LT-6098 FR-320NetK Rev. 0 June 2015 Page 1
FR-320K
Addendum for FR-320K Installation
LT-6098 FR-320NetK InstallationAttention: This specific application requires a setup not listed in either the LT-951 FR-320 Series or the LT-
894 FleX-Net™ Installation and Operation Manuals. This document takes precedence over bothLT-951 and LT-894 wherever there is a conflict.
Introduction
This addendum describes how to implement a FR-320 Releasing panel into a FleX-Net™ system panel.The FR-320K adds releasing capability to the FleX-Net™ system without the need for a separate external cabinet.
About the FR-320NetK Intelligent Network Fire Alarm and Release Control System
The FR-320K panel adds releasing capability to Mircom's FleX-Net™ MNS. Based upon Mircom's already UL listed FR-320 Releasing panel and FleX-Net™ systems, this system permits pre-release, abort, manual release, and reset control.
The FR-320K's chassis permits easy mounting to the Mircom's BBX-FXMNS cabinet. The FR-320K includes all necessary items to connect the FR-320 releasing panel to the Mircom's FleX-Net™ system.
The FleX-Net™ and FR-320K panels have independent power arrangements. Each panel has its own AC supply and battery setup. The connection between the FR-320K and the FleX-Net™ panels is by isolated relays.
The FR-320K uses the FR-320 pre-programmed mode #2 to enable activation features via the FleX-Net™ initiating device circuits. In this configuration, the Mass Notification System (MNS) capability is not present at this panel node.
Note: The releasing devices used must be wired locally to this panel.
Overall Features:
• Provides additional releasing capability to FleX-Net™ MNS system
• Built-in Addressable loop which supports Classic Loop Interface Protocol (CLIPS) and Advanced Protocol (AP) addressable devices
• Tamper resistant enclosures with password protected features for enhanced access control
• Local and remote placement of controls and indicators
• Visible notification and strobes support
• Large LCD displays
• Fire Alarm Control Panel Interface (FACI)
• Building Management System Interface (BMSI)
• Fire Alarm Control:
•Base system is equipped with one Intelligent Signaling Line Circuit (SLC). Expandable up to 21 SLCs
Page 2 LT-6098 FR-320NetK Rev. 0 June 2015
•Each SLC is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Style 6 or 7 Class A) or Style 4 (Class B)•Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each•Built-in Ethernet port•Remote diagnostics via a built-in web server
• Network Features:
•Up to 63 nodes•Fully integrated digital network audio and control over a single pair of copper wire or fibre optic cable•Supports over 5,000 points per node•Supports over 250,000 points on a single network•Peer-to-peer network communications
• Releasing Features:
• Each initiating circuit is pre-configured as: Alarm, Supervisory (Latching or non-latching), Water-Flow, Manual Release Switch, Abort Switch, or Manual Release/Abort combination, depending upon the selected pre-programmed configuration. There are two LEDs per circuit, one for Trouble (amber), and one dual color (amber/red) LED for Supervisory (amber) and Alarm (red)•Basic unit has 4 power limited class B (style Y) output circuits. Output circuits 1 & 2 are indicating circuits while output circuits 3 & 4 are releasing circuits (circuit 4 can work as an indicating circuit in some situations.) Each indicating circuit process type is pre-configured and can be silenceable•The signal rates depend on the selected pre-programmed configuration.•A pushbutton associated with each initiating, indicating, and releasing circuit can individually bypass the circuit•Configurable Signal Silence Inhibit and Auto Signal Silence Timers•Subsequent Alarm, Supervisory, and Trouble operation•Relay Contacts for Common Alarm, Common Supervisory, Common Trouble, and Auxiliary Alarm Relay (disconnectable)•RS-485 Interface for RA-1000 Series Remote Multiplex Annunciators and Smart relay Module•Optional Modules for additional Relay Circuits, City Tie and Polarity Reversal Signaling.•Extensive transient protection•Easy configuration of the panel using LCD service tool (CFG-300)•Releasing circuit protection from false alarm by disconnecting the battery if the voltage falls below 19V
LT-6098 FR-320NetK Rev. 0 June 2015 Page 3
FR-320NetK includes:
BBX-FXMNS FleX-Net™ Backbox
FR-320K FR-320 Main Board and Agent Releasing Kit for FleX-Net™
FX-2000MNS FleX-Net™ Main Board and Chassis
RM-1008A Relay Adder Module
RM-306 Relay Adder Module
DM-1008A Detection Adder Module
SGM-1004A Four Indicating Circuit Module
DSPL-420 Main Display for FX-2000MNS
RAX-1048TZDS Zone Display for FX-2000MNS
MGD-32 Master Graphic Annunciator
RAM-1016TZDS Main Remote LED Annunciator
CH-1181 TR-063 Transformer support for FXMNS box
CH-1183 FR-320 Main PCB Support Plate for FXMNS backbox
CH-1184 RAM-1016TZDS Adaptor Plate
TR-061 FR-320 Transformer
TR-063 FX-2000MNS Transformer
Page 4 LT-6098 FR-320NetK Rev. 0 June 2015
Physical Installation
Tools needed:
• Hexnut driver
• Phillips screwdriver
Chassis Mounting
Using the CH-1183 support plate, anchor the FR-320K to the FXMNS back box in the area above the FX-2000MNS board. Otherwise, physical installation is as listed in each component’s manual.
Figure 1 Chassis Mounting
Board Mounting
Mount all other boards in as illustrated. Otherwise, physical installation is as listed in each component’s Installation and Operation manuals:
• LT-894 FleX-Net™
• LT-951 FR-320
• LT-847 MGD-32
FR-320Board
FR-320Batteries
FR-320Transformer
FX-2000NBatteries
FX-2000NAC transformer
FX-2000NBoard
BBX-FXMNSBackbox
CH-1181 Support Plate
FR-320K
CH-1183 Support Plate
RM-306Board
DM-1008ABoard
RM-1008ABoard SGM-1004A
Board
LT-6098 FR-320NetK Rev. 0 June 2015 Page 5
Figure 2 Board Mounting Positions in the BBX-FXMNS Backbox
Interior of Inner Door Interior of Backbox
FR-320K
RM-306
FX-2000MNS
DM-1008A RM-1008A
SGM-1004A
RAM-1016TZDS
MGD-32
RAX-1048TZDS
DSPL-420
Page 6 LT-6098 FR-320NetK Rev. 0 June 2015
Electrical Power Consumption
The FR-320K has its own AC transformer and battery hookups, independent from the other FleX-Net™ components.
Table 1 FR-320K Specifications
FR-320K Fire Control Panel Chassis
General Digital Signal Processor (DSP) based design. Fully configurable using frontpanel LCD display with Password Access.
Indicating (NAC) Circuits
2 supervised style Y (Class B) indicating circuits, configured as strobes oraudibles. Terminals are labeled SIG 1 and SIG 2.
Power limited / Regulated 24VDC FWR / 1.7A @ 49C per circuit
Initiating Circuits 6 supervised style B (Class B) initiating circuits, configurable. Terminals arelabeled DET. Compatibility ID A.
Power limited / 19VDC reg. / 3mA for detectors /110MVpp AC ripple / 45mA max(alarm short)
Releasing Circuit Terminals are labeled SIG 3 and SIG 4
21.1 VDC@ 1 A max per circuit, 1.7A max combined
Current Consumption Standby: 183mA
Alarm: 318mA
Supervised Auxiliary Power (non resettable)
Power limited / 21.1VDC regulated / 300mA max
RS-485 Connection For Remote Annunciators. Terminals are labeled RS485. Line impedance is 120ohms.
Electrical ratings AC line voltage 120 VAC 60Hz 1.2A / 240 VAC 50 Hz 0.6 A, 10Aslow blow fuse on secondary of transformer
Power Supply Rating 6.5A AC maximum @ secondary of transformer
Max power allowed • 4A
• 1.7A (aux power unfiltered if used)
• 0.5A (aux power filtered if used)
• 0.3A (resettable auxiliary power if used)
• 1.7A (for releasing circuits)
If no auxiliaries are used the max power is 4A for the indicating and the releasingcircuits
Auxiliary relays (resistive loads)
Must be connected to a listed power limited source of supply. Terminals are labelled ALARM, TROUBLE, SUPV and AUX.
Common Alarm Form C, 1 A max, 28 VDC
Common Supv Form C, 1 A max, 28 VDC
Common Trouble Form C, 1 A max, 28 VDC
Aux Relay Form C, 1 A max, 28 VDC
LT-6098 FR-320NetK Rev. 0 June 2015 Page 7
See the LT-951 FR-320 Installation Manual for more information.
Field Wiring
Adding the FR-320K to the FleX-Net™ system is straight forward as both boards are located in the same backbox. This reduces the need for extra conduit and running long cables.
1. For general wiring options (i.e. ribbon cables), refer to these installation and operation manuals:
• LT-894 FleX-Net™
• LT-951 FR-320
• LT-847 MGD-32
• LT-617 RAM-1016TZDS
2.Use the following diagrams to wire up the FR-320K:
Unfiltered supply (full wave rectified)
Power limited / Unregulated / Special Application
1.7A Max, 21.3 VDC to 42.00 VDC
Minimum Load 5mA
Battery Type 24VDC Gel Cell/Sealed lead acid – 10AH to 26AH
Charging capability 10AH~26AH
Current Consumption standby: 200 mA
alarm: 350 mA
Protection 10A on board (F1) slow blow micro fuse
Compliance Type of Service A, M, WF, SS
Type of Signaling Non-Coded
Applicable Standards NFPA 12, 12A, 12B, 12, 15, 16,70,72,2001, UL-864Rev. 9
Table 1 FR-320K Specifications (Continued)
FR-320K Fire Control Panel Chassis
Page 8 LT-6098 FR-320NetK Rev. 0 June 2015
2.1 Wiring for FR-320K panel
Figure 3 FR-320K Panel
S-+ NCNO C NCNO C NCNO C NCNO C
JW2
JW1
-+ -+ -+ -+ -+ -+
DET 1 DET 2 DET 3 DET 4 DET 5 DET 6
-+ -+ -+ -+ -+ -+
SIG 1 SIG 2 SIG 3 SIG 4 AUX 4-WIRE SPLY
COM
-CO
M+
TRB
TRL
UN
FLTD
SPL
Y
RTI P
ORT
JW5
JW6
JW4
TO P
R-30
0 M
OD
ULE
TO
RM-3
06 R
ELA
Y M
ODUL
E
RS-485 AUX. RELAY ALARM RELAY SUPERVISORY RELAY
TROUBLE RELAY
POW
ERSI
GN
AL
JW7
For f
ront
pan
el p
rogr
amm
ing
use
CFG
-300
confi
gura
tion
tool
not
UL
-864
or U
LC-S
527
lis
ted
. Ple
ase
refe
r to
Doc
umen
t LT-
922
for d
etai
ls.
Initiating zones 1 to 6 Indicating/Releasing zones 1 to 4
P3P4
SYST
EMRE
SET
AC O
NX M ?
GRO
UN
D F
AULT
CPU
FA
IL
ABO
RT
RELE
ASE
COM
MO
N AL
ARM
COM
MO
N S
UPV
REM
OTE
TRO
UBLE
COM
MO
N TR
OUB
LE
BATT
ERY T
ROUB
LE
SIG
NA
LSI
LEN
CE
AUXI
LIA
RYD
ISCO
NN
ECT
LAM
PTE
ST
BUZZ
ER
SILE
NCE
RAC2
(ZO
NE
4)
RAC1
(ZO
NE
3)
NAC
2(Z
ON
E 2)
NAC
1(Z
ON
E 1)
IAC6
(ZO
NE
1)
IAC5
(ZO
NE
5)
IAC4
(ZO
NE
4)
IAC3
(ZO
NE
3)
IAC2
(ZO
NE
2)
IAC1
(ZO
NE
1)
PRE
RELE
ASE
JW5
JW4
Sole
noid
EO
L m
odul
eM
P-32
0R/W
From
RM
-100
8A,
Rela
y 2
and
6
Sole
noid
EO
L m
odul
eM
P-32
0R/W
WAR
NIN
G: E
OL
has t
o be
clo
se n
ippl
e
con
nect
ed to
the
sole
noid
coi
l.
Sole
noid
Coi
l
Sole
noid
Coi
l
From
RM
-100
8A, R
elay
3 a
nd 7
From
RM
-100
8A, R
elay
4 a
nd 8
To
DM
-100
8A IN
8
To
MG
D-3
2RS
-485
Inpu
t
To M
GD
-32
24VD
C IN
PUT
To
DM
-100
8A IN
4
+ - + -
+ -
Rly
2 N
O
Rly
6 C Rly
3 N
ORl
y 7
CRl
y 4
NO
Rly
8 C
STYL
E Y
WIR
ING
STYL
E Y
WIR
ING
IND
ICAT
ING
CIRC
UIT
-1
IND
ICAT
ING
CIRC
UIT
-2
Lege
nd:
BELL
STRO
BE
HO
RN3.
9K 1
/2 W
ATT
ELR
LT-6098 FR-320NetK Rev. 0 June 2015 Page 9
2.2 Wiring for FX-2000MNS
Figure 4 FX-2000MNS Panel
F1
JW6
MAI
N FI
RE A
LARM
BO
ARD
FIEL
D W
IRIN
G T
ERM
INAL
S
P3
P18
P2P1
P16
P15
P10
P11
P4
J1
P9
P7
P5 P6
P8
+ BR
-
+BA
T -
P14
P19
JW1
JW4
JW5
JW2
SW2
18
ON
To A
ddre
ssab
le se
nsor
s an
d m
odul
esre
fer t
o Fl
eX-N
etLT
-894
Man
ual
NAC
0IN
DICA
TIO
N
NAC
1
NAC
2
NAC
3
(PO
WER
-LIM
ITED
)CI
RCUI
T 1
(PO
WER
-LIM
ITED
)
(PO
WER
-LIM
ITED
)
(PO
WER
-LIM
ITED
)
(PO
WER
-LIM
ITED
)
INDI
CATI
ON
CIRC
UIT
2
4-W
IRE
+PO
WER
SUPP
LY- +
AUX.
PO
WER
-
TRB
RTI
INTE
RFAC
ETR
L
2 POOL
B A
+ - + - + -+ - + + - -
INDI
CATI
ON
CIRC
UIT
1
INDI
CATI
ON
CIRC
UIT
2
+ -+ - + + - -
COM
-
NO
NC
COM
NO
NC
COM
NO
NC
+
S
SP4
P3
RS4
85TR
OU
BLE
ALAR
MSU
PV.
CO
MM
ON
TR
OU
BLE
CO
NTA
CTS
24 V
DC
, 1 A
MP
RES
ISTI
VE L
OAD
AUXI
LIAR
Y C
OM
MO
NSU
PERV
ISO
RYC
ON
TAC
TS24
VD
C, 1
AM
PR
ESIS
TIVE
LO
AD
AUXI
LIAR
Y C
OM
MO
NAL
ARM
CO
NTA
CTS
24 V
DC
, 1 A
MP
RES
ISTI
VE L
OAD
SIG
GN
Dor
CO
M(-)
MUS
T BE
CO
NN
ECTE
D TO
A L
ISTE
D P
OW
ER L
IMIT
ED S
UPPL
Y SO
URCE
E+TS
2
I+ _NA
C Ex
tern
al
Pow
er C
onne
ctio
n
Page 10 LT-6098 FR-320NetK Rev. 0 June 2015
2.3 Wiring for MGD-32
Figure 5 MGD-32 Annunciator Chassis
From RM-1008A Module
Rly 1 NO
Rly 5 C
+
-
S
S
-
+
-+
-+
Note: All circuits are power limited andmust use type FPL, FPLR, or FPLP powerlimited cable.
RS-485 and 24V DC Power Wiring
24 VDC power from FR-320 panel (Twisted Pair)
24 VDC Power to RAM-1016TZDS Module (Twisted Pair)
RS-485 to RAM-1016TZDS Module(Twisted Pair)
RS-485 from FR-320 panel (Twisted Pair)
LT-6098 FR-320NetK Rev. 0 June 2015 Page 11
2.4 Wiring for RAM-1016TZDS
Figure 6 RAM-1016TZDS Main Remote LED Annunciator
+
24 VDCINPUT
-
S
S
-
+
-+
-+
P11
RS-485INPUT
RS-485OUTPUT
24 VDCOUTPUT
24 VDC OUTPUT POWER FROM MGD-32 Module
RS-485 OUTPUT FROM MGD-32 Module
+
-
+
-
Page 12 LT-6098 FR-320NetK Rev. 0 June 2015
2.5 Wiring for RM-1008A
Figure 7 RM-1008A 8 Relay Adder Module
AUX RELAY 1~8CONTACTS28 VDC, 1 AMPRESISTIVE LOAD
AU
X R
ELAY
5C
ON
TAC
TS28
VD
C, 1
AM
PRE
SIST
IVE
LOA
D
AU
X R
ELAY
6C
ON
TAC
TS28
VD
C, 1
AM
PRE
SIST
IVE
LOA
D
AU
X R
ELAY
7C
ON
TAC
TS28
VD
C, 1
AM
PRE
SIST
IVE
LOA
D
AU
X R
ELAY
8C
ON
TAC
TS28
VD
C, 1
AM
PRE
SIST
IVE
LOA
D
RLY
1RL
Y 5
RLY
6
RLY
7
RLY
8
RLY
2
RLY
3
RLY
4
CO
M
CO
M
CO
M
NC
CO
M
NC
NC
NC
NO
NC
CO
M
NO
NC
CO
M
NO
CO
M
NC
NO
CO
M
NC
NO
NO
NO
NO
To DET1 on FR-320 panel
To DET5 on FR-320 panel
To DET6 on FR-320 panel
Det 1-Det 1+
Det 5+Det 5-
Det 6+Det 6 -
Relay 1 NO
Relay 5 C
Relay 6 C
Relay 2 NO
Relay 3 NO
Relay 7 C
Relay 8 C
Relay 4 NO
Relay 7 NC
Relay 8 NC
Relay 5 NC
To System Rese t on MGD-32 module
System Reset
COM
LT-6098 FR-320NetK Rev. 0 June 2015 Page 13
2.6 Wiring for RM-306
Figure 8 RM-306 Six Relay Adder Module
P1
To DM-1008A Relay INI7
INI7-INI7+
Page 14 LT-6098 FR-320NetK Rev. 0 June 2015
2.7 Wiring for DM-1008A
Figure 9 DM-1008A Module
INI 1
+
INI 1
-
INI 2
+
INI 2
-
INI 3
+
INI 3
-
INI 4
+
INI 4
-
INI 2
STYL
E B/
D
INI 1
STYL
E B/
D
STYL
E B
(CLA
SS B
)W
IRIN
G
SUPE
RVIS
ED IN
ITIA
TIN
G C
IRCU
IT #
1(A
LARM
ZO
NE)
(PO
WER
LIM
ITED
)
INI 5
+
INI 5
-
INI 6
+
INI 6
-
INI 7
+
INI 7
-
INI 8
+
INI 8
-
INI 4
STYL
E B/
D
INI 3
STYL
E B/
D From
FR-
320
Trou
ble
Rela
y
Not
e: In
itiat
ing
circ
uits
of t
he D
M-1
008A
sho
uld
be S
tyle
B (C
lass
B) b
y de
faul
t . If
Sty
le D
(Cla
ss A
) use
d, th
e Fl
eX-N
et C
onfig
urat
or m
ust b
e se
t to
NO
T us
e Cr
oss-
zone
Det
ectio
n Zo
nes.
3.9K
1/2
WAT
T EL
R
OR
ELRX
-300
/R
3.9K
1/2
WAT
T EL
R
OR
ELRX
-300
/R
STYL
E B
(CLA
SS B
)W
IRIN
G
SUPE
RVIS
ED IN
ITIA
TIN
G C
IRCU
IT #
2(A
LARM
ZO
NE)
(PO
WER
LIM
ITED
)
HEA
T D
ETEC
TOR
Lege
nd:
SMO
KE D
ETEC
TOR
3.9K
1/2
W E
LR L
ISTE
D S
5434
MO
DEL
MP-
300
MAN
UFA
CTU
RED
BY
MIR
COM
PULL
STA
TIO
N
MAN
UAL
REL
EASE
SW
ITCH
Use
MS-
403,
404
USE
ONL
Y NO
CO
NTA
CT
ABO
RT S
WIT
CHCO
NNEC
T A
UL/
ULC
LIS
TED
ABO
RT S
TATI
ON
ACCE
PTAB
LE T
O
THE
AHJ,
CO
MPL
YING
WIT
H TH
E FO
LLO
WIN
G SP
ECIF
ICAT
IONS
MAX
IMUM
IM
PEDE
NCE
=1.
4K O
HM
S RA
TED
CURR
ENT
= 4
5mA
RATE
D VO
LTAG
E= 2
4V
From
RM
-306
Rel
ay A
dder
Mod
ule
Rela
y 3
From
FR-
320
Supe
rvis
ory
Rela
yN
O
C NO
C
NO
C
LT-6098 FR-320NetK Rev. 0 June 2015 Page 15
Pre- Programmed Mode
Pre-programmed Mode 2 is the FR-320K default program setting which includes new features.
Note: Cross Zone smokes detectors must not use verified alarm.
For more information, see LT-951 FR-320 Installation Manual.
Table 2 Mode 2 Agent Release, Single Hazard, Combined Release
Note: WF or Water Flow is not available.
Zone Configuration
The FleX-Net™ monitors the Detection Zones via relay control. Connect either Detection Zone 1 or 2, but not both.
• Detection Zone -1: Alarm (Hazard Area 1)
• Detection Zone -2: Alarm (Hazard Area 1)
• Detection Zone -5: Abort Switch
• Detection Zone -6: Manual Release
The FR-320K activates the Notification and Releasing Appliance Circuits.
• NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch active
• NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit (optional)
• RAC-1: Releasing Circuit (Hazard Area 1)
• RAC-2: Releasing Circuit (Hazard Area 1)
Hazard Configuration• Default Release Timer Value: 60 seconds
Detection Zones PhantomZones
Release Timers
Z1 Z2 Z3 Z4 Z5 Z6 Zp1 Zp2 RT1 Exp RT2 Exp
Alm Alm WF Sup AB MR Z1+Z2 Z3+Z4
Out1 Signal Steady X X X
Out2 Signal Escalating X
Out3 Rel. Releasing X X
Out4 Rel. Releasing X X
RLS TMR 1 Started X X
RLS Tmr 1 Stopped X
RLS Tmr 1 Canceled X X
RLS Tmr 1 Restarted X X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Canceled
Page 16 LT-6098 FR-320NetK Rev. 0 June 2015
• Default Manual Release Delay: 0 seconds
• Default Abort Delay Type: Standard UL
• Default Soak Timer Value: 0 seconds
NAC Configuration• Default Escalating NAC code of Hazard Area State:
•Hazard Idle: Off•Hazard Alert: Temporal•Hazard Alarm: Temporal•Hazard Release: Steady
• Default NAC code of Supervisory Signal is 20 BPM
How the FR-320K Panel Works in this Mode
The following is an example of how the FleX-Net™ and FR-320K system can work, based on Preprogrammed Mode 2. Full setup options are available via the FleX-Net™ Configurator software.
• Activation of either Z-1 or Z-2 turns NAC-1 on steady
• Activation of either Z-1 or Z-2 changes the Hazard Area 1 state from Idle into Alarm directly. NAC-1 turns on steady. NAC-2 turns on Temporal. Release Timer-1 is started
• Expiration of Release Timer-1 activates both RAC-1 and RAC-2. NAC-1 and NAC-2 turn on steady
• Activation of Z-6 starts Manual-release Timer 1 (MDT-1) and overrides the abort function in any situation. NAC-1 turns on steady. NAC-2 turns on Temporal. Upon the expiration of MDT-1, RAC-1 and RAC-2 turn on.
• During Hazard Alarm state, if Z-5 is pressed, Release Timer-1 is stopped, reset, and then restarted. If Z-5 is held for up to 50 seconds then the release device will actuate in 60 seconds after first pressing the abort switch. However, if Z-5 is held for longer than 50 seconds then the release device will actuate in 10 seconds.
Compatible Solenoids
The following table lists the solenoids with the FR-320K.
Manufacturer and Series Part Number Extended Description
Parker 73212BN4TNLVNOC322C2 Valve Solenoid
Siemens 500-697913BG Valve Solenoid
ASCO8210G207 Valve Solenoid
T8210A107 Valve Solenoid
BSCO 510006 Actuator
TSP 17842 Actuator
Kidde-Fenwal 486500-01 Actuator
TLX Technologies PA0036 Actuator