ahindra DG PV Hybrid Powered by Mahindra Sun MACX TM Access reliable green and affordable power today Technical details Powered by Mahindra Sun MACX TM Access reliable green and affordable power today Technical details d Solution Powered by Mahindra Sun MACX TM Access reliable green and affordable power today Technical details Powered by Mahindra Sun MACX TM Access reliable green and affordable power today Technical details

Transcript of Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD...

Page 1: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

Mahindra DG PV Hybrid SolutionPowered by Mahindra Sun MACXTM

Access reliable green and affordable power today

Technical details

Mahindra DG PV Hybrid SolutionPowered by Mahindra Sun MACXTM

Access reliable green and affordable power today

Technical details

Mahindra DG PV Hybrid SolutionPowered by Mahindra Sun MACXTM

Access reliable green and affordable power today

Technical details

Mahindra DG PV Hybrid SolutionPowered by Mahindra Sun MACXTM

Access reliable green and affordable power today

Technical details

Page 2: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

High Carbon footprint

Reliable source of power

High cost of generation

Green energy

Variable source of power

Lowered cost of generation

DG

Benefits of DG PV Solution

Why DG PV Hybrid System?

Green energy (30% lower diesel consumption)

Reliable source of power (consistent power 24x7)

Low cost of generation (30% LCOE reduction)

Green energy

Variable source of power

Lowered cost of generation

PV

Green energy (30% lower diesel consumption)

Reliable source of power (consistent power 24x7)

Low cost of generation (30% LCOE reduction)

Page 3: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

Target MarketApplications of Mahindra Sun MACX

Military camps Industries

Hotels/ Resorts Islands

Industries Residential colonies

Islands Institutions (Hospital, College etc)

Page 4: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

2

Diesel Generation (Single/ Multiple)

Battery Backup(optional)

Distribution Panel

Grid

Mahindra Advanced Controller Unit

(MACXTM)

2

Sun MACXTM (Mahindra Advanced Controller Unit) Works for single and three phase systems

Acts as the brain of the system and protects against both undercurrent and overcurrent situations

Prevents reverse flow of powerCompatible with all diesel generators

24x7 customer helpline for service requestsRemote diagnostics anytime, anywhere using unique URL

Power up with Mahindra Susten

2

Battery Backup(optional)

Solar PV

LoadBidirectional Inverter

Solar Inverter

Mahindra Advanced Controller Unit

(MACXTM)

2

Sun MACXTM (Mahindra Advanced Controller Unit) Works for single and three phase systems

Acts as the brain of the system and protects against both undercurrent and overcurrent situations

Prevents reverse flow of powerCompatible with all diesel generators

24x7 customer helpline for service requestsRemote diagnostics anytime, anywhere using unique URL

Power up with Mahindra Susten

Stability

Customization

Retrofit

Automation

Page 5: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

Functions and features

• Interface between Solar PV, DG set and loads

• Intelligent Energy Management

• Prevents underloading of DG

• Data logging (2 month back up)

• Vendor Agnostic

Functions and features

• Interface between Solar PV, DG set and loads

• Intelligent Energy Management

• Prevents underloading of DG

• Data logging (2 month back up)

• Vendor Agnostic

Page 6: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

2

SOLAR (100 kW PV)

Available: GRID, PVCase 1: PV < LOADNormal operation

50 kW

8 AM

Mahindra DG PV Hybrid Illustration

2

INVERTER

GRID

Sun MACXTM

50 kWEnergy Flow

Communication

Control

Power line

2

LOAD

Available: GRID, PVCase 1: PV < LOADNormal operation

100 kW

Energy Meter

8 AM

2

Electrical Panel

0 kW DG 125 kVA

100 kW LOAD on50 kW GRID on50 kW SOLAR on

System stable no switching(Normal

operation)

Page 7: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

3

Available: GRID, PVCase 2: PV > LOAD

High SOLAR generationPV begins to adjust with LOAD

PV limited to LOAD capacityNo power drawn from GRID

60 kW

SOLAR (100 kW PV)

40 kW

11 AM

Mahindra DG PV Hybrid Illustration

3

INVERTER

GRID

Sun MACXTM

0 kWEnergy Flow

Communication

Control

Power line

3

LOAD

Available: GRID, PVCase 2: PV > LOAD

High SOLAR generationPV begins to adjust with LOAD

PV limited to LOAD capacityNo power drawn from GRID

40 kW

Energy Meter

11 AM

3

Electrical Panel

0 kW DG 125 kVA

40 kW LOAD on0 kW GRID on for reference for SOLAR

0 kW GRID on for reference for SOLAR60 kW of SOLAR on

(exceeds LOAD)

SOLAR reduced to 40 KW to meet LOADSystem stability

ensured

Page 8: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

1

Available: GRID fails, DG on, PV onCase 3: LOAD = 80% DG

DG lowered to 50% loading

0 kW

SOLAR (100 kW PV)

40 kW

12 PM

Mahindra DG PV Hybrid Illustration

1

INVERTER

GRID

Sun MACXTM

0 kWEnergy Flow

Communication

Control

Power line

1

LOADAvailable: GRID fails, DG on, PV on

Case 3: LOAD = 80% DGDG lowered to 50% loading

100 kW

Energy Meter

12 PM

1

Electrical Panel

100 kW DG 125 kVA60 kW

100 kW LOAD on100 kW DG on at 80% loading

Solar is onIt is checked if higher SOLAR generation is

possible

SOLAR generation present

SOLAR increased to 40 kW

DG loading is reduced to 50%Saving on fuel consumption

Page 9: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

1

Available: DG, PVCase 4: LOAD < PV +30% DG

High SOLAR generationSOLAR begins to reduceDG loading below 30%

SOLAR limited DG loading brought to 30%

75 kW

SOLAR (100 kW PV)

42.5 kW

1 PM

Mahindra DG PV Hybrid Illustration

1

INVERTER

GRID

Sun MACXTM

0 kWEnergy Flow

Communication

Control

Power line

1

LOADAvailable: DG, PV

Case 4: LOAD < PV +30% DG High SOLAR generationSOLAR begins to reduceDG loading below 30%

SOLAR limited DG loading brought to 30%

80 kW

Energy Meter

1 PM

1

Electrical Panel

25 kW DG 125 kVA37.5 kW

100 kW LOAD on100 kW LOAD onDG on at 20% High generation

of 75 kW SOLAR is on

SOLAR generation reduced to 62.5

kW

DG loading changes to safe

loading of 30%, ensuring

long life of system

Page 10: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

0

10

20

30

40

50

60

70

80

90

1 2

90 Useful Solar Energy

Increasing intelligence of solar installations Increase solar penetration Reduce diesel consumption Integrate remote monitoring facility

0

10

20

30

40

50

60

70

80

90

1 2

Useful Solar Energy

Solar Generation

Increasing intelligence of solar installations Increase solar penetration Reduce diesel consumption Integrate remote monitoring facility

3 4 5 6 7 8 9 10 11 12 13 14 15 16

Solar DG Load Solar Generation

Useful Solar Energy DG Consumption Excess Solar Power

Without Controller

With Controller

2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Useful Solar Energy DG Consumption Excess Solar Power

Solar Generation Load

Page 11: Mahindra DG PV Hybrid Solution - eqmagpro.com · 1 Available: GRID fails, DG on, PV on Case 3: LOAD = 80% DG DG lowered to 50% loading 0 kW SOLAR (100 kW PV) 40 kW 12 PM Mahindra

Installation at IgatpuriInstallation at Igatpuri

66 kWp solar and 82.5 kVA DG set (Solar to DG penetration: 80%)

The administration building operates in island mode (absence of grid)

84% of energy requirement met by DG PV Hybrid; reduction in diesel by 40%