LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK...

42
LOWER WONGA SOLAR FARM Development Application for a Material Change of Use- Noise Impact Assessment || April 2017

Transcript of LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK...

Page 1: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

LOWER WONGA SOLAR FARM Development Application for a Material Change of Use- Noise Impact Assessment || April 2017

Page 2: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

           

ASK Consulting Engineers Pty Ltd 

ABN: 55 622 586 522 ACN: 128 491 967 PO Box 3901 South Brisbane QLD 4101 

P: 07 3255 3355   F: 07 3844 7180 www.askconsulting.com.au [email protected] 

  

Lower Wonga Solar Farm 

Lower Wonga, Queensland 

Noise Impact Assessment  

Report: 8796R01V01.docx 

Prepared for: 

Bordstrong Developments Pty Ltd 

 

27 March, 2017 

 

    

     

     

Page 3: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  2

Document Control 

W:\8700\8796\ASK Out\8796R01V01.docx 

Document Ref  Date of Issue  Status  Author  Reviewer 

8796R01V01  27 March, 2017  Final  SP  SL 

         

         

         

 

Document Approval 

Author Signature 

 

Approver Signature 

 

Name  Stephen Pugh  Name  Stephen Pugh 

Title  Director  Title  Director 

 

Disclaimer: This document and associated tasks were undertaken  in accordance with  the ASK Consulting Engineers Quality  Assurance  System, which  is  based  on  Australian  Standard  / NZS  ISO  9001:2008.  This  document  is  issued subject to review, and authorisation by a Senior Consultant noted in the above table. If the table is incomplete, this document  shall be  considered  as preliminary or draft only  and no  reliance  shall be placed upon  it other  than  for information to be verified later. 

This document is prepared for our Client's particular requirements which are based on a specific brief with limitations as agreed to with the Client. It is not intended for and should not be relied upon by a third party and no responsibility is undertaken to any third party without prior consent provided by ASK Consulting Engineers. The information herein should not be reproduced, presented or reviewed except  in full. Prior to passing on to a third party, the Client  is to fully inform the third party of the specific brief and limitations associated with the commission. 

The information contained herein is for the identified purpose of acoustics only. No claims are made and no liability is accepted  in  respect of design and construction  issues  falling outside of  the specialist  field of acoustics engineering including  and  not  limited  to  structural  integrity,  fire  rating,  architectural  buildability  and  fit‐for‐purpose, waterproofing, safety design and  the  like. Supplementary professional advice should be sought  in  respect of  these issues.  

Copyright: This report and the copyright thereof are the property of ASK Consulting Engineers Pty Ltd  (ABN 55 622 586 522).  It must not be copied  in whole or  in part without the written permission of ASK Consulting Engineers Pty Ltd. This report has been produced specifically for the Client and project nominated herein and must not be used or retained for any other purpose. www.askconsulting.com.au    

Page 4: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  3

Contents 

1.  Introduction  5 

2.  Study Area Description  6 

3.  Proposed Development  9 

4.  Acoustic Criteria  11 

4.1  Gympie Regional Council  11 

4.2  Environmental Protection Act  11 

4.3  Environmental Protection (Noise) Policy  11 

4.3.1  Overview  11 

4.3.2  Background Creep  11 

4.3.3  Acoustic Quality Objectives  11 

4.4  EcoAccess Guidelines  12 

4.4.1  EcoAccess – Planning for Noise Control  12 

4.4.2  Control and Prevention of Background Creep  12 

4.4.3  Sleep Disturbance Criteria  12 

4.4.4  EcoAccess – Assessment of Low Frequency Noise  13 

5.  Acoustic Measurements  15 

5.1  Overview  15 

5.2  Attended Noise Measurements  16 

5.3  Noise Logging  17 

6.  Construction Noise Assessment  19 

6.1  Overview  19 

6.2  General Recommendations  19 

7.  Operational Noise Assessment  21 

7.1  Noise Limits  21 

7.2  Inverter and Transformer Noise  21 

7.2.1  Overview  21 

7.2.2  Source Noise Data  21 

7.2.3  Modelling and Results  22 

7.2.4  Noise Assessment and Mitigation  24 

7.3  Substation Noise  25 

7.4  Other Noises  26 

8.  Recommendations & Conclusion  27 

Page 5: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  4

Appendices 

Appendix A  Glossary  28 

Appendix B  Project Drawings  29 

Appendix C  Noise Logging Results  30 

Appendix D  Noise Level Contours  35 

Page 6: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  5

1. Introduction 

ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty Ltd to provide acoustic  consultancy  services  for  the proposed  Lower Wonga  solar  farm being  constructed adjacent  the Woolooga substation, located near the intersection of the Wide Bay Highway and Gympie Woolooga Road.   

This  acoustic  report  is  to  accompany  a  Development  Application  for  consideration  by  Department  of Environment  and  Heritage  Protection.   The  application  is  made  over  land  in  the  Lower  Wonga  area bounded by the Wide Bay Highway, Gympie‐Woolooga Road and Phillip Road. The area encompasses the following lots / Plans. 

Lot 235 on LX2129 

Lots 236, 237, 243, 244 on LX496 

Lots 1, 2, 3 on RP183439  

The proposed development includes the construction and operation of a 350 Megawatt (MW) photovoltaic (PV)  solar  plant.  The  land  area  of  574  ha,  will  have  up  to  240  ha  of  PV  panel  coverage.  The  site  in operational  mode  will  accommodate  buildings,  access  roadways,  parking  area  and  lay  downs  and vegetative screening between the site and the public roads. The total operational land coverage will be up to 300ha. 

The purpose of this report is as follows: 

Outline the relevant project noise criteria. 

Present the results of noise monitoring. 

Predict and assess the noise emissions from the development. 

Describe noise mitigation requirements. 

To aid in the understanding of the terms in this report a glossary is included in Appendix A. 

 

 

 

Page 7: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  6

2. Study Area Description 

The proposed development is to be located at the corner of the Wide Bay Highway and Gympie‐Woolooga Road.    The  site  is  approximately  23  kilometres  north‐west  of  Gympie  and  7  kilometres  south‐east  of Woolooga.   The  site  location,  inclusive of  the existing  substation,  is  shown  in  Figure 2.1  and  Figure 2.2 (source: State of Queensland Aerial Photography). 

 

Figure 2.1 Site Location 

3km 

Subject Site 

Town of Woolooga 

Woolooga Substation 

Page 8: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  7

The site adjoins the Woolooga Substation as well as cleared grazing land and rural residences. 

The proposed development is surrounded by rural residential premises to the north, south, east and west. 

The nearest potentially affected sensitive receivers are  identified  in Figure 2.2 with  locations provided  in Table 2.1 (Source: Client). 

 

Figure 2.2  Site Location and Nearest Sensitive Receivers (Houses 1 to 23) 

   

1km 

Subject Site 

Woolooga Substation 

Page 9: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  8

Table 2.1  Nearest Sensitive Receiver Locations 

Receptor (House ID) 

 

Address and/or Lot Number 

 

Coordinates (Universal Transverse Mercator, 56J) 

Easting  Northing 

House 1  Gympie‐Woolooga Road  443177.93 m E  7114090.98 m S 

House 2  Gympie‐Woolooga Road  443390.79 m E  7113879.36 m S 

House 3  Phillip Road  444267.69 m E  7111970.92 m S 

House 4  Wide Bay Highway  446865.81 m E  7114282.16 m S 

House 5  Wide Bay Highway  446762.31 m E  7113890.28 m S 

House 6  Phillip Road  446649.86 m E  7112620.74 m S 

House 7  Hayes Road  446829.24 m E  7114887.36 m S 

House 8  Hayes Road  446416.66 m E  7114678.06 m S 

House 9  Phillip Road  445154.29 m E  7111514.39 m S 

House 10  Via Wide Bay Highway  443312.29 m E  7116225.30 m S 

House 11  Via Wide Bay Highway  444420.64 m E  7115985.45 m S 

House 12  Wide Bay Highway  443511.31 m E  7115525.67 m S 

House 13  Wide Bay Highway  444069.14 m E  7114818.55 m S 

House 14  Hayes Road  446572.71 m E  7115451.40 m S 

House 15  Hayes Road  446509.51 m E  7115884.77 m S 

House 16  Hayes Road  445933.69 m E  7116660.13 m S 

House 17  Hayes Road  446702.65 m E  7116156.72 m S 

House 18  Wide Bay Highway  442329.89 m E  7115693.44 m S 

House 19  Wide Bay Highway  442734.99 m E  7114794.55 m S 

House 20  Phillip Road  445753.98 m E  7111752.74 m S 

House 21  Gympie‐Woolooga Road  443119.60 m E  7110815.84 m S 

House 22  Tones Road  441031.33 m E  7111740.99 m S 

House 23  Gympie‐Woolooga Road  443764.88 m E  7111529.26 m S 

 

Page 10: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  9

3. Proposed Development 

The proposed development includes the construction and operation of a 350 Megawatt (MW) photovoltaic (PV) solar plant, including: 

Arrays of solar modules and cabling. 

Inverter transformers. 

Internal maintenance roads and tracks. 

Underground and overhead high voltage conductors. 

High voltage substation. 

Site based energy storage location and lay down area. 

Operations and administration building. 

Maintenance and storage building.  

Road access. 

The project drawings are included in Appendix B. An overview of the site layout is included in Figure 3.1.  In Figure 3.1 the solar arrays are shown as blue areas, and the substation and transmission line corridors are shown as pink areas. 

 

Figure 3.1  Proposed Site Layout 

Potential noise impacts associated with the development include: 

Noise and vibration associated with the construction phase of the project. This  includes noise from construction equipment operating on site. 

Woolooga Substation 

Page 11: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  10

Operational noise associated with normal  running of  the  solar plant. This  includes noise  from  the electrical systems (e.g. substation, inverters) and any maintenance work undertaken on site. 

These potential impacts are required to be considered in the project design. 

 

Page 12: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  11

4. Acoustic Criteria 

4.1 Gympie Regional Council 

The site  is  located within the Gympie Regional Council area and therefore  is required to comply with the requirements of the Gympie Regional Council Planning Scheme. The policy does not specify noise limits but references  the  Department  of  Environment  and  Heritage  Protection  (EHP)  –  Environmental  Protection Policy (Noise) and Environmental Protection Act to achieve nuisance code outcomes. 

4.2 Environmental Protection Act 

In Queensland, the environment is protected under the Environmental Protection Act 1994.  The object of the Act  is  to protect Queensland’s environment while allowing  for development  that  improves  the  total quality of  life, both now and  in the future,  in a way that maintains the ecological processes on which  life depends (ecologically sustainable development).   

4.3 Environmental Protection (Noise) Policy 

4.3.1 Overview 

In respect of the acoustic environment, the object of the Act  is achieved by the Environmental Protection (Noise) Policy 2008 (EPP (Noise)). This policy identifies environmental values to be enhanced or protected, states  acoustic  quality  objectives,  and  provides  a  framework  for making  decisions  about  the  acoustic environment.  

4.3.2 Background Creep 

The EPP(Noise) contains noise criteria  for controlling background creep, which are  to be applied “for an activity involving noise”.  The criteria are as follows: 

To the extent that it is reasonable to do so, noise from an activity must not be— 

(a) for noise  that  is continuous noise measured by LA90,T—more  than nil dBA greater  than  the existing acoustic environment measured by LA90,T; or 

(b) for  noise  that  varies  over  time measured  by  LAeq,adj,T—more  than  5dBA  greater  than  the  existing acoustic environment measured by LA90,T. 

The EPP(Noise) does not define  “continuous noise”, but by definition,  the  “continuous noise” would be required to occur for at least 90% of a measurement period (typically 15 minutes or 60 minutes). Thus this criterion could apply for equipment such as mechanical plant. 

The criterion for “noise that varies over time” is appropriate for noise sources operating for less than 90% of a measurement period, and could apply to  intermittent events  (e.g. vehicles) or mechanical plant that does not run continuously (e.g. air‐conditioning).  

4.3.3 Acoustic Quality Objectives 

The EPP (Noise) contains a range of acoustic quality objectives for a range of receptors.  The objectives are in the form of noise  levels, and are defined for various periods of the day, and use a number of acoustic parameters. 

Schedule  1 of  the  EPP(Noise)  includes  the  following  acoustic quality objectives  to be met  at  residential dwellings: 

Page 13: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  12

Outdoors 

○ Daytime and Evening: 50 dBA LAeq,adj,1hr, 55 dBA LA10,adj,1hr and 65 dBA LA1,adj,1hr 

Indoors 

○ Daytime and Evening: 35 dBA LAeq,adj,1hr, 40 dBA LA10,adj,1hr and 45 dBA LA1,adj,1hr 

○ Night: 30 dBA LAeq,adj,1hr, 35 dBA LA10,adj,1hr and 40 dBA LA1,adj,1hr 

In the DEHP EcoAccess Guideline “Planning For Noise Control” documentation it is proposed that the noise reduction provided by a typical residential building façade  is 7 dBA assuming open windows. That  is, with an  external  noise  source,  a  7  dBA  reduction  in  noise  levels  from  outside  a  house  to  inside  a  house  is expected when windows are fully open. Thus the indoor noise objectives noted above could be converted to the following external objectives (with windows open): 

Daytime and Evening: 42 dBA LAeq,adj,1hr, 47 dBA LA10,adj,1hr and 52 dBA LA1,adj,1hr 

Night: 37 dBA LAeq,adj,1hr, 42 dBA LA10,adj,1hr and 47 dBA LA1,adj,1hr 

A sensitive receptor is defined as “an area or place where noise is measured”. 

The EPP(Noise)  states  that  the objectives are  intended  to be progressively achieved over  the  long  term. However, as this project involves the introduction of new noise sources it would seem reasonable that the acoustic quality objectives are achieved upon commencement of operation of the project, and this may be the  intent  of  the  policy.  Therefore,  consideration  to  achieving  these  acoustic  quality  objectives will  be included in the design noise limits for the project. 

The acoustic quality objectives do not take into consideration the existing noise environment and therefore may not be applicable for areas that are particularly quiet or particularly noisy (e.g. near a road). Therefore, it  is  considered  that  the objectives  should not be used  as  the  sole noise  limits  for  a development,  and reference  should also be made  to noise  limits which are determined with  consideration  for  the existing noise environment. 

4.4 EcoAccess Guidelines 

DEHP has a number of EcoAccess guidelines relevant to the assessment of noise and vibration.  These are summarised as follows. 

4.4.1 EcoAccess – Planning for Noise Control 

DEHP  EcoAccess  Guideline  “Planning  For  Noise  Control”  contains  procedures  and  methods  that  are applicable for setting conditions relating to noise emitted from  industrial premises for planning purposes. The guideline  is applicable to noise from all sources,  individually and  in combination, which contribute to the total noise from a site. 

4.4.2 Control and Prevention of Background Creep 

The procedure  takes  into  account  three  factors:  firstly,  the  control  and prevention of background noise creep  in  the  case of  a  steady noise  level  from equipment  such  as  caused by  ventilation  fans  and other continuously operating machinery; secondly, the containment of variable noise levels and short‐term noise events  such  as  those  caused  by  forklifts  and  isolated  hand  tools  to  an  acceptable  level  above  the background  noise  level;  thirdly,  the  setting  of  noise  limits  that  should  not  be  exceeded  to  avoid  sleep disturbance.  

4.4.3 Sleep Disturbance Criteria 

The World Health Organization (WHO) issued its “Guidelines for Community Noise” in April 1999. The WHO guideline states the following in regard to sleep disturbance from continuous noise from activities such as mining operations:  

Page 14: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  13

“Where noise is continuous, the equivalent sound pressure level should not exceed 30 dBA indoors, if negative effects on  sleep are  to be avoided. When noise  is composed of a  large proportion of low‐frequency sounds a still  lower guideline value  is recommended, because  low‐frequency noise (eg from a ventilation system) can disturb rest and sleep even at low sound pressure levels.”  

The  EcoAccess  Guideline  “Planning  for  Noise  Control”,  in  referring  to  the  World  Health  Organisation guidelines, makes the following general recommendation regarding short term transient noise events: 

“As a rule in planning for short‐term or transient noise events, for good sleep over eight hours, the indoor  sound  pressure  level measured  as  a maximum  instantaneous  value  should  not  exceed approximately 45 dBA maxLpA more than 10 to 15 times per night.” 

For less regular night events, the allowable internal noise level is higher, as follows: 

Approximately 3 events per night:  50 dBA Lmax. 

Approximately 1 event per night:  65 dBA Lmax. 

Note:  For the purpose of this assessment the maxLpA level is defined using the Lmax descriptor. 

The WHO guideline states the following in regard to annoyance response to community noise: 

“Annoyance  to community noise varies with  the  type of activity producing  the noise. During  the daytime  few  people  are  seriously  annoyed  by  activities  with  LAeq  levels  below  55  dBA;  or moderately annoyed by  LAeq  levels below 50 dBA.  Sound pressure  levels during  the evening and night  should  be  5  –  10  dBA  lower  than  during  the  day. Noise with  low  frequency  components requires even lower levels.”    

DEHP propose that the noise reduction provided by a typical residential building façade is 7 dBA assuming open windows.    Thus  the  indoor  noise  objectives  noted  above  could  be  considered  external  objectives (with windows open) with the appropriate correction. 

The criteria are summarised in Table 4.1 Summary of WHO Sleep Disturbance and Annoyance Criteria. 

Table 4.1 Summary of WHO Sleep Disturbance and Annoyance Criteria 

Descriptor  Number of Noise Events 

Indoor Criterion dBA 

Outdoor Criterion dBA 

Sleep Disturbance  

(Short Duration Events) 

10 – 15  Lmax 45  Lmax 52 

3  Lmax 50  Lmax 57 

1  Lmax 55  Lmax 62 

Sleep Disturbance (Continuous Noise)  Continuous  Leq 30  Leq 37 

Annoyance (Night Time)  Continuous  Leq 35  Leq 42 

Note:  The outdoor criteria are based on a DEHP EcoAccess nominated outdoor‐to‐indoor noise reduction of 7 dBA for open windows.  

4.4.4 EcoAccess – Assessment of Low Frequency Noise 

DEHP EcoAccess Guideline “Assessment of Low Frequency Noise” contains methods and procedures  that are applicable to low frequency noise emitted from industrial premises and mining operations for planning purposes.  Items  such  as  boilers,  pumps,  transformers,  cooling  fans,  compressors,  oil  and  gas  burners, foundries, wind  farms, electrical  installations, diesel engines, ventilation and air‐conditioning equipment, wind turbulence and  large chimney resonance may comprise sources of high  level noise having frequency content less than 200 Hz.   

Page 15: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  14

These sources may exhibit a spectrum  that characteristically shows a general  increase  in sound pressure level with decrease in frequency. Annoyance due to low frequency noise can be high even though the dBA level measured  is relatively  low. Typically, annoyance  is experienced  in the otherwise quiet environments of  residences,  offices  and  factories  adjacent  to  or  near  low  frequency  noise  sources.  Generally,  low level/low frequency noises become annoying when the masking effect of higher frequencies is absent. This loss of high frequency components may occur as a result of transmission through the fabric of a building, or in propagation over long distances. 

Where a noise immission occurs exhibiting an unbalanced frequency spectrum, the overall sound pressure level inside residences should not exceed 50 dBZ to avoid complaints of low frequency noise annoyance. A spectrum  is considered unbalanced when  the un‐weighted overall noise  level  is more  than 15 dB higher than the A‐weighted overall noise level. 

Page 16: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  15

5. Acoustic Measurements 

5.1 Overview 

Acoustic measurements  consisted of noise  logging  (Sites A, B and C) and attended noise measurements (Sites A to E). The noise measurement locations are shown in Figure 5.1 and are described as follows: 

Location A: Front yard of House 8 

Location B : Driveway of House 1 

Location C: Driveway of House 3 

Location D: Adjacent the Wide Bay Highway directly under overhead powerlines.  

Located E: Front gate of the Woolooga substation entrance. 

 

 

Figure 5.1  Site area and monitoring locations 

500 m 

Page 17: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  16

The noise monitoring was undertaken  in general accordance with Australian Standard AS1055 Acoustics – Description and measurement of environmental noise and the EHP Noise Measurement Manual. 

5.2 Attended Noise Measurements 

Attended noise measurements were undertaken at Locations A to E as shown on Figure 5.1.  

The  measurements  were  undertaken  on  01/02/2017  between  2:00pm  and  12:00am  (midnight). Measurements were taken over 5 and 15 minute periods using a field and laboratory calibrated Rion NA27 Type 1 sound level meter.  The microphone height was approximately 1.3m above natural ground level and was  located  in  the  free  field.   Weather during  the  time of monitoring was  fine, 20% cloud cover, with a breeze from the west at approximately 1 to 3 m/s.   

The measured noise levels are summarised in Table 5.1.   

Table 5.1 Attended Noise Measurement Results 

Location  Date & Time 

Period (Minutes) 

Results & Notes 

A  2:11pm 01/02/17 

15  Statistical noise levels:  L10  48 dBA, Leq 48 dBA, L90 32 dBA 

Noise from loud insects    60 dBA (3.15 to 5 kHz) 

Noise from insects    35 to 37 dBA (3.15 to 5 kHz) 

Passing car on Highway    39, 36 dBA 

Passing car on Hayes Road    57, 54 dBA 

Wind rustling trees    36 dBA 

B  2:57pm 01/02/17 

15  Statistical noise levels:  L10  45 dBA, Leq 43 dBA, L90 38 dBA 

Noise from insects dominant    40 dBA 

Passing car on Gympie‐Woolooga Road    43 to 53 dBA 

Passing truck on Gympie‐Woolooga Road    50 dBA 

C  3:30pm 01/02/17 

15  Statistical noise levels:  L10  48 dBA, Leq 46 dBA, L90 29 dBA 

Distant hum from Highway    26 dBA 

Light wind in trees     31 dBA 

Strong wind in trees    47 to 50 dBA 

Crows    45, 44 dBA 

Birds    30, 33, 36, 50 (cockatoo) 

Calm conditions, distant birds    23 to 24 dBA 

C  10:01pm 01/02/17 

15  Statistical noise levels:  L10  36 dBA, Leq 36 dBA, L90 32 dBA 

Noise from insects dominant    30 to 35 dBA (3.15 to 5 kHz) 

Noise from loud insects    41, 46  dBA 

B  10:30pm 01/02/17 

15  Statistical noise levels:  L10  45 dBA, Leq 42 dBA, L90 37 dBA 

Noise from loud insects    45,44,45 dBA (3.15 to 5 kHz) 

Noise from insects    38 to 42 dBA (3.15 to 5 kHz) 

Distant cow noises    41, 42 

Passing car on Gympie‐Woolooga Road    57, 55 dBA 

Audible hum from substation. No loud but can hear when all is quiet. 

Page 18: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  17

Location  Date & Time 

Period (Minutes) 

Results & Notes 

D  10:54pm 01/02/17 

5  Statistical noise levels:  L10  42 dBA, Leq 40 dBA, L90 34 dBA 

Noise from insects    34 to 43 dBA (3.15 to 5 kHz) 

Distant cars 

E  11:08pm 01/02/17 

5  Statistical noise levels:  L10  40 dBA, Leq 40 dBA, L90 38 dBA 

Noise from insects    35 to 42 dBA (3.15 to 5 kHz) 

Noticeable hum from substation     17 to 20 dBA (100Hz)  

A  11:20pm 01/02/17 

15  Statistical noise levels:  L10  36 dBA, Leq 37 dBA, L90 28 dBA 

Noise from insects    29 to 33 dBA (3.15 to 5 kHz) 

Passing car on Wide Bay Highway    44 dBA 

Operator moving in grass    45 to 50 dBA 

Note:  * The reported noise levels, excluding the statistical noise levels, are the instantaneous levels read from the sound level meter, and generally represent the range in noise levels or maximum noise levels for a particular noise source. 

5.3 Noise Logging 

Noise  logging was undertaken at Locations A, B and C as shown on Figure 5.1.   Logging was undertaken from  01/02/2017  to  08/02/2017  using  field  and  laboratory  calibrated  Larson  Davis  LD831  Type  1 environmental noise loggers.  Noise logging was undertaken in the free field.   

Data from the Bureau of Meteorology (Gympie)  indicates that weather during the monitoring period was generally fine and warm, but with light rainfall on Saturday 4th (0.2mm).  Overall, the noise monitoring data is considered acceptable for use in this report. 

The measured noise  levels are graphed  in Appendix C. From the noise  logging the statistical results have been summarised and are presented in Appendix C. 

The background noise levels at each location have been calculated using the lowest 10th percentile method and are shown  in Table 5.2.   Background noise  levels have been calculated  for the required day  (7am to 6pm), evening (6pm to 10pm) and night (10pm to 7am) periods, and also an extended day period (6am to 7pm) which is considered to better account for the likely solar production time. 

It was apparent from the monitoring audio samples and the frequency analysis of the data that the noise environment was dominated by  insects  in  the night and evening periods, and was also  impacted  in  the daytime  by  insects  and  birds.    Therefore,  the  background  noise  levels  have  been  recalculated with  the insect and bird noise removed  from  the data by  filtering specific  frequency bands.   The resulting  filtered background noise levels are shown in Table 5.2. 

It  is noted  that  in some  instances  it  is difficult  to ascertain  the background noise  level  in  the absence of insect  and  birds  due  to  their  noises  affecting multiple  frequency  (octave)  bands.    Removing  the  noise contribution  from  the  affected octave bands  in  their  entirety  can over‐estimate  the  contribution of  the birds and insects.  Therefore, a range of background noise levels has been reported where insect and bird noise affects multiple octave bands.   

Page 19: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  18

Table 5.2  Background Noise Levels  

Period  Background Noise Level L90 dBA  Background Noise Level L90 dBA  

(With Insect & Bird Noise Filtered Out) 

Location A (North) 

Location B (West) 

Location C (South) 

Location A (North) 

Location B (West) 

Location C (South) 

Day (7am to 6pm)  36  37  32  34  27‐30*  26‐28* 

Evening (6pm to 10pm)  28  32  34  23  23  21 

Night (10pm to 7am)  29  26  33  19  19  19 

Extended Day (6am to 7pm)  ‐  ‐  ‐  33  25‐28*  26‐28* 

Note:   *  It  is difficult  to ascertain  the background noise  level  in  the absence of  insect and bird noise due  to  the influence over multiple octave bands.  Therefore, a range of background noise levels is proposed. 

 

From  the  results  in Table 5.2,  it  can be  seen  that  the background noise  levels at  the  site are  low, as  is expected of rural areas. The daytime background noise level at Location A is higher than Locations B and C, and this is considered to be due to the noise associated with road traffic on the Highway. 

Whilst the background noise levels were as low as 19 dBA L90 at night, the minimum background noise level under state policy is generally taken as 25 dBA L90. 

Based on the above results, it is proposed that background noise levels are used as follows in Table 5.3. 

Table 5.3  Proposed Project Background Noise Levels 

Period  Background Noise Level L90 dBA 

Residences Near Highway  

(refer note 1) 

Residences distant from Highway 

(refer note 2) 

Day (7am to 6pm)  34  28 

Evening (6pm to 10pm)  25*  25* 

Night (10pm to 7am)  25*  25* 

Extended Day (6am to 7pm)  33  27 

Notes:  * Minimum background noise level of 25 dBA L90 applies. 

  1 Residences near highway (refer Figure 2.2) include houses 4, 5, 8, 13, 18 & 19. 

  2 Residences distant from highway (refer Figure 2.2) include 1‐3, 6, 7, 9‐12, 14‐17, & 20‐23. 

Page 20: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  19

6. Construction Noise Assessment 

6.1 Overview 

The  construction  of  a  solar  farm  involves  road  construction,  civil  works,  excavation,  foundation construction and electrical  infrastructure works.   These works will generate noise from the use of on‐site machinery, vehicle movements and other construction related activities.  

There are no specific construction noise criteria  in  the Environmental Protection Act 1994 or other state legislation.  The Environmental Protection Act 1994 notes that noise limits are not applied to building work between 6:30am and 6:30pm on a business day  (typically Monday  to Friday) or Saturday.   Outside  these times, the Act notes that building work must be inaudible. 

The relaxation of noise limits during daytime construction is generally considered appropriate.  The reasons for  the  relaxation  of  limits  include  (i)  construction  activities  are  not  a  long‐term  noise  source,  and  (ii) operational  noise  can  typically  be more  readily  controlled  as  they  are  fixed,  often within  enclosures  or buildings, whereas construction activities are often external sources and mobile. 

Although noise limits may be relaxed for construction activities during the daytime, it is required that noise emissions are minimised where practicable, especially where construction will occur for long periods.   

6.2 General Recommendations 

Noise and vibration from typical expected construction activities have been assessed.  Generally noise and vibration  from  construction are  to be managed  through hours of operation and, where practical, use of appropriate buffer distances. 

The  noise  and  vibration management  plan  should make  reference  to  Australian  Standard  AS2436‐2010 “Guide to noise and vibration control on construction, demolition and maintenance sites”.   This standard provides details on strategies to minimise construction noise, such as the following: 

Plant and Equipment Strategies: 

Employing  quieter  techniques  for  all  high  noise  activities  such  as  rockbreaking,  concrete  sawing, power and pneumatic tools. 

Choosing  quieter  plant  and  equipment  based  on  the  optimal  power  and  size  to most  efficiently perform the required tasks.    

Operating plant and equipment in the quietest and most efficient manner. 

Where possible modify equipment to reduce noise  levels, however only after consultation with the manufacturer.  For example, providing mufflers to existing equipment.     

Regularly  inspecting  and maintaining  plant  and  equipment  to minimise  noise  and  vibration  level increases  to  ensure  that  all  noise  and  vibration  reduction  devices  are  operating  effectively.  Maintenance should be carried out by trained persons.     

Excessive noise caused by resonance of body panels and cover plates can be reduced by stiffening with  additional  ribs  or  by  increasing  the  damping  with  a  surface  coating  of  resonance‐damping material.    Rattling  noises  can  be  controlled  by  tightening  loose  parts  and  fixing  resilient material between the surfaces in contact.   

For stationary plant where limited access is required, the noise source should be enclosed.   

Plant that is used intermittently, e.g. cranes, dozers, graders, back hoes, bobcats and loaders, should be shut down in the intervening periods between work or throttled down to a minimum.   

Page 21: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  20

In  demolition  work  alongside  occupied  premises  there  should,  if  possible,  be  a  break  in  solid connections, e.g. concrete paving, between the working areas and the adjoining buildings.  This will reduce the transmission of vibration and structure‐borne noise.  Care should be taken that any such break  is of no  structural  significance  in  relation  to  the planned  system of demolition.    The break should result in premature collapse due to lack of continuity of restraint.   

Vibration  from machinery  with  rotating  parts  can  be  reduced  by  attention  to  proper  balancing.  Frictional noise from the cutting action of tools and saws may be reduced if the tools are kept sharp.  Other noises caused by frictional in machines, conveyor rollers and trolleys can be reduced by proper lubrication.       

 

On‐site Noise Mitigation Strategies: 

Maximising the distance between noise activities and noise sensitive land uses. 

Undertaking noise fabrication work off site where possible. 

Adopting alternatives to reversing alarms. 

Using temporary site building and material stockpiles as noise barriers.   These can often be created using site earthworks and may be included as a part of final landscape design. 

Installing purpose built noise barriers, acoustic sheds and enclosures. 

 

General Strategies: 

Regular reinforcement (such as toolbox talks) of the need to minimize noise and vibration. 

Regular identification of noisy activities and adoption of improvement techniques. 

When dropping materials  into for example trucks, the surfaces on to which the materials are being moved  could  be  covered  by  some  resilient material.    Particular  care  should  be  taken  during  the loading  and  unloading  of  scaffolding.   Where material  cannot  be  lowered  into  skips  or  by  other means, it is recommended that properly constructed and damped chutes be considered.    

Avoiding the use of portable radios, public address systems or other methods of site communication that may unnecessarily impact upon nearby residents.     

Developing routes for the delivery of materials and parking of vehicles to minimise noise. 

Where possible avoiding the use of equipment which generates impulsive noise. 

Minimising the need for vehicle reversing for example by arranging for one way site traffic routes. 

Minimise the movement of materials, equipment and unnecessary metal‐on‐metal contact. 

Minimising truck movements. 

Scheduling respite periods. 

 

 

   

Page 22: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  21

7. Operational Noise Assessment 

During operation of the solar farm the most likely sources of noise will be from the inverters and electrical substation, and occasional maintenance activities. 

7.1 Noise Limits 

A  number  of  noise  criteria were  presented  in  Section  4.3,  including  background  creep,  acoustic  quality objectives and EcoAccess sleep disturbance criteria. 

It is assumed that this solar plant (inverters and substation) will only operate between 6am and 7pm, and thus the background creep and acoustic quality objectives are considered relevant. 

The  noise  from  the  solar  plant  (inverters  and  substation)  is  likely  to  be  continuous,  and  thus  the background creep limit of L90 + 0 dBA (refer Section 4.3.2) is applicable. That is, the noise limit is equal to the existing background noise level, and is therefore as follows during the extended day time (refer Table 5.2): 

For residences near the highway:    33 dBA (including houses 4, 5, 8, 13, 18 & 19)  

For residences distant from highway:  27 dBA (including houses 1‐3, 6, 7, 9‐12, 14‐17, & 20‐23) 

Compliance  with  these  background  creep  limits  will  result  in  compliance  with  the  acoustic  quality objectives in Section 4.3.3 and sleep disturbance criteria in Section 4.4.3. 

The EHP EcoAccess  guidelines  also  include  a  low  frequency noise  limit  to be  achieved  inside  residences (refer Section 4.4.4). The  internal  limit  is 50 dBZ and an un‐weighted (dBZ)  level more than 15 dB higher than  the A‐weighted  (dBA) noise  level.   On  some projects an additional  low  frequency  limit  is  included, being an external limit of 60 dBC and a C‐weighted (dBC) level more than 20 dB higher than the A‐weighted (dBA) noise level. 

7.2 Inverter and Transformer Noise 

7.2.1 Overview 

Photovoltaic  panels  produce  energy  at  a  Direct  Current  (DC)  voltage  and  require  the  conversion  to Alternating Current (AC) to allow connection to the transmission grid. The panel blocks will be connected to inverters  for  conversion  to  AC.  The  latest  power  station  design  utilises  2.5MW  inverters  in  a  double (5.0MW)  back‐to‐back  arrangement  connected  to  transformer.  The  arrangement  results  in  a  5.0MW Medium Voltage Power Station (SMA MVPS5000). The project will require a total of 73 MVPS5000 units.  

7.2.2 Source Noise Data 

The sound power level data for a single inverter (2.5MW, SMA SC2500‐EV) has been provided as 92 dBA Lw. The spectrum is included in Figure 7.1. 

Page 23: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  22

 

Figure 7.1  Inverter (SMA SC2500‐EV) Sound Power Level 

From Figure 7.1 it can be seen that the inverter is tonal in the 3.15 kHz one‐third octave band.   

Sound power level data for the 5.0MW systems (MVPS5000) is not available, but noise data was provided at distances of 1 metre  from each  side of  the MVPS enclosure.   This data has been used with  standard shipping container size  information  to arrive at a MVPS5000 sound power  level of 99 dBA Lw.  It  is noted that  this  sound power  level  (99 dBA)  is more  than  twice  the  sound power  level of an  individual 2.5MW inverter (92 dBA x 2 = 95 dBA).  The sound spectrum of the MVPS5000 is assumed to be the same shape as the 2.5MW inverter, and remains tonal in the 3.15 kHZ one‐third octave band.   

7.2.3 Modelling and Results 

The proposed operational scenario has been modelled using  the SoundPLAN v7.4 computer package and the following inputs: 

SoundPLAN ISO 9613.2 algorithms. 

Sound  power  level  data  of  99  dBA  for  each  of  73  x MVPS5000  units.  Locations  for  units  as  per drawing ‘Inverter Overlay (Indicative) – 27 Feb 2017.pdf’. 

Terrain  information  provided  as  LIDAR  for  site  and  combined  with  topographical  data  for  the surrounding area from Geosciences Australia 1 second SRTM. 

SoundPLAN ground absorption factor of 0.5 (i.e. 50% absorption). 

Page 24: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  23

The results are presented in Table 7.1 below and shown graphically in Figure D.1 in Appendix D. 

A tonality adjustment has been determined at each  location by reviewing the predicted one‐third octave band levels at 3.15kHz and the adjoining bands.  Where the noise level in the 3.15 kHz band exceeded the neighbouring  bands  by  5  dB  or  more,  a  5  dB  tonality  penalty  is  applied.  Where  the  exceedance  of neighbouring bands  is 1 dB to 4 dB, a 2 dB tonality penalty  is applied. The resulting  limits are  included  in Table 7.1. 

Table 7.1  Predicted External Noise Levels at Nearest Residences due to MVPS Units 

Residence  Noise Level Leq dBA 

Tonality Adjustment 

Adjusted Noise Level Leq,adj,T dBA 

Limit (Extended Daytime 6am to 7pm) Leq,adj,T dBA 

Exceedance dB 

House 1  30  2  32  27  5 

House 2  35  5  40  27  13 

House 3  37  5  42  27  15 

House 4  29  2  31  33  0 

House 5  32  2  34  33  1 

House 6  33  2  35  27  8 

House 7  27  2  29  27  2 

House 8  30  2  32  33  0 

House 9  30  2  32  27  5 

House 10  21  0  21  27  0 

House 11  24  0  24  27  0 

House 12  25  0  25  27  0 

House 13  30  2  32  33  0 

House 14  24  0  24  27  0 

House 15  23  0  23  27  0 

House 16  21  0  21  27  0 

House 17  21  0  21  27  0 

House 18  19  0  19  33  0 

House 19  23  0  23  33  0 

House 20  32  2  34  27  7 

House 21  22  0  22  27  0 

House 22  17  0  17  27  0 

House 23  28  2  30  27  3 

 From Table 7.1 it can be seen that the predicted noise level exceedance is up to 15 dB at House 3.  Lesser exceedances are also predicted at Houses 1, 2, 5‐7, 9, 20 & 23. 

The predicted low frequency noise levels are included in Table 7.2. 

   

Page 25: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  24

Table 7.2  Predicted External Low Frequency Noise Levels at Nearest Residences due to MVPS Units 

Residence  C‐weighted Noise Level dBC  Z‐Weighted External Noise Level dBZ 

Overall Leq dBC  dBC ‐ dBA  Overall Leq dBZ  dBZ ‐ dBA 

House 1  43  13  45  15 

House 2  45  10  47  12 

House 3  46  9  48  11 

House 4  42  13  44  15 

House 5  43  12  46  14 

House 6  45  12  47  14 

House 7  40  14  43  16 

House 8  43  12  45  14 

House 9  42  12  44  14 

House 10  36  15  38  18 

House 11  38  14  40  17 

House 12  39  14  42  17 

House 13  42  13  44  15 

House 14  38  14  41  16 

House 15  38  15  40  17 

House 16  36  15  38  18 

House 17  36  15  39  17 

House 18  35  16  37  18 

House 19  38  14  40  17 

House 20  44  12  46  14 

House 21  37  15  39  17 

House 22  33  16  36  19 

House 23  41  13  43  15 

MAX  46  16  48  19 

From Table 7.2 it can be seen that the external C‐weighted noise levels will comply with the external limit of  60  dBC  based  on  a maximum  external  level  of  46  dBC.    The  internal  (indoor)  noise  levels would  be expected to be lower than the predicted external noise levels. Therefore the internal limit of 50 dBZ will be readily achieved based on a maximum external level of 48 dBZ.   

Therefore no low frequency noise reduction measures are required. 

7.2.4 Noise Assessment and Mitigation 

The noise modelling results indicate the following noise level exceedances: 

House 1:    5 dB exceedance 

House 2:    13 dB exceedance 

Page 26: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  25

House 3:    15 dB exceedance 

House 5:    1 dB exceedance 

House 6:    8 dB exceedance  

House 7:    2 dB exceedance 

House 9:    5 dB exceedance 

House 20:  7 dB exceedance 

House 23:  3 dB exceedance 

There are a number of mitigation strategies that could be considered in the project, including: 

Implementing noise controls at the source by requiring a maximum equipment sound power level as part of  the procurement  of  the  inverter/transformers.  In  this  instance  reducing  the  sound power level from the modelled level of 99 dBA down to 84 dBA Lw,eq,T (assuming tonality penalty of 5 dB) or 89 dBA Lw,eq,adj,T (if free of tonal characteristics) would result in compliance. 

Design  of  noise  barriers  around  the  inverter/transformers  –  Barriers  may  be  able  to  achieve reductions of 5 to 15 dBA depending on the height, extent and construction. 

Orientating the inverter/transformers to minimise noise emissions to nearest residences – Improved noise directivity data could be used to optimise equipment orientation and reduce noise emissions. The reductions may only be small, but never‐the‐less cost‐effective. 

Relocating  inverter/transformers  further  from  residences  towards  the  centre  of  the  site  –  It  is understood  this would  have  cost  impacts with  respect  to  cable  lengths  and  associated  potential power losses, but may prove cost‐effective in some locations. 

Purchase of properties most affected by the project noise.  For example, purchase of properties with Houses 2 and 3, would reduce the maximum exceedance from 15 dB down to 8 dB. 

It may be appropriate and more cost‐effective to implement more significant noise mitigation strategies to inverter/transformers  located  nearer  to  residences,  and  reduced  mitigation  to  inverter/transformers located further from residences.   

It is noted that the noise levels are based on the supplied noise data and estimated tonality adjustments. It may be desirable to target increased noise reductions so as to minimise the risk of noise exceedances due to uncertainty inherent within the data and modelling process.  

7.3 Substation Noise  

The project will require the addition of a substation, which is proposed to adjoin the existing substation in 1 of 2 locations as per Figure 7.2. 

The proposed substation is located approximately 450 metres from the nearest sensitive receiver, House 13 to the north. 

The substation will transform  from  the project 33 kV to either 33 kV, 132 kV or 275 kV and  is subject to further assessment. 

It  is assumed  that  this plant will only operate between 6am and 7pm, and  thus  the  ‘extended day  time’ limits would apply. 

 

Page 27: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  26

 

Figure 7.2  Potential Substation Locations 

From Section 7.1, the predicted MVPS  (inverter) noise  level at House 13  is 32 dBA (from Table 7.1).   The proposed  noise  limit  is  33  dBA.    Therefore  the  allowable  noise  contribution  at  this  residence  from  the substation is 22 dBA at House 13.   

Thus  the  allowable  sound  power  level  of  the  proposed  substation  is  83  dBA  Lw,eq,T  (assuming  tonality penalty of 5 dB) or 88 dBA Lw,eq,adj,T (if free of tonal characteristics). 

This  sound  power  limit  should  be  included  in  the  procurement  specification,  and  additional modelling undertaken to verify its resulting noise contribution. 

It  is  noted  that  if  noise mitigation  is  applied  to  the  solar  inverter/transformers,  this would  permit  an increased noise contribution from the substation.   

7.4 Other Noises 

There will also be other occasional onsite noises including vehicles, maintenance shed and activities and air‐conditioning  units  associated with  the  operations  and  administration  building. Onsite  equipment  could include  industrial mowers, tractor slashers, small to medium trucks and tippers, crane, forklift, fire tender and solar panel cleaners. 

It  is considered  that many of  these  items of equipment and activities are  typical of  those  found  in  rural areas,  and would  be  unlikely  to  cause  nuisance  if  they  occur  occasionally,  and  during  daytime  hours. Additionally  it  is  required  that  the  maintenance  shed  and  activities  are  located  as  far  from  nearby residences as practicable, and the building is orientated to minimise noise emissions to nearby residences. 

It  is understood that emergency activities may need to occur at night, and this may be common with the requirements of the adjoining existing substation, and thus may already be typical of the area. Never‐the‐less  it  is required that night‐time activities be reasonable restricted such that noise  limits  in Table 5.2 are achieved except in the occasion of an emergency.  

 

Page 28: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  27

8. Recommendations & Conclusion 

The proposed Lower Wonga Solar Farm has been assessed with respect to noise  impacts from the facility onto nearby residences.  The following noise conclusions and recommendations apply to the project: 

The  relevant  criteria  for operational noise  is  considered  to be  the background  creep  criterion  for continuous noise in the EPP(Noise), which is as follows:  

To the extent that it is reasonable to do so, noise from an activity must not be— 

– for noise that is continuous noise measured by LA90,T—more than nil dBA greater than the existing acoustic environment measured by LA90,T; or 

Baseline noise monitoring has indicated that background noise levels are as follows (Refer Table 5.3): 

Period  Background Noise Level L90 dBA 

Residences Near Highway   Residences distant from Highway 

Day (7am to 6pm)  34  28 

Evening (6pm to 10pm)  25*  25* 

Night (10pm to 7am)  25*  25* 

Extended Day (6am to 7pm)  33  27 

Construction noise and vibration associated with the development has been considered in Section 6. There are no specific construction noise criteria  in the Environmental Protection Act 1994 or other state  legislation.   The Environmental Protection Act 1994 notes that noise  limits are not applied to building  work  between  6:30am  and  6:30pm  on  a  business  day  (typically Monday  to  Friday)  or Saturday.    Outside  these  times,  the  Act  notes  that  building  work  must  be  inaudible.    General recommendations for noise and vibration minimisation are included in Section 6.   

Operational noise from the 73 x  inverter/transformers has been assessed  in Section 7.2 against the nominated noise limits. A noise level reduction of 15 dB at the worst affected receiver is required to achieve compliance with the nominated criteria. A range of mitigation strategies has been suggested including: 

○ Implementing noise controls at the source by requiring a maximum equipment sound power level as part of the procurement of the inverter/transformers.  

○ Design of noise barriers around the inverter/transformers. 

○ Orientating the inverter/transformers to minimise noise emissions to nearest residences. 

○ Relocating inverter/transformers further from residences towards the centre of the site. 

○ Purchase of properties most affected by the project noise.  . 

Operational noise from the substation has been assessed in Section 7.3 against the nominated noise limits. Based on the nominated locations in Figure 7.2, it is required that the allowable sound power level  of  the  proposed  substation  is    83  dBA  Lw,eq,T  (assuming  tonality  penalty  of  5  dB)  or  88  dBA Lw,eq,adj,T  (if  free of  tonal  characteristics).  It  is noted  that  if noise mitigation  is  applied  to  the  solar inverter/transformers, this would permit an increased sound power level for the substation. 

By  following  the  above  recommendations,  it  is  predicted  that  noise  levels  will  be  compliant  with  the nominated criteria. 

 

Page 29: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  28

Appendix A Glossary 

Parameter or Term  Description 

dB  The decibel (dB) is the unit measure of sound.  Most noises occur in a range of 20 dB (quiet rural area at night) to 120 dB (nightclub dance floor or concert). 

dBA  Noise levels are most commonly expressed in terms of the ‘A' weighted decibel scale, dBA.  This scale closely approximates the response of the human ear, thus providing a measure of the subjective loudness of noise and enabling the intensity of noises with different frequency characteristics (e.g. pitch and tone) to be compared. 

Day  The period between 7am and 6pm. 

Evening  The period between 6pm and 10pm. 

Night  The period between 10pm and 7am. 

Free‐field  The description of a noise receiver or source location which is away from any significantly reflective objects (e.g. buildings, walls). 

L1  The noise level exceeded for 1% of the measurement period.   

L10  The noise level exceeded for 10% of the measurement period.  It is sometimes referred to as the average maximum noise level. 

L90  The noise level exceeded for 90% of the measurement period.  This is commonly referred to as the background noise level. 

Leq  The equivalent continuous sound level, which is the constant sound level over a given time period, which is equivalent in total sound energy to the time‐varying sound level, measured over the same time period. 

Leq,1hour  As for Leq except the measurement intervals are defined as 1 hour duration. 

Lmax  Maximum A‐weighted sound pressure level. 

Leq(24 hour)  The average Leq noise level over the 24‐hour period from midnight to midnight. 

L10(18 hour)  The arithmetic average of the one‐hour L10 values between 6am and midnight.  This parameter is used in the assessment of road traffic noise. 

Rw  Weighted Sound Reduction Index – is a single number evaluation of the property of a partition to attenuate sounds.  For the majority of partitions, the value of Rw will be similar to the value for STC.  Partitions with particularly poor performance at 100 Hz may have lower values for Rw than for STC.  Conversely, partitions with poor performance at 4000 Hz may have higher Rw than for STC. (As per AS1276.1‐1999). 

Habitable Rooms  According to the "Building Code of Australia" a Habitable Room is: " a room used for normal domestic activities and  Includes a bedroom, living room, lounge room, music room, television room, kitchen, dining room, sewing room, study, playroom, family room, home theatre, and sunroom, but 

Excludes a bathroom, laundry, water closet, pantry, walk‐in wardrobe, corridor, hallway, lobby, photographic darkroom, clothes drying room, and other spaces of a specialised nature occupied neither frequently nor for extended periods." 

 

Page 30: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  29

Appendix B Project Drawings 

   

Page 31: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

SolarQ – Development Application – Engineering Report

Engineer Report Page 16

Attachment 1: Development Land Area

Page 32: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

SolarQ – Development Application – Engineering Report

Engineer Report Page 17

Attachment 2: Site Layout (Draft and Prior to Final Design)

Page 33: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

SolarQ – Development Application – Engineering Report

Engineer Report Page 21

Attachment 6 – Woolooga Substation current layout

Page 34: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

SolarQ – Development Application – Engineering Report

Engineer Report Page 22

Attachment 7 – Powerlink Woolooga Substation 132kV and 275kV Expansion areas

Page 35: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty
Page 36: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  30

Appendix C Noise Logging Results 

 

Figure C.1  Graph of Noise Logging Results at Location A 

Page 37: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  31

 

Figure C.2  Graph of Noise Logging Results at Location B 

 

Figure C.3  Graph of Noise Logging Results at Location C 

Page 38: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  32

Table C.1  Statistical Noise Levels at Location A 

Parameter  Statistic  Noise Levels dBA 

Day  Evening  Night 

Lmax  Maximum  89  80  79 

Top 10%  73  72  67 

Average  66  61  57 

(Median)  66  60  57 

Bottom 10%  58  51  50 

Minimum  51  45  41 

L1  Maximum  83  75  72 

Top 10%  71  66  59 

Average  61  54  51 

(Median)  60  53  52 

Bottom 10%  51  46  44 

Minimum  45  41  36 

L10  Maximum  73  73  69 

Top 10%  67  57  52 

Average  55  48  44 

(Median)  54  46  43 

Bottom 10%  45  41  37 

Minimum  40  32  33 

Leq  Maximum  70  70  66 

Top 10%  63  54  50 

Average  52  45  42 

(Median)  52  43  40 

Bottom 10%  44  38  36 

Minimum  38  31  32 

L90  Maximum  65  48  52 

Top 10%  51  40  47 

Average  42  35  36 

(Median)  41  35  34 

Bottom 10%  35  28  30 

Minimum  31  26  27 

 

 

 

Page 39: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  33

Table C.2  Statistical Noise Levels at Location B 

Parameter  Statistic  Noise Levels dBA 

Day  Evening  Night 

Lmax  Maximum  90  70  79 

Top 10%  67  62  62 

Average  61  56  52 

(Median)  60  57  50 

Bottom 10%  56  47  42 

Minimum  50  43  34 

L1  Maximum  82  63  73 

Top 10%  61  57  55 

Average  56  50  45 

(Median)  56  51  44 

Bottom 10%  52  43  35 

Minimum  47  34  29 

L10  Maximum  65  57  59 

Top 10%  57  55  49 

Average  52  44  40 

(Median)  52  43  39 

Bottom 10%  48  37  31 

Minimum  44  31  27 

Leq  Maximum  68  54  57 

Top 10%  54  52  47 

Average  49  43  38 

(Median)  49  41  37 

Bottom 10%  45  36  30 

Minimum  42  30  25 

L90  Maximum  51  51  50 

Top 10%  46  47  44 

Average  42  37  33 

(Median)  41  36  32 

Bottom 10%  37  32  26 

Minimum  35  28  23 

 

 

 

Page 40: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  34

Table C.3  Statistical Noise Levels at Location C 

Parameter  Statistic  Noise Levels dBA 

Day  Evening  Night 

Lmax  Maximum  107  83  80 

Top 10%  81  69  66 

Average  70  56  55 

(Median)  69  54  53 

Bottom 10%  61  47  47 

Minimum  52  40  41 

L1  Maximum  80  69  66 

Top 10%  69  59  56 

Average  61  49  50 

(Median)  61  48  50 

Bottom 10%  54  41  44 

Minimum  46  38  39 

L10  Maximum  74  67  60 

Top 10%  61  54  52 

Average  55  45  46 

(Median)  54  44  47 

Bottom 10%  47  38  40 

Minimum  40  36  35 

Leq  Maximum  72  64  55 

Top 10%  59  51  50 

Average  52  43  44 

(Median)  52  41  45 

Bottom 10%  44  36  38 

Minimum  40  34  33 

L90  Maximum  57  45  53 

Top 10%  47  42  48 

Average  40  37  40 

(Median)  40  36  41 

Bottom 10%  32  33  32 

Minimum  26  32  29 

Page 41: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

 

8796R01V01.docx  35

Appendix D Noise Level Contours 

 

Page 42: LOWER WONGA SOLAR FARM - Gympie Council · 2017-05-03 · 8796R01V01.docx 5 1. Introduction ASK Consulting Engineers Pty Ltd (ASK) was commissioned by Bordstrong Developments Pty

������

������

������

������

������

������

������

������

������

������

������

������

�����

�����

������ ������

������ ������

������ ������

������ ������

������ ������

������ ������

�������������� ����������� ������ ��������

������

�� ���� ������ �� ������������� ������������

�������������������������������������������������������������� ����������������������������������������

���� �� �� !������

! "#! "$! "%! &'! &&! &#! &$! &%! �'! �&! �#! �$

()*+$,,*+$%�*-���*+$%�.����.����*/��0' ���