What is aMotor
ControlCentre?
-
A Motor Control Centre isa grouping of various motor
control & distributiondevices in one commonenclosure, fed from acommon bus system
-
A Motor Control Centreconsists of 4 basic
components:
-Incoming-Enclosure
-Bus System-Units
-
Cutler-Hammer manufactures2 lines of Motor Control
Centres
Freedom Series 2100
Advantage
-
IncomingMain Lugs Only
MCC fed by upstream CB or FusibleSwitch and therefore there is no meansto disconnect power at the MCC.
Screw or Crimp type, up to 1000 MCM6 per phase, Top or bottom entry
Lugs are connected to Vertical Bus,which has the same rating as theHorizontal Bus (up to 1600A)
-
Incoming
Cutler-Hammer SeriesC Circuit Breakers F (150A & 225A) Frame
comes standard with ThermalMagnetic trips only
K (400A) & L (600A) Frameare available with Thermal
Magnetic or optional DigitripRMS 310 Electronic Trip
N (800A & 1200A) & R(1600A, 2000A & 2500A)
Frame are stnd with DigitripRMS 310 Electronic Trip
Main Circuit Breaker
-
Incoming
Main Fusible SwitchCutler-Hammer heavy duty Industrially rated K Switch
Available up to 1200 Amps
Molded Case SwitchUsing Hi-Mag CB (MCS) to provide disconnecting means at
MCC, without short circuit protection
-
Incoming
Bus Link to existingCutler-Hammer MCCs
Bus Duct EntryManufactured to suit
customers bus duct, basedupon customer supplied bus
duct flange drawing
Bus links & Transition cells toconnect to Cutler-Hammer,
Westinghouse, Commander &Sylvania MCCs manufactured since
1950
Transition Sections10 wide cells provide
transition to Switchgear &Transformers
-
EnclosureIndoor
-EEMAC 1-EEMAC 1A (gasketed)EEMAC 2 (driphood)
EEMAC 12 (dust tight)
Outdoor-EEMAC 3R (rain, sleet proof)
walk in or non-walk in
-
Enclosure
Standard Section height is90, not including 1 high
channel sill
Standard Section width is 20
-
Wider Sections are available for largerstarters, Transfer Switches, PLCs, etc.
20 24 28 32 44
-
Enclosure
Side View
16 deepSection
V
e
r
t
i
c
a
l
B
u
s
L
o
c
a
t
i
o
n
Units mounton Front Side
only
16 21
Side View
21 deepSection
Units mounton Front Side
Units mounton rear on
Back to BackMCCs
V
e
r
t
i
c
a
l
B
u
s
L
o
c
a
t
i
o
n
-
Cutler-Hammers standard back toback arrangement is a total of 21
deep and employs a commonHorizontal & Vertical Bus for front
& rear units.
As an alternate, we can supply 16or 21 deep (front mounted sections)mounted back to back, to form a 32
or 42 deep back to back design,with 2 sets of busses. Horizontalbusses would be cross connected
with custom buswork
Enclosure
-
Enclosure9 high top and bottom wireways on Front
mounted sections
4 5/8 vertical wireway(larger wireways available on sections over
20 wide)
15 top & 3 bottom wireway standard onrear sections and optional on front
72 of unit mounting space available onFront and Rear of all sections
Reduced height sectionsavailable in increments of 6
-
Enclosure-ASA 61 exterior finish (ASA 49 and other special colours available as an option)-White interior panels-12 gauge steel sub frame-14 gauge steel doors & covers-lifting eyes
Optional features:-Channel sills (adds 1 to overall height)-Bottom plates (stnd on EEMAC 12)-Driphood-Space heater & thermostat-Non conductive handrails-Canopy lights-Corner sections+
Handrail
Driphood
-
MCC Bus System
Horizontal Bus
Vertical Bus
Horizontal Ground Bus
Option Vertical Ground
Neutral Bus
Horizontal Ground Bus can be mounted at bottomif no Neutral bus is being used
-
Horizontal BusCopper or AluminumTin or Silver plated
-600 Amp-800 Amp
-1200 Amp-1600 Amp-2000 Amp-2500 Amp-3200 Amp
CSA rated for 65 degree C rise
-
Vertical BusCopper or AluminumTin or Silver plated
-400 Amp (standard on Frontmounted sections
-600 Amp (standard on Back toBack Sections, optional on front)
-800 Amp-1200 Amp-1600 Amp
In the incoming section, the Vertical bus hasthe same rating as the Horizontal bus (up to
1600A)
-
Ground BusHorizontal Ground Bus (stnd locationat top of section, also may be mounted
at bottom of section)
Standard horizontal ground is 300Amp (1/4 x 1). Optional 600 Amp
(1/4 x 2) is available
Optional Vertical Ground Bus (1/4 x 1)mounted in the vertical wireway
Neutral Bus On 4 wire systems, mounted atbottom of section, available at 300A,600A and 800A
-
Bus Bracing
Bus braces mechanically holdthe bus in place and prevent bus
deflection caused by a shortcircuit
Standard Horizontal and VerticalBus bracings are 42,000 Amps
65,000 & 100,000 Amp bracingare available as options
-
Bus IsolationAll MCC power busses are
isolated to prevent accidentalcontact
Horizontal bus is mountedbehind steel barriers the top
wireway
Vertical bus comes with glasspolyester barriers with
removeable stab hole covers
Glass Polyestor Barrierswith stab covers
-
Bus Insulation
Horizontal bus is available withoptional Insulating boots, up to
2500 amp
An optional Labyrinth Insulatingbarrier is available on the
Vertical bus. Optional automaticshutters are available.
Bus boots on the Horizontal bus
Labyrinth barriers on Vertical bus
-
MCC Bus SystemHorizontal Bus600 Amp to 3200 Amp
Vertical Bus400 Amp to 1600 Amp
Horizontal Ground Bus300 Amp (1/4 x 1)or 600 Amp (1/4 x 2)
Option Vertical Ground300 Amp (1/4 x 1)
Neutral Bus300 Amp, 600 Ampor 800 Amp
Horizontal Ground Bus can be mounted at bottomif no Neutral bus is being used
-
Incoming Cables
Main CircuitBreaker Open
MCC bus notEnergized
-
Main CircuitBreaker Closed
MCC busEnergized
Incoming Cables
-
PLU
G O
NTO
MC
CV
ERTI
CA
L B
US
TO M
OTO
R
M
R
OL
TO M
OTO
R
STA
RTE
R
STOPSTART
M
M
Main CB ClosedMCC Bus Energized
Starter CB Open
-
Main CB ClosedMCC Bus Energized
Starter CB Closed
PLU
G O
NTO
MC
CV
ERTI
CA
L B
US
TO M
OTO
R
M
R
OL
TO M
OTO
R
STA
RTE
R
STOPSTART
M
M
Main CB ClosedMCC Bus Energized
Starter CB ClosedStarter coil not energized
-
PLU
G O
NTO
MC
CV
ERTI
CA
L B
US
TO M
OTO
R
M
OL
TO M
OTO
R
STA
RTE
R
STOP START
M
M
Main CB ClosedMCC Bus Energized
Starter CB ClosedMomentary Start PB depressed
Starter Coil energizedMotor Starts
-
PLU
G O
NTO
MC
CV
ERTI
CA
L B
US
TO M
OTO
R
M
OL
TO M
OTO
R
STA
RTE
R
STOPSTART
M
M
Main CB ClosedMCC Bus Energized
Starter CB ClosedSeal in Contact closes
Momentary Start PB releasedStarter Coil energized
Motor Runs
-
PLU
G O
NTO
MC
CV
ERTI
CA
L B
US
TO M
OTO
R
M
OL
TO M
OTO
R
STA
RTE
R
STOP
START
M
M
Main CB ClosedMCC Bus Energized
Starter CB ClosedStop Pushbutton depressedStarter Coil De-energiaed
Motor Stops
-
UnitsCommon MCC Units
-Combination Motor Starters-Fusible & CB type Feeders
-Panelboards-Distribution Transformers
-PLCs-Metering
-Hydro Metering Compartment-Transfer Switches
-Clipper TVSS units
-
Motor Starters
Motor Starter units are CombinationStarters, consisting of a Starter and a
disconnect device, either a CircuitBreaker (HMCP or Thermal Mag)
or Fusible Switch
-
Freedom Starters
Size 1 to 6 EEMAC rated,or optional IEC starters,c/w adjustable bimetallic
overload relay
Compact 6 size 1 (IEC size F) and18 Size 3 & 4 (CB type) are available
-
Advantage Starters
Size 1 to 6 EEMAC Starter c/wElectronic Overload Relay
Various control, metering & groundfault modules are available as well as
PONI communications modules
Compact 6 size 1-2 and 18 Size 3-4(CB type) are available
-
6 Compact Starters
-Provides space savings, 12 unitsin a Front mounted Section & 23
in a Back to Back-Available with Freedom NEMA,
Freedom IEC or Advantage-HMCP or Fusible Switch
-Up to 25 HP in someconfigurations
-
Optional Units
Developed based on feedbackfrom various MCC users
-Slider operator mounted on RHside (mandatory in many
industries for safety)-Rugged Industrially rated KSwitch with visible contact
blades-Full accessibility to Power
Fuses
-
SV9000 Drives
Currently available in MCCs upto 250 HP at 690Volts, withlarger sizes in development.
Simple programming with astandard or graphic keypad or
through a PC50 HP VFDs
mounted two high inan MCC
-
IT Solid State Starter
Intelligent Technology (IT), theindustries most compact MCC
Solid State Starter design,requiring 30-63% less space
Up to 900 HP at 690V
Compact, easy to program andadvanced functionality
125 HP IT Starter in18 high MCC unit
-
Vacuum Contactors
Available in 135, 270 & 540Amp ratings.
Used in conjunction with C306Freedom Overload in MCCs
Provides long service life andlow maintenance requirements
-
FeedersThermal Magnetic CB type Feeders from
HFD to RD Frame
Available in 6 compact and Dualconfigurations (maximum 150A)
Fusible Feeders using K-Switch, up to 1200Amps
Available in 6 compact (up to 60A) andDual (up to 100A) configurations
Dual MountedCB typeFeeder
-
PanelboardsPow-R-Line panelboards,
up to 42 Circuitsthru 600 Volts
Distribution TransformersSingle Phase up to 50 KVAThree Phase up to 45 KVA
-
TVSS
Clipper TransientVoltage SurgeSuppression
(TVSS)
Surge ratings100kA to 500kA
-
PLCs
Wide rangingexperience in
mounting & wiringCutler Hammer PLCs
as well as allcompetitive PLCs
-
OEM
Basic Class 1 Type ASections & Units supplied to
OEMs c/w-Blank panel (with or without Circuit
Breaker & operating mechanism-Devices (PLC, VFDs, etc) mounted
& wired by the OEM-Special heights available
-
Digital Metering
Cutler Hammer PowerManagement Products
-IQ Analyser-IQ DP-4000-IQ Generator
-IQ Data-IQ 200
IQ DP-4130Digital Meter
-
Metering
Standard AnalogueMeters
Service EntranceSections c/w Utility
MeteringCompartments
-
Transfer Switch
Designed to control Emergency &Standby Power Systems
Available as type A (not intended toprovide short circuit & overloadprotection) or type B (c/w shortcircuit & overload protection)
Available up to 1200 Amp in MCCs
-
MCC unit features
OperatingMechanism
DevicePanel
Bus Stabs
GroundingClip
TerminalBlock
CircuitBreaker
Contactor&
Overload
PivotTube
UnitLatch
-
Operating MechanismGrey Toggle Slider
MCC unit features
-Indicates position of the Disconnect
Interlocked with door so that:-When ON door cannot open and
unit cannot be withdrawn-When door is open, operator is held
in OFF-Unit cannot be withdrawn unless in
OFF position-A Defeater mechanism is provided
for Authorized personnel
-Padlockable in OFF position
-
Unit ground clipGrounds unit to structure
prior to engaging theMCC bus
MCC unit featuresBus Stabs
-Plugs units onto theVertical bus up to 400A-Fully shrouded, floating
stab fingers-Tin plated (silver
optional) copper/steelalloy stab
-
MCC unit features
Unit Device PanelMounted on MCC unit
Hinges down for unit access
Holds up to six devices:-30mm Pilot Devices
(Lights, PBs Selector Switches)-Mini Meters
(Ammeter, Voltmeters, ETM)
-
MCC unit features
Unit Latch locks unit in position
Latches & locks in 3 positions:-Fully engaged
-Test or detent position-Withdrawn
Door Latch
Heavy duty 1/4 turn latchprovides positive door closureand latch position indication
-
Unit Wiring# 16 TEW control wire as standard
# 14 and other wire types also available
Sleeve type or Heatshrink wiretags
7 Point non pull-apart Terminal Block is standard(mounted on RH unit side)
7 Point pull-apart TB also available(mounted on RH unit side)
Other TBs are also available(mounted on elevated channel)
-
Unit WiringType A - No terminal blocks
Type B - Control TBs in Starter unitsType C - Control TBs in Starter units which are wired
to master control TBs at the top or bottom of eachMCC Section
Class I - No interwiring between unitsClass II - complete control system including controldrawings showing remote devices and/or interwiring
between units.
-
Unit WiringST
AR
TER
Class IType A
Fieldwiringdirectly
ontoStarter
STA
RTE
R
Class IType B
Fieldwiringonto
controlTBs,which
arefactorywired to
theStarter
STA
RTE
R
Class IType C
Fieldwiringonto
masterTBs (attop or
bottom)which
arewired toTBs inStarterUnit
-
Unit Wiring
STA
RTE
RST
AR
TER
Class II factorywiring
between two ormore units in
the MCC
-
Unit Wiring
11A
AUTO
HAND
OFF2
3M
TRFUX1
H1
120VX2
600V
OL
X2
STOPREMOTE
PLC
FIREALARM
Class I I wiring diagramshowing remote devices
-
DeviceNet MCC
DeviceNet is an open communicationnetwork that connects intelligent control
devices
DeviceNet is built around a published, openstandard
Specification controlled by ODVA
-
DeviceNet MCC
DeviceNet MCCs
-Reduces total installedcosts
-Provides advanceddiagnostics
-Reduces or eliminatesdowntime
-
DeviceNet MCC
Shipping split on DeviceNet MCC
Shipping split on standard MCC withinterwiring to a PLC
-
PANELMATE
WPONIDNA
WPONIDNAWPONIDNA WPONIDNA
WPONIDNA
WPONIDNA
24VDC POWERSUPPLY
MAINCB FEEDER
FVRSize 1
ITSolidState
FVNRSize 4
FVNRSize 2
FVNRSize 1
SV9000VFD
DeviceNet MCCConceptual View
Terminating Resistor
Trunk Cable (thick)
Tee Connector
Crop Cable (thin)