions (in mm)
Intermediate piece ZLS722
Additional socket with external terminals
Busbar isolator ZLS239
6020165/C
72
21.5
35
43.5
87
72 5.5 Z20
115.
eps
7
35 3543
.5
18 Z20
116.
eps
49.5
Z20
113.
eps
35.5
Dimensions (in mm)
power supply
Feeder blocks
Busbar cover ZLS100Combi module with ZLS802
Extension adapter ZLS101
ZLS 224, 225 ZLS 228, 229
Incoming terminal component
29.3
61
7.5
3535
42.5
168
221.
5
240
125.
..150
62.8
Z20
114.
eps
45.5
144
36
47
86
83
133
Z20
0356
.ep
s
49.5
2016
5/C
ABB Control LimitedGrovelands HouseLongford RoadExhall, Coventry, CV7 9 NDUnited KingdomPhone 01203 368 500Fax 01203 368 401
ABB AS Automation TechnologyProducts DivisionP.O. Box 797 BrakeroyaNO-3002 DrammenNorwayTlf: 32 85 80 00Fax: 32 85 80 10E-Mail: [email protected]://www.abb.no/nocrl
www.abb.com
ABB BVLylantse Baan 9P.O. Box 532NL-2900 Capelle a/d IJsselNetherlandsTel. 010 258 22 50Fax 010 458 65 59
ABB AutomationTechnology Products ATSaltänsvägen 28SE-72161 VästeråsSwedenTelefon 021-32 07 00Telefax 021-32 05 20
ABB ELECTRO n.v.Hoge Wei, 27B-1930 ZaventemBelgiumTel. 02 718 63 11Fax 02 718 68 31
ABB OYDomestic SalesP.O. Box 182FIN-00381 HELSINKIFinlandTel. 010-22 2000Fax 010-22 22010
1 N and PE conductor terminals 32A, 100A and 200A
2 Busbar cover 9, 18 and 144 mm for additional socket
3 Busbar cover for the socket
4 Busbar for N and PE
5 6-module and 8-module Additional socket base
6 Socket end-piece
7 6-module and 8-module socket
8 Busbar for L1, L2, L3, N and PE
9 Busbar for auxiliary contacts(only when use smissline components)
10 Incoming terminal block, Standard 100A left or righton the system160A on Center Power supply of the systemmaximum 50 mm2
11 Incoming terminal oversize, Standard 200A on CenterPower supply of the system maximum 95 mm2
12 Busbar isolator for isolate the interrupted busbarsfrom each other
13 DIN Rail for cover for using on the busbar cover
14 Adapter for 32A, 63A and 100A single orCombination bottom or top feed
smissline Plug-in System
� �
�
�
�
�
�
�
� �
�