Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2...

88
Ready to install Low voltage power circuit protection Panelboards & enclosed equipment

Transcript of Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2...

Page 1: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Ready to install Low voltage power circuit protectionPanelboards & enclosed equipment

MGLV5751 (RTI Intro) 14/9/05 2:09 pm Page 1

Page 2: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

This catalogue provides selection information forthe Merlin Gerin ready to install low voltage powercircuit protection products, their connectionsystems and enclosures.

Selection information for other products in the Merlin Gerin range can be

found in the following catalogues which can be found on our website

www.schneider.co.uk

Ready to install distribution boards,

DIN rail mounted equipment, enclosures and

connection systems

Order reference: MGLV5750

Compact LV circuit breakers and

switch disconnectors 80-3200A

Order reference: MGLV5730

Canalis Busbar trunking

Order reference: CAN5309

MGLV5751 (RTI Intro) 14/9/05 2:09 pm Page 2

Page 3: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Contents

Safepact 2 Section one 5 - 10

Enclosed Interpact Section two 11 - 12

MGF Fusegear Section three 13 - 16

Powerpact 4 panelboards Section four 17 - 36

Powerpact 4 panelboard metering

Section five 37 - 44

Powerpact 4 pan assemblies Section six 45 - 50

Technical data Section seven 51 - 54

Dimensions Section eight 55 - 66

Advantage Section nine 67 - 68

Schneider Electric overview Section ten 69 - 74

Comprehensive quick reference index

Section eleven 75 - 86

MGLV5751 (RTI Intro) 14/9/05 2:09 pm Page 3

Page 4: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGLV5751 (RTI Intro) 14/9/05 2:09 pm Page 4

Page 5: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Safepact 2 Section one

Enclosed MCCBs 63 to 630A 6

7

Earth leakage 8

Auxiliaries and accessories 9

Enclosed switch disconnector 100 to 630A

5

MGLV5751 (RTI Sec 01) 2/9/05 5:55 pm Page 5

Page 6: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Safepact 2Enclosed MCCBs 63 to 630A

6

RangeMCCBRating Adjustment Two Pole 3 pole + neutral 4 pole63A 50 - 63 MGE0632C MGE0633C MGE0634C100A 80 - 100 MGE1002C MGE1003C MGE1004C125A 100 - 125 MGE1252C MGE1253C MGE1254C160A 125 - 160 MGE1602C MGE1603C MGE1604C200A 160 - 200 MGE2003C MGE2004C250A 200 - 250 MGE2503C MGE2504C400A 160 - 400 MGE4003C MGE4004C630A 250 - 630 MGE6303C MGE6304C

MCCB + earth leakageRating 4 pole63A MGE0634EC100A MGE1004EC125A MGE1254EC160A MGE1604EC200A MGE2004EC250A MGE2504EC400A MGE4004EC630A MGE6304EC

Application For use in commercial and industrial applications, providing protection

isolation and control of motors and power circuits MCCBs can be fitted with adjustable Vigi earth leakage module for improving

disconnection times and providing fire protection Suitable for switching inductive loads, AC23 contact rating and high

mechanical endurance Security of isolation, positive contact indication in accordance with BS 7671

and padlockable rotary handle or toggle padlocking options

Offer ASTA certification of breaking capacity to

BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling

access Removable gland plates with optional

extension boxes Trip indication and test button Shrouded disconnectable neutral with 3 pole device Steelwork finished in polyester epoxy powder,

cream colour RAL9001

Accessories (See page 9) Voltage releases for remote tripping Auxiliary change over contacts for remote

indication Connection accessories for ease of wiring Rotary handle provides padlocking and ease of

operation Earth leakage

Technical data Enclosure ingress protection IP42 Rated operational voltage Ue 415V Rated current at 400C Rated ultimate short-circuit breaking capacity

Icu = 70kA Rated service short-circuit breaking capacity

Isu = 100% Icu = 70kA Motor ratings see page 52 Earth leakage module settings - see page 8

MGE1003C

MGE1003C

C-O operations in 000’s 100A 160A 250A 400A 630AElectrical endurance 30 40 20 12 8Mechanical endurance In/2 50 40 20 12 8

In 30 20 10 6 4

MGLV5751 (RTI Sec 01) 2/9/05 5:55 pm Page 6

Page 7: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Safepact 2Enclosed switch disconnector 100 to 630A

7

Application For use in commercial and industrial applications, providing isolation and

control of motors and power circuits Suitable for switching inductive loads, AC23 contact rating and high

mechanical endurance Security of isolation, positive contact indication in accordance with BS 7671

and padlockable rotary handle

Offer Supplied with terminal shields Removable front cover provides all round cabling

access Removable gland plates and optional extension

boxes Trip indication and test button Shrouded disconnectable neutral with 3 pole

device Steelwork finished in polyester epoxy powder,

cream colour RAL9001

Accessories (See page 9) Voltage releases for remote tripping Auxiliary change over contacts for remote

indication Connection accessories for ease of wiring Rotary handle provides padlocking and ease of

operation Earth leakage

Technical data Enclosure ingress protection IP42 Rated operational voltage Ue 415V Rated current at 400C Earth leakage module settings - see page 8

MGE1003SC

MGE1003SC

C-O operations in 000’s 100A 160A 250A 400A 630AElectrical endurance 30 40 20 12 8Mechanical endurance In/2 50 40 20 12 8

In 30 20 10 6 4

RangeSwitch disconnectorRating 3 pole + neutral 4 pole100A MGE1003SC MGE1004SC160A MGE1603SC MGE1604SC250A MGE2503SC MGE2504SC400A MGE4003SC MGE4004SC630A MGE6303SC MGE6304SC

Switch disconnector + earth leakage (RCCB)Rating 4 pole100A MGE1004SEC160A MGE1604SEC250A MGE2504SEC400A MGE4004SEC630A MGE6304SEC

MGLV5751 (RTI Sec 01) 2/9/05 5:55 pm Page 7

Page 8: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Safepact 2Earth leakage

8

MGE1003EC

29211

Application The vigi earth leakage module option disconnects the circuit breaker when an

electrical earth fault is detected Used to overcome high earth fault loop impedance and associated excessive

disconnection times eg long cable runs Enhanced personal and equipment protection

Offer Adjustable sensitivity and time delay settings for

discrimination with other RCDs Protection against nuisance tripping due to

transient overvoltages etc. to IEC255-4 andIEC801-2 - 5

Class A immunity to DC components of up to6mA

Accessories (See page 9) Remote indication of tripping using optional

changeover contact SDV

Technical dataRating Sensitivity settings (A)Up to 160A 0.03*, 0.3, 1, 3 and 10200 - 250 0.03*, 0.3, 1, 3, and 10400 - 630 0.3, 1, 3, 10 and 30

Time delay settings (ms)0, 60, 150 and 310* If the sensitivity is set to 30mA there is no time delaywhatever the time delay setting.

Extension boxes Provide extra cabling space when using oversized

cables. Colour RAL9001

Size To fit rating Part No.100mm 63 - 250A MGEX160C200mm 63 - 250A MGEX250C120mm 400 - 630A MGEX630C

MGLV5751 (RTI Sec 01) 2/9/05 5:55 pm Page 8

Page 9: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Safepact 2Auxiliaries and accessories

9

MGE 100/160/250

Changeover contactAuxiliary switch used for remote indication, electricalinterlocking etc. Function is dependent upon positionfitted within device. OF indicates contact position ‘ON’ and ‘OFF’ SD indicates device is in trip position SDE indicates device has tripped due to

overcurrent or earth fault (100/160/250 requiresSDE adaptor 29451

SDV indicates device has tripped due to earth fault

Part No.OF/SD/SDE/SDV 29450SDE adaptor forMGE 100/160/250 29451

Shunt trip (MX) Enables remote tripping on application of voltage

from coil Coil permanently rated

Aux. supply Part No.voltage (V)220/240 29387380/415 29388

Undervoltage release (MN) Enables remote tripping on removal of voltage to

coil Coil permanently rated Prevents reclosing of device before restoration of

supply to undervoltage release

Aux. supply Part No.voltage (V)220/240 29407380/415 29408

Rotary handle Permits the device to be padlocked in OFF

position by 1 - 3 padlocks, 5 - 8mm hasp Maintains indication of ON/OFF and TRIPPED

positions Maintains access to ‘push to trip’ button Ronis/Profalux keylocks available on 400/630A

Part No.For MGE 100/160/250 29337For MGE 400/630 32597

Cable clamp For bare (uncrimped) cable connections See technical data for cable terminations in detail Other options available: refer to NS catalogue, or

consult us

Part No.For MGE 100/160up to 95mm2 (set of 4) 29243120 to 185mm2 (set of 4) 29260For MGE 25025 to 95mm2 (set of 4) 29228120 to 185mm2 (set of 4) 29260For MGE 400/630up to 2x240mm2 (set of 4) 32482

MGE 400/630

ApplicationThese diagrams show the position of auxiliaries whenfitted inside the MCCB or switch disconnector.

MN/MX

OF SD SDE OF2

SDV

(VIGI)

MN/MX

OF1 SD SDEOF2 OF3

SDV

(VIGI)

29450

29387

29407

29337

29243

MGLV5751 (RTI Sec 01) 2/9/05 5:55 pm Page 9

Page 10: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

10

MGLV5751 (RTI Sec 01) 2/9/05 5:55 pm Page 10

Page 11: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Enclosed Interpact Section two

Enclosed Interpact switch disconnectors 12

11

MGLV5751 (RTI Sec 02) 2/9/05 5:53 pm Page 11

Page 12: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Enclosed InterpactSwitch disconnectors

12

ApplicationHeavy duty sheet steel enclosures for use in commercial and industrialapplications, providing isolation and control of electrical loads. Suitable forswitching highly inductive loads without derating. For use in environments where asuperior degree of protection is required. Four pole isolation with positive contactindication. Padlockable handle. Alternative red/yellow handle for use in industrialapplications. 480V 3 ph 4 wire 50/60Hz systems.

Technical data Degree of protection IP55 to BS EN 60529 Sheet steel, epoxy/polyester powder coated,

beige colour Door interlocked rotary handle, padlockable Black handle as standard, with Red/yellow handle

option Removable bottom gland plate Switch disconnector manufactured and tested to

BS EN 60947-3 4 pole switching with fully rated neutral Rated operational current at AC23A = nominal

rating up to 480V Rated operational voltage 690V 50/60Hz (500V

for 63A)For further details of the switch disconnectors refer toInterpact catalogue Ref No. PB-W1043

Terminations 63A: clamp connections accepting 1.5 - 16mm2

rigid cable 100 - 630A flat pads for crimped lugs For details of maximum lug dimensions refer to

table on page 55 Termination details are identical to those of the

Compact MCCBs

Black rotary handle Red rotary handle with yellow surround

Rating Part No. Part No. 63A MGES063 MGES063R100A MGES100 MGES100R160A MGES160 MGES160R250A MGES250 MGES250R320A MGES320 MGES320R400A MGES400 MGES400R500A MGES500 MGES500R630A MGES630 MGES630R

AccessoriesRating 63A 100-160A 250A 320-630A Auxiliary switch 29450 29450 29450 29450Pair long terminal shields 28957 28958 29324 32565Set of 4 crimp cable lugs for Cu cables c/w 3 phase barriers

95mm2 28952120mm2 29256150mm2 29257185mm2 29258240mm2 32501300mm2 32503

MGES063

MGLV5751 (RTI Sec 02) 2/9/05 5:54 pm Page 12

Page 13: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGF Fusegear Section three

Switch disconnector fuse and Switch disconnector 14

Fuse switch disconnector and Switch disconnector 15

Busbar chambers 16

Accessories 16

13

MGLV5751 (RTI Sec 03) 2/9/05 5:52 pm Page 13

Page 14: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGF FusegearSwitch disconnector fuseSwitch disconnector

14

ApplicationHeavy duty fuse products for use in commercial and industrial environments, providingisolation and traditional fuse protection for electrical loads.

Features Rated for 240/415V 50/60Hz Ratings 20A, 32A, 63A, 100A, SP&SwN, TP&N Utilisation category AC20A, AC21A, AC22A, AC23B at rated current Degree of protection IP41 Handle position provides positive contact indication Door handle prevents door being opened when switch is ON or padlocked Handle padlockable in ON and OFF positions Fuse links supplied as standard

Construction Live terminals fully shrouded Door interlock has integral defeat mechanism allowing door to be opened without

switching OFF. This feature is not operable when the handle is padlocked Removable gland plates with cable knockouts Lift off door provides greater access for installation and cabling Door opens within the width of the unit allowing units to be mounted adjacent Neutral has disconnectable link and capacity for 3 outgoing cables Keyhole slots in the enclosure base allow easy installation Earthing kit provided as standard Easy access to fuse links Steelwork finished in polyester epoxy powder, cream colour RAL9001

Technical data Standard BS EN 60947-3 Rated operational voltage 415V 50/60Hz

MGFA, MGFLRating 20A 32A 63A 100A

Rated current at 400C, A 20 32 63 100

Rated impulse voltage 6kV 6kV 6kV 6kV

Rated short time withstand Icw, A 416 416 756 1300

Rated short circuit making capacity Icm 1.35kA 1.35kA 1.35kA 3.5kA

Rated short circuit breaking capacity Icn 50kA 50kA 50kA 50kA

Utilisation category at rated current AC-20A/ 21A/ 22A/ 23B

Kilowatt rating 11kW 15kW 30kW 55kW

Cable size, maximum mm2 10mm2 10mm2 25mm2 50mm2

ReferencesRating Switch disconnector fuse Switch disconnector

(A) Part No. Part No.

Single pole and switched neutral

20 MGFA0201C MGFL0201C

32 MGFA0321C MGFL0321C

63 MGFA0631C MGFL0631C

100 MGFA1001C MGFL1001C

Three pole and neutral

20 MGFA0203C MGFL0203C

32 MGFA0323C MGFL0323C

63 MGFA0633C MGFL0633C

100 MGFA1003C MGFL1003C

Fuse link dataRating (A) BS88 reference Bussman reference

20 A1, A2 NITD20

32 A1, A2 AA032

63 A2, A3 BA063

100 A2, A3, A4 CEO100

MGLV5751 (RTI Sec 03) 2/9/05 5:52 pm Page 14

Page 15: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGF FusegearFuse switch disconnector

Switch disconnector

15

ApplicationHeavy duty fuse products for use in commercial and industrial environments, providingisolation and traditional fuse protection for electrical loads.

Features Rated for 240/415V 50/60Hz Ratings 100A, 160A, 200A, 250A, 315A, 400A, 500A, 630A TP&N Utilisation category AC20A, AC21A, AC22A, AC23B at rated current,

AC23A for ratings up to 160A Handle position provides positive contact indication Door handle prevents door being opened when switch is ON or padlocked Handle padlockable in ON and OFF positions Device may be fed to either top or bottom terminals Fuse links or copper links supplied as standard

Construction All terminals are fully shrouded Quick make and break silver plated contacts Door interlock has defeat mechanism allowing switch to be closed with door open Removable plain gland plates are fitted at top and bottom Cabling space may be increased by the addition of the cable boxes Lift off door provides greater access for installation and cabling Door opens within the width of the unit allowing units to be mounted adjacent Neutral is fitted with disconnectable link Earthing kit provided as standard Easy access to fuse links Removable cross rails allow cables to be laid in easily Direct front access to terminals without dismantling the mechanism Clear shrouds allow easy access for inspection and visual indication of contact position Steelwork finished in polyester epoxy powder, cream colour RAL9001

Technical data Standard BS EN 60947-3 Rated operational voltage 415V 50/60Hz

MGFS, MGFDRating

Rated current at 400C, A

Rated impulse voltage

Rated short time withstand Icw, A

Rated short circuit making capacity Icm

Rated short circuit breaking capacity Icn

Utilisation category at rated current

Kilowatt rating

Terminal stud

Terminal lug, maximum palm width

Maximum cable size

ReferencesRating Fuse switch disconnector Switch disconnector Cable box

(A) Part No. Part No. Part No.

Three pole and neutral

100 MGFS1003C MGFD1003C MGFX100C

160 MGFS1603C MGFD1603C MGFX160C

200 MGFS2003C MGFX250C

250 MGFS2503C MGFD2503C MGFX250C

315 MGFS3153C MGFX500C

400 MGFS4003C MGFD4003C MGFX500C

500 MGFS5003C MGFD5003C MGFX500C

630 MGFS6303C MGFD6303C MGFX630C

Fuse link dataRating (A) BS88 reference Bussman reference Cu links (Set of 3)

100 B1 CD100 MGFQ100

160 B2 DD160 MGFQ160

200 B2 DD200 MGFQ250

250 B3 ED250 MGFQ250

315 C1 EFS315 MGFQ400

400 C1 EF400 MGFQ400

500 C2 FF500 MGFQ630

630 C2 FF630 MGFQ630

100A

100

8kV

3.4kA

5kA

50kA

AC-23A

55kW

M8

20mm

50mm2

160A

160

8kV

3.4kA

5kA

50kA

AC-23A

90kW

M8

20mm

50mm2

200A

200

8kV

5.23kA

8kA

50kA

AC-23B

110kW

M10

30mm

120mm2

250A

250

8kV

5.23kA

8kA

50kA

AC-23B

130kW

M10

30mm

120mm2

315A

315

8kV

12kA

24kA

50kA

AC-23B

175kW

M12

50mm

400mm2

400A

400

8kV

12kA

24kA

50kA

AC-23B

220kW

M12

50mm

400mm2

500A

500

8kV

12kA

24kA

50kA

AC-23B

250kW

M12

50mm

400mm2

630A

630

8kV

12kA

24kA

50kA

AC-23B

300kW

M12

50mm

400mm2

MGLV5751 (RTI Sec 03) 2/9/05 5:52 pm Page 15

Page 16: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGF FusegearBusbar chambers

16

ApplicationThe wall mounting busbar chambers provide an easy means of mounting andinterconnecting fusegear products.

RangeThree ratings and three busbar lengths are availableConnection kits enable busbar chambers to be linkedand all devices connected to the bars.

Technical data Manufactured to BS EN 60439-1 Rated voltage 415V 50/60Hz Solid copper busbars rated at 200, 400 and 630A Neutral bar is fully rated Busbar chamber lengths: 750, 1200 and 1800mm Chambers have common depth (200mm) and

common height (450mm) End plates, top plates and bottom plates are fully

removable for connections and for access Steelwork finished in polyester epoxy powder,

cream colour RAL9001

Rating Length (mm) Length (mm) Length (mm)750 1200 1800Part No. Part No. Part No.

200 MGFB20007C MGFB20012C MGFB20018C400 MGFB40007C MGFB40012C MGFB40018C630 MGFB63007C MGFB63012C MGFB63018C

Busbar connection kits Each kit comprises connections for three phases and neutralRating Busbar interconnections to Cable connections to

link busbar chambers* connect to busbars**Part No. Part No.

200 MGFK200 MGFC200400 MGFK400 MGFC400630 MGFK630 MGFC630

Fuse switch connection kitsEach kit comprises connections for three phases and neutralRating Top mounted Bottom mounted

Part No. Part No.100, 160 MGFZ160 MGFZ160200, 250 MGFZ250 MGFZ250315 - 630 MGFZ630T MGFZ630

Fuse switch connection kits comprise 4 copper links with connection hardware toconnect a fuse switch to the busbars.

Note: the kit required for fitting devices of 315A or greater differs dependent on whether it is mounted aboveor below the busbar chamber.

* The busbar connection kits allow 2 or more busbar chambers to be electricallyand mechanically joined together providing facilities for a greater number of outgoing circuits.

** The cable connection kits comprise 4 bolts, nuts and washers to connect a setof cables fitted with crimped lugs to the busbars.

MGFB20007C

MGLV5751 (RTI Sec 03) 2/9/05 5:52 pm Page 16

Page 17: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 panelboards Section four

Selection table 18

22250A powerboard

250A panelboard 24

26400/630A panelboard

800A panelboard 28

301600A panelboard

Accessories 32

17

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 17

Page 18: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4Introduction

18

The Merlin Gerin range of wall and floor mounted Powerpact 4panelboards is designed, manufactured and tested to BS EN 60439-1. The structures are rigid sheet steel finished in acream colour epoxy powder (RAL 9001).

All the boards contain a unique connection system that ensuresthat all busbar/breaker connections are tightened to the correcttorque. The system comprises a tightening bolt head whichshears off when the correct torque is reached. Facilities areprovided to enable the breaker to be repositioned at a later time if so required.

The breaker range comprises single pole, single pole withswitched neutral, double pole, triple pole and three pole withswitched neutral and four pole. Incoming device ratings up to1600A and outgoing ratings up to 630A.

The extremely flexible board design allows 1, 2, 3 and 4 polebreakers to be positioned in any order on the busbar stack thusallowing maximum use of the available space and also allowingbreakers feeding associated loads to be positioned together. For this reason the number of outgoing ways in the table below is expressed in single pole ways as well as three pole ways.

Special breakers

Details of the standard breakers that may be fitted into the varioussizes of panelboard are given on the following pages.

The full range of Compact NS moulded case circuit breakersincludes a wide range of breakers for special applications, higherbreaking capacities, additional ratings and adaptations includingrotary handles and motor mechanisms for remote operation. Mostof these breakers, of ratings up to 630A, can be adapted for usein the Powerpact 4 panelboards.

To order these special breakers add the words "…for use in Powerpact 4 panelboard" to your orderingdescription of the breaker.

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 18

Page 19: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4Selection table

19

250A 250A 400/630A 800A 1600A

Powerboard Panelboard Panelboard Panelboard Panelboard

Busbar short circuit withstand 36kA, 1s 36kA, 1s 36kA, 1s 50kA, 1s 50kA, 1s

Number of outgoing ways 13SP inc incomer

17SP inc incomer

15SP (5TP)

18SP (6TP)

21SP (7TP)

27SP (9TP)

36SP (12TP)

39SP (13TP)

42SP (14TP)

54SP (18TP)

Incoming device 100A MCCB

160A MCCB

250A MCCB

400A MCCB

630A MCCB

800A MCCB

1250A MCCB

1600A MCCB

250A fuse switch

Incomer - field installable

Two incomers, mechanically interlocked

Main incoming cable entry Top

Bottom

Incoming metering

Outgoing metering

Top/bottom extension boxes

Side extension boxes

Integrated control and distribution unit

Earth leakage protection on outgoing circuits

Standard

Option

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 19

Page 20: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Merlin Gerin Powerpact 4 PanelboardThe easy steps to install a circuit breaker

20

The 4 pole busbar system ready to accept

the circuit breaker.

The circuit breaker is placed in the

panelboard and pushed up to the busbars.

1P, 2P, 3P and 4 pole breakers may be

mixed in any order on the busbars.

The circuit breaker fixing screw is fitted and

tightened to retain the breaker in the board.

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 20

Page 21: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Merlin Gerin Powerpact 4 PanelboardThe easy steps to install a circuit breaker

21

The connections to the busbars are

tightened until the tops of the connection

bolts shears off. This ensures that the

correct torque has been applied to the

connections.

The circuit breaker is now mechanically &

electrically connected in the panel board. It

is now ready for the outgoing cables.

Note how the breaker cassette fully

shrouds the busbars. Unused positions

must be fitted with blanking plates.

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 21

Page 22: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4250A powerboards

22

NS moulded case circuit breakersApplicationPowerpact 4 powerboard has a unique interconnection system which automaticallygives the correct torque settings. 1, 2, 3, or 4 pole devices may be mixed to suitthe installation needs without loss of space.

A

442

NS250

NS160

NS100

C60H MCB

NS400

NS630

NS800

Masterpact

Full discrimination simply by missing a step.

MG25C2

3 pole outgoing MCCB

ApplicationThe wall mounted Powerpact 4 powerboard is perfectly suited to installations wherespace is restricted or only a few outgoing circuits are required. They make ideal sub-main splitter boards and, by adding a mechanical interlock can be used for manualchangeover applications. These powerboards are also available in versions having metering facility. There arecut-outs to accept 96mm square meters. Metering can easily be installed on site bythe use of current transformer modules fitted to the required circuits. The necessarywiring looms are supplied with the board. For full details refer to page 37.

Technical data Manufactured and tested to BS EN 60439-1 Busbar rated at 250A at 415V, 50Hz Short circuit withstand: 36kA for 1 second Rigid folded sheet steel construction with

removable gland plates and end walls Degree of protection: IP4X Form 3b type 2 as standard Form 4b types 2 & 6 can be achieved by use of

individual disconnectable neutral links adjacent tobreakers or by the use of 4 pole breakers. Tunnelterminals are to be fitted on the breaker outgoingterminals and shrouded by short terminal shields.

Steelwork finished in polyester epoxy powder,cream RAL9001

Lockable overall sheet steel door as standard

Neutral bar Incoming: M12 Outgoing: 9 - 12 way terminal bar + 6/8 M8

bolted connections (bolts provided)

Earth connection Outgoing: 12 way terminal bar

Main earth connection Reversible M10 bolt

Dimensions: in mm

9 way 13 wayWidth 600 778Height 650 650Depth 268 268A (fixing centres) 306 484Weight kg 32 57

Incoming cabling space 260mm

Technical data Manufactured and tested to BS EN 60947-2. Ics = 100% Icu Calibration temperature: 400C Thermal adjustment: (3 and 4 pole) 0.8 - 1 x In

MCCB Icu Terminal size16 - 100A 36kA 6mm bolt160 - 250A 36kA 8mm bolt

Full technical specifications can be obtained fromCompact NS moulded case circuit breaker catalogueref. No. MGLV5558.

If you require higher breaking capacities, electronictrip or motor protection MCCBs refer to the note onpage 18.

MG25C2M

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 22

Page 23: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4How to order 250A

powerboards

23

Step 1. Select powerboard requiredMG25C2 13 SP positions. Accepts 4 pole incoming breaker & 9 SP outgoing

polesMG25C4 17 SP positions. Accepts 4 pole incoming breaker & 13 SP outgoing

polesMG25C2M as MG25P2 plus the facility to add 4 metersMG25C4M as MG25P4 plus the facility to add 5 meters

Step 3. Select powerboard accessoriesSingle pole blanking plate MGPBBPEach powerboard is supplied with 3 blanks.Side extension box MG25EXC2 spare door keys MGK33Metering position blanking plate 03908

One 3P terminal shield for 250A breaker is supplied as standard for the mainincoming terminals.

Step 4. Select MCCB accessoriesMechanical interlock (5) 29354

(5) Between toggle operated breakers. Not suitable for rotary handles.

For the range of MCCB accessories, refer to pages 32 to 34.

For fully dimensioned drawings see section 8.

MG25C2

Step 2. Select incoming and outgoing MCCBsCurrent Part No.rating (A) SP 2P 3P 4P16 MGP0161 (1) MGP0162 (2) MGP0163 MGP016425 MGP0251 (1) MGP0252 (2) MGP0253 MGP025430/32 (3) MGP0301 (1) MGP0302 (2) MGP0323 MGP032440 MGP0401 (1) MGP0402 (2) MGP0403 MGP040463 MGP0631 (1) MGP0632 (2) MGP0633 MGP063480 MGP0801 (1) MGP0802 (2) MGP0803 MGP0804100 MGP1001 (1) MGP1002 (2) MGP1003 (4) MGP1004 (4)125 MGP1251 (1) MGP1252 (2) MGP1253 MGP1254160 MGP1601 (1) MGP1602 (2) MGP1603 MGP1604200 MGP2003 MGP2004250 MGP2503 MGP2504(1) Add suffix L1, L2, L3 when selecting single pole MCCBs(2) Add suffix L1N, L2N, L3N, L12, L23, L31 when ordering double pole MCCBs (3) 30A for SP and DP, 32A for 3 and 4P.(4) For full discrimination with downstream C60H MCBs use MGP1013 (3 pole) orMGP1014 (4 pole).

Switch disconnector up to 250A MGP2503NA MGP2504NADisconnectable neutral links (occupies one SP way) MGP250NL

MGLV5751 (RTI Sec 04) 6/9/05 10:24 am Page 23

Page 24: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4250A panelboards

24

MG2C5

ApplicationThe wall mounted Powerpact 4 gives maximum flexibility to the installer.It will accept top or bottom entry main cable without modification.

Range Incoming 250A Outgoing - 15, 21, 27, or 39 single pole ways Busbar rating - 250A 4 pole

Technical data Manufactured and tested to BS EN 60439-1 Busbar rated at 250A at 415V 50Hz Short circuit withstand 36kA for 1s Rigid folded sheet steel construction with

removable gland plates Degree of protection - IP4X Form 3b type 2 as standard Form 4b types 2 & 6 can be achieved by use of

individual disconnectable neutral links adjacent tobreakers or by the use of 4 pole breakers. Tunnelterminals are to be fitted on the breaker outgoingterminals and shrouded by short terminal shields.The incoming breaker should be 4 pole breakeror have a disconnectable link fitted adjacent tothe 3 pole breaker.

Steelwork finished in polyester epoxy powdercream colour RAL9001

Lockable overall sheet steel doors as standard

Incoming devices The main incoming device is side mounted at the

bottom right hand side If a 4 pole incomer is used, the number of

outgoing ways available is reduced by one singlepole way

The main incoming terminal shroud can bepositioned to suit a 3P or 4P incoming breaker

Neutral bar Incoming M8 bolted connection Outgoing - one connection per single pole way:

10mm dia

Earth bar Incoming M8 bolted connection Outgoing - one connection per single pole way:

10mm dia

Dimensions In mm

NS moulded case circuit breakersA range of low breaking capacity 3 pole devicescovers the fault levels encountered at this level ofdistribution. Powerpact 4 panelboards have a uniqueinterconnection system which automatically gives thecorrect torque settings. 1, 2, 3 and 4 pole devicesmay be mixed to suit the installation needs withoutloss of space.

Technical data Manufactured and tested to BS EN 60947-2 Ics = 100% Icu Calibration temperature 400C Thermal adjustment (3 and 4 pole)

16 - 250A = 0.8 - 1x In

Type Rating Icu Terminal MGPE 16 - 125 16kA M6 boltMGP 16 - 100 36kA M6 boltMGP 125 - 250 36kA M8 bolt

Full technical specifications can be obtained fromCompact NS moulded case circuit breaker catalogueRef. No. MGLV5558.

15 21 27 39(5-TP) way (7-TP) way (9-TP) way (13-TP) way

Width 853 853 853 853Height 680 785 890 1075Depth 270 270 270 270Weight kg 40 44 50 60

Gland plate to incomer terminals 198 mm to first pole

NS250

NS160

NS100

C60H MCB

NS400

NS630

NS800

Masterpact

Full discrimination simply by missing a step.

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 24

Page 25: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4How to order 250A

panelboards

25

Step 1. Select panelboard requiredMG2C5 15 outgoing single pole waysMG2C7 21 outgoing single pole waysMG2C9 27 outgoing single pole waysMG2C13 39 outgoing single pole ways

Step 2. Select incoming deviceRating (A) 100A 160A 250AMCCB 3 pole MGP1003 MGP1603 MGP2503MCCB 4 pole MGP1004 MGP1604 MGP2504Switch Disconnector 3 pole MGP1003NA MGP1603NA MGP2503NASwitch disconnector 4 pole MGP1004NA MGP1604NA MGP2504NAFuse switch (5) MG2C250FSLug unit 3 pole (6) MGP2503LLLug unit 4 pole (6) MGP2504LL

Step 3. Select outgoing deviceCurrent Part No. 16kA 36kA 36kArating (A) SP 2P 3P 3P 4P16 MGP0161 (1) MGP0162 (2) MGPE0163 MGP0163 MGP016425 MGP0251 (1) MGP0252 (2) MGPE0253 MGP0253 MGP025430/32 (3) MGP0301 (1) MGP0302 (2) MGP0323 MGP032440 MGP0401 (1) MGP0402 (2) MGPE0403 MGP0403 MGP040450 MGP0501 (1) MGP0502 (2) MGP0503 MGP050463 MGP0631 (1) MGP0632 (2) MGPE0633 MGP0633 MGP063480 MGP0801 (1) MGP0802 (2) MGPE0803 MGP0803 MGP0804100 MGP1001 (1) MGP1002 (2) MGPE1003 MGP1003 (4) MGP1004 (4)125 MGP1251 (1) MGP1252 (2) MGPE1253 MGP1253 MGP1254160 MGP1601 (1) MGP1602 (2) MGP1603 MGP1604(1) Add suffix L1, L2, L3 when selecting single pole MCCBs(2) Add suffix L1N, L2N, L3N, L12, L23, L31 when ordering double pole MCCBs(3) 30A for SP and 2P, 32A for 3P and 4P(4) For full discrimination with downstream C60H MCBs use MGP1013 (3 pole) or MGP1014 (4 pole)(5) This incoming unit is an additional enclosure that fits above or below the standard panelboard. It comescomplete with all connections and accessories to electrically and mechanically join the enclosures(6) Protection must be provided upstream by a suitably rated breaker.

Disconnectable neutral link (occupies one SP way) 250A MGP250NL

Step 4. Select panelboard accessoriesSingle pole blanking plate (3 supplied with each board) MGPBBPTop/bottom 200mm extension box MG6CEX2 spare door keys MGK33

Step 5. Select MCCB accessoriesFor the range of MCCB accessories available refer to pages 32 to 34.

For fully dimensioned drawings see section 8.

1P & 2P MCCB

3 Pole MCCB

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 25

Page 26: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4400/630A panelboards

26

NS250

NS160

NS100

C60H MCB

NS400

NS630

NS800

Masterpact

ApplicationThe wall mounted Powerpact 4 gives maximum flexibility to the installer.It can be arranged for top or bottom entry without the use of kits.

Range Incoming up to 250, 400 or 630A Outgoing - 18, 36 or 54 single pole ways Busbar rating - 630A 4 pole

Technical data Manufactured and tested to BS EN 60439-1 Busbar rated at 630A at 415V, 50Hz Short circuit withstand 36kA for 1

second Rigid folded sheet steel construction with removable

gland plates and end walls Degree of protection - IP4X Form 3b type 2 as standard Form 4b types 2 & 6 can be achieved by use of

individual disconnectable neutral links adjacent tobreakers or by the use of 4 pole breakers. Tunnelterminals are to be fitted on the breaker outgoingterminals and shrouded by short terminal shields.The main neutral bar either side of the incomershould be removed and discarded together with theconnecting copper bar. The incoming breakershould be 4 pole breaker or have a disconnectablelink fitted to the left of a 3 pole breaker.

Steelwork finished in polyester epoxy powder creamcolour RAL9001

Lockable overall sheet steel doors as standard

Neutral bar Incoming M12 bolted connection Outgoing (all bolts provided)

18 way = 10 x M8 bolts36 way = 16 x M8 bolts54 way = 22 x M8 bolts

Earth bar Outgoing 24 x 25mm2 tunnel terminal

Main earth connections 2 x reversible M10 bolt

Top entryFor top entry main cables the board may be inverted. The spare set of labels supplied should be used to correctly label the board. Ensure that a “top entry” incomer is selected

Dimensions In mm

6 way 12 way 18 wayWidth 850 850 850Height 1178 1493 1808Depth 270 270 270A fixing centres 1035 1350 1665Weight kg 66 89 98

Gland plate to incomer terminals 250A - 375mm 400A - 290mm 630A - 290mm

NS moulded case circuit breakersPowerpact 4 panelboards have a unique interconnection system which automatically gives thecorrect torque settings. 1, 2, 3, and 4 pole devicesmay be mixed to suit the installation needs withoutloss of space.

Technical data for circuit breakers Manufactured and tested to BS EN 60947-2 Ics = 100% Icu Calibration temperature 400C Thermal adjustment (3 and 4 pole)

16 - 250A = 0.8 - 1 x In400 - 630A = 0.4 - 1 x In

MCCB Icu Terminalsize16 - 100A 36kA 6mm bolt160 - 250A 36kA 8mm bolt400 - 630A 50kA 10mm bolt

Earth fault protection May be added to any 4 pole MCCB Sensitivities 30, 300mA, 1, 3 and 10A Time delay 0, 60, 150, 310 milli-seconds

Metering The design of these PP4 panelboards allows the

easy, site installation of metering facilities toincoming and outgoing supplies. For detailsplease refer to the metering section on page 37.

Full technical specifications can be obtained fromour MCCB catalogue

If you require higher breaking capacities, electronictrip or motor protection MCCBs refer to the note onpage 18.

Full discrimination simply by missing a step.

710

A

MG6C6

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 26

Page 27: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4How to order 400/630A

panelboards

27

Step 2. Select incoming deviceBottom entry Top entry

Rating (A) 250A 400A 630A 250A 400A 630AMCCB 3 pole MGP2503 MGP4003 MGP6303 MGP2503T MGP4003T MGP6303TMCCB 4 pole MGP2504 MGP4004 MGP6304 MGP2504T MGP4004T MGP6304TSwitch disconnector 3 pole MGP2503NA MGP4003NA MGP6303NA MGP2503NAT MGP4003NAT MGP6303NATSwitch disconnector 4 pole MGP2504NA MGP4004NA MGP6304NA MGP2504NAT MGP4004NAT MGP6304NATDirect connection - - MGPINC - - -For cables greater than 240mm2 the use of a top/bottom extension box is recommended

The line (supply) terminals on the incoming device must be suitably shrouded. The board is supplied with 1 - 3 pole shroudfor a 400/630A breaker. For other breakers suitable terminal shields should be ordered seperately250A 3 pole 29323250A 4 pole 29324400/630A 4 pole 32565Note: These terminal shields are supplied in pairs.

Step 1. Select panelboard required (Ways in number at ≤250A)MG6C6 18 outgoing single pole waysMG6C12 36 outgoing single pole waysMG6C18 54 outgoing single pole ways

Step 3. Select outgoing MCCBsCurrent Part No.rating (A) SP 2P 3P 4P16 MGP0161 (1) MGP0162 (2) MGP0163 MGP016425 MGP0251 (1) MGP0252 (2) MGP0253 MGP025430/32 (6) MGP0301 (1) MGP0302 (2) MGP0323 MGP032440 MGP0401 (1) MGP0402 (2) MGP0403 MGP040463 MGP0631 (1) MGP0632 (2) MGP0633 MGP063480 MGP0801 (1) MGP0802 (2) MGP0803 MGP0804100 MGP1001 (1) MGP1002 (2) MGP1003 (7) MGP1004 (7)125 MGP1251 (1) MGP1252 (2) MGP1253 MGP1254160 MGP1601 (1) MGP1602 (2) MGP1603 MGP1604200 MGP2003 MGP2004250 MGP2503 MGP2504400 (5) MGP4003 (3) MGP4004 (4)630 (5) MGP6303 (3) MGP6304 (4)(1) Add suffix L1, L2, L3 when selecting single pole MCCBs(2) Add suffix L1N, L2N, L3N, L12, L23, L31 when ordering double pole MCCBs(3) 4 SP ways used, requires shrouding kit, see page 34.(4) 6 SP ways used, requires shrouding kit, see page 34, MGPBB25 1/2 pole shrouding plate.(5) When fitting 400A & 630A breakers a side extension box will almost certainly be required.(6) 30A for SP and DP, 32A for 3 and 4P.(7) For full discrimination with downstream C60H MCBs use MGP1013 (3 pole) or MGP1014 (4 pole)Disconnectable neutral link 250A 630A

MGP250NL MGP630NL(1 SP way) (2 SP ways and

requires MGPBB25 1/2 pole shrouding plate)

Step 4. Select panelboard accessoriesSingle pole blanking plate MGPBBP (each panelboard is supplied with 3 blanks

Side extension box for MG6P6 MG6P12 MG6P18250mm MGPXC206 MGPXC212 MGPXC218500mm MGPXC506 MGPXC512 MGPXC518

Top/bottom extension box 200mm MG6CEX MG6CEX MG6CEXShrouding kit MGPCH6 MGPCH12 MGPCH182 spare door keys MGK33

Step 5. Select MCCB accessoriesFor the range of MCCB accessories available refer to pages 32 to 34.For fully dimensioned drawings see section 8.

Corner unitsFor squaring off a panelboard whena top or bottom extension and sideextension is used together.

Extension boxTop/bottom Side Part No.200 250 MGPC2025200 500 MGPC2050

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 27

Page 28: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4800A panelboards

28

768

172

A

NS250

NS160

NS100

C60H MCB

NS400

NS630

NS800

Masterpact

ApplicationThe wall mounted Powerpact 4 gives maximum flexibility to the installer.It can be supplied suitable for top or bottom entry.

Range Incoming 800A Outgoing - 18, 36 or 54 single pole ways Busbar rating - 800A 4 pole

Technical data Manufactured and tested to BS EN 60439-1 Busbar rated at 800A at 415V, 50Hz. Short circuit withstand 50kA for 1 second Rigid folded sheet steel construction with removable

gland plates and end walls Degree of protection: IP4X Form 3b type 2 as standard Form 4b types 2 & 6 can be achieved by use of

individual disconnectable neutral links adjacent tobreakers or by the use of 4 pole breakers. Tunnelterminals are to be fitted on the breaker outgoingterminals and shrouded by short terminal shields.

The main neutral bar either side of the incomershould be removed and discarded together with theconnecting copper bar. The incoming breakershould be 4 pole breaker.

Steelwork finished in polyester epoxy powder creamcolour RAL9001

Lockable overall sheet steel doors as standard

Neutral bar Incoming M12 bolted connection Outgoing (all bolts provided)

18 way = 10 x M8 bolts36 way = 16 x M8 bolts54 way = 22 x M8 bolts

Earth bar Incoming M10 bolted connection Outgoing 24 x 25mm2 tunnel terminal

Main earth connections 2 x reversible M10 bolt

Dimensions In mm

6 way 12 way 18 wayWidth 850 850 850Height 1580 1896 2210Depth 270 270 270A 1035 1350 1665Weight kg 86 104 122

Gland plate to incomer terminals 800A - 490mm Main connection M12 bolt

NS outgoing moulded case circuitbreakersPowerpact 4 panelboards have a unique interconnection system which automatically gives thecorrect torque settings. 1, 2, 3, and 4 pole devicesmay be mixed to suit the installation needs withoutloss of space.

Technical data for circuit breakers Manufactured and tested to BS EN 60947-2 Ics = 100% Icu Calibration temperature 400C Thermal adjustment (3 and 4 pole)

16 - 250A = 0.8 - 1 x In400 - 630A = 0.4 - 1 x In800A = 0.4 - 1 x In

MCCB Icu Terminal size16 - 100A 25kA 6mm bolt160 - 250A 36kA 8mm bolt400 - 630A 45kA 10mm bolt800A 50kA 2 x 12mm bolt

Earth fault protection May be added to any 4 pole MCCB Sensitivities 30, 300mA 1, 3, and 10A Time delay 0, 60, 150, 310 milli - seconds

Metering The design of these PP4 panelboards allows the

easy, site installation of metering facilities toincoming and outgoing supplies. For detailsplease refer to the metering section on page 37.

Full technical specifications can be obtained fromour MCCB catalogue.

If you require higher breaking capacities, electronictrip or motor protection MCCBs refer to page 18.

Full discrimination simply by missing a step.

MG8C6

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 28

Page 29: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4How to order 800A

panelboards

29

Step 1. Select panelboard required (supplied with top/bottom extension box fitted)Main cable entry 18 way (6 TP ways) 36 way (12 TP ways) 54 way (18 TP ways)Bottom MG8C6 MG8C12 MG8C18Top MG8C6T MG8C12T MG8C18T

Step 2. Select incoming device (all boards accept 3 or 4 pole incomers) 3 pole 4 poleNS800N MCCB with Micrologic 5.0 control unit MGP8003B5 MGP8004B5NS800NA switch disconnector MGP8003NA MGP8004NANS800 breakers with alternative control units, motor operators, rotary handles and internal accessories may be fitted as incomers to theseboards. For full details refer to our Compact LV circuit breaker and switch-disconnectors catalogue. When specifying these alternativebreakers you must include one long terminal shield and one set of phase separators.

Step 3. Select outgoing MCCBsCurrent Part No.rating (A) SP 2P 3P 4P16 MGP0161 (1) MGP0162 (2) MGP0163 MGP016425 MGP0251 (1) MGP0252 (2) MGP0253 MGP025430/32 (6) MGP0301 (1) MGP0302 (2) MGP0323 MGP032440 MGP0401 (1) MGP0402 (2) MGP0403 MGP040463 MGP0631 (1) MGP0632 (2) MGP0633 MGP063480 MGP0801 (1) MGP0802 (2) MGP0803 MGP0804100 MGP1001 (1) MGP1002 (2) MGP1003 (7) MGP1004 (7)125 MGP1251 (1) MGP1252 (2) MGP1253 MGP1254160 MGP1601 (1) MGP1602 (2) MGP1603 MGP1604200 MGP2003 MGP2004250 MGP2503 MGP2504400 (5) MGP4003 (3) MGP4004 (4)630 (5) MGP6303 (3) MGP6304 (4)(1) Add suffix L1, L2, L3 when selecting single pole MCCBs(2) Add suffix L1N, L2N, L3N, L12, L23, L31 when ordering double pole MCCBs(3) 4 SP ways used, requires shrouding kit, see page 00.(4) 6 SP ways used, requires shrouding kit, see page 00, MGPBB25 1/2 pole

shrouding plate.(5) When fitting 400A & 630A breakers a side extension box will almost certainly

be required.(6) 30A for SP and DP, 32A for 3 and 4P.(7) For full discrimination with downstream C60H MCBs use MGP1013 (3 pole) or

MGP1014 (4 pole)Disconnectable neutral link 250A 630A

MGP250NL MGP630NL(1 SP way) (2 SP ways and

requires MGPBB25 1/2 pole shrouding plate)

For the range of MCCB accessories available, refer topage 32 to 34.

For fully dimensioned drawings see section 8.

Step 4. Select panelboard accessoriesSingle pole blanking plate MGPBBP (each panelboard is supplied with 3 blanks)

Side extension box for 6 way 12 way 18 way250mm MGPXC206 MGPXC212 MGPXC218500mm MGPXC506 MGPXC512 MGPXC518

Top/bottom 200mm ext. box MG6CEX MG6CEX MG6CEXShrouding kit MGPCH6 MGPCH12 MGPCH182 spare door keys MGK33

Step 5. Select MCCB accessories Corner unitsFor squaring off a panelboard whena top or bottom extension and sideextension is used together.

Extension boxTop/bottom Side Part No.200 250 MGPC2025200 500 MGPC2050400 250 MGPC4025400 500 MGPC4050A 400mm extension box is fitted asstandard at the incoming end ofthe board.

3 Pole MCCB

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 29

Page 30: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 41600A panelboards

30

NS250

NS160

NS100

C60H MCB

NS400

NS630

NS800

Masterpact

ApplicationThe floor mounted Powerpact 4 is the easy answer to large power requirements. It provides an off-the-shelfsolution to switchboard style standard distribution applications.

Range Incoming: up to 1600A Outgoing: 14TP ways (42 SP ways) Top or bottom main cable entry Incoming metering included as standard. Outgoing

metering an option.

Technical data Manufactured and tested to BSEN60439-1 Busbars rated at 1600A at 415V, 50Hz Short circuit withstand 50kA for 1s Rigid folded sheet steel construction with removable

gland plates and end covers Steelwork finished in polyester epoxy powder, cream

colour RAL9001 Degree of protection: IP30 Form 3b type 2 as standard Form 4b types 2 & 6 can be achieved by use of

individual disconnectable neutral links adjacent tobreakers or by the use of 4 pole breakers. Tunnelterminals are to be fitted on the breaker outgoingterminals and shrouded by short terminal shields.

A side extension cubicle is available as an option forhandling large cables

Metering A PowerLogic PM700PMG multi function digital

meter is fitted as standard to monitor the incomingsupply.Readings available voltage, current, frequency,power, energy, demand values and harmonicdistortion. The meter also provides a pulse outputfor kWh and kVArh.

A side extension cubicle may be fitted that hasprovision for metering all outgoing circuits. Fordetails see Section 5. This cubicle also acts as acable extension box.

NS moulded case circuit breakersPowerpact 4 panelboards have a unique interconnection system which automatically gives thecorrect torque settings. 1, 2, 3, and 4 pole devicesmay be mixed to suit the installation needs withoutloss of space.

Technical data for circuit breakers Manufactured and tested to BS EN 60947-2 Ics = 100% Icu Calibration temperature 400C Thermal adjustment (3 and 4 pole)

16 - 250A = 0.8 - 1 x In400 - 630A = 0.4 - 1 x In1250 - 2000A = 0.4 x In

MCCB Icu Terminal size16 - 100A 25kA 6mm bolt160 - 250A 36kA 8mm bolt400 - 630A 45kA 10mm bolt

Earth fault protection May be added to any 4 pole MCCB Sensitivities 30, 300mA 1, 3, 10A Time delay 0, 60, 150, 310 milli - seconds

Full technical specifications can be obtained from ourCompact NS moulded case circuit breaker catalogueRef. No. MGLV5558.

If you require higher breaking capacities, electronictrip or motor protection MCCBs refer to page 18.

Full discrimination simply by missing a step.

Dimensions mm

Panelboard with extension cubicle Width 1256 1656Height 2106 2106 Depth 450 450 Weight 375kg +30kg

Dimension of main terminals from gland plate 708mm Main terminals will accept up to 3 lugs 400mm2 per phase

1600A panelboard with plain extension cubicle

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 30

Page 31: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4How to order 1600A panelboards

31

Step 1. Select panelboard requiredMain cable entry 14 TP ways Plain extension cubicle Metering extension cubicleBottom MG16C14 MG16CEX4 MG16CEM4Top MG16C14T MG16CEX4 MG16CEM4

Step 4. Select panelboard accessoriesSingle pole blanking plate MGPBBP Each board is supplied with 6 blanksSide extension boxes see above More than one extension cubicle may be fitted if

required

Step 5. Select MCCB accessoriesFor the range of MCCB accessories available refer to pages 32 to 33.

Step 3. Select outgoing MCCBsCurrent Part No.rating (A) SP 2P 3P 4P16 MGP0161 (1) MGP0162 (2) MGP0163 MGP016425 MGP0251 (1) MGP0252 (2) MGP0253 MGP025430/32 (5) MGP0301 (1) MGP0302 (2) MGP0323 MGP032440 MGP0401 (1) MGP0402 (2) MGP0403 MGP040463 MGP0631 (1) MGP0632 (2) MGP0633 MGP063480 MGP0801 (1) MGP0802 (2) MGP0803 MGP0804100 MGP1001 (1) MGP1002 (2) MGP1003 (6) MGP1004 (6)125 MGP1251 (1) MGP1252 (2) MGP1253 MGP1254160 MGP1601 (1) MGP1602 (2) MGP1603 MGP1604200 MGP2003 MGP2004250 MGP2503 MGP2504400 MGP4003 (3) MGP4004 (4)630 MGP6303 (3) MGP6304 (4)(1) Add suffix L1, L2, L3 when selecting single pole MCCBs(2) Add suffix L1N, L2N, L3N, L12, L23, L31 when ordering double pole MCCBs (3) 4 SP ways used(4) 6 SP ways used, requires shrouding kit and MGPBB25 1/2 pole shrouding plate.(5) 30A for SP and DP, 32A for 3 and 4P.(6) For full discrimination with downstream C60H MCBs use MGP1013 (3 pole) or MGP1014 (4 pole)Disconnectable neutral link 250A 630A

MGP250NL MGP630NL(1 SP way) (2 SP ways and

requires MGPBB25 1/2 pole shrouding plate)

Step 2. Select incoming deviceAll boards accept 3 or 4 pole incomers3 pole 4 pole

NS1250N MCCB with Micrologic 5.0 control unit 33564 33566NS1600N MCCB with Micrologic 5.0 control unit 33568 33570

NS1250NA switch disconnector 33489 33494NS1600NA switch disconnector 33490 33495Many other options are available for these incoming units including rotary handles, electrical operators,auxiliary switches, voltage releases and other control units. Please specify at time of order.The Micrologic 5.0 unit is recommended to ensure discrimination with outgoing breakers

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 31

Page 32: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4Accessories

32

Toggle padlocking attachments clip fixing in OFF position Current rating Removable Fixed 250A 29370 29371630A 29370 32631800A 44936 32631

Residual current protection modulesUsing 4 pole residual current add-on modules (Vigi block) for incoming or outgoing ways (requires a 4 pole MCCB).

Frame rating Earth leakage Current Vigi moduletripping current rating Part No.options (A) MCCB

Up to 160A 0.03 - 0.3 - 1 - 3 - 10 * NS100/160 29211200 - 250A 0.03 - 0.3 - 1 - 3 - 10 * NS250 31536400 - 630A 0.3 - 1 - 3 - 10 - 30 * NS400/630 32456* Time delay setting (ms) 0 - 60 - 150 and 310 (30mA - instantaneous only).(i) For combinations of items of RCDs, metering and remote metering please contact us for further information.

Ammeter3 phase ammeter complete with CT’s (mounted on the breaker). Can be fitted on incoming or outgoing device.

Current rating Part No.3 Pole 4 Pole

NS100 29455 29456NS160 30555 30556NS250 31565 31566NS400 32655 32656NS630 32855 32856

Metering facility3 phase current transformer module with voltage measurement outputsFits directly on the terminals of the breaker.The voltage measurement outputs have inbuilt protection with automatic resetSuitable for use with the PowerLogic range of meters

Part No.Breaker CT ratio VA output Class at VA 3 pole 4 pole

outputNS100 125/5 1.1 1.0 29461 29462NS160 150/5 1.1 1.0 30561 30562NS250 250/5 1.1 0.5 31569 31570NS400 400/5 2.0 0.5 32653 32654NS630 600/5 2.0 0.5 32861 32862

Current transformer module3 phase current transformer moduleFits directly on the terminals of the breaker.

Part No.Breaker CT ratio VA output Class at VA 3 pole 4 pole

outputNS100 100/5 1.6 3.0 29457 29458NS160 150/5 3.0 3.0 30557 30558NS250 250/5 5.0 3.0 31567 31568NS400 400/5 8.0 3.0 32657 32658NS630 600/5 8.0 3.0 32857 32858

29211

29455

29457

MCCB + Rotary handle

Rotary handles with inbuilt padlocking facilities(for 3 or 4 pole devices only)Current rating Black Red/YellowUp to 250A 29337 29339400/630A 32597 32599

MCCB + Motor operator

Motor operator moduleAll 3 pole and 4 pole breakers up to 250A can be fitted with a motor operatormechanism allowing remote opening and closing of the circuit breaker.Operating voltages50Hz a.c. 48 - 415Vd.c. 24 - 250VSpecify requirements at time of ordering the breaker.

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 32

Page 33: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4Accessories

33

Auxiliary switch (for 3 or 4 pole devices only)For all MCCBs. Used to indicate open, closed or tripped status.SDE adaptor required for trip unit devices up to 250A TM or MA (to indicate trip onovercurrent).If you need to indicate open, closed and tripped status, two auxiliary switches willbe needed.

Voltage releases to fit all MCCBs 16/630A (for 3 or 4 pole devices)AC 50/60Hz:Voltage Part No. Part No.(V) Shunt trip Undervoltage release 200/240 29387 29407380/415 29388 29408Other voltages available - refer to Compact NS catalogue.

Part No.Auxiliary changeover switch 29450SDE adaptor 29451

Connection accessoriesBare cable connectorsCapacity Breaker Part No. Part No.

rating (max.) set of 3 set of 41.5 - 95mm2 160 29242 2924310 - 185mm2 250 29259 2926035 - 300mm2 630 32479 324802 x 95 - 240mm2 630 32481 32482

Crimp cable lugs (supplied with phase barriers)120mm2 copper 250 29252 29256150mm2 copper 250 29253 29257185mm2 copper 250 29254 29258240mm2 copper 630 32500 32501300mm2 copper 630 32502 32503150mm2 aluminium 250 29504 29505185mm2 aluminium 250 29506 29507240mm2 aluminium 630 32504 32505300mm2 aluminium 630 32506 32507

29242

29450

29387

SpreadersA Pole pitch mm Quantity Part No.250 45 Set of 3 31563250 45 Set of 4 31564630 52.5 Set of 3 32490630 52.5 Set of 4 32491

31564

Terminal shields (supplied in pairs)Current rating (A) Part No.Up to 160 A single pole and 250A neutral link 29320Up to 160A 2 pole 29320 x 2Up to 250A 3 pole 29323Up to 250A 4 pole 29324Up to 400/630A 3 pole 32564Up to 400/630A 4 pole 32565For shielding a TP MCCB with neutral link use the 4 pole terminal shield.

Terminal shields

MGPBBP

Single pole shrouding platesMGPBBP MGPBB25Single pole shrouding plates arerequired for each unoccupied outgoing way.

In addition a 25mm shrouding plate isalways required when 4 pole 400A or630A circuit breakers are mounted onthe outgoing pan assembly.

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 33

Page 34: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4Accessories

34

Extension boxesTop/bottomFor spreading large cables, mounting current transformers or control gear.

SideProvides additional cabling space or space for mounting current transformers or metering.

CornerAllows a board to be squared off when a top/bottomextension and a side extension are fitted to apanelboard.

NoteThe use of side extension boxes is recommendedwhen 400/630A outgoers are fitted. When outgoingcircuits have earth fault protection or direct ammetersa side extension box and shrouding kit must befitted.

For ordering references, see Panelboard Selectionpages 22 - 29.

MGPEXS6

Replacement items

Door and cover assembly250A powerboard 9 way MG25FCC2

13 way MG25FCC49 way + metering MG25FCC2M13 way + metering MG25FCC4M

400/630A 18 way MG6FCC6panelboard 36 way MG6FCC12

54 way MG6FCC18800A 18 way MG8FCC6panelboard 36 way MG8FCC12

56 way MG8FCC18Gland plate for400/630/800A panelboard MGPGPC8Door lock kit up to 800A MGPP4S0072 spare door keys MGK33Touch up paint RAL9001 Spray 08962

Brush 08961Adhesive drawing pocket RAL9001 08963

Shrouding kit (400/630A and 800A panelboards only)Provides additional support for device and shrouding for front cover. One shrouding kit must be used per side when fitting either outgoing 400/630AMPMCCBs or outgoing ammeter and/or earth leakage protection. In addition to theshrouding kit an additional 25mm three stage filler piece is required when 4 pole400A or 630AMP circuit breakers are fitted on the outgoing pan assemblyMGPTSF25.Number of outgoing ways Shrouding kitSP TP Part No.18 6 MGPCH636 12 MGPCH1254 18 MGPCH18

MGPSHR6

Integrated control and distributionsystem (ICDS)Side mounted on 400 - 800A panelboards.

The ICDS unit offers the facility to incorporate MCBs,and command and control products into a singleintegrated unit.

The ICDS has mounting rails to accept: An Isobar 4 TP&N pan assembly An Isobar 4 SP&N pan assembly or a DIN rail to

accept 34 x 9mm modules A tray for control gear

Order referencesTo fit 6 way panelboardEnclosure MGPXCA6Pan assemblies

8 way TP&N MGBN8E15 way SP&N MGAN15P

To fit 12 way panelboardEnclosure MGPXCA12Pan assemblies

16 way TP&N MGBN16E15 way SP&N MGAN15P

The Isobar 4c pan assemblies need to be orderedseperately

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 34

Page 35: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4Auxiliary function

possibilities

35

MN/MX Rotary handle

OF1 OF2 OF3 SD SDE

SDV

OF - Changeover auxiliary contactSD - Changeover alarm switchMX - Shunt tripMN - Undervoltage releaseSDE - Fault alarmSDV - Earth fault alarmCAF - Early make auxiliary contacts (with rotary handle)CAO - Early break auxiliary contacts (with rotary handle)COM - Communications function

All accessories are capable of being fitted on site.Full details may be obtained from the Compact NSmoulded case circuit breaker catalogue Ref. No. PB 5079.

Manually operated device

OF1

OF2

OF3

SD

COM

CA

F1

CA

F2

CA

O1

CA

O2

SD

E MNorMX

rotary handle

MN/MX Motormechanismor Rotary handle

OF SD SDE OF2

SDV

NS100/160/250 NS400/630

NS800/1600

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 35

Page 36: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

36

MGLV5751 (RTI Sec 04) 6/9/05 10:25 am Page 36

Page 37: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 metering facilities Section five

38Metering facilities for incoming & outgoing devices

PowerLogic power meter series PM700MG 41

37

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 37

Page 38: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 Metering facilities for incomingand outgoing circuits

38

The Merlin Gerin range of panelboards includes the facilities for metering incomingand outgoing circuits of panelboards, using standard components that can beadded to boards during installation. No longer is there a need to have panelsspecially manufactured on long lead times.

ApplicationTo meet the requirements of Part L2 of the Building Regulations it is necessary forbuilding owners and/or occupiers to monitor and control the energy used in everybuilding. It is recommended that electrical distribution boards having a load of50kW or more should have separate metering. On a three phase 400V supply thisequates to 70A per phase so is likely to cover most loads from a panelboard with630A incoming supply.

Power meterAll kits either use or recommend the use of Merlin Gerin PM700 range of multi-function power meters. There are 3 modelsPM700MG Basic meterPM700PMG as the PM700MG but with pulse outputs for kWh and kVArhPM710MG as the PM700MG but with MODBUS communications.For full details of these meters please refer to page 41

As standard, the meter fitted into incoming meter kits is the PM700PMG withpulse outputs. The meter accuracy is 0.5% of reading from 20% to 120% forcurrent and voltage and 1% for power. The real energy reading complies with IEC62053-21 Class 1.The meter is in a DIN sized 96 mm sq. case fitting into a 92 mm sq. aperture.

Power meter inputsThe NS moulded case circuit breakers up to 630A have current transformermodules that fit directly on to the load terminals of the breaker. As well as thecurrent transformer coils they also have self protected voltage connections offeach phase. This eliminates the need to have additional overcurrent protection onthese circuits. The meter is wired direct from this CT module without the need forany intermediate devices.

Panelboard configurations250A Powerboard.There are two versions of this equipment, basic or with the facility to havemetering.The meter versions allow metering to be added to any 3 or 4 pole MCCB fitted inthe board. All components are easily fitted; there are no extension boxes to fit orapertures to cut.The meters are positioned behind the overall lockable door preventingunauthorised access to the meters. MG25P2M has 4 apertures, MG25P4M has 5.

Note: the meters and CT modules must be ordered separately. The wiring loomsto link the CT modules to the meters are included with the panelboards

Metering options are not available for the 250A panelboard. It is recommendedthat a MG6Pxx board is used with a 250A incomer

630 & 800A PanelboardsIncoming meteringThis is easily added to a board when it is first being installed. The kit comprises anextension box that houses the meter and, when fitted to the same end of theboard as the incomer, provides additional space for the main incoming cables. Allcomponents including the meter, CTs and wiring is included in the kit. The meter isfully set up for the CT ratio and the voltage configuration.

Outgoing circuit meteringMetering can be fitted to some or all of the three phase outgoing circuits on 630A& 800A boards whether the boards are fitted with incoming metering or not.

Ordering references250A Powerboard with metering facility13 SP positions MG25C2M17 SP positions MG25C4M

MG25C2M

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 38

Page 39: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 Metering facilities for incoming

and outgoing circuits

39

The arrangement consists of side extension boxes that house the meters and alsoprovide additional cabling space. Meters and current transformers are orderedseparately to meet the needs of the installation. The necessary cable looms areincluded with the steelwork.The meters are mounted on hinged doors. The box also contains the auxiliarybusbar that provides the 240V control supply for the meters.The left hand extensions have sufficient meter positions for half the number ofoutgoing ways. The right hand extensions have positions for half the number ofoutgoing ways plus three additional positions. These extra positions may be usedfor additional metering or mounting surge arresters, control fuses etc. The lowertwo positions have a transparent window and DIN rail. This can be removed if notrequired.Note: the meters, CT modules and surge arresters must be ordered separately

Incoming and outgoing metering for boards up to 630A(This arrangement is not applicable for boards fitted with MGPINC directconnections).When both incoming and outgoing metering is required there is a very costeffective solution by incorporating the incoming metering into the right hand sideextension box. Components required are Standard extension box MG6PEX to provide the required cable spreading

space Current transformer module to fit on line side of incoming breaker. See details

on page 40. PM700 meter. Two MSPP12 corner units, optionalThe meter should be cabled to the CT module according to the diagram supplied.(loom not supplied) The auxiliary supply to the meter should be taken from one phase and neutral andmust be suitably fused.Note. A warning notice should be placed in the board as the voltage connectionsare taken off the live side of the main breaker.

MG6Pxx 630A boardIncoming metering kit 400A MG64M

630A MG66MMG8Pxx 800A boardIncoming metering kit 800A MG88M

630A & 800A outgoing metering side extension boxes6 way board left hand side (*) 3 meter positions MGPCM6L

right hand side (*) 6 meter positions MGPCM6R12 way board left hand side (*) 6 meter positions MGPCM12L

right hand side (*) 9 meter positions MGPCM12R18 way board left hand side (*) 9 meter positions MGPCM18L

right hand side (*) 12 meter positions MGPCM18R(*) When the board is inverted for top entry main cables these side extensions fit on the otherside of the board

6 way 12 way 18 way

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 39

Page 40: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 Metering facilities for incoming and outgoing circuits

40

Current transformer modules for direct fitting to NS breakers in all boardsBreaker Poles CT ratio ReferenceNS100 3 125/5 29461NS100 4 125/5 29462NS160 3 150/5 30561NS160 4 150/5 30562NS250 3 250/5 31569NS250 4 250/5 31570NS400 3 400/5 32653NS400 4 400/5 32654NS630 3 600/5 32861NS630 4 600/5 32862

Unused 92 x 92 metering apertures can be blanked off using Part No. 03908

1600A Panelboards

Incoming meteringA PM700PMG meter is fitted as standard in the boards. The meter is fully set upfor use on a 415V 3ph 4 wire system and for use with the 1600/5 currenttransformers that are installed on the busbars.

Outgoing circuit meteringMetering can be fitted to some or all of the three phase outgoing circuits in theseboards. The arrangement consists of a side extension cubicle that houses themeters and also provides additional cabling space. Meters and currenttransformers are ordered separately to meet the needs of the installation. Thenecessary cable looms are included with the cubicle.The meters are mounted on the front, hinged cover of the cubicle and can bealigned with their associated breaker.The cubicle also contains the auxiliary busbar that provides the 240V controlsupply for the meters

1600A PanelboardSide extension cubicle MG16CEM4

1600A panelboard with metering on side extension

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 40

Page 41: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

PowerlogicPower meter series PM700MG

41

The PowerLogic power meter series 700 is an inexpensive and compact 96 x 96 mmunit that offers all the basic measurement capabilities required to monitor anelectrical installation. With its large easy-to-read display, the meter can display allthree phases and neutral at the same time. The anti-glare and scratch resistantdisplay features an intuitive interface with self-guiding menus. A unique green backlight and large numbers make it easy to read even in extreme lighting conditionsand viewing angles.

The PM700 product offering consists of three models, each with an integrated displayand providing metering measurements including THD and min/max values. The unitmodels include a basic metering unit, a unit with an RS 485 Modbus communicationport, or a unit with 2 pulse outputs.

Applications Panel instrumentation

Submetering and cost allocation

Remote monitoring of an electrical installation

Harmonic monitoring (THD)

Contract optimisation and load profiling

Characteristics

Large, easy-to-read display Multiple values displayed at the same time on an anti-glare display featuring a

green back-light

Easy to operate Intuitive navigation with context-sensitive menus for easy use

Only 50mm deep Measures 96 x 96 x 50 mm including connectors and Modbus communications

Energy class 1 as defined by IEC 61036 Sufficient accuracy for submetering and cost allocation

Power, current demand, THD, min/max Expanded metering data for the cost of analog metering

Description Part numberPM700/700P/710Power Meter with THD, min/max PM700MGPower Meter with THD, min/max, 2 pulse outputs PM700PMGPower Meter with THD, min/max, RS 485 communications PM710MG

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 41

Page 42: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

42

PowerLogicPower meter series PM700MG

Instantaneous rms valuesCurrent I per phase, neutral, average of 3 phases

Voltage V per phase, average of 3 phases

Frequency F 45 to 65 Hz

Active power W total and per phase

Reactive power VAr total and per phase

Apparent power VA total and per phase

Power factor PF 0 to 1

Energy valuesActive energy Wh up to 1.84 x 1018 Wh

Reactive energy VAr up to 1.84 x 1018 Wh

Apparent energy VA up to 1.84 x 1018 Wh

Demand valuesCurrent I per phase (thermal)

Active power W total in time block

Reactive power VAr total in time block

Apparent power VA total in time block

Maximum demand valuesCurrent I phase

Active power W total

Reactive power VAr total

Apparent power VA total

Power quality valuesTotal harmonic distortion % current and voltage (L-L & L-N)

PM700PMG, as PM700MG plusPulse outputs pulse duration and weight adjustable

Active energy solid state relay

Reactive energy solid state relay

PM710MG, as PM700MG plusCommunicating meter

RS485 link 2 - wire

Communication protocol MODBUS RTU

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 42

Page 43: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

43

PowerLogicPower meter series PM700MG

PM700 series back view

Electrical characteristicsType of measurement True rms up to the 15th harmonic

On three-phase AC system (3P 3P + N)32 samples per cycle

Measurement Current and voltage 0.5 %accuracy Power 1 %

Frequency ± 0.01 Hz from 45 to 65 HzReal Energy IEC 61036 Class 1Reactive Energy IEC 61036 Class 2

Data update rate 1 sInput-voltage Measured voltage 10 to 480 V AC (direct L-L)characteristics 10 to 277 V AC (direct L-N)

0 to 3.2 MV AC (with external VT)Metering over-range 1.2 UnImpedance 2 MΩ (L-L) / 1 MΩ (L-N)Frequency range 45 to 65 Hz

Input-current CT ratings Primary Adjustable from 5A to 65534 Acharacteristics Secondary 5 A starting at 10 mA

Measurement input range 0 to 6 APermissible overload 15 A continuous

50 A for 10 seconds per hour120 A for 1 second per hour

Impedance < 0.1 ΩLoad < 0.15 VA

Control Power AC 110 to 415 ±10 % V AC, 5 VADC 125 to 250 ±20 % V DC, 3 WRide-through time 100 ms at 120 V AC

Output Pulse output PM700P Static output (240 ±10 % V AC or 300 ±10% V DC, 100 mA max. @ 25 °C, derate 0.56 mA per °C above 25°C) 2.41 kV rms isolation

Mechanical characteristicsWeight 0.37 kg

IP degree of protection (IEC 60529) IP52 front display, IP30 meter bodyDimensions 96 x 96 x 88 mm (meter with display)

96 x 96 x 50 mm (behind mounting surface)Environmental conditionsOperating Meter -0 °C to +60 °Ctemperature Display -10 °C to +50 °CStorage temp. Meter + display -40 °C to +85 °CHumidity rating 5 to 95 % RH at 50 °C (non-condensing)Pollution degree 2Metering category III, for distribution systems up to 277 V L-N /

480 V AC L-LDielectric withstand As per EN61010, UL508Electromagnetic compatibilityElectrostatic discharge Level III (IEC 61000-4-2)Immunity to radiated fields Level III (IEC 61000-4-3)Immunity to fast transients Level III (IEC 61000-4-4)Immunity to impulse waves Level III (IEC 61000-4-5)Conducted immunity Level III (IEC 61000-4-6)Immunity to magnetic fields Level III (IEC 61000-4-8)Immunity to voltage dips Level III (IEC 61000-4-11)Conducted and radiated emissions CE commercial environment/FCC part 15 class B

EN55011Harmonics emissions IEC 61000-3-2Flicker emissions IEC 61000-3-3SafetyEurope CE, as per IEC 61010-1U.S. and Canada UL508CommunicationRS 485 port 2-wire, up to 19200 bauds, Modbus RTUFirmware characteristicsMin./max. Worst min. and max. with phase indication for

voltages, currents, voltage unbalance, and THD. Min. and max. values for power factor (True and Displacement), power (P, Q, S) and frequency

Firmware update Update via the communication portsDisplay characteristicsDimensions 73 x 69mm Back-lit green LCD (6 lines total, 4 concurrent values)

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 43

Page 44: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

PowerLogicPower meter series PM700MG

44

Selection guide PM700 PM710 PM700PGeneralUse on LV and HV systems

Current and voltage accuracy 0.5% 0.5% 0.5%Energy and power accuracy 1.0% 1.0% 1.0%

Instantaneous rms valuesCurrent, voltage, frequency

Active, reactive, Total and per phase

apparent powerPower factor Total

Energy valuesActive, reactive, apparent energy

Demand valuesCurrent Present and max.

Active, reactive, Present and max.

apparent powerSetting of calculation mode Block, sliding block,

rolling block

Data recordingMin/max of instantaneous values

Display and I/OBacklit LCD Display

Pulse output - - 2

CommunicationRS 485 port - 2 wire -Modbus protocol - -1 Mounting slots

2 RS485 communications (450C) or 2 pulse outputs (450P)

3 Heartbeat LED

4 Control power

5 Voltage inputs

6 Current inputs

4 wire connection with 3 CT’s and no VT

MGLV5751 (RTI Sec 05) 12/9/05 12:04 pm Page 44

Page 45: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 pan assemblies Section six

46Outgoing devices

Incoming devices 47

48Accessories

45

MGLV5751 (RTI Sec 06) 6/9/05 10:30 am Page 45

Page 46: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 pan assemblies630A or 800A busbar ratingsOutgoing devices

46

3 pole outgoing MCCB

Outgoing pan assembly

MGP250NL

Application for outgoing MCCBsOutgoing MCCBs are supplied complete with totally shrouded busbar connectionsand the following trip units as standard: Up to 250A - thermal magnetic (TM) tripunits. 400 to 630A - STR225E electronic trip units. Other trip units (motor, generator, earth fault & transformer applications) are available on request. Pleasecontact us for further information. One MCCB direct connection can be used as anincomer when used with incoming pan assembly.

Outgoing MCCBsCurrent Part No.rating (A) SP 2P 3P 4P16 MGP0161 (1) MGP0162 (2) MGP0163 MGP016425 MGP0251 (1) MGP0252 (2) MGP0253 MGP025430/32 (6) MGP0301 (1) MGP0302 (2) MGP0323 MGP032440 MGP0401 (1) MGP0402 (2) MGP0403 MGP040463 MGP0631 (1) MGP0632 (2) MGP0633 MGP063480 MGP0801 (1) MGP0802 (2) MGP0803 MGP0804100 MGP1001 (1) MGP1002 (2) MGP1003 (7) MGP1004 (7)125 MGP1251 (1) MGP1252 (2) MGP1253 MGP1254160 MGP1601 (1) MGP1602 (2) MGP1603 MGP1604200 MGP2003 MGP2004250 MGP2503 MGP2504400 (5) MGP4003 (3) MGP4004 (4)630 (5) MGP6303 (3) MGP6304 (4)(1) Add suffix L1, L2, L3 when selecting single pole MCCBs. (2) Add suffix L1N, L2N, L3N, L12, L23, L31, when ordering double pole MCCBs. (3) 4 SP ways used, requires shrouding kit, see page 49.(4) 6 SP ways used, requires shrouding kit, see page 49, MGPBB25 1/2 pole

shrouding plate.(5) When fitting 400A & 630A breakers a side extension box may be required.(6) 30A for SP and DP, 32A for 3 and 4P.(7) For full discrimination with downstream C60H MCBs, use MGP1013 (3 pole) or

MGP1014 (4 pole).

Outgoing disconnectable neutral link Offers SP&N and TP&N facilityCurrent Part No.rating (A)100/250 MGP250NL (1 SP way)400/630 (4) MGP630NL (2 SP ways)

(4) Requires MGPBB25 1/2 pole shrouding plate.

Pan assemblies provide easy to connect high density connection independent ofdevice mix for mounting of moulded case circuit breakers into a low voltage powerdistribution switchboard. Can be fed from the side or bottom fed using incomingpan assembly.

Outgoing pan assemblySP ways Part No.

630A busbar 800A busbar18 MG6PAC6 MG8PAC636 MG6PAC12 MG8PAC1254 MG6PAC18 MG8PAC1872 MG6PAC24 MG8PAC2490 MG6PAC30 MG8PAC30

MGLV5751 (RTI Sec 06) 6/9/05 10:30 am Page 46

Page 47: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 pan assemblies630A or 800A busbar ratings

Incoming devices

47

4 pole incoming MCCB

Incoming pan assembly

Neutral bar kit

Terminal shields

MGPBBP

Incoming deviceCurrent Part No. Part No.rating (A) MCCBs Switch disconnector

3P 4P 3P 4P250 MGP2503 MGP2504 MGP2503NA MGP2504NA400 MGP4003 MGP4004 MGP4003NA MGP4004NA630 MGP6303 MGP6304 MGP6303NA MGP6304NA800 33466 33469 33487 33492

Direct connectionRating Part No.630A MGPINC + MG6PACN

Incoming pan assemblyIncoming section including mounting tray metal shroud and copper busbar ‘T’ section to allow cassetted breakers to feed pan from bottom.Current Part No.rating (A) 3P 4P630 MG6PACN MG6PACN800 MG8PACN3 MG8PACN4

18 way neutral bar kitMounts on either side of incoming device when usingincoming pan assembly. Includes disconnectable neutral link.Type Part No.630A MG6PANKIT800A MG8PANKIT

Terminal shields (supplied in pairs)Current Part No.rating (A)Up to 160 A single pole & 250A neutral link: 29320Up to 160A 2 pole 29320 x 2Up to 250A 3 pole 29323Up to 250A 4 pole 29324400/630A 3 pole 32564400/630A 4 pole 32565For shielding a TP MCCB with neutral link use the 4 pole terminal shield.

Single pole shrouding platesMGPBBP MGPBB25

Technical data Trip units: 250A -630A - (as outgoing devices)

800A - Micrologic 2.0 electronic trip unit. Othertrip units available on request. Please contact usfor further information

250 to 630A units can be mounted directly to thepan assembly or mounted vertically at thebottom, in conjunction with the incoming panassembly (MG6PACN)

Pan assemblies can be fed at the top using a topentry breaker, refer to page 37

800A unit can only be mounted vertically inconjunction with the incoming pan assemblyMG8PACN3 (3 pole) or MG8PACN4 (4 pole)

Incoming terminal shields should always be fittedwith MCCB or switch disconnector incomingdevices

Manual source changeover system can beachieved with rotary handles/key interlocks.Please contact us for further information

Top entry incoming devices available on request.Please contact us for further information

Single pole shrouding plates arerequired for each unoccupied outgoing way.

In addition a 25mm shrouding plate isalways required when 4 pole 400A or630A circuit breakers are mounted onthe outgoing pan assembly.

MGLV5751 (RTI Sec 06) 6/9/05 10:30 am Page 47

Page 48: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 pan assemblies630A or 800A busbar ratingsAccessories

48

Toggle padlocking attachments clip fixing in OFF position Current rating Removable Fixed 250A 29370 29371630A 29370 32631800A 44936 32631

Residual current protection modulesUsing 4 pole residual current add-on modules (Vigi block) for incoming or outgoing ways (requires a 4 pole MCCB).

Frame rating Earth leakage Current Vigi moduletripping current rating Part No.options (A) MCCB

Up to 160A 0.03 - 0.3 - 1 - 3 - 10 * NS100/160 29211200 - 250A 0.03 - 0.3 - 1 - 3 - 10 * NS250 31536400 - 630A 0.3 - 1 - 3 - 10 - 30 * NS400/630 32456* Time delay setting (ms) 0 - 60 - 150 and 310 (30mA - instantaneous only).(i) For combinations of items of RCDs, metering and remote metering please contact us for further information.

Ammeter3 phase ammeter complete with CT’s (mounted on the breaker). Can be fitted on incoming or outgoing device.

Current rating Part No.3 pole 4 pole

NS100 29455 29456NS160 30555 30556NS250 31565 31566NS400 32655 32656NS630 32855 32856

Metering facility3 phase current transformer module with voltage measurement outputsFits on directly on the terminals of the breaker.The voltage measurement outputs have inbuilt protection with automatic resetSuitable for use with the PowerLogic range of meters

Part No.Breaker CT ratio VA output Class at VA 3 pole 4 pole

outputNS100 125/5 1.1 1.0 29461 29462NS160 150/5 1.1 1.0 30561 30562NS250 250/5 1.1 0.5 31569 31570NS400 400/5 2.0 0.5 32653 32654NS630 600/5 2.0 0.5 32861 32862

Current transformer module3 phase current transformer moduleFits directly on the terminals of the breaker.

Part No.Breaker CT ratio VA output Class at VA 3 pole 4 pole

outputNS100 100/5 1.6 3.0 29457 29458NS160 150/5 3.0 3.0 30557 30558NS250 250/5 5.0 3.0 31567 31568NS400 400/5 8.0 3.0 32657 32658NS630 600/5 8.0 3.0 32857 32858

29211

29455

29457

Rotary handles with inbuilt padlocking facilities(for 3 or 4 pole devices only)Current rating Black Red/YellowUp to 250A 29337 29339400/630A 32597 32599

Motor operator moduleAll 3 pole and 4 pole breakers up to 250A can be fitted with a motor operatormechanism allowing remote opening and closing of the circuit breaker.Operating voltages50Hz a.c. 48 - 415Vd.c. 24 - 250VSpecify requirements at time of ordering the breaker.

29457

MCCB + Rotary handle

MCCB + Motor operator

MGLV5751 (RTI Sec 06) 6/9/05 10:30 am Page 48

Page 49: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Powerpact 4 pan assemblies630A or 800A busbar ratings

Accessories

49

29242

29450

29387

Front cover

MGPSHR6

Auxiliary switch (for 3 or 4 pole devices only)For all MCCBs up to 630A. Used to indicate open, closed or tripped status.SDE adaptor required for trip unit TM or MA (to indicate trip on overcurrent).

If you need to indicate open, closed and tripped status, two auxiliary switches willbe needed.

Voltage releases to fit all MCCBs 100/630A (for 3 or 4 pole devices)AC 50/60Hz:Voltage Part No. Part No.(V) Shunt trip Undervoltage release 200/240 29387 29407380/415 29388 29408Other voltages available - refer to Compact NS catalogue.

Part No.Auxiliary changeover switch 29450SDE adaptor 29451

Front cover (up to 18TP ways only) Number of outgoing ways Part No. Part No.SP TP 630A interior 800A interior18 6 MG6PAFC6 MG6PAFC636 12 MG6PAFC12 MG6PAFC1254 18 MG6PAFC18 MG6PAFC18Note: If RCD, metering, remote metering or 400/630A outgoing devices are fittedthen a shrouding kit must be used.

Shrouding kit (with MG6 FC front covers only)Provides additional support for device and shrouding for front cover .Oneshrouding kit must be used per side when fitting either outgoing 400/630AMPMCCBs or outgoing ammeter and/or earth leakage protection. In addition to theshrouding kit an addition a 25mm three stage filler piece is required when 4 pole400A or 630AMP circuit breakers are fitted on the outgoing pan assemblyMGPTSF25.

Number of outgoing ways Shrouding kitSP TP Part No.18 6 MGPCH636 12 MGPCH1254 18 MGPCH18

Connection accessoriesBare cable connectorsCapacity A Quantity Part No.1.5mm2 to 95mm2 160 Set of 3 292421.5mm2 to 95mm2 160 Set of 4 2924310mm2 to 185mm2 250 Set of 3 2925910mm2 to 185mm2 250 Set of 4 2926035mm2 to 300mm2 630 Set of 3 3247935mm2 to 300mm2 630 Set of 4 324802 x 95mm2 to 240mm2 630 Set of 3 324812 x 95mm2 to 240mm2 630 Set of 4 32482

SpreadersA Pole pitch mm Quantity Part No.250 45 Set of 3 31563250 45 Set of 4 31564630 52.5 Set of 3 32490630 52.5 Set of 4 32491

MGLV5751 (RTI Sec 06) 6/9/05 10:31 am Page 49

Page 50: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

50

MGLV5751 (RTI Sec 06) 6/9/05 10:31 am Page 50

Page 51: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Technical data Section seven

52Safepact 2

Motor loads 52

53Powerpact 4 panelboards

51

54Degrees of protection provided by enclosures

MGLV5751 (RTI Sec 07) 2/9/05 5:49 pm Page 51

Page 52: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Technical informationSafepact 2 Motor loads

52

Discrimination

The table below indicates where total discrimination exists between devices.

Upstream Compact MGE1003 MGE1253 MGE1603 MGE2003 MGE2503 MGE4003 MGE6303rating (A)

Downstreamcircuit breaker Rating (A)multi 9 C60H 10 - 16

20 - 25

32 - 40

50 - 63

Compact NS80H 2.5 - 6.3

12.5

25 - 80

NS100N 16 - 100

NS160N 125 - 160

NS250N 200 - 250 Note: For further information on this product range: consult us.

D1

D2

Safepact 2

Guidance for motor loads

Specific “magnetic only” MCCBs are available for short circuit protection of motors.However, the standard MCCB may be used, as detailed below.

Max motor size (kW) Running current (A) @ 415V

16A 2.2 5.025A 3.7 7.540A 4 8.463A 9 1780A 15 28100A 22 40125A 25 47160A 33 60200A 45 80250A 69 128

Note: These tables offer guidance only, for DOL starting assuming: A starting current of 7 x FLC Run-up time =8 seconds for motors

< 3kW10 seconds for motors > 3kW

The running current is a typical value and may vary from manufacturer to manufacturer.

MGLV5751 (RTI Sec 07) 2/9/05 5:49 pm Page 52

Page 53: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Technical informationPowerpact 4 panelboards

53

Technical data

Possible terminalcapacity for Breakingcrimped lug capacity(mm) @ 415V

Current device Ø L100A MGP100 MCCB SP 6 25 25,000A @ 240V100A MGP100 MCCB TP 6 25 36,000A100A MGPE125 MCCB TP 6 25 16,000A160A MGP160 MCCB TP 6 25 36,000A250A MGP250 MCCB 8 25 36,000A

MGP250NA Switch disconnector 8 25 –400A MGP400 MCCB 10 32 50,000A

MGP400A Switch disconnector 10 32 –630A MGP630 MCCB 10 32 50,000A

MGP630NA Switch disconnector 10 32 –800A NS800 12 44 50,000A

NS800NA Switch disconnector 12 44 –

MGP INC Direct connection 10 32 –

Outgoing Earth connection 6 25mm tunnel –Outgoing Neutral connection 6 25 –Incoming Earth connection 10 32 –Incoming Neutral connection 12 40 –

Other connections available on request. If you require higher breaking capacity, consult us.

L

Ø

Total discrimination on the standard range

D1

D2

NS630

NS400

NS250

NS160

NS100

Simple rule for the standard range: just take a step between each frame rating toobtain total discrimination.

All the circuit breakers are equipped with standard trip units.

Consult us for full details of discrimination/cascading.

Discrimination

Busbar connectionsThe Powerpact 4 panelboards have a unique connection system which gives thecorrect torque settings when connecting the cassetted breakers to the busbars.If necessary the breakers can be removed from the bars and fitted elsewhere. Inthis case the correct torque must be applied to the connections.Breakers up to 250A 20NmBreakers 400 & 630A 28Nm

1600A PanelboardIncoming connection details 4 - Ø12.5 holes on 50 mm pitchPole pitch = 70mmDistance to gland plate = 708mm

MGLV5751 (RTI Sec 07) 2/9/05 5:49 pm Page 53

Page 54: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Technical informationDegrees of protectionprovided by enclosures

54

aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaa60600

150

ExampleIP 55

Protection indexStandard BSEN 60529 gives a protection code (IP)which characterises the ability of equipment towithstand the following external influences: Presence of solid bodies, Presence of water. This code comprises two digits, depending on theseexternal influences. The protection index is assignedto the equipment following a series of tests laid downin the respective standards.

External influencesIn many national and international standards, a largenumber of external influences to which an electrical installation can be subjected are indexed and coded:presence of water, presence of solid objects, risk ofimpact, vibrations, presence of corrosive substances,etc. These influences may be present with variableintensity depending on the conditions of installation:The presence of water may be in the form of a fewdrops or total immersion.

Test according to BSEN60529

1st digit

Protection against solid bodies

2nd digit

Protection against liquids

No protection

Protection against solid bodies greater than 50mm

Protection against solid bodies greater than12.5mm

Protection against solid bodies greater than 2.5mm

Protection against solid bodies greater than 1mm

Protection against dust (no harmfuldeposits)

Total protection against dust

No protection

Protection againstvertical drops ofwater (condensation)

Protection againstdrops of water fallingup to 15° from vertical

Protection againstrainwater up to 60°from vertical

Protection againstwater projected fromall directions

protection againsthosing with waterfrom all directions

Protection againstswamping with water

Protection againstimmersion

0

1

2

3

4

5

6

0

1

2

3

4

5

6

7

Protection against hosingwith water from all directions

Protection against dust(no harmful deposits)

ø 50mm

ø 12.5mm

ø 2.5mm

ø 1mm

or DC

MGLV5751 (RTI Sec 07) 2/9/05 5:49 pm Page 54

Page 55: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions Section eight

56Safepact 2

Enclosed Interpact 56

57MGF Fusegear

58MGF busbar chambers

Powerpact 4 powerboards 250A 59

59Powerpact 4 panelboards 250A and 400/630A

60Powerpact 4 panelboards 800A

61Powerpact 4 extension boxes

62Powerpact 4 metering extensions

Powerpact 4 panelboards 1250/1600A 63

64Powerpact 4 pan assemblies incoming MCCB

65Outgoing pan assemblies 630A

66Outgoing pan assemblies 800A

55

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 55

Page 56: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Safepact 2

56

Safepact 2 MCCB or switch disconnectorgeneral purpose enclosure IP40

Extension boxes for Safepact 2 MCCB enclosures

Safepact 2 MCCB or switch disconnectorgeneral purpose enclosure IP40including earth leakage protection

Height Width Cable Overall Enclosurespace depth depth

Rating A B C* D EUp to 100A 420 230 140 211 145

160A250A400A 700 356 236 235 169630A

Note: C* - we recommend fitting cable extension boxes on each end of the 160, 250 and 630Aratings, unless utilising trunking

Height Width Cable Overall Enclosurespace depth depth

Rating A B C1 C2 D EUp to 100A 420 230 140 65 211 145

160A 520 230 140 165250A 620 230 140 265400A 820 356 236 256 235 169630A

Height (A) Part No. 100 MGEX 160C200 MGEX 250C120 MGEX 630C

A

A

A

B

D

E

C

C

Height Width Cable Overall Enclosurespace depth depth

Rating A B C D E63A 350 350 130 300 250100A 350 350 125 300 250160A 350 350 125 300 250250A 450 350 165 300 250320A 650 350 235 300 250400A 650 350 235 300 250500A 650 350 235 300 250630A 650 350 235 300 250

A

B

D

E

C

C

B

D

E

C2

C1

Enclosed Interpact

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 56

Page 57: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)MGF Fusegear

57

Rating100A160A200/250A400A500A630A* Weights do not include the fuse links

A380380380455455455

B292292340489489489

C200200200270270270

D260260260335335335

E130130180289289289

F818180100100100

G142142142212212212

H226226274423423423

J100150180300300400

K292292340489489489

L220220220290290290

Rating20A32A63A100A* Weights do not include the fuse links

A210210235260

B240240350400

C105105105120

D160160270320

E50505565

F51515151

G44445060

H20203238

J25253240

Weight Kg*4.104.825.347.37

Switch disconnector fuse MGFASwitch disconnector MGFL

516 C

50

D B

E E

G G

AJ

F

Lift-off doorhinged RH sideRemovable

end plates

Centreknockouts

H. diaknockouts

Wall fixing holes6 dia

K

Fuse switch disconnector MGFSSwitch disconnector MGFD

C 6

LK

J

3333

33

G

25

H

Cable entrybox

Earth bolt

Castelllock

End plate

EF F

B

60

D

60

A

Weight Kg*15.615.619.536.236.236.2

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 57

Page 58: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Busbar chamber

58

15Fixing holes 11 dia x 4

8200

LC

40 B

A

450340

Type A BMBFB...07TN 750 670MBFB...12TN 1200 1120MBFB...18TN 1800 1720

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 58

Page 59: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Powerpact 4 powerboards and panelboards

250A and 400/630

59

A

D

B

240

260

C

Board ref. A B C DMG2C5 679 850 541 670MG2C7 784 850 646 670MG2C9 889 850 751 670MG2C13 1074 850 920 670MG6C6 1178 850 1035 710MG6C12 1493 850 1350 710MG6C18 1808 850 1665 710C and D are the fixing dimensions about the centreline

Material thickness1.2mm cover1.6mm enclosure

250, 400/630A panelboard

AC

268B

D

Board ref. A B C DMG25C2 & MG25C2M 650 600 442 306MG25C4 & MG25C4M 650 778 442 484MG25EXC 650 600 442 306C and D are the fixing dimensions about the centre line

250A powerboard

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 59

Page 60: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Powerpact 4 panelboards 250, 400/630 and 800A

60

A C

710

extension box included

850

240

260

B

D

Board ref. A B C DMG8C6 1578 1035 991 172MG8C12 1893 1350 1306 172MG8C18 2208 1665 1621 172

Material thickness1.2mm cover1.6mm enclosure

800A panelboard

510650

140

260

240

710

850

250A panelboard

MG2C250FS

Fuse switch incomer for 250A panelboard

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 60

Page 61: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Powerpact 4 extension boxes

61

200 or 400*

250 or 500250 or 500

200 or 400*

850

Corner Corner

CornerCorner Top extension

Bottom extension

Side extension

ormeterbox

Side extension

ormeterbox

Panelboard

All extension boxes are the same depth as the main board - 240mm.

* 400mm extension box is fitted as standard at the incoming end of the 800A panelboard.

Corner units are available to suit all combinations of top/bottom and side extension boxes.

Overall dimension tablePanelboard Part No. MG25C2 MG25C2M MG25C4 MG25C4M MG2C5 MG2C7 MG2C9 MG2C13 MG6C6 MG6C12 MG6C18 MG8C6 MG8C12 MG8C18

Height Standard 653 653 653 653 679 784 889 1074 1178 1493 1808 1583 1898 2213

With 1 top or bottom ext box 883 988 1093 1278 1382 1697 2012 1787 2102 2417

with top & bottom ext box 1087 1192 1297 1482 1586 1901 2216 1991 2306 2621

Width Standard 600 600 778 778 850 850 850 850 850 850 850 850 850 850

with 1-250mm side ext box 1105 1105 1105 1105 1105 1105

with 1-500mm side ext box 1360 1360 1360 1360 1360 1360

with 1-600mm side ext box 1200 1200 1378 1378

with 1-250 & 1-500mm side ext box 1615 1615 1615 1615 1615 1615

with 2-250mm side ext boxes 1360 1360 1360 1360 1360 1360

with 2-500mm side ext boxes 1870 1870 1870 1870 1870 1870

Depth 263 263 263 263 263 263 263 263 263 263 263 263 263 263

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 61

Page 62: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Powerpact 4 metering extensions630, 800A panelboard with side extension metering boxes

62

The side extensions with metering are dimensionally the same as standard 250mm sideextensions

All apertures are 92mmsq. to accept standard DIN 96 meters.

1360

800A Panelboard only

1377

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 62

Page 63: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)1600A panelboard

63

1656466

2106

400800400

Optionalsection

763363 363

1563

38 38

1256Without optional section

MGLV5751 (RTI Sec 08) 8/9/05 9:30 am Page 63

Page 64: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)Powerpact 4 pan assembly andincoming MCCB

64

Reference A6 way 34612 way 66118 way 97624 way 129130 way 1606

Reference CNS800 475NS630 330NS250 228Dimension C = centre line

of incoming breaker

terminals (plan view).

NN

660

37

A

690

311

62630

204.1

20

164.178.1

45

C

98.151

81

30

5

C

62

37

NS250 incoming MCCB connections

NS630 incoming MCCB connections

NS800 incoming MCCB connections

242

20

180.170.1

35.5

C

95.151

81

30

70

5

246.1

20

188.178.1

45

C

105.151

81

30

5

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 64

Page 65: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)630A outgoing pan

assembly only

65

Reference A6 way 34612 way 66118 way 97624 way 129130 way 1606

Cover

92.3

143.1

690

660

A

37

37

12.5

10.3

25

ø9.5

13.5

10R

4.5R

248

170.1

250

with

out

cove

r

331

194.1NS630

NS

250

251.1

84.1

C

6

50

40

64.1

Incoming busbar connectionsdirect to outgoing pan assembly

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 65

Page 66: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Dimensions (mm)800A outgoing pan assembly only

66

Reference A6 way 34612 way 66118 way 97624 way 129130 way 1606

Cover

92.3

143.1

690

660

A

37

37

10.3

ø9

C

25.544.5

114.5

95.5

13.5

ø10

ø4.5

248

170.1

331

194.1NS630

NS

250

251.1

84.1

8

50.1

170.1

130.1

90.1

64.1

Incoming busbar connectionsdirect to outgoing pan assembly

Phasebarsonly

250

with

out

cove

r

MGLV5751 (RTI Sec 08) 2/9/05 5:46 pm Page 66

Page 67: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Advantage Section nine

67

Fully assembled and custom built distribution panels and switchboards 68

MGLV5751 (RTI Sec 09)A 7/9/05 11:54 am Page 67

Page 68: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

AdvantageFully assembled and custom built distribution panels and switchboards

68

Merlin Gerin Advantage is a service which providesassembled distribution equipment delivered to anylocation in main land UK within just 3-4 weeks

The Advantage service means: Less installation time

All products are supplied fully assembled and delivered to site Tailor-made solution

Equipment can be designed and constructed specifically to your requirements

DeliveryOrder via your authorised Merlin Gerin distributor and we will deliver direct to site anywhere in main land UK

Total project assistanceFully detailed drawings and test certificates for all assembled distribution equipment

ConvenienceIt could not be easier, let us assemble, test and deliver all of your distribution boards to site when you need them reducing storage and minimising risk of loss or damage

Assembled standard product – delivered within 3weeks*The assembly of standard boards: Type A SP and N boards. Isobar 4c TP and N boards. Powerpact 4 MCCB panelboards. Isobar 4c distribution boards joined together. Powerpact 4 panelboards joined together. Combined MCB distribution boards and MCCB panelboards. All complete with incoming and outgoing devices and traffolyte

labels (if required).

Engineered standard product - delivered within 4weeks*Large and more complex installations may require theassembly of Merlin Gerin products plus the incorporation ofother equipment within one composite enclosure. Theadditional equipment could include: Isobar 4c distribution boards or Powerpact 4 panelboards

incorporating control equipment. Isobar 4c TP and N boards fitted with incoming contactor

devices. Power factor correction equipment. Facilities for building management systems. Change over contactors. Automatic source changeover systems. Protective devices such as earth fault relays. Instrumentation.* subject to customer requirements

Note: all Advantage products are manufactured and tested to BS EN 60439-1 and in accordance with ISO 9001 procedures before leaving the Merlin Gerinproduction facility.

MGLV5751 (RTI Sec 09)A 7/9/05 11:54 am Page 68

Page 69: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Schneider Electric Overview Section ten

69

MGLV5751 (RTI Sec 10) 7/9/05 8:18 am Page 69

Page 70: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Schneider ElectricAn overview

70

Schneider Electric operates the largest, dedicated sales force in the UKelectrical industry.

Sales engineers have specialist expertise and an understanding of the customer needswithin each of the following market sectors:

Building systems and solutions

Industrial systems and solutions

Energy and infrastructure systems andsolutions

Schneider Electrics expertise is founded on itsthree international brands – Merlin Gerin, Square Dand Telemecanique.

With over 100 years experience in the electrical industry,Schneider Electric has established itself as a world and UK leaderin the supply and manufacture of products for the distribution,monitoring and control of electrical power.

Schneider Electric regards its customers as commercial partners,who, like us, demand the highest standards of excellence in termsof products, projects and services.

Schneider Electric is proud to provide the solutions to meet theirneeds.

MGLV5751 (RTI Sec 10) 7/9/05 8:18 am Page 70

Page 71: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Schneider ElectricAn overview

Building systems and solutions

71

The real reason for putting technology intobuildings is to simplify tasks, enhance safety andimprove the quality of life.

Schneider Electric knows this and has created attractive,functional products for the residential building sector. Well beingcomfort and entertainment are key concepts in this area.

Related industries

Retail

Education

Health

Entertainment centres

Offices

Warehouses

Agriculture

Factory

Private residential

Public residential

Principal customers in the construction market

Contracting authorities

Main contractors

Building engineers

Schneider Electric means greater comfort, lower operating costs and enhanced safety.

The same objectives apply to commercial buildings such asoffices, hotels, shopping centres, hospitals, schools and carefacilities for the elderly.

Schneider Electric offer a wide range of solutions in the area ofbuilding management services and uses its expertise in all ofthese buildings to protect people and equipment.

MGLV5751 (RTI Sec 10) 7/9/05 8:18 am Page 71

Page 72: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Schneider ElectricAn overviewIndustrial systems and solutions

72

Across a wide range of applications including:

Conveyors

Packaging

Materials handling

Hoisting

Schneider Electric focus on performance in all areas of industry.

Our products and services adapt to each specific business and environment, fromdiscrete manufacturing and production lines to continuous processes in a wide variety ofindustries such as:

Automotive

Food and beverage

Pharmaceuticals

Construction materials

Waste management

MGLV5751 (RTI Sec 10) 7/9/05 8:18 am Page 72

Page 73: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Schneider ElectricAn overview

Energy infrastructure systems and solutions

73

Key markets

Electricity distribution

Water

Rail

Airports

Seaports

Defence

Gas

Telecommunications

Road

Schneider Electric is involved in the entire electrical distribution chainfrom power plants to end users. Customer demand for completeavailability, uncompromising quality and absolute safety has made thesearch for excellence our key mission.

Today, electrical substation and network protection, monitoring and control are highlyeffective in reducing outage time.

Proven technologies offer a wide range of simple, efficient and flexible solutions foroptimised, step by step investments.

Infrastructure

Schneider Electric is involved in developing infrastructure andtransportation systems around the world. In areas where nofailures can be tolerated, such as road and rail equipment,harbour installations and airports, Schneider Electric providessolutions in electrical distribution, control and monitoring,automation and supervision.

Principal customers in the electric power market

Power suppliers involved in generation and distribution

Utility companies

Major contractors

Large end user sites

Government departments

MGLV5751 (RTI Sec 10) 7/9/05 8:18 am Page 73

Page 74: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Schneider ElectricAn overviewProjects and services - delivering tailored solutions for your business

74

We provide solutions enabling you to reduce the totalcost and lifetime ownership risk of your electricaldistribution and automation systems, whilst fulfiling yourongoing quality, safety and environmental obligations.

co

nsultation

trai

ning

mode r n i s a t i o n

o p e r a t i o n

implemen

tati

on

design

Choice of servicesOur services aim to add value to each project phase, butthe choice of services you use is entirely yours. You maywant a full set of services that together provide a packageof support covering the entire lifecycle of your project, oryou can select a combination of services to complementyour resources or knowledge.If you are not sure of what you need, our consultationservices will help you to define the parameters of yoursolution.

ConsultationThese services provide you with an assured way to roadmap your project. We take your ideas and requirementsand apply our wide range of application experience andtechnical competence to produce conceptual designs andindicative costings.

DesignUsing the analysis from the consultation phase, orinformation that you may provide, the design phase selectsthe most suitable equipment and provides detaileddrawings and technical specifications.

ImplementationThis is often the most time-pressured stage of a projectwhen schedules demand fast implementation andcommissioning. These services provide high qualityinstallation and commissioning, preceded by thoroughpreparation.

OperationEfficient operation is vital to derive the best value from yourinvestment. These services ensure that installations achievethe highest operational efficiency and are cost effectivelymaintained with minimum downtime.

ModernisationFaulty or ageing equipment can be refurbished andrepaired if this is the most cost effective action.

TrainingA wide range of training services are available includingproduct standards and legislation. Each is regularlyupdated to stay current with the latest technology. Trainingcan be delivered at a Schneider Electric training facility, orat a customer’s own site.

Pro

jects & Services

MGLV5751 (RTI Sec 10) 7/9/05 8:19 am Page 74

Page 75: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Comprehensive quick reference index

Section eleven

75

Note

This index includes all products in both this catalogue and inthe Ready to install distribution boards catalogue Ref No. MGLV5750.This contains information on distribution boards, DIN rail mounted equipment, enclosures and connectionsystems. This can be ordered by calling 0870 608 8 608 orto download the catalogue please visit www.schneider.co.uk

Items listed but without a page number are in MGLV5750

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 75

Page 76: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

BP

C60HB101

C60HB102

C60HB104

C60HB106

C60HB110

C60HB116

C60HB120

C60HB125

C60HB132

C60HB140

C60HB150

C60HB163

C60HB201

C60HB202

C60HB204

C60HB206

C60HB210

C60HB216

C60HB220

C60HB225

C60HB232

C60HB240

C60HB250

C60HB263

C60HB301

C60HB302

C60HB304

C60HB306

C60HB310

C60HB316

C60HB320

C60HB325

C60HB332

C60HB340

C60HB350

C60HB363

C60HB401

C60HB402

C60HB404

C60HB406

C60HB410

C60HB416

C60HB420

C60HB425

C60HB432

C60HB440

C60HB450

C60HB463

C60HC101

C60HC102

C60HC104

C60HC106

C60HC10R100

C60HC10R30

C60HC10RA30

C60HC110

C60HC116

C60HC120

C60HC125

C60HC132

C60HC140

C60HC150

C60HC163

C60HC16R100

C60HC16R30

C60HC16RA30

C60HC201

C60HC202

C60HC204

C60HC206

C60HC20R100

C60HC20R30

C60HC20RA30

C60HC210

C60HC216

C60HC220

C60HC225

C60HC232

C60HC240

C60HC250

C60HC263

C60HC301

IndexBy part number

76

5 blanking plates

1P 1A mcb type B

1P 2A mcb type B

1P 4A mcb type B

1P 6A mcb type B

1P 10A mcb type B

1P 16A mcb type B

1P 20A mcb type B

1P 25A mcb type B

1P 32A mcb type B

1P 40A mcb type B

1P 50A mcb type B

1P 63A mcb type B

2P 1A mcb type B

2P 2A mcb type B

2P 4A mcb type B

2P 6A mcb type B

2P 10A mcb type B

2P 16A mcb type B

2P 20A mcb type B

2P 25A mcb type B

2P 32A mcb type B

2P 40A mcb type B

2P 50A mcb type B

2P 63A mcb type B

3P 1A mcb type B

3P 2A mcb type B

3P 4A mcb type B

3P 6A mcb type B

3P 10A mcb type B

3P 16A mcb type B

3P 20A mcb type B

3P 25A mcb type B

3P 32A mcb type B

3P 40A mcb type B

3P 50A mcb type B

3P 63A mcb type B

4P 1A mcb type B

4P 2A mcb type B

4P 4A mcb type B

4P 6A mcb type B

4P 10A mcb type B

4P 16A mcb type B

4P 20A mcb type B

4P 25A mcb type B

4P 32A mcb type B

4P 40A mcb type B

4P 50A mcb type B

4P 63A mcb type B

1P 1A mcb type C

1P 2A mcb type C

1P 4A mcb type C

1P 6A mcb type C

RCBO 10A 100MA Type C

RCBO 10A 30MA Type C

RCBO 10A 30mA Class A Type C

1P 10A mcb type C

1P 16A mcb type C

1P 20A mcb type C

1P 25A mcb type C

1P 32A mcb type C

1P 40A mcb type C

1P 50A mcb type C

1P 63A mcb type C

RCBO 16A 100MA TypeC

RCBO 16A 30MA Type C

RCBO 16A 30mA Class A Type C

2P 1A mcb type C

2P 2A mcb type C

2P 4A mcb type C

2P 6A mcb type C

RCBO 20A 100MA Type C

RCBO 20A 30MA Type C

RCBO 20A 30mA Class A Type C

2P 10A mcb type C

2P 16A mcb type C

2P 20A mcb type C

2P 25A mcb type C

2P 32A mcb type C

2P 40A mcb type C

2P 50A mcb type C

2P 63A mcb type C

3P 1A mcb type C

Part Page No.Description

C60HC302

C60HC304

C60HC306

C60HC310

C60HC316

C60HC320

C60HC325

C60HC32R100

C60HC32R30

C60HC32RA30

C60HC332

C60HC340

C60HC350

C60HC363

C60HC45R100

C60HC45R30

C60HC45RA30

C60HC6R100

C60HC6R30

C60HD101

C60HD102

C60HD104

C60HD106

C60HD110

C60HD116

C60HD120

C60HD125

C60HD132

C60HD140

C60HD150

C60HD163

C60HD201

C60HD202

C60HD204

C60HD206

C60HD210

C60HD216

C60HD220

C60HD225

C60HD232

C60HD240

C60HD250

C60HD263

C60HD301

C60HD302

C60HD304

C60HD306

C60HD310

C60HD316

C60HD320

C60HD325

C60HD332

C60HD340

C60HD350

C60HD363

MG16C14

MG16C14T

MG16CEX4

MG16CEM4

MBBN24C

MG125SPEV

MG12EE

MG18EE

MG24EE

MG250SPEV

MG25C2

MG25C2M

MG25C4

MG25C4M

MG25EXC

MG25FCC2

MG25FCC2M

MG25FCC4

MG25FCC4M

MG2C13

MG2C250FS

MG2C5

MG2C7

MG2C9

MG36EE

MG48EE

MG54EE

MG64M

3P 2A mcb type C

3P 4A mcb type C

3P 6A mcb type C

3P 10A mcb type C

3P 16A mcb type C

3P 20A mcb type C

3P 25A mcb type C

RCBO 32A 100mA Type C

RCBO 32A 30mA Type C

RCBO 32A 30mA Class A Type C

3P 32A mcb type C

3P 40A mcb type C

3P 50A mcb type C

3P 63A mcb type C

RCBO 45A 100mA Type C

RCBO 45A 30mA Type C

RCBO 45A 30mA Class A Type C

RCBO 6A 100mA Type C

RCBO 6A 30mA Type C

1P 1A mcb type D

1P 2A mcb type C

1P 4A mcb type C

1P 6A mcb type C

1P 10A mcb type C

1P 16A mcb type C

1P 20A mcb type C

1P 25A mcb type C

1P 32A mcb type C

1P 40A mcb type C

1P 50A mcb type C

1P 63A mcb type C

2P 1A mcb type C

2P 2A MCB

2P 4A MCB

2P 6A MCB

2P 10A MCB

2P 16A MCB

2P 20A MCB

2P 25A MCB

2P 32A MCB

2P 40A MCB

2P 50A MCB

2P 63A MCB

3P 1A MCB

3P 2A MCB

3P 4A MCB

3P 6A MCB

3P 10A MCB

3P 16A MCB

3P 20A MCB

3P 25A MCB

3P 32A MCB

3P 40A MCB

3P 50A MCB

3P 63A MCB

Powerpact 4 1600A 14 way Panelboard

Powerpact 4 1600A 14 way Panelboard- top entry

Powerpact 4 side extension panel 400W with metering facility

Powerpact 4 side extension panel 400W

Door and cover for MGB24N

125A single phasing kit

12 way extra earth bar

18 way extra earth bar

24 way extra earth bar

250A single phasing kit

Powerboard 250A 9 SP ways

Powerboard 250A 9 SP ways with metering facility

Powerboard 250A 13 SP ways

Powerboard 250A 13 SP ways with metering facility

Panelboard extension box for MG25P2

Powerpact 4 door & cover 9 way

Powerpact 4 door & cover 9 way with metering

Powerpact 4 door & cover 13 way

Powerpact 4 door & cover 13 way with metering

Panelboard 250A 13 way

Powerpact 4 fuse incomer for 250A

Panelboard 250A 5 way

Panelboard 250A 7 way

Panelboard 250A 9 way

36 way extra earth bar

48 way extra earth bar

54 way extra earth bar

Powerpact 4 400A metering kit

Part PageNo.

Description

31

31

31

31, 40

23

23, 38

23

23, 38

23

34

34

34

34

25

25

25

25

25

39

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 76

Page 77: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MG66M

MG6C12

MG6C18

MG6C6

MG6CEX

MG6FCC12

MG6FCC18

MG6FCC6

MG6PAC12

MG6PAC18

MG6PAC24

MG6PAC30

MG6PAC6

MG6PACN

MG6PAFC12

MG6PAFC18

MG6PAFC6

MG6PANKIT

MG72EE

MG88M

MG8C12

MG8C12T

MG8C18

MG8C18T

MG8C6

MG8C6T

MG8FCC12

MG8FCC18

MG8FCC6

MG8PAC12

MG8PAC18

MG8PAC24

MG8PAC30

MG8PAC6

MG8PACN3

MG8PACN4

MG8PANKIT

MGACE

MGALK

MGAN1010MS

MGAN12

MGAN1228MS

MGAN126MS

MGAN12C

MGAN12FK

MGAN12P

MGAN12PS

MGAN15

MGAN15C

MGAN15FK

MGAN15P

MGAN15PS

MGAN23

MGAN23C

MGAN24FK

MGAN416MS

MGAN46DS

MGAN46SL

MGAN48SL

MGAN520MS

MGAN6

MGAN66DS

MGAN66SL

MGAN6C

MGAN6FK

MGAN6P

MGAN6PS

MGAN716MS

MGAN76DS

MGAN9

MGAN912MS

MGAN96MS

MGAN9C

MGAN9FK

MGAN9P

MGAN9PS

MGANWL

MGBGPEXN

MGBL

MGBN100CCI

MGBN12

MGBN12C

MGBN12E

Powerpact 4 630A metering kit

Panelboard 630A 36 SP ways

Panelboard 630A 54 SP ways

Panelboard 630A 18 SP ways

Panelboard top/bott 200mm extension

Cover 630A 36 way panelboard

Cover 630A 54 way panelboard

Cover 630A 18 way panelboard

Outgoing pan assembly 630A 36 SP ways

Outgoing pan assembly 630A 54 SP ways

Outgoing pan assembly 630A 72 SP ways

Outgoing pan assembly 630A 90 SP ways

Outgoing pan assembly 630A 18 SP ways

Incoming pan assembly 630A

Cover 630/800A 36 way pan assembly

Cover 630/800A 54 way pan assembly

Cover 630/800A 18 way pan assembly

18 way neutral bar kit 630A

72 way extra earth bar

Powerpact 4 800A metering kit

Panelboard 800A 12 way

Panelboard 800A 12 way top entry

Panelboard 800A 18 way

Panelboard 800A 18 way top entry

Panelboard 800A 6 way

Panelboard 800A 6 way top entry

Cover for 800A 36 way panelboard

Cover for 800A 54 way panelboard

Cover for 800A 18 way panelboard

Outgoing pan assembly 800A 36 SP ways

Outgoing pan assembly 800A 54 SP ways

Outgoing pan assembly 800A 72 SP ways

Outgoing pan assembly 800A 90 SP ways

Outgoing pan assembly 800A 18 SP ways

Incoming pan assembly NS800 3P

Incoming pan assembly NS800 4P

18 way neutral bar kit 800A

Clean earth kit A

M4 & M6 Allen key kit

10 way + 5 SP way DIN rail dist. board

12 way SP Distribution Board

12 way+14 SP way DIN rail dist. board

12 way + 3 SP way DIN rail dist. board

Door and cover for MGA12N

Flush mounting kit for A type

A board replacement pan ass 12 way

pan ass 12 way SP&N black sliders

15 way SP Distribution Board

Door and cover for MGA15N

Flush mounting kit for A type

A board replacement pan ass 15 way

pan ass 15 way SP&N black sliders

23 way SP Distribution Board

Door and cover for MGA23N

Flush mounting kit for A type

4 way + 8 SP way DIN rail dist. board

4 way cir/t A, 6 way cir/t B dist. board

4+6 way SP&N split load dist. board

4+8 way SP&N split load dist. board

5 way + 10 SP way DIN rail dist. board

6 way SP Distribution Board

6 way cir/t A, 6 way cir/t B dist. board

6+6 way SP&N split load dist. board

Door and cover for MGA6N

Flush mounting kit for A type

A board replacement pan ass 6 way

pan ass 6 way SP&N black sliders

7 way + 8 SP way DIN rail dist. board

7 way cir/t A, 6 way cir/t B dist. board

9 way SP Distribution Board

9 way + 6 SP way DIN rail dist. board

9 way + 3 SP way DIN rail dist. board

Door and cover for MGA9N

Flush mounting kit for A type

A board replacement pan ass 9 way

pan ass 9 way SP&N black sliders

A board spare labels

Gland plate for Isobar 4 extension box

Key lock for new Isobar door catch

Isobar 4 contactor incomer kit

12 way TP Distribution Board

Doo and cover for MGB12N

pan ass 12 way TP+ earth and neutral on mtg. plate

Part Page No.Description

MGBN12HDGK

MGBN12P

MGBN12PE

MGBN12PS

MGBN12SXP

MGBN12SXS

MGBN16

MGBN16C

MGBN16E

MGBN16HDGK

MGBN16P

MGBN16PE

MGBN16PS

MGBN16SXP

MGBN16SXS

MGBN18

MGBN18C

MGBN18E

MGBN18P

MGBN18PS

MGBN24

MGBN24E

MGBN24P

MGBN24PE

MGBN24PS

MGBN24SXP

MGBN24SXS

MGBN4

MGBN4C

MGBN4E

MGBN4P

MGBN4PS

MGBN4SXP

MGBN4SXS

MGBN6

MGBN6C

MGBN6E

MGBN6HDGK

MGBN6P

MGBN6PE

MGBN6PS

MGBN8

MGBN8C

MGBN8E

MGBN8HDGK

MGBN8P

MGBN8PE

MGBN8PS

MGBN8SXP

MGBN8SXS

MGBNBCE25

MGBNBCE7

MGBNEX034N

MGBNEXA15N

MGBNEXN

MGBNGPN

MGBNKWH

MGBNSJK

MGBNTJKN

MGBNWL

MGE0632C

MGE0633C

MGE0634C

MGE0634EC

MGE1002C

MGE1003C

MGE1003SC

MGE1004C

MGE1004EC

MGE1004SC

MGE1004SEC

MGE1252C

MGE1253C

MGE1254C

MGE1254EC

MGE1602C

MGE1603C

MGE1603SC

MGE1604C

MGE1604EC

MGE1604SC

MGE1604SEC

MGE2003C

12 way IP55 type B heavy duty dist board

B board replacement pan ass 12 way

pan ass 12 way TP+ E and N on mtg. plate

pan ass 12 way TP&N black sliders

51 SP way steel encl plain front cover

51 SP way steel enclslotted front cover

16 way TP Distribution Board

Door and cover for MGB16N

pan ass 16 way TP+ earth and neutral on mtg. plate

16 way IP55 type B heavy duty dist board

B board replacement pan ass 16 way

pan ass 16 way TP+ E and N on mtg. plate

pan ass 16 way TP&N black sliders

68 SP way steel encl plain front cover

68 way steel enclslotted front cover

18 way TP&N metal distribution board

Door and cover for MGB18N

pan ass 18 way TP+ earth and neutral on mtg. plate

B board replacement pan ass 18 way

pan ass 18 way TP&N black sliders

24 way TP Distribution Board

pan ass 24 way TP+ earth and neutral on mtg. plate

B board replacement pan ass 24 way

pan ass 24 way TP+ E and N on mtg. plate

pan ass 24 way TP&N black sliders

85 SP way steel encl plain front cover

85 SP way steel enclslotted front cover

4 way TP Distribution Board

Door and cover for MGB4N

pan ass 4 way TP+ earth and neutral on mtg. plate

B board replacement pan ass 4 way

pan ass 4 way TP&N black sliders

34 SP way steel encl plain front cover

34 SP way steel enclslotted front cover

6 way TP Distribution Board

Doo and cover for MGB6N

pan ass 6 way TP+ earth and neutral on mtg. plate

6 way IP55 type B heavy duty dist board

B board replacement pan ass 6 way

pan ass 6 way TP+ E and N on mtg. plate

pan ass 6 way TP&N black sliders

8 way TP Distribution Board

Door and cover for MGB8N

pan ass 8 way TP+ earth and neutral on mtg. plate

8 way IP55 type B heavy duty dist board

B board replacement pan ass 8 way

pan ass 8 way TP+ E and N on mtg. plate

pan ass 8 way TP&N black sliders

34 SP way steel encl plain front cover

34 SP way steel enclslotted front cover

Spare earth/clean earth B boards

Spare earth/clean earth B boards

34 way mod extension box

15 way SP&N extension box

Type B board extension box + plain cover

Isobar 4 B board top/bottom gland plate

Kilowatt Hour Metering kit for MG B

Side joining kit

Joining kit B board top/bottom

B board self labels

Enclosed MCCB 63A 2P

Enclosed MCCB 63A 3P

Enclosed MCCB 63A 4P

Enclosed MCCB 63A 4P + earth fault

Enclosed MCCB 100A 2P

Enclosed MCCB 100A 3P

Enclosed switch disconnector 100A 3P

Enclosed MCCB 100A 4P

Enc MCCB 100A 4P + earth fault

Enc switch disconnector 100A 4P

Enclosed switch 100A 4P + earth fault

Enclosed MCCB 125A 2P

Enclosed MCCB 125A 3P

Enclosed MCCB 125A 4P

Enclosed switch 125A 4P + earth fault

Enclosed MCCB 160A 2P

Enclosed MCCB 160A 3P

Enclosed switch 160A 3P

Enclosed MCCB 160A 4P

Enc MCCB 160A 4P + earth fault

Enclosed switch 160A 4P

Enclosed switch 160A 4P + earth fault

Enclosed MCCB 200A 3P

Part Page No.Description

IndexBy part number

77

39

27

27

27

27, 29

34

34

34

46

46

46

46

46

47

49

49

49

47

39

29

29

29

29

29

29

34

34

34

46

46

46

46

46

47

47

47

34

34

34

6

6

6

6

6

6

7

6

6

7

7

6

6

6

6

6

6

7

6

6

7

7

6

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 77

Page 78: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGE2004C

MGE2004EC

MGE2503C

MGE2503SC

MGE2504C

MGE2504EC

MGE2504SC

MGE2504SEC

MGE4003C

MGE4003SC

MGE4004C

MGE4004EC

MGE4004SC

MGE4004SEC

MGE6303C

MGE6303SC

MGE6304C

MGE6304EC

MGE6304SC

MGE6304SEC

MGES063

MGES063R

MGES100

MGES100R

MGES160

MGES160R

MGES250

MGES250R

MGES320

MGES320R

MGES400

MGES400R

MGES500

MGES500R

MGES630

MGES630R

MGEX160C

MGEX250C

MGEX630C

MGFA0201C

MGFA0203C

MGFA0321C

MGFA0323C

MGFA0631C

MGFA0633C

MGFA1001C

MGFA1003C

MGFB20007C

MGFB20012C

MGFB20018C

MGFB40007C

MGFB40012C

MGFB40018C

MGFB63007C

MGFB63012C

MGFB63018C

MGFC200

MGFC400

MGFC630

MGFD1003C

MGFD1603C

MGFD2503C

MGFD4003C

MGFD5003C

MGFD6303C

MGFK200

MGFK400

MGFK630

MGFL0201C

MGFL0203C

MGFL0321C

MGFL0323C

MGFL0631C

MGFL0633C

MGFL1001C

MGFL1003C

MGFQ100

MGFQ160

MGFQ250

MGFQ400

MGFQ630

MGFS1003C

MGFS1603C

IndexBy part number

78

Enclosed MCCB 200A 4P

Enclosed MCCB 200A 4P + earth fault

Enclosed MCCB 250A 3P

Enclosed switch 250A 3P

Enclosed MCCB 250A 4P

Enclosed MCCB 250A 4P + earth fault

Enclosed switch 250A 4P

Enclosed switch 250A 4P + earth fault

Enclosed MCCB 400A 3P

Enclosed switch 400A 3P

Enclosed MCCB 400A 4P

Enclosed MCCB 400A 4P + earth fault

Enclosed switch 400A 4P

Enclosed switch 400A 4P + earth fault

Enclosed MCCB 630A 3P

Enclosed switch 630A 3P

Enclosed MCCB 630A 4P

Enclosed MCCB 630A 4P + earth fault

Enclosed switch 630A 4P

Enclosed switch 630A 4P + earth fault

Enclosed Interpact 63A

Enclosed Interpact 63A red/yellow handle

Enclosed Interpact 100A

Enclosed Interpact 100A red/yellow handle

Enclosed Interpact 160A

Enclosed Interpact 160A red/yellow handle

Enclosed Interpact 250A

Enclosed Interpact 250A red/yellow handle

Enclosed Interpact 320A

Enclosed Interpact 320A red/yellow handle

Enclosed Interpact 400A

Enclosed Interpact 400A red/yellow handle

Enclosed Interpact 500A

Enclosed Interpact 500A red/yellow handle

Enclosed Interpact 630A

Enclosed Interpact 630A red/yellow handle

Safepact extension 100mm 63 - 250A

Safepact extension 200mm 63 - 250A

Safepact extension 200mm 630A

Switch disconnector fuse 20A SP&SwN

Switch disconnector fuse 20A TP&N

Switch disconnector fuse 32A SP&SwN

Switch disconnector fuse 32A TP&N

Switch disconnector fuse 63A SP&SwN

Switch disconnector fuse 63A TP&N

Switch disconnector fuse 100A SP&SwN

Switch disconnector fuse 100A TP&N

Busbar chamber 200A 750mm

Busbar chamber 200A 1200mm

Busbar chamber 200A 1800mm

Busbar chamber 400A 750mm

Busbar chamber 400A 1200mm

Busbar chamber 400A 1800mm

Busbar chamber 630A 750mm

Busbar chamber 630A 1200mm

Busbar chamber 630A 1800mm

Busbar cable connection kit 200A

Busbar cable connection kit 400A

Busbar cable connection kit 630A

Switch disconnector 100A TP&N

Switch disconnector 160A TP&N

Switch disconnector 250A TP&N

Switch disconnector 400A TP&N

Switch disconnector 500A TP&N

Switch disconnector# 630A TP&N

Busbar interconnection kit 200A

Busbar interconnection kit 400A

Busbar interconnection kit 630A

Switch disconnector 20A SP&SwN

Switch disconnector 20A TP&N

Switch disconnector 32A SP&SwN

Switch disconnector 32A TP&N

Switch disconnector 63A SP&SwN

Switch disconnector 63A TP&N

Switch disconnector 100A SP&SwN

Switch disconnector 100A TP&N

Set of 3 copper links 100A

Set of 3 copper links 160A

Set of 3 copper links 250A

Set of 3 copper links 400A

Set of 3 copper links 630A

Fuse switch disconnector 100A TP&N

Fuse switch disconnector 160A TP&N

Part

6

6

6

7

6

6

7

7

6

7

6

6

7

7

6

7

6

6

7

7

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

12

8

8

8

14

14

14

14

14

14

14

14

16

16

16

16

16

16

16

16

16

16

16

16

15

15

15

15

15

15

16

16

16

14

14

14

14

14

14

14

14

15

15

15

15

15

15

15

Page No.Description

MGFS2003C

MGFS2503C

MGFS3153C

MGFS4003C

MGFS5003C

MGFS6303C

MGFX100C

MGFX160C

MGFX250C

MGFX500C

MGFX630C

MGFZ160

MGFZ250

MGFZ630

MGFZ630T

MGI1252

MGI1253N

MGI1254

MGK33

MGLA

MGLAP

MGN16DE

MGN22DE

MGN28DE

MGN34DE

MGN56DE

MGNA12

MGNA15

MGNA24

MGNA4

MGNA6

MGNA7

MGNA9

MGNB12

MGNB16

MGNB18

MGNB24

MGNB4

MGNB6

MGNB8

MGNCB1004

MGNCB1604

MGNCB2004

MGNCB2504

MGNDSI

MGNI1603

MGNI1604

MGNI160RCCB

MGNI2003

MGNI2004

MGNI2254

MGNI2503

MGNI2504

MGNPBN250TB

MGP0161

MGP0162

MGP0163

MGP0164

MGP0251

MGP0252

MGP0253

MGP0254

MGP0301

MGP0302

MGP0323

MGP0324

MGP0401

MGP0402

MGP0403

MGP0404

MGP0631

MGP0632

MGP0633

MGP0634

MGP0801

MGP0802

MGP0803

MGP0804

MGP1001

MGP1002

MGP1003

MGP1003NA

MGP1004

Fuse switch disconnector 200A TP&N

Fuse switch disconnector 250A TP&N

Fuse switch disconnector 315A TP&N

Fuse switch disconnector 400A TP&N

Fuse switch disconnector 500A TP&N

Fuse switch disconnector 630A TP&N

Cable box 100A

Cable box 160A

Cable box 250A

Cable box 315/400/500A

Cable box 630A

Fuse switch connection kit 100, 160A

Fuse switch connection kit 250A

Fuse switch connection 315 - 630A bottom

Fuse switch connection 315 - 630A top

125A 2P switch disconnector

125A 3P switch disconnector

125A 4P switch disconnector

2 keys for distribution board & panelboard

Locking attachment

Padlock for MGLA

16 MOD steel enclosure

22 MOD steel enclosure

28 MOD steel enclosure

34 MOD steel enclosure

56 MOD steel enclosure

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

Distributed neutral kit

100A 4P TP&N dist board MCCB incomer

160A 4P TP&N dist board MCCB incomer

200A 4P TP&N dist board MCCB incomer

250A 4P TP&N dist board MCCB incomer

Dual incoming unit for B board

160A 3P+N switch disconnector incomer

160A 4P switch disconnector

160A switch disconnector + earth fault

200A 3P switch disconnector

200A 4P switch disconnector

225A 4P switch disconnector

250A 3P switch disconnector

250A 4P switch disconnector

250A terminal block w/o extension box

Powerpact 4 MCCB 16A 1P

Powerpact 4 MCCB 16A 2P

Powerpact 4 MCCB 16A 3P

Powerpact 4 MCCB 16A 4P

Powerpact 4 MCCB 25A 1P

Powerpact 4 MCCB 25A 2P

Powerpact 4 MCCB 25A 3P

Powerpact 4 MCCB 25A 4P

Powerpact 4 MCCB 30A 1P

Powerpact 4 MCCB 30A 2P

Powerpact 4 MCCB 32A 3P

Powerpact 4 MCCB 32A 4P

Powerpact 4 MCCB 40A 1P

Powerpact 4 MCCB 40A 2P

Powerpact 4 MCCB 40A 3P

Powerpact 4 MCCB 40A 4P

Powerpact 4 MCCB 63A 1P

Powerpact 4 MCCB 63A 2P

Powerpact 4 MCCB 63A 3P

Powerpact 4 MCCB 63A 4P

Powerpact 4 MCCB 80A 1P

Powerpact 4 MCCB 80A 2P

Powerpact 4 MCCB 80A 3P

Powerpact 4 MCCB 80A 4P

Powerpact 4 MCCB 100A 1P

Powerpact 4 MCCB 100A 2P

Powerpact 4 MCCB 100A 3P

Powerpact 4 100A 3P switch disconnector

Powerpact 4 MCCB 100A 4P

Part Page No.Description

15

15

15

15

15

15

15

15

15

15

15

16

16

16

16

23, 27, 29, 34

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

25

23, 25, 27, 29, 31, 46

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 78

Page 79: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGP1004NA

MGP1013

MGP1014

MGP1251

MGP1252

MGP1253

MGP1254

MGP1601

MGP1602

MGP1603

MGP1603NA

MGP1604

MGP1604NA

MGP2003

MGP2004

MGP2503

MGP2503LL

MGP2503NA

MGP2503NAT

MGP2503T

MGP2504

MGP2504LL

MGP2504NA

MGP2504NAT

MGP2504T

MGP250NL

MGP4003

MGP4003NA

MGP4003NAT

MGP4003T

MGP4004

MGP4004NA

MGP4004NAT

MGP4004T

MGP6303

MGP6303NA

MGP6303NAT

MGP6303T

MGP6304

MGP6304NA

MGP6304NAT

MGP6304T

MGP630NL

MGP8003B5

MGP8003NA

MGP8004B5

MGP8004NA

MGPBB25

MGPBBP

MGPC2025

MGPC2050

MGPC4025

MGPC4050

MGPCH12

MGPCH18

MGPCH6

MGPCM12L

MGPCM12R

MGPCM18L

MGPCM18R

MGPCM6L

MGPCM6R

MGPE0163

MGPE0253

MGPE0403

MGPE0633

MGPE0803

MGPE1003

MGPE1253

MGPGPC8

MGPINC

MGPL

MGPLSK

MGPP4S007

MGPXC206

MGPXC212

MGPXC218

MGPXC506

MGPXC512

MGPXC518

MGPXCA6

MGPXCB12

MGTB1001

Powerpact 4 100A 4P switch disconnector

Powerpact 4 MCCB 100A 3P

Powerpact 4 MCCB 100A 4P

Powerpact 4 MCCB 125A 1P

Powerpact 4 MCCB 125A 2P

Powerpact 4 MCCB 125A 3P

Powerpact 4 MCCB 125A 4P

Powerpact 4 MCCB 160A 1P

Powerpact 4 MCCB 160A 2P

Powerpact 4 MCCB 160A 3P

Powerpact 4 160A 3P switch disconnector

Powerpact 4 MCCB 160A 4P

Powerpact 4 160A 4P switch disconnector

Powerpact 4 MCCB 200A 3P

Powerpact 4 MCCB 200A 4P

Powerpact 4 MCCB 250A 3P

Powerpact 4 lug unit 3P

Powerpact 4 250A 3P switch disconnector

Powerpact 4 250A 3P switch disconnector

Powerpact 4 MCCB 250A 3P

Powerpact 4 MCCB 250A 4P

Powerpact 4 lug unit 4P

Powerpact 4 250A 4P switch disconnector

Powerpact 4 250A 4P switch disconnector

Powerpact 4 MCCB 250A 4P

Powerpact 4 neutral link 250A

Powerpact 4 MCCB 400A 3P

Powerpact 4 400A 3P switch disconnector

Powerpact 4 400A 3P switch disconnector

Powerpact 4 MCCB 400A 3P

Powerpact 4 MCCB 400A 4P

Powerpact 4 400A 4P switch disconnector

Powerpact 4 400A 4P switch disconnector

Powerpact 4 MCCB 400A 4P

Powerpact 4 MCCB 630A 3P

Powerpact 4 630A 3P switch disconnector

Powerpact 4 630A 3P switch disconnector

Powerpact 4 MCCB 630A 3P

Powerpact 4 MCCB 630A 4P

Powerpact 4 630A 4P switch disconnector

Powerpact 4 630A 4P switch disconnector

Powerpact 4 MCCB 630A 4P

Powerpact 4 neutral link 630A

Powerpact 4 800A 3P incoming

Powerpact 4 800A 3P switch disconnector

Powerpact 4 800A 4P incoming

Powerpact 4 800A 4P switch disconnector

Powerpact 4 25mm blank plate

Powerpact 4 SP blank plate

PP4 Panelboard corner unit 200H x 250W

PP4 Panelboard corner unit 200H x 500W

PP4 Panelboard corner unit 400H x 250W

PP4 Panelboard corner unit 400H x 500W

Powerpact 4 shrouding kit 12 way

Powerpact 4 shrouding kit 18 way

Powerpact 4 shrouding kit 6 way

12 way left hand metering box

12 way right hand metering box

18 way left hand metering box

18 way right hand metering box

6 way left hand metering box

6 way right hand metering box

Powerpact 4 MCCB 16A 16kA 3P

Powerpact 4 MCCB 25A 16kA 3P

Powerpact 4 MCCB 40A 16kA 3P

Powerpact 4 MCCB 63A 16kA 3P

Powerpact 4 MCCB 80A 16kA 3P

Powerpact 4 MCCB 100A 16kA 3P

Powerpact 4 MCCB 125A 16kA 3P

Gland plate for Powerpact 4 630/800A

Powerpact 4 direct incomer 630A

Padlock with 2 keys

Spare key

Powerpact 4 door lock up to 800A

Powerpact 4 MG6P6 250mm extension

Powerpact 4 MG6P12 250mm extension

Powerpact 4 MG6P18 250mm extension

Powerpact 4 MG6P6 500mm extension

Powerpact 4 MG6P21 500mm extension

Powerpact 4 MG6P18 500mm extension

Powerpact 4 ICDSN unit for 6 way

Panelboard ICDSN unit for 12 way

100A 1P terminal block

Part Page No.Description

MGTB1252

MGTB1254

MGTB2504

MGV250102

MGV630302

MGV630304

MGV631002

MGV633002

MGV633004

MSIS95AN

NKIT

PM700MG

PM700PMG

PM710MG

PRGPM

RMG1000302

RMG1001002

RMG1001002S

RMG1003002

RMG160102

RMG250102

RMG250302

RMG250304

RMG253004

RMG400302

RMG400304

RMG403002

RMG403004

RMG630302

RMG630304

RMG631002

RMG631004

RMG633002

RMG633004

RMG800302

RMG801002

RMG803002

2499

2504

2505

2506

2507

2508

2510

2514

2515

2516

2517

2518

2520

2521

2524

2525

2526

2527

2528

2530

2554

2556

2557

2560

3908

4012

4013

4014

4583

4584

4585

4586

4587

4588

4590

4629

5056

5114

5115

5116

5196

5224

5502

5503

5504

5505

125A 2P terminal block

125A 4P terminal block

250A 4P terminal block

25A 10MA 2P Vigi

63A 30MA 2P Vigi

63A 30MA 4P Vigi

63A 100MA 2P Vigi

63A 300MA 2P Vigi

63A 300MA 4P Vigi

250A Incoming components for MG pan assembley

Pack of 4 neutral links

PowerLogic Meter

PowerLogic Meter

PowerLogic Meter

Gland plate metal

100A 30MA 2P RCD

100A 100MA 2P RCD

2P 100A 100MA

100A 300MA 2P RCD

16A 10MA 2P RCD

25A 10MA 2P

25A 30MA 2P RCD

25A 30MA 4P RCD

25A 300MA 4P RCD

40A 30MA 2P RCB

40A 30MA 4P RCD

40A 300MA 2P RCB

40A 300MA 4P RCD

63A 30MA 2P RCB

63A 30MA 4P RCD

63A 100MA 2P RCB

63A 100MA 4P RCD

63A 300MA 2P RCD

63A 300MA 4P RCD

80A 30MA 2P RCD

80A 100MA 2P RCD

80A 300MA 2P RCD

Aerosol paint - RAL7032

430x330x200mm enclosure and door

530x430x200mm enclosure and door

650x440x250mm enclosure and door

750x540x300mm enclosure and door

850x640x300mm eenclosure and door

1055x850x350mm enclosure and door

430x330x200mm enclosure and door

530x430x200mm enclosure and door

650x440x250mm enclosure and door

750x540x300mm enclosure and door

850x640x300mm enclosure and door

1055x850x350mm enclosure and door

External wall fixing lugs

Chassis for 430mm high enclosure

Chassis for 530mm high enclosure

Chassis for 650mm high enclosure

Chassis for 750mm high enclosure

Chassis for 850mm high enclosure

Chassis for 1055mm high enclosure

Variable sliders for 200mm enclosure

Variable sliders for 250mm enclosure

Variable sliders for 300mm enclosure

Variable sliders for 350mm enclosure

92x92 blanking plate

2P 1P+N Multiclip distribution block

3P Multiclip distribution block

4P 3P+1N Multiclip distribution block

Enclosure 300x250x150mm + door

Enclosure 400x300x200mm + door

Enclosure 500x400x200mm + door

Enclosure 600x400x200mm + door

Enclosure 700x500x200mm + door

Enclosure 800x600x250mm + door

Enclosure 1000x800x250mm + door

Enclosure external + lugs

Enc stackable spacers, H=55mm

Enclosure clip-on nuts, M4 (x20)

Enclosure clip-on nuts, M5 (x20)

Enclosure clip-on nuts, M6 (x20)

UT enclosure key lock handle + 2 keys

Enclosure stack spacers,M8,H=50mm

Prisma GK W-M enclosure 7 mod.

Prisma GK W-M enclosure 11 mod.

Prisma GK W-M enclosure 15 mod

Prisma GK W-M enclosure 19 mod

Part Page No.Description

IndexBy part number

79

25

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46

23, 25, 27, 29, 31, 46, 47

25, 27

23, 25, 27, 47

27

27

23, 25, 27, 29, 31, 46, 47

25, 27

23, 25, 27, 47

27

27

23, 25, 27, 29, 31,46

27, 29, 31, 46, 47

27, 47

27

27

27, 29, 31, 46, 47

27, 47

27

27

27, 29, 31, 46, 47

27, 47

27

27

27 29 31 46 47

27 47

27

27

27, 29, 31, 46

29

29

29

29

27, 29, 31, 33, 46, 47

23, 27, 29, 31, 33, 46, 47

27, 29

27, 29

29

29

27, 29, 34, 49

27, 29, 34, 49

27, 29, 34, 49

39

39

39

39

39

39

25

25

25

25

25

25

25

34

27, 47

34

27, 29

27, 29

27, 29

27, 29

27, 29

27, 29

34

34

38, 41

38, 41

38, 41

23, 40

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 79

Page 80: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

5506

5507

5508

5532

5533

5534

5535

5536

5537

5538

5542

5543

5544

5545

5546

5547

5548

5557

5580

6619

7046

7802

7803

7804

7805

7806

7813

7814

8961

8962

8963

9211

9214

9218

9219

9220

9224

9228

9231

9234

9238

9239

9240

9244

9248

9251

9252

9253

9254

9255

9257

9263

9264

9265

9266

9268

9917

10901

10902

10903

10904

10911

10912

10913

10914

13392

13394

13396

13398

13429

13430

13441

13442

13443

13444

13512

13514

13575

13576

13577

13578

13579

13581

IndexBy part number

80

Prisma GK W-M enclosure 23 mod

Prisma GK W-M enclosure 27 mod

Prisma GK W-M enclosure 33 mod

Prisma GK plain door 7 mod.

Prisma GK plain door 11 mod.

Prisma GK plain door 15 mod.

Prisma GK plain door 19 mod.

Prisma GK plain door 23 mod.

Prisma GK plain door 27 mod.

Prisma GK plain door 33 mod.

Prisma GK trans. Door 7 mod.

Prisma GK trans. Door 11 mod.

Prisma GK trans. Door 15 mod.

Prisma GK trans. Door 19 mod.

Prisma GK trans. Door 23 mod.

Prisma GK trans. Door 27 mod.

Prisma GK trans. Door 33 mod.

Canopy W600 + hardware

Prisma GK handle + 2 key

5 Pratic adaptors

12x2 mm flat bar, L=461mm

plain front plate 2 mod

Plain front plate, 3 mod

Plain front plate, 4 mod

Plain front plate, 5 mod

Plain front plate, 6 mod

Prisma front plate 3 mods

Prisma front plate 4 mod

RAL9001 touch up paint - brush

RAL9001 touch up paint - spray

Plastic drawing pocket

Perforated mounting plate 300

Perforated mounting plate 400

Perforated mounting plate 500

Perforated mounting plate 600

Perforated mounting plate 700

Perforated mounting plate 800

Perforated mounting plate 1000

Plain mounting plate 300x200

Plain mounting plate 400x300

Plain mounting plate 500x400

Plain mounting plate 600x400

Plain mounting plate 700x500

Plain mounting plate 800x600

Plain mounting plate 1000x800

Vertical uprights 400 nominal

Vertical uprights 500 nominal

Vertical uprights 600 nominal

Vertical uprights 700 nominal

Vertical uprights 800 nominal

Vertical uprights 1000 nomina

4 Multi fix rails 300 nominal

4 Multi fix rails 400 nominal

4 Multi fix rails 500 nominal

4 Multi fix rails 600 nominal

4 Multi fix rails 800 nominal

Set of screw

1 row Pragma C IP40 + door

2 row Pragma C IP40 + door

3 row Pragma C IP40 + door

4 row Pragma C IP40 + door

1 row Pragma C IP40 + Door

2 row Pragma C IP40 + Door

3 row Pragma C IP40 + Door

4 row Pragma C IP40 + Door

2 SP way Mini Opale enclosure

4 SP way Mini Opale enclosure

6 SP way Mini Opale enclosure

8 SP way Mini Opale enclosure

Blanking/label 10x5 way

Blanking strip 24 way

Kaedra 4 mod ins enclosure IP65

Kaedra 6 mod ins enclosure IP65

Kaedra 8 mod ins enclosure IP65

Kaedra 12 mod ins enclosure IP65

125A 4P multi-stage distribution block

125A 4P multi-stage distribution block

80A, 4 hole strip terminal block

80A terminal bock 8 hole

80A terminal bock 16 hole

80A, 22 hole strip terminal block

80A terminal bock 32 hole

80A terminal bock 32 hole

Part

34

34

34

Page No.Description

13582

13583

13584

13585

13586

13587

13589

13600

13625

13665

13730

13811

13812

13813

13814

13815

13816

13841

13842

13843

13844

13845

13846

13851

13852

13853

13854

13855

13856

13861

13863

13864

13866

13871

13875

13876

13877

13879

13880

13947

13948

14181

14190

14210

14211

14599

14603

14801

14802

14803

14804

14811

14812

14813

14814

14818

14880

14881

14882

14883

14884

14885

14886

14887

14888

14890

14891

14892

14893

14894

14915

14936

14937

14938

14939

14949

14962

14963

14964

14965

14975

14976

14977

4/8 hole terminal block yell/gr cover

IP2 cover for terminal block grn

4/8 hole terminal block red cover

IP2 cover for terminal block red

8 hole terminal block blue cover

IP2 cover for block blue 16

IP2 cover for block blue 16

Sloping terminal block support

Key lock for IP55 pragma c/d

Pragma C enclosure lock + key

Blanking strip grey 10x5 Mod

1 row Pragma metal enclosure

2 row Pragma metal enclosure

3 row Pragma metal enclosure

4 row Pragma enclosure

5 row Pragma enclosure

6 row Pragma enclosure

1 row Pragma enclosure + door

2 row Pragma enclosure + door

3 row Pragma enclosure + door

4 row Pragma enclosure + door

5 row Pragma enclosure + door

6 row Pragma enclosure + door

1 row Pragma enclosure + door

2 row Pragma enclosure + door

3 row Pragma enclosure + door

4 row Pragma enclosure + door

5 row Pragma enclosure + door

6 row Pragma enclosure + door

Interpact mounting/front plate

NS mounting plate & front plate

Pragma slotted mounting plate

Connections to Polybloc

1 row plain front plate

160A connection blocks

Earth/neutral terminal block

Enclosure door lock key No. 405

Label strip 24 pole

Enclosure touch up paint

Kaedra sealing kit

Lock & key for IP65 Mini Pragma

4 wall mounting brackets

Glands for Kaedra

Prisma P window 10 mod

Prisma P DIN rail support 10 mod

4 SP way G9 IP30 steel enclosure

5 SP way G9 IP30 steel enclosure

1P comb busbar, 108x9mm

2P comb busbar, 108x9mm

3P comb busbar, 108x9mm

3P+N comb busbar, 108x9mm

1P comb busbar, 27mm pitch

2P comb busbar, 27mm pitch

3P comb busbar, 27mm pitch

4P comb busbar, 27mm pitch

Comb busbar end and tooth caps

1P+N comb busbar, 26x9mm

1P comb busbar, 24x9mm

2P comb busbar, 24x9mm

3P comb busbar, 24x9mm

4P comb busbar, 24x9mm

4 25mm2 insulated connectors

End caps 1P/2P/1P+N comb x40

End caps 3P/4P/3P+N comb x40

Tooth caps for comb teeth x40

Comb busbar, 1 P + N, 48x9mm

1P comb busbar (x2) 48x9mm

2P comb busbar 2x48mm

3P comb busbar (x2) 48x9mm

4P comb busbar (x2) 48x9mm

Symm/asym rail stops(x10)

1P terminal block

2P terminal block

1P terminal block

2P terminal block

140A 12 hole stepped terminals

80A 4 hole connection strip

80A 7 hole connection strip

80A 11 hole connection strip

125A,14 hole connection strip

80A 4 hole distribution block

125A 6 hole distribution block

125A 10 hole distribution block

Part Page No.Description

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 80

Page 81: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

14979

14989

15005

15006

15007

15008

15009

15010

15011

15012

15013

15014

15015

15016

15019

15020

15023

15024

15057

15059

15060

15063

15064

15090

15091

15092

15093

15094

15096

15100

15101

15125

15126

15151

15152

15196

15201

15202

15208

15209

15212

15213

15214

15215

15216

15218

15219

15220

15222

15233

15266

15268

15270

15280

15281

15284

15319

15320

15321

15322

15323

15335

15336

15337

15338

15359

15363

15365

15366

15367

15368

15393

15409

15410

15411

15416

15440

15443

15464

15465

15466

15467

15500

125A 14 hole distribution block

Blue & yellow/green ident cards

20A 1P (I) switch disconnector

20A 2P (I) switch disconnector

20A 3P (I) switch disconnector

20A 4P (I) switch disconnector

32A 1P (I) switch disconnector

32A 2P (I) switch disconnector

32A 3P (I) switch disconnector

32A 4P (I) switch disconnector

63A 1P (I) switch disconnector

63A 2P (I) switch disconnector

63A 3P (I) switch disconnector

63A 4P (I) switch disconnector

40A 4P I switch disconector

40A 2P I switch disconector

40A 3P I switch disconector

40A SP I switch disconector

125A 1P (I) switch disconnector

125A 3P (I) switch disconnector

125A 4P (I) switch disconnector

20A SP I sw'h discon'r + Indic'r

20A 2P I sw'h discon'r + Indic'r

100A 1P (I) switch disconnector

100A 2P (I) switch disconnector

100A 3P (I) switch disconnector

100A 4P (I) switch disconnector

Terminal shield (1P PR) for 100A

I switch disconnr auxiliary switch

32A SP I sw'h discon'r + Indic'r

32A 2P I sw'h discon'r + Indic'r

CMV voltmeter selector switch

CMA ammeter selector switch

Device holder - 22mm

Device holder - Universal

PM9 Multimeter

0 - 600Vac digital voltmeter

0 - 10A digital ammeter

20 - 100Hz digital frequency meter

Digital Ammeter range 0 - 5000A

240 - 8 - 12Vac 16VA bell transformer

240 - 8 - 12Vac 4VA bell transformer

Bell transformer 4VA 230 / 8 v

Bell transformer 25VA 230 / 12 - 24 v

240 - 8 - 12Vac 8VA bell transformer

240 - 12/24Vac 16VA transformer

240 - 12/24Vac 25VA transformer

240 - 12/24Vac 40VA transformer

240 - 12/24Vac 63VA transformer

MINp Delay off timer

IC2000P light level time switch

Photo cell for IC2000

Multi function time switch

Memory for MF timeswitch 15270

Photo cell for IC2000

IC200 light sensing switch

63A contactor 2NO+1NC 240V coil

SO bell 220/240 Volt

SO bell 12 Volt

RO buzzer 220/240 Volt

RO buzzer 12 Volt

24HR analogue time switch

24HR analogue time switch

IH 1c 24hr 150hr reserve 2 chan'l

IH 60 minute analogue time switch

MIN timer terminal shield

MIN time switch 1 - 7mins

IH 24 hour analogue time switch

IH 24 hour + 7 day analogue

IH 7 day analogue time switch

IC2000 light sensitive switch

2A 240Vac RBN changeover relay

ATLC+S impulse relay auxiiary

ATLC+C impulse relay aux

ATLT impulse relay aux

RTBT interface relay

Hours counter 240V

CI Impulse counting module

Single phase kilowatt hour meter

Three phase kilowatt hour meter

Single phase kWH meter

Three phase kWH meter

16A 1P 230 - 240Vac coil TL relay

Part Page No.Description

15502

15503

15505

15510

15511

15512

15513

15514

15515

15516

15517

15518

15520

15521

15522

15523

15524

15525

15526

15527

15528

15530

15531

15532

15533

15534

15535

15536

15537

15538

15539

15540

15541

15542

15636

15646

15651

15656

15658

15668

15687

15688

15689

15690

15692

15693

15695

15696

15720

15721

15722

15723

15775

15776

15777

15779

15840

15841

15845

15846

15847

15848

15854

15914

15917

15919

15920

15921

15922

15923

15957

15958

15959

15960

15961

15962

15963

15964

15966

15967

15968

15969

15971

1P 48Vac 24Vdc TLI relay

16A 1P 24Vac coil TL relay

32A 1P 230 - 240Vac ETL for TL32

16A 1P 230 - 240Vac coil TL relay

16A 1P 130Vac 48Vdc TL relay

16A 1P 48Vac 24Vdc TL relay

16A 1P 24vac coil TL relay

16A 1P 12Vac coil TL relay

32A 1P 230 - 240Vac coil TL relay

TLM impulse relay

TLS impulse relay

TLC impulse relay

16A 2P 230 - 240vac coil TL relay

16A 2P 130Vac 48Vdc relay

16A 2P 48Vac 24Vdc relay

16A 2P 24Vac coil TL relay

16A 2P 12vac coil TL relay

TLc impulse relay 24Vac

TLc impulse relay 48Vac

TLs impulse relay 24Vac 12Vdc

TLs impulse relay 48Vac 24Vdc

ETL 230 - 240Vac coil aux for Tl/TLI

16A 1P 130Vac 48Vdc ETL relay

16A 1P 48Vac 24Vdc ETL relay

ETL 24Vac coil aux for TL/TLI

16A 1P 12Vac 6Vdc ETL relay

10A (AC1) 240Vac RLI relay

10A (AC1) 48Vac RLI relay

10A (AC1) 24Vac RLI relay

10A (AC1) 12Vac RLI relay

10A (AC1) 240Vac ERL extension

10A (AC1) 48Vac ERL extension

10A (AC1) 24Vac ERL extension

10A (AC1)12Vac ERL extension

1 pole STI fuse carier

1 pole and neutral STI fuse carier

2 pole STI fuse carrier

3 pole STI fuse carier

3 pole and neutral STI fuse carier

Blown fuse indicator

PF30 10kA 1P+N surge arrester

PF30 10kA 3P+N surge arrester

PF30r 10kA 1P+N surge arrester

PF30r 10kA 3P+N surge arrester

PF15 5kA 1P+N surge arrester

PF15 5kA 3P+N surge arrester

PF8 2kA 1P+N surge arrester

PF8 2kA 3P+N surge arrester

1 channel IHP time switch

1 channel IHP time switch

2 channel IHP time switch

2 channel IHP time switch

2A gG fuse links 10.3x38mm

4A gG fuse links 10.3x38

6A gG fuse links 10.3x38mm

10A gG fuse links 10.3x38mm

TH6 thermostat

TH3 thermostat

TH6 thermostat ground probe

TH6 thermostat ambient probe

TH6 thermostat outdoor probe

TH6 thermostat collar probe

IHP 18mm I channel

ACTo+F add on aux contact

ACTt add on time delay unit

ACTp filter 24V devices

ACTp filter 240V devices

25A 3/4P contactor screw shield

40/63A 2P contactor screw shield

63A 3/4P contactor screw shield

Contactor 16A 2NC 240V ac

25A 1P contactor 240V ac

25A 2P contactor 240Vac coil

25A 2P contactor 240Vac coil

25A 3P contactor 240V coil

25A 4P contactor 240Vac coil

25A 4P contactor 240Vac coil

25A 4P contactor 2NO+2NC

40A 2P contactor 240V coil

40A 3P contactor 240V coil

40A 4P contactor 240V coil

40A 4P contactor 240V coil

63A 2P contactor 240V coil

Part Page No.Description

IndexBy part number

81

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 81

Page 82: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

15972

15973

15974

15975

15977

15978

15981

15982

15983

15984

15986

15987

15988

16020

16022

16023

16024

16025

16026

16029

16030

16031

16032

16033

16034

16035

16036

16037

16038

16039

16040

16041

16042

16043

16044

16045

16060

16061

16065

16066

16067

16068

16069

16070

16111

16113

16115

16116

16118

16120

16122

16124

16126

16127

16129

16130

16261

16364

16451

16452

16453

16454

16456

16459

16460

16461

16462

16463

16464

16465

16468

16469

16470

16471

16473

16474

16476

16477

16478

16479

16480

16481

16482

IndexBy part number

82

63A 3P contactor 3NO 240Vac coil

63A 4P contactor 240Vac coil

63A 4P contactor 240Vac coil

63A 4P contactor 2NO+2NC

100A 2P contactor 240V coil

100A 4P contactor 240V coil

25A 2P contactor with manual ctrl

Contactor W/MANL 3NO 25A

25A 4P contactor with manual ctrl

40A 2P contactor with manual ctrl

40A 4p contactor 4NO 240Vac coil

63A 2P contactor with manual ctrl

63A 4P contactor with manual ctrl

25A 2P contactor 24Vac coil

25A 4P contactor 24Vac coil

25A 4P contactor 24Vac coil

63A 2P contactor 24V coil

63A 4P contactor 24Vac coil

63A 4P contactor 24Vac coil

Ammeter 0 - 30A direct connection

AMP ammeter without scale 5A

AMP ammeter scale 0 - 5A

AMP ammeter scale 0 - 50A

AMP ammeter scale 0 - 75A

AMP ammeter scale 0 - 100A

AMP ammeter scale 0 - 150A

AMP ammeter scale 0 - 200A

AMP ammeter scale 0 - 250A

AMP ammeter scale 0 - 300A

AMP ammeter scale 0 - 400A

AMP ammeter scale 0 - 500A

AMP ammeter scale 0 - 600A

AMP ammeter scale 0 - 800A

AMP ammeter scale 0 - 1000A

AMP ammeter scale 0 - 1500A

AMP ammeter scale 0 - 2000A

0 - 300V Modular Voltmeter

VLT voltmeter 0 - 500V

RTA time delay before ON relay

RTB time delay before OFF relay

RTC time delay before OFF relay

RTH time delay before OFF relay

RTL pulsed On and OFF timer

RTMF time delay relay

16A contactor 1NC 24Vac coil

16A contactor 1NO 240Vac coil

16A contactor 2NC 24Vac coil

16A contactor 2NC 240Vac+Man

16A contactor 3NC 24Vac coil

16A contactor 3NC 240Vac coil

16A contactor 4NC 24Vac coil

16A contactor 4NC 240Vac coil

16A contactor 1NO+1NC 24Vac

16A contactor 1NO+1NC 240Vac

16A contactor 2NO+2NC 24Vac

16A contactor 2NO+2NC 240Vac

80A 30mA 4P RCCB RMG

IH 1c 24hr no reserve

CT 50/5 trop 21mm ID 1.25VA

CT 75/5 trop 21mm ID 1.5VA

CT 100/5 trop 21mm ID 2.5VA

CT 125/5 trop 21mm ID 4VA

CT 200/5 trop 21mm ID 6VA

CT 150/5 trop 22 ID/30x10 5.5VA

CT 200/5 trop 22 ID/30x10 7VA

CT 250/5 trop 22 ID/30x10 9VA

CT 300/5 trop 22 ID/30x10 11VA

CT 400/5 trop 22 ID/30x10 15VA

CT 500/5 trop 22 ID/30x10 18VA

CT 600/5 trop 22ID/30x10 21.5VA

CT 250/5 trop 35 ID/40x10 5VA

CT 300/5 trop 35 ID/40x10 8VA

CT 400/5 trop 35 ID/40x10 12VA

CT 500/5 trop 35 ID/40x10 12VA

CT 500/5 trop 51X31/64X11

CT. 600/5 TROP 51X31/64X12

CT 200/5 trop 65x32 slot 2VA

CT 250/5 trop 65x32 slot 4VA

CT 300/5 trop 65x32 slot 6VA

CT 400/5 trop 65x32 slot 7.5VA

CT 500/5 trop 65x32 slot 10VA

CT 600/5 trop 65x32 slot 10VA

CT 800/5 trop 65x32 slot 15VA

Part Page No.Description

16483

16500

16501

16502

16503

16504

16505

16506

16509

16510

16511

16512

16513

16514

16515

16518

16519

16520

16521

16523

16524

16528

16529

16530

16531

16532

16533

16534

16535

16537

16538

16540

16541

16542

16543

16544

16545

16547

16548

16549

16550

16551

16552

16553

16557

16558

16559

16562

16563

16564

16567

16568

16569

16572

16573

16574

16577

16578

16579

16581

16583

16585

16587

16589

16590

16591

16627

16956

16990

16992

16994

16995

17065

17066

17067

17070

17071

17072

17075

17076

18030

18031

18032

CT 1000/5 trop 65x32 slot 20VA

CT 40/5 trop 21mm ID 1VA

CT 50/5 STD 21mm ID 1.25VA

CT 75/5 STD 21mm ID 1.5VA

CT 100/5 STD 21mm ID 2.5VA

CT 125/5 STD 21mm ID 4VA

CT 150/5 STD 21mm ID 4VA

CT 200/5 STD 21mm ID 6VA

CT 150/5 STD 22 ID/30x10 5.5VA

CT 200/5 STD 22 ID/30x10 7VA

CT 250/5 STD 22 ID/30x10 9VA

CT 300/5 STD 22 ID/30x10 11VA

CT 400/5 STD 22 ID/30x10 15VA

CT 500/5 STD 22 ID/30x10 18VA

CT 600/5 STD 22 ID/30x10 21.5VA

CT 250/5 STD 35 ID/40x10 5VA

CT 300/5 STD 35 ID/40x10 8VA

CT 400/5 STD 35 ID/40x10 12VA

CT 500/5 STD 35 ID/40x10 12VA

CT 500/5 STD 51X31/64X11

CT 600/5 STD 51X31/64X11

CT 300/5 STD 65x32 slot 6VA

CT 400/5 STD 65x32 slot 7.5VA

CT 500/5 STD 65x32 slot 10VA

CT 600/5 STD 65x32 slot 10VA

CT 800/5 STD 65x32 slot 15VA

CT 1000/5 STD 65x32 slot 20VA

CT 1250/5 trop 65x32 slot 25VA

CT 1500/5 trop 65x32 slot 30VA

CT 1250/5

CT 1500/5 trop 84x34 slot 20VA

CT 1250/5 trop 127x38 slot 12VA

CT 1500/5 trop 127x38 slot 15VA

CT 2000/5 trop 127x38 slot 20VA

CT 2500/5 trop 127x38 slot 25VA

CT 3000/5 trop 127x38 slot 30VA

CT 2500/5 trop 127x52 slot 50VA

CT 4000/5 trop 127x52 slot 80VA

CT 5000/5 trop 165x55 slot 60VA

CT 6000/5 trop 165x55 slot 70VA

copper sleeve for 21mm ID CT

copper sleeve for 22mm ID CT

CT terminal cover

CT terminal cover

PRD65r 1P+N surge arrester

PRD65r 3P surge arrester

PRD65r 3P+N surge arrester

PRD40r 1P+N surge arrester

PRD40r 3P surge arrester

PRD40r 3P+N surge arrester

PRD40 1P+N surge arrester

PRD40 3P surge arrester

PRD40 3P+N surge arrester

PRD15 1P+N surge arrester

PRD15 3P surge arrester

PRD15 3P+N surge arrester

PRD8 1P+N surge arrester

PRD8 3P surge arrester

PRD8 3P+N surge arrester

C65r - 275 surge arrester cartridge

C40r - 275 surge arrester cartridge

C40 - 275 surge arrester cartridge

C15 - 275 surge arrester cartridge

C8 - 275 surge arrester cartridge

C neutral r surge arrester cartridge

C neutral surge arrester cartridge

Curr transf 250/5

16A 2P contactor 1NO+1NC

CDM PIR detector

Presence detector

CDPt Pressence detector

CDPt additional remote

ME1 kilowatt hour meter 63A

ME1z kilowatt hour meter 63A

ME1zr kilowatt hour meter 63A

ME4 kilowatt hour meter 63A

6E4zr kilowatt hour meter 63A

ME4zrt kilowatt hour meter 63A

ME3 kilowatt hour meter 63A

ME3zr kilowatt hour meter 63A

BP Grey pushbutton 1NC

BP Red pushbutton 1NC

BP Grey pushbutton 1NO

Part Page No.Description

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 82

Page 83: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

18033

18034

18035

18036

18037

18038

18039

18070

18071

18072

18073

18074

18308

18309

18310

18311

18312

18320

18321

18322

18323

18324

18326

18327

18330

18331

18332

18333

18334

18335

18394

18395

18396

18397

18398

18399

18400

18401

18402

18403

18404

18405

18406

18407

18408

18409

18410

18411

18412

18413

18414

18415

18416

18417

18418

18419

18420

18421

18422

18423

18424

18425

18426

18427

18428

18429

18430

18431

18432

18433

18434

18435

18436

18437

18438

18439

18440

18441

18442

18443

18444

18445

18446

BP Grey pushbutton 1NO + 1NC

BP Double pushbutton 1NC + 1NO

BP Double pushbutton 1NO + 1NO

Grey p/button 1NO+ light

Grey p/button 1NC+red light

Grey p/button 1NO+green light

Grey p/button 1NC+red light

CM 2 pos 20A selector switch

CM 2 pos 20A selector switch

CM 2 pos 20A selector switch

CM 3 pos 20A selector switch

CM 3 pos 20A selector switch

Contactor auxiliary ACTC

Contactor auxiliary ACTC

1P/2P TMC60 remote control

3P/4P TMC60 remote control

1 - 2P Tm remote control

V 110/230Vac red indicator light

V 110/230Vac green indicator light

V 110/230Vac white indicator light

V 110/230Vac blue indicator light

V 110/230Vac yellow indicator light

V 230Vac red flash indicator light

3 phase indicator lights 230/400V

V 12/48Vac/dc red indicator light

V 12/48Vac/dc green indicator light

V 12/48Vac/dc white indicator light

V 12/48Vac/dc blue indicator light

V 12/48Vac/dc yellow indicator light

110/230Vac double indicator light

10A 1P 15kA C120H MCB Type B

16A 1P 15kA C120H MCB Type B

20A 1P 15kA C120H MCB Type B

25A 1P 15kA C120H MCB Type B

32A 1P 15kA C120H MCB Type B

40A 1P 15kA C120H MCB Type B

50A 1P 15kA C120H MCB Type B

63A 1P 15kA C120H MCB Type B

80A 1P 15kA C120H MCB Type B

100A 1P 15kA C120H MCB Type B

125A 1P 15kA C120H MCB Type B

10A 2P 15kA C120H MCB Type B

16A 2P 15kA C120H MCB Type B

20A 2P 15kA C120H MCB Type B

25A 2P 15kA C120H MCB Type B

32A 2P 15kA C120H MCB Type B

40A 2P 15kA C120H MCB Type B

50A 2P 15kA C120H MCB Type B

63A 2P 15kA C120H MCB Type B

80A 2P 15kA C120H MCB Type B

100A 2P 15kA C120H MCB Type B

125A 2P 15kA C120H MCB Type B

10A 3P 15kA C120H MCB Type B

16A 3P 15kA C120H MCB Type B

20A 3P 15kA C120H MCB Type B

25A 3P 15kA C120H MCB Type B

32A 3P 15kA C120H MCB Type B

40A 3P 15kA C120H MCB Type B

50A 3P 15kA C120H MCB Type B

63A 3P 15kA C120H MCB Type B

80A 3P 15kA C120H MCB Type B

100A 3P 15kA C120H MCB Type B

125A 3P 15kA C120H MCB Type B

10A 4P 15kA C120H MCB Type B

16A 4P 15kA C120H MCB Type B

20A 4P 15kA C120H MCB Type B

25A 4P 15kA C120H MCB Type B

32A 4P 15kA C120H MCB Type B

40A 4P 15kA C120H MCB Type B

50A 4P 15kA C120H MCB Type B

63A 4P 15kA C120H MCB Type B

80A 4P 15kA C120H MCB Type B

100A 4P 15kA C120H MCB Type B

125A 4P 15kA C120H MCB Type B

10A 1P 15kA C120H MCB Type C

16A 1P 15kA C120H MCB Type C

20A 1P 15kA C120H MCB Type C

25A 1P 15kA C120H MCB Type C

32A 1P 15kA C120H MCB Type C

40A 1P 15kA C120H MCB Type C

50A 1P 15kA C120H MCB Type C

63A 1P 15kA C120H MCB Type C

80A 1P 15kA C120H MCB Type C

Part Page No.Description

18447

18448

18449

18450

18451

18452

18453

18454

18455

18456

18457

18458

18459

18460

18461

18462

18463

18464

18465

18466

18467

18468

18469

18470

18471

18472

18473

18474

18475

18476

18477

18478

18479

18480

18481

18482

18483

18484

18485

18486

18487

18488

18489

18490

18491

18492

18493

18494

18495

18496

18497

18498

18499

18500

18501

18502

18503

18504

18505

18506

18507

18508

18509

18510

18511

18512

18513

18514

18515

18516

18517

18518

18519

18520

18521

18522

18523

18524

18525

18526

18527

18528

18544

100A 1P 15kA C120H MCB Type C

125A 1P 15kA C120H MCB Type C

10A 2P 15kA C120H MCB Type C

16A 2P 15kA C120H MCB Type C

20A 2P 15kA C120H MCB Type C

25A 2P 15kA C120H MCB Type C

32A 2P 15kA C120H MCB Type C

40A 2P 15kA C120H MCB Type C

50A 2P 15kA C120H MCB Type C

63A 2P 15kA C120H MCB Type C

80A 2P 15kA C120H MCB Type C

100A 2P 15kA C120H MCB Type C

125A 2P 15kA C120H MCB Type C

10A 3P 15kA C120H MCB Type C

16A 3P 15kA C120H MCB Type C

20A 3P 15kA C120H MCB Type C

25A 3P 15kA C120H MCB Type C

32A 3P 15kA C120H MCB Type C

40A 3P 15kA C120H MCB Type C

50A 3P 15kA C120H MCB Type C

63A 3P 15kA C120H MCB Type C

80A 3P 15kA C120H MCB Type C

100A 3P 15kA C120H MCB Type C

125A 3P 15kA C120H MCB Type C

10A 4P 15kA C120H MCB Type C

16A 4P 15kA C120H MCB Type C

20A 4P 15kA C120H MCB Type C

25A 4P 15kA C120H MCB Type C

32A 4P 15kA C120H MCB Type C

40A 4P 15kA C120H MCB Type C

50A 4P 15kA C120H MCB Type C

63A 4P 15kA C120H MCB Type C

80A 4P 15kA C120H MCB Type C

100A 4P 15kA C120H MCB Type C

125A 4P 15kA C120H MCB Type C

10A 1P 15kA C120H MCB Type D

16A 1P 15kA C120H MCB Type D

20A 1P 15kA C120H MCB Type D

25A 1P 15kA C120H MCB Type D

32A 1P 15kA C120H MCB Type D

40A 1P 15kA C120H MCB Type D

50A 1P 15kA C120H MCB Type D

63A 1P 15kA C120H MCB Type D

80A 1P 15kA C120H MCB Type D

100A 1P 15kA C120H MCB Type D

125A 1P 15kA C120H MCB Type D

10A 2P 15kA C120H MCB Type D

16A 2P 15kA C120H MCB Type D

20A 2P 15kA C120H MCB Type D

25A 2P 15kA C120H MCB Type D

32A 2P 15kA C120H MCB Type D

40A 2P 15kA C120H MCB Type D

50A 2P 15kA C120H MCB Type D

63A 2P 15kA C120H MCB Type D

80A 2P 15kA C120H MCB Type D

100A 2P 15kA C120H MCB Type D

125A 2P 15kA C120H MCB Type D

10A 3P 15kA C120H MCB Type D

16A 3P 15kA C120H MCB Type D

20A 3P 15kA C120H MCB Type D

25A 3P 15kA C120H MCB Type D

32A 3P 15kA C120H MCB Type D

40A 3P 15kA C120H MCB Type D

50A 3P 15kA C120H MCB Type D

63A 3P 15kA C120H MCB Type D

80A 3P 15kA C120H MCB Type D

100A 3P 15kA C120H MCB Type D

125A 3P 15kA C120H MCB Type D

10A 4P 15kA C120H MCB Type D

16A 4P 15kA C120H MCB Type D

20A 4P 15kA C120H MCB Type D

25A 4P 15kA C120H MCB Type D

32A 4P 15kA C120H MCB Type D

40A 4P 15kA C120H MCB Type D

50A 4P 15kA C120H MCB Type D

63A 4P 15kA C120H MCB Type D

80A 4P 15kA C120H MCB Type D

100A 4P 15kA C120H MCB Type D

125A 4P 15kA C120H MCB Type D

C120 MCB terminal shield

C120 MCB terminal screw shield

Rear connection terminal + shield

300mA 2P C120H s Class AC Vigi

Part Page No.Description

IndexBy part number

83

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 83

Page 84: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

18545

18546

18547

18548

18549

18556

18557

18558

18559

18560

18561

18563

18564

18565

18566

18567

18568

18569

18570

18571

18572

18573

18574

18575

18576

18577

18578

18579

18580

18581

18582

18583

18584

18585

18586

18587

18588

18589

18591

18592

18593

18594

18595

18596

18597

18598

18599

18610

18611

18612

18613

18614

18615

18616

18617

18618

18621

18622

18623

18624

18625

18626

18627

18628

18629

18632

18633

18634

18635

18636

18637

18638

18639

18640

18642

18644

18649

18650

18651

18652

18653

18654

18655

IndexBy part number

84

1000mA 2P C120H s Class AC Vigi

300mA 3P C120H s Class AC Vigi

1000mA 3P C120H s Class AC Vigi

300mA 4P C120H s Class AC Vigi

1000mA 4P C120H s Class AC Vigi

300mA 2P C120H si Type Vigi

1000mA 2P C120H si Vigi

300mA 3P C120H si Type Vigi

1000mA 3P C120H si Type Vigi

300mA 4P C120H si Type Vigi

1000mA 4P C120H si Type Vigi

30mA 2P C120H Class AC Vigi

300mA 2P C120H Class AC Vigi

500mA 2P C120H Class AC Vigi

30mA 3P C120H Class AC Vigi

300mA 3P C120H Class AC Vigi

500mA 3P C120H Class AC Vigi

30mA 4P C120H Class AC Vigi

300mA 4P C120H Class AC Vigi

500mA 4P C120H Class AC Vigi

30mA 2P C120H Class A Vigi

300mA 2P C120H Class A Vigi

500mA 2P C120H Class A Vigi

30mA 3P C120H Class A Vigi

300mA 3P C120H Class A Vigi

500mA 3P C120H Class A Vigi

30mA 4P C120H Class A Vigi

300mA 4P C120H Class A Vigi

500mA 4P C120H Class A Vigi

300mA 2P C120H Class A Vigi

500mA 2P C120H Class A Vigi

1000mA 2P C120H Class A Vigi

300mA 3P C120H Class A Vigi

500mA 3P C120H Class A Vigi

1000mA 3P C120H Class A Vigi

300mA 4P C120H Class A Vigi

500mA 4P C120H Class A Vigi

1000mA 4P C120H Class A Vigi

30mA 2P C120H si Type Vigi

300mA 2P C120H si Type Vigi

500mA 2P C120H si Type Vigi

30mA 3P C120H si Type Vigi

300mA 3P C120H si Type Vigi

500mA 3P C120H si Type Vigi

30mA 4P C120H si Type Vigi

300mA 4P C120H si TypeVigi

500mA 4P C120H si Type Vigi

10A 1P 25kA NG125N curve C

16A 1P 25kA NG125N curve C

20A 1P 25kA NG125N curve C

25A 1P 25kA NG125N curve C

32A 1P 25kA NG125N curve C

40A 1P 25kA NG125N curve C

50A 1P 25kA NG125N curve C

63A 1P 25kA NG125N curve C

80A 1P 25kA NG125N curve C

10A 2P 25kA NG125N curve C

16A 2P 25kA NG125N curve C

20A 2P 25kA NG125N curve C

25A 2P 25kA NG125N curve C

32A 2P 25kA NG125N curve C

40A 2P 25kA NG125N curve C

50A 2P 25kA NG125N curve C

63A 2P 25kA NG125N curve C

80A 2P 25kA NG125N curve C

10A 3P 25kA NG125N curve C

16A 3P 25kA NG125N curve C

20A 3P 25kA NG125N curve C

25A 3P 25kA NG125N curve C

32A 3P 25kA NG125N curve C

40A 3P 25kA NG125N curve C

50A 3P 25kA NG125N curve C

63A 3P 25kA NG125N curve C

80A 3P 25kA NG125N curve C

100A 3P 25kA NG125N curve C

125A 3P 25kA NG125N curve C

10A 4P 25kA NG125N curve C

16A 4P 25kA NG125N curve C

20A 4P 25kA NG125N curve C

25A 4P 25kA NG125N curve C

32A 4P 25kA NG125N curve C

40A 4P 25kA NG125N curve C

50A 4P 25kA NG125N curve C

Part Page No.Description

18656

18658

18660

18662

18663

18664

18665

18666

18667

18668

18669

18670

18671

18672

18673

18674

18705

18706

18707

18708

18709

18710

18711

18712

18713

18714

18715

18716

18717

18718

18719

18720

18721

18722

18723

18724

18725

18726

18727

18728

18729

18730

18731

18732

18733

18734

18735

18736

18737

18738

18739

18740

18868

18869

18870

18871

18872

18873

18874

18875

18876

18879

18880

18881

18882

18883

18884

18885

18886

18887

18889

18890

18891

18892

18893

18894

18895

18896

19000

19001

19002

19003

19004

63A 4P 25kA NG125N curve C

80A 4P 25kA NG125N curve C

100A 4P 25kA NG125N curve C

125A 4P 25kA NG125N curve C

80A 3P 25kA NG125N curve B

100A 3P 25kA NG125N curve B

125A 3P 25kA NG125N curve B

80A 4P 25kA NG125N curve B

100A 4P 25kA NG125N curve B

125A 4P 25kA NG125N curve B

80A 3P 25kA NG125N curve D

100A 3P 25kA NG125N curve D

125A 3P 25kA NG125N curve D

80A 4P 25kA NG125N curve D

100A 4P 25kA NG125N curve D

125A 4P 25kA NG125N curve D

10A 1P 36kA NG125H curve C

16A 1P 36kA NG125H curve C

20A 1P 36kA NG125H curve C

25A 1P 36kA NG125H curve C

32A 1P 36kA NG125H curve C

40A 1P 36kA NG125H curve C

50A 1P 36kA NG125H curve C

63A 1P 36kA NG125H curve C

80A 1P 36kA NG125H curve C

10A 2P 36kA NG125H curve C

16A 2P 36kA NG125H curve C

20A 2P 36kA NG125H curve C

25A 2P 36kA NG125H curve C

32A 2P 36kA NG125H curve C

40A 2P 36kA NG125H curve C

50A 2P 36kA NG125H curve C

63A 2P 36kA NG125H curve C

80A 2P 36kA NG125H curve C

10A 3P 36kA NG125H curve C

16A 3P 36kA NG125H curve C

20A 3P 36kA NG125H curve C

25A 3P 36kA NG125H curve C

32A 3P 36kA NG125H curve C

40A 3P 36kA NG125H curve C

50A 3P 36kA NG125H curve C

63A 3P 36kA NG125H curve C

80A 3P 36kA NG125H curve C

10A 4P 36kA NG125H curve C

16A 4P 36kA NG125H curve C

20A 4P 36kA NG125H curve C

25A 4P 36kA NG125H curve C

32A 4P 36kA NG125H curve C

40A 4P 36kA NG125H curve C

50A 4P 36kA NG125H curve C

63A 4P 36kA NG125H curve C

80A 4P 36kA NG125H curve C

4A 2P NG125LMA

6.3A 2P NG125LMA

10A 2P NG125LMA

12.5A 2P NG125LMA

16A 2P NG125LMA

25A 2P NG125LMA

40A 2P NG125LMA

63A 2P NG125LMA

80A 2P NG125LMA

4A 3P NG125LMA

6.3A 3P NG125LMA

10A 3P NG125LMA

12.5A 3P NG125LMA

16A 3P NG125LMA

25A 3P NG125LMA

40A 3P NG125LMA

63A 3P NG125LMA

80A 3P NG125LMA

63A 3P NG125 NA switch dis

80A 3P NG125 NA switch dis

100A 3P NG125 NA switch dis

125A 3P NG125 NA switch dis

63A 4P NG125 NA switch dis

80A 4P NG125 NA switch dis

100A 4P NG125 NA switch dis

125A 4P NG125 NA switch dis

63A 2P NG125 Vigi 30mA

63A 2P NG125 Vigi 300mA

63A 3P NG125 Vigi 30mA

63A 3P NG125 Vigi 300mA

63A 4P NG125 Vigi 30mA

Part Page No.Description

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 84

Page 85: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

19005

19008

19009

19012

19013

19014

19015

19016

19030

19031

19032

19033

19034

19035

19036

19037

19039

19041

19042

19044

19046

19047

19049

19053

19054

19055

19056

19058

19059

19060

19064

19065

19066

19067

19068

19069

19070

19071

19072

19073

19074

19075

19076

19077

19078

19080

19081

19082

19083

19084

19085

19086

19087

19088

19089

19090

19091

19092

19093

19094

19095

19100

19101

19106

19107

19249

19250

19252

19254

19255

19256

19257

19258

19260

19261

19263

19264

19266

19268

19269

19270

19271

19272

63A 4P NG125 Vigi 300mA

63A 2P NG125 Vigi 30mA

63A 2P NG125 Vigi 300mA

63A 2P NG125 Vigi 30mA

63A 2P NG125 Vigi 300mA

63A 3P NG125 Vigi 30mA

63A 3P NG125 Vigi 300mA

63A 4P NG125 Vigi 30mA

63A 4P NG125 Vigi 300mA

63A 2P NG125 Vigi 300mA TD

63A 2P NG125 Vigi 1000mA TD

63A 3P NG125 Vigi 300mA TD

NG125 Vigi 3P 63A 1000mA TD

63A 4P NG125 Vigi 300mA TD

63A 4P NG125 Vigi 1000mA TD

63A 3P NG125 Vigi 300..3000mA

63A 4P NG125 Vigi 300..3000mA

125A 3P NG125 Vigi 30mA

125A 4P NG125 Vigi 30mA

125A 4P NG125 Vigi 300mA

125A 3P NG125 Vigi 300..1000mA

125A 4P NG125 Vigi 300..1000mA

125A 3P NG125 Vigi 300..3000mA

125A 4P NG125 Vigi 300..3000mA

63A 3P NG125 Vigi 300..3000mA

63A 4P NG125 Vigi 300..3000mA

125A 3P NG125 Vigi 300..3000mA

125A 4P NG125 Vigi 300..3000mA

NG125 Vigi SDV,NO aux contact

NG125 Vigi SDV,NC aux contact

NG125 Vigi MXV auxiliary

NG125 230..415Vac MX+OF aux

NG125 48..130Vac MX+OF aux

NG125 24Vac MX+OF auxiliary

240Vac voltage release (MN)

48Vac voltage release (MN)

48Vdc voltage release (MN)

OF+OF electrical auxiliary

OF+SD electrical auxiliary

OF+OF or OF+SD electrical aux/y

63A 2P NG125 RCD terminal shield

63A 3P NG125 RCD terminal shield

63A 4P NG125 RCD terminal shield

63A 3P NG125 RCd terminal shield

63A 4P NG125 RCD terminal shield

1P NG125 terminal shield

2P NG125 terminal shield

3P NG125 terminal shield

4P NG125 terminal shield

1P NG125 terminal screw shield (x10)

2P NG125 terminal screw shield (x10)

3P NG125 terminal screw shield (x10)

4P NG125 terminal screw shield (x10)

Rotary handle,standard black

Rotary handle,red/yellow front

NG125 padlocking accessory

INS40/80 bare cable connector (x4)

Direct Rotary Handle

NG125 connection screws&nuts

NG125 cable lugs

NG125 terminal for alu cable

125A 3P NG125 Vigi 30mA,si Type

125A 4P NG125 Vigi 30mA,si Type

125A 3P NG125 Vigi 300..3000mA

125A 4P NG125 Vigi 300..3000mA

4A 6kA DPN rated curve B

6A 6kA DPN rated curve B

10A 6kA DPN curve B

16A 6kA DPN curve B

20A 6kA DPN curve B

25A 6kA DPN curve B

32A 6kA DPN curve B

40A 6kA DPN curve B

1A 6kA DPN curve C

2A 6kA DPN curve C

4A 6kA DPN curve C

6A 6kA DPN curve C

10A 6kA DPN curve C

16A 6kA DPN curve C

20A 6kA DPN curve C

25A 6kA DPN curve C

32A 6kA DPN curve C

40A 6kA DPN curve C

Part Page No.Description

19661

19663

19665

19666

19667

19668

19669

20267

21100

21101

21102

21103

21104

21105

21106

21107

21108

21109

21110

21111

21112

21113

21115

21116

21117

21118

21119

21120

21121

21127

21128

21129

21130

21133

21140

21141

21142

21143

21144

21145

21146

21147

21148

21180

21181

23111

23116

23146

23213

23227

23249

23253

23258

23303

23308

24872

24873

24875

24876

24877

24878

24879

24880

24881

24882

24883

24884

25211

25212

25214

25215

25216

25217

25218

25219

25220

25221

25222

25223

26476

26477

26478

26483

6A 30mA 2P DPN Vigi curve C

10A 30mA 2P DPN Vigi curve C

16A 30mA 2P DPN Vigi curve C

20A 30mA 2P DPN Vigi curve C

25A 30mA 2P DPN Vigi curve C

32A 30mA 2P DPN Vigi curve C

40A 30mA 2P DPN Vigi curve C

Brackets for through door mounting

0.1 - 0.16A P25M MCB

0.16 - 0.25A P25M MCB

0.25 - 0.4A P25M MCB

0.4 - 0.63A P25M MCB

0.63 - 1A P25M MCB

1 - 1.6A P25M MCB

1.6 - 2.5A P25M MCB

1.5 - 4A P25M MCB

4 - 6.3A P25M MCB

6.3 - 10A P25M MCB

9 - 14A P25M MCB

13 - 18A P25M MCB

17 - 23A P25M MCB

20 - 25A P25M MCB

P25M limiter block

P25M MCB contact position, F+F

P25M MCB contact position, O+F

P25M position&alarm F+SD.F

P25M position&alarm O+SD.F

P25M position&alarm F+SD.O

P25M position+alarm 0+SD.O

P25M 240 MX voltage release

P25M 415 MX inst voltage release

P25M MN undervoltage release

P25M MN undervoltage release

P25M IP55 enclosure

P25M MCB green indicator

P25M MCB green neon indicator

P25M MCB red neon indicator

P25M MCB red neon indicator

P25M MCB busbar terminal block

2P P25M MCB comb busbar

4P P25M MCB comb busbar

P25M insulated cable connector

P25M comb busbar end cover

RCP phase failure relay

RCI relay 230V

80A 100mA 2P RMG

100A 300mA 2P RMG

63A 300mA 4P RMG

100A 300mA 4P RCCB (RMG)

100A 300mA 4P RMG

25A 30mA 2P Class A RCD

40A 30mA 2P Class A RCD

63A 30mA 2P Class A RCD

40A 30mA 4P Class A RCD

63A 30mA 4P Class A RCD

1A 4P 10kA C60H curve C

2A 4P 10kA C60H curve C

4A 4P 10kA C60H curve C

6A 4P 10kA C60H curve C

10A 4P 10kA C60H curve C

16A 4P 10kA C60H curve C

20A 4P 10kA C60H curve C

25A 4P 10kA C60H curve C

32A 4P 10kA C60H curve C

40A 4P 10kA C60H curve C

50A 4P 10kA C60H curve C

63A 4P 10kA C60H curve C

1A 4P 10kA C60H curve D

2A 4P 10kA C60H curve D

4A 4P 10kA C60H curve D

6A 4P 10kA C60H curve D

10A 4P 10kA C60H curve D

16A 4P 10kA C60H curve D

20A 4P 10kA C60H curve D

25A 4P 10kA C60H curve D

32A 4P 10kA C60H curve D

40A 4P 10kA C60H curve D

50A 4P 10kA C60H curve D

63A 4P 10kA C60H curve D

MCB 110-415Vac/110-130Vdc MX

MCB 48Vac/dc MX

MCB 12/24Vac/dc MX

2P replacement cover for Vigibloc

Part Page No.Description

IndexBy part number

85

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 85

Page 86: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

26484

26485

26923

26924

26927

26929

26946

26947

26948

26959

26960

26961

26962

26963

26969

26970

26971

26975

26976

26977

26978

26979

26980

26981

26982

26991

27001

27053

27060

27062

27145

27150

28952

28957

28958

29211

29228

29242

29243

29252

29253

29254

29256

29257

29258

29259

29260

29320

29323

29324

29337

29339

29354

29370

29371

29387

29388

29407

29408

29450

29451

29455

29456

29457

29458

29461

29462

29504

29505

29506

29507

30555

30556

30557

30558

30561

30562

31536

31563

31564

31565

31566

31567

IndexBy part number

86

3P replacement cover for Vigibloc

4P replacement cover for Vigibloc

RMG auxiliary switch (OFS)

C60H/RMG OF auxiliary contact

C60H SD fault indicatibg switch

C60H OF+SD/OF selector switch

MX+OF shunt trip

MCB MX+OF shunt trip

MCB 24Vac/dc MX+OF shunt trip

MCB 115Vac 400Hz MN

Undervoltage release (MN)

Undervoltage release (MN)

Undervoltage release (MN)

Undervoltage release,time delay

Emergency stop (MNx)

MCB/RCD padlock attachment

MCB emergency stop (MNx)

1P C60H MCB terminal shields

2P C60H MCB terminal shields

MCB 230Vac MNx (C60)

4P C60H MCB terminal shields

MCB voltage threshold release

MCB voltage threshold release

C60H MCB terminal screw shield

C60H Vigi terminal screw shield

MCB 400Vac MNx (C60)

C60H MCB interpole barrier

MCB screw connection

16 - 50mm2 alu cable terminal

Modular device spacer

C120 MCB padlock attachment

C120 MCB label holder

4 cable lugs 95mm2 Cu cable

Pair terminal shields Interpact 63A

Pair terminal shields Interpact 160A

Earth fault protection 160A

4 Tunnel terminal 25 - 95mm2

3 Tunnel terminal 160A 1.5 - 95mm2

4 Tunnel terminal 160A 1.5 - 95mm2

3 lugs NS250 120mm2 Cu cable

3 lugs NS250. 150mm2 Cu cable

3 lugs NS250.185mm2 Cu cable

4 lugs NS250 120mm2 Cu cable

4 lugs NS250 150mm2 Cu cable

4 lugs NS250 185mm2 Cu cable

3 Tunnel terminal 1.5 - 185mm2

4 Tunnel terminal 120 - 185mm2

One pole terminal shield

Three pole terminal shield, pair

Four pole terminal shield, pair

Black rotary handle for 63 - 250A

Red/yellow rotary handle for 63 - 250A

Mechanical interlock for 2 MCCB

Toggle padlocking attachment

Toggle padlocking attachment

Shunt trip 240V

Shunt trip 380/415V

Undervoltage release 240V

Undervoltage release 380/415V

Auxiliary switch

SDE auxiliary contact adaptor

Direct metering 100A 3P

Direct metering 100A 4P

CT module 100A 3P

CT module 100A 4P

CT module with voltage output 100/5 3P

CT module with voltage output 100/5 4P

3 lugs NS250. 150mm2 Al cable

4 lugs NS250. 150mm2 Al cable

3 lugs NS250. 185mm2 Al cable

4 lugs NS250. 185mm2 Al cable

Direct metering 160A 3P

Direct metering 160A 4P

CT module 160A 3P

CT module 160A 4P

CT module with voltage output 150/5 3P

CT module with voltage output 150/5 4P

MCCB Vigi module 250A 4P

1 set of 3P spreader 250A

1 set of 4P spreader 250A

Ammeter module 250A 3P

Ammeter module 250A 4P

CT module 250A 3P

Part

12

12

12

32, 48

9

33, 49

9, 33, 49

33

33

33

12, 33

12, 33

12, 33

33, 49

9, 33, 49

33, 47

27, 33, 47

12, 27, 33, 47

9, 32, 48

32, 48

23

32, 48

32, 48

9, 33, 49

9, 33, 49

9, 33, 49

9, 33, 49

9, 12, 33, 49

9, 33, 49

32, 48

32, 48

32, 48

32, 48

32, 40, 48

32, 40, 48

33

33

33

33

32, 48

32, 48

32, 48

32, 48

32, 40, 48

32, 40, 48

32, 48

33, 49

33, 49

32, 48

32, 48

32, 48

Page No.Description

31568

31569

31570

32456

32479

32480

32481

32482

32490

32491

32500

32501

32502

32503

32504

32505

32506

32507

32564

32565

32597

32599

32631

32653

32654

32655

32656

32657

32658

32855

32856

32857

32858

32861

32862

33466

33469

33487

33489

33490

33492

33494

33495

33564

33566

33568

33570

44936

57655

99217

99219

99221

99223

99225

99560

7795P

7796P

7797P

7798P

7799P

99246A

99246B

CT module 250A 4P

CT module with voltage output 250/5 3P

CT module with voltage output 250/5 4P

MCCB Vigi module 400A 4P

3 clamps for 35 - 300mm2

4 clamps for 35 - 300mm2

3 clamps 2x35 - 240mm2

4 clamps 2x35 - 240mm2

1 set of 3P spreader 630A

1 set of 4P spreader 630A

3 lugs for NS630. 240mm2

4 lugs for Interpact. 240mm2

3 lugs for NS630. 300mm2

4 lugs for NS630. 300mm2

3 lugs for NS630. 240mm2

4 lugs for NS630. 240mm2

3 lugs for NS630. 300mm2

4 lugs for NS630. 300mm2

Terminal shields 3P, one pair

Terminal shields 4P, one pair

Black rotary handle 400/630A

Red/yellow rotary handle 400/630A

Fixed toggle padlock device

CT module with voltage output 400/5 3P

CT module with voltage output 400/5 4P

Ammeter module 400A 3P

Ammeter module 400A 4P

CT module 400A 3P

CT module 400A 4P

Ammeter module 600A 3P

Ammeter module 600A 4P

CT module 600A 3P

CT module 600A 4P

CT module with voltage output 600/5 3P

CT module with voltage output 600/5 4P

NS800N 3P Micrologic 2.0

NS800N 4P Micrologic 2.0

NS800NA 3P MCCB

NS1250NA 3P MCCB

NS1600NA 3P MCCB

NS800NA 4P MCCB

NS1250NA 4P MCCB

NS1600NA 4P MCCB

NS1250N 3P Micrologic 5.0

NS1250N 4P Micrologic 5.0

NS1600N 3P Micrologic 5.0

NS1600N 4P Micrologic 5.0

MCCB padlocking device

CE30 passive infrared detector

Earth and neutral bar 19 hole

Earth and neutral bar 24 hole

Earth and neutral bar 37 hole

Earth and neutral bar 48 hole

Earth and neutral bar 72 hole

3 SP way G9 IP30 steel enclosure

Prisma Front cover 6 way

Prisma Front cover 8 way

Prisma Front cover 12 way

Prisma Front cover 16 way

Prisma Front cover 24 way

4 way hinged cover

4 way hinged cover

Part Page No.Description

32, 48

32, 40, 48

32, 40, 48

32, 48

33, 49

33, 49

33, 49

9, 33, 49

33, 49

33, 49

33

12, 33

33

12, 33

33

33

33

33

33, 47

12, 27, 33, 47

9, 32, 48

32, 48

32, 48

32, 40, 48

32, 40, 48

32, 48

32, 48

32, 48

32, 48

32, 48

32, 48

32, 48

32, 48

32, 40, 48

32, 40, 48

47

47

47

31

31

47

31

31

31

31

31

31

32, 48

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 86

Page 87: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 87

Page 88: Low voltage power circuit protection · ASTA certification of breaking capacity to BS EN 60947-2 Supplied with terminal shields Removable front cover provides all round cabling access

Enclosed switch disconnectors

Merlin Gerin is a world leader in the manufacture and supply of high, medium and low voltage products for the distribution, protection, control and management of electrical systems and is focused on the needs of both thecommercial and industrial sectors. The newly launched VDINetwork Solutions offer provides flexible, configurableethernet systems for all communication needs.

Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltageelectrical distribution equipment, systems and services areused extensively in residential and commercial applications.

Telemecanique is a UK market leader and world expert inautomation and control. It provides complete solutions, withit's range of components, Modicon range of high technologyprogrammable controllers (PLCs), multiple fieldbus andethernet communication networks, HMI, motion controlsystems, variable speed drives and communicationssoftware. In addition, it offers power distribution throughprefabricated busbar trunking.

Schneider Electric’s local supportSchneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largestdedicated sales force in the UK electrical industry, operate from 4 customer support centres.

Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.

To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includesfacilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing excellent meeting facilities.

www.schneider.co.uk

OCT 2005MGLV5751

Industrial systems and solutions showroomSchneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ

Building systems and solutions showroomSchneider Electric Ltd, Stafford Park 5, Telford, Shropshire TF3 3BL

Energy and Infrastructure systems and solutions showroomSchneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS

Product showrooms

Fax 0870 608 8 6060870 608 8 608Nationwide support on one number - call the Customer Information Centre on

ScotlandSchneider Electric LtdUnit 11000Academy Business ParkGower StreetGlasgow G51 1PR

South WestSchneider Electric LtdPO Box 41Langley RoadChippenhamWiltshire SN15 1JJ

North WestSchneider Electric LtdMarket House Church Street Wilmslow Cheshire SK9 1AY

Local customer support centres

member of

.co.uk

MGLV5751 (RTI Sec 11) 13/9/05 3:23 pm Page 88