Luminaire lightdistribution basics
Presented by Morgan Catha,Grandlite Product Development Engineer
September 26, 2014
![Page 2: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/2.jpg)
Photometry concepts
Lumen: A quantity of emitted light energy in the visible spectrum (“luminous flux”). Defined in terms of the sensitivity of the human eye to light. One lumen is 1/683 watts or more of visible light energy, depending on the spectrum of the light source.
![Page 3: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/3.jpg)
Candela: A measure of “luminous intensity”, defined as lumens per solid angle (measured in steradians). Expresses how much light is being emitted in a particular direction.
Photometry concepts
![Page 4: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/4.jpg)
Footcandle: A measure of “illuminance”, the amount of visible light energy falling on a surface. Defined as one lumen per square foot. Another common unit is “lux”, equal to one lumen per square meter.
Photometry concepts
![Page 5: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/5.jpg)
Luminance: An expression of the intensity of light leaving a surface in a particular direction. Measured in candelas per square meter.
Photometry concepts
![Page 6: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/6.jpg)
“Brightness”
![Page 7: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/7.jpg)
“Brightness”
‘"Brightness" should be used only for nonquantitative references to physiological sensations and perceptions of light.’
-- Federal Standard 1037C, the Federal Glossary of Telecommunication
Terms (1996)
![Page 8: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/8.jpg)
Photometric Testing
Rotating mirror Goniophotometer -- measures light output
![Page 9: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/9.jpg)
Grandlite goniophotometry
laboratory
Photometric Testing
![Page 10: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/10.jpg)
A type C rotating mirror goniophotometer is used to record candela values for each angle
Photometric Testing
![Page 11: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/11.jpg)
The candela values are stored in a .ies file
Photometric Testing
![Page 12: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/12.jpg)
Photometric Reports
Polar candela plot • Shows cross-sections of light intensity
• Useful for seeing the overall shape of a luminaire’s light distribution
![Page 13: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/13.jpg)
Photometric Reports
Isoilluminance plot • Shows lines of equal illuminance on target surface
• Useful for seeing how a luminaire illuminates the area around it
![Page 14: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/14.jpg)
Photometric Reports
Luminaire Classification System Graph • Shows backlight, uplight and glare by sector
• Useful for seeing how the BUG rating is determined
![Page 15: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/15.jpg)
B.U.G. Rating
![Page 16: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/16.jpg)
B.U.G. Rating
![Page 17: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/17.jpg)
B.U.G. Rating
![Page 18: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/18.jpg)
B.U.G. Rating
![Page 19: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/19.jpg)
B.U.G. Rating
![Page 20: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/20.jpg)
IES Cutoff Classifications
![Page 21: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/21.jpg)
IES Cutoff Classifications
![Page 22: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/22.jpg)
IES Cutoff Classifications
![Page 23: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/23.jpg)
IES Cutoff Classifications
![Page 24: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/24.jpg)
IES Roadway Types
![Page 25: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/25.jpg)
IES Roadway Types• Type I - Half-maximum candela trace falls between 1 MH LRL on the House side and 1 MH LRL on the Street side • Type II - Half-maximum candela trace on the Street side is beyond the 1 MH LRL but not beyond the 1.75 MH LRL • Type III - Half-maximum candela trace on the Street side is beyond the 1.75 MH LRL but not beyond the 2.75 MH LRL • Type IV - Half-maximum candela trace on the Street side is beyond the 2.75 MH LRL • Type V - Has circular symmetry being essentially the same at all lateral angles around the luminaire • Type VS - Zonal lumens (below 90-degress vertical) for each of the eight horizontal octants (0-45, 45-90, 90-135, 135,180, 180-225, 225-270, 270-315, 315-360) are within +-10% of the average zonal lumens of all octants
![Page 26: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/26.jpg)
IES Roadway Types• Very Short (VS): The maximum intensity points to a point in the VS zone of the grid, 0-1.0 MH TRL
• Short (S): The maximum intensity points to a point in the S zone of the grid, 1.0 - 2.25 MH TRL
• Medium (M): The maximum intensity points to a point in the M zone of the grid, 2.25 - 3.75 MH TRL
• Long (L): The maximum intensity points to a point in the L zone of the grid, 3.75 - 6.0 MH TRL
• Very Long (VL): The maximum intensity points to a point in the VL zone of the grid, > 6.0 MH TRL
![Page 27: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/27.jpg)
IES Roadway Types
![Page 28: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/28.jpg)
IES Roadway Types• Maximum candela point furthest lateral point between 2.25 and 3.75 mounting heights = Medium
• Half maximum candela trace furthest longitudinal point between 1.75 and 2.75 mounting heights = Type 3
![Page 29: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/29.jpg)
IES Flood Types
![Page 30: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/30.jpg)
IES Flood Types
BeamField
10% of maximum candela
50% of maximum candela
Maximum candela
![Page 31: Luminaire Light Distribution Classifications](https://reader036.fdocuments.us/reader036/viewer/2022062300/55924de01a28abc7658b462f/html5/thumbnails/31.jpg)
IES Flood Types
Example: NEMA 7x7 means the field angle is 130 degrees or wider in both the horizontal and vertical planes. For short, “NEMA 7”.