LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well...

78
Page 1 User Manual LVRSys™ Outdoor Low Voltage Regulator System TM (Low voltage regulator system)

Transcript of LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well...

Page 1: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 1

User Manual

LVRSys™ Outdoor

Low Voltage Regulator SystemTM

(Low voltage regulator system)

Page 2: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 2 User guidance

We take care of it.

Contents 1. User guidance ................................................................................................................ 5

1.1 Target group ............................................................................................................................. 5

1.2 Warnings ................................................................................................................................... 5

1.3 Tips ............................................................................................................................................ 5

1.4 Other symbols ........................................................................................................................... 6

1.5 Applicable documentation ........................................................................................................ 6

1.6 Storage ...................................................................................................................................... 6

2. Scope of Delivery/Options .............................................................................................. 7

2.1 Scope of delivery standard system ........................................................................................... 7

2.2 Options ...................................................................................................................................... 7

2.2.1 Integrated cable distribution box ............................................................................................. 7

2.2.2 Voltage/current measurements ............................................................................................... 7

2.2.3 Service power output ............................................................................................................... 8

2.2.4 External components ................................................................................................................ 8

2.2.5 Power quality measurement .................................................................................................... 8

2.2.6 Pivot lever locking cylinder ....................................................................................................... 8

2.2.7 Control technology ................................................................................................................... 9

2.2.8 Connection technology ............................................................................................................. 9

3. Safety instructions .......................................................................................................... 9

4. Technical Data .............................................................................................................. 10

5. Intended use ................................................................................................................ 12

6. Description and Principle of Operation .......................................................................... 13

7. Packaging and transport ............................................................................................... 15

7.1 Packaging ................................................................................................................................ 16

7.1.1 Cabinet .................................................................................................................................... 16

7.1.2 Transformer block ................................................................................................................... 16

7.1.3 Concrete base ......................................................................................................................... 17

7.2 Transport on pallets ................................................................................................................ 17

7.2.1 Cabinet .................................................................................................................................... 17

7.2.2 Transformer block ................................................................................................................... 18

7.2.3 Concrete base ......................................................................................................................... 18

7.3 Transport by crane .................................................................................................................. 18

7.3.1 Cabinet .................................................................................................................................... 18

7.3.2 LVRSysTM cabinet ..................................................................................................................... 18

Page 3: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 3

7.3.3 Transformer block .................................................................................................................. 20

8. Installation .................................................................................................................... 22

8.1 System overview .................................................................................................................... 22

8.2 Covering ................................................................................................................................. 23

8.3 LVRSys™ assembly ................................................................................................................. 24

8.4 Base hole for grounding base ................................................................................................ 24

8.5 Mounting of the ground base ................................................................................................ 25

8.6 Insertion of the transformers package .................................................................................. 26

8.7 Mounting the LVRSys™ on a concrete base ........................................................................... 27

8.8 Closure ................................................................................................................................... 28

8.9 Electrical connection of the transformer block and LVRSys ™ cabinet ................................. 29

8.9.1 Primary wires and temperature contacts .............................................................................. 29

8.9.2 Secondary wires ..................................................................................................................... 29

8.10 PEN and local grounding point ............................................................................................... 30

8.11 Connecting the low-voltage cable ......................................................................................... 30

9. Put the LVRSys™ into operation and take it out of operation .......................................... 32

9.1 Put the LVRSys™ into operation............................................................................................. 35

9.2 Take LVRSys™ out of operation and BYPASS mode ............................................................... 36

10. Operation/Regulator operation ..................................................................................... 37

10.1 Indicator lamps ...................................................................................................................... 37

10.2 Switches ................................................................................................................................. 37

10.3 Boot process .......................................................................................................................... 37

10.4 Menu navigation .................................................................................................................... 38

10.5 Automatic mode .................................................................................................................... 39

10.6 Blocked mode ........................................................................................................................ 39

10.7 Manual mode ......................................................................................................................... 40

10.8 Overview of the displays ........................................................................................................ 41

10.9 Parameters ............................................................................................................................. 42

10.9.1 Set point ................................................................................................................................. 43

10.9.2 Tolerance band+ and tolerance band- ................................................................................... 43

10.9.3 Time delay .............................................................................................................................. 44

10.9.4 Grid impedance ...................................................................................................................... 45

10.9.5 Synchro phasing ..................................................................................................................... 46

10.10 Setup ...................................................................................................................................... 46

10.10.1 Phase spacing ......................................................................................................................... 47

10.10.2 KNI (current transformer factor)............................................................................................ 47

10.10.3 Communication ...................................................................................................................... 47

Page 4: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 4 User guidance

We take care of it.

10.10.4 NTP Time Synchronisation ...................................................................................................... 47

10.10.5 Language ................................................................................................................................. 47

10.10.6 Delete statistics ....................................................................................................................... 47

10.11 Drag indicator ......................................................................................................................... 47

10.12 Info/Update ............................................................................................................................ 48

10.12.1 Firmware update .................................................................................................................... 48

10.12.2 LOG ERR .................................................................................................................................. 50

10.12.3 Archive log book ..................................................................................................................... 50

10.12.4 Evaluate logbook (Measurement data) with Microsoft Excel ................................................ 52

10.12.5 Evaluate logbook (Event data) in Notepad++ ......................................................................... 55

10.13 Communication ....................................................................................................................... 56

10.13.1 Modbus ................................................................................................................................... 56

10.13.2 IEC 60870-5-104 ...................................................................................................................... 59

10.13.3 NTP Time Synchronisation ...................................................................................................... 65

10.13.4 Additional log files .................................................................................................................. 65

11. Controls and Power stage ............................................................................................. 66

11.1 Controls ................................................................................................................................... 66

11.2 Interfaces and log files ............................................................................................................ 67

11.2.1 USB .......................................................................................................................................... 67

11.2.2 Ethernet .................................................................................................................................. 67

11.2.3 RS 232 ..................................................................................................................................... 67

11.2.4 RS 485 ..................................................................................................................................... 68

11.3 Current transformers .............................................................................................................. 68

11.4 Power stage ............................................................................................................................ 68

11.5 Current transformers .............................................................................................................. 69

11.6 Fuses Power stage .................................................................................................................. 69

11.7 Microfuses .............................................................................................................................. 71

11.8 Lightning protection ............................................................................................................... 72

11.9 Transformer protection .......................................................................................................... 73

12. External devices and modifications ............................................................................... 74

12.1 External devices ...................................................................................................................... 74

12.2 PQI-DA smart .......................................................................................................................... 74

13. Servicing/Cleaning/Spare parts ..................................................................................... 75

14. Standards and Laws ...................................................................................................... 75

15. Disassembly and disposal ............................................................................................. 76

16. Warranty ..................................................................................................................... 76

Page 5: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 5

1. User guidance

This User Manual is a summary of the information needed for the installation, putting into operation and operation of the low-voltage regulator.

Read the User Manual in its entirety and do not use the product unless you have understood what you read.

1.1 Target group

The User Manual is intended for skilled technicians as well trained and certified operators.

The contents of this User Manual must be accessible to people tasked with the installation and operation of the system.

1.2 Warnings

Structure of the warnings

Warnings are structured as follows:

SIGNAL WORD

Nature and source of the danger.

Consequences in the event of non-observance.

Actions to avoid the danger.

Types of warnings

Warnings are distinguished by the type of danger they are warning against:

DANGER! Warns of an immediately impending danger that can result in death or serious injuries when not avoided.

WARNING! Warns of a potentially dangerous situation that can result in death or serious injuries when not avoided.

CAUTION! Warns of a potentially dangerous situation that can result in fairly serious or light injuries when not avoided.

NOTICE: Warns of a potentially dangerous situation that results in material or environmental damage when not avoided.

1.3 Tips

Tips on the appropriate device use and recommendations.

Page 6: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 6 User guidance

We take care of it.

1.4 Other symbols

Instructions

Structure of the instructions:

Instructions for an action.

Indication of an outcome, if necessary.

Lists

Structure of unnumbered lists:

0 List level 1

– List level 2

Structure of numbered lists:

1) List level 1

2) List level 1

1. List level 2

2. List level 2

1.5 Applicable documentation

For the safe and correct use of the product, observe the additional documentation that is delivered with the system as well as the relevant standards and laws.

1.6 Storage

Store the user manual, including the supplied documentation, readily accessible near the system.

Page 7: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 7

2. Scope of Delivery/Options

2.1 Scope of delivery standard system

0 LVRSys™ cabinet (1-phase or 3-phase)

0 Concrete base (for outdoor installation) (feature C1)

0 Transformer block (feature B2)

0 LVRSys™ user manual

0 LVRSys™ Mounting instructions

0 Circuit diagram LVRSys™ cabinet

0 LVRSys™ test certificate

2.2 Options

2.2.1 Integrated cable distribution box

0 1 input and 1 output (standard) (feature J0)

0 Unregulated 1 additional input (feature J1)

(Cabinet widened by 20cm)

0 Unregulated 2 additional inputs (feature J2)

(Cabinet widened by 20cm)

0 Unregulated 3 additional inputs (feature J3)

(Cabinet widened by 40cm)

0 Regulated 1 additional output (feature J4)

(Cabinet widened by 20cm)

0 Regulated 2 additional outputs (feature J5)

(Cabinet widened by 20cm)

0 Regulated 3 additional outputs (feature J6)

(Cabinet widened by 40cm)

0 Combinations of inputs and outputs on demand (feature J9)

0 (With each 2 switch strips the cabinet widened by 20cm)

2.2.2 Voltage/current measurements

In the standard system, the regulator only needs the output voltages of the LVRSys™. The output has in each case 3 test connections. Measurements can be extended/specified by:

Page 8: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 8 Scope of Delivery/Options

We take care of it.

0 Without current measurement (feature M0)

0 Current measurement 3x (output) (feature M1)

0 Current measurement 4x (output) (feature M2)

0 Current measurement 3x (input) (feature M3)

0 Current measurement 4x (input) (feature M4)

0 Current measurement for PQI DA-smart (feature M5)

2.2.3 Service power output

The service power output can be specified by:

0 Without Schuko socket (feature K0)

0 Schuko socket with FI fuse (CEE 7/4) (Germany - 16 A) (feature K1)

0 Socket with FI fuse (SEV 1011) (Switzerland – Typ 13 / 16 A) (feature K2)

0 More on request (feature K9)

2.2.4 External components

Measuring devices, remote controls, etc… can be installed in the cabinet upfront if so

agreed in the planning phase. They can be specified as:

0 Without external installation (feature P0)

0 Communication module (feature P1)

0 More on request (feature P2)

2.2.5 Power quality measurement

Power quality measurements can be specified by:

0 Without PQI DA-smart (feature I0)

0 Power quality measurement at LVRSys™ output (M5 must be selected) (feature I1)

0 Power quality measurement at LVRSys™ input (M5 must be selected) (feature I2)

0 2x PQI DA-smart (M5 must be selected) (feature I3)

2.2.6 Pivot lever locking cylinder

0 Profile cyliner DIN 18254 (standard) (feature N1)

0 Pivot lever locking cylinder Ø 22 each (feature N2)

0 More on request (feature N9)

Page 9: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 9

2.2.7 Control technology

0 Without control technology (feature L0)

0 Modbus TCP/IP (standard) (feature L1)

0 IEC 60870-104 (feature L2)

0 More on request (feature L9)

2.2.8 Connection technology

0 Flat terminals M12 25 mm² - 240 mm² (from 70 kVA and more) (feature D1)

0 V-Steal-box terminals 25 mm² - 300 mm² (from 70 kVA and more) (feature D2)

0 Box terminals 16 mm² - 300 mm² (for systems up to 70 kVA) (feature D3)

0 Direct connection isolator (contained in B3) (feature D4)

0 More on request (feature D9)

3. Safety instructions

Follow the operating instructions.

Keep the operating instructions with the device.

Do not operate the device if it is not in impeccable condition.

Make sure the device is only operated by qualified personnel.

Connect the device as specified.

Make sure the device is not operated outside the design limits (see Sec. 4 Technical Da-

ta).

Do not use the device in environments where explosive gases, dust or fumes occur

Make sure the front covers are present and close properly.

Clean the device only with commercially available cleaning agents.

Page 10: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 10 Technical Data

We take care of it.

4. Technical Data

Ambient temperature -40°C to 45°C

Maximum permitted air temperature in the switch cabinet

70 °C

Altitude of the installation (NN) < 2000 m

Safety class IP 55/electronic IP 66

Rated voltage 400 V/230 V ±20% (L-L/LE)

Rated current 32 A (22 kVA system)

63 A (44 kVA system)

100 A (70 kVA system)

125 A (87 kVA system)

160 A (110 kVA system)

200 A (144 kVA system)

250 A (175 kVA system)

355 A (250 kVA system)

580 A (400 kVA system)

909 A (630 kVA system)

Rated frequency 50 Hz

Rated impulse withstand voltage 6 kV

Short time current resistance (1 s) 5 kA (up to 44 kVA system)

15 kA (70 kVA up to 630 kVA system)

Rated conditional short-circuit current 20 kA (up to 44 kVA system)

50 kA (70 kVA up to 630 kVA system)

Rated conditional short-circuit current

protected with fuses

3 kA (22 kVA system)

5 kA (44 kVA system)

10 kA (70 kVA system)

12 kA (87 kVA system)

14 kA (110 kVA system)

16 kA (144 kVA system)

20k A (175 kVA system)

30 kA (250 kVA system)

50 kA (400 kVA system)

50 kA (630 kVA system)

High rated peak withstand currents 20 kA (up to 44 kVA system)

50 kA (70 up to 630 kVA system)

Efficiency 99.4% - 99.8%

Regulation ranges

±6 % of

±7 % of

±8 % of

±10 % of

±16 % of

Up to ±24 % of

Page 11: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 11

Step number/Distance 6 %

Step number/Distance 7 %

Step number/Distance 8 %

Step number/Distance 10 %

Step number/Distance 16 %

Step number/Distance 24 %

9 / 1.5 %

9 / 1.75 %

9 / 2 %

9 / 2.5 %

9/ 4 %

9 / 6 %

Switch cabinet dimensions W/D/H

80 cm/40 cm/135 cm (22 kVA - 44 kVA System)

120 cm/40 cm/135 cm (87 kVA - 250 kVA System)

140 cm/40 cm/135 cm (400 kVA System 6 %)

140 cm/50 cm/145 cm (400 kVA System 10 %)

160 cm/50 cm/155 cm (630 kVA System)

Switch cabinet weight

100 kg (22 kVA - 44 kVA System)

150 kg (87 kVA - 250 kVA System)

200 kg (400 kVA System 6 %)

220 kg (400 kVA System 10 %)

300 kg (630 kVA System)

Ground base W/D/H dimensions

80 cm/40 cm/100 cm (22 kVA - 44 kVA System)

120 cm/40 cm/100 cm (87 kVA - 250 kVA System)

140 cm/40 cm/100 cm (400 kVA System 6 %)

140 cm/50 cm/100 cm (400 kVA System 10 %)

160 cm/50 cm/100 cm (630 kVA System)

Ground base weight

200 kg (22 kVA - 44 kVA System)

260 kg (87 kVA - 250 kVA System)

280 kg (400 kVA System 6 %)

290 kg (400 kVA System 10 %)

320 kg (630 kVA System)

Dimensions W/D/H of transformer block 3-phase

40 cm/28cm/100cm (22 kVA System)

40 cm/28cm/100cm (44 kVA System)

40 cm/28cm/100cm (70 kVA System)

40 cm/28cm/100cm (87 kVA System)

50 cm/28cm/100cm (110 kVA System)

50 cm/28cm/100cm (144 kVA System)

50 cm/28cm/100cm (175 kVA System)

50 cm/28cm/100cm (250 kVA System)

70 cm/35cm/100cm (400 kVA System)

70 cm/35cm/100cm (630 kVA System)

Page 12: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 12 Intended use

We take care of it.

Table 4-1 Technical data

5. Intended use

This product is designed exclusively to regulate voltage at the low voltage level (400V L-L).

Weight of transformer block 3- phase

60 kg ( 22 kVA System)

100 kg( 44 kVA System)

120 kg ( 70 kVA System)

150 kg ( 87 kVA System)

150 kg (110 kVA System)

170 kg (144 kVA System)

200 kg (175 kVA System)

250 kg (250 kVA System)

450 kg (400 kVA System)

550 kg (630 kVA System)

Max. power consumption of secondary electronics

200 mA (230 V)

Cooling - passive (convection via switch cabinet housing)

- active (redundant ventilation system)

(depending on the application conditions)

Short-circuit impedance approx. 0.3%

Maximum phasing duration 30 ms

Noise emissions < 30 dB(A)

EMC stability DIN EN 61000-6-1

EMC interference emission DIN EN 61000-6-3

Assembly instructions DIN EN 61439-1/5

Low voltage directive 2014/35/EU

Page 13: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 13

Description and Principle of Operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

6. Description and Principle of Operation

The LVRSys™ regulator concept is based on a linear regulator. By coupling and uncoupling two transformers with a selected transfer ratio, the output voltage can be regulated in several (e.g. 9) steps. The maximum control range depends on the version (e.g. from ±6% up to ±20%).

The transformers are controlled by thyristors. The stages of the transformers are determined by the thyristors' switching settings.

Step Transformer 1.5%/2.5%

Transformer 4.5%/7.5%

-6% -1.5% -4.5%

-4.5% 0% -4.5%

-3% +1.5% -4.5%

-1.5% -1.5% 0%

0% 0% 0%

+1.5% +1.5% 0%

+3% -1.5% +4.5%

+4.5% 0% +4.5%

+6% +1.5% +4.5%

Table 6-1 Generation of the voltage levels in steps

The control signals for the thyristors are generated by driver circuits that switch them intelligently. By monitoring the magnetic flux in the transformers, the transformers can be switched without voltage dips, current increases or generating harmonics.

The step change required is output by the controller. The controller can determine the step based on the bus bar voltage or the output currents.

All three phases are regulated independently of one another. This helps improve the symmetry of the grids.

The safety contactor activates automatically in the event of a failure. This ensures that the transformers are shorted and as such the low-voltage grid will operate unregulated.

Page 14: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Description and Principle of Operation

Page 14

We take care of it.

V_in

V_o

ut

TC

F

T

S

TR2TR1

Figure 6-1 Single-phase functional diagram

TR1 Additional transformer 1

TR2 Additional transformer 2

F Fuse

S Safety contactor (NCC principle)

T Thyristor

TC Thyristor control

V_in Unregulated input voltage

V_out Regulated output voltage

Table 6-2 Explanation of the abbreviations

Page 15: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 15

Packaging and transport

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

V_in

V_o

ut

TC

4,5% TR 1,5% TR

Figure 6-2 Example of 3% voltage reduction

In the example shown in Figure 6-2, the output voltage is reduced by 3% compared with the input voltage. The transformer 4.5% TR converts the primary voltage, which is switched by thyristors, in a negative direction and subtracts 10.35 V (4.5% of 230 V) from the output voltage. The transformer 1.5% TR converts the primary voltage in a positive direction and adds 3.45 V (1.5% of 230 V) to the output voltage.

7. Packaging and transport

Figure 7-1: LVRSysTM Outdoorsystem with transformer block and concrete socket

Page 16: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Packaging and transport

Page 16

We take care of it.

7.1 Packaging

7.1.1 Cabinet

Figure 7-2 Packaging and shock stickers

To protect the system, the packaging consists of USB plates.

Check the shock stickers before opening.

For red stickers:

Do not remove the packaging.

Contact A. Eberle GmbH & Co. KG.

7.1.2 Transformer block

The transformer block is packed in an upright position and anchored on a pallet. The transport packing is a film.

Page 17: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 17

Packaging and transport

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

7.1.3 Concrete base

The concrete base is packed in individual parts on a pallet

7.2 Transport on pallets

7.2.1 Cabinet

CAUTION! Switch cabinet can be damaged if handled incorrectly during transport!

Only transport LVRSys™ in an upright position.

Make sure the switch cabinet cannot topple over.

Fasten mounting devices on the board wall.

Figure 7-3 Transporting the cabinet by lorry

Page 18: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Packaging and transport

Page 18

We take care of it.

7.2.2 Transformer block

CAUTION! Transformer block can be damaged if handled incorrectly during transport!

Only transport transformer block in an upright position.

Make sure the transformer block cannot topple over.

Fasten mounting devices on the board wall.

7.2.3 Concrete base

No special transport sensitivities

7.3 Transport by crane

7.3.1 Cabinet

DANGER! Falling switch cabinet is a danger to life!

Make sure no one is below a hanging load.

CAUTION! Falling switch cabinet can damage the system!

Secure the LVRSys™ with all of the transport lugs.

Load the transport lugs only with vertical load (maximum devia-tion 60°).

Do not lift the LVRSys™ with a jolt.

7.3.2 LVRSysTM cabinet

Removing the hood:

Loosen the screws at the front (1).

Lift the hood at the front (2).

Push the hood to the back (3).

Lift the hood upward (4).

Installing the hood:

Lower the hood from above (5).

Push the hood to the front (6).

Fasten the screws at the front (7).

Page 19: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 19

Packaging and transport

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Figure 7-4 Installing and removing the hood

The screws can be loosened and fastened with a TX 25 screwdriver. The tightening torque may not exceed 6 Nm.

Use all four transport lugs.

1 2

3 4 5

6

1 2

7

Page 20: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Packaging and transport

Page 20

We take care of it.

Figure 7-5 Transport lugs

7.3.3 Transformer block

DANGER! A falling transformer block represents a danger to life!

Make sure no one is below a hanging load.

CAUTION! Falling transformer block can damage the system!

Secure the transformer block with all of the transport lugs.

Load the transport lugs only with vertical load (maximum devia-tion 60°).

Do not lift the transformer block with a jolt.

Page 21: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 21

Packaging and transport

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Figure7-6: Transformer block with 4 crane lugs

Use all four transport lugs.

Page 22: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Installation

Page 22

We take care of it.

8. Installation

8.1 System overview

PEN

8

1

23

4

5

6

7

8 9 10 11 12

Figure 8-1 LVRSysTM system overview

Page 23: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 23

Installation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

1 LVRSysTM cabinet

2 Concrete base

3 Transformer block

4 Cabinet for electronic IP66

5 Switch-disconnector-fuse for connection to the low voltage network and bypass

6 PEN bus with insert nuts M12 and M8

7 C-profile bus for cable catch

8 Switch disconnector fuse connection for LVRSysTM IN (Intern/transformer block secondary connection input) NH2 in systems up to 250 kVA

NH3 in systems for 400 kVA and higher

9 Switch disconnector fuse connection for cable input (Accessibility for external wires from local grid transformer)

NH2 in systems up to 250 kVA

NH3 in systems for 400 kVA and higher

10 Bypass connector

NH2 in systems up to 250 kVA

NH3 in systems for 400 kVA and higher

11 Switch breaker fuse connection for the cable output (Accessibility for external wires from the load)

NH2 in systems up to 250 kVA

NH3 in systems for 400 kVA and higher

12 Switch breaker fuse connection for LVRSysTM OUT (Intern/transformer block secondary connection output)

NH2 in systems up to 250 kVA

NH3 in systems for 400 kVA and higher

Table 8-3 Explanation of Figure 8-1 listed numbers

8.2 Covering

The LVRSysTM must be protected against short circuit and continuous overcurrent. All systems are designed with a safety equipment according to Table

In consultation with the A. Eberle Support Team larger fuses may be used as indicated.

Page 24: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Installation

Page 24

We take care of it.

Circuit breaker C

NH- fuse gG NH2

NH- fuse gG NH3

32 A (22 kVA system)

63 A (44 kVA system)

100 A (70 kVA system)

125 A (87 kVA system)

160 A (110 kVA system)

200 A (144 kVA system)

250 A (175 kVA system)

355 A (250 kVA system)

400 kVA (400 kVA system)

630 kVA (630 kVA system)

Table 8-4 System covering at the input (connecting block 9)

8.3 LVRSys™ assembly

Make sure there is sufficient ventilation to extract the heat.

Observe the following minimum distances:

– 10 cm to walls or other switch cabinets

– 50 cm to the ceiling

– 100 cm to 120 cm near doors.

Avoid direct sunlight.

8.4 Base hole for grounding base

Cut out a base hole that is 110 to 130 cm deep.

Found it with 30 cm of broken stones and gravel.

Pave foundation (

Install the grounding base.

Figure 8-2 FoundingMounting the grounding base

Page 25: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 25

Installation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

8.5 Mounting of the ground base

Two people are needed to set up the base.

Required tools

0 Spirit level

0 Wrench 13 and 19, 25 Nm.

When edging the base with flagging or similar material, a minimum distance to the base of 5 cm must be observed as an expansion gap.

Do not bring vibratory equipment in contact with the base.

To avoid the collection of condensation around the base, seal the final layer of filling in the base with suitable material.

Recommendation:

0 Dry fine gravel as the bottom layer

0 Dry river sand as the middle layer

0 Poor concrete, gas concrete or styrofoam as the final layer.

The grounding base is made of light-weight concrete and consists of:

0 Foundation plate

0 Two side components

0 Two split base plates

0 Installation material

0 Fastening screws.

To give the sides more stability, support them with earth-moist concrete.

Align the foundation plate with recesses facing upward

Page 26: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Installation

Page 26

We take care of it.

Place the side components with notches facing upward on the foundation plate.

Fasten the rear panel:

Connect the larger plate at the bottom with two screws and brackets to the side components.

Connect the smaller plate at the top with two screws and brackets to the side components.

Pull through the wiring.

Of the two-part front panel, first fasten the larger plate at the bot-tom with two screws and brackets to the side components.

Then connect the smaller plate at the top with two screws and brackets to the side components.

Installation depth of the ground-ing base ca. 70 cm

Figure 8-3 Installing the grounding base

8.6 Insertion of the transformers package

Embedded the transformer package on the left side of the socket (front view).

Transformer package with connection cable (thick cables) to the left and thin connect-ing cables with plugs for the control electronics to the right.

Correction of the transformer package so no walls are touched.

Page 27: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 27

Installation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Transformer Package

Connection cable Switch disconnector

(left side)

Connection cable control unit

(right side)

Figure 8-4 : Top view earthing base and transformer package

8.7 Mounting the LVRSys™ on a concrete base

Figure 8-5 Mounting ducts

Connect the switch cabinet through four mounting ducts with the grounding base.

Only use the provided screws M 12 x 25 mm.

Page 28: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Installation

Page 28

We take care of it.

8.8 Closure

Installing and removing the locking cylinder:

Turn the cover cap to the right to open it (1).

Insert the key in the locking cylinder and turn right to open (2).

Unscrew fastening screw (M5) from the locking cylinder (3).

Pull out the locking cylinder towards the switch cabinet (4).

Slide in the new locking cylinder (5).

Screw fastening screw (M5) into the locking cylinder (6).

Insert the key in the locking cylinder and turn left to lock (7).

Turn cover cap left to close (8).

Figure 8-6 Installing and removing the locking cylinder

1 2

3 4 5

6

1 2

7 8

Page 29: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 29

Installation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

8.9 Electrical connection of the LVRSys ™ cabinet and the trans-

former block

8.9.1 Primary wires and temperature contacts

Affix coded plug on the housing bottom

Locking plug and fix the wires with cable clamping clips

Figure 8-7 Connection of the transformer and the electrical control

8.9.2 Secondary wires

(1) Connect secondary wires of the transformer (1/Lin//2/Lin//3/Lin) with LVRSys IN NH- disconnector (cable lug)

(5) Connect secondary wires of the transformer (1/Lout//2/Lout//3/Lout) with LVRSys OUT NH- disconnector (cable lug)

Fix wires with cable clamping clips

1 2 3 4 5

Figure 8-8 Switch-disconnector-fuse

Page 30: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Installation

Page 30

We take care of it.

8.10 PEN and local grounding point

The operator of the installation must ensure that the local grounding point is conform with DIN 18014 or DIN EN 62305-3.

Connect the local grounding point to the PEN bus

Connect PEN input with PEN bus

Connect PEN output with PEN bus

Figure 8-9 Connection of the PEN bus with insert nut

8.11 Connecting the low-voltage cable

DANGER! Danger of electric shock!

Make sure the LVRSys™ is de-energized before connecting it.

CAUTION! Destruction of components due to overload!

Use cable clasps in the LVRSys™ system's inputs and outputs.

CAUTION! Destruction of components due to overload!

Only switch on the low voltage grid in BYPASS mode. (See Sec. 9.2 Take LVRSys™ out of operation and BYPASS mode).

Sequence:

Isolate the low voltage grid.

Clamp L1/L2/L3 according to DIN EN 61439.

Clamp PEN/local cabinet grounding according to DIN EN 61439.

Install the cable clips on C profile rails under input and output.

Couple the low voltage grid.

Page 31: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 31

Installation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Figure 8-10 Installation of low voltage cables with flat connector

For Aluminum wires the oxide layer must be mechanically removed and the conduction

must be treated with acid and alkali free fat before contacting the cables.

System Flat terminals (Nm)

feature D1

Box terminals (Nm)

feature D2/D3

Up to 70 kVA 3,5

70 kVA up to 250 kVA (NH2) 35 - 40 32

400 kVA up to 630 kVA (NH3) 35 - 40 32

Table 8-5 Torque table connection LVRSys™

Page 32: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Putting in and taking out of operation of the LVRSys™

Page 32

We take care of it.

9. Putting in and taking out of operation of the LVRSys™

DANGER! Danger of electric shock!

Never open the NH separator partially.

Always use the handle to open the lid.

NH fuses are intended exclusively for use by skilled electricians or people trained in electrotechnical work, see IEC 60269-2.

The following must be observed when switching devices:

Make sure the device is put into and taken out of operation and operated by skilled electricians only or people who have been trained according to VDE 0105-100.

Use the handle to operate the fuse lid.

Figure 9-1 Operation NH- Disconnector

Page 33: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 33

Putting in and taking out of operation of the LVRSys™

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Error OperationService-Switch

System- Switch

Figure 9-2 Signal lamps and switches

StateOff

StateOn

Figure 9-3 Switch position

Page 34: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Putting in and taking out of operation of the LVRSys™

Page 34

We take care of it.

1 2 3 4 5

Figure 9-4: NH-load bar

CAUTION! Voltage interruption in the low voltage grid!

(2) Connecting bar LV-grid input. Do not connect at any time!

(4) Connecting bar LV-grid output. Do not connect at any time!

1 Connection load bar for LVRSys IN (intern/transformer block secondary wire

input)

2 Connection load bar for INPUT (connection external wires coming from local

grid transfomer)

3 Bypass

4 Connection load bar for OUTPUT (connection external wires going to the load)

5 Connection load bar for LVRSys OUT (intern/transformer block secondary wire

output)

Page 35: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 35

Putting in and taking out of operation of the LVRSys™

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

9.1 Put the LVRSys™ into operation

The initial position is:

0 Closed BYPASS.

0 Open input (LVRSys-IN).

0 Open output (LVRSys-OUT).

0 The regulator in position Off.

CAUTION! Destruction of components due to overload!

Only switch on the LVRSys™ according to the described process.

Close LVRSys-IN.

Close LVRSys-OUT.

Open LVRSys-BYPASS.

Switch regulator to ON position (See Sec. 10.2).

Regulator automatically moves up.

LVRSys™ is active.

Local network is regulated over LVRSys™.

Page 36: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Putting in and taking out of operation of the LVRSys™

Page 36

We take care of it.

9.2 Take LVRSys™ out of operation and BYPASS mode

The initial position is:

0 Closed input (LVRSys-IN).

0 Closed output (LVRSys-OUT).

0 The regulator in position ON.

0 Open BYPASS.

CAUTION! Destruction of components due to overload!

Isolate the LVRSys™ only according to the described process.

Switch regulator to OFF position

Electronics (regulator/actuator/contactors) are de-energized.

Transformers are short-circuited through opener contactors.

Close LVRSys-BYPASS.

Open LVRSys-OUT.

Open LVRSys-IN.

LVRSys™ is isolated from the grid.

BYPASS is active.

The local grid is supplied through the BYPASS.

Page 37: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 37

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10. Operation/Regulator operation

10.1 Indicator lamps

The red and green indicator lamps show that state the system is in:

0 Red: Error state

0 Green: Error-free state; system is in operating mode.

Follow the instructions. when an indicator lamp illuminates red.

Note the error code (Sec. 10.12.2).

When the error cannot be corrected, you have to contact the A.Eberle support team.

Take the system out of operation as described in Sec. 9.2 Take LVRSys™ out of opera-

tion and BYPASS mode.

You must follow A. Eberle GmbH & Co. KG.'s instructions when putting the system back

into operation.

10.2 Switches

The switch settings create the following states:

0 Switch system on:

– Switch to the right: System on

– Switch upward: System off

0 Switch service switch:

– Switch to the right: Switch service active

– Switch upward: Switch service inactive

The use of the service switch is reserved for firmware updates.

10.3 Boot process

Activating the System on switch automatically starts the regulator's boot process.

After 25 seconds, the display shows Boot....

After completing the boot process (ca. 45 sec), the regulator is in 'Automatic'

mode.

Page 38: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 38

We take care of it.

The boot process must be completed in order to perform all other activities such as configuration, changing the display pages, etc.

10.4 Menu navigation

By default, the regulator is in Automatic mode when operating error free.

The main display shows the external conductor's three phase voltages and the current tap for each phase.

Figure 10-1 Regulator display

1 Mode

2 Browse up (only in the user menu or active manual mode)

3 Enter key (confirm)

4 Browse right

5 Browse down (only in the user menu or active manual mode)

6 Browse left

1

2

3 4

5

6

Page 39: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 39

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.5 Automatic mode

The regulator is active in Automatic mode. After the boot process (connecting the supply voltage) has finished, the regulator switches into Automatic mode.

Figure 10-2 Automatic mode

The display shows:

0 three phase voltages

0 the phases' current tap position

10.6 Blocked mode

The regulator is blocked in blocked mode. Only the Enter key can be activated.

Figure 10-3 Blocked mode display

Page 40: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 40

We take care of it.

10.7 Manual mode

The regulator is not active in Manual mode. A tap change per second is possible. The bars on the graphic time scale turn red in the event of deviations.

Changing taps manually:

Select Manual mode, press Enter in Automatic mode. (See Sec. 10.8 Overview of the

displays).

To switch to a lower tap, press the down key.

To switch to a high tap, press the up key.

Figure 10-4 Manual mode display

The display shows:

0 Mode

0 Phase

0 Current tap position

0 Voltage value

0 Deviation from setpoint in %.

Page 41: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 41

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.8 Overview of the displays

Figure 10-5 Overview of the navigation menu

Page 42: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 42

We take care of it.

10.9 Parameters

Each parameter is described below:

Figure 10-6 Configuring the regulator

Select the Parameter menu (see Sec. 10.8 Overview of the displays).

To select the items submenu, press the up or down key.

Press the Enter key.

Configuration:

The parameters are set by pressing the up/down and left/right keys.

Press Enter to confirm the selection.

Page 43: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 43

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.9.1 Set point

The default is 230 V.

Set the set point.

10.9.2 Tolerance band+ and tolerance band-

The defaults are:

0 225 V for tolerance band– (Tolband neg)

0 235 V for tolerance band+ (Tolband pos)

Set the tolerance bands.

Figure 10-7 Tolerance band zone

1 Regulator active

2 Phasing process

3 Regulator inactive

4 Set point

5 Tolerance bands (tolerance band-/and tolerance band+)

The regulator is inactive if the voltage lies within the area between the tolerance bands. When the tolerance bands are exceeded, the regulator is activated and as such it will switch the phases according to the parameter settings.

Page 44: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 44

We take care of it.

10.9.3 Time delay

The default is 1.

Set time delay to steps of 0.1.

The settable value (time delay) ranges from 0 to 10, where the value of 10 represents the maximum sensitivity.

Figure 10-8 Response time in connection with phase spacing of 1.5%

Figure 10-9 Response time in connection with phase spacing of2.5%

Example: For time delay 1 and voltage deviation 3%:

Phase spacing 1.5% equals to a response time of 9 s.

Phase spacing 2.5% equals to a response time of 15 s.

Page 45: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 45

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.9.4 Grid impedance

The Grid impedance function can only be used if the Current measurement option is integrated (Sec. 2.2 Options).

The default is grid impedance is 0 Ω, hence the impedance is deactivated.

When the impedance is deactivated:

Current-dependent regulation is deactivated.

When the impedance is activated:

Current values are included in regulation.

Resistance symbol displays in the status window.

Set impedance in 0.01 Ω steps.

Figure 10-10 Active Impedance display

The configuration of the grid impedance takes into account the load current in the regulator algorithm.

Example:

0.4kV

PV Feeder

KV

LVRSys™ DT

Figure 10-11 Example network branch with a 500 m cable section

Cable NA2X2Y 4 x 150 mm²

Cable length 500 m

Cable resistance 0.5 km x 0.206 Ω/km = 0.1 Ω

Table 10-1 Cable data

In the example, the voltage value at the end of the cable would deviate from the regulator's voltage value by 100 A x 0.1 Ω = 10 V, at a current flow of 100 A.

When configuring the grid impedance, the regulator constantly calculates the voltage from the voltage value in the regulator + grid impedance x grid current.

500 m

Page 46: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 46

We take care of it.

Type of wire spec. cable resistance Ω/km

NAYY-J 4 x 70 mm² 0,453

NAYY-J 4 x 95 mm² 0,321

NAYY-J 4 x 120 mm² 0,255

NAYY-J 4 x 150 mm² 0,208

NAYY-J 4 x 185 mm² 0,167

NAYY-J 4 x 240 mm² 0,131

Overhead line AL 4 x 50 mm² 0,662

Overhead line AL 4 x 70 mm² 0,519

Overhead line AL 4 x 95 mm² 0,432

Table 10-2: Specification of cable resistance

10.9.5 Synchro phasing

Synchro phasing is deactivated by default.

Activating or deactivating synchro phasing

A. Eberle GmbH & Co. KG. recommends activating synchro phasing in systems with a bus bars, and deactivating it in systems with strand synchro phasing.

10.10 Setup

Figure 10-12 Setup

Select the Setup menu (see Sec. 10.8 Overview of the displays).

Page 47: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 47

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

To select the item submenu, press the up or down key.

Press the Enter key.

Configuration:

The parameters are set by pressing the up/down and left/right keys.

Press Enter to confirm the selection.

10.10.1 Phase spacing

Phase spacing is set at the factory.

Do not change the phase spacing.

10.10.2 KNI (current transformer factor)

For A. Eberle GmbH & Co. KG. current transformers, the transfer ratio is set at the factory.

When external current transformers are used:

Enter the conversion ratio.

10.10.3 Communication

See Sec. 10.13 10.13Communication.

10.10.4 NTP Time Synchronisation

See Sec. 10.13.3 NTP .

10.10.5 Language

Possible languages:

0 German

0 English

10.10.6 Delete statistics

Delete individual statistics:

Select.

Confirm selection.

Selected statistic is deleted.

10.11 Drag indicator

Drag indicator contains 15 min average values for the:

0 maximum voltages (Ph 1-3)

0 maximum currents (Ph 1-3)

Page 48: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 48

We take care of it.

0 maximum output values

0 maximum and minimum temperatures in switch cabinet (T 1-2).

– T1: Temperature of the power stage in °C

– T2: Temperature of the air in the switch cabinet in °C.

Values can be reset individually.

Resetting the current values also resets the output values.

10.12 Info/Update

The menu item Info/Update contains:

0 Time

0 Date

0 Firmware version

0 Logbook error entries

0 Run Firmware update

0 Store logbook event.

10.12.1 Firmware update

CAUTION! Destruction of components due to overload!

Make sure the service switch is active before starting the update process.

Activating the service switch isolates the thyristors from the mains voltage and short-circuits the transformers. The control function is out of order. A secure update process can be started.

Update file

Unzip the zip file (from email of download).

Save the files on a FAT32 formatted USB stick

The folder structure below is mandatory, no superordinate folder on the USB stick

(USB-stick:\unzipped files; e.g. E:\...).

Page 49: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 49

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Figure 10-13 Folder structure for the update via the USB stick

Full update procedure:

Activate the service switch. (See Sec. 10.2Switches)

Regulator goes into error mode.

Insert USB stick.

Select menu item Firmware update.

Press Yes to confirm the selection.

Please wait displays.

Do not press any buttons or activate the service switch during the update process.

Regulator needs about 5 minutes for the update process to complete.

The regulator reinitializes.

The regulator stays in error mode while the update is completed.

Deactivate the service switch.

Remove the USB stick.

Regulator goes into automatic mode.

The update procedure is finished.

Page 50: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 50

We take care of it.

10.12.2 LOG ERR

The last error is displayed.

Note the error if the installation/update is malfunctioning or is not complete.

Contact the A. Eberle GmbH & Co. KG. Support team.

Error code table

Transformer 0x001

Contactor 0x002

Overvoltage 0x004

Under voltage 0x008

Over temperature Channel 1 0x010

Over temperature Channel 2 0x020

Over temperature Channel 3 0x040

EEPROM 0x080

SPI 0x100

Input voltage 0x200

Frequency 0x400

Service switch 0x800

Table 10-3 The error code table

10.12.3 Archive log book

Insert USB stick.

Select menu item Logbook.

Select submenu item Start time.

Data are archived from the start time.

The data Event data, measurement data, service data must be activated to archive them.

0 ( ) Selection inactive

0 (x) Selection active

Select the submenu item Event data, measurement data and service data.

Select with the up or down key.

Press Yes to confirm the selection.

Select the submenu item Archive data.

Press Yes to confirm the selection.

Please wait displays.

Page 51: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 51

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Regulator writes data to the USB stick.

Event data

Event data list contains:

0 Parameters

0 Reparameterization

0 State (Automatic/Manual/Blocked)

0 State changes (Automatic-Manual)

0 Error

Measurement data

Measurement data list contains:

0 U1 to U3 (10 minutes average values in V)

0 U1Z to U3Z (10 minutes average values in V, only with option current transformer and

0 I1 to I3 (10 minutes average values in A; only for option Current transformer)

0 P1 to P3 (10 minutes average values in kW; only for option Current transformer)

0 Q1 to Q3 (10 minutes average values in kvar; only for option Current transformer)

0 S1 to S3 (10 minutes average values in kVA; only for option Current transformer)

0 T1 to T3 (10 minutes average values in °C)

0 Tap 1 to Tap 3 (current tap position Ph1-Ph3 at the time)

0 Taps/Period 1-3 (10 minutes average values of tap position Ph1-Ph3).

Service data

Service data are intended solely for the A. Eberle GmbH & Co. KG. support team to perform evaluations.

Page 52: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 52

We take care of it.

10.12.4 Evaluate logbook (Measurement data) with Microsoft Excel

(other spreadsheet software can also be used).

Open the Measurement data in Excel.

Select the first column (A).

Figure 10-14 Selecting the first column

Under Data, press Text to Columns.

Figure 10-15 Selecting data and text in columns

Convert Text to Columns Wizard - Step 1 of 3 select Delimited.

Page 53: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 53

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Press Next to confirm

Figure 10-16 Text conversion wizard - Step 1 of 3

Convert Text to Columns Wizard - Step 2 of 3 select Space.

Press Next to confirm

Figure 10-17 Text conversion wizard - Step 2 of 3

Convert Text to Columns Wizard - Step 3 of 3 presses on Advanced...

Page 54: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 54

We take care of it.

Figure 10-18 Text conversion wizard - Step 3 of 3

Decimal separator: Select Point.

Press OK to confirm

Press Finish in the Convert Text to Columns Wizard to confirm.

Figure 10-19 Other text import settings

Splitting measurement data across columns.

Page 55: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 55

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.12.5 Evaluate logbook (Event data) in Notepad++

(other text processing software can also be used).

Figure 10-20 Event data opened in Notepad++

Page 56: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 56

We take care of it.

10.13 Communication

10.13.1 Modbus

10.13.1.1 Modbus Setup

Select the submenu Communication to configure the parameters for the communica-

tion interfaces.

Available communication interfaces:

0 Ethernet

0 RS232

0 RS485

Figure 10-21 Overview of the communication settings

Select menu communication (See Sec. 10.8 Overview of the displays).

To select submenu items, press the up or down key

Press the Enter key.

Configuration:

Page 57: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 57

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

The parameters are set by pressing the up/down and left/right keys.

Press Enter to confirm the selection.

Standard parameters for the Modbus Communication are:

0 Address 4

0 Baud rate 19200

0 Data bits 8

0 Parity odd

0 Stop bits 1

0 Handshake Xon/Xoff

0 Transmission delay 0

0 RS232 mode.

10.13.1.2 Register mapping

Input register (16-Bit data, read only)

Name permitted values Standard Addressing

Status 2 - Operation, 1 - Error 2 101

Table 10-4 Status

Holding registers (16-Bit data, read and write)

Name permitted values Standard Addressing

Operating status 0 - Auto, 1 - Manual, 2 - Blocked 0 201

Ph1 Step up 0/1 1 - Command Step up 0 202

Ph2 Step up 0/1 1 - Command Step up 0 203

Ph3 Step up 0/1 1 - Command Step up 0 204

Ph1 Step up 0/1 1 - Command Step down 0 205

Ph2 Step down 0/1 1 - Command Step down 0 206

Ph3 Step down 0/1 1 - Command Step down 0 207

Delete statistics 0/1 1 - Command Delete statistics 0 208

Reset Drag indicator 0/1 1 - Command Reset Drag indicator

0 209

Table 10-5 Operating status and regulator commands

Input register (16-Bit data, read only)

Name permitted values Unit Addressing

Phase spacing 0 - 1000 0.01 301

Step phase 1 0 - 8 1 302

Step phase 2 0 - 8 1 303

Step phase 3 0 - 8 1 304

Voltage phase 1 0 - 65000 0.1 V 305

Voltage phase 2 0 - 65000 0.1 V 306

Page 58: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 58

We take care of it.

Input register (16-Bit data, read only)

Name permitted values Unit Addressing

Voltage phase 3 0 - 65000 0.1 V 307

Current phase 1 0 - 65000 0.1 A 308

Current phase 2 0 - 65000 0.1 A 309

Current phase 3 0 - 65000 0.1 A 310

Active power phase 1 -32500 - 0 - 32500 0.1 kW 311

Active power phase 2 -32500 - 0 - 32500 0.1 kW 312

Active power phase 3 -32500 - 0 - 32500 0.1 kW 313

Apparent power phase 1 0 - 65000 0.1 kVA 314

Apparent power phase 2 0 - 65000 0.1 kVA 315

Apparent power phase 3 0 - 65000 0.1 kVA 316

Reactive power phase 1 -32500 - 0 - 32500 0.1 kVar 317

Reactive power phase 2 -32500 - 0 - 32500 0.1 kVar 318

Reactive power phase 3 -32500 - 0 - 32500 0.1 kVar 319

Step number Day Ph1 0 - 99999999 1 320

Step number Day Ph2 0 - 99999999 1 321

Step number Day Ph3 0 - 99999999 1 322

Step number Week Ph1 0 - 99999999 1 323

Step number Week Ph2 0 - 99999999 1 324

Step number Week Ph3 0 - 99999999 1 325

Step number Month Ph1 0 - 99999999 1 326

Step number Month Ph2 0 - 99999999 1 327

Step number Month Ph3 0 - 99999999 1 328

Step number Year Ph1 0 - 99999999 1 329

Step number Year Ph2 0 - 99999999 1 330

Step number Year Ph3 0 - 99999999 1 331

Temperature Controls 0 - 65000 0.1°C 332

Temperature Power stage 0 - 65000 0.1°C 333

Temperature cabinet 0 - 65000 0.1°C 334

Drag indicator U1 max. 0 - 65000 0.1 V 335

Drag indicator U2 max. 0 - 65000 0.1 V 336

Drag indicator U3 max. 0 - 65000 0.1 V 337

Drag indicator I1 max. 0 - 65000 0.1 A 338

Drag indicator I2 max. 0 - 65000 0.1 A 339

Drag indicator I3 max. 0 - 65000 0.1 A 340

Drag indicator P1 max. 0 - 65000 0.1 kW 341

Drag indicator P2 max. 0 - 65000 0.1 kW 342

Drag indicator P3 max. 0 - 65000 0.1 kW 343

Page 59: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 59

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Input register (16-Bit data, read only)

Name permitted values Unit Addressing

Drag indicator T1 max. 0 - 65000 0.1°C 344

Drag indicator T2 max. 0 - 65000 0.1°C 345

Drag indicator T3 max. 0 - 65000 0.1°C 346

Drag indicator T1 max. 0 - 65000 0.1°C 347

Drag indicator T2 max. 0 - 65000 0.1°C 348

Drag indicator T3 max. 0 - 65000 0.1°C 349

Firmware 0 - 65000 1 350

LOG-ERR 0 - 65000 1 351

Table 10-6 Measurement and informational value registers

Holding registers (16-Bit data, read and write)

Name permitted values Standard Unit Addressing

Mode 0 - RS232; 1 - RS485; 2 - TCP/IP 0 1 401

Baud rate 12, 24, 48, 96, 192, 384, 768, 1152 192 100 Bit/s 402

Parity 0 (none), 1 (odd), 2 (even) 2 --- 403

Address 1..247, 255 according to produc-tion

255 1 404

Set point 0 - 65000 23000 0.01 V 405

Tolerance band+ 0 - 65000 23500 0.01 V 406

Tolerance bands- 0 - 65000 22500 0.01 V 407

Time delay 0 - 1000 100 0.01 408

Synchro phasing 0 - async. 1 - sync. 0 1 409

Grid impedance 0 – 500 0 0.001 Ω 410

Table 10-7 Parameter registers

10.13.2 IEC 60870-5-104

The IEC 60870-5-104 is a communication protocol that communicates over the TCP/IP interface. The IEC Protocol has to be unlocked via a license. If this communication is required, contact the A. Eberle suppport team.

10.13.2.1 License IEC 60870-5-104 unlock

The licensce file will be transmitted by the A. Eberle Support Team and is linked to the serial number of the system.

Save License file on FAT32 formatted USB stick.

Connect USB stick to LVRSys™.

Select menu item License File.

Confirm with Yes.

IEC 60870-5-104 is unlocked.

Page 60: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 60

We take care of it.

10.13.2.2 Process information for monitoring

By default implemented process information to monitor:

Type identification Process information

01 Single message

03 Double message

13 Measured value, short floating

30 Single message with timestamp

31 Double message with timestamp

36 Measured value, short floating with time stamp

Table 10-8 Process information for monitoring

10.13.2.3 Process control information

By default implemented process information to control.

Type identification Process information

45 Single message

46 Double message

50 Setpoint command

63 Setpoint command with timestamp

58 Single command with timestamp

59 Double command with timestamp

100 Query command

103 Time synchronization command

107 Test command with time stamp

Table 10-9 Process control information

10.13.2.4 CSV configuration of the IEC 60870-5-104 Slave

The LVRSys IEC 60870-5-104 Slave can be configurd by using a CSV file. When starting the system, the CSV file will be loaded and the IEC 60870-5-104 slave is then ready for use.

In the standard lvrsys_t104_target.csv all possible configurations are described. The desirec changes must be made directly in the file, using the following steps:

Get CSV-File lvrsys_t104_target.csv from A. Eberle Support-Team.

Adjust CSV-File as desired with Notepad or MS Excel.

Save CSV-File as lvrsys_t104_target.csv (MS-DOS File if MS Excel is used) on a FAT32

formatted USB stick.

Connect USB stick to LVRSys™.

Select menu item Communication->IEC60870-5-104->T104 CSV load.

IEC 60870-5-104 configuration adapted.

Page 61: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 61

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.13.2.5 IEC 60870-5-104 Parameter

0 T104 active (disabled – all configurations 0 / activated – configurations are loaded)

The new configurations of IEC 60870-5-104 Slave will be changed from disabled -

> activated.

0 T104 Station CA is the IP address of the allowed station (ASDU)

Default is 1 (Each station allowed).

0 T104 TCP/IP Port Address of the 1st. instance of the T104

Default is 2404.

0 Timeout (T104 Timeout. Param.)

Parameter Default Notice

t0 30 s Timeout of the connection establishment

t1 15 s Timeout of transmission or testing-ASDUs

t2 10 s Timeout for acknowledgments without data telegrams t2 < t1

t3 20 s Timeout for sending test frames with long time delays

Table 10-10 Timeout parameter

0 T104 IP Bind (enabled only in redundant systems)

LVRSys IEC 60870-5-104 slave can be linked in the first instance to a system IP. This is useful if redundancy systems are used to communicate or there is an additional connection via other networks such as WLAN or UMTS. LVRSys IEC 60870-5-104 slave reads only the first instance.

In redundant systems with different IP addresses and the same port address

T104 IP Bind must be activated.

0 T104 redundancy

Figure 10-22 parameter overview IEC 60870-5-104

10.13.2.6 Redundancy System

0 LVRSys IEC 60870-5-104 slave can use five IEC 60870-5-104 connections simultaneously.

0 Each instance has ist own IEC 60870-5-104 process images and messages.

Page 62: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 62

We take care of it.

LVRSys IEC 60870-5-104 slave does not hold any events or messages in the queue. When the connection is available again messages will be transmitted and the process informations renewed.

If there is no connection the LVRSys IEC 60870-5-104 slave will not renew process

information and collect any messages. Once the connection is available again,

the LVRSys IEC 60870-5-104 slave renews process information and transmits new

messages.

The redundant instances are always connected to the set IP addresses! If no IP

address is set, the instances connect to all networks (IP = 0.0.0.0).

In redundant systems with different IP addresses and the same port address the

T104 IP Bind must be enabled. Otherwise the first instance will connect with all

the networks and the other instances cannot connect.

10.13.2.7 IEC 60870-5-104 register allocation

Alarms/Message

Name Permitted val-

ues Standard

IEC60870-104 Addressing

IEC60870-104 Type

Status Operation EIN -> Betrieb 0 355 30

Status Error ON -> Error 0 356 30

Error 1 (Contactor) ON -> Alarm / OFF -> Normal

- 357 30

Error 2 (Transformer) ON -> Alarm / OFF -> Normal

- 358 30

Error 3 (Service) ON -> Alarm / OFF -> Normal

- 359 30

Error 4 (Over temperature) ON -> Alarm / OFF -> Normal

- 360 30

Table 10-11 Register Alarms/Messages

Commands

Name Permitted val-

ues Standard

IEC60870-104 Addressing

IEC60870-104 Type

Ph1 Step switch ON -> increase / OFF -> decrease

- 551 59

Ph2 Step switch ON -> increase / OFF -> decrease

- 552 59

Ph3 Step switch ON -> increase / OFF -> decrease

- 553 59

Delete statistic ON -> delete - 453 58

Drag indicator resetting ON -> resetting - 454 58

Table 10-12 Register commands

Measured values + counter

Name Permitted val-

ues Standard

IEC60870-104 Addressing

IEC60870-104 Type

Page 63: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 63

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Step Phase 1 0 - 8 0 101 36

Step Phase 2 0 - 8 0 102 36

Step Phase 3 0 - 8 0 103 36

Voltage Phase 1 0 0 104 36

Voltage Phase 2 0 0 105 36

Voltage Phase 3 0 0 106 36

Current Phase 1 0 0 107 36

Current Phase 2 0 0 108 36

Current Phase 3 0 0 109 36

Active Power Phase 1 0 0 110 36

Active Power Phase 2 0 0 111 36

Active Power Phase 3 0 0 112 36

Apparent Power Phase 1 0 0 113 36

Apparent Power Phase 2 0 0 114 36

Apparent Power Phase 3 0 0 115 36

Reactive Power Phase 1 0 0 116 36

Reactive Power Phase 2 0 0 117 36

Reactive Power Phase 3 0 0 118 36

Number of stages Tag Ph1 0 0 119 36

Number of stages Tag Ph2 0 0 120 36

Number of stages Tag Ph3 0 0 121 36

Number of stages week Ph1 0 0 122 36

Number of stages week Ph2 0 0 123 36

Number of stages week Ph3 0 0 124 36

Number of stages month Ph1 0 0 125 36

Number of stages month Ph2 0 0 126 36

Number of stages month Ph3 0 0 127 36

Number of stages year Ph1 0 0 128 36

Number of stages year Ph2 0 0 129 36

Number of stages year Ph3 0 0 130 36

Temperature Cabinet 0 0 131 36

Drag indicator U1 max. 0 0 132 36

Drag indicator U2 max. 0 0 133 36

Drag indicator U3 max. 0 0 134 36

Drag indicator I1 max. 0 0 135 36

Drag indicator I2 max. 0 0 136 36

Drag indicator I3 max. 0 0 137 36

Drag indicator P1 max. 0 0 138 36

Drag indicator P2 max. 0 0 139 36

Drag indicator P3 max. 0 0 140 36

Page 64: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Operation/Regulator operation

Page 64

We take care of it.

Drag indicator Temp Cabinet max.

0 0 141 36

Drag indicator Temp Cabinet min. 0 0 142 36

Table 10-13 Register measured values +counter

Parameters Actual values

Name Permitted val-

ues Standard

IEC60870-104 Addressing

IEC60870-104 Type

Phase spacing 0 – 1000 100 100 36

Synchro phasing ON -> Active,

OFF -> Inactive 0 850 31

Set point 0 0 145 36

Tolerance band + 0 0 146 36

Tolerance band - 0 0 147 36

Time delay 0 0 148 36

Impedance 0 0 149 36

Operation mode Auto ON -> Auto / OFF

-> OFF - 350 30

Operation mode Manual ON -> Manual /

OFF -> OFF - 351 30

Operation mode Blocked ON -> Blocked /

OFF -> OFF - 352 30

Table 10-14 Register Parameters actual values

Set parameters

Name Permitted val-

ues Standard

IEC60870-104 Addressing

IEC60870-104 Type

Synchro phasing ON -> Aktiv, OFF

-> Inaktiv 1 550 59

Set point 200 - 250 230 200 63

Tolerance band + 200 - 250 235 201 63

Tolerance band - 200 - 250 225 202 63

Time delay 0.1 - 10 1 203 63

Impedance 0 - 0.5 0 204 63

Synchro phasing ON -> Auto - 450 58

Set point ON -> Manual - 451 58

Operation mode Blocked ON -> Blocked - 452 58

Table 10-15 Register Set parameters

Additional

Name Permitted val-

ues Standard

IEC60870-104 Addressing

IEC60870-104 Type

FW Version 0 0 144 36

Table 10-16 Register additional

Page 65: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 65

Operation/Regulator operation

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

10.13.3 NTP Time Synchronisation

The NTP Time synchronisation is based on a connection to an NTP server.

Access to network or internet is needed.

Set the desired server IP NTP IP1, NTP IP2.

Possible IP for Internet connection 192.53.103.108 (PTB, Braunschweig)

DST Flag (x) -> Daylight saving time.

( ) -> no Daylight saving time.

Set Time zone relative to GMT (Germany +1).

NTP HW RTC (x) -> Time is not synchronized with NTP.

( ) -> Time is synchronized via NTP if NTP IP set.

10.13.4 Additional log files

Ask A. Eberle GmbH & Co. KG. about the implementation of additional communication

log files.

Page 66: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Controls and Power stage

Page 66

We take care of it.

11. Controls and Power stage

11.1 Controls

Figure 11-1 Controls overview

1 Thyristor driver board

2 Binary input and output circuit board

3 Current and voltage measurement circuit board

4 CPU circuit board

5 Controller display

6 USB interface

7 Ethernet interface

8 RS 232 Interface

9 RS 485 Interface

Table 11-1 Controls description

Page 67: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 67

Controls and Power stage

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

11.2 Interfaces and log files

11.2.1 USB

USB interface is for firmware update and logbook backup.

Figure 11-2 USB interface

11.2.2 Ethernet

Ethernet interface is for communication interface for Modbus applications.

Figure11-3 Ethernet interface

11.2.3 RS 232

RS 232 interface is for communication interface for Modbus applications.

Figure 11-4 RS 232 interface

1 Empty 6 Empty

2 Rx 7 RTS

3 Tx 8 CTS

4 Empty 9 Empty

5 GND

Table 11-2 Description of the interface

Page 68: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Controls and Power stage

Page 68

We take care of it.

11.2.4 RS 485

RS 485 interface is for communication interface for Modbus applications.

Figure 11-5 RS 485 interface

1 P

2 N

3 GND

Table 11-3 Interface description

11.3 Current transformers

DANGER! Danger of electric shock!

Short circuiting of the current transformers.

11.4 Power stage

Page 69: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 69

Controls and Power stage

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

Figure 11-6 Power stage

DANGER! Danger of electric shock!

Don’t remove protective cover

The power stage controls the transformers (See sec. 6 Description and Principle of Operation).

The power stage is behind the Plexiglas cover.

11.5 Current transformers

Current transformers are located in the NH- Disconnector LVRSys Out.

Connectors of the current transformers may be deducted only in the bypass mode.

DANGER! Danger of electric shock!

Bypass operation

11.6 Fuses Power stage

System NH- disconnector/circuit breaker (F1)

Neozed D (F8)

Neozed D (F9)

Neozed D (F7)

22kVA - 6% C 32 Automat 25kA 16A D01 6A D01 6A D01

22kVA - 8% C 32 Automat 25kA 16A D01 6A D01 6A D01

22kVA - 10% C 32 Automat 25kA 16A D01 6A D01 6A D01

22kVA - 16% C 32 Automat 25kA 16A D01 6A D01 6A D01

22kVA - 20% C 32 Automat 25kA 16A D01 6A D01 6A D01

22kVA - 24% C 32 Automat 25kA 16A D01 6A D01 6A D01

44kVA - 6% C 63 Automat 25kA 16A D01 6A D01 6A D01

44kVA - 8% C 63 Automat 25kA 16A D01 6A D01 6A D01

44kVA - 10% C 63 Automat 25kA 16A D01 6A D01 6A D01

Page 70: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Controls and Power stage

Page 70

We take care of it.

System NH-

disconnector/circuit breaker (F1)

Neozed D (F8)

Neozed D (F9)

Neozed D (F7)

44kVA - 16% C 63 Automat 25kA 16A D01 6A D01 6A D01

44kVA - 20% C 63 Automat 25kA 20A D02 6A D01 6A D01

44kVA - 24% C 63 Automat 25kA 25A D02 6A D01 6A D01

55kVA - 6% 80A gG - 000 16A D01 6A D01 6A D01

55kVA - 10% 80A gG - 2 16A D01 6A D01 6A D01

70kVA - 6% 100A gG - 2 16A D01 6A D01 6A D01

87kVA - 7% 125A gG - 2 16A D01 6A D01 6A D01

70kVA - 8% 100A gG - 2 16A D01 6A D01 6A D01

70kVA - 10% 100A gG - 2 16A D01 6A D01 6A D01

70kVA - 16% 100A gG - 2 25A D02 6A D01 6A D01

70kVA – 20% 100A gG - 2 35A D02 10A D01 6A D01

70kVA - 24% 100A gG - 2 40A D02 10A D01 6A D01

110kVA - 6% 160A gG - 2 16A D01 6A D01 6A D01

110kVA - 8% 160A gG - 2 20A D02 6A D01 6A D01

110kVA - 10% 160A gG - 2 25A D02 6A D01 6A D01

110kVA - 16% 160A gG - 2 40A D02 10A D01 6A D01

110kVA - 24% 160A gG - 2 63A D02 16A D01 6A D01

144kVA - 6% 200A gG - 2 20A D02 6A D01 6A D01

144kVA - 7% 200A gG - 2 20A D02 6A D01 6A D01

144kVA - 8% 200A gG - 2 25A D02 6A D01 6A D01

144kVA - 10% 200A gG - 2 35A D02 10A D01 6A D01

175kVA - 6% 250A gG - 2 25A D02 6A D01 6A D01

175kVA - 7% 250A gG - 2 25A D02 10A D01 6A D01

175kVA - 8% 250A gG - 2 35A D02 10A D01 6A D01

175kVA - 10% 250A gG - 2 40A D02 10A D01 6A D01

250kVA - 6% 355A gG - 2 35A D02 10A D01 6A D01

250kVA - 7% 355A gG - 2 40A D02 10A D01 6A D01

250kVA - 8% 355A gG - 2 40A D02 16A D01 6A D01

250kVA - 10% 355A gG - 2 50A D02 16A D01 6A D01

400kVA - 6% 400kVA gTr - 3 50A D02 16A D01 6A D01

400kVA - 8% 400kVA gTr - 3 80A gG - 000 20A D02 6A D01

400kVA - 10% 400kVA gTr - 3 100A gG- 000 25A D02 6A D01

630kVA - 6% 630kVA gTr - 3 100A gG -000 25A D02 6A D01

630kVA - 8% 630kVA gTr - 3 125A gG -000 35A D02 6A D01

630kVA - 10% 630kVA gTr - 3 125A gG -000 35A D02 6A D01

Table 11-4 Fuses Power stage

Page 71: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 71

Controls and Power stage

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

11.7 Microfuses

System resistor 1

5 x 20mm

resistor 2

5 x 20mm

Control unit

5 x 20mm

Measurement circuit

5 x 20mm

22kVA - 6% HT 0,4A 5x20 HT 0,5A 5x20 3,15 A T 5x20 2 A T 5x20

22kVA - 8% HT 0,4A 5x20 HT 0,63A 5x20 3,15 A T 5x20 2 A T 5x20

22kVA - 10% HT 0,4A 5x20 HT 0,63A 5x20 3,15 A T 5x20 2 A T 5x20

22kVA - 16% HT 0,5A 5x20 HT 1A 5x20 3,15 A T 5x20 2 A T 5x20

22kVA - 20% HT 0,5A 5x20 HT 1,25A 5x20 3,15 A T 5x20 2 A T 5x20

22kVA - 24% HT 0,5A 5x20 HT 1,25A 5x20 3,15 A T 5x20 2 A T 5x20

44kVA - 6% HT 0,5A 5x20 HT 1A 5x20 3,15 A T 5x20 2 A T 5x20

44kVA - 8% HT 0,5A 5x20 HT 1A 5x20 3,15 A T 5x20 2 A T 5x20

44kVA - 10% HT 0,5A 5x20 HT 1,25A 5x20 3,15 A T 5x20 2 A T 5x20

44kVA - 16% HT 0,63A 5x20 HT 2A 5x20 3,15 A T 5x20 2 A T 5x20

44kVA - 20% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

44kVA - 24% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

55kVA - 6% HT 0,5A 5x20 HT 1,25A 5x20 3,15 A T 5x20 2 A T 5x20

55kVA - 10% HT 0,63A 5x20 HT 2A 5x20 3,15 A T 5x20 2 A T 5x20

70kVA - 6% HT 0,63A 5x20 HT 2A 5x20 3,15 A T 5x20 2 A T 5x20

87kVA - 7% HT 0,63A 5x20 HT 2A 5x20 3,15 A T 5x20 2 A T 5x20

70kVA - 8% HT 1,25A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

70kVA - 10% HT 2A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

70kVA - 16% HT 0,63A 5x20 HT 2A 5x20 3,15 A T 5x20 2 A T 5x20

70kVA – 20% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

70kVA - 24% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

110kVA - 6% HT 2A 5x20 HT 6,3A 5x20 3,15 A T 5x20 2 A T 5x20

110kVA - 8% HT 3,15A 5x20 HT 6,3A 5x20 3,15 A T 5x20 2 A T 5x20

110kVA - 10% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

110kVA - 16% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

110kVA - 24% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

144kVA - 6% HT 1,25A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

144kVA - 7% HT 1A 5x20 HT 3,15A 5x20 3,15 A T 5x20 2 A T 5x20

144kVA - 8% HT 1,25A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

144kVA - 10% HT 1,25A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

175kVA - 6% HT 2A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

175kVA - 7% HT 1,25A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

175kVA - 8% HT 2A 5x20 HT 5A 5x20 3,15 A T 5x20 2 A T 5x20

175kVA - 10% HT 2A 5x20 HT 6,3A 5x20 3,15 A T 5x20 2 A T 5x20

250kVA - 6% HT 3,15A 5x20 HT 6,3A 5x20 3,15 A T 5x20 2 A T 5x20

Page 72: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Controls and Power stage

Page 72

We take care of it.

System resistor 1

5 x 20mm

resistor 2

5 x 20mm

Control unit

5 x 20mm

Measurement circuit

5 x 20mm

250kVA - 7% HT 3,15A 5x20 HT 6,3A 5x20 3,15 A T 5x20 2 A T 5x20

250kVA - 8% HT 3,15A 5x20 HT 8A 5x20 3,15 A T 5x20 2 A T 5x20

250kVA - 10% HT 5A 5x20 HT 8A 5x20 3,15 A T 5x20 2 A T 5x20

400kVA - 6% HT 5A 5x20 HT 8A 5x20 3,15 A T 5x20 2 A T 5x20

400kVA - 8% HT 5A 5x20 HT 10A 5x20 3,15 A T 5x20 2 A T 5x20

400kVA - 10% HT 6,3A 5x20 HT 10A 5x20 3,15 A T 5x20 2 A T 5x20

630kVA - 6% HT 5A 5x20 HT 10A 5x20 3,15 A T 5x20 2 A T 5x20

630kVA - 8% HT 5A 5x20 HT 10A 5x20 3,15 A T 5x20 2 A T 5x20

630kVA - 10% HT 6,3A 5x20 HT 10A 5x20 3,15 A T 5x20 2 A T 5x20

Table 11-5 Microfuses for Resistors, control unit and measuring circuits

11.8 Lightning protection

The lightning and surge protection is in all systems coordinated according to EN 61643-11 type 1 + type. 2

Figure 11-7 LIghtning protection Type 1 DV M TNC 255 FM (951305)

In case of persistent lightning strikes, the use of lightning protection module turns red. The LVRSys goes to automatic bypass mode and disconnects the electronics from the grid. To remedy the error follow the steps:

Take LVRSys out of operation (See sec. 9.2).

Replace Lightning exchange (DV MOD Art. 255 951 001).

Put LVRSys only after instruction in operation (See sec.9.1).

Page 73: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 73

Controls and Power stage

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

11.9 Transformer protection

Figure 11-8 Transformer protectionDG S 275 FM (952090)

If errors occurs like control error or thyristor error the LVRys goes automatically into the bypass mode. Following steps should be taken:

Take LVRSys out of operation (See sec. 9.2).

Contact A. Eberle Support Team.

Put LVRSys only after instruction in operation (See sec.9.1).

Page 74: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

External devices and modifications

Page 74

We take care of it.

12. External devices and modifications

12.1 External devices

Extenral devices can be installed by A. Eberle GmbH & Co. KG. The wiring diagram will be extended and includes the components.

External devices are eg.:

0 Communication Modems

0 Remote control equipment

12.2 PQI-DA smart

0 When the option Power quality measurement at LVRSys™ input is selected (feature I2), voltage taps and current transformer are installed on the input side of the busbar system.

0 When the option Power quality measurement at LVRSys™ output is selected (feature I1), voltage taps and current transformer are installed on the output side of the busbar system.

DANGER! Danger of electric shock!

Current transformer short circuit.

Open fuse.

The PQI-DA smart are only free of voltage when fuse is open and current transformer are short circuit.

Page 75: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Page 75

Servicing/Cleaning/Spare parts

LEREF "Verzeichnis Ueberschrift" \ MERGEFORMAT Index

Fehler! Verwenden Sie die Registerkarte 'Start', um Verzeichnis Ueberschrift

dem Text zuzuweisen, der hier angezeigt werden soll.Contents

13. Servicing/Cleaning/Spare parts

0 The service interval depends on the operating and environmental conditions.

0 The maintenance interval can be set by customer. A-Eberle advises an interval of 5 years.

14. Standards and Laws

LVD 2014/35/EU

DIN EN 61439-1 Low-voltage switchgear and controlgear assemblies - Part 1: General rules

DIN EN 61439-5 Low-voltage switchgear and controlgear assemblies - Part 5: Assemblies for power distribution in public networks

DIN EN 0298-4 Application of cables and cords in power installations - Part 4: Recommended current-carrying capacity for sheathed and non-sheathed cables for fixed wirings in buildings and for flexible cables and cords

DIN EN 61000-6-1 Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity for residential, commercial and light-industrial environments

DIN EN 61000-6-3 Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission standard for residential, commercial and light-industrial environments

DIN EN 50160 Voltage characteristics of electricity supplied by public distribution networks

DIN EN 82079-1 Preparation of instructions for use - Structuring, content and presentation - Part 1: General principles and detailed requirements

Page 76: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Disassembly and disposal

Page 76

We take care of it.

15. Disassembly and disposal

DANGER! Danger of electric shock!

Make sure the LVRSys™ is de-energized before disassembling it.

Make sure the LVRSys™ is de-energized

Remove low voltage cable.

Remove local cabinet grounding.

The disposal of the LVRSys™ will be carried out by A. Eberle GmbH & Co. KG..

All components are to be sent to:

A. Eberle GmbH & Co. KG

Frankenstraße 160

D-90461 Nuremberg

16. Warranty

A. Eberle GmbH & Co. KG. waranted that this product and accessories will remain free of defects in material and workmanship for a period of three years from the date of purchase.

This warranty does not cover damage caused by:

0 accidents

0 misuse

0 abnormal operating conditions

To make a claim under this warranty, please contact A. Eberle GmbH & Co KG in Nuremberg, Germany.

Page 77: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

Notes

Page 77

Notes

Page 78: LVRSys™ Outdoor - · PDF fileThe User Manual is intended for skilled technicians as well trained and certified operators. ... 0 Current measurement for PQI DA-smart (feature M5)

A. Eberle GmbH & Co. KG

Frankenstraße 160

D-90461 Nuremberg

Tel.: +49 (0) 911/62 81 08-0

Fax: +49 (0) 911/62 81 08 96

Email: [email protected]

http://www.a-eberle.de

Edition of: 15/06/2016

Copyright 2015 A. Eberle GmbH & Co. KG

Subject to change without prior notice.