5900 Sea Lion Place Suite 150 Carlsbad, CA 92010 760.476.3419 [email protected] www.chilldyne.com The Chilldyne Cool-Flo® System is a direct-to-chip liquid cooling system that delivers coolant under negative pressure. Chilldyne’s technologies were designed specifically to eliminate the risks associ- ated with liquid cooling while keeping deployment and operating costs low. The Chilldyne system mitigates risk with its patented leak-proof design. Liquid Cooling for Data Centers CF-CDU15 Rack-Scale Overview Chilldyne’s Rack-Scale liquid cooling system offers all the well-known benefits of liquid cooling without the cost, complexity and risk. Coolant delivered to the servers and manifolds is under negative pressure on both the supply and return so coolant cannot leak out; only air can leak into the system. The Chilldyne Cooling Distribution Unit (CDU) can use cooling tower water at 15-30 o C (59-86 o F) to remove up to 15 kW of server heat. The CF-CDU15 is a packaged system with pre-installed software and web page based moni- toring and controls . This provides flexibility in integration with your data center for a trial or a user laptop for demo. The software and user interface for the RSS is harmonized with Chilldyne’s Full-Scale System (FSS) for production data-center use. This allows users to familiarize themselves with the operation and control of the Full-Scale System before deploying it in a production environment. 8 lpm cooling flow at 5-40 o C (41-104 o F) Monitors water temperature flow rate and heat transfer, fills, drains and test for leaks Failure tolerant, negative pressure system Data logging of key performance parameters Web based software: control and monitor from anywhere. Automatic drain and fill under remote control. Enables liquid cooled product development. ABOUT THE RACK-SCALE SYSTEM KEY FEATURES Vacuum Pump CDU

Transcript of Liquid Cooling for Data Centers CF CDU15 Rack Scale Overvie · 2017-09-01 · for demo. The...

5900 Sea Lion Place

Suite 150

Carlsbad, CA 92010

760.476.3419

[email protected]

www.chilldyne.com

The Chilldyne Cool-Flo® System is a direct-to-chip liquid cooling system that delivers coolant under

negative pressure. Chilldyne’s technologies were designed specifically to eliminate the risks associ-

ated with liquid cooling while keeping deployment and operating costs low. The Chilldyne system

mitigates risk with its patented leak-proof design.

Liquid Cooling for Data Centers

CF-CDU15 Rack-Scale Overview

Chilldyne’s Rack-Scale liquid cooling system offers all the well-known benefits of liquid cooling without the

cost, complexity and risk. Coolant delivered to the servers and manifolds is under negative pressure on

both the supply and return so coolant cannot leak out; only air can leak into the system. The Chilldyne

Cooling Distribution Unit (CDU) can use cooling tower water at 15-30oC (59-86oF) to remove up to 15 kW of

server heat. The CF-CDU15 is a packaged system with pre-installed software and web page based moni-

toring and controls . This provides flexibility in integration with your data center for a trial or a user laptop

for demo. The software and user interface for the RSS is harmonized with Chilldyne’s Full-Scale System

(FSS) for production data-center use. This allows users to familiarize themselves with the operation and

control of the Full-Scale System before deploying it in a production environment.

• 8 lpm cooling flow at 5-40oC (41-104oF)

• Monitors water temperature flow rate and heat transfer, fills, drains and test for leaks

• Failure tolerant, negative pressure system

• Data logging of key performance parameters

• Web based software: control and monitor from anywhere.

• Automatic drain and fill under remote control.

• Enables liquid cooled product development.

ABOUT THE RACK-SCALE SYSTEM

KEY FEATURES

Vacuum Pump CDU

5900 Sea Lion Place

Suite 150

Carlsbad, CA 92010

760.476.3419

[email protected]

www.chilldyne.com

Allows for remote operation (fill, run, drain, purge, test…) via web page. Displays system state and error

messages, such as loss of facility cooling. Calculates heat removed, dew point, facility water flow rate.

Run Mode

Reports data on flow rate, pressure temperature,

heat pumped, water quality etc.

Service Mode

Allows user to evacuate coolant from all the

servers, Fill, Drain and conduct a vacuum

test to test for any leaks in the system.

Dual Xeon Kit

Liquid and air cold plate/

heat sink and no drip hot

swap connector. Standard

90mm heat sink design

GPU Cold Plate

Custom Cold plate for 300 watt Fury X

GPU, uses OEM VRM cooler

No Drip Hot Swap Connector

Patented technology for automatic

draining of server

SOFTWARE AND ACCESSORIES

5900 Sea Lion Place

Suite 150

Carlsbad, CA 92010

760.476.3419

[email protected]

www.chilldyne.com

Chilldyne’s Cool-Flo System is an efficient and

low cost liquid cooling system that reduces

data center power consumption 3 ways:

• 75-100% reduction in HVAC power

• 75% reduction in server fan power

• 5- 10% reduction in CPU power

This example shows a legacy data center

power reduction of 45% with the Cool-Flo

System. Any data center can bring their

Power Usage Efficiency (PUE) down to 1.2 or

less regardless of the climate.

Liquid Cooling Power Savings

Retains Air Cooling

Utilizing standard finned heat sinks

modified for liquid cooling, the Chilldyne

system can retain the ability to air cool

servers and can operate as a standard air-

cooled system to minimize down-time

Leak-Proof System

Cool-Flo® uses negative pressure on both

supply and return so if a leak occurs

anywhere air will flow into the system

instead of coolant leaking out

Failure Tolerant

The system will maintain cooling even with

one server open to air. Leaks are a mainte-

nance issue, they do not reduce uptime.

Increased Density With liquid cooling, the power density is

only limited by the electricity that can be

delivered to the chip. This means shorter

connections between servers and higher speed

data transfer.

Low Cost and Easy Installation

The Chilldyne system has no hidden installation

costs or delays. Plumbing is only required for the

CDU while the racks and servers can be installed by

data center technicians.

Reduced Setup Time

The CDU automatically fills and drains the system,

monitors the coolant and adds or drains coolant as

needed. Air purging is automatic to reduce setup

time and maintenance effort.

Automatic Coolant Evacuation

The Cool-Flo No-Drip/Hot Swap Connector

automatically evacuates coolant from a server when it

is disconnected from a system The racks can also be

drained automatically

Low Cost, High Volume

The system utilizes low cost plastic tubing and simple

connections, minimizing cost and allowing data center

technicians, not plumbers, to reconfigure racks.

INNOVATIVE TECHNOLOGIES

5900 Sea Lion Place

Suite 150

Carlsbad, CA 92010

760.476.3419

[email protected]

www.chilldyne.com

Chilldyne CDU Specifications CF-CDU15

Dimensions: 8.75x21x32in (CDU) mounted near servers. 8.75x21x26in (Vacuum Pump) in rack or under

floor.

Weight: 52 lbs (CDU) 45 lbs (Vacuum Pump)

Frame Details: Constructed out of PVC for maximum corrosion resistance. These units fit into a standard

computer rack.

Panel Details: Removable top for full service access.

Power : 120-240 V 50/60 Hz

Cooling water: 3 gpm (12 lpm) for full power, 5 psi (35 KPa) DeltaP

Vacuum: 2 CFM @ 20 in Hg ( 30 lpm @ -70 KPA) can be provided by Chilldyne vacuum pump unit.

CDU Cooling Control

• The water temperature to the servers is maintained at a temperature above the dew point in the data

center based on a temperature and humidity sensor included in the CDU

• Tap water once through the CDU can be used for temporary testing in most locations, depending on

local regulations. Facility Chilled water, standalone chillers , radiators can also be used.

Heat Exchanger:

• The unit is equipped with a single, stainless steel brazed plate liquid/liquid heat exchanger. Facility

cooling water flows in a second loop within the CDU through these heat exchangers.

• The facility side of the HXs are connected using 3/4” diameter garden hose fittings.

Controller:

• The unit includes a microprocessor controller which provides a web page interface which can be

operated with any computer equipped with an Ethernet connection.

• The unit automatically controls the flow through the servers, tests the system for leaks, fills, drains

and maintains coolant levels

• The unit monitors and records the vacuum, pressure, temperature (pump and facility side), dew

point, water levels, and coolant levels

Environmental:

• Ambient conditions 41-104oF (5-40oC), 0-95%RH (non-condensing), 0-6000ft (0-2000m) elevation.

Higher and lower temperature ranges are available via special order.

Service

• The CDU can be connected to a coolant reservoir, which contains coolant with anti corrosion and anti

bacterial additives. The coolant reservoir level should be checked every 3 months.

• The coolant should be drained and replaced annually.