LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC...

28
LPG vaporizing solutions Soluzioni per la vaporizzazione del gpl LP Gas

Transcript of LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC...

Page 1: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

LPG vaporizing solutions

Soluzioni per la vaporizzazione del gpl

LP Gas

Page 2: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

From over 13 years Samtech is a worldwide supplier for the lpg industries.

The 3,500 plus installations of vaporizers, regulation units and hot water units for lpg

systems operating not only in Europe or Middle East but also in extreme weather conditions, from

Scandinavian countries, to South Africa, from China to South America, are a guarantee of the

quality of our products.

These numbers alone, are an evidence of the confi dence the main oil and lpg distribution

companies around the world have in Samtech products. Therefore we are proud to say that

“Samtech is your best partner for lpg systems”.

Da oltre 13 anni Samtech forniscel’industria del gpl.

Garanzia della qualità dei nostri prodotti sono gli oltre 3.500 impianti funzionanti nel mondo con vaporizzatori, gruppi di regolazione e centrali termiche per sistemi alimentati da gpl, impianti che lavorano nelle condizioni estreme dei paesi Scandinavi, del Sudafrica, della Cina e del Sudamerica, passando per l’Europa e il Medio Oriente.

Questi numeri dicono da soli quanta e quale sia la fi ducia che le migliori compagnie petrolifere e di distribuzione gpl di tutti i continenti ripongono nei prodotti Samtech ed è per questo che siamo orgogliosi di affermare che “Samtech è il tuo miglior partner per i sistemi gpl”.

Page 3: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

QUANDO ABBIAMO FONDATO LA SAMTECH …… nel 1994 la nostra aspirazione era quella di creare una realtà giovane e vivace che portasse un approccio nuovo in un mercato già fortemente strutturato. L’avvento di normative Europee standardizzate, che hanno investito il settore in modo signifi cativo nell’ultimo decennio, ha permesso alla nostra azienda di distinguersi adottando da subito quelle Direttive che l’avrebbero proposta per molti anni alla clientela come interlocutore privilegiato.

L’ESPERIENZA MATURATA …… in questi anni nella produzione e commercializzazione di tecnologie applicate all’utilizzo e al controllo del gas, sia esso GPL che metano, è ora garanzia di professionalità e competenza, sancita, prima ancora che dalle Omologazioni, dalle conferme che ogni giorno ci arrivano da clienti e distributori in tutto il mondo.

LA MISSIONLa scelta oculata di nuove partnership, il consolidamento di quelle acquisite negli anni, la dotazione di risorse strutturali e umane importanti, l’apertura a nuovi business e a nuovi mercati vanno nel senso di una visione che abbraccia obiettivi ambiziosi di crescita e danno all’azienda le peculiarità del dinamismo e della fl essibilità al servizio del cliente.

foto produzione vaporizzatori

WHEN SAMTECH WAS FOUNDED….…in 1994 we had the goal of establishing a dynamic company with a new approach to a well established

market. The arrival of Standard European Directives during the past decade has greatly infl uenced various sectors of our industry and allowed Samtech to distinguish itself by

immediately complying with these directives and therefore become a preferred supplier for our clients both now and in

the future.

THE ACQUIRED EXPERIENCE…… after many years of production and market know-how focused on the control of lpg and methane gas

our products carry a warranty of professionalism and competence confi rmed not only by our homologation

process but also by the daily feedback received by distributors and clients around the world.

OUR MISSION…… with the well considered choice of our new partnerships,

the integration of our human and capital resources, along with the opening of new markets worldwide, we are moving

Samtech towards our vision which includes ambitious growth targets along with dynamism and fl exibility to serve

our clients.

With all the above in mind, we are pleased to present our new 2007 lpg Vaporizers Catalogue

Con queste premesse è con orgoglio che Vi presentiamo il nuovo catalogo 2007

Vaporizzatori per gpl.

Page 4: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

Samvap lpg feed-out vaporizers EL-O / XC / WA-OVaporizzatori Samvap EL-O / XC / WA-O

Vaporizer safety and working equipmentOrgani di sicurezza e funzionamento del vaporizzatore

Page 5: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporizzazione/vaporization 5

Dati di progetto del vaporizzatoreCircuito acqua• Pressione di prova pneumatica: 3 bar• Pressione di esercizio: atmosferica• Temperatura di esercizio: -10 +95°C • Norme di progetto: VSR. M. S. - ISPESLCircuito GPL• Pressione di prova idraulica: 50 bar• Pressione di esercizio: 20 bar max • Temperatura di esercizio: -40 +120°C• Norme di progetto: VSR. M. S. - ISPESL

Design data of the vaporizerShell side (water)• Pressure of pneumatic test: 3 bar• Working pressure: atmospheric pressure• Working temperature: -10 +95°C • Design standard: VSR. M. S. - ISPESLTube side (gas)• Pressure of hydraulic test: 50 bar• Working pressure: 20 bar max • Working temperature: -40 +120°C• Design standard: VSR. M. S. - ISPESL

Page 6: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

6 vaporization/vaporizzazione

Lpg feed-out vaporizers Samvap EL-O and XChot water with electric heating elements

Vaporizzatori gpl feed-out Samvap EL-O e XCad acqua calda con resistenza elettrica

XC1 15/25/50/100 XC 100/200 XC 250/600

Caratteristiche standard• Facile installazione• Facile ed economica manutenzione• Lunga durata nel tempo• Bassissimo costo di gestione nel tempo • No parti scaldanti direttamente a contatto con il gas (evita

incrostazioni, surriscaldamenti e deterioramenti della resistenza elettrica)

• No schede elettroniche dedicate: tutti i componenti elettrici sono standard e facilmente reperibili sul mercato

• Doppia resistenza elettrica in acciaio inox • Valvola a sfera in acciaio fl angiata in entrata• Sistema di sicurezza meccanico di controllo del fl usso liquido • Termometro acqua• Manometro e valvola di sicurezza gas • Vaso espansione aperto con indicatore livello acqua• Valvola di spurgo circuito gas

EL-O CE Principali caratteristiche• Completo di box EEx-d con termostati di: lavoro (uno per

resistenza), max temperatura, minima temperatura (in caso di emergenza può essere quello di lavoro)

• Necessita di quadro elettrico da installare in zona sicura• Senza cablaggi elettrici dei componenti

XC CE Principali caratteristiche• Estrema rapidità e facilità di installazione• Quadro elettrico EEx-d incorporato con spie di stato e interruttore

on-off predisposto per comandi esterni (elettrovalvola, sirena, etc..)

• Quadro elettrico EEx-d incorporato senza spie di stato e senza interruttore on-off (1)

• Pronto all’uso con tutti i componenti elettrici già cablati• Necessita solo del collegamento alla rete elettrica

Opzioni• Interruttore EEx-d di alto livello gas• Interruttore EEx-d di minimo livello acqua• Trasduttori EEx-i per la gestione remota dei segnali di temperatura

e pressione• Elettrovalvole EEx-d in entrata e uscita• Vaso di espansione chiuso• Quadro elettrico IP 55 per EL-O• Cablaggi e cavi in guaina per EL-O• Cavi in guaina per XC• Barilotti raccoglicondensa

Standard features• Easy to install• Easy and economic maintenance• Durability• Minimal long term management cost• No heating elements in direct contact with gas to avoid build-up,

over heating and deterioration of the heating elements• No electronic dedicated heads, with standard electric components

easy to source in any market• Double stainless steel heating elements• Flanged stainless steel ball valve on the inlet phase• Mechanical safety device on the liquid fl ow• Water thermometer • Gas relief valve and manometer• Open expansion tank with level indicator• Gas drain valve

EL-O CE main features• Complete with EEx-d box with thermostas, one for each heating

element, one for max and one for min temperature (in case of emergency it can replace one of heating elements)

• Control panel to be installed in safety area is needed• No electrical cables for components are supplied

XC CE main features• Easy and quick to install• Built-in EEx-d control panel with pilot lights, on-off switch and

preset for external signal (electrovalve, siren, etc. ...)• Built-in EEx-d control panel without pilot lights and on-off

switch (1)• Ready to use with all electrical components connected• Just plug it in!

Options• EEx-d level switch for max gas level• EEx-d level switch for min water level• EEx-d transducers for remote management for temperature and

pressure signals• EEx-d solenoid valves on the inlet or outlet phase• Closed expansion tank• IP 55 remote control panel for EL-O• Wiring on vaporizer and cables to no Ex zone for EL-O• Cables with conduit for XC• Liquid condensate trap

EL-O 15/100

EL-O100/250

EL-O250/600

Page 7: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 7

EL-O / XC -10°C EL-O / XC -40°CTYPETIPO

CODECODICE

CAPACITYPORTATA

kg/h

POWERPOTENZA

kW

EL-O 15 CE VPR520150/C 15 2,8

EL-O 25 CE VPR520250/C 25 4

EL-O 50 CE VPR520500/C 50 8

EL-O 100 CE VPR521001/C 100 16

EL-O 100 CE VPR521000/C 100 8+8

EL-O 150 CE VPR521506/C 150 8+12

EL-O 200 CE VPR522006/C 200 12+12

EL-O 250 CE VPR522505/C 250 16+16

EL-O 300 CE VPR523005/C 300 16+24

EL-O 350 CE VPR523505/C 350 24+24

EL-O 400 CE VPR524005/C 400 24+32

EL-O 500 CE VPR525005/C 500 32+32

EL-O 600 CE VPR526005/C 600 36+36

EL-O 700 CE VPR527005/C 700 42+42

EL-O 800 CE VPR528005/C 800 4x24

EL-O 900 CE VPR529005/C 900 3x24+1x36

EL-O 1000 CE VPR52105M/C 1000 2x24+2x36

XC 15 CE (1) VPR540150/C 15 2,8

XC 15 CE VPR540151/C 15 2,8

XC 25 CE (1) VPR540250/C 25 4

XC 25 CE VPR540251/C 25 4

XC 50 CE (1) VPR540500/C 50 8

XC 50 CE VPR540501/C 50 8

XC 100 CE (1) VPR541002/C 100 16

XC 100 CE) VPR541001/C 100 16

XC 100 CE VPR541000/C 100 8+8

XC 150 CE VPR541506/C 150 8+12

XC 200 CE VPR542006/C 200 12+12

XC 250 CE VPR542505/C 250 16+16

XC 300 CE VPR543005/C 300 16+24

XC 350 CE VPR543505/C 350 24+24

XC 400 CE VPR544005/C 400 24+32

XC 500 CE VPR545005/C 500 32+32

XC 600 CE VPR546005/C 600 36+36

XC 700 CE VPR547005/C 700 42+42

XC 800 CE VPR548005/C 800 4x24

XC 900 CE VPR549005/C 900 3x24+1x36

XC 1000 CE VPR54105M/C 1000 2x24+2x36

TYPETIPO

CODECODICE

CAPACITYPORTATA

kg/h

POWERPOTENZA

kW

EL-O 15 CE VPR520150/C 15 2,8

EL-O 25 CE VPR520250/C 25 4

EL-O 50 CE VPR520500/C 50 8

EL-O 100 CE VPR521001/C 100 16

EL-O 100 CE VPR521000/C 100 8+8

EL-O 150 CE VPR521501/C 150 8+16

EL-O 200 CE VPR522001/C 200 16+16

EL-O 250 CE VPR522500/C 250 16+24

EL-O 300 CE VPR523000/C 300 24+24

EL-O 350 CE VPR523500/C 350 24+32

EL-O 400 CE VPR524000/C 400 32+32

EL-O 500 CE VPR525000/C 500 36+36

EL-O 600 CE VPR526000/C 600 42+42

EL-O 700 CE VPR527000/C 700 4x24

EL-O 800 CE VPR528000/C 800 3x24+1x36

EL-O 900 CE VPR529000/C 900 2x24+2x36

EL-O 1000 CE VPR52100M/C 1000 1x24+3x36

XC 15 CE (1) VPR540150/C 15 2,8

XC 15 CE VPR540151/C 15 2,8

XC 25 CE (1) VPR540250/C 25 4

XC 25 CE VPR540251/C 25 4

XC 50 CE (1) VPR540500/C 50 8

XC 50 CE VPR540501/C 50 8

XC 100 CE (1) VPR541002/C 100 16

XC 100 CE VPR541001/C 100 16

XC 100 CE VPR541000/C 100 8+8

XC 150 CE VPR541501/C 150 8+16

XC 200 CE VPR542001/C 200 16+16

XC 250 CE VPR542500/C 250 16+24

XC 300 CE VPR543000/C 300 24+24

XC 350 CE VPR543500/C 350 24+32

XC 400 CE VPR544000/C 400 32+32

XC 500 CE VPR545000/C 500 36+36

XC 600 CE VPR546000/C 600 42+42

XC 700 CE VPR547000/C 700 4x24

XC 800 CE VPR548000/C 800 3x24+1x36

XC 900 CE VPR549000/C 900 2x24+2x36

XC 1000 CE VPR54100M/C 1000 1x24+3x36

Lpg feed-out vaporizers Samvap EL-O and XChot water with electric heating elements

Vaporizzatori gpl feed-out Samvap EL-O e XCad acqua calda con resistenza elettrica

referred to gas temperature to determine the power of heating elementriferito alla temperatura del gas per defi nire la potenza della resistenza-10°C or -40°C:

NOTES:(1) Built-in EEx-d control panel without pilot lights and on-off switch

NOTE: (1) Quadro elettrico EEx-d incorporato senza spie di stato e senza interruttore on-off

Page 8: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

8 vaporization/vaporizzazione

EL-O size and connections / dimensioni e attacchi

model / modellocapacity/portata

kg/hconnections / attacchi size / dimensioni mmDi/gas Do/gas A B C D E F G

EL-O 15 CE 15 DN25 DN25 1875 285 380 1500 534 497 156

EL-O 25 CE 25 DN25 DN25 1875 285 380 1500 534 497 156

EL-O 50 CE 50 DN25 DN25 1875 285 380 1500 534 497 156

EL-O 100 CE 100 DN25 DN25 1875 285 380 1500 534 497 225

EL-O 150 CE 150 DN25 DN25 1875 285 590 1500 380 343 225

EL-O 200 CE 200 DN25 DN25 1875 285 590 1500 380 343 225

EL-O 250 CE 250 DN25 DN32 1875 285 590 1500 380 343 225

EL-O 300 CE 300 DN25 DN32 1875 285 590 1500 380 343 225

EL-O 350 CE 350 DN25 DN32 1875 285 590 1500 380 343 225

EL-O 400 CE 400 DN32 DN40 2225 285 590 1850 380 343 225

EL-O 500 CE 500 DN32 DN40 2225 285 590 1850 380 343 225

EL-O 600 CE 600 DN32 DN40 2225 285 590 1850 380 343 225

EL-O 700 CE 700 DN32 DN50 2225 595 590 2050 715 497 225

EL-O 800 CE 800 DN32 DN50 2225 595 590 2050 715 497 225

EL-O 900 CE 900 DN32 DN50 2225 595 590 2050 715 497 225

EL-O1000CE 1000 DN32 DN50 2225 595 590 2050 715 497 225

XC size and connections / dimensioni e attacchi

model / modellocapacity/portata

kg/hconnections / attacchi size / dimensioni mmDi/gas Do/gas A B C D E F G

XC 15 CE 15 DN25 DN25 1875 285 380 1500 534 497 190

XC 25 CE 25 DN25 DN25 1875 285 380 1500 534 497 190

XC 50 CE 50 DN25 DN25 1875 285 380 1500 534 497 190

XC 100 CE 100 DN25 DN25 1875 285 590 1500 380 343 190

XC 150 CE 150 DN25 DN25 1875 285 590 1500 380 343 190

XC 200 CE 200 DN25 DN25 1875 285 590 1500 380 343 295

XC 250 CE 250 DN25 DN32 1875 285 590 1500 380 343 295

XC 300 CE 300 DN25 DN32 1875 285 590 1500 380 343 295

XC 350 CE 350 DN25 DN32 1875 285 590 1500 380 343 295

XC 400 CE 400 DN32 DN40 2225 285 590 1850 380 343 295

XC 500 CE 500 DN32 DN40 2225 285 590 1850 380 343 295

XC 600 CE 600 DN32 DN40 2225 285 590 1850 380 343 590

XC 700 CE 700 DN32 DN50 2225 595 590 2050 715 497 590

XC 800 CE 800 DN32 DN50 2225 595 590 2050 715 497 590

EL-O 900 CE 900 DN32 DN50 2225 595 590 2050 715 497 590

EL-O1000 CEXC 1000 DN32 DN50 2225 595 590 2050 715 497 590

Page 9: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 9

Lpg feed-out vaporizers Samvap WA-Ohot water feeded by external boiler

Vaporizzatori gpl feed-out Samvap WA-Oad acqua calda alimentata da caldaia

WA-O750/1000/1500

WA-O300/600

WA-O50/250

TIPOTYPE

CODICECODE

PORTATACAPACITY

KG/H WA-O 50 CE VPR510500/C 50

WA-O 100 CE VPR511000/C 100

WA-O 200 CE VPR512000/C 200

WA-O 250 CE VPR512500/C 250

WA-O 300 CE VPR513000/C 300

WA-O 350 CE VPR513500/C 350

WA-O 500 CE VPR515000/C 500

WA-O 600 CE VPR516000/C 600

WA-O 750 CE VPR517500/C 750

WA-O 1000 CE VPR51010M/C 1000

WA-O 1500 CE VPR51015M/C 1500

WA-O 2000 CE VPR51020M/C 2000

WA-O zona 1

On request:• capacities over 2.000 kg/h• ASME design and construction• ANSI 300 fl anged

Su richiesta:• portate superiori a 2.000 kg/h• costruzione e progettazione ASME• fl angiatura ANSI 300

Caratteristiche standard• Facile installazione• Facile ed economica manutenzione• Lunga durata nel tempo• Bassissimo costo di gestione nel tempo • No elementi scaldanti direttamente a contatto con il gas (evita

incrostazioni, surriscaldamenti)• Non necessita alimentazione elettrica: la versione base standard

non richiede elettricità• Valvola a sfera in acciaio fl angiata in entrata• Sistema di sicurezza meccanico di controllo del fl usso liquido • Manometro, termometro e valvola di sicurezza acqua• Manometro e valvola di sicurezza gas• Valvole di spurgo circuito gas e acqua• Collegato con una caldaia esterna

Opzioni• Interruttore EEx-d di alto livello gas• Trasduttori EEx-i per la gestione remota dei segnali di temperatura

e pressione• Elettrovalvole EEx-d in entrata e uscita• Termostato EEx-d di minima temperatura• Barilotti raccoglicondensa

Standard features• Easy to install• Easy and economic maintenance• Durability• Minimal long term management cost• No heating elements in direct contact with gas to avoid build-up

and over heating • No electric power required for standard version• Flanged steel ball valve on the inlet phase• Mechanical safety device on the liquid fl ow• Water manometer, thermometer and relief valve• Gas manometer and relief valve• Gas and water drain valves• To be connected to an external hot water boiler unit

Options• EEx-d level switch for max gas level• EEx-d transducers for remote management for temperature and

pressure signals• EEx-d solenoid valves on the inlet and the outlet phase• EEx-d thermostat for minimum temperature• Liquid condensate trap

Page 10: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

10 vaporization/vaporizzazione

WA-O size and connections / dimensioni e attacchi

model / modellocapacity/portata

kg/hconnections / attacchi size / dimensioni mm

Di/gas Do/gas DI/DO H2O A B C D E F

VPR510500/C 50 DN25 DN25 1" 1650 285 380 1500 534 534

VPR511000/C 100 DN25 DN25 1" 1650 285 380 1500 534 534

VPR512000/C 200 DN25 DN25 1" 1650 285 380 1500 534 534

VPR512500/C 250 DN25 DN25 1" 1650 285 380 1500 534 534

VPR513000/C 300 DN25 DN32 1¼" 1650 285 590 1500 380 343

VPR513500/C 350 DN25 DN32 1¼" 1650 285 590 1500 380 343

VPR515000/C 500 DN32 DN40 1¼" 1980 285 590 1850 380 343

VPR516000/C 600 DN32 DN40 1¼" 1980 285 590 1850 380 343

VPR517500/C 750 DN32 DN50 1¼" 1650 595 590 1500 715 866

VPR51010M/C 1000 DN32 DN50 1¼" 2050 595 590 1850 715 866

VPR51015M/C 1500 DN32 DN50 1¼" 2050 595 590 1850 715 866

VPR51020M/C 2000 DN40 DN50 1¼" 2050 595 830 1850 715 866

Lpg feed-out vaporizers Samvap WA-Ohot water feeded by boiler

Vaporizzatori gpl feed-out Samvap WA-Oad acqua calda alimentata da caldaia

Page 11: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 11

Vaporizing unit 900 kg/h capacity with 3x300 kg/h Samvap XC Gruppo di vaporizzazione portata 900 kg/h

con 3x300 kg/h Samvap XC

Vaporizing unit 600 kg/h capacity with 2x300 kg/h Samvap WA-O

Gruppo di vaporizzazione portata 600 kg/hcon 2x300 kg/h Samvap WA-O

Vaporizing unit 6000 kg/h capacity with 6x1,000 kg/h Samvap WA-O

Gruppo di vaporizzazione portata 6000 kg/hcon 6x1.000 kg/h Samvap WA-O

Samtech offers SAMVAP MULTI solutions on skid according to customer needs.Samtech reference list includes units with SAMVAP EL-O and XC up to 2,500 kg/h and with WA-O up to 6,000 kg/h

Samtech è in grado di offrire soluzioni su skid SAMVAP MULTI in accordo alle esigenze del cliente; le referenze Samtech comprendono impianti con SAMVAP EL-O e XC fino a 2.500 kg/h e con WA-O fino a 6.000 kg/h

Samvap Multivaporizing solutions for large and fl exible lpg capacities

Samvap Multisoluzioni di vaporizzazione per grandi e fl essibili portate

Page 12: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

12 vaporization/vaporizzazione

Samvap optionsOpzioni per Samvap

CLV 510621

REMOTE CONTROL PANEL IP55 - CE marked for Samvap EL-OPANNELLO DI CONTROLLO REMOTO IP55 - con marcatura CE per Samvap EL-O

- : not available non disponibile• : option available for all Samvap per tutti i SamvapEL, XC, WA: specifi c option opzione specifi ca

Tipo kW 15 25 50 100 150 200 250 300 350 400 500 600 700 750 800 900 1000 1500 2000

QEC752003 2,8 EL - - - - - - - - - - - - - - - - - -QEC752004 4 - EL - - - - - - - - - - - - - - - - -QEC752005 8 - - EL - - - - - - - - - - - - - - - -QEC752011 16 - - - EL - - - - - - - - - - - - - - -QEC752010 8+8 - - - EL - - - - - - - - - - - - - - -QEC752013 8+12 - - - - EL - - - - - - - - - - - - - -QEC752015 8+16 - - - - EL - - - - - - - - - - - - -QEC752018 12+12 - - - - - EL - - - - - - - - - - - - -QEC752020 16+16 - - - - - EL EL - - - - - - - - - - - -QEC752025 16+24 - - - - - - EL EL - - - - - - - - - - -QEC752030 24+24 - - - - - - - EL EL - - - - - - - - - -QEC752035 24+32 - - - - - - - - EL EL - - - - - - - - -QEC752040 32+32 - - - - - - - - - EL EL - - - - - - - -QEC752050 36+36 - - - - - - - - - - EL EL - - - - - - -QEC752060 42+42 - - - - - - - - - - - EL EL - - - - - -QEC752070 4x24 - - - - - - - - - - - - EL - EL - - - -QEC752080 3x24 + 1x36 - - - - - - - - - - - - - - EL EL - - -QEC752090 2x24 + 2x36 - - - - - - - - - - - - - - EL EL - -QEC752100 1x24 + 3x36 - - - - - - - - - - - - - - - - EL - -

OQE010200Extra costo per gestione interruttore livello acquaExtra cost for water level switch management

EL EL EL EL EL EL EL EL EL EL EL EL EL - EL EL EL - -

OQE010600Extra costo per gestione interruttore livello gasExtra cost for lpg level switch management

EL EL EL EL EL EL EL EL EL EL EL EL EL - EL EL EL - -

WIRING AND CABLES for Samvap EL-O - Cables for power feeding for vaporizers and thermostats, with protective conduit and EEx-d fi ttings. 5 mts lenght, longher cables on request.CABLAGGI E CAVI per Samvap EL-O - Cablaggi e cavi di alimentazione per resistenze e termostati, con guaina di protezione e raccorderia EEx-d. Lunghezza mt 5, lunghezze superiori a richiesta.

CCE715203 2,8 EL - - - - - - - - - - - - - - - - - -CCE715204 4 - EL - - - - - - - - - - - - - - - - -CCE715205 8 - - EL - - - - - - - - - - - - - - - -CCE715211 16 - - - EL - - - - - - - - - - - - - - -CCE715210 8+8 - - - EL - - - - - - - - - - - - - - -CCE715213 8+12 - - - - EL - - - - - - - - - - - - - -CCE715215 8+16 - - - - EL - - - - - - - - - - - - - -CCE715218 12+12 - - - - - EL - - - - - - - - - - - - -CCE715220 16+16 - - - - - EL EL - - - - - - - - - - - -CCE715225 16+24 - - - - - - EL EL - - - - - - - - - - -CCE715230 24+24 - - - - - - - EL EL - - - - - - - - - -CCE715235 24+32 - - - - - - - - EL EL - - - - - - - - -CCE715240 32+32 - - - - - - - - - EL EL - - - - - - - -CCE715250 36+36 - - - - - - - - - - EL EL - - - - - - -CCE715260 42+42 - - - - - - - - - - - EL EL - - - - - -CCE715270 4x24 - - - - - - - - - - - - EL - EL - - - -CCE715280 3x24 + 1x36 - - - - - - - - - - - - - - EL EL - - -CCE715290 2x24 + 2x36 - - - - - - - - - - - - - - - EL EL - -CCE71521M 1x24 + 3x36 - - - - - - - - - - - - - - - - EL - -

LEVEL SWITCHES installed on vaporizerINTERRUTTORI DI LIVELLO montati su vaporizzatore

CLV520221Minimo livello acqua EEx-dLow water level switch EEx-d

EL EL EL EL EL EL EL EL EL EL EL EL EL - EL EL EL - -

CLV500621Alto livello gas EEx-dHigh lpg level switch EEx-d

EL EL EL/WA EL/WA EL EL/WA EL/WA EL/WA EL/WA EL EL/WA EL/WA EL WA EL EL EL/WA WA WA

CLV540221Minimo livello acqua EEx-d (pre-allarme, allarme+blocco tensione)Low water level switch EEx-d (pre-alarm, alarm+voltage shut-down)

XC XC XC XC XC XC XC XC XC XC XC XC XC - XC XC XC - -

CLV540621Alto livello gas EEx-d (spia allarme+comando elettrovalvola)High lpg level switch EEx-d (pilot alarm+solenoid valve command)

XC XC XC XC XC XC XC XC XC XC XC XC XC - XC XC XC - -

CCE735100Cavi con guaina (5mt) e raccordi EEx-d per interruttore livello gasCables with conduit (5mts) and EEx-d fi ttings for LPG level switch

EL EL EL/WA EL/WA EL EL/WA EL/WA EL/WA EL/WA EL EL/WA EL/WA EL WA EL EL EL/WA WA WA

CCE765100Cavi con guaina (5mt) e raccordi EEx-d per interruttore livello acquaCables with conduit (5 mts) and EEx-d fi ttings for water level switch

EL EL EL EL EL EL EL EL EL EL EL EL EL - EL EL EL - -

CCE72/73/74/76

Page 13: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 13

Samvap optionsOpzioni per Samvap

water condensate trapbarilotto

KEV electrovalveelettrovalvola KEV

EEx-d protection kit

NORMALLY CLOSED SOLENOID VALVE KIT EEx-d 230 VacKIT ELETTROVALVOLA EEx-d 230 Vac N.C.

- : not available non disponibile• : option available for all Samvap per tutti i SamvapEL, XC, WA: specifi c option opzione specifi ca

15 25 50 100 150 200 250 300 350 400 500 600 700 750 800 900 1000 1500 2000

KEV325288 DN 25 PN40 Flangiata/Flanged EL EL • • • • • • • - - - - - - - - - -

KEV332288 DN 32 PN40 Flangiata/Flanged - - - - - - • • • EL EL • EL WA EL EL • WA WA

KEV340288 DN 40 PN40 Flangiata/Flanged - - - - - - - - - EL • • EL - - - - - -

KEV350288 DN 50 PN40 Flangiata/Flanged - - - - - - - - - - - - - WA EL EL • WA WA

KEL300000Kit di protezione EEx-d per elettrovalvolaEEx-d protection kit for solenoid valve

• • • • • • • • • EL • • EL WA EL EL • WA WA

KEL300100Cablaggi al quadro EEx-d (VPR54) con cavo e raccordi EEx-dWiring to the EEx-d box (VPR54) with cable and EEx-d fi ttings

XC XC XC XC XC XC XC XC XC XC XC XC XC - XC XC XC - -

CCE725100Cavi (5 mt) con guaina e raccordi EEx-d per elettrovalvolaCables (5 mts) with conduit and EEx-d fi ttings for solenoid valve

• • • • • • • • • EL • • EL WA EL EL • WA WA

THERMOSTAT for minimum temperatureTERMOSTATO per minima temperatura

KTR580040Termostato di EEx-d montato sul vaporizzatoreEEx-d thermostat asssembled on vaporizer

- - WA WA WA WA WA WA WA - WA WA - WA - - WA WA WA

TRM511045Termostato IP53 M1/2” con sonda L=100mm da montare su linea acquaIP53 thermostat M1/2” with probe L=100mm to be mounted on water pipeline

- - WA WA WA WA WA WA WA - WA WA - WA - - WA WA WA

KEL200000Kit di protezione EEx-d per termostatoEEx-d protection kit for thermostat

- - WA WA WA WA WA WA WA - WA WA - WA - - WA WA WA

CCE745100Cavi (5 mt) con guaina e raccordi EEx-d per termostatoCables (5 mts) with conduit and EEx-d fi ttings for thermostat

- - WA WA WA WA WA WA WA - WA WA - WA - - WA WA WA

CONTROL PANEL to control solenoid valveQUADRO ELETTRICO per comando elettrovalvola

QEC751010Quadro IP55 per gestione termostato/elettrovalvolaIP55 control panel to control thermostat/solenoid valve

- - WA WA WA WA WA WA WA - WA WA - WA - - WA WA WA

QEC751013Quadro IP55 per gestione interruttore livello gas+termostato/elettrovalvolaIP55 control panel to control lpg level switch+thermostat/solenoid valve

- - WA WA WA WA WA WA WA - WA WA - WA - - WA WA WA

WATER CONDENSATE TRAP Ts -10°C “CE” markedBARILOTTO RACCOGLICONDENSA Ts -10°C con marcatura “CE”

BRC108525/C DN 25 PN40 EL EL • • • • WA - - - - - - - - - - - -

BRC108532/C DN 32 PN40 - - - - - - • • • - - - - - - - - - -

BRC108540/C DN 40 PN40 - - - - - - - - - EL • • EL - - - - - -

BRC108550/C DN 50 PN40 - - - - - - - - - - - - - WA EL EL • WA WA

BRC108580/C DN 80 PN40 - 100 litri/liters • • • • • • • • • • • • • • • • • • •

OTHER OPTIONSALTRE OPZIONI

KVE060000Kit vaso di espansione chiuso (6 litri)Closed expansion tank kit (6 liters)

EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC EL/XC - EL/XC EL/XC EL/XC - -

close expansion tankvaso di espansione chiuso

thermostats for minimum temperaturetermostati minima temperatura

Page 14: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

14 vaporization/vaporizzazione

PACKING in wooden crate for SAMVAPGABBIE IN LEGNO per vaporizzatori SAMVAP 15 25 50 10

0

150

200

250

300

350

400

500

600

700

750

800

900

1000

1500

2000

ZIV177077067 177 x 77 x 67 cm EL EL EL EL - - - WA WA - - - - - - - - - -

ZIV177077057 177 x 77 x 57 cm - - WA WA - WA WA - - - - - - - - - - - -

ZIV177077077 177 x 77 x 77 cm XC1 XC1 XC1 XC1 - - - - - - - - - - - - - - -

ZIV177077082 177 x 77 x 82 cm XC XC XC EL/XC1 EL EL - - - - - - - - - - - - -

ZIV177077087 177 x 77 x 87 cm - - - - - EL EL EL EL - - - - - - - - - -

ZIV177077099 177 x 77 x 99 cm - - - XC XC XC XC XC XC - - - - - - - - - -

ZIV177077108 177 x 77 x 108 cm - - - - - - - - - - - - - WA - - - - -

ZIV217077067 217 x 77 x 67 cm - - - - - - - - - - WA WA - - - - - - -

ZIV217077108 217 x 77 x 108 cm - - - - - - - - - XC XC XC - - - - WA WA -

ZIV220090130 217 x 77 x 95 cm - - - - - - - - - EL EL EL - - - - - - -

ZIV217095108 217 x 95 x 108 cm - - - - - - - - - - - - - - - - - - WA

ZIV512503 pianale/pallet (cm 177x74) • • • • • • • • • - - - - - WA - - - -

ZIV512504 pianale/pallet (cm 217x74) - - - - - - - - - EL • • EL - - - WA WA -

ZIV512505 pianale/pallet (cm 217x90) - - - - - - - - - - - - - - - - - - WA

Samvap optionsOpzioni per Samvap

Samvap EL-O / XC / WA-O vaporizers spare partsRicambi per vaporizzatori samvap EL-O / XC / WA-O

CODECODICE

DESCRIPTIONDESCRIZIONE

MAN121062/0025manometro gas a bagno di glicerina cassa inox DN63 scala 0-25 bar glicerine bath stainless steel pressure gauge for gas DN63 0-25 bar

TRM218040/0120termometro DN80 AR 1/2 gas 0-120° ISPESL thermometer DN80 1/2 gas connection 0-120°

MAN112041/0006Manometro acqua cassa ABS, DN40 scala 0-6 bar.Pressure gauge for water, ABS case, DN40 0-6 bar

VSS741508valvola di sicurezza acqua 2 bar water safety valve 2 bar

VSS741510Valvola di sicurezza acqua 3 bar con attacco manometro.Water safety valve 3 bar with pressure gauge connection.

VSS771515valvola di sicurezza gas ISPESL 17,65 bar gas safety valve 17,65 bar

VSS721500valvola di sfi ato aria 1/2 air blend valve 1/2

RBL120808rubinetto spillo ottone MF 1/4 per manometro gas brass needle valve for gas pressure gauge MF 1/4

APM270800rubinetto spillo in acciaio MF 1/4 per manometro gas steel needle valve for gas pressure gauge MF 1/4

VSF511521valvola a sfera PN40 spurgo gas MF 1/2 brass ball valve MF 1/2 PN40 for gas drain

Page 15: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 15

CODECODICE

DESCRIPTIONDESCRIZIONE

RES180285/Cresistenza EEx-d ATEX 2,8 kW EEx-d heating elements ATEX 2,8 kW

RES180400/Cresistenza EEx-d ATEX 4 kW EEx-d heating elements ATEX 4 kW

RES180805/Cresistenza EEx-d ATEX 8 kW (L=600 mm) per EL-O 50EEx-d heating elements ATEX 8 kW (L=600 mm) for EL-O 50

RES180806/Cresistenza EEx-d ATEX 8 kW per EL-O 100/150EEx-d heating elements ATEX 8 kW for EL-O 100/150

RES181206/Cresistenza EEx-d ATEX 12 kWEEx-d heating elements ATEX 12 kW

RES181605/Cresistenza EEx-d ATEX 16 kW (L=600 mm) per EL-O 100EEx-d heating elements ATEX 16 kW (L=600 mm) for EL-O 100

RES181600/Cresistenza EEx-d ATEX 16 kW attacco fl angiatoEEx-d heating elements ATEX 16 kW fl anged connection

RES181606/Cresistenza EEx-d ATEX 16 kW attacco fi lettatoEEx-d heating elements ATEX 16 kW threaded connection

RES182400/Cresistenza EEx-d ATEX 24 kW EEx-d heating elements ATEX 24 kW

RES183200/Cresistenza EEx-d ATEX 32 kW EEx-d heating elements ATEX 32 kW

RES183600/Cresistenza EEx-d ATEX 36 kW EEx-d heating elements ATEX 36 kW

RES184200/Cresistenza EEx-d ATEX 42 kW EEx-d heating elements ATEX 42 kW

TRM580040termostato EEx-d per vaporizzatori WA-OEEx-d thermostat for WA-O vaporizer

TRM569900termostato di blocco per max temperatura riarmo manuale shutt-off thermostat for max temperature manual reset

TRM559900termostato regolazione per temperatura minima e di lavoro regulating thermostat for working and min temperature

KVP020101vaso di espansione completo di tubo e spia visivawater expansion tank with threaded pipe and level indicator

VES060000vaso di espansione chiuso 6 litri6 liters closed water expansion tank

CLV010221Livellostato EEx-d per minimo livello acqua doppio contattoEEx-d level switch for minimum water level double contact

CLV060120Livellostato EEx-d per massimo livello gasEEx-d level switch for max gas level

EMV763413spia visiva per vaso di espansione water level indicator for expansion tank

Samvap EL-O / XC / WA-O vaporizers spare partsRicambi per vaporizzatori samvap EL-O / XC / WA-O

RESTRM 56

TRM 21

CLV

TRM 55 MAN 12

TRM 58

VSS 77

Page 16: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

16 vaporization/vaporizzazione

Vaporizing and regulating units on skidGruppi di vaporizzazione e riduzione su skid

Perché i gruppi di vaporizzazione e regolazione Samtech sono sempre più apprezzati:

• Unico ordine per vaporizzatore e regolatori: meno ordini, più potere contrattuale con il fornitore = meno costi, più tempo per fare altre cose

• Progettazione e dimensionamento fatta da esperti ingegneri: prestazioni e funzionamento garantito = meno costi di progettazione e/o consulenze e meno costi per gestire problemi connessi ad errate valutazioni dell’installazione

• Assemblaggio e collaudo dell’unità fatta da tecnici esperti: migliore qualità nell’esecuzione dell’insieme, meno imprevisti al momento dell’avviamento = minori costi di personale qualificato

• Rapidità di installazione: in pochissimo tempo si è in grado di mettere in esercizio l’impianto = meno costi di installazione in loco

• Conservazione del valore dell’investimento nel tempo: l’unità essendo trasportabile consente di recuperare l’impianto e utilizzarlo presso un altro cliente = migliore ammortamento del bene, recupero e risparmio costi in caso di riutilizzo

• Politiche commerciali più incisive sul cliente: la precisa identificazione dell’impianto e la possibilità di riprendere il bene concesso in comodato in tempi molto rapidi, funge da deterrente nei confronti del cliente-consumatore = maggiore potere contrattuale e minore volatilità nei confronti della clientela, costi di recupero molto contenuti

• Garanzia della qualità del prodotto e dei processi costruttivi: Samtech opera in regime di gestione, progettazione e produzione secondo ISO 9001 = meno costi dovuti ad imprevisti e scarsa qualità

• Certezza dell’utilizzo di materiali e componenti di qualità: l’esperienza Samtech nella costruzione di oltre 500 unità garantisce l’uso di componenti e materiali testati nella loro qualità ed affidabilità = meno costi per sostituzioni e manutenzione

• Unico interlocutore per riparazioni e ricambi di vaporizzatore e regolatori: l’accorpamento di ordini per riparazioni e ricambi consente di avere più potere contrattuale nei confronti del fornitore = minori costi di gestione

• Costi certi e conosciuti, fissi ed invariabili di tutto l’insieme fino allo start-up dell’impianto: un unico prezzo per tutta la fornitura dell’insieme = budget di spesa certo, verificabile senza extra costi

• Servizio di supporto tecnico pre-post vendita: per i clienti delle unità l’ufficio tecnico Samtech è a disposizione per supportare il cliente nella scelta e per assistere telefonicamente nel post-vendita = meno costi per individuare la soluzione tecnica,e per risolvere i problemi

• Marcatura CE dell’insieme (opzionale): l’ufficio tecnico Samtech è in grado di fornire l’intera unità con marcatura CE secondo direttiva PED consentendo di presentare, nella fase di ottenimento delle autorizzazioni, un unico insieme già marchiato e quindi evitando successive procedure di valutazione = meno costi di progettazione ed autorizzazione

• I vantaggi si moltiplicano se l’unità è ordinata insieme ad una centrale termica

Why are Samtech vaporizers and regulating units increasingly appreciated?These are main advantages:

• One order for vaporizer and regulators, all together less orders, more contractual power with the supplier, more time for yourself.

• Designed made by our technical staff performances and working guarantee = less design costs and/or consulting and less costs for troubleshooting.

• Assembling and testing guaranteed by our technical experts: better quality for the whole performance, less inconvenience during start up = lower costs for skilled personnel and for unexpected trouble during start up.

• Fast installation: in a very short time the plant can be started up = less costs of installation in loco.

• Save the investment value during the time: due to unit’s portability is allowed recover the plant and reuse near other client.

• More incisive commercial policy to clients: the right identifi cation of the plant and the possibility to recover the material allowed in commodate in a faster time, function as deterrent towards clients – consumer = more contractual power and less volatility towards clients, recovered costs held down.

• Quality of Samtech products and building process guarantee: Samtech works under managing design and production system, in according with ISO 9001 = less costs due to inconvenience and scanty quality.

• Certainty used material and element of best quality: Samtech experience assured by building over 500 units guarantee elements and material tested quality and reliability = less costs for substitutions and maintenance

• Sole interlocutor for repairs and spare parts of vaporizers and regulators: the unifi cation of orders for repairs and spare parts allow more contractual power towards supplier = less managing costs

• Certain and known costs, fi xed and invariable: all together up to start up of the plant; one price for the whole supply = clear budget, verifi able without extra-costs.

• Customer service pre-post sale: for Samtech clients our technical department is at disposal for support the best solution and assistance = less costs for solve issues with a technical solution.

• Service assistance: Samtech service assistance completing our offer can offer start up, ordinary and extraordinary maintenance including spare parts, assuring a long-life = less managing costs, investment life, safe costs.

• CE marked overall (option): Samtech technical department can supply the whole unit CE marked in according wit PED allowing to make application, during authorizations inquiry phase, a sole unit marked, therefore avoiding further evaluation processes = less design and authorization costs

• Advantages increase if unit is ordered with a thermal unit

Page 17: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 17

1st stage, double line,200 kg/h capacity

I° salto, doppia linea,portata 200 kg/h

1st stage, double line, 300 kg/h capacitywith metering line

I° salto, doppia linea,portata 300 kg/h con misura

1st Stage, double line, 1000 kg/h capacity with condensate trap

I° salto, doppia linea, portata 1000 kg/hcon raccoglitore di condense

1st stage, double line, 1.000 kg/h capacitywith metering line

I° salto, doppia linea, portata 1.000 kg/h con misura

I° salto,doppia linea, portata 600 kg/h

1st stage, double line, 600 kg/h capacity

1st Stage, 6.000 kg/h capacity with metering line

I° salto, portata 6.000 kg/h con misura

Vaporizing and regulating units on skidGruppi di vaporizzazione e riduzione su skid

1st stage, double line, 900 kg/h capacity

I° salto, doppia linea, portata 900 kg/h

1st stage, double line, 900 kg/h capacity

I° salto, doppia linea, portata 900 kg/h

Page 18: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

18 vaporization/vaporizzazione

1st stage single and double line1° stadio singola e doppia linea

Portata kg/hCapacity kg/h

DN ingressoND Inlet

DN uscitaND Outlet

DN da serbatoioND from tank

50 25 40 25100 25 40 25150 25 40 25200 25 50 25250 25 50 25300 25 50 25350 25 65 40500 32 80 40600 32 80 40750 32 100 501000 40 100 501500 40 125 502000 50 150 50

Su richiesta altre portate - On request other capacitiesFlangiatura classe PN40 - Flange rating PN40

ND inlet

DN ingresso

PI

PI PI

ND outlet

DN uscita

DN da serbatoio

ND from tank

14

1015

2

1

8

13

12

69

4 75

8

457

3

11

3

Pos.DescrizioneDescription

QuantitàQty

1 Vaporizzatore feed-outFeed out vaporizer 01

2 Valvola a sfera Ball valve 01

3 Valvola di intercettazioneCut-off valve 02

4 Filtro a cartuccia (opzionale)Filter with decanter (option) 02

5 Regolatore (con o senza blocco)Pressure regulators (with or without UPSO/OPSO) 02

6 Manometro con rubinetto a spilloManometer with needle valve 02

7 Manometro differenziale (opzionale)Differential manometer (option) 02

8 Valvola di intercettazioneCut-off valve 02

9* Valvola di sfi oro esterna con valvola a sferaExternal relief valve with ball valve 01

10 Valvola ad azionamento elettrico o pneumatico (opz.)Electrical or pneumatical actuated valve (option) 01

11 Valvola di intercettazione fase gas da serbatoio (opz.)Cut-off valve gas phase from tank (option) 01

12 Valvola di intercettazione uscita (opzionale)Cut-off outlet valve (option) 01

13 Valvola a sfera 1/4”Ball valve 1/4” 01

14 Skid di supporto in acciaio verniciatoSteel skid in painted steel 01

15 Armadio di protezione (opzionale)Protection Kiosk (option) 01

* Prevista solo da portate superiori a 300 kg/h Only for capacities over 300 Kg/h

ND inlet

DN ingresso

ND from tank

DN da serbatoio

ND outletDN uscita

PI

M

PI

PIPI

17

12

18

19

16

20

9

10

5

5

1311

3 4

2

14

315

4

15

10

9

8

87

6

1

Pos.DescrizioneDescription

QuantitàQty

1 Vaporizzatore feed-outFeed out vaporizer 01

2 Valvola a sfera - Ball valve 01

3 Valvola di intercettazione - Cut-off valve 02

4 Filtro a cartuccia (opz.) - Filter with decanter (option) 02

5 Regolatore di alta pressione (con o senza blocco)Hig pressure regulators (with or without Upso-Opso) 02

6 Manometro con rubinetto a spilloManometer with needle valve 02

7* Valvola di sfi oro esterna 1° salto con valvola a sferaExternal relief valve for 1st stage with ball valve 02

8 Valvola di intercettazione - Cut-off valve 02

9 Valvola di intercettazione - Cut-off valve 02

10 Regolatore di bassa pressione (con o senza blocco)Low pressure regulators (with or without Upso-Opso) 02

11 Valvola di intercettazioneExternal relief valve for 2nd stage with ball valve 02

12* Valvola di sfi oro esterna 2° salto con valvola a sferaCut-off outlet valve (option) 01

13 Manometro con rubinetto a spilloManometer with needle valve 01

14 Valvola ad azionamento elettrico o pneumatico (opz.)Electrical or pneumatical actuated valve (option) 01

15 Manometro differenziale (opz.)Differential manometer (option) 01

16 Skid di supporto - Steel skid 01

17 Valvola di intercettazione ingresso da serbatoio (opz.)Cut-off inlet valve from tank (option) 01

18 Valvola di intercettazione uscita (opzionale)Cut-off outlet valve (option) 01

19 Valvola a sfera 1/4” - Ball valve 1/4” 01

20 Armadio di protezione (opzionale)Protection Kiosk (option) 01

* Prevista solo da portate superiori a 300 kg/h Only for capacities over 300 Kg/h

1st and 2nd stage single and double line1° e 2° stadio singola e doppia linea

Vaporizing and regulating units on skidGruppi di vaporizzazione e riduzione su skid

Page 19: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 19

Vaporizing and regulating units on skid single and double line with EL-O vaporizers

Gruppi di vaporizzazione e riduzione su skidsingola e doppia linea con vaporizzatori EL-O

EL-O 1st and 2nd stage - 1° e 2° stadio

CapacityPortatakg/h

Lineslinee

Regulator1st stageRiduttore1° salto

Regulator2nd stageRiduttore2° salto

VaporizerVaporizzatore

Code/Codicewithout Upso & Opso

senza blocco

Code/Codicewith Upso & Opso

con blocco

KioskArmadio

50 1 IPR 75 DKR 70 EL-O 50 1GV130700 1GV130710 S / A 1000

50 2 IPR 75 DKR 70 EL-O 50 1GV130720 1GV130730 S / A 1000

100 1 IPR 75 IPR 75 EL-O 100 1GV130740 1GV130750 S / A 1000

100 2 IPR 150 IPR 150 EL-O 100 1GV130760 1GV130770 S / A 1000

150 1 IPR 150 IPR 150 EL-O 150 1GV130780 1GV130790 1600

150 2 IPR 150 IPR 150 EL-O 150 1GV130800 1GV130810 1800

200 1 IPR 150 IPR 150 EL-O 200 1GV130820 1GV130830 1600

200 2 IPR 150 IPR 150 EL-O 200 1GV130840 1GV130850 1800

300 2 IPR 150 IPR 150 EL-O 300 1GV130860 1GV130870 1800

350 2 IPR 150 IPR 300 EL-O 350 1GV130880 1GV130890 1800

400 2 IPR 300 IPR 300 EL-O 400 1GV130900 1GV130910 2002

500 2 IPR 300 IPR 600 EL-O 500 1GV130920 1GV130930 2002

EL-O 1st stage - 1° stadio

CapacityPortatakg/h

Lineslinee

RegulatorRiduttore

OutletTaratura

bar

VaporizerVaporizzatore

Code/Codicewithout Upso & Opso

senza blocco

Code/Codicewith Upso & Opso

con blocco

KioskArmadio

50 1 IPR 75 0,5 / 1 / 1,5 EL-O 50 1GV120250 1GV120260 K1000/A950

50 2 IPR 75 0,5 / 1 / 1,5 EL-O 50 1GV120270 1GV120280 S/A1000

100 1 IPR 75 0,5 / 1 / 1,5 EL-O 100 1GV120010 1GV120020 K1000/A950

100 2 IPR 75 0,5 / 1 / 1,5 EL-O 100 1GV120030 1GV120040 S/A1000

150 1 IPR 150 APA 0,5 / 1 / 1,5 EL-O 150 1GV120050 1GV120060 S/A1000

150 2 IPR 150 APA 0,5 / 1 / 1,5 EL-O 150 1GV120070 1GV120080 1600

200 1 IPR 150 APA 0,5 / 1 / 1,5 EL-O 200 1GV120090 1GV120100 S/A1000

200 2 IPR 150 APA 0,5 / 1 / 1,5 EL-O 200 1GV120110 1GV120120 1600

250 2 IPR 150 APA 0,5 / 1 / 1,5 EL-O 250 1GV120130 1GV120140 1600

300 2 IPR 150 APA 0,5 / 1 / 1,5 EL-O 300 1GV120150 1GV120160 1600

350 2 IPR 150 APA 0,5 / 1 EL-O 350 1GV120170 1GV120180 1800

350 2 IPR 300 DN40 APA 1,5 EL-O 350 1GV120190 1GV120200 1800

400 2 IPR 300 DN40 APA 0,5 / 1 / 1,5 EL-O 400 1GV120210 1GV120120 2002

500 2 IPR 300 DN40 APA 0,5 / 1 / 1,5 EL-O 500 1GV120230 1GV120240 2002

NOTES: On request capacity up to 1,000 kg/hFlows are guarantee with a minimum upstream pressure of 2 barAll units are always supplied with fl anged connection from tank gas phase.If it’s necessary the skid/kiosk dimension should be modify if any apparatus will be added on the unit (metering line, condensate trap, etc.)For skid dimension refer to page “Protection kiosk”

NOTE:Su richiesta portate fi no a 1.000 kg/h.Le portate sono garantite con una pressione minima a monte pari a 2 barTutti i gruppi sono provvisti di entrata fase gas da serbatoioLe dimensioni degli skid di supporto e degli armadi di protezione possono subire variazioni se vengono aggiunti al gruppo altri apparati (misura, barilotti etc.)Le dimensioni dello skid si possono ricavare dalla pagina “Armadi di protezione”

NOTES:On request capacity up to 1,000 kg/hFlows are guarantee with a minimum upstream pressure of 2 barVaporizing-reducing units are always supplied with fl anged connection from tank gas phase.2nd stage outlet pressure 35 mbarIf it’s necessary the skid/kiosk dimension should be modify if any apparatus will be added on the unit (metering line, condensate trap, etc.)For skid dimension refer to page “Protection kiosk”

NOTE:Su richiesta portate fi no a 1.000 kg/h.Le portate sono garantite con una pressione minima a monte pari a 2 barTutti i gruppi sono provvisti di entrata fase gas da serbatoioPressione di regolazione del 2° salto 35 mbarLe dimensioni degli skid di supporto e degli armadi di protezione possono subire variazioni se vengono aggiunti al gruppo altri apparati (misura, barilotti etc.)Le dimensioni dello skid si possono ricavare dalla pagina “Armadi di protezione”

Page 20: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

20 vaporization/vaporizzazione

Vaporizing and regulating units on skid single and double line with XC vaporizers

Gruppi di vaporizzazione e riduzione su skidsingola e doppia linea con vaporizzatori XC

NOTES: On request capacity up to 1,000 kg/h.Flows are guarantee with a minimum upstream pressure of 2 barVaporizing-reducing units are always supplied with fl anged connection from tank gas phase.If it’s necessary the skid/kiosk dimension should be modify if any apparatus will be added on the unit (metering line, condensate trap, etc.)For skid dimension refer to page “Protection kiosk”

NOTE:Su richiesta portate fi no a 1.000 kg/h.Le portate sono garantite con una pressione minima a monte pari a 2 barTutti i gruppi sono provvisti di entrata fase gas da serbatoioLe dimensioni degli skid di supporto e degli armadi di protezione possono subire variazioni se vengono aggiunti al gruppo altri apparati (misura, barilotti etc.)Le dimensioni dello skid si possono ricavare dalla pagina “Armadi di protezione”

XC 1st stage - 1° stadio

CapacityPortatakg/h

Lineslinee

RegulatorRiduttore

OutletTaratura

bar

VaporizerVaporizzatore

Code/Codicewithout Upso & Opso

senza blocco

Code/Codicewith Upso & Opso

con blocco

KioskArmadio

50 1 IPR 75 0,5 / 1 / 1,5 XC 50 1GV160250 1GV160260 S / A 1000

50 2 IPR 75 0,5 / 1 / 1,5 XC 50 1GV160270 1GV160280 S / A 1000

100 1 IPR 75 0,5 / 1 / 1,5 XC 100 1GV160010 1GV160020 S / A 1000

100 2 IPR 75 0,5 / 1 / 1,5 XC 100 1GV160030 1GV160040 S / A 1000

150 1 IPR 150 APA 0,5 / 1 / 1,5 XC 150 1GV160050 1GV160060 S / A 1000

150 2 IPR 150 APA 0,5 / 1 / 1,5 XC 150 1GV160070 1GV160080 1600

200 1 IPR 150 APA 0,5 / 1 / 1,5 XC 200 1GV160090 1GV160100 1200

200 2 IPR 150 APA 0,5 / 1 / 1,5 XC 200 1GV160110 1GV160120 1600

250 2 IPR 150 APA 0,5 / 1 / 1,5 XC 250 1GV160130 1GV160140 1600

300 2 IPR 150 APA 0,5 / 1 / 1,5 XC 300 1GV160150 1GV160160 1600

350 2 IPR 150 APA 0,5 / 1 XC 350 1GV160170 1GV160180 1600

350 2 IPR 300 DN40 APA 1,5 XC 350 1GV160190 1GV160200 1600

400 2 IPR 300 DN40 APA 0,5 / 1 / 1,5 XC 400 1GV160210 1GV160220 1602

500 2 IPR 300 DN40 APA 0,5 / 1 / 1,5 XC 500 1GV160230 1GV160240 1602

XC 1st and 2nd stage - 1° e 2° stadio

CapacityPortatakg/h

Lineslinee

Regulator1st stageRiduttore1° salto

Regulator2nd stageRiduttore2° salto

VaporizerVaporizzatore

Code/Codicewithout Upso & Opso

senza blocco

Code/Codicewith Upso & Opso

con blocco

KioskArmadio

50 1 IPR 75 DKR 70 XC 50 1GV130340 1GV130350 S / A 1000

50 2 IPR 75 DKR 70 XC 50 1GV130360 1GV130370 S / A 1000

100 1 IPR 75 DKR 70 XC 100 1GV130380 1GV130390 S / A 1000

100 2 IPR 75 DKR 70 XC 100 1GV130400 1GV130410 S / A 1000

150 1 IPR 75 IPR 75 XC 150 1GV130420 1GV130430 1600

150 2 IPR 75 IPR 75 XC 150 1GV130440 1GV130450 1800

200 1 IPR 150 IPR 150 XC 200 1GV130460 1GV130470 1600

200 2 IPR 150 IPR 150 XC 200 1GV130480 1GV130490 1800

300 2 IPR 150 IPR 150 XC 300 1GV130500 1GV130510 1800

350 2 IPR 150 IPR 300 XC 350 1GV130520 1GV130530 1800

400 2 IPR 300 IPR 300 XC 400 1GV130540 1GV130550 2002

500 2 IPR 300 IPR 600 XC 500 1GV130560 1GV130570 2002

NOTES:On request capacity up to 1,000 kg/hFlows are guarantee with a minimum upstream pressure of 2 barVaporizing-reducing units are always supplied with fl anged connection from tank gas phase.2nd stage outlet pressure 35 mbarIf it’s necessary the skid/kiosk dimension should be modify if any apparatus will be added on the unit (metering line, condensate trap, etc.)For skid dimension refer to page “Protection kiosk”

NOTE:Su richiesta portate fi no a 1.000 kg/h.Le portate sono garantite con una pressione minima a monte pari a 2 barTutti i gruppi sono provvisti di entrata fase gas da serbatoioPressione di regolazione del 2° salto 35 mbarLe dimensioni degli skid di supporto e degli armadi di protezione possono subire variazioni se vengono aggiunti al gruppo altri apparati (misura, barilotti etc.)Le dimensioni dello skid si possono ricavare dalla pagina “Armadi di protezione”

Page 21: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 21

WA-O 1st stage - 1° stadio

CapacityPortatakg/h

Lineslinee

RegulatorRiduttore

OutletTaratura

bar

VaporizerVaporizzatore

Code/Codicewithout Upso & Opso

senza blocco

Code/Codicewith Upso & Opso

con blocco

KioskArmadio

50 / 100 1 IPR 75 0,5 / 1 / 1,5 WA-O 100 1GV140280 1GV140290 K1000/A950

50 / 100 2 IPR 75 0,5 / 1 / 1,5 WA-O 100 1GV140300 1GV140310 S / A 1000

200 1 IPR 150 AP 0,5 / 1 / 1,5 WA-O 200 1GV140320 1GV140330 K1000/A950

200 2 IPR 150 AP 0,5 / 1 / 1,5 WA-O 200 1GV140040 1GV140050 S / A 1000

250 2 IPR 150 AP 0,5 / 1 / 1,5 WA-O 250 1GV140060 1GV140070 S / A 1000

300 2 IPR 150 AP 0,5 / 1 / 1,5 WA-O 300 1GV140080 1GV140090 1600

350 2 IPR 150 APA 0,5 / 1 WA-O 350 1GV140100 1GV140110 1600

350 2 IPR 300 DN40 APA 1,5 WA-O 350 1GV140340 1GV140350 1600

500 2 IPR 300 DN40 APA 0,5 / 1 / 1,5 WA-O 500 1GV140120 1GV140130 1602

600 2 IPR 300 DN40 APA 0,5 / 1 / 1,5 WA-O 600 1GV140140 1GV140150 1602

750 2 IPR 600 DN50 APA 0,5 / 1 / 1,5 WA-O 750 1GV140160 1GV140170 2000

1000 2 IPR 600 DN50 APA 0,5 / 1 / 1,5 WA-O 1000 1GV140520 1GV140530 2002

1500 2 IPR 600 DN50 APA 0,5 / 1 / 1,5 WA-O 1500 1GV140540 1GV140550 2002

2000 2 IPR 600 DN50 APA 0,5 / 1 WA-O 2000 1GV140560 1GV140580 2002

2000 2 RMI DN80 AP 1,5 WA-O 2000 1GV140590 1GV140600 2002

Vaporizing and regulating units on skid single and double line with WA-O vaporizers

Gruppi di vaporizzazione e riduzione su skidsingola e doppia linea con vaporizzatori WA-O

WA-O 1st and 2nd stage - 1° e 2° stadio

CapacityPortatakg/h

Lineslinee

Regulator1st stageRiduttore1° salto

Regulator2nd stageRiduttore2° salto

VaporizerVaporizzatore

Code/Codicewithout Upso & Opso

senza blocco

Code/Codicewith Upso & Opso

con blocco

KioskArmadio

50/100 1 IPR 75 DKR 70 WA-O 100 1GV130220 1GV130230 S/A 1000

50/100 2 IPR 75 DKR 70 WA-O 100 1GV130000 1GV130010 S/A 1000

150 1 IPR 75 IPR 75 WA-O 150 1GV130260 1GV130270 S/A 1000

150 2 IPR 75 IPR 75 WA-O 150 1GV130040 1GV130050 S/A 1000

200 1 IPR 150 IPR 150 WA-O 200 1GV130280 1GV130290 1600

200 2 IPR 150 IPR 150 WA-O 200 1GV130060 1GV130300 1600

300 2 IPR 150 IPR 150 WA-O 300 1GV130100 1GV130110 1800

500 2 IPR 300 IPR 300 WA-O 500 1GV130120 1GV130130 2002

600 2 IPR 300 IPR 600 WA-O 600 1GV130140 1GV130150 2002

750 2 IPR 600 IPR 600 WA-O 750 1GV130160 1GV130170 2802

1000 2 IPR 600 IPR 600 WA-O 1000 1GV130180 1GV130190 2802

1500 2 IPR 600 IPR 600 WA-O 1500 1GV130200 1GV130210 2802

2000 2 IPR 600 RMI 80 WA-O 2000 1GV130310 1GV130320 2802

NOTES: Flows are guarantee with a minimum upstream pressure of 2 barVaporizing-reducing units are always supplied with fl anged connection from tank gas phase.If it’s necessary the skid/kiosk dimension should be modify if any apparatus will be added on the unit (metering line, condensate trap, etc.)For skid dimension refer to page “Protection kiosk”

NOTE:Le portate sono garantite con una pressione minima a monte pari a 2 barTutti i gruppi sono provvisti di entrata fase gas da serbatoioLe dimensioni degli skid di supporto e degli armadi di protezione possono subire variazioni se vengono aggiunti al gruppo altri apparati (misura, barilotti etc.)Le dimensioni dello skid si possono ricavare dalla pagina “Armadi di protezione”

NOTES:Flows are guarantee with a minimum upstream pressure of 2 barVaporizing-reducing units are always supplied with fl anged connection from tank gas phase.2nd stage outlet pressure 35 mbarIf it’s necessary the skid/kiosk dimension should be modify if any apparatus will be added on the unit (metering line, condensate trap, etc.)For skid dimension refer to page “Protection kiosk”

NOTE:Le portate sono garantite con una pressione minima a monte pari a 2 barTutti i gruppi sono provvisti di entrata fase gas da serbatoioPressione di regolazione del 2° salto 35 mbarLe dimensioni degli skid di supporto e degli armadi di protezione possono subire variazioni se vengono aggiunti al gruppo altri apparati (misura, barilotti etc.)Le dimensioni dello skid si possono ricavare dalla pagina “Armadi di protezione”

Page 22: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

22 vaporization/vaporizzazione

DN da serbatoio

ND from tank

ND outlet

ND inlet

DN ingresso

PI

PI

DN uscita

PI

4 7

12

4 7

1015

11

Pos.DescrizioneDescription

QuantitàQty

4 Filtro a cartucciaFilter with decanter 02

7 Manometro differenzialeDifferential manometer 02

10 Valvola ad azionamento elettrico o pneumatico*Electrical or pneumatical actuated valve* 01

11 Valvola di intercettazione fase gas da serbatoioCut-off valve gas phase from tank 01

12 Valvola di intercettazione uscitaCut-off outlet valve 01

15 Armadio di protezioneProtection Kiosk 01

CapacityPortata

kg/h

OPTIONAL POSITIONS / POSIZIONI OPZIONALI

4(n° 2 pz/pcs)

7(n° 2 pz/pcs)

10*PneumaticPneumatica

10*ElectrovalveElettrovalvola

11 12

50/100 KFL102525 KMN762002 KVA122516 KEL325288 KVS0125401 KVS140401

150 KFL102525 KMN762002 KVA122516 KEL325288 KVS0125401 KVS140401

200/250 KFL102525 KMN762002 KVA122516 KEL325288 KVS0125401 KVL115011

300 KFL102525 KMN762002 KVA123216 KEL332288 KVS0132401 KVL115011

350 KFL192532 KMN762002 KVA124016 KEL340288 KVS0132401 KVL116511

400/500 KFL192540 KMN762002 KVA124016 KEL340288 KVS0140401 KVL118011

600/700 KFL192540 KMN762002 KVA124016 KEL340288 KVS0140401 KVL118011

750/800 KFL192550 KMN762002 KVA125016 KEL350288 KVS0140501 KVL118511

900/1000 KFL192550 KMN762002 KVA125016 KEL350288 KVS0140501 KVL118511

1500 KFL192550 KMN762002 KVA125016 KEL350288 KVS0140501 KVL118711

2000 KFL192580 KMN762002 KVA125016 KEL350288 KVS0140501 KVL118911

Options for vaporizing-regulating units1st stage

Gruppi di vaporizzazione e riduzione su skid1° salto

NOTES:* KVA code: Ball valve - Pneumatic actuator - Fittings and gaskets -

Assembly KEL code: EEx-d N.C. electrovalve

NOTE:* Codice KVA: Valvola a sfera - Attuatore pneumatico - Viteria e guarnizioni -

Montaggio Codice KEL: elettrovalvola EEx-d N.C.

Page 23: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 23

Pos.DescrizioneDescription

QuantitàQty

4 Filtro a cartucciaFilter with decanter 02

7 Valvola di sfi oro esterna 1° salto con valvola a sferaExternal relief valve for 1st stage with ball valve 02

12 Valvola di sfi oro esterna 2° salto con valvola a sferaCut-off outlet valve 01

14 Valvola ad azionamento elettrico o pneumatico*Electrical or pneumatical actuated valve* 01

15 Manometro differenzialeDifferential manometer 01

17 Valvola di intercettazione fase gas da serbatoioCut-off inlet valve from tank 01

18 Valvola di intercettazione uscitaCut-off outlet valve 01

20 Armadio di protezioneProtection Kiosk 01

CapacityPortata

kg/h

OPTIONAL POSITIONS / POSIZIONI OPZIONALI

414*

PneumaticPneumatica

14*ElectrovalveElettrovalvola

15 17 18

50/100 KFL102525 KVA122516 KEL325288 KMN762002 KVS0125401 KVS140401

150 KFL102525 KVA122516 KEL325288 KMN762002 KVS0125401 KVS140401

200/250 KFL102525 KVA122516 KEL325288 KMN762002 KVS0125401 KVL115011

300 KFL102525 KVA123216 KEL332288 KMN762002 KVS0132401 KVL115011

350 KFL192532 KVA124016 KEL340288 KMN762002 KVS0132401 KVL116511

400/500 KFL192540 KVA124016 KEL340288 KMN762002 KVS0140401 KVL118011

600/700 KFL192540 KVA124016 KEL340288 KMN762002 KVS0140401 KVL118011

750/800 KFL192550 KVA125016 KEL350288 KMN762002 KVS0140501 KVL118511

900/1000 KFL192550 KVA125016 KEL350288 KMN762002 KVS0140501 KVL118511

1500 KFL192550 KVA125016 KEL350288 KMN762002 KVS0140501 KVL118711

2000 KFL192580 KVA125016 KEL350288 KMN762002 KVS0140501 KVL118911

Options for vaporizing-regulating units1st and 2nd stage

Gruppi di vaporizzazione e riduzione su skid1° e 2° salto

NOTES:* KVA code: Ball valve - Pneumatic actuator - Fittings and gaskets -

Assembly KEL code: EEx-d N.C. electrovalve

NOTE:* Codice KVA: Valvola a sfera - Attuatore pneumatico - Viteria e guarnizioni -

Montaggio Codice KEL: elettrovalvola EEx-d N.C.

Page 24: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

24 vaporization/vaporizzazione

Perché le centrali termiche Samtech sono sempre più apprezzate?

Ecco i principali vantaggi:• No opere murarie: l’impianto viene fornito con un armadio

metallico, non sono necessarie pratiche per licenze edilizie = meno costi per opere civili e per permessi autorizzativi

• Unico ordine per caldaia, pompe, quadro elettrico, canna fumaria: meno ordini, più potere contrattuale con il fornitore = meno costi, più tempo per fare altre cose

• Integrazione della logica di funzionamento con gli strumenti del vaporizzatore: i quadri elettrici delle centrali Samtech sono già predisposti per la gestione degli strumenti del vaporizzatore (elettrovalvola, termostato, interruttori livello) = meno costi per gestire la logica dell’impianto

• Progettazione e dimensionamento fatta da esperti termotecnici: prestazioni e funzionamento garantito = meno costi di progettazione e/o consulenze e meno costi per gestire problemi connessi ad errate valutazioni tecniche dell’impianto

• Assemblaggio e collaudo dell’unità fatta da tecnici esperti: migliore qualità nell’esecuzione dell’insieme, meno imprevisti al momento dell’avviamento = minori costi di personale qualificato e per imprevisti all’avviamento

• Rapidità di installazione: in pochissimo tempo si è in grado di mettere in esercizio l’impianto = meno costi di installazione in loco

• Conservazione del valore dell’investimento nel tempo: l’unità essendo trasportabile consente di recuperare l’impianto e utilizzarlo presso un altro cliente = migliore ammortamento del bene, recupero e risparmio costi in caso di riutilizzo

• Politiche commerciali più incisive sul cliente: la precisa identificazione dell’impianto e la possibilità di riprendere il bene concesso in comodato in tempi molto rapidi, funge da deterrente nei confronti del cliente-consumatore = maggiore potere contrattuale e minore volatilità nei confronti della clientela, costi di recupero molto contenuti

• Garanzia della qualità del prodotto e dei processi costruttivi: Samtech opera in regime di gestione, progettazione e produzione secondo ISO 9001 = meno costi dovuti ad imprevisti e scarsa qualità

• Certezza dell’utilizzo di materiali e componenti di qualità: l’esperienza Samtech nella costruzione di oltre 150 unità garantisce l’uso di componenti e materiali testati nella loro qualità ed affidabilità = meno costi per sostituzioni e manutenzione

• Unico interlocutore per riparazioni e ricambi di vaporizzatore, regolatori e centrale termica: l’accorpamento di ordini per riparazioni e ricambi consente di avere più potere contrattuale nei confronti del fornitore = minori costi di gestione

• Costi certi e conosciuti, fissi ed invariabili di tutto l’insieme fino allo start-up dell’impianto: un unico prezzo per tutta la fornitura dell’insieme = budget di spesa certo, verificabile senza extra costi

• Servizio di supporto tecnico pre-post vendita: per i clienti delle unità l’ufficio tecnico Samtech è a disposizione per supportare il cliente nella scelta e per assistere telefonicamente nel post-vendita = meno costi per individuare la soluzione tecnica,e per risolvere i problemi

• I vantaggi si moltiplicano se la centrale è ordinata insieme ad un gruppo di vaporizzazione

• Fornitura gratuita dei documenti per denuncia Ispesl e prevenzione incendi (solo per mercato italiano): minore uso di consulenti esterni = meno costi imputabili all’impianto

Why are Samtech thermal units increasingly appreciated?

These are main advantages:

• No building works: the plant is supplied with a metallic kiosk, no needs authorizations for building permits = less costs for civil work and authorization permits

• One order for thermal unit, pumps, control panel, chimney fl ue: less order, more contractual power with supplier = less costs, more time for yourself

• Integration logical operation: with vaporizer’s options: Samtech thermal unit’s control panel already suitable for vaporizer’s options management (normally closed electrovalve, thermostat, level switch) = less costs for managing logical operation

• Designed by our thermo-technical experts: performances and working guarantee = less design costs and/or consulting and less costs for troubleshooting

• Assembling and testing guarantee by our technical experts: better quality for the whole performance, less inconvenience during start up= lower costs for skilled personnel and for unexpected trouble during start up

• Fast installation: in a very short time the plant can be started up = less costs of installation in loco

• Save the investment value during the time: due to unit’s portability is allowed recover the plant and reuse near other client

• More incisive commercial policy to clients: the right identifi cation of the plant and the possibility to recover the material allowed in commodate in a faster time, function as deterrent towards clients – consumer = more contractual power and less volatility towards clients, recovered costs held down

• Quality of Samtech products and building process guarantee: Samtech works under managing design and production system, in according with ISO 9001 = less costs due to inconvenience and scanty quality

• Certainty used material and element of best quality: Samtech experience assured by building over 150 units guarantee elements and material tested quality and reliability = less costs for substitutions and maintenance

• Sole interlocutor for repairs and spare parts of vaporizers and regulators: the unifi cation of orders for repairs and spare parts allow more contractual power towards supplier = less managing costs

• Certain and known costs, fi xed and invariable: all together up to start up of the plant; one price for the whole supply = clear budget, verifi able without extra-costs

• Customer service pre-post sale: for Samtech clients our technical department is at disposal for support the best solution and assistance = less costs for solve issues with a technical solution

• Advantages increase if unit is ordered with a vaporizing and regulating unit

Hot water units on skidCentrali termiche su skid

Page 25: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 25

Hot water units on skidCentrali termiche su skid

Hot water unit with kioskCentrale termica con armadio

1000 x 1000 x h1700 mm

Hot water unit of 37,000 kcal/h

Centrale termica da 37.000 kcal/h

Hot water unit 120,000 / 250,000 kcal/h with doors on 3 sides

Centrale termica 120.000 / 250.000 kcal/h con porte su 3 lati

Hot water unit with 3 burners for a total power of 750.000 kcal/h

Centrale termica con 3 caldaie per una potenza tot.di 750.000 kcal/h

Hot water unit of 500.000 kcal/h

Centrale termica da 500.000 kcal/h

Hot water unit with 3 burners for a total power of 270.000 kcal/h

Centrale termica con 3 caldaie per una potenza tot.di 270.000 kcal/h

Page 26: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

26 vaporization/vaporizzazione

Centrali termiche su skidHot water units on skid

Caratteristiche tecniche standard

• Caldaie a basamento, corpo in ghisa• Tiraggio naturale, camera aperta• Facile ed economica manutenzione• Lunga durata nel tempo• Basso costo di gestione nel tempo • Ideale per impianti non presidiati: gestione elettromeccanica

semplice ed affi dabile• No schede/gestioni elettroniche: componenti facilmente reperibili

sul mercato• Bruciatore ad alto rendimento in acciaio inox • Portata termica variabile con funzionamento bistadio (sopra 51

kW)• Canna fumaria in acciaio inox• Pompe primaria e di ricircolo• Vaso di espansione• Riduttore di pressione acqua• Regolatore di pressione gas e fi ltro• Contatore gas a membrana per totalizzazione consumi• Quadro elettrico IP 55 completo delle funzioni di gestione del

vaporizzatore• Pulsante di emergenza installato all’esterno dell’armadio• Armadio in alluminio

Opzioni• Armadio in acciaio inox• Pompa manuale carico acqua• Trasduttori Eex per la gestione remota dei segnali di temperatura

e pressione• Piantana per installazione quadro in zona remota • Coibentazione armadio• Valvola di blocco su regolatore gas• Termostato min. temperatura su ritorno acqua da vaporizzatore• Flussostato• Orologio programmatore• Sistemi di telecontrollo a distanza via gsm

TYPETIPO

Power CodeCodiceKcal kW

Rendimax N 23 EL PV 20.000 23 LCV812000

Rendimax N 30 EL PV 26.000 30 LCV812700

Domus 31 ICN 37.000 33 LCV813700

Pegasus F2 N 51 44.000 51 LCV814500

Pegasus F2 N 68 59.000 68 LCV816000

Pegasus F2 N 85 73.000 85 LCV817000

Pegasus F2 N 102 88.000 102 LCV819000

Pegasus F3 N 136 118.000 136 LCV81120X

Pegasus F3 N 170 147.000 170 LCV81150X

Pegasus F3 N 221 191.000 221 LCV81190X

Pegasus F3 N 289 250.000 289 LCV81250X

Technical features

• Floor standing, cast-iron body• Natural draught, open chamber• Simple and economic maintenance• Long life• Low operating costs • Rational construction, highlighting the simplicity of installation

and maintenance operations• Without the easy-breakable electronic cards: all the components

are easily available on the market• High effi ciency burner in stainless steel• Variable thermal power with double stage working (over 51 kW)• Chimney fl ue in stainless steel• Primary and re-circulating pumps• Expansion tank• Water pressure regulator• Gas pressure regulator with strainer• Diaphragm gas meter for total consumption• Electrical control panel IP55 presetted to manage also all the

options for vaporizers• External emergency button• Aluminium protection kiosk

Options• Stainless steel protection kiosk• Manual pump for water loading• Eex transducers for remote reading of temperature and pressure

signals• Pedestal for control panel• Thermostat for minimum temperature to be installed on the water

line from vaporizer• Flow switch• Programmable clock• Systems for remote GSM control

Page 27: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

vaporization/vaporizzazione 27

Armadi di protezioneProtection kiosk

CODECODICE

EXTERNAL DIM. mmDIMENSIONI ESTERNE mm

DOORSPORTE

h l pACG507070 K 700 1100 700 500 2

ACG507080 K 800 1100 800 500 2

ACG507100 K1000 1700 1000 600 2+2

ACG507120 K1200 1700 1200 700 2+2

ACG508060 S1000 1700 1000 1000 2+2

ACG507140 K1400 1700 1400 800 2+2

ACG507160 K1600 1700 1600 800 2+2

ACG507170 K1602 2100 1600 800 2+2

ACG507180 K1800 1700 1800 900 2+2

ACG507200 K2000 2000 2000 1000 2+2

ACG507220 K2002 2100 2000 1000 2+2

ACG507240 K2400 2000 2400 1200 3+3

ACG507280 K2800 2000 2800 1200 4+4

ACG507290 K2802 2100 2800 1200 4+4

ACG507300 K3000 2300 3000 1500 4+4

ACG578080 A 800 1100 800 500 1

ACG578100 A 950 1700 1000 600 2+2

ACG578060 A1000 1700 1000 1000 2+2

ACG578120 A1200 1700 1200 700 2+2

ACG578140 A1400 1700 1400 800 2+2

ACG578141 A1401 2000 1400 1000 2+2

ACG578160 A1600 1700 1600 800 2+2

ACG578162 A1602 2100 1600 800 2+2

ACG578180 A1800 1700 1800 900 2+2

ACG578190 A1801 2000 1800 900 2+2

ACG578191 A1802 2000 1800 1200 2+2

ACG578195 A2000 2000 2000 1000 2+2

ACG578196 A2002 2100 2000 1000 2+2

ACG578220 A2001 2000 2000 1200 2+2

ACG578240 A2400 2000 2400 1200 3+3

ACG578280 A2800 2000 2800 1200 4+4

ACG578282 A2802 2100 2800 1200 4+4

ACG578300 A3000 2300 3000 1500 4+4

ACG900001 Kiosk assembly on skid - Montaggio armadio su skid

ACG900101 1 added door for blind side - 1 porta aggiunta per lato cieco

TIPO/TYPE:K / S: acciaio inox / stainless steel A: alluminio / aluminium

Tipo ad 1 porta1 door type

Esecuzioni specialiSpecial executions

Tipo a 2 porte2 doors type

TECHNICAL FEATURES- Stainless steel (K): plate fi nishing 2/B thickness 10/10

FIRST RATE- Aluminium (A): alloy thickness 20/10 corrosion-

resistant- Abat-vents with fl ame retardant stainless steel- Aeration on 1/10 of the surface- Doorstop on each door- Keylock with hidden handles- Manufactured according D.M. 24/11/1984 and

according applicable safety rules- Doors on two sideson request:- Out of standard dimensions- Other materials (painted steel plate, copper, ecc..)- Concrete versions- Special coverings- Acoustic and thermal insulation

CARATTERISTICHE TECNICHE- Acciaio inox (K): lamiera fi nitura 2/B spessore 10/10

prima scelta- Alluminio (A): lega sp.20/10 resistente alla corrosione- Feritoie con rete antifi amma in acciaio inox- Aerazione 1/10 della superfi cie in pianta- Ferma porte ad ogni porta- Serrature con maniglie a scomparsa- Realizzati in accordo al D.M. del 24/11/1984 e alle

vigenti disposizioni- Porte disposte su due latisu richiesta:- Dimensioni fuori standard- Altri materiali (lamiera verniciata, rame, ecc..)- Versioni in calcestruzzo- Rivestimenti speciali- Insonorizzazione / coibentazione

Page 28: LPG vaporizing solutions - Equipgas · 2013-02-06 · Lpg feed-out vaporizers Samvap EL-O and XC hot water with electric heating elements Vaporizzatori gpl feed-out Samvap EL-O e

Your best partner in gas systems.

Samtech s.r.l.Via dell’Industria, 1635030 Cervarese Santa Croce (PD) - ItalyTel. +39 049 9903931 - Fax +39 049 [email protected]

www.samtechgas.com Sta

mp

ato

012

/060

7C

reat

ive

Stu

dio

srl

- Ve

ggia

no (P

D)