Submittal Data Sheet M40C-36HRDN1- M Project Name Location Date Location Approval Date Engineer Unit Designation Submitted To Drawing Number Submitted By Reference Approval Construction (Circle One) Performance Specification Outdoor Unit Model M40D-36HRDN1-M Maximum Zones 4 Cooling Capacity (BTUH) 35,400 Refrigerant R-410a Sensible Capacity (BTUH) 29,028 Noise Level Cooling Outdoor (High) (Dba) 64 SEER 15.5 Noise Level Heating Outdoor (High) (Dba) 65 HSPF (BTUH/H/W) 8.0 Connection (Tubing) Flare Connection Pipe size Supply/Return 1/4” , 3/8” Heating Capacity (BTUH) 38,000 Maximum Tube Length (Feet) 200 Maximum Height Difference (Feet) 32 Electrical Physical Voltage/Phase/Cycle 230/1/60 Net Weight (Indoor/Outdoor) (LBS) 190 Cable Indoor to outdoor 14AWG/4 conductor Shielded Height Condensing Unit (Inches) 38” Minimum Circuit Ampacity Depth Condensing Unit (Inches) 14” Recommended Fuse Size 40 Length Condensing Unit (Inches) 39” Current Rating Cooling 16.1

description

Free Match Quad Zone

Transcript of M40C-36HRDN1-M MultiZone Submittal Data Sheet

Page 1: M40C-36HRDN1-M MultiZone Submittal Data Sheet

Submittal Data Sheet

M40C-36HRDN1- M

Project Name Location Date

Location Approval Date

Engineer Unit Designation

Submitted To Drawing Number

Submitted By

Reference Approval Construction (Circle One)

Performance Specification

Outdoor Unit Model M40D-36HRDN1-M Maximum Zones 4Cooling Capacity (BTUH) 35,400 Refrigerant R-410a

Sensible Capacity (BTUH) 29,028Noise Level Cooling Outdoor (High) (Dba) 64

SEER 15.5Noise Level Heating Outdoor (High) (Dba) 65

HSPF (BTUH/H/W) 8.0 Connection (Tubing) FlareConnection Pipe size Supply/Return 1/4” , 3/8”

Heating Capacity (BTUH) 38,000 Maximum Tube Length (Feet) 200 Maximum Height Difference (Feet) 32

Electrical PhysicalVoltage/Phase/Cycle 230/1/60 Net Weight (Indoor/Outdoor) (LBS) 190

Cable Indoor to outdoor14AWG/4 conductor

Shielded Height Condensing Unit (Inches) 38”Minimum Circuit Ampacity Depth Condensing Unit (Inches) 14”Recommended Fuse Size 40 Length Condensing Unit (Inches) 39”Current Rating Cooling 16.1Current Rating Heating 18.0 Cooling Input Power (W) 3,703 Heating Input Power (W) 4,140