2 of 178 PROPOSED: B+ G+12+ R RES. BUILDING AREA: AL NAHDA SECOND DETAILS OF CONNECTED LOAD / MAX. DEMAND PLOT NO: 241-587 PANEL REF: OWNER: ESSA ABDULFATTAH KAZIM AL MULLA LOCATION: G.F L.V ROOM CONSULTANTS: FA BAKER CONSULTANTS. FED FROM : L.V PANEL-1 S/N CIRCUIT RATING-AMPS FAULT PVC/XLPE CABLE SIZE ECC CONNECTED LOAD-KW KWH METER FEEDER SP / ACB MCCB MCB DUTY SWA/PVC/SC 2/4X1C 2/3/4C SIZE-1C R-PH Y-PH B-PH TOTAL 1-PH 3-PH 3-PH CT DB. NO. TP KA mm2 mm2 mm2 KW KW KW KW 1 2 3 4 1 INCOMER - 1 4P 2500A 65 XLPE/SWA/PVC DEWA CABLE 2X 1C 150 457.36 443.91 445.81 1347.09 72 1 OUTGOING ( D.O.T @ 0.85 ) 1 SMDB - G.LL TP 600A 35 XLPE/SWA/PVC 2X4C 185 1X1C 185 108.58 109.23 108.08 325.90 2 SMDB-T1 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 25.57 23.87 25.57 75.00 6 3 SMDB-T2 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 25.57 23.87 25.57 75.00 6 4 SMDB-T3 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 25.57 23.87 25.57 75.00 6 5 SMDB-T4 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 6 SMDB-T5 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 7 SMDB-T6 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-T7 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-T8 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-T9 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-T10 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-T11 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-T12 TP 160A 35 XLPE/SWA/PVC 1X 4C 70 1X 1C 35 24.12 23.12 22.67 69.91 6 SMDB-F.P TP 350A 35 XLPE/SWA/PVC 1X 4C 240 1X 1C 120 55.00 55.00 56.00 166.00 DB-SS SP 40A 35 XLPE/SWA/PVC 1X3C 10 1.00 1.00 CAP BANK TP 1000A 35 XLPE/SWA/PVC 3X 4C 240 3X 1C 120 - - - - TOTAL CONNECTED LOAD PER PHASE 457.36 443.91 445.81 1,347.09 0 72 0 1 DEMAND FACTOR 0.85 - MAX. DEMA 1,145.03 KW TOTAL CONNECTED LOAD ( 3 PH ) 1,347.09 KW PROVIDE CT METER WHEN MAX. DEMAND > 100 KW CONTRACTOR : POWER FACTOR L.L.C. (1) UP TO 60 A (2) UP TO 100 A (3) 125 - 160 A (4) LV / CT …. / …. FAX: 04-3232473 ( 1 PHASE ) ( 3 PHASE ) LENGTH OF CABLE (m ) TEL:.04-3232476

description

qeg

Transcript of Load Schedule

L.V PANELPROPOSED: B+ G+12+ R RES. BUILDINGAREA: AL NAHDA SECONDDETAILS OF CONNECTED LOAD / MAX. DEMANDPLOT NO: 241-587PANEL REF:OWNER: ESSA ABDULFATTAH KAZIM AL MULLALOCATION:G.F L.V ROOMCONSULTANTS: FA BAKER CONSULTANTS.FED FROM :L.V PANEL-1S/NCIRCUITRATING-AMPSFAULTPVC/XLPECABLE SIZELENGTH OF CABLE (m )ECCCONNECTED LOAD-KWKWH METERFEEDERSP /ACBMCCBMCBDUTYSWA/PVC/SC2/4X1C2/3/4CSIZE-1CR-PHY-PHB-PHTOTAL1-PH3-PH3-PHCTREMARKSDB. NO.TPKAmm2mm2mm2KWKWKWKW12341INCOMER - 14P2500A65XLPE/SWA/PVCDEWA CABLE2X 1C 150457.36443.91445.811347.097212400/5A CTOUTGOING ( D.O.T @ 0.85 )1SMDB - G.LLTP600A35XLPE/SWA/PVC2X4C 1851X1C 185108.58109.23108.08325.902SMDB-T1TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3525.5723.8725.5775.0063SMDB-T2TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3525.5723.8725.5775.0064SMDB-T3TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3525.5723.8725.5775.0065SMDB-T4TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.9166SMDB-T5TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.9167SMDB-T6TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-T7TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-T8TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-T9TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-T10TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-T11TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-T12TP160A35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916SMDB-F.PTP350A35XLPE/SWA/PVC1X 4C 2401X 1C 12055.0055.0056.00166.00DB-SSSP40A35XLPE/SWA/PVC1X3C 101.001.00CAP BANKTP1000A35XLPE/SWA/PVC3X 4C 2403X 1C 120----400 KVARTOTAL CONNECTED LOAD PER PHASE457.36443.91445.811,347.0907201DEMAND FACTOR 0.85 - MAX. DEMAND1,145.03 KWTOTAL CONNECTED LOAD ( 3 PH )1,347.09 KWPROVIDE CT METER WHEN MAX. DEMAND > 100 KWCONTRACTOR : POWER FACTOR L.L.C.TEL:.04-3232476(1) UP TO 60 A(2) UP TO 100 A(3) 125 - 160 A(4) LV / CT . / . AFAX: 04-3232473( 1 PHASE )( 3 PHASE )

&C&P of 178TEL:.04-3232476

SMDBPROPOSED: B+ G+12+ R RES. BUILDINGAREA: AL NAHDA SECONDDETAILS OF CONNECTED LOAD / MAX. DEMANDPLOT NO: 241-587PANEL REF:OWNER: ESSA ABDULFATTAH KAZIM AL MULLALOCATION:G.F L.V ROOMCONSULTANTS: FA BAKER CONSULTANTS.FED FROM :SMDB-G.LLS/NCIRCUITRATING-AMPSFAULTPVC/XLPECABLE SIZELENGTH OF CABLE (m )ECCCONNECTED LOAD-KWKWH METERFEEDERSP /ACBMCCBMCBDUTYSWA/PVC/SC2/4X1C2/3/4CSIZE-1CR-PHY-PHB-PHTOTAL1-PH3-PH3-PHCTREMARKSDB. NO.TPKAmm2mm2mm2KWKWKWKW12341INCOMER - 1TP600A (N/A)35XLPE/SWA/PVC2X4C 1851X 1C 185108.58109.23108.08325.90OUTGOING1DB-B.FTP63A25XLPE/SWA/PVC1X 4C 161X 1C 167.007.855.9520.802DB-G.FTP63A25XLPE/SWA/PVC1X 4C 161X 1C 168.628.978.2725.853DB-G.TELTP40A25XLPE/SWA/PVC1X 4C 101X 1C 102.202.403.758.354DB-T1LLTP40A25XLPE/SWA/PVC1X 4C 161X 1C 166.106.106.1018.305DB-T2LLTP40A25XLPE/SWA/PVC1X 4C 161X 1C 166.106.106.1018.306DB-T3LLTP40A25XLPE/SWA/PVC1X 4C 161X 1C 166.106.106.1018.307DB-T4LLTP40A25XLPE/SWA/PVC1X 4C 161X 1C 166.106.106.1018.308SMDB-RTP300A25XLPE/SWA/PVC1X 4C 1851X 1C 9552.1751.4251.52155.109GARBAGE ISO.TP32A25XLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.0030mA ELCB10WATER PUMPTP40A25XLPE/SWA/PVC1X 4C 101X 1C 103.003.003.009.0030mA ELCB11SUMP PUMP-1TP25A25XLPE/SWA/PVC1X 4C 61X 1C 61.001.001.003.0030mA ELS+ALARM12SUMP PUMP-2TP25A25XLPE/SWA/PVC1X 4C 61X 1C 61.001.001.003.0030mA ELS+ALARM13B.EXHAUST FANTP63A25XLPE/SWA/PVC1X 4C 161X 1C 167.207.207.2021.60100mA ELS+ALARMTOTAL CONNECTED LOAD PER PHASE108.58109.23108.08325.90DEMAND FACTOR 0.85 - MAX. DEMAND277.02 KWTOTAL CONNECTED LOAD ( 3 PH )325.90 KWPROVIDE CT METER WHEN MAX. DEMAND > 100 KWCONTRACTOR : POWER FACTOR L.L.C.TEL:.04-3232476(1) UP TO 60 A(2) UP TO 100 A(3) 125 - 160 A(4) LV / CT . / . AFAX: 04-3232473( 1 PHASE )( 3 PHASE )PROPOSED: B+ G+12+ R RES. BUILDINGAREA: AL NAHDA SECONDDETAILS OF CONNECTED LOAD / MAX. DEMANDPLOT NO: 241-587PANEL REF:OWNER: ESSA ABDULFATTAH KAZIM AL MULLALOCATION:R.F ELE.CABINET ROOMCONSULTANTS: FA BAKER CONSULTANTS.FED FROM :SMDB-RS/NCIRCUITRATING-AMPSFAULTPVC/XLPECABLE SIZELENGTH OF CABLE (m )ECCCONNECTED LOAD-KWKWH METERFEEDERSP /ACBMCCBMCBDUTYSWA/PVC/SC2/4X1C2/3/4CSIZE-1CR-PHY-PHB-PHTOTAL1-PH3-PH3-PHCTREMARKSDB. NO.TPKAmm2mm2mm2KWKWKWKW12341INCOMER - 1TP300A (N/A)35XLPE/SWA/PVC1X 4C 1851X 1C 9552.1751.4251.52155.10OUTGOING1DB-G.GYMTP40A25XLPE/SWA/PVC1X 4C 101X 1C 102.972.572.277.802DB-L.GYMTP40A25XLPE/SWA/PVC1X 4C 101X 1C 102.872.672.277.803DB-RTP40A25XLPE/SWA/PVC1X 4C 161X 1C 167.136.785.6319.554DB-R.TELTP40A25XLPE/SWA/PVC1X 4C 101X 1C 102.202.404.358.955LIFT - 1TP40A25XLPE/SWA/PVC1X 4C 101X 1C 104.004.004.0012.00300mA ELCB6LIFT - 2TP40A25XLPE/SWA/PVC1X 4C 101X 1C 104.004.004.0012.00300mA ELCB7FAHU-TP125A25XLPE/SWA/PVC1X 4C 501X 1C 2517.0017.0017.0051.00100mA ELCB8SOLAR HETER-1TP63A25XLPE/SWA/PVC1X 4C 161X 1C 165.005.005.0015.0030mA ELCB9SOLAR HETER-2TP63A25XLPE/SWA/PVC1X 4C 161X 1C 165.005.005.0015.0030mA ELCB10BOOSTER PUMPTP32A25XLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.0030mA ELCB13SW-POOL-CPTP80A25XLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.00100mA ELCB14TPXLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.00100mA ELCB15TPXLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.00100mA ELCB16TPXLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.00100mA ELCB17TPXLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.00100mA ELCBTOTAL CONNECTED LOAD PER PHASE52.1751.4251.52155.10DEMAND FACTOR 0.85 - MAX. DEMAND131.84 KWTOTAL CONNECTED LOAD ( 3 PH )155.10 KWPROVIDE CT METER WHEN MAX. DEMAND > 100 KWCONTRACTOR : POWER FACTOR L.L.C.TEL:.04-3232476(1) UP TO 60 A(2) UP TO 100 A(3) 125 - 160 A(4) LV / CT . / . AFAX: 04-3232473( 1 PHASE )( 3 PHASE )PROPOSED: B+ G+12+ R RES. BUILDINGAREA: AL NAHDA SECONDDETAILS OF CONNECTED LOAD / MAX. DEMANDPLOT NO: 241-587PANEL REF:OWNER: ESSA ABDULFATTAH KAZIM AL MULLALOCATION:T.F ELE. CABINET ROOMCONSULTANTS: FA BAKER CONSULTANTS.FED FROM :SMDB-T1 TO SMDB-T3 TYPS/NCIRCUITRATING-AMPSFAULTPVC/XLPECABLE SIZELENGTH OF CABLE (m )ECCCONNECTED LOAD-KWKWH METERFEEDERSP /ACBMCCBMCBDUTYSWA/PVC/SC2/4X1C2/3/4CSIZE-1CR-PHY-PHB-PHTOTAL1-PH3-PH3-PHCTREMARKSDB. NO.TPKAmm2mm2mm2KWKWKWKW12341INCOMER - 1TP160A (N/A)35XLPE/SWA/PVC1X 4C 701X 1C 3525.5723.8725.5775.006OUTGOING1FDB-101TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 105.005.504.8015.3012FDB-102TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.702.604.8012.1013FDB-103TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 103.036.033.3312.4014FDB-104TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 106.233.233.3312.8015FDB-105TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.602.205.2012.0016FDB-106TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 102.004.304.1010.401TOTAL CONNECTED LOAD PER PHASE25.5723.8725.5775.006DEMAND FACTOR 0.85 - MAX. DEMAND63.75 KWTOTAL CONNECTED LOAD ( 3 PH )75.00 KWPROVIDE CT METER WHEN MAX. DEMAND > 100 KWCONTRACTOR : POWER FACTOR L.L.C.TEL:.04-3232476(1) UP TO 60 A(2) UP TO 100 A(3) 125 - 160 A(4) LV / CT . / . AFAX: 04-3232473( 1 PHASE )( 3 PHASE )PROPOSED: B+ G+12+ R RES. BUILDINGAREA: AL NAHDA SECONDDETAILS OF CONNECTED LOAD / MAX. DEMANDPLOT NO: 241-587PANEL REF:OWNER: ESSA ABDULFATTAH KAZIM AL MULLALOCATION:T.F ELE. CABINET ROOMCONSULTANTS: FA BAKER CONSULTANTS.FED FROM :SMDB-T4 TO SMDB-T12 TYPS/NCIRCUITRATING-AMPSFAULTPVC/XLPECABLE SIZELENGTH OF CABLE (m )ECCCONNECTED LOAD-KWKWH METERFEEDERSP /ACBMCCBMCBDUTYSWA/PVC/SC2/4X1C2/3/4CSIZE-1CR-PHY-PHB-PHTOTAL1-PH3-PH3-PHCTREMARKSDB. NO.TPKAmm2mm2mm2KWKWKWKW12341INCOMER - 1TP160A (N/A)35XLPE/SWA/PVC1X 4C 701X 1C 3524.1223.1222.6769.916OUTGOING1FDB-401TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.405.494.7614.6512FDB-402TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.502.554.4011.4513FDB-403TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.464.802.0911.3514FDB-404TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.602.284.9011.7815FDB-405TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 104.204.302.6211.1216FDB-406TP40 A25XLPE/SWA/PVC1X 4C 101X 1C 101.963.703.909.561TOTAL CONNECTED LOAD PER PHASE24.1223.1222.6769.916DEMAND FACTOR 0.85 - MAX. DEMAND59.42 KWTOTAL CONNECTED LOAD ( 3 PH )69.91 KWPROVIDE CT METER WHEN MAX. DEMAND > 100 KWCONTRACTOR : POWER FACTOR L.L.C.TEL:.04-3232476(1) UP TO 60 A(2) UP TO 100 A(3) 125 - 160 A(4) LV / CT . / . AFAX: 04-3232473( 1 PHASE )( 3 PHASE )PROPOSED: B+ G+12+ R RES. BUILDINGAREA: AL NAHDA SECONDDETAILS OF CONNECTED LOAD / MAX. DEMANDPLOT NO: 241-587PANEL REF:OWNER: ESSA ABDULFATTAH KAZIM AL MULLALOCATION:B.F PUMP ROOMCONSULTANTS: FA BAKER CONSULTANTS.FED FROM :SMDB-FIRE PUMPS/NCIRCUITRATING-AMPSFAULTPVC/XLPECABLE SIZELENGTH OF CABLE (m )ECCCONNECTED LOAD-KWKWH METERFEEDERSP /ACBMCCBMCBDUTYSWA/PVC/SC2/4X1C2/3/4CSIZE-1CR-PHY-PHB-PHTOTAL1-PH3-PH3-PHCTREMARKSDB. NO.TPKAmm2mm2mm2KWKWKWKW12341INCOMER - 1TP350A (N/A)35XLPE/SWA/PVC1X 4C 2401X 1C 12055.055.056.0166.0OUTGOING1FIRE PUMPTP350A25XLPE/SWA/PVC1X 4C 2401X 1C 12052.0052.0053.00157.00STARTER100mA ELS+ALARM2JOCKY PUMPTP40A25XLPE/SWA/PVC1X 4C 101X 1C 101.001.001.003.00100mA ELS+ALARM3DIESEL PUMPTP40A25XLPE/SWA/PVC1X 4C 101X 1C 102.002.002.006.00100mA ELS+ALARMTOTAL CONNECTED LOAD PER PHASE55.0055.0056.00166.00DEMAND FACTOR 1.0 - MAX. DEMAND166.00 KWTOTAL CONNECTED LOAD ( 3 PH )166.00 KWPROVIDE CT METER WHEN MAX. DEMAND > 100 KWCONTRACTOR : POWER FACTOR L.L.C.TEL:.04-3232476(1) UP TO 60 A(2) UP TO 100 A(3) 125 - 160 A(4) LV / CT . / . AFAX: 04-3232473( 1 PHASE )( 3 PHASE )

&C&P of 178TEL:.04-3232476TEL:.04-3232476TEL:.04-3232476

FDB-T4 to 12PROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-401SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T4FDB-501 , 601 , 701 , 801 , 901 , 1001 , 1101,1201 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGCOOKCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR40A 4P 100mA1R1102.52.5BED ROOM-1 / BATH40.10.402Y1102.52.5LIVING RM / DINING40.10.403B1102.52.5KITCHEN20.10.204R2102.52.5L.P.G10.10.105Y2102.52.5BED ROOM-2 / BATH50.10.506B2SPACE40A 4P 100mA7R3SPACE8Y32042.5F.C.U-110.290.299B32042.5F.CU-210.260.2610R42042.5BED ROOM-130.20.6040A11Y42042.5LIVING RM / DINING40.20.804P12B42042.5KITCHEN40.20.8030 mA13R52042.5BED ROOM-230.20.6014Y52042.5KITCHEN10.50.5015B52042.5LIVING RM / DINING20.20.4040 A16R63064FAC-1L12.72.70U.V TIMER + CONT.4P17Y63064KITCHEN13.03.00W/O 13A SSO100 mA18B63064FAC-1B13.13.10U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.45.54.814.74.45.54.814.740APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-402SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T4FDB-502 , 602 , 702 , 802 , 902 , 1002, 1102,1202 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGISOCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR1R1102.52.5LIVING RM / DINING40.10.4040A2Y1102.52.5BED RM-1 / BATH40.10.404P3B1102.52.5KITCHEN20.10.20100 mA4R2SPACE5Y2102.52.5BED RM-2 / BATH30.10.306B2102.52.5L.P.G10.10.1040A7R3SPACE4P8Y32042.5F.C.U-110.260.26100mA9B3SPACE10R42042.5BED RM-230.20.6040A11Y42042.5KITCHEN10.50.504P12B42042.5KITCHEN40.20.8030 mA13R52044LIVING RM / DINING20.20.4014Y52042.5LIVING RM / DINING40.20.8015B52042.5BED RM-130.20.6040 A16R63064FAC-2L13.13.10U.V TIMER + CONT.4P17Y62042.5F.CU-210.290.29100 mA18B63064FAC-2B12.72.70U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.52.64.411.54.52.64.411.540APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-403SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T4FDB-503, 603 , 7073, 803 , 903, 1003, 1103,1203 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGISOCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR1R1102.52.5KITCHEN20.10.240A2Y1102.52.5BED RM-1 / BATH40.10.44P3B1102.52.5LIVING RM / DINING30.10.3100 mA4R22042.5F.C.U-110.260.265Y2102.52.5L.P.G10.10.16B2102.52.5BED RM-2 / BATH30.10.37R32042.5KITCHEN40.20.840A8Y32042.5BED RM-130.20.64P9B32042.5LIVING RM / DINING40.20.830 mA10R42042.5KITCHEN10.50.511Y42042.5BED RM-230.20.612B42042.5LIVING RM / DINING20.20.440 A13R53064FAC-2A12.72.70U.V TIMER + CONT.4P14Y53064FAC-2B13.13.10U.V TIMER + CONT.100 mA15B52042.5F.CU-210.290.29Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.54.82.113.14.54.82.111.440APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-404SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T4FDB-504 , 604 , 704 , 804 , 904 , 1004, 1104,1204 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGSPURCCUFCUS A/CUNITRYBAmmmmFANS/OS/OO/L40 A TP ISOLATOR1R1102.52.5L.P.G10.100.1040A2Y1102.52.5LIVING RM / DINING30.100.304P3B1102.52.5KITCHEN20.100.20100 mA4R2102.52.5BED ROOM-2 / BATH40.100.405Y22042.5F.C.U-110.290.296B2102.52.5BED ROOM-1 / BATH30.100.307R32042.5BED ROOM-130.200.6040A8Y32042.5LIVING RM / DINING40.200.804P9B32042.5KITCHEN40.200.8030 mA10R42042.5LIVING RM / DINING20.200.4011Y42042.5BED RM-230.200.6012B42042.5KITCHEN10.500.5040 A13R53064.0FAC-4A13.103.10U.V TIMER + CONT.4P14Y52042.5F.C.U-210.290.29100 mA15B53064.0FAC-4A13.103.10U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.62.34.911.84.62.34.911.840APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-405SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T4FDB-505 , 605, 705 , 805 , 905 , 1005, 1105,1205 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGSPURCCUFCUS A/CUNITRYBAmmmmFANS/OS/OO/L40 A TP ISOLATOR1R1102.52.5LIVING RM / DINING30.100.3040A2Y1102.52.5KITCHEN20.100.204P3B1102.52.5BED RM-1 / BATH40.100.40100 mA4R2SPACE5Y2102.52.5L.P.G10.100.106B2102.52.5BED RM-2 / BATH30.100.3040A7R3SPACE4P8Y3SPACE100 mA9B32042.5F.CU-210.260.2610R42042.5LIVING RM / DINING40.200.8040A11Y42042.5KITCHEN40.200.804P12B42042.5BED RM-140.200.8030 mA13R52044LIVING RM / DINING20.200.4014Y52044KITCHEN10.500.5015B52042.5BED RM-230.200.6040 A16R63064FAC-5A12.702.70U.V TIMER + CONT.4P17Y63064FAC-5A12.702.70U.V TIMER + CONT.100 mA18B62042.5F.C.U-110.260.26Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.24.32.611.14.24.32.611.140APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-406SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T4FDB-506 , 606, 706 , 806 , 906 , 1006, 1106,1206 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGISOCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40A TP ISOLATOR1R1102.52.5KITCHEN20.100.2040A2Y1102.52.5BED RM-1 / BATH40.100.404P3B1102.52.5LIVING RM / DINING50.100.50100 mA4R22042.5F.C.U-110.260.265Y2SPACE6B2102.52.5L.P.G10.100.107R32042.5KITCHEN40.200.8040A8Y32042.5BED RM-130.200.604P9B32042.5LIVING RM / DINING40.200.8030 mA10R42044KITCHEN10.500.5011Y4SPACE0.0012B42042.5LIVING RM / DINING20.200.4040 A13R52042.5F.CU-210.200.204P14Y53064FAC-6A12.702.70U.V TIMER + CONT.100 mA15B53064FAC-6B12.102.10U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC2.03.73.99.62.03.73.99.640A

&CPage &P of 178&R&D

DB-LLPROPOSED: B+ G+12 +R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-B.FSHEET :1/2LOCATION:BASEMENT FLOORFED FROM :SMDB-G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O63 A TP ISOLATOR1R1162.52.5COMPOUND WALL110.11.140A2Y1102.52.5PUMP ROOM20.10.24P3B1102.52.5LIFT LOBBY30.050.2100 mA4R2102.52.5PARKING60.10.65Y2162.52.5DRIVER WAY110.11.16B2162.52.5STAIR CASE-1160.11.67R3162.52.5PARKING120.11.28Y3162.52.5DRIVER WAY120.11.29B3162.52.5STAIRCASE-1180.11.840A10R4102.52.5PARKING90.10.94P11Y4102.52.5RAMP/GEN.RM70.10.7100 mA12B4--SPACE13R5102.52.5PARKING90.10.914Y5162.52.5STAIR CASE-2150.11.515B5162.52.5STAIRCASE-2150.11.516R62042.5PARKING40.20.840A17Y62042.5PUMP ROOM20.20.44P18B62042.5GATE BARRIER10.50.530 mA19R73242.5PARKING50.21.0RING20Y72042.5GEN.RM20.20.421B7---SPACE20.20.440A22R82042.5GATE BARRIER10.50.54P23Y8---SPACE30 mA24B8--SPACECable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC7.05.56.0PROPOSED: B+G+12 RES.BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-B.FSHEET :2/2LOCATION:BASEMENT FLOORFED FROM :SMDB- G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O63A TP ISOLATOR40A25R9SPACE4P26Y93064BAC-1 PUMP12.352.4U.V TIMER + CONT.100 mA27B9--SPACECable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC7.007.855.9520.807.07.96.020.840APROPOSED: B+G+12 RES.BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:DB-GTELSHEET :1 / 1LOCATION:TEL. ROOMFED FROM :SMDB-G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR40A1R1102.52.5TELEPHONE ROOM20.10.24P2Y1--SPACE100 mA3B12064TEL. CU-111.351.4U.V TIMER + CONT.40A4R2--SPACE4P5Y22042.5TELEPHONE ROOM20.20.430 mA6B22042.5TELEPHONE ROOM20.20.440A7R32041TEL. ISOLATOR-116.02.04P8Y3AMPXX2.0100 mA9B3TP6.04.02.0Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC2.22.43.88.42.22.43.88.440APROPOSED: B+G+12 RES.BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:DB-T1LL , DB-T2LL , DB-T3LL AND DB-T4LL TYPSHEET :1/2LOCATION:FIRST FLOOR ELE.CABINETFED FROM :SMDB-G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR1R1102.52.51ST F. CORRIDOR120.050.640A2Y1102.52.51ST F. CORRIDOR30.10.34P3B1102.52.52ND F. CORRIDOR120.050.6100 mA4R2102.52.52ND F. CORRIDOR30.10.35Y2102.52.53RD F. CORRIDOR120.050.66B2102.52.53RD F. CORRIDOR30.10.37R32042.51ST F. CORRIDOR20.20.440A8Y32042.51ST F. CORRIDOR20.20.4FOR CCTV4P9B32042.52ND F. CORRIDOR20.20.430 mA10R42042.52ND F. CORRIDOR20.20.4FOR CCTV11Y42042.53RD F. CORRIDOR20.20.412B42042.53RD F. CORRIDOR20.20.4FOR CCTV13R52042.51ST F. CORRIDOR10.50.5FIRE DAMPER40A14Y52042.51ST F. CORRIDOR10.50.5FIRE DAMPER4P15B52042.52ND F. CORRIDOR10.50.5FIRE DAMPER30 mA16R62042.52ND F. CORRIDOR10.50.5FIRE DAMPER17Y62042.53RD F. CORRIDOR10.50.5FIRE DAMPER18B62042.53RD F. CORRIDOR10.50.5FIRE DAMPERCable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC2.72.72.7PROPOSED: B+ G+12 +R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-T1LL , DB-T2LL , DB-T3LL AND DB-T4LL TYPSHEET :2/2LOCATION:FIRST FLOOR ELE.CABINETFED FROM :SMDB-G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O40A TP ISOLATOR40A19R73064.01ST F. CORRIDOR13.13.1U.V TIMER + CONT.4P20Y73064.02ND F. CORRIDOR13.13.1100 mA21B73064.03RD F. CORRIDOR13.13.140A22R82042.51ST F. CORRIDOR10.30.34P23Y82042.52ND F. CORRIDOR10.30.3100 mA24B82042.53RD F. CORRIDOR10.30.3Cable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC6.106.106.1018.36.16.16.118.340APROPOSED: B+G+12 RES.BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-G.FSHEET :2/2LOCATION:G.F L.V ROOMFED FROM :SMDB-G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O63A TP ISOLATOR1R1102.52.5COMPOUND WALL110.11.140A2Y1102.52.5PARKING80.10.84P3B1102.52.5DRIVER WAY30.10.3100 mA4R2102.52.5GARBAGE ROOM40.10.45Y2102.52.5PARKING60.10.66B2102.52.5L.V ROOM20.10.27R3102.52.5LIFT LOBBY / ENT.HALL110.050.640A8Y3102.52.5PASSAGE / ENT.LOBBY70.050.44P9B32042.5F.C.U-110.50.5100 mA10R4102.52.5ENTRANCE HALL120.11.211Y4---SPACE12B4102.52.5SECURITY ROOM20.10.213R52042.5GARBAGE ROOM20.20.440A14Y52042.5PASSAGE / ENT.LOBBY20.20.44P15B52042.5L.V ROOM30.20.630 mA16R63242.5LIFT LOBBY / ENT.HALL60.21.2RING17Y62042.5PASSAGE / ENT.LOBBY30.20.618B62042.5SECURITY ROOM20.20.440A19R72042.5LIFT LOBBY / ENT.HALL20.20.44P20Y72042.5GATE BARRIER10.50.530 mA21B72042.5GATE BARRIER10.50.540A22R8---SPACEU.V TIMER + CONT.4P23Y82064GAC-1LV12.352.4100 mA24B82064GAC-2GEN12.22.2Cable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC5.255.604.90PROPOSED: B+G+12 RES.BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-G.FSHEET :2/2LOCATION:G.F L.V ROOMFED FROM :SMDB-G.LLRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O63A TP ISOLATOR40A25R92061GAC-4ENT14.11.4U.V TIMER + CONT.4P26Y9AMPXX1.4100 mA27B9TP6.04.01.440A28R102061EXHAUST FAN162.04P29Y10AMPXX2.0100 mA30B10TP6.04.02.0Cable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC8.628.978.2725.98.69.08.325.940A

&CPage &P of 178&R&D

DB-RPROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-G.GYMSHEET :1 / 1LOCATION:GYM ROOMFED FROM :SMDB-RRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MSPURCCUFCUS A/CUNITRYBAmmmmFANS/OS/OO/L40 A TP ISOLATOR40A1R1102.52.5GENTS GYM60.10.64P2Y1102.52.5GENTS GYM TOILETS80.10.8100 mA3B12042.5F.C.U-110.50.54R23242.5GENTS GYM50.21.0RING40A5Y22042.5GENTS GYM20.20.44P6B2---SPACE30 mA7R3--SPACE8Y3SPACE0.09B32042.5GENTS GYM20.20.440A10R420RAC-2GG14.11.4U.V TIMER + CONT.4P11Y4AMP6.04.01.4100 mA12B4TP1.4Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC2.972.572.279.603.02.62.37.840APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-L.GYMSHEET :1 / 1LOCATION:GYM ROOMFED FROM :SMDB-RRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MSPURCCUFCUS A/CUNITRYBAmmmmFANS/OS/OO/L40 A TP ISOLATOR40A1R1102.52.5LADIES GYM70.10.74P2Y1102.52.5LADIES GYM TOILETS90.10.9100 mA3B12042.5F.C.U-110.50.54R22042.5LADIES GYM40.20.8RING40A5Y22042.5LADIES GYM20.20.44P6B2SPACE30 mA7R3SPACE8Y3SPACE0.09B32042.5LADIES GYM TOILETS20.20.440A10R420RAC-1LG14.11.4U.V TIMER + CONT.4P11Y4AMP6.04.01.4100 mA12B4TP1.4Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC2.872.672.279.602.92.72.37.840APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241-587PANEL REF:DB-RSHEET :1 / 1LOCATION:ROOF FLOORFED FROM :SMDB-RRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR1R1102.52.5LIFT MACHINE ROOM20.10.240A2Y1SPACE4P3B1102.52.5ROOF CORRIDOR100.11.0100 mA4R2102.52.5TERRACE60.10.65Y2102.52.5TERRACE / ROOF70.10.76B2SPACE40A7R3SPACE4P8Y3SPACE30 mA9B32042.5CORRIDOR30.20.610R4SPACE40A11Y42042.5ROOF CORRIDOR10.50.5FIRE DAMPER4P12B42042.5ROOF CORRIDOR10.50.5FIRE DAMPER30 mA13R52042.5ROOF CORRIDOR10.50.5FOR CCTV14Y52042.5ROOF CORRIDOR10.50.5FOR CCTV15B52042.5LIFT MACHINE ROOM10.50.5FIRE DAMPER40A16R63064.0CORRIDOR CU-13.13.1U.V TIMER + CONT.4P17Y63064.0LIFT CU-12.352.4U.V TIMER + CONT.100 mA18B62042.5CORRIDOR F.C.U-10.30.340A19R720SPF-1 ISOLATOR11.50.5ELS+ALARM4P20Y7AMP6.04.00.5100 mA21B7TP0.540A22R820SPF-1 ISOLATOR11.50.5ELS+ALARM4P23Y8AMP6.04.00.5100 mA24B8TP0.540A25R920LLPF- ISOLATOR13.01.0ELS+ALARM4P26Y9AMP6.04.01.0100 mA27B9TP1.040A28R1020SEF- ISOLATOR12.20.7ELS+ALARM4P29Y10AMP6.04.00.7100 mA30B10TP0.7Cable Size:1X 4C 16 mm2 XLPE+/SWA/PVC+1C 16 mm PVC AS E+CC7.16.85.619.67.16.85.619.640APROPOSED: B+G+12 RES.BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:DB-R.TELSHEET :1 / 1LOCATION:GSM. ROOMFED FROM :SMDB-RRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MISO.CCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR40A1R1102.52.5ROOF TELEPHONE ROOM20.10.24P2Y1--SPACE100 mA3B12064ROOF TELEPHONE ROOM CU-12.352.4U.V TIMER + CONT.40A4R2SPACE4P5Y22042.5ROOF TELEPHONE ROOM20.20.430 mA6B2---SPACE40A7R320ISOLATOR FOR TEL.RM -116.02.04P8Y3AMP6.04.02.0100 mA9B3TP2.0Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC2.22.44.49.02.22.44.49.040A

&CPage &P of 178&R&D

FDB-T1 to 3PROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-101SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T1FDB-201 , 301 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGCOOKCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR40A 4P 100mA1R1102.52.5BED ROOM-1 / BATH40.10.42Y1102.52.5LIVING RM / DINING40.10.43B1102.52.5KITCHEN20.10.24R2102.52.5L.P.G10.10.15Y2102.52.5BED ROOM-2 / BATH50.10.56B2SPACE40A 4P 100mA7R3SPACE8Y32042.5F.C.U-110.30.39B32042.5F.CU-210.30.310R42042.5BED ROOM-130.20.640A11Y42042.5LIVING RM / DINING40.20.84P12B42042.5KITCHEN40.20.830 mA13R52042.5BED ROOM-230.20.614Y52042.5KITCHEN10.50.515B52042.5LIVING RM / DINING20.20.440 A16R63064FAC-1L13.33.3U.V TIMER + CONT.4P17Y63064KITCHEN13.03.0W/O 13A SSO100 mA18B63064FAC-1B13.13.1U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC5.05.54.815.35.05.54.815.340APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-102SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T1FDB-202, 302 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGISOCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR1R1102.52.5LIVING RM / DINING40.10.440A2Y1102.52.5BED RM-1 / BATH40.10.44P3B1102.52.5KITCHEN20.10.2100 mA4R2SPACE5Y2102.52.5BED RM-2 / BATH30.10.36B2102.52.5L.P.G10.10.140A7R3SPACE4P8Y32042.5F.C.U-110.30.3100mA9B3SPACE10R42042.5BED RM-230.20.640A11Y42042.5KITCHEN10.50.54P12B42042.5KITCHEN40.20.830 mA13R52044LIVING RM / DINING20.20.414Y52042.5LIVING RM / DINING40.20.815B52042.5BED RM-130.20.640 A16R63064FAC-2L13.33.3U.V TIMER + CONT.4P17Y62042.5F.CU-210.30.3100 mA18B63064FAC-2B13.13.1U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.72.64.812.14.72.64.812.140APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-103SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T1FDB-203, 303 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGISOCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40 A TP ISOLATOR1R1102.52.5KITCHEN20.10.240A2Y1102.52.5BED RM-1 / BATH40.10.44P3B1102.52.5LIVING RM / DINING30.10.3100 mA4R2SPACE0.05Y2102.52.5L.P.G10.10.16B2102.52.5BED RM-2 / BATH30.10.37R32042.5KITCHEN40.20.840A8Y32042.5BED RM-130.20.64P9B32042.5LIVING RM / DINING40.20.830 mA10R42042.5KITCHEN10.50.511Y42042.5BED RM-230.20.612B42042.5LIVING RM / DINING20.20.440 A13R52042.5F.C.U-110.30.34P14Y53064.0FAC-3A13.13.1U.V TIMER + CONT.100 mA15B52042.5F.C.U-210.30.340 A16R620FAC-3B13.71.2U.V TIMER + CONT.4P17Y6AMP6.04.01.2100 mA18B6TP1.2Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC3.06.03.313.13.06.03.312.440APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-104SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T1FDB-204, 304 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGSPURCCUFCUS A/CUNITRYBAmmmmFANS/OS/OO/L40 A TP ISOLATOR1R1102.52.5L.P.G10.10.140A2Y1102.52.5LIVING RM / DINING30.10.34P3B1102.52.5KITCHEN20.10.2100 mA4R2102.52.5BED ROOM-2 / BATH40.10.45Y210SPARE0.2FUTURE LOAD6B2102.52.5BED ROOM-1 / BATH30.10.37R32042.5BED ROOM-130.20.640A8Y32042.5LIVING RM / DINING40.20.84P9B32042.5KITCHEN40.20.830 mA10R42042.5BED ROOM-230.20.611Y42042.5LIVING RM / DINING20.20.412B42042.5KITCHEN10.50.540 A13R53064.0FAC-4A13.33.3U.V TIMER + CONT.4P14Y52042.5F.C.U-110.30.3100 mA15B52042.5F.C.U-210.30.340 A16R620FAC-4B13.71.2U.V TIMER + CONT.4P17Y6AMP6.04.01.2100 mA18B6TP1.2Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC6.23.23.312.86.23.23.312.840APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-105SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T1FDB-205, 305 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGSPURCCUFCUS A/CUNITRYBAmmmmFANS/OS/OO/L40 A TP ISOLATOR1R1102.52.5LIVING RM / DINING30.10.340A2Y1102.52.5KITCHEN20.10.24P3B1102.52.5BED RM-1 / BATH40.10.4100 mA4R2SPACE5Y2102.52.5L.P.G10.10.16B2102.52.5BED RM-2 / BATH30.10.340A7R3SPACE4P8Y32042.5F.CU-210.30.3100 mA9B3SPACE10R42042.5LIVING RM / DINING40.20.840A11Y42042.5KITCHEN40.20.84P12B42042.5BED RM-140.20.830 mA13R52044LIVING RM / DINING20.20.414Y52044KITCHEN10.50.515B52042.5BED RM-230.20.640 A16R63064FAC-5A13.13.1U.V TIMER + CONT.4P17Y62042.5F.C.U-110.30.3100 mA18B63064FAC-5B13.13.1U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC4.62.25.212.04.62.25.212.040APROPOSED: B+ G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLOT NO: 241 - 587PANEL REF:FDB-106SHEET :1 / 1LOCATION:FLAT ENTRANCEFED FROM :SMDB - T1FDB-206, 306 TYPRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HW/MLPGISOCCUFCUS A/CUNITRYBAmmmmFANS/OS/O40A TP ISOLATOR1R1102.52.5KITCHEN20.10.240A2Y1102.52.5BED RM-1 / BATH40.10.44P3B1102.52.5LIVING RM / DINING50.10.5100 mA4R22042.5F.C.U-110.30.35Y2SPACE6B2102.52.5L.P.G10.10.17R32042.5KITCHEN40.20.840A8Y32042.5BED RM-130.20.64P9B32042.5LIVING RM / DINING40.20.830 mA10R42044KITCHEN10.50.511Y4SPACE0.012B42042.5LIVING RM / DINING20.20.440 A13R52042.5F.CU-210.20.24P14Y53064FAC-6A13.33.3U.V TIMER + CONT.100 mA15B53064FAC-6B12.32.3U.V TIMER + CONT.Cable Size:1X 4C 10 mm2 XLPE+/SWA/PVC+1C 10 mm PVC AS E+CC2.04.34.110.42.04.34.110.440A

&CPage &P of 178&R&D

DB-SS (2)PROJECT : B+G+6 FLOORS DIP HEADQUARTERSAREA: DUBAI INVESTMENT PARKPLANNED COMPLETION DATE : DECEMBER - 2009PLOT: 598 - 1205PANEL REF:DB - SSSHEET :1 / 1LOCATION:TRANSFORMER ROOMFED FROM :LV MDB - 3GROUND FLOORRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HH/DSPURCCUFCUS A/CUNITCAmmmmFANS/OS/OO/L40 A TP ISOLATOR1C1102.52.5TRANSFORMER ROOM80.10.8F12C216--SPARE0.63C3202.52.5TRANSFORMER ROOM60.21.24C420--SPARE0.656789101112131415161718192021222324Cable Size:2X1C 6mm2 XLPE/SWA/PVC+1C 6 mm PVC AS E+CCSINGLE PHASE

&CPage &P of 178&R&D

DB-SSPROJECT : B+G+12+R RES. BUILDINGAREA: AL NAHDA SECONDPLANNED COMPLETION DATE :PLOT: 241-587PANEL REF:DB - SSSHEET :1 / 1LOCATION:TRANSFORMER ROOMFED FROM :LV MDB - 1GROUND FLOORRATINGRATG.SL.CIRMCBCCTECCCONNECTED LOADLOAD PER CIR.OFOFNo.No.RTG.WIREWIREROOM /KWKWREMARKSINCOMERELCBINSIZESIZEAREALTGC.FANEX.15A13AW/HH/DSPURCCUFCUS A/CUNITBAmmmmFANS/OS/OO/L40A SP ISOLATOR40A 2P1B1102.52.5TRANSFORMER ROOM40.10.4100mA2B2---SPACE40A 2P3B32044TRANSFORMER ROOM30.20.630mA4B4---SPACE56789101112131415161718192021222324Cable Size:1X3C 10mm2 XLPE/SWA/PVCSINGLE PHASE1.0