Maestro Occupancy sensing switch · The MS-OPS6M2U-DV and MS-VPS6M2U products allow the installer...
Transcript of Maestro Occupancy sensing switch · The MS-OPS6M2U-DV and MS-VPS6M2U products allow the installer...
-
Maestro® Sensor
369741a 1 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Maestro® Occupancy sensing switchTo power the sensing circuit, occupancy sensing switches require a small flow of current when the load is in the OFF state. This can be accomplished by connecting the power supply return wire to ground or to neutral.Local codes in certain municipalities require that a neutral conductor be run to the switch box, regardless of construction. In one particular instance, installing occupancy sensors that use the ground wire to function is not permitted.The MS-OPS6M2U-DV and MS-VPS6M2U products allow the installer to configure the device to connect to either ground or neutral.
• Toconnecttoground,simplyinstalltheproductinits"out-of-thebox"condition.• Toconnecttoneutral,installthesuppliedwhitesleeveoverthegreenwire.
For more information about occupancy sensing switches and the National Electrical code, see:www.lutron.com/TechnicalDocumentLibrary/048469.pdf
Features• PassiveinfraredsensorswithexclusiveLutron® XCTTM Technology for fine motion
detection• 180°sensorfield-of-view• Upto30ftx30ft(9mx9m)[900ft2(81m2)]majormotioncoverageand
20ftx20ft(6mx6m)[400ft2(36 m2)]minormotioncoverage• OccupancyversioncanbesettoAuto-ON/Auto-OFForManual-ON/Auto-OFF• VacancyversionavailabletomeetCATitle24requirements• Adjustabletimeout(1,5,15,or30minutes)andhigh/lowsensitivityadjustment• Occupancysensingswitchloads:incandescent,halogen,ELV,MLV,CFL,LED,magneticfluorescent,electronic
fluorescent, and fan.
Models availableMS-OPS6M2U-DV MS-VPS6M2U-DV
MS-OPS6M2U-DVMS-VPS6M2U-DV
-
Maestro® Sensor
369741a 2 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
SpecificationsRegulatory Approvals
• UL® Listed to U.S. and Canadian safety requirements.
• NOMCertification(pending).
Power• 120–277V~50/60Hz1
Key Design Features• Alllightingloads.• Crush/tamperresistantlens.• Smartambientlightdetection.• Adaptiveswitchingalgorithmforextendedrelaylife.• XCTTM Technology for fine motion detection.
Environment• Ambientoperatingtemperature:32°Fto104°F
(0°Cto40°C),0%–90%humidity,non-condensing.Indoor use only.
Warranty• 5-YearLimitedWarranty.ForadditionalWarranty
information, please visit www.lutron.com/TechnicalDocumentLibrary/Sensor_Warranty.pdf
Additional Information• ForMaestro® Occupancy sensing dimmer models,
please see Lutron® P/N 369270.• ForotherMaestro® Occupancy sensing switch
models, please see Lutron® P/N 369666.• ForusewithMA-AS,MSC-AS,MA-AS-277,or
MSC-AS-277tocontroltheloadfrommorethantwolocations, please see Lutron® P/N 048435.
• Formoreinformation,pleaseseewww.lutron.com/occvacsensors
• LutronTechnicalHotline:1.800.523.9466.
Advanced FeaturesSwitchingAdaptivezerocrossfeaturemaximizesrelaylifebyswitchingatthepointofminimumenergyontheACpowercurve.Activelyadaptstovariationsinrelaytiming.
XCTTM TechnologyAdvancedsensingtechnologyforfinemotiondetection ensures that the lights stay on while the room is occupied, and that the sensor does not turn on falsely when there is no occupancy in the room. For more information, see www.lutron.com/TechnicalDocumentLibrary/white%20paper%20XCT%204-23-09%20B.pdf
1 Maximum current ratings for individual models are provided in the Selection Matrixonpage4.
-
Maestro® Sensor
369741a 3 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Custom SettingsAmbient Light Detection
• Lightsturnononlyifnaturallightinroomislow.• Smart—Ambientlightthresholdadjustspreciselyto
the user’s preference.Instructions: If switch turns on when there is enough natural light, or if switch does not turn on when there is not enough natural light, press thelargebuttonwithin5secondsofenteringtheroom.Overtime,thisinteraction will “teach” the switch your preferred setting.
Sensor Operation• Occupancy/Vacancy:Auto-ON/Auto-OFFor
Manual-ON/Auto-OFF• Vacancyonly:Manual-ON/Auto-OFFonly
Timeout Options(SeeAdditional Featuresonpage4fordefaultsettings)
• 1Minute• 5Minutes• 15Minutes• 30Minutes
Sensitivity Options• Highsensitivity(default)• Lowsensitivity
Auto-ON Options(MS-OPSonly)
• Occupancy(default):Auto-ON/Auto-OFF• Vacancy*:Manual-ON/Auto-OFF• LowLight:Lightsturnononlyifneeded(ifambient
lightisbelowthreshold) *Thereisa15-secondgraceperiodthatbeginswhenthelightsare
automatically turned off, during which the lights will automatically turn back on in response to motion. This grace period is provided as a safety and convenience feature in the event that the lights turn off while the room is still occupied, so that the user does not need to manually turn thelightsbackon.After15seconds,thegraceperiodexpiresandthelights must be manually turned on.
Manual Off-While-Occupied Options(MS-OPSonly—seeAdditional Featuresonpage4fordefaultsetting)
• Enabled– WhentheOccupancysensingswitchismanually
turned off, the Occupancy sensing switch will not turn the lights back on automatically while the room is occupied.
– Oncetheroomisvacated,theAuto-ONfeaturereturns to normal operation after the timeout period has expired.
– Thismaybethepreferenceinconferenceroomsor classrooms while viewing presentations. This feature requires motion to keep the lights off.
• Disabled– WhentheOccupancysensingswitchismanually
turnedoff,theAuto-ONfeaturewillreturntonormaloperationafter25seconds.
– Thismaybethepreferenceiftheuseralwayswants the lights to turn on upon entering and the lights to turn off when the room is vacant.
-
Maestro® Sensor
369741a 4 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Selection Matrix
1XXinmodelnumberrepresentscolor/finishcode.
2OccupancysensorscanbeconfiguredasAuto-ON/Auto-OFForManual-ON/Auto-OFF. VacancysensorsareconfiguredasManual-ON/Auto-OFFonly.
3Standardmechanical3-wayswitchcannotbecombinedwithcompanionswitch.
4CompanionswitchMA-AS,MSC-AS,MA-AS-277,orMSC-AS-277isrequiredformulti-locationinstallations(morethantwolocationscontrollingthesamelightingcircuit).Uptoninecompanionswitchesmaybeconnected.
5Thegreenwirecanbeconnectedtogroundor,whencoveredbythewhitesleeve,canbeconnectedtoneutral(seeillustrationsonpage7).
Crush/tamper-resistant lens
Ambient light detection
Switching
XCTTM technology
Manual off-while-occupied default setting
Default timeout (minutes)
Model Number1
MS-OPS6M2U-DV-XX Smart Adaptive Enabled 15MS-VPS6M2U-DV-XX Smart Adaptive 15
Additional Features
1XXinmodelnumberrepresentscolor/finishcode.
Vacancy only2 (Title 24 compliant)
Single-pole onlySingle-pole / 3-way capability
Works with standard mechanical 3-way switch3
Works with companion switch3, 4
All lighting loads (120 V~ only)
Max current rating
All lighting loads (120 – 277 V~ only)
Fan (120 V~)
Light + Fan (120 V~)
Neutral or ground wire required for functionality5Off-state power
Minimum load required
Model Number1
MS-OPS6M2U-DV-XX 6A 3A 3A MS-VPS6M2U-DV-XX 6A 3A 3A
-
Maestro® Sensor
369741a 5 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
5ft (1.5m)
10ft (3m)
15ft (4.5m)
20ft (6m)
25ft (7.5m)
30ft (9m)
Horizontal Beam Diagram
5ft (1.5m)
5ft (1.5m)
0
10ft (3m)
10ft (3m)
15ft (4.5m)
15ft (4.5m)
20ft (6m)
20ft (6m)
25ft (7.5m)
25ft (7.5m)
30ft (9m)
30ft (9m)
Vertical Beam Diagram
4ft (1.2m)
00 10ft (3m)
15ft (4.5m)
20ft (6m)
25ft (7.5m)
30ft (9m)
NEMA WD7 Coverage
5ft (1.5m)
5ft (1.5m)
0
10ft (3m)
10ft (3m)
15ft (4.5m)
15ft (4.5m)
5ft (1.5m)
Majormotioncoverage:900ft2(81m2)
Minormotioncoverage:400ft2(36m2)
Occupancy Sensing Switch Placement and Operation• TheabilityoftheOccupancysensingswitchtodetectmotionrequiresline-of-sightofroomoccupants.The
Occupancy sensing switch must have an unobstructed view of the room.• HotobjectsandmovingaircurrentscanaffecttheperformanceoftheOccupancysensingswitch.• TheperformanceoftheOccupancysensingswitchdependsonatemperaturedifferentialbetweentheambient
roomtemperatureandthatofroomoccupants.WarmerroomsmayreducetheabilityoftheOccupancysensingswitch to detect occupants.
DefinitionsMajor motion: movement of a person entering or passing through an area.Minor motion:movementofapersonoccupyinganareaandengaginginsmallactivities(e.g.,reachingforatelephone,turningthepagesofabook,openingafilefolder,pickingupacoffeecup).
-
Maestro® Sensor
369741a 6 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
DimensionsMeasurementsshownas:in(mm).
Front View Side View
411⁄16(119)
215⁄16(75)
11⁄8(30)
5/16(8)
1/8(3)
Mounting
WallplateAdapter/Wallplate (soldseparately)
Occupancy Sensing SwitchWallbox
Mounting screws Adaptermountingscrews
Operation
MS-OPS6M2U-DVMS-VPS6M2U-DV
Sensor Lens
Sensor LED(behindlens) Pulses during configuration of custom settings and in the Test mode.
TapswitchTapon/off
-
Maestro® Sensor
369741a 7 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Slide white sleeve over green wire until flush with back cover.
White(connectstoNeutral)
Converting Ground Wire to Neutral WireThe green wire can be connected to ground or, when covered by the white sleeve, can be connected to neutral.
Blue(3-way)
Black(hot/switchedhot)
Green(connectstoGround)
Whitesleeve
Bare: always connect to ground
-
Maestro® Sensor
369741a 8 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Continued on next page...
Wiring Diagrams: Single-Location InstallationsWiring Diagram 1: Connect occupancy sensing switch to groundSingle-Location Installation (120-277 V~)1, 2-OPS6M2U-DV 3, -VPS6M2U-DV 3
120-277V~ 50/60Hz
Green
Ground
Hot/Live
Neutral
Load
Blue1
Bare
Black Black
Occupancy sensing switch
Wiring Diagram 2: Connect occupancy sensing switch to neutralSingle-Location Installation (120-277 V~)1, 2-OPS6M2U-DV4, -VPS6M2U-DV4
Occupancy sensing switch
120-277V~ 50/60Hz White
Ground
Hot/Live
Neutral
Load
Blue1
Bare
Black Black
1 Whenusingcontrolsinsinglelocationinstallations,tightentheblueterminalorcapbluewire.DoNOTconnecttheblueterminal/wiretoanyotherwireortoground.2 Fanloadappliesto120V~only(notforusewith277V~).3 Green wire is connected to ground.4 Wirecoveredbywhitesleeveisconnectedtoneutral.
-
Maestro® Sensor
369741a 9 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
1 Only one Occupancy sensing switch can be used per multi-location circuit.2 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.Standardmechanical3-way
switchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).3 Fanloadappliesto120V~only(notforusewith277V~).4 Green wire is connected to ground.
Wiring Diagram 3: Connect occupancy sensing switch to ground3-way Installation with Standard Mechanical 3-way Switch (120-277 V~)1, 2, 3-OPS6M2U-DV 4, -VPS6M2U-DV 4
Black
Blue
Green
Ground
Occupancy sensing switch
Green screw
Ground
120-277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical 3-way
switch
BlackJumper wire
BareDifferent color screw (Common)
OR
Black
Blue
Ground
Occupancy sensing switch
Green
Ground
120V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical 3-way
switch
BlackJumper wire
Bare Different color screw (Common)Green screw
Wiring Diagrams: 3-way Installations with Standard Mechanical 3-way Switch
Continued on next page...
-
Maestro® Sensor
369741a 10 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Continued on next page...
Wiring Diagram 4: Connect occupancy sensing switch to neutral3-way Installation with Standard Mechanical 3-way Switch (120-277 V~)1, 2, 3-OPS6M2U-DV4, -VPS6M2U-DV4
Black
Blue
WhiteGround
Occupancy sensing switch
Green screw
Ground
120-277V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical 3-way
switch
BlackJumper wire
BareDifferent color screw (Common)
OR
Black
Blue
Ground
Occupancy sensing switch
WhiteGround
120V~ 50/60Hz
Hot/Live
Neutral
Load
Standard mechanical 3-way
switch
BlackJumper wire
Bare Different color screw (Common)Green screw
Wiring Diagrams: 3-way Installations with Standard Mechanical 3-way Switch (continued)
1 Only one Occupancy sensing switch can be used per multi-location circuit.2 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.Standardmechanical3-way
switchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).3 Fanloadappliesto120V~only(notforusewith277V~).4 Wirecoveredbywhitesleeveisconnectedtoneutral.
-
Maestro® Sensor
369741a 11 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Continued on next page...
Wiring Diagram 5: Connect occupancy sensing switch to groundMulti-Location Installation (120 V~)1, 2, 3-OPS6M2U-DV 4, -VPS6M2U-DV 4
Blue
Green
Ground
Occupancy sensing switch3
Black
Ground
120V~ 50/60Hz
Brass BrassBlack
Blue Blue
Green Green
Ground
Hot/Live
Neutral
Load
MA-AS or MSC-AS
MA-AS or MSC-AS
Bare
Black Black
1 Only one Occupancy sensing switch can be used per multi-location circuit.2 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.Standardmechanical3-way
switchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).3 Occupancy sensing switch can be installed in any location.4 Green wire is connected to ground.5 Wirecoveredbywhitesleeveisconnectedtoneutral.
Wiring Diagram 6: Connect occupancy sensing switch to neutralMulti-Location Installation (120 V~)1, 2, 3-OPS6M2U-DV 5, -VPS6M2U-DV 5withMA-ASorMSC-AS
MA-AS or MSC-AS
MA-AS or MSC-AS
Blue
WhiteGround
Occupancy sensing switch3
Black
Ground
120V~ 50/60Hz
Brass BrassBlack
Blue Blue
Green Green
Ground
Hot/Live
Neutral
Load
Bare
Black Black
Wiring Diagrams: Multi-location Installations
-
Maestro® Sensor
369741a 12 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
1 Only one Occupancy sensing switch can be used per multi-location circuit.2 Asinglestandardmechanical3-wayswitchorupto9companionswitchesmaybeconnectedtomostOccupancysensingswitches.Standardmechanical3-way
switchcannotbecombinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150 ft(46 m).3 Occupancy sensing switch can be installed in any location.4 Fanloadappliesto120V~only(notforusewith277V~).5 Green wire is connected to ground.6 Wirecoveredbywhitesleeveisconnectedtoneutral.
Wiring Diagrams: Multi-location Installations (continued)
Occupancy sensing switch3
Black
Blue
Green
Ground
Black
Blue
Green
Ground
277V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or MSC-AS-277
MA-AS-277 or MSC-AS-277
Wiring Diagram 7: Connect occupancy sensing switch to groundMulti-Location Installation (277 V~)1, 2, 3, 4-OPS6M2U-DV 5, -VPS6M2U-DV 5withMA-AS-277orMSC-AS-277
Occupancy sensing switch3
Black
Blue
WhiteGround
Black
Blue
Green
Ground
277V~ 50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or MSC-AS-277
MA-AS-277 or MSC-AS-277
Wiring Diagram 8: Connect occupancy sensing switch to neutralMulti-Location Installation (277 V~)1, 2, 3, 4-OPS6M2U-DV6, -VPS6M2U-DV6withMA-AS-277orMSC-AS-277
-
Maestro® Sensor
369741a 13 11.15.12
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Switch with Occupancy/ Vacancy Sensor
Colors and Finishes
• Duetoprintinglimitations,colorsandfinishesshowncannotbeguaranteedtomatchactualproductcolorsperfectly.
• Colorchipkeychainsareavailableformoreprecisecolormatching:– GlossFinishes:DG-CK-1– SatinFinishes:SC-CK-1
Satin Finishes
TaupeTP
TurquoiseTQ
PlumPL
MerlotMR
TerracottaTC
SiennaSI
MidnightMN
HotHT
Desert StoneDS
EggshellES
BiscuitBI
SnowSW
PalladiumPD
GreenbriarGB
BluestoneBG
Mocha StoneMS
GoldstoneGS
Sea GlassSG
StoneST
LimestoneLS
Gloss Finishes
WhiteWH
IvoryIV
AlmondAL
LightAlmondLA
GrayGR
BrownBR
BlackBL
A: B: C: D: E: F: G: 1H: 2I: 3J: 4K: 5L: 6M: 7N: 8O: 9P: 10Q: 11R: 12S: 13